ADDENDUM NO. 3, February 24, 2015
RE: WMSB - ALNWICK Project Project No. 5511-010 FROM: Larson Design Group 1000 Commerce Park Drive Williamsport, PA 17701 (570) 323-6603 (570) 323-9902 fax TO: Prospective Bidders This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated January 29, 2015; Addendum No. 1, dated February 9, 2015; and Addendum No. 2, dated February 18, 2015, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject Bidder to disqualification. It is the responsibility of each prime contractor to provide their respective subcontractors with the information contained in all issued addenda.
CLARIFICATION: In addition to the work shown on the drawings and noted in the specifications for each prime contractor, a brief clarification of some of the work follows: A. CLARIFICATIONS
1. It is the responsibility of the EC to provide back boxes, conduit above ceiling, pull data cabling, provide and terminate data jacks, provide network patch panels, and terminate connects to patch panels. EC shall run tests on data cabling.
2. MC cabling is allowed as whips to lighting fixtures and between receptacles. Junction boxes and conduit are required from electrical panels to locations above ceiling, below concrete or behind inaccessible walls.
3. Under the base contract, the contractor shall provide B-1 base as shown on A1.3 everywhere. Add Alternate #1 is to install the Chemetal base on the millwork only.
![Page 2: New FROM: Larson Design Group 1000 Commerce Park Drive … · 2015. 2. 24. · ADDENDUM NO. 3, February 24, 2015 RE: WMSB - ALNWICK Project Project No. 5511-010 FROM: Larson Design](https://reader037.vdocuments.site/reader037/viewer/2022090603/6055e3f2dc9f491fef0b72f8/html5/thumbnails/2.jpg)
Addendum No. 3 WMSB - ALNWICK Project 5511-010 Page 2 of 2
B. CHANGES TO PRIOR ADDENDA:
1.
C. CHANGES TO BIDDING REQUIREMENTS:
1. Site - Add a line for Add Alternate #1. D. CHANGES TO AGREEMENT AND OTHER CONTRACT FORMS:
1. N/A E. CHANGES TO CONDITIONS OF THE CONTRACT:
1. Find attached Site Construction Responsibility Matrix. This document describes the site construction responsibilities under the General Construction Contract and those under the Site Construction Contract. This document is to provide clarification to the division of work between contracts.
F. CHANGES TO SPECIFICATIONS:
1. N/A G. CHANGES TO DRAWINGS:
1. Drawing A5.6 - Add note, “Hearthstone by Eldorado Stone. Interior Designer to select color from standard range.”
2. See Electrical Drawings in Attachments
H. ATTACHMENTS:
1. Site Construction Responsibility Matrix 2. E0.1 3. E2.1 4. E4.1 5. SE0.1
END OF ADDENDUM
![Page 3: New FROM: Larson Design Group 1000 Commerce Park Drive … · 2015. 2. 24. · ADDENDUM NO. 3, February 24, 2015 RE: WMSB - ALNWICK Project Project No. 5511-010 FROM: Larson Design](https://reader037.vdocuments.site/reader037/viewer/2022090603/6055e3f2dc9f491fef0b72f8/html5/thumbnails/3.jpg)
Page 1 of 1
W E S T M I L T O N S T A T E B A N K – S I T E C O N S T R U C T I O N
SITE CONSTRUCTION RESPONSIBILITY MATRIX
Element General Contractor
Site Contractor
Building Demolition and Utility Service Disconnections (By Others)
Site Demolition Work X
Parking and Drive Areas; All Bituminous Paving X
Excavation and Grading (Unless Noted Otherwise) X
Site Utilities to 5’-0” outside the building X
Site Utilities past 5’-0” outside the building X
Excavation, Backfill, Foundations, and Subbase for Building X
Excavation, Backfill, Foundations, and Subbase for Concrete Pads, Islands, and Elements under General Contractor Scope
X
Concrete Pads Indicated to be by Building Contractor on Sheet C1.2 X
Concrete Pads, Curbs and Walks NOT indicated to be by Building Contractor on C1.2
X
Concrete Islands at Drive-Thru, including curbing and concrete infills (as indicated on Sheets C1.2 and C1.4
X
Flagpole supply and installation (Refer to Sheet A1.0) X
Planting and Landscaping X
Site Electrical – Wiring, Controls, Fixtures, and Poles X Site Electrical – Excavation, Bedding, Backfill, Conduit, and Foundations X Bollards and Decorative Covers X Enclosures around Generator Pad and AC units detailed on Sheet A6.2, including Aluminum Gates and Foundations
X
Erosion and Sediment Control Work X
Stormwater Management Work X
All elements on Civil Drawings not otherwise indicated X
All elements on Cover, Architectural, Structural, Mechanical, Plumbing, and Electrical Plans not otherwise indicated
X
![Page 4: New FROM: Larson Design Group 1000 Commerce Park Drive … · 2015. 2. 24. · ADDENDUM NO. 3, February 24, 2015 RE: WMSB - ALNWICK Project Project No. 5511-010 FROM: Larson Design](https://reader037.vdocuments.site/reader037/viewer/2022090603/6055e3f2dc9f491fef0b72f8/html5/thumbnails/4.jpg)
ELECTRICAL LINETYPES
E
EU
CTV
T
UT
OH
UE
LV
E
C
CONDUIT TURNING UP
CONDUIT CONCEALED IN CONSTRUCTION IN FINISHEDAREAS, EXPOSED IN UNFINISHED AREAS
CONDUIT CONCEALED IN OR UNDER SLAB
NON-RIGID RACEWAY SYSTEM
CONDUIT TURNING DOWN
EXISTING UNDERGROUND ELECTRICAL
ELECTRICAL TO BE DEMOLISHED
CABLE TV LINE
TELEPHONE LINE
UNDERGROUND TELEPHONE LINE
OVERHEAD ELECTRICAL SERVICE, PRIMARY ORSECONDARY
UNDERGROUND ELECTRICAL SERVICE, PRIMARY ORSECONDARY
LOW VOLTAGE
ELECTRICAL LINE
COMMUNICATIONS LINE
CABLE TRAY A. PRIOR TO CONSTRUCTION & INSTALLATION, CONTRACTOR TO VERIFY EXISTING CONDITIONS AND NOTIFY ARCHITECT/ENGINEER
OF CONFLICTS OR CONDITIONS WHICH INTERFERE WITH INSTALLATION AS SET FORTH IN CONTRACT DOCUMENTS.B. CONTRACTOR RESPONSIBLE FOR ALL FLOOR OPENINGS, EXCAVATIONS, AND PENETRATIONS,UNLESS SPECIFICALLY NOTED.
