Noise Feasibility Study

Proposed Redevelopment of

Glen Abbey Golf Club

Oakville, Ontario

Prepared for:

ClubLink Corporation ULC and ClubLink Holdings Ltd.

15675 Dufferin Street

King City, ON

L7B 1K5

Prepared by

Rajjot Arora, BASc EIT

and

Sheeba Paul, MEng, PEng

October 13, 2016

Page 2: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Table of Contents

1 Introduction and Summary ............................................................................................................. 1

2 Site Description and Noise Sources ................................................................................................ 2

3 Sound Level Criteria ....................................................................................................................... 2

3.1 Traffic Noise ............................................................................................................................ 2

4 Traffic Noise Assessment ............................................................................................................... 4

4.1 Road Traffic Data .................................................................................................................... 4

4.2 Road Traffic Noise Predictions ............................................................................................... 5

5 Discussion and Recommendations ................................................................................................. 7

5.1 Outdoor Living Areas .............................................................................................................. 7

5.2 Indoor Living Areas ................................................................................................................ 8

5.3 Building Façade Constructions ................................................................................................ 9

5.4 Warning Clauses .................................................................................................................... 11

6 Summary of Recommendations .................................................................................................... 12

6.1 Implementation ...................................................................................................................... 16

Figure 1 – Key Plan

Figure 2 – Draft Plan of Subdivision Showing Block Numbers

Figure 3 – Site Plan Showing Prediction Locations

Figure 4 – Site Plan Showing Ventilation Requirements

Appendix A – Road Traffic Data

Appendix B – Sample Stamson Calculations

Page 3: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 1

Proposed Redevelopment of Glen Abbey Golf Club, Oakville, ON October 13, 2016

1 Introduction and Summary

HGC Engineering was retained by Clublink Corporation ULC and ClubLink Holdings Ld. to

conduct a Noise Feasibility Study of the proposed redevelopment of Glen Abbey Golf Club, south of

Upper Middle Road West and north and east of Dorval Drive in the Town of Oakville, Ontario. The

proposed redevelopment is to include a mix of residential, commercial and open space uses on

approximately 230 acres of land. The study is required by the municipality as part of the planning

applications process.

The primary sources of noise are road traffic on Upper Middle Road West, Dorval Drive and Street

A (connecting Dorval Drive and Upper Middle Road West, part of the redevelopment). Ultimate

annual average daily traffic data (AADT) was obtained from the Region of Halton for Dorval Drive

and Upper Middle Road West. Road traffic data for Street A was provided by BA Group. This data

was used to predict future traffic sound levels at the locations of the proposed dwelling facades and

in rear yard outdoor living areas. The predicted sound levels were compared to the guidelines of the

Ministry of Environment and Climate Change (MOECC).

The sound level predictions indicate that noise control measures should be incorporated into the

design of the buildings such that indoor sound levels comply with the MOECC noise criteria.

Acoustic barriers are required for the rear yards of dwelling units with exposure to Upper Middle

Road West. Central air conditioning systems are required for the apartments with exposure to Upper

Middle Road West, Dorval Drive and Street A. Forced air ventilation systems with ductwork sized

for the future installation of central air conditioning by the occupant is recommended for the

townhouse units with exposure to Dorval Drive, Upper Middle Road West and Street A. Upgraded

glazing constructions are required for all building façades directly adjacent to and with exposure to

Upper Middle Road West. All remaining units may be constructed with any building construction

meeting the minimum requirements of the Ontario Building Code (OBC). Warning clauses are also

recommended to inform future owners and tenants of the road traffic noise impacts. A detailed noise

study should be required when more detailed lotting or phasing information is available.

Page 4: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 2

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

2 Site Description and Noise Sources

Figure 1 is a key plan indicating the location of the subject site. The proposed redevelopment is

located south of Upper Middle Road West and north and east of Dorval Drive, in Oakville, Ontario.

Figure 2 shows the draft plan of the subdivision with block numbers prepared by Glen Schnarr &

Associates Inc dated October 4, 2016. Figure 3 is the proposed concept plan dated August 17, 2016.

The sound level prediction locations [A] to [W] for the proposed redevelopment are shown in

Figure 3. The proposed residential development will consist of detached units, townhouse units,

apartments, retail uses, commercial uses, open space, parks, buffer bocks, natural heritage system

block and roadways.

HGC Engineering personnel visited the site on January 12, 2016 in order to investigate the acoustic

and topographic environment of the site. The site is currently a golf course. The acoustical

environment surrounding the site is urban in nature. Surrounding the site are existing residential uses.

Upper Middle Road West and Dorval Drive consist of 2 lanes in each direction. Background sound

levels from road traffic on Upper Middle Road West and Dorval Drive dominate the site. There are

no other significant sources of sound within 500 m of the site.

3 Sound Level Criteria

3.1 Traffic Noise

Guidelines for acceptable levels of road traffic noise impacting residential developments are given in

the MOECC publication NPC-300, “Environmental Noise Guideline Stationary and Transportation

Sources – Approval and Planning”, release date October 21, 2013 and are listed in Table I below.

The values in Table I are energy equivalent (average) sound levels [LEQ] in units of A-weighted

decibels [dBA].

