FCU & AHU
Creates A Better Life
23/4/28
![Page 2: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/2.jpg)
Fan coil unit
![Page 3: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/3.jpg)
How to Read the Model Name?
T1 127V 60 Hz Duct Type
F1 Exposed Floor-stand Type (side air intake)
Nominal Air Volume(CFM)
Chilled Water Fan coil unit
C One Way Cassette T DuctA 4 Way Cassette B 4 Way Cassette (Compact)
T2 2nd Generation Duct Type
Type Code
F2 Exposed Flood-stand Type (below air intake)F3 Concealed Flood-stand Type
-- Normal Static Pressure H High Static Pressure
E with Electrical HeaterR Remote Control RA Remote Control with Electrical HeaterFunction Code
T3 New High-static Pressure Type
G Wall-mounted TypeH1 Exposed Ceiling and Floor Type (side air intake)
H2 Exposed Ceiling and Floor Type (back air intake)H3 Concealed Ceiling and Floor Typy
![Page 4: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/4.jpg)
Fan Coil
Ceiling and
Floor
Duct Wall mounted
Floor Standing
Cassette
![Page 5: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/5.jpg)
1-Way4-Way
Compact
4-Way 4 pipes
Cassette
MKCMKBMKA MKD
![Page 6: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/6.jpg)
1.1. Cooling capacity: 5.7~10.4kW;Cooling capacity: 5.7~10.4kW;
2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);
3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);
4.4. Maximum water inlet temp. is 70 ;℃Maximum water inlet temp. is 70 ;℃
Four-way Cassette
Model List:Model List:
*EAH: Electric Auxiliary Heater
Without EAH With EAHMKA-600R MKA-600RA 2100wMKA-750R MKA-750RA 2100wMKA-850R MKA-850RA 2700wMKA-950R MKA-950RA 2700wMKA-1200R MKA-1200RA 2700w
![Page 7: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/7.jpg)
Four-way cassette
Variable color for the panel:
5.5. LED display in the panel;LED display in the panel;6.6. Different color for the panel;Different color for the panel;7.7. Fresh air function;Fresh air function;8.8. Reserve spaces for air side-outletReserve spaces for air side-outlet
3 Pre-cut holeSend air to the nearby room
BlueWhite Grey Black
![Page 8: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/8.jpg)
New design
1.1. Cooling capacity: 3.0~5.5kW;Cooling capacity: 3.0~5.5kW;
2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);
3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);
4.4. Maximum water inlet temp. is 70℃Maximum water inlet temp. is 70℃5.5. Dimension: 580×254×580Dimension: 580×254×580
Four-way Cassette(60*60)
Model List:Model List:Without EAH* With EAH
MKB-300R MKB-300RA 1000wMKB-400R MKB-400RA 1000wMKB-450R / /MKB-500R / /
*EAH: Electric Auxiliary Heater
Compact
![Page 9: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/9.jpg)
1.1. Cooling capacity: 3040w, 3790w;Cooling capacity: 3040w, 3790w;
2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);
3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);
One-way Cassette
Model List:Model List:
Without EAH With EAHMKC-300R MKC-300RA 1000wMKC-400R MKC-400RA 1000w
*EAH: Electric Auxiliary Heater
![Page 10: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/10.jpg)
4-way pipe
Heat water pipe
Chill water pipe
Models MKD-600F
MKD-750F
MKD-850F
MKD-950F
MKD-1200F
MKD-1500F
Cooling capacity(Btu/h) 17406 20239 21058 22867 31672 36109
Heating capacity(Btu/h)
22765 26860 27509 29590 39761 43072
1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.
2.2. Save a lot of energies in winter.Save a lot of energies in winter.
3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.
![Page 11: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/11.jpg)
4-way pipe
Heat water pipe
Chill water pipe
Models MKD-300
MKD-400
MKD-500
Cooling capacity(Btu/h) 10236 12624 15354
Heating capacity(Btu/h)
13648 17401 20472
1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.
2.2. Save a lot of energies in winter.Save a lot of energies in winter.
3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.
![Page 12: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/12.jpg)
Accessories for cassette
EAH Filter Additional drain pan
3-way valve
Connection kit
Controller
MKA C S O O O SMKB C S O O O SMKC C S O O O SMKD C S O O O SC: the accessories is optional, but it should be assembled in the factory;
S: the accessories is standard;
O: the accessories is optional, it can installed by the installer.
Accessories table:
![Page 13: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/13.jpg)
Block for air outlet hole:
Accessories for cassette
Note: the block is only for four-way cassette(80*80 type).