UPON COMPLETION, ALL PENETRATIONS TO BE SEALED TO MAINTAIN FIRE RATING AS SPECIFIED ON ARCHITECTURAL DRAWINGS.C. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY INDICATED AS PART OF
ANOTHER PRIME CONTRACT.D. ALL WORK SHOWN ON THIS DRAWING IS THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS CLEARLY INDICATED AS PART OF
ANOTHER PRIME CONTRACT.E. ALL WORK TO BE COMPLETED IN COMPLIANCE WITH CURRENT VERSION OF NEC AND ALL LOCAL CODES.
F. MINIMUM WIRE SIZE TO BE #12 AWG (FOR POWER).G. MINIMUM CONDUIT SIZE TO BE 3/4" EMT. INSTALL & SUPPORT IN ACCORDANCE WITH CURRENT VERSION OF NEC.
H. RECEPTACLES TO BE INSTALLED WITH GROUNDING POLE TO THE TOP OR, IF MOUNTED HORIZONTALLY, TO THE LEFT.I. PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR WITHIN EACH BRANCH CIRCUIT RACEWAY.
J. CONTRACTOR RESPONSIBLE FOR OBTAINING ALL PERMITS & INSPECTIONS.K. PROVIDE SUBMITTALS FOR SUBSTITUTIONS ON ANY EQUIPMENT.L. SUBMIT O&M MANUALS TO OWNER UPON COMPLETION OF WORK.
M. PROVIDE TRAINING SESSION FOR DESIGNATED MAINTENANCE PERSONNEL.N. PROVIDE TEMPORARY POWER REQUIRED FOR ALL TRADES.O. INSTALL FIRESTOPPING TO MAINTAIN ALL EXISTING FIRE SEPARATIONS.P. GROUND ALL EQUIPMENT ACCORDING TO CURRENT VERSION OF NEC.
Q. ALL RECEPTACLES DENOTED WP (WEATHERPROOF) TO BE GFI PROTECTED.R. ALL DEVICES & FIXTURES TO BE SPECIFICATION GRADE OR BETTER.S. CONTRACTOR TO PROVIDE BONDING TO STEEL PER NEC250.50.
ELECTRICAL GENERAL NOTES
OC
FAA
FACP
J
F
S
H
C
S
S
S
S
TC
WP
P/S
DVR
PC
C
WP
C
D
OC
3
WP-WEATHERPROOF, PROVIDE BOX AND CONDUIT
FARADAY PM6608/6696
WIREMOLD PFB / LEVITON
TIME CLOCK
PHOTO CELL
PARKING LOT LUMINAIRE
IP BOX SECURITY CAMERA
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL PANEL
FARADAY MPC-DACT
FARADAY MPC-6000
MANUAL FIRE ALARM PULL STATION
VISUAL FIRE ALARM DEVICE
DUAL ACTION
-FARADAY ZR-MC-R
AUDIO/VISUAL FIRE ALARM DEVICE -FARADAY ZH-MC-R
FARADAY 8710SMOKE DETECTOR ADDRESSABLE PHOTOELECTRIC
FARADAY 8712 -HEAT DETECTOR
DATA/TELEPHONE NETWORK FLOOR JACK
DATA NETWORK JACK
TELEPHONE JACK
STEEL CITY PROVIDE BOX AND 3/4" CONDUIT TO ABOVE CLG.JUNCTION BOX
CUTLER HAMMER/SQUARE D -FUSED DISCONNECT
PASS AND SEYMOUR PS5262 -QUADRUPLEX RECEPTACLE
LEGRAND WIREMOLDDUPLEX FLOOR BOX RECEPTACLE
PASS AND SEYMOUR PS2094 GFI PROTECT., PROVIDE TAYMAC 20510 COVERWEATHERPROOF RECEPTACLE
PASS AND SEYMOUR PS5362 20A RATINGCOUNTERTOP RECEPTACLE
PASS AND SEYMOUR PS2094 20A RATINGGFI PROTECTED RECEPTACLE
PASS AND SEYMOUR PS5362 20A RATINGDUPLEX RECEPTACLE
DUAL TECHNOLOGYCEILING MOUNT OCCUPANCY OR VACANCY SENSOR
PASS AND SEYMOUR 93844 -DIMMING SWITCH
SENSOR SWITCH WSD WALL SWITCH DECORATOR SENSOROCCUPANCY SENSOR
THREE WAY SWITCH -PASS AND SEYMOUR PS20AC3
PASS AND SEYMOUR PS20AC1 -SINGLE POLE SWITCH
EXIT SIGN WALL MOUNT
EXIT SIGN CEILING MOUNT
PENDANT/CHAIN MOUNT LIGHT FIXTURE
2X2 RECESSED CEILING MOUNT LIGHT FIXTURE
1X4 RECESSED CEILING MOUNT LIGHT FIXTURE REFER TO LIGHT FIXTURE SCHEDULE -
IN GROUND LIGHT FIXTURE REFER TO LIGHT FIXTURE SCHEDULE -
WALL MOUNTED LIGHT FIXTURE REFER TO LIGHT FIXTURE SCHEDULE -
RECESSED CEILING LIGHT FIXTURE REFER TO LIGHT FIXTURE SCHEDULE -
ELECTRICAL SYMBOL LEGEND
SYMBOL DESCRIPTION REMARKSMFR/MODEL NO.