Page 5: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 3

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Table I: Road Traffic Noise Criteria

Space Daytime LEQ(16 hour)

Road

Nighttime LEQ(8 hour)

Road

Outside Bedroom Windows 55 dBA 50 dBA

Outdoor Living Areas 55 dBA --

Inside Living/Dining Rooms 45 dBA 45 dBA

Inside Bedrooms 45 dBA 40 dBA

Daytime refers to the period between 07:00 and 23:00, while nighttime refers to the period between

23:00 and 07:00. The term "Outdoor Living Area" (OLA) is used in reference to an outdoor patio, a

backyard, a terrace or other area where passive recreation is expected to occur. Balconies that are

less than 4 m in depth are not considered to be outdoor living areas under MOECC guidelines.

The guidelines in the MOECC publication allow the daytime sound levels in an Outdoor Living Area

to be exceeded by up to 5 dBA, without mitigation, if warning clauses are placed in the purchase and

rental agreements to the property. Where OLA sound levels exceed 60 dBA, physical mitigation is

required to reduce the OLA sound level to below 60 dBA and as close to 55 dBA as technically,

economically and administratively feasible. The Region of Halton’s minimum noise barrier height is

2.4 m and the maximum height is 3.5 m, based on the Draft Noise Abatement Guidelines dated April

2013. The Town of Oakville maximum acoustic fence height is 2.4 m based on the Development

Engineering Procedures and Guidelines Manual dated October 2009.

A central air conditioning system as an alternative means of ventilation to open windows is required

for dwellings where nighttime sound levels outside bedroom or living/dining room windows exceed

60 dBA or daytime sound levels outside bedroom or living/dining room windows exceed 65 dBA.

Forced-air ventilation with ducts sized to accommodate the future installation of air conditioning by

the occupant is required when nighttime sound levels at bedroom or living/dining room windows are

in the range of 51 to 60 dBA or when daytime sound levels at bedroom or living/dining room

windows are in the range of 56 to 65 dBA.

Building components such as walls, windows and doors must be designed to achieve indoor sound

level criteria when the plane of bedroom window sound level is greater than 60 dBA or the daytime

sound level is greater than 65 dBA due to road traffic noise.

Page 6: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 4

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Warning clauses to notify future residents of possible noise excesses are also required when

nighttime sound levels exceed 50 dBA at the plane of the bedroom or living/dining room window

and daytime sound levels exceed 55 dBA in the outdoor living area and at the plane of the bedroom

or living/dining room window due to road traffic.

4 Traffic Noise Assessment

4.1 Road Traffic Data

Traffic data for Dorval Drive and Upper Middle Road West was obtained from the Region of Halton

in the form of Ultimate Average Annual Daily Traffic (AADT) and is provided in Appendix A. A

commercial vehicle percentage of 5% for medium trucks and 3% for heavy trucks was used for both

roadways. A day/night split of 90/10% was used along with posted speed limit of 60 km/h for both

roadways.

Traffic data for “Street A” connecting Dorval Drive and Upper Middle Road West was provided by

BA Group in the form of future AM and PM peak hour volumes. An AADT of 10 950 vehicles per

day for the year 2031 was applied. A commercial vehicle percentage of 1.5% for medium trucks and

1.5% for heavy trucks was assumed in the analysis. A day/night split of 90/10% was used along with

assumed speed limit of 50 km/h. Table II summarizes the traffic volume data used in this study.

Page 7: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 5

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Table II: Ultimate Road Traffic Data (2031)

Road Name Cars Medium

Trucks

Heavy

Trucks Total

Dorval Drive

Daytime 25 337 1 377 826 27 540

Nighttime 2 815 153 92 3 060

Total 28 152 1 530 918 30 600

Upper

Middle Road

West

Daytime 38 005 2 066 1 239 41 310

Nighttime 4 223 230 138 4 590

Total 42 228 2 295 1 377 45 900

Street A

Daytime 9 559 148 148 9 855

Nighttime 1 062 16 16 1 095

Total 10 622 164 164 10 950

4.2 Road Traffic Noise Predictions

To assess the levels of road traffic noise which are predicted to impact the property in the future,

sound level predictions were made using STAMSON version 5.04, a computer algorithm developed

by the MOECC. This modelling software was used to predict the future road traffic sound levels

(LEQ) at the building facades. Sample STAMSON output is included in Appendix B.

Predictions of the traffic sound levels were made at various locations around the proposed

redevelopment. Sound levels were predicted in the plane of the living/dining room and bedroom

windows during daytime and nighttime hours to investigate ventilation requirements or at the top

storey of the apartment buildings. The results of these predictions are summarized in Table III and

Table IV. The acoustic requirements may be subject to modifications if the site plan is changed

significantly.

Page 8: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 6

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Table III: Predicted Future Sound Levels, LEQ [dBA], Without Mitigation

Prediction

Location Description

Outdoor Living

Area LEQ(16)

Daytime

LEQ(16)

Nighttime

LEQ(8)

[A] Block 155: Townhouse units with

exposure to Dorval Drive -- 61 54

[B] Block 155: Townhouse unit with some

exposure to Dorval Drive -- 56 49

[C] Block 155: Townhouse units with some

exposure to Dorval Drive -- <55 <50

[D] Block 155: Apartment units with

exposure to Dorval Drive -- 60 53

[E] Block 156: Townhouse unit with some

exposure to Dorval Drive -- 57 51

[F] Block 156: Townhouse units with some

exposure to Dorval Drive -- <55 <50

[G] Block 156: Townhouse units with

exposure to Dorval Drive and Street A -- 61 55

[H] Block 156: Townhouse units with

exposure to Street A -- 60 54

[I] Block 156: Apartment units with

exposure to Street A and Dorval Drive -- 60 53

[J] Block 159: Townhouse units with

exposure to Street A -- 58 52

[K] Block 158: Townhouse unit with

exposure to Street A -- 59 53

[L] Block 158: Townhouse unit with some

exposure to Street A -- 55 <50

Page 9: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 7

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Table IV: Predicted Future Sound Levels, LEQ [dBA], Without Mitigation