(Optional)
![Page 14: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/14.jpg)
Accessories for cassette
Additional drain pan (optional):
For 4-way cassette compact For 4-way cassette
![Page 15: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/15.jpg)
Accessories for cassette
3-way valve Connection Kit
Electronic coil
Valve
(Optional) (Optional)
![Page 16: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/16.jpg)
Wireless controller
Wired controller
Central controller
Controllers for cassette
Standard Optional Optional
Note: NIM is necessary if use central controller to control the cassette.
![Page 17: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/17.jpg)
2 Rows
3 Rows
4 Rows
Duct
HSP
MKT2 MKT3 MKT4 MKT5 MKT3H
4 Pipe
![Page 18: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/18.jpg)
Duct (2-Rows without EAH)
1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are optional (Assembled in factory);Air return plenums (including filter) are optional (Assembled in factory);3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
12Pa 30(50)PaMKT2-200 MKT2H-200MKT2-300 MKT2H-300MKT2-400 MKT2H-400MKT2-500 MKT2H-500MKT2-600 MKT2H-600MKT2-800 MKT2H-800
MKT2-1000 MKT2H-1000MKT2-1200 MKT2H-1200MKT2-1400 MKT2H-1400
Model List:Model List:
MKT2, MKT2HMKT2, MKT2H
![Page 19: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/19.jpg)
Duct (2-Rows with EAH)
MKT2-xxxE, MKT2H-xxxEMKT2-xxxE, MKT2H-xxxE
Model List:Model List:
12Pa 30(50)Pa EAHMKT2-200E MKT2H-200E 500wMKT2-300E MKT2H-300E 650wMKT2-400E MKT2H-400E 1000wMKT2-500E MKT2H-500E 1000wMKT2-600E MKT2H-600E 1500wMKT2-800E MKT2H-800E 2000w
MKT2-1000E MKT2H-1000E 2000wMKT2-1200E MKT2H-1200E 3000wMKT2-1400E MKT2H-1400E 3000w
1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are standard;Air return plenums (including filter) are standard;3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
![Page 20: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/20.jpg)
1.1. Cooling capacity:Cooling capacity: 2.2~12.1kW;2.2~12.1kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. For For MKT3H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Duct (3-Rows without EAH)
12Pa 30(50)PaMKT3-200 MKT3H-200MKT3-300 MKT3H-300MKT3-400 MKT3H-400MKT3-500 MKT3H-500MKT3-600 MKT3H-600MKT3-800 MKT3H-800
MKT3-1000 MKT3H-1000 MKT3-1200 MKT3H-1200
Model List:Model List:
![Page 21: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/21.jpg)
1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Duct (4-Rows without EAH)
30PaMKT4H-200MKT4H-300MKT4H-400MKT4H-500MKT4H-600MKT4H-800
MKT4H-1000MKT4H-1200MKT4H-1500MKT4H-2000
Model List:Model List:
![Page 22: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/22.jpg)
1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Duct (4-Rows with EAH)
30PaMKT4H-200EMKT4H-300EMKT4H-400EMKT4H-500EMKT4H-600EMKT4H-800E
MKT4H-1000EMKT4H-1200EMKT4H-1500EMKT4H-2000E
Model List:Model List:
![Page 23: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/23.jpg)
High Static Pressure Duct (without EAH)
1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Static PressureMKT3H-800 70Pa
MKT3H-1000 70PaMKT3H-1200 70PaMKT3H-1400 70PaMKT3H-1600 100PaMKT3H-2000 100PaMKT3H-2200 100Pa
Model List:Model List:MKT3H SeriesMKT3H Series
![Page 24: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/24.jpg)
With EAH EAH Static Pressure
MKT3H-800E 3Kw 70PaMKT3H-1000E 3Kw 70PaMKT3H-1200E 3Kw 70PaMKT3H-1400E 3Kw 70PaMKT3H-1600E 10Kw 100PaMKT3H-2000E 10Kw 100PaMKT3H-2200E 10Kw 100Pa
High Static Pressure Duct (with EAH)
Model List:Model List:MKT3H-xxxE SeriesMKT3H-xxxE Series
1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
![Page 25: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/25.jpg)
4 Pipe ducted type
1 fan 2 fans 4 fans
Models MkT5-200
MkT5-300
MKT5-400
MKT5-500
MKT5-600
MkT5-800
MkT5-1000
MkT5-1200
Cooling capacity(Btu/h) 6826 9215 12287 14676 17065 23208 26621 34812
Heating capacity(Btu/h)
10239 13652 17747 19454 24573 32765 36860 46075
1.For ESP,12Pa and 30Pa are optional.1.For ESP,12Pa and 30Pa are optional.2.The functions are same as 2 pipe ducted type.2.The functions are same as 2 pipe ducted type.
![Page 26: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/26.jpg)
Accessories for duct
EAH Air return plenum &Filter
Additional drain pan
3-way valve
Connection kit
Controller
MKT2No C S O O OYes S S O O O
MKT3 No C S O O O
MKT4No C S O O OYes S S O O O
MKT3HNo C S O O OYes S S O O O
MKT5 No C S O O OC: the accessories are optional, but it should be assembled in the factory;
S: the accessories are standard;
O: the accessories are optional, it can be installed by the installer.