REFER TO LIGHT FIXTURE SCHEDULE -
REFER TO LIGHT FIXTURE SCHEDULE -
REFER TO LIGHT FIXTURE SCHEDULE CONNECT AHEAD OF LOCAL SWITCHING
REFER TO LIGHT FIXTURE SCHEDULE
-REFER TO LIGHT FIXTURE SCHEDULE
RATED 20A
-
PROVIDE APPROPRIATE FLANGE FORMOUNTING FLUSH TO FLOOR
CONNECT AHEAD OF LOCAL SWITCHING
TORK
TORK
BY OTHERS
IP DOME CAMERA PROVIDE BACK BOX AND CONDUIT
POWER SUPPLY
DVR
LEGRAND WIREMOLD RFB4QUADRUPLEX FLOOR BOX RECEPTACLE
PASS AND SEYMOUR COORDINATE WITH OWNERSPECIAL PURPOSE RECEPTACLE
PROVIDE BOX AND 3/4" C. TO ABOVE CEILING.
PROVIDE BOX AND 3/4" C. TO ABOVE CEILING.
PROVIDE BOX AND 3/4" C. TO ABOVE CEILING.
PROVIDE BOX AND 3/4" C. TO ABOVE CEILING.
BY OTHERS
BY OTHERS
SENSOR SWITCH
BY OTHERS
PROVIDE BOX AND 3/4" CONDUIT TO ABOVE CLG.
PROVIDE BOX AND 3/4" CONDUIT TO ABOVE CLG.LEVITON
LEVITON
PROVIDE APPROPRIATE FLANGE FORMOUNTING FLUSH TO FLOOR
PROVIDE APPROPRIATE FLANGE FOR MOUNTINGFLUSH TO FLOOR
VA
A.F.F. TO CENTER
A.F.F. TO CENTER
A.F.F. TO CENTER
A.F.F. TO CENTER
A.F.F. OR ON EQUIPMENT
A.F.F. TO TOP BREAKER
ELECTRICAL MOUNTING HEIGHTS
(UNLESS OTHERWISE NOTED)
6'
5'
45"
6'
18"
45"LIGHTING CONTROL SWITCHES:
RECEPTACLES & TELEPHONE/DATAOUTLETS:
COUNTERTOP RECEPTACLES/TELEPHONE/DATA:
WALL MOUNTED LIGHTINGFIXTURES:
DISCONNECT SWITCHES:
PANEL BOARDS:
TYPE DESCRIPTION MOUNTING# TYPE WATT V A W
MANUFACTURE CATALOG NO. REMARKSLAMP RATINGS
A 2X2 RECESSED LED RECESSED 1 LED 35 120 0.3 35 COOPER METALUX 22EN-LD1-34-UNV-L840-CD-1 -
TYPE
A
MOUNTING
GRID
1X4 SUSPENDED LED SUSPENDED 1 LED 12048C 0.4 488'-0"
B
CHAINCOOPER METALUX 4WNLED-LD1-41-F-UNV-L840-CD-1-U
LIGHTING FIXTURE SCHEDULE
1x4 RECESSEDPERIMETER LED
RECESSED 1 LED 12038D 0.3 38GYP PROVIDE DRYWALL KIT79-PF-2-L40-8'-0"-UNV-STD-1-C-DC-W
4x4 RECESSEDSQUARE LED
RECESSED 1 LED 12019F 0.2 19GRID -LED4X4-DLM20-4K-1-LSQ4411PR
2 FOOT SPAN WALLWASH LED
PENDANT 1 LED 12037
G
0.3 37CEILING -LA-8-02-3-80-40-AH
CANOPY LIGHT SURFACE 1 LED 12075
T
0.6 75CEILING -XPG3D-S-LED-68-350-NW-UE-BLKU
HEIGHT
2X2 RECESSED LED RECESSED 1 LED 25 120 0.2 25 COOPER METALUX 22EN-LD1-25-UNV-L840-CD-1 -GRID
COOPER NEO-RAY
ATLANTIC LIGHTING
COOPER HALO
LSI
EXIT SIGN RECESSED 1 LED 1205E1 0.05 5GYPPROVIDE CHEVRONS AS
REQUIREDES6-1-R-WCOOPER SURE-LITES
EXIT SIGN RECESSED 1 LED 120E2 GYP ES6-1-R-CCOOPER SUTE-LITES
SITE POLE GRADE 3 LED 12025S3 0.6 75-PROVIDE 12" CENTER GLOBE / 10" OUTER GLOBES
ARCH TO SELECT FINISHA-1841 TALL ST. CHARLES
3 LIGHT LAMP POST
S2PROVIDE 12" ROUND GLOBES
ARCH TO SELECT FINISH
WALL SCONCE WALL 1 LED 12025S1 0.2 25ARCHPROVIDE 10" ROUND GLOBES
ARCH TO SELECT FINISH#1510 VICTORIAN LAMPRECTANGULAR BACK
TUSCUMBIA IRON WORKS
J
ROUND CHANDELIER PENDANT 30 BULB 12015H 3.75 45012'-0" ARCH TO SELECT FINISHCAMINO ROUND CHANDELIER
63" FORGED IRON
RESTORATIONHARDWARE
WALL SCONCE WALL 1 LED 12025 0.2 25ARCH#1510 VICTORIAN LAMPRECTANGULAR BACK
TUSCUMBIA IRON WORKS
TUSCUMBIA IRON WORKS
LOW VOLT TRACK LIGHT TRACK 1 MR 12010 0.4 10- -700KHELLO-5TECH LIGHTING
5 0.05 5 -
1X4 COVE LED COVE 1 LED 12018 0.4 18- ARCH TO SELECT TILTCOOPER AMETRIX LC-1-40K-1-D10-UNV-24-XX
EMERGENCY LIGHT WALL MOUNTED 1 LED 120E3 WALL PGN-BHUBBEL DUAL LITE17 0.15 17 -
4x4 RECESSEDSQUARE LED
RECESSED 1 LED 12019F1 0.2 19GRID PROVIDE DRYWALL KITLED4X4-DLM20-4K-1-LSQ4411PRATLANTIC LIGHTING
IN GRADE - FLAG POLELIGHTING
GRADE 1 LED 120150 1.25 150GRADE -M9720-22-P38150CM-MVOLT-
MFL-FLC-34S-STR-LP-XXXHYDRELK
4x4 RECESSEDSQUARE LED
RECESSED 1 LED 12019F2 0.2 19GRIDWALL WASH /
PROVIDE DRYWALL KITLEDW4X4-DLM20-4K-1-LSQ4411PRATLANTIC LIGHTING
PROJECT NO.:
Lars
on D
esig
n G
roup
Arc
hit
ects
E
ng
ineers
S
urv
eyo
rs
SHEET NO.:
1000 C
om
merc
e P
ark
Drive S
uite 2
01
William
sport
, P
A 1
7701
PH
ON
E 5
70.3
23.6
603
TO
LL F
RE
E 8
77.3
23.6
603
FA
X 5
70.3
23.9
902
ww
w.lars
ondesig
ngro
up.c
om
Lars
on
Desig
n G
rou
pN
O.