Prediction

Location Description

Outdoor Living

Area LEQ(16)

Daytime

LEQ(16)

Nighttime

LEQ(8)

[M] Multiple Blocks: Apartment units with

exposure to Street A -- 60 53

[N] Block 142: Townhouse units with

exposure to Upper Middle Road West 63 65 59

[O] Block 142: Townhouse units with some

exposure to Upper Middle Road West 58 58 52

[P] Block 142: Townhouse units with some

exposure to Upper Middle Road West 55 55 50

[Q] Block 142: Apartment units with

exposure to Upper Middle Road West -- 62 56

[R]

Block 142: Apartment units with

exposure to Street A and Upper Middle

Road West

-- 65 59

[S] Block 143: Apartment units with

exposure to Upper Middle Road West -- 67 60

[T]

Block 143: Apartment units with

exposure to Street A and Upper Middle

Road West

-- 64 58

[U] Block 143: Apartment units with

exposure to Upper Middle Road West -- 67 60

[V] Block 145: Apartment units with

exposure to Upper Middle Road West -- 56 50

[W] Block 144: Apartment units with some

exposure to Upper Middle Road West -- 56 50

5 Discussion and Recommendations

The predictions indicate that the traffic sound levels will exceed the outdoor MOECC guidelines

listed in Table I at the facades of the proposed buildings. Recommendations to meet the indoor

MOECC guidelines are discussed below.

5.1 Outdoor Living Areas

The dwelling units in the apartments may include balconies or terraces which are less than 4 metres

in depth. These are exempt from the definition of OLA under MOECC guidelines. Physical

mitigation is not required.

Page 10: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 8

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

The majority of townhouse units may include decks and patios which are less than 4 metres in depth.

These are exempt from the definition of OLA under MOECC guidelines. Physical mitigation is not

required.

The predicted sound levels in the rear yards of townhouse units with exposure to Upper Middle Road

West (prediction location [N]) will be 64 dBA. This is 9 dBA in excess of the MOECC guideline

limit. Physical mitigation is required. A 2.4 m high acoustic fence will reduce the overall sound level

in the rear yards to 56 dBA. The 1 dBA in excess is acceptable to the MOECC, with the use of a

noise warning clause. The location of the acoustic barriers is shown in Figure 4.

The predicted sound levels in the rear yards of the townhouse units with some exposure to Upper

Middle Road West (prediction location [O]) will be 57 dBA. A 2.4 m high acoustic fence at the

townhouse units with exposure to Upper Middle Road West (prediction location [N]) will reduce the

sound levels in the rear yards of units at prediction location [O] to 55 dBA. This is acceptable to the

MOECC, with the use of a noise warning clause. Physical mitigation is not required.

The remaining units away from the major roadways will have rear yards with sound levels less than

55 dBA. Physical mitigation is not required.

As a general note, acoustic barriers may be a combination of an acoustic wall and an earth berm. The

wall component of the barrier should be of a solid construction with a surface density of no less than

20 kg/m2. The walls may be constructed from a variety of materials such as wood, brick, pre-cast

concrete or other concrete/wood composite systems provided that it is free of gaps or cracks. The

heights and extents of the barriers should be chosen to reduce the sound levels in the OLA’s to below

60 dBA and as close to 55 dBA as is technically, administratively and economically feasible, subject

to the approval of the municipality respecting any applicable fence height by-laws.

5.2 Indoor Living Areas

The predicted daytime sound levels at apartment buildings with exposure to Dorval Drive (prediction

location [D] and [I]), Street A (prediction location [M]) and Upper Middle Road West (prediction

location [Q], [R], [S], [T], [U], [V], [W]) will be greater than 56 dBA and greater than 60 dBA

during nighttime. To address these excesses, MOECC guidelines recommend that all apartment

Page 11: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 9

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

buildings with exposure to Dorval Drive, Street A and Upper Middle Road West be equipped with

central air conditioning systems or an alternative means of ventilation to open windows, so that the

windows can be kept closed. Window or through-the-wall air conditioning units similar to motel-

style are not recommended because of the noise they produce and because the units penetrate

through the exterior wall which degrades the overall sound insulating properties of the envelope

unless they are in their own closet with an access door for maintenance. The location, installation and

sound ratings of the outdoor air conditioning devices should minimize noise impacts and comply

with criteria of MOECC publication NPC-300. Figure 4 indicates the units with central air

conditioning.

The predicted daytime sound levels at the townhouse dwelling units with exposure to Dorval Drive

(prediction location [A], [B], [E], [G]), Street A (prediction location [H], [J] and [K]) and Upper

Middle Road West (prediction location [N] and [O]) will be between 55 dBA and 65 dBA and

between 51 and 60 dBA during nighttime. These units will require forced air ventilation systems

with ductwork sized for the provision for the future installation of central air conditioning systems by

the occupant or an alternative means of ventilation to open windows. These units are indicated in

Figure 4. The location, installation and sound ratings of the outdoor air conditioning devices should

minimize noise impacts and comply with criteria of MOECC publication NPC-300.

All remaining units within the redevelopment do not require any specific ventilation requirements.

5.3 Building Façade Constructions

The predicted sound levels at apartment building facade with exposure to Upper Middle Road West

(prediction locations [S] and [U]) are greater than 65 dBA during the daytime due to road traffic.

MOECC guidelines recommend that the windows, walls and doors be designed so that the indoor

sound levels comply with MOECC noise criteria.

The detailed building plans were not yet available for review by HGC Engineering at the time of this

study. Preliminary calculations have been performed to determine the building envelope

constructions likely to be required to maintain indoor sound levels within MOECC guidelines. The

calculation methods were developed by National Research Council (NRC). They are based on the

Page 12: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 10

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

predicted future sound levels at the building facades and the anticipated area of the façade

components (walls, windows and doors) relative to the floor area of the adjacent room.

In this analysis, it has been assumed that sound transmitted through elements other than the glazing

elements is negligible in comparison. Thus, the exterior walls should have sufficient acoustical

insulation value such that the noise transmitted through the walls is negligible in comparison with the

windows. Exterior walls that include spandrel glass or metal panels within an aluminum window

system can have sufficient sound insulation if a drywall assembly on separate framing behind the

spandrel panels is used.

There may be glazed exterior doors (sliding or swing) for entry onto the balconies from living/dining

rooms and some bedrooms. The glazing areas on the doors are to be counted as part of the total

window glazing area. All exterior doors should include good weather seals to reduce air (and noise)

infiltration to the minimum achievable levels.

Units Closest to Upper Middle Road West

For the purpose of this preliminary analysis, typical window-to-floor areas were assumed to be 70%

(i.e. 50% fixed, 20% operable including glazed sliding patio doors). Based upon these assumptions,

it was determined that the glazing along the north façade facing Upper Middle Road must achieve a

sound transmission class (STC) rating of at least 30 in order to achieve the target indoor sound level

criteria. Awning windows, and swing or sliding doors to balconies should have tight seals sufficient

to achieve similar acoustical performance ratings.

When detailed floor plans and building elevations for the buildings closest to Upper Middle Road

West are available, an acoustical consultant should provide revised recommendations based on actual

window to floor area ratios.

The remaining facades will have daytime sound levels that are less than 65 dBA and less than 60

dBA during nighttime. Thus, any exterior wall and double glazed window construction meeting the

minimum requirements of the Ontario Building Code (OBC) will provide adequate sound insulation.

Page 13: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 11

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Remaining Dwelling Units

All other remaining townhouse and apartment units will have daytime sound levels that are less than

65 dBA and 60 dBA during nighttime. For these units, any exterior wall and doubled glazed window

construction meeting the minimum requirements of the Ontario Building Code (OBC) will provide

adequate sound insulation for the dwelling units.

5.4 Warning Clauses

The MOECC guidelines recommend that warning clauses be included in the property and tenancy

agreements for all units with anticipated road traffic sound levels. Examples are provided below.

Suggested wording for future dwellings with sound levels exceeding the MOECC criteria is given

below.

Type A:

Purchasers/tenants are advised that despite the inclusion of noise control features in the

development and within the building units, sound levels due to increasing road traffic may on

occasion interfere with some activities of the dwelling occupants, including any raised patio

and/or balcony, as sound levels exceed the sound level limits of the Municipality and the

Ministry of the Environment and Climate Change.

Suggested wording for future dwellings for which physical mitigation has been provided is given

below.

Type B:

Purchasers/tenants are advised that despite the inclusion of noise control features in the

development and within the building units, sound levels due to increasing road traffic may

occasionally interfere with some activities of the dwelling occupants as the sound levels

exceed the noise criteria of the Municipality and the Ministry of the Environment and

Climate Change.

Page 14: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 12

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Suggested wording for future dwellings requiring forced air ventilation systems is given below.

Type C:

This dwelling unit has been fitted with a forced air heating system and the ducting etc., was

sized to accommodate central air conditioning. Installation of central air conditioning will

allow windows and exterior doors to remain closed, thereby ensuring that the indoor sound

levels are within the Municipality’s and the Ministry of the Environment and Climate Change

noise criteria. (Note: The location and installation of the outdoor air conditioning device

should be done so as to minimize the noise impacts and comply with criteria of MOECC

publication NPC-300.)

Suggested wording for future dwellings requiring central air conditioning systems is given below.

Type D:

This dwelling unit has been supplied with a central air conditioning system which allows

windows and exterior doors to remain closed, thereby ensuring that the indoor sound levels

are within the noise criteria of the Municipality and the Ministry of the Environment and

Climate Change.

The sample clauses are provided by the MOECC as an example and can be modified by the

Municipality as required.

6 Summary of Recommendations

The following list and Table V and Table VI summarizes the recommendations made in this report.

1. A 2.4 m high acoustic barrier is required for the rear yards of townhouse units with exposure

to Upper Middle Road West.

2. Central air conditioning systems will be required for the apartment buildings with exposure to

Dorval Drive, Street A and Upper Middle Road West. Forced air ventilation systems with

ductwork sized for future installation of central air conditioning systems by the occupant will

be required for the townhouse units with exposure to Dorval Drive, Street A and Upper

Middle Road West. The location, installation and sound ratings of the air conditioning

devices should comply with NPC-300.

Page 15: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 13

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

3. Upgraded glazing construction will be required for the apartment buildings with exposure to

Upper Middle Road West, as indicated in section 5.3. When detailed floor plans are available,

an acoustical consultant should provide revised recommendations based on actual window to

floor area ratios.

4. Warning clauses should be included in the property and tenancy agreements to inform future

owners and tenants of the property of the potential road traffic noise impacts.