DA
TE
CO
MM
EN
TS
BY
CH
K
It is a violation of the law for anyperson, unless acting under thedirection of a licensed Architect,Engineer or Land Surveyor, toalter an item in any way. Plans,
maps, specifications, studies, andreports not containing a red inkseal imprint on the cover sheet
accompanied by an originalsignature by the licensed
professional may have beenfraudulently altered and shall notbe considered an original copy.
Copyright Protected 2015, LarsonDesign Group.
RP
HO
NE
10
1-3
0-1
5IS
SU
ED
FO
R B
ID/P
ER
MIT
C:\U
sers
\JR
ed
inski\D
ocu
me
nts
\55
11-0
10
WM
SB
_C
en
tra
l_JR
ed
inski.rv
t2
/24
/20
15
4:0
7:2
5 P
M
5511-010
E0.1
AL
NW
ICK
397 P
OIN
T T
OW
NS
HIP
DR
IVE
, N
OR
TH
UM
BE
RL
AN
D, P
A 1
7857
WE
ST
MIL
TO
N S
TA
TE
BA
NK
EL
EC
TR
ICA
L L
EG
EN
DS
AN
D N
OT
ES
94
0 H
IGH
ST
RE
ET
WE
ST
MIL
TO
N, P
A 1
78
86
(57
0)
- 5
68
-68
51
JJR
SN
W
30
2-2
4-1
5A
DD
EN
DU
M 3
3
![Page 5: New FROM: Larson Design Group 1000 Commerce Park Drive … · 2015. 2. 24. · ADDENDUM NO. 3, February 24, 2015 RE: WMSB - ALNWICK Project Project No. 5511-010 FROM: Larson Design](https://reader037.vdocuments.site/reader037/viewer/2022090603/6055e3f2dc9f491fef0b72f8/html5/thumbnails/5.jpg)
48"C CC
CC
C
WP
J
AT
S
J
J J
J J
J
J
JJ
PC
J
J J
JJJ
J
J
J
TC
J
J
WP WP
J
WH1
B-6
B-18
B-20
B-9
B-3
B-4
B-4
B-12B-26
B-16
B-21
B-23
B-25
B-1
A-1,3
AHU-5
A
B
B-24
B-10
B-2
B-2
B-7
B-27
B-19
B-5
A-9
B-6
A-5,7
CASH COUNT110
BREAK124
HALL123
HALL120
STORAGE122
JANITOR121
STORAGE119
S DEP118
ELEC/DATA117
WOMEN112
HALL116
MEN111
HALL115
OFFICE107
OFFICE106
CONSULT.105
OFFICE104
VESTIBULE101
WAITING102
CONSULT.108
TELLER109
WAITING103
B-15
B-13
B-29
B-11
CU-1 CU-2 CU-3 CU-4
CU
-5
AH
U-2
AH
U-3
AH
U-4
A-11
A-13 A-15 A-17
A-23,25A-27,29
A-31,33A-35,37
A-39,41
A-19,21 EF-2 EF-1
A-20 A-20
B-22
AHU-1B-4
B-17
B-17
RP1
B-14
B-28
B-32
B-30
B-33
1 2
3 4
3 4
13
14
1314
5
7
6
8
UH-1
A-36
9
B-34 B-34 B-34
C
84
"8
4"
60"
60"
60" 60"
84"
84"
B-36
10
10
16
11
A-38A-38
A-38
15
12
12
12
48"
171717
17
18
19
20
20
20
21
B-4 B-4
B-8
B-38
PROJECT NO.:
Lars
on D
esig
n G
roup
Arc
hit
ects
E
ng
ineers
S
urv
eyo
rs
SHEET NO.:
1000 C
om
merc
e P
ark
Drive S
uite 2
01
William
sport
, P
A 1
7701
PH
ON
E 5
70.3
23.6
603
TO
LL F
RE
E 8
77.3
23.6
603
FA
X 5
70.3
23.9
902
ww
w.lars
ondesig
ngro
up.c
om
Lars
on
Desig
n G
rou
pN
O.
DA
TE
CO
MM
EN
TS
BY
CH
K
It is a violation of the law for anyperson, unless acting under thedirection of a licensed Architect,Engineer or Land Surveyor, toalter an item in any way. Plans,
maps, specifications, studies, andreports not containing a red inkseal imprint on the cover sheet
accompanied by an originalsignature by the licensed
professional may have beenfraudulently altered and shall notbe considered an original copy.
Copyright Protected 2015, LarsonDesign Group.
RP
HO
NE
10
1-3
0-1
5IS
SU
ED
FO
R B
ID/P
ER
MIT
C:\U
sers
\JR
ed
inski\D
ocu
me
nts
\55
11-0
10
WM
SB
_C
en
tra
l_JR
ed
inski.rv
t2
/24
/20
15
4:0
7:2
5 P
M
5511-010
E2.1
AL
NW
ICK
397 P
OIN
T T
OW
NS
HIP
DR
IVE
, N
OR
TH
UM
BE
RL
AN
D, P
A 1
7857
WE
ST
MIL
TO
N S
TA
TE
BA
NKF
IRS
T F
LO
OR
PO
WE
R P
LA
N
94
0 H
IGH
ST
RE
ET
WE
ST
MIL
TO
N, P
A 1
78
86
(57
0)
- 5
68
-68
51
JJR
SN
W
SCALE: 1/4" = 1'-0"1
FIRST FLOOR POWER PLAN
GENERAL NOTES:1. PROVIDE 400A 3-POLE MAIN DISCONNECT . REFER TO
ELECTRICAL ONELINE.2. PROVIDE METER BASE, UTILITY TO PROVIDE METER. REFER
TO ELECTRICAL ONELINE.3. PROVIDE JUNCTION BOX TO FEED ELECTRICAL WORK WITHIN
CASE WORK. JUNCTION BOX TO FEED BOTH TELLERSTATIONS. REFER TO INTERIOR DESIGNER DRAWINGS FORCOORDINATION.
4. PROVIDE JUNCTION BOX FOR DATA CABLING. CONNECTDATA TO DATA JACKS WITHIN CASE WORK. DATA JUNCTIONBOX TO FEED BOTH TELLER STATIONS. MINIMUM OF (4) DATACONNECTIONS. REFER TO INTERIOR DESIGNER DRAWINGSFOR COORDINATION.
5. PROVIDE JUNCTION BOX FOR GAS FIRE PLACE. REFER TOMECHANICAL DRAWINGS.
6. PROVIDE JUNCTION BOXES FOR POWER TO PNEUMATICTUBE SYSTEM. PROVIDE 3/4" CONDUIT WITH PULL STRINGFOR DATA CABLING. COORDINATE WITH PNEUMATIC TUBESYSTEM COMPANY.
7. PROVIDE STANDARD WALL BOX FOR WIRELESS REMOTE FORCF-1. REFER TO MECHANICAL DRAWINGS.
8. PROVIDE FULL HEIGHT DATA RACK FOR OWNER SUPPLIEDEQUIPMENT. PROVIDE REQUIRED OUTLETS FOR RACKMOUNTED UPS.
9. PROVIDE JUNCTION BOX FOR POWER CONNECT TO ATM.REFER TO MANUFACTURERS SPECIFICATIONS.
10. PROVIDE A RECEPTACLE AND DATA JACK AT 5'-0" FOR WALLMOUNTED TV. PROVIDE RECESSED WALL BOX TO MOUNT TVFLAT AGAINST WALL. COORDINATE WITH INTERIORDESIGNER FOR EXACT LOCATION AND HEIGHT BEFOREROUGHIN.
11. PROVIDE RECEPTACLE AND DATA JACK AT 7'-0" FOR WALLMOUNTED SECURITY TV. PROVIDE RECESSED WALL BOX TOMOUNT TV FLAT AGAINST WALL. PROVIDE REQUIREDSECURITY CONNECTIONS TO ALLOW CONNECTION TOSECURITY SYSTEM. REFER TO INTERIOR DESIGNERDRAWINGS FOR EXACT LOCATION AND HEIGHT BEFOREROUGHIN.
12. PROVIDE A JUNCTION BOX FOR ILLUMINATED EXTERIOR SIGN.REFER TO ARCHITECTURAL DRAWINGS FOR EXACTLOCATION AND HEIGHT.
13. PROVIDE JUNCTION BOX TO FEED ELECTRICAL WORK WITHINCASE WORK. REFER TO INTERIOR DESIGNER DRAWINGS FORCOORDINATION.
14. PROVIDE JUNCTION BOX FOR DATA CABLING. CONNECTDATA TO DATA JACKS WITHIN CASE WORK. MINIMUM OF (2)DATA CONNECTIONS. REFER TO INTERIOR DESIGNERDRAWINGS FOR COORDINATION.
15. MOUNT RECEPTACLES AND DATA JACKS BETWEENCOUNTER TOP AND WINDOW SILL. REFER TOARCHITECTURAL DRAWINGS FOR ELEVATIONS.
16. PROVIDE A RECEPTACLE AND DATA JACK AT 7'-0" FOR WALLMOUNTED TV. PROVIDE RECESSED WALL BOX TO MOUNT TVFLAT AGAINST WALL. COORDINATE WITH INTERIORDESIGNER FOR EXACT LOCATION AND HEIGHT BEFOREROUGHIN.
17. PROVIDE JUNCTION BOX FOR LANE LIGHT. CONTRACTOR TOINSTALL 3 GANG OUTLET BOX AT SWITCH HEIGHT, PULL ALLCABING AND MAKE FINAL CONNECTION FOR LANE LIGHTINGCONTROL. LANE LIGHTING PROVIDED BY OTHERS.
18. PROVIDE 4" JUNCTION BOX WITH FLAT COVER FOR ALARMSYSTEM. TO BE PROVIDED BY EQUIPMENT PROVIDER ANDINSTALLED BY CONTRACTOR. CONTRACTOR TO PROVIDEAND INSTALL 3/4" CONDUIT WITH PULLSTRING BETWEENJUNCTION BOX AND ALARM PANEL LOCATION ANDELECTRICAL PANEL.
19. CONTRACTOR TO PROVIDE BACK BOXES AND CONDUITSWITH PULL STRINGS TO ABOVE CEILING FOR SECURITYEQUIPMENT. EQUIPMENT BY OTHERS. REFER TO SECURITYPLANS FOR LOCATIONS.