5. A detailed noise study is required to revise the acoustic recommendations on a phase by

phase basis or when more detailed lotting information is available.

Page 16: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 14

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Table V: Summary of Noise Control Requirements and Noise Warning Clauses

Prediction

Location Description

Acoustic

Barrier Ventilation

Requirements

*

Warning

Clause

Building

Façade

Construction

[A] Block 155: Townhouse units

with exposure to Dorval Drive -- Forced Air A, C OBC

[B]

Block 155: Townhouse unit

with some exposure to Dorval

Drive

-- Forced Air A, C OBC

[C]

Block 155: Townhouse units

with some exposure to Dorval

Drive

-- -- -- OBC

[D] Block 155: Apartment units

with exposure to Dorval Drive -- Central A/C A, D OBC

[E]

Block 156: Townhouse unit

with some exposure to Dorval

Drive

-- Forced Air A, C OBC

[F]

Block 156: Townhouse units

with some exposure to Dorval

Drive

-- -- -- OBC

[G]

Block 156: Townhouse units

with exposure to Dorval Drive

and Street A

-- Forced Air A, C OBC

[H] Block 156: Townhouse units

with exposure to Street A -- Forced Air A, C OBC

[I]

Block 156: Apartment units

with exposure to Street A and

Dorval Drive

-- Central A/C A, D OBC

[J] Block 159: Townhouse units

with exposure to Street A -- Forced Air A, C OBC

[K] Block 158: Townhouse unit

with exposure to Street A -- Forced Air A, C OBC

[L] Block 158: Townhouse unit

with some exposure to Street A -- -- -- OBC

Note:

* The location, installation and sound rating of the air conditioning condensers must be compliant with MOECC

Guideline NPC-300.

OBC – meets the minimum requirements of the Ontario Building Code.

Page 17: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 15

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

Table VI: Summary of Noise Control Requirements and Noise Warning Clauses

Prediction

Location Description

Acoustic

Barrier

Ventilation

Requirements

*

Warning

Clause

Building

Façade

Construction

[M] Multiple Blocks: Apartment

units with exposure to Street A -- Central A/C A, D OBC

[N]

Block 142: Townhouse units

with exposure to Upper Middle

Road West

Forced Air B, C OBC

[O]

Block 142: Townhouse units

with some exposure to Upper

Middle Road West

-- Forced Air A, C OBC

[P]

Block 142: Townhouse units

with some exposure to Upper

Middle Road West

-- -- --

[Q]

Block 142: Apartment units

with exposure to Upper Middle

Road West

-- Central A/C A, D OBC

[R]

Block 142: Apartment units

with exposure to Street A and

Upper Middle Road West

-- Central A/C A, D OBC

[S]

Block 143: Apartment units

with exposure to Upper Middle

Road West

-- Central A/C A, D STC - 30

[T]

Block 143: Apartment units

with exposure to Street A and

Upper Middle Road West

-- Central A/C A, D OBC

[U]

Block 143: Apartment units

with exposure to Upper Middle

Road West

-- Central A/C A, D STC - 30

[V]

Block 145: Apartment units

with exposure to Upper Middle

Road West

-- Central A/C A, D OBC

[W]

Block 144: Apartment units

with some exposure to Upper

Middle Road West

-- Central A/C A, D OBC

Note:

* The location, installation and sound rating of the air conditioning condensers must be compliant with MOECC

Guideline NPC-300.

OBC – meets the minimum requirements of the Ontario Building Code.

Page 18: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Noise Feasibility Study Page 16

Proposed Redevelopment of Glen Abbey Golf Course, Oakville, ON October 13, 2016

6.1 Implementation

To ensure that the noise control recommendations outlined above are fully implemented, it is

recommended that:

1) When detailed floor plans are available, an acoustical consultant should provide revised

recommendations based on actual window to floor area ratios.

2) When more detailed lotting information is available, the study should be revised to reflect a

detailed draft plan.

3) Prior to the issuance of occupancy permits for this redevelopment, the Municipality’s

building inspector or a Professional Engineer qualified to provide acoustical engineering

services in the Province of Ontario should certify that the noise control measures for the

dwelling units have been properly incorporated, installed and constructed.

Page 19: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

Figure 1: Key Plan

rarora
Polygon
Page 20: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

�����������

�������������� ������� ������� ������� ������� ����� ������� ������ ������� ������� ������� ������� ������ ������ ������

������ ������

������� ������ ����� �

����� �

������� ������� ������ ������ ������� ���������������� ����������� !�"#��$!%&

��������' ���������(� !�"$�''!%&

��������������)����'��* !"'�$$!%&��������'�����)�����'��� !�"'�+$!%&

��������#�����)�����'�$( !�"���$!%&��������������)�����'�$$ !�"��'�!%&�������(������)�����'��' !�"����!%&

�������(*����������+��' !�"���('!%&

�������*��� " �����������������)&#��#� !�"���+�!%&

��������$�����)��������# !�"$���!%&�������*#�� "�������&'��( !�"��**!%&����������������������������������

��������������$������� �,�������� ��+���� ��## !�"#���!%&

�������$#�������� ��#���� '�+# !�"��#�!%& �������$(����� �������� �#����� '��' !�"���#!%&�������(��������)�����)'�+' !�"���$!%&�������$$����� �������� ������� '�(* !�"��(*!%&