20. REFER TO PNEUMATIC TUBE SYSTEM DRAWINGS FORCOORDINATION OF POWER AND DATA CABLING.
21. PROVIDE PHOTO CELL MOUNTED AS HIGH AS POSSIBLE.PROVIDE 3/4" CONDUIT WITH PULL STRING BACK TOELECTRICAL ROOM. REFER TO DETAIL 4/E4.1 3
02
-24-1
5A
DD
EN
DU
M 3
3
3
3
3
3
![Page 6: New FROM: Larson Design Group 1000 Commerce Park Drive … · 2015. 2. 24. · ADDENDUM NO. 3, February 24, 2015 RE: WMSB - ALNWICK Project Project No. 5511-010 FROM: Larson Design](https://reader037.vdocuments.site/reader037/viewer/2022090603/6055e3f2dc9f491fef0b72f8/html5/thumbnails/6.jpg)
G
(2) 4" CONDUITS WITH PULLSTRINGS FOR UTILITY. REFER TOELECTRICAL SITE PLANS.
(4) 600MCM AND (1) 1/0 GND IN 4"C.(2) #12AWG AND (1) #12AWG GND IN 3/4"CONDUIT FOR BATTERY CHARGER.(3) #10AWG AND (1) #12AWG GND IN 3/4"CONDUIT FOR BLOCK HEATER.(1) 1" C. W/ (12) #12AWG AND (2) CAT6CABLING FOR GENERATOR CONTROLS.
REFER TO SITE PLAN FORCONDUIT AND WIRE SIZES.
DESCRIPTIONNUMBER
CONDUIT AND WIRE SCHEDULE
(4) 600MCM AND (1) 1/0 GND IN 4"C.
(4) 3/0 AND (1) #6 CU GND IN 2"C
FIRST FLOOR
3/0 CU. G.PER NEC
INSTALL GROUNDINGELECTRODE SYSTEM
PER NEC 250-66
BLDG.STEEL
CONC.FOOTING
MAINWATER
LINE
PANEL
B
200A
208/120V
3ɸ 4W
PANEL
A
400A
208/120V
3ɸ 4W
3/0 CU. G.PER NEC
ROOF
INTERIOREXTERIOR
ATS
400A
120/208V
3ɸ
4-POLE
4 4
MAIN
DISC
400A
120/208V
3ɸ
TO UTILITY
C/TCABINET
1 32
3 4
1
2
5
11
M
2
3
GROUNDRING
5
3
TO SITELIGHTING
4
5
TC
4
GENERATORANNUNCIATOR
PANEL
7
1
2
PROVIDE 400A, 208V 3PHASE, NEMA 3R FUSED SERVICE RATED
DISCONNECT SWITCH FUSE AT 400A. PROVIDE C/T CABINET FOR UTILITY.
PROVIDE METER CABINET, UTILITY METER PROVIDED BY UTILITY.
PROVIDE 400A, 4-POLE, 208V AUTOMATIC TRANSFER SWITCH.
PROVIDE 120/208V 3-PHASE, 42 SPACE, MAIN CIRCUIT BREAKER
ELECTRICAL PANEL, SEE PANEL SCHEDULE AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
PROVIDE KOHLER 125KW NATURAL GAS GENERATOR, MODEL#
125REZGC. 120/208V, 3-PHASE, ALTERNATOR:4R12X. PROVIDE WEATHER
AND SOUND ATTENUATING ENCLOSURE. PROVIDE BATTERY CHARGER.
PROVIDE BLOCK HEATER. PROVIDE CONCRETE PAD, REFER TO
STRUCTURAL DRAWINGS FOR DETAILS.
PROVIDE TIME CLOCK, REFER TO TIME CLOCK DETAIL 2/E4.1 FOR
CIRCUITING AND OPERATION.
PROVIDE GENERATOR ANNUNCIATOR PANEL IN ELECTRICAL ROOM.
1. RACEWAYS ENCLOSING SERVICE CONDUCTORS SHALL MEET NEC 230.53.
2. PROVIDE GROUND FAULT PROTECTION PER NEC 230.95.
3. NEW ELECTRICAL SERVICE SHALL COMPLY WITH NEC 300.5 (D)(3).
4. CONTRACTOR SHALL PROVIDE AIC RATING LABELS WITH CALCULATION DATES
FOR ALL ELECTRICAL EQUIPMENT.
5. PROVIDE PERMANENT SERVICE DISCONNECT IDENTIFICATION IN ACCORDANCE
WITH NEC 230.70 (B).
3
4
5
GENERAL NOTES
KEY NOTES
6
7
N
H
1 2 3 4
TIME POWER
TIME CLOCK,INTERMATIC NO.ET104COR APPROVED EQUAL.INSTALL IN ELECTRICALROOM. PROGRAM OFFTIME AS DIRECTED BYOWNER.
LIGHTING CONTACTOR,20A. 4P. 120V. W/120VCONTROL COIL ANDN.O. CONTACTS.MOUNTED IN NEMA-1ENCLOSURE INELECTRICAL RM.
20 AMP CIRCUITA-8
INSTALL IN A HINGED NEMA 1ENCLOSURE IN ELECTRICAL RM.
PC
PHOTO CELL MOUNTED AT 10'INTERMATIC K4221C OR EQUALLOCATED ON NORTH SIDE OFBUILDING
C
TO OUTSIDE LIGHTSAND SITE LIGHTING
20 AMP CIRCUITA-32
H
N
TO IN GRADE FLAGPOLE LIGHT/ EXTERIORBUILDING LIGHTS
PROJECT NO.:
Lars
on D
esig
n G
roup
Arc
hit
ects
E
ng
ineers
S
urv
eyo
rs
SHEET NO.:
1000 C
om
merc
e P
ark
Drive S
uite 2
01
William
sport
, P
A 1
7701
PH
ON
E 5
70.3
23.6
603
TO
LL F
RE
E 8
77.3
23.6
603
FA
X 5
70.3
23.9
902
ww
w.lars
ondesig
ngro
up.c
om
Lars
on
Desig
n G
rou
pN
O.
DA
TE
CO
MM
EN
TS
BY
CH
K
It is a violation of the law for anyperson, unless acting under thedirection of a licensed Architect,Engineer or Land Surveyor, toalter an item in any way. Plans,
maps, specifications, studies, andreports not containing a red inkseal imprint on the cover sheet
accompanied by an originalsignature by the licensed
professional may have beenfraudulently altered and shall notbe considered an original copy.
Copyright Protected 2015, LarsonDesign Group.
RP
HO
NE
10
1-3
0-1
5IS
SU
ED
FO
R B
ID/P
ER
MIT
C:\U
sers
\JR
ed
inski\D
ocu
me
nts
\55
11-0
10
WM
SB
_C
en
tra
l_JR
ed
inski.rv
t2
/24
/20
15
4:0
8:5
8 P
M
5511-010
E4.1
AL
NW
ICK
397 P
OIN
T T
OW
NS
HIP
DR
IVE
, N
OR
TH
UM
BE
RL
AN
D, P
A 1
7857
WE
ST
MIL
TO
N S
TA
TE
BA
NK
EL
EC
TR
ICA
L S
CH
ED
UL
ES
, O
NE
LIN
ES
AN
D D
ET
AIL
S
94
0 H
IGH
ST
RE
ET
WE
ST
MIL
TO
N, P
A 1
78
86
(57
0)
- 5
68
-68
51
JJR
SN
W
Cooling 0 kVA 0.00% 0 kVA
Receptacle 14.1 kVA 85.41% 12.1 kVA Total Est. Demand... 185 A
Power 44.2 kVA 100.00% 44.2 kVA Total Conn. Current: 189 A
Other 4.2 kVA 100.00% 4.2 kVA Total Est. Demand: 66.6 kVA
Lighting 2.3 kVA 125.00% 2.8 kVA Total Conn. Load: 68.1 kVA
HVAC 3.3 kVA 100.00% 3.3 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Load: 22.7 kVA 20.3 kVA 25.1 kVA
A-41 -- -- -- 1.4 kVA 0 kVA 1 20 A Spare A-42
A-39 CU-5 20 A 2 1.4 kVA 0 kVA 1 20 A Spare A-40
A-37 -- -- -- 1.4 kVA 1.8 kVA 1 20 A Power A-38
A-35 CU-4 20 A 2 1.4 kVA 1 kVA 1 20 A UH-1 A-36
A-33 -- -- -- 1.4 kVA 0 kVA 1 20 A Spare A-34
A-31 CU-3 20 A 2 1.4 kVA 1.4 kVA 1 20 A LTG - SITE / CANOPY LIGHTING-TC A-32
A-29 -- -- -- 2.9 kVA 0.8 kVA 1 20 A TOWER CHANDELIER A-30
A-27 CU-2 40 A 2 2.9 kVA 0.2 kVA 1 20 A WAITING AREA TRACK LIGHTING A-28
A-25 -- -- -- 2.3 kVA 0.2 kVA 1 20 A WAITING AREA TRACK LIGHTING A-26
A-23 CU-1 35 A 2 2.3 kVA 0.8 kVA 1 20 A LTG - WAITING COVE A-24
A-21 -- -- -- 0.2 kVA 0.2 kVA 1 20 A LTG - TELLER A-22
A-19 AHU-5 20 A 2 0.2 kVA 0.6 kVA 1 20 A LTG - RESTROOMS / EF-1, EF-2 A-20
A-17 AHU-4 20 A 1 0.8 kVA 0.4 kVA 1 20 A LTG - WAITING / CAFE A-18
A-15 AHU-3 20 A 1 0.8 kVA 0.4 kVA 1 20 A LTG - OFFICE 104, 105, 106, 107 A-16
A-13 AHU-2 20 A 1 1 kVA 0.2 kVA 1 20 A LTG - VESTIBULE 101 A-14
A-11 AHU-1 20 A 1 0.8 kVA 0.7 kVA 1 20 A LTG - HALL 113, 115, 116, 120, 123 A-12
A-9 RP-1 20 A 1 0.5 kVA 0.3 kVA 1 20 A LTG - BREAK 124 A-10
A-7 -- -- -- 1.1 kVA 0.1 kVA 1 20 A LTG - CANOPY ATM / EXTERIOR / TC A-8
A-5 ELECTRIC BASEBOARD HEATER 20 A 2 1.1 kVA 10.7... -- -- -- A-6
A-3 -- -- -- 1 kVA 11 kVA -- -- -- A-4
A-1 WATER HEATER 20 A 2 1 kVA 9.9 kVA 3 200 A PANEL 'B' A-2
CKT Circuit Description TripPole
s
A B C A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 MCB Rating: 400 A
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: ATS - UTILITY Phases: 3 Mains Type: MCB
Location: ELEC/DATA 117 Volts: 120/208 Wye A.I.C. Rating:
Panelboard: A
Total Est. Demand... 82 A
Total Conn. Current: 88 A
Receptacle 14.1 kVA 85.41% 12.1 kVA Total Est. Demand: 29.6 kVA
Power 16.2 kVA 100.00% 16.2 kVA Total Conn. Load: 31.6 kVA
Other 1.3 kVA 100.00% 1.3 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Load: 9.9 kVA 11 kVA 10.7 kVA
B-41 GENERATOR BLOCK HEATER 20 A 1 3 kVA 0 kVA 1 20 A Spare B-42
B-39 GENERATOR BATTERY CHARGER 20 A 1 1 kVA 0 kVA 1 20 A Spare B-40