��������*� ���������$# !�"#�+#!%&

�������*�������� ���'��� !�"'�$�!%&�������*'������� ���'�$' !�"'���!%&

�������$+����� �������� ������ '��# !�"'�+�!%&

�������$������ �������� ������� '��( !�"��#�!%&�������$*�������� ������� '�+# !�"��#�!%&�������$������� �,�������� ��+���� ���' !�"����!%& �������+'�������� �#����� '�*( !�"���#!%&�������+������� #(���� '�** !�"����!%& �������+������� ������ '�+� !"��$(!%&

�������+#�������� ��#���� '�*� !�"���'!%&�������+$�������� (*���� '�+� !�"���(!%& �������++������ �,��������� �'����� '�(� !�"��+�!%&�������+(������ �,�������� �$#���� '��* !�"���#!%&�������+��������� ��'���� '�*� !�"���'!%& �������+*������ $$���� '�(� !�"��+#!%&

�������+������� �,�������� ������� '�*( !�"���#!%&�������('����� ������ �,�������� ��'���� '�*� !�"��''!%&�������(������� �,�������� ��$���� '�*# !�"��'+!%&�������(��������� ������� '��� !�"���+!%& �������+� ��������* !"����!%&

�������*$�� �"�������&'�#� !�"'���!%&

�������(#������ �,�������� ������� '�** !�"����!%&

�������**�� �����'�(� !�"����!%&

�������*+�� �����'�$� !�"���(!%&

-./01/23�4566789�:;/<6/23=>-1-21/72�17�:-�6-1->?/2-6@��������������������������:50-6�72�3>-51->�7ABC�DEF�174�7A�:529�:;AA->C�DGF�015:<-�174�7A�0<74-�:;AA->C�DGF�6>/4�</2-�:;AA->

�� �����������:50-6�72�3>-51->�7ABC�174�7A�:529C�015:<-�174�7A�0<74-C�6>/4�</2-

>7;265:7;1

>7;265:7;1<5260854-6/0<526 <5260854-6/0<5260

-./01/23>5H67>�-0151-=17�:-�>-15/2-6@=271�5�45>1�7A�544</851/72@��������������)�������

�� �� ������ �� ���� ������� ����

������)����� ����� ���������� �����)����� ����������

�������)����

��)����������������������)������������ -./01/23>-0/6-21/5<

-./01/23>-0/6-21/5<-./01/23>-0/6-21/5<-./01/23>-0/6-21/5<

-./01/23>-0/6-21/5<-./01/23>-0/6-21/5<

-./01/23>-0/6-21/5< -./01/23I5<<-H

-./01/23I5<<-H�������*��� �����'�$� !�"����!%&

-./01/23>-0/6-21/5<����������

������� ��� ����� ���� ����%�����)� �����

:<789�DJK3>--2L5H45>9

�������($������ �,�������� �#����� '��� !�"���'!%&�������(+������ �,�������� ������ '��* !�"���#!%& �������(( �������� (+���� '��� !�"'�(�!%&

�������������

������������� ���"�������)&'�'$ !�"'��'!%&��������*���� ���"�������)&'��$ !�"'�#+!%&

������������� ���"�������)&'�'# !�"'�'�!%&

>7;265:7;1

��������������

���������������������������������:50-6�72�3>-51->�7ABC�DEF�174�7A�:529�:;AA->C�DGF�015:<-�174�7A�0<74-�:;AA->C�DGF�6>/4�</2-�:;AA->

����� �������������� ��" MN%OPO%�QR%!SORTSR�UN�VNSNWXOTNVOT�%RTYZQS!SORT�[OS WNQN\!TS�!ZS RWOSONY&

�������*(�� �����'��$ !�"'�#+!%&

�����������

�������������)�����������

����� �������� �� �)���������

��������

] _ �abc ]deb�f�g]dhib jcklmn jckmon a_peb�������q����'X�"#'�& $*q((r*#r*(q�'�r�#�r�#�r�#$q�$� ��'� $��� +��������q����+X�"#��& ���r��' '�'( '��+ ��������q�����'X�"$'�& $$q$�r(�r(*r��q�#r�+q��r*$r*+r�'*q��'r��(q��*r���r��#r��$r���r��� ���� ���$ ���������q��#��'X�"$#�& $'q$#r(�r*�r���q��+r��*r�#'r�## '�*$ ��'* �$�������q��+��'X�"+'�& �'r�$r���r��+r��( '�#� '��� +�������q��*��'X�"('�& �q#�r*'r*� #��$ ���$ $������� �,��������� �$�r�$#r�$*q�+�r�(�q�(( �+��� #��+� �$������� ������� �s��������� �$$q�$�r�(' #�#* *�#+ +*��������)������) �(� '�+' ���$���� �(*q��+ �'�$� �+������������������� ��( '�#$ '�*$���� ��� ���q��� '��� '�+��������� ��� �*'r�*� '�+� ��$��������������� ) ���"�� & �*�q�*$ #��$� *'��$�� ����� �*+q�** ���� $�$� ������� �*�q��� $�#� �'�(���+X���������"+*�X& '�$( ���$���+X�����"�*�X& '�#* '��$���'X�����"$r��'X& ��'' ��������'X�����"��#X& ��(+ $�'*�(�'X�����"$�'X& ���� �������+X�����"��X& '��� '�+$#$�'X�����"�'X& '�## '�*�#(�'X�����"�r'�+X& #��� ��*(btuvwxwywz{�ede ] |}| }~��~ ~~}�|~ �~~~�OYSOT���!�VRW�YS!SN�"TRS�!�M!WS�RP�!MMQO%!SORT& ���+ #�'�ede ] }��}� ~�~�~|������������������������������

bag�che] _ bic���] _j �e��] _�d��bag p�pbpd_h]ag]p_i�hdj�dj epd_�a]h��h]ag]p_i��d] p_�b�]p�pec����� �¡¢£¤¥¥¥¥¥¥����������� ���r�*r���,��'���� �����r� ��� �r���������������������������������)����������d¦_cjb�hcjep�ph ec�����)�������§����� �������,�� ����� ������������������� ������� ��������������� ����� ��������������������������������������� ���� ¨¨¨¨¨¨¨¨¨¨¨¨¨ ����������©�����r��'�(���� �������� ����r��� ��������������������������,���������������� �������baj�c�djb�hcjep�ph ec�����)������)���������������� ����������� ������ ��������� ����������� ���������������������� ������������������� ����������)������������)� ����� ���� ¨¨¨¨¨¨¨¨¨¨¨¨¨ ���������©�����r��'�(��§�����)����� r��� r��������� ����� ����������� ���������������,������ ��)����(����������������� ���r� ����'������������ ���r�����$������©��'+q*��q����^ pepd_ ]�p_�dj� epd_"���� ������+�"��&�������������������&��������������������)��� ��r�r�r�rr�r�r��,������ ����������������������)����� ��&�������������������������������������&� ���)�������������)������&� ������)����� ����� �� �������������] _ �abc�bh�c a]c

%!QN��©�+''"�$���#(&�%SRUNW�$r��'�(_decbq��!TN[!�q�R%!Qs�RQQN%SRW�V!�QO� S�SWO!T�QN�ª�#�+X���#�+Xq��R%!Qq�R%!Q�V!�QO� S�WRZTVOT��ª�#��+Xq��R%!Qs�RQQN%SRWq�RQQN%SRW�V!�QO� S�SWO!T�QN�ª���+X�����+Xq��R%!Qs�RQQN%SRWq�WSNWO!Q�V!�QO� S�SWO!T�QN�ª��+�'X����+�'X

rarora
Text Box
Figure 2: Draft Plan of Subdivision Showing Block Numbers
Page 21: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario
rarora
Text Box
Figure 3: Draft Site Plan Showing Prediction Locations
rarora
Text Box
[A]
rarora
Text Box
[C]
rarora
Text Box
[F]
rarora
Text Box
[E]
rarora
Text Box
[I]
rarora
Text Box
[H]
rarora
Text Box
[G]
rarora
Text Box
[K]
rarora
Text Box
[L]
rarora
Line
rarora
Text Box
[D]
rarora
Line
rarora
Text Box
[B]
rarora
Text Box
[J]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[W]
rarora
Text Box
[V]
rarora
Text Box
[U]
rarora
Text Box
[S]
rarora
Text Box
[T]
rarora
Text Box
[Q]
rarora
Text Box
[R]
rarora
Text Box
[N]
rarora
Text Box
[O]
rarora
Text Box
[P]
Page 22: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario
rarora
Text Box
Figure 4: Draft Site Plan Showing Barrier and Ventilation Requirements
rarora
Text Box
[A]
rarora
Text Box
[C]
rarora
Text Box
[F]
rarora
Text Box
[E]
rarora
Text Box
[I]
rarora
Text Box
[H]
rarora
Text Box
[G]
rarora
Text Box
[K]
rarora
Text Box
[L]
rarora
Line
rarora
Text Box
[D]
rarora
Line
rarora
Text Box
[B]
rarora
Text Box
[J]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[M]
rarora
Text Box
[W]
rarora
Text Box
[V]
rarora
Text Box
[U]
rarora
Text Box
[S]
rarora
Text Box
[T]
rarora
Text Box
[Q]
rarora
Text Box
[R]
rarora
Text Box
[N]
rarora
Text Box
[O]
rarora
Text Box
[P]
rarora
Text Box
Forced Air
rarora
Rectangle
rarora
Rectangle
rarora
Text Box
Central A/C
rarora
Text Box
2.4 m Acoustic Barrier
rarora
Line
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygon
rarora
Polygonal Line
Page 23: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

APPENDIX A

Road Traffic Data

Page 24: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

1

Raj Arora

From: Raj AroraSent: January-14-16 4:55 PMTo: 'Krusto, Matt'Subject: RE: Road Traffic Data Request

Perfect. Thank you, Raj  

From: Krusto, Matt [mailto:[email protected]]  Sent: January‐14‐16 4:22 PM To: Raj Arora Subject: RE: Road Traffic Data Request  Hi Raj,  Please assume 5% medium and 3% heavy for both roadways.  Matt  

From: Raj Arora [mailto:[email protected]] Sent: Thursday, January 14, 2016 4:01 PM To: Krusto, Matt Subject: RE: Road Traffic Data Request  Hi Matt,  Thank you for the data. Would you by any chance have commercial vehicles percentages for the two roadways?  Thanks,  Rajjot Arora, BASc

HGC Engineering NOISE | VIBRATION | ACOUSTICS Howe Gastmeier Chapnik Limited t: 905.826.4044   

From: Krusto, Matt [mailto:[email protected]]  Sent: January‐13‐16 3:11 PM To: Raj Arora Subject: RE: Road Traffic Data Request  Hi Raj,  Please use the following ultimate traffic data (2031) for the following roadways:  Dorval Drive (4 lanes in 2031) ‐ 30,600 AADT Upper Middle Road (6 lanes in 2031) – 45,900 AADT  