B-37 Spare 20 A 1 0 kVA 1.4 kVA 1 20 A VACUUM TUBE SYSTEM B-38
B-35 Spare 20 A 1 0 kVA 0.2 kVA 1 20 A RCPT B-36
B-33 RCPT - COPIER 20 A 1 1.4 kVA 1.2 kVA 1 20 A RCPT B-34
B-31 CF-1 20 A 1 0.5 kVA 1.4 kVA 1 20 A VACUUM TUBE SYSTEM B-32
B-29 CF-1 CONTROLLER 20 A 1 0.2 kVA 1.4 kVA 1 20 A VACUUM TUBE SYSTEM B-30
B-27 RCPT WAITING 102 20 A 1 0.5 kVA 0.4 kVA 1 20 A GAS FIRE PLACE B-28
B-25 RCPT WAITING 102 20 A 1 0.6 kVA 0.2 kVA 1 20 A RCPT WATER FOUNTAIN B-26
B-23 RCPT WAITING 102 20 A 1 0.6 kVA 1.3 kVA 1 20 A RCPT OFFICE 104 B-24
B-21 RCPT WAITING 102 20 A 1 0.6 kVA 0.7 kVA 1 20 A RCPT CONSULT 105 B-22
B-19 RCPT CONSULT 108 20 A 1 0.9 kVA 0.7 kVA 1 20 A RCPT OFFICE 106 B-20
B-17 WAITING AREA DESKS 20 A 1 1.2 kVA 0.7 kVA 1 20 A RCPT OFFICE 107 B-18
B-15 TELLER COUNTER 20 A 1 1.4 kVA 0.4 kVA 1 20 A RCPT RESTROOMS 111,112 B-16
B-13 TELLER COUNTER 20 A 1 1.4 kVA 0.4 kVA 1 20 A RCPT ELEC/DATA 117 B-14
B-11 RCPT TELLER WINDOW 20 A 1 0.4 kVA 0.4 kVA 1 20 A RCPT ELEC/DATA 117 B-12
B-9 ATM 20 A 1 1.4 kVA 0.4 kVA 1 20 A RCPT ELEC/DATA 117 B-10
B-7 RCPT CASH COUNT 110 20 A 1 0.7 kVA 0.4 kVA 1 20 A RCPT ELEC/DATA 117 B-8
B-5 RCPT BREAK 124 20 A 1 0.7 kVA 0.7 kVA 1 20 A RCPT STORAGE 119, 122 B-6
B-3 RCPT BREAK 124 20 A 1 0.5 kVA 1.1 kVA 1 20 A RCPT FANITOR 121 B-4
B-1 RCPT DED BREAK 124 20 A 1 0.2 kVA 1.1 kVA 1 20 A RCPT HALL 113, 116, 120, 123 B-2
CKT Circuit Description TripPole
s
A B C A B C Poles Trip Circuit Description CKT
Enclosure: Type 1 MCB Rating: 200 A
Mounting: Surface Wires: 4 Mains Rating: 200 A
Supply From: A Phases: 3 Mains Type: MCB
Location: ELEC/DATA 117 Volts: 120/208 Wye A.I.C. Rating:
Panelboard: B
NAME
HP V TYPE
STARTER DISCONNECT
MINFUSE
NEMAFUSE
INDLGT
AWG
AHU-1 -
AHU-2
AHU-3
AHU-4
AHU-5
CU-1
CU-2
CU-3
CU-4
CU-5
ELECTRICAL MECHANICAL EQUIPMENT SCHEDULE
-
-
-
-
-
-
-
-
-
120 1
O
6.8
8.4
6.8
6.8
1.0
22.1
27.8
13.6
13.6
13
FLA/MCA
AUTO/COMB/MAN
-
-
-
-
-
-
-
-
-
-
NEMAENCL
PB/HOA
CON-TACT
MOTOR
MINFUSE
NEMAENCL
WIRE &CONDUIT
DIA AMP
CIRCUITBREAKER
POLE PANEL REMARKS
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
12 3/4" 20
2
-
-
-
-
-
-
-
-
-
-
20
120
120
120
208
208
208
208
208
208
1
1
1
1
1
1
1
1
1
20
20
20
20
35
40
20
20
20
12
12
12
12
8
8
12
12
12
3/4"
3/4"
3/4"
3/4"
1"
1"
3/4"
3/4"
3/4"
ELECTRIC WATER HEATER SCHEDULE
WH-1 - 10 - - - - - - - - - 20 2 A 2KW WATER HEATER208 1 20 12 3/4"
RE-CIRCULATION PUMP SCHEDULE
RP-1 1/12 10 - - - - - - - - - 20 1 A -120 1 20 12 3/4"
ELECTRIC BASEBOARD SCHEDULE
BB-1 - - - - - - - - - - - 20 A .75KW BB HEATER208 1 20 12 3/4"
BB-2 - - - - - - - - - - - 20 A208 1 20 12 3/4"
BB-3 - - - - - - - - - - - 20 A208 1 20 12 3/4"
A
A
A
A
A
A
A
A
A
A
2
20
20
20
20
35
40
20
20
20
2
2
2
2
2
1
1
1
1
EXHAUST FAN SCHEDULE
EF-1 - 1 - - - - - - - - - 20 ACONNECT TO LOCAL
SWITCHING120 1 20 12 3/4" 1
EF-2 - 1 - - - - - - - - - 20 ACONNECT TO LOCAL
SWITCHING120 1 20 12 3/4" 1
CONDENSING UNIT SCHEDULE
GAS FURNACE SCHEDULE
CIRCULATION FAN SCHEDULE
CF-1 - 0.6 - - - - - - - - - 20 BCONNECT TO
REMOTE SWITCH120 1 20 12 3/4" 1
ELECTRIC UNIT HEATER SCHEDULE
UH-1 - 8.5 - - - - - - - - - 20 B -120 1 20 12 3/4" 1
2
2
SCALE: NTSE4.1
2 LIGHTING CONTACTOR DETAILSCALE: NTSE4.1
1 ELECTRICAL ONELINE
.75KW BB HEATER
.75KW BB HEATER
30
2-2
4-1
5A
DD
EN
DU
M 3
3
3
3