Page 25: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

2

Let me know if there are any questions.  Matt  Matt Krusto | Transportation Co-ordinator Transportation Planning Infrastructure Planning & Policy Public Works Department, Region of Halton E: [email protected] | T: 905-825-6000 x 7225  

From: Raj Arora [mailto:[email protected]] Sent: Tuesday, January 12, 2016 11:44 AM To: Krusto, Matt Subject: Road Traffic Data Request  Hello Matt,   HGC Engineering is performing a noise study for a proposed redevelopment of Glen Abbey Gold Course. The proposed development is to include a mixed use residential neighbourhood.     Please find attached a Google link for your reference.    https://www.google.ca/maps/place/glen+abbey+golf+course/@43.449111,‐79.7142073,15z/data=!4m2!3m1!1s0x0:0x1f4226f0bf87ba46?sa=X&ved=0ahUKEwitr4HW26TKAhUHKx4KHRzNCHcQ_BIIazAL   We need road traffic volumes for Upper Middle Road and Dorval Drive.   We typically use current AADT volumes, along with commercial vehicle percentages, day/night split and speed. If you have projected data, we can use that also.    Thank you,  Rajjot Arora, BASc Project Consultant CELEBRATING 20 YEARS | 1994-2014  HGC Engineering NOISE | VIBRATION | ACOUSTICS Howe Gastmeier Chapnik Limited 2000 Argentia Road, Plaza One, Suite 203, Mississauga, Ontario, Canada L5N 1P7 t: 905.826.4044 e: [email protected] Visit our website: www.hgcengineering.com Follow Us – LinkedIn | Twitter | YouTube This e-mail and any attachments may contain confidential and privileged information. If you are not the intended recipient, please notify the sender immediately by return e-mail, delete this e-mail and destroy any copies. Any dissemination or use of this information by a person other than the intended recipient is unauthorized and may be illegal.

  

Page 26: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

1425 Upper Middle/Street A320

530 1500

45 205 525 510

195 85 95 345 75 Dorval/Old Abbey/Street AStreet B / Dorval 75 60 35 155

1415 1330 95

### Upper Middle/Street A555

10 545 1865 10

100 435 ### 1475

150 115 10 85 285 185 Dorval/Old Abbey/Street AStreet B / Dorval 195 60 85 80

1065 920 65

2031 Future Total ‐ AM Peak Hour

2031 Future Total ‐ PM Peak Hour

Page 27: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

APPENDIX B

Sample STAMSON 5.04 Output

Page 28: Noise Feasibility Study Proposed Redevelopment of Glen ... planning/da-15190901-noisefeas.pdfNoise Feasibility Study Proposed Redevelopment of Glen Abbey Golf Club Oakville, Ontario

STAMSON 5.0 NORMAL REPORT Date: 16-09-2016 10:26:55

MINISTRY OF ENVIRONMENT AND ENERGY / NOISE ASSESSMENT

Filename: loca.te Time Period: Day/Night 16/8 hours

Description: Prediction Location [A] (Block 155: Townhouse units with exposure to Dorval Drive)

Road data, segment # 1: Dorval (day/night)

------------------------------------------

Car traffic volume : 25337/2815 veh/TimePeriod *

Medium truck volume : 1377/153 veh/TimePeriod *

Heavy truck volume : 826/92 veh/TimePeriod *

Posted speed limit : 60 km/h

Road gradient : 0 %

Road pavement : 1 (Typical asphalt or concrete)

* Refers to calculated road volumes based on the following input:

24 hr Traffic Volume (AADT or SADT): 30600

Percentage of Annual Growth : 0.00

Number of Years of Growth : 10.00

Medium Truck % of Total Volume : 5.00

Heavy Truck % of Total Volume : 3.00

Day (16 hrs) % of Total Volume : 90.00

Data for Segment # 1: Dorval (day/night)

----------------------------------------

Angle1 Angle2 : -90.00 deg 90.00 deg

Wood depth : 0 (No woods.)

No of house rows : 0 / 0

Surface : 1 (Absorptive ground surface)

Receiver source distance : 60.00 / 60.00 m

Receiver height : 4.50 / 4.50 m

Topography : 1 (Flat/gentle slope; no barrier)

Reference angle : 0.00

Results segment # 1: Dorval (day)

---------------------------------

Source height = 1.32 m

ROAD (0.00 + 60.75 + 0.00) = 60.75 dBA

Angle1 Angle2 Alpha RefLeq P.Adj D.Adj F.Adj W.Adj H.Adj B.Adj SubLeq

----------------------------------------------------------------------------

-90 90 0.58 71.55 0.00 -9.49 -1.31 0.00 0.00 0.00 60.75

----------------------------------------------------------------------------

Segment Leq : 60.75 dBA

Total Leq All Segments: 60.75 dBA

Results segment # 1: Dorval (night)

-----------------------------------

Source height = 1.32 m

ROAD (0.00 + 54.23 + 0.00) = 54.23 dBA

Angle1 Angle2 Alpha RefLeq P.Adj D.Adj F.Adj W.Adj H.Adj B.Adj SubLeq

----------------------------------------------------------------------------

-90 90 0.58 65.02 0.00 -9.49 -1.31 0.00 0.00 0.00 54.23

----------------------------------------------------------------------------

Segment Leq : 54.23 dBA

Total Leq All Segments: 54.23 dBA

TOTAL Leq FROM ALL SOURCES (DAY): 60.75

(NIGHT): 54.23