Accessories table:
![Page 27: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/27.jpg)
Air return plenums and electrical heaters:
Accessories for duct
The EAH must be installed in the factory;The air return plenums must be installed in the factory;The duct with EAH must select air return plenums, because the EAH is installed inside the air return plenums;
![Page 28: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/28.jpg)
3-way valve
Electronic coil
Valve
Accessories for duct
(Optional)Connection Kit
(Optional)
![Page 29: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/29.jpg)
Thermostat.
For the units without EAH
For the units with EAH
Controllers for Duct
OptionalOptional
![Page 30: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/30.jpg)
MKF1 MKF2 MKF3 MKF5
Floor Standing
MKF4
ExposedFlat panel
Side intake
ExposedCurving panel
Bottom intake
ExposedFlat panel
Bottom intake
ConcealedExposedCurving panel
Side intake
![Page 31: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/31.jpg)
Floor-standing
Exposed typeExposed type Exposed MKF1-150 MKF2-150MKF1-250 MKF2-250MKF1-300 MKF2-300MKF1-400 MKF2-400MKF1-450 MKF2-450MKF1-500 MKF2-500MKF1-600 MKF2-600MKF1-800 MKF2-800MKF1-900 MKF2-900
Model List:Model List:
MKF1: air return from front side
MKF2: air return from bottom ( standard with foot)
1. Vertical installation on the floor- much more comfortable in heating mode;
2. 3-way valve can be built in the cabinet;
3. Pipe connection can be left or right (installer change it).
![Page 32: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/32.jpg)
Flat type air outlet grill
Exposed type New air outlet grill
Floor-standing
ExposedMKF4-150 MKF5-150MKF4-250 MKF5-250MKF4-300 MKF5-300MKF4-400 MKF5-400MKF4-450 MKF5-450MKF4-500 MKF5-500MKF4-600 MKF5-600MKF4-800 MKF5-800MKF4-900 MKF5-900MKF4: air return from front side
MKF5: air return from bottom ( standard with foot)
Model List:
The grill is modular design- easily removed and cleaned
![Page 33: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/33.jpg)
Floor-standing
Concealed typeConcealed typeModel List:Model List:
ConcealedMKF3-150MKF3-250MKF3-300MKF3-400MKF3-450MKF3-500MKF3-600MKF3-800MKF3-900
1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;
![Page 34: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/34.jpg)
Accessories for Floor standing
C: the accessories is optional, but it should be assembled in the factory;
S: the accessories is standard;
O: the accessories is optional, it can installed by the installer.
Accessories table:
Filter Additional drain pan
3-way valve
Connection kit
Controller
Exposed S S O O OConcealed / S O O O
![Page 35: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/35.jpg)
Accessories for Floor standing
3-way valve, connection kit and additional drain pan
3-way valve-Optional
Connection kit-Optional
![Page 36: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/36.jpg)
Thermostat (optional):
Controllers for Floor-standing
KJR-15B/E Simple controller
KJR-15B/E(P) With anti cold air function
The controller can be hided in the cabinet (only for MKF1,2,4,5)
Optional
Optional
![Page 37: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/37.jpg)
MKH2 MKH3
Ceiling and Floor
ExposedCurving panel
Back intake
ConcealedExposedCurving panel
Side intake
MKH1
![Page 38: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/38.jpg)
Ceiling-Floor
Exposed typeExposed type Model List:Model List:
air return from front side
1. Vertical installation on the floor- much more comfortable in heating mode;
2. 3-way valve can be built in the cabinet;
3. Pipe connection can be left or right (installer change it);
4. Ceiling and Vertical installation for optional will be more convenience.
ExposedMKH1-150MKH1-250MKH1-300MKH1-400MKH1-450MKH1-500MKH1-600MKH1-800MKH1-900
![Page 39: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/39.jpg)
Ceiling-Floor
Exposed typeExposed type Model List:Model List:
air return from bottom
1. Vertical installation on the floor- much more comfortable in heating mode;
2. 3-way valve can be built in the cabinet;
3. Pipe connection can be left or right (installer change it);4. Ceiling and Vertical installation for optional will be more convenience.
ExposedMKH2-150MKH2-250MKH2-300MKH2-400MKH2-450MKH2-500MKH2-600MKH2-800MKH2-900
![Page 40: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/40.jpg)
Concealed typeConcealed type Model List:Model List: ConcealedMKH3-150MKH3-250MKH3-300MKH3-400MKH3-450MKH3-500MKH3-600MKH3-800MKH3-900
1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;
Ceiling-Floor
![Page 41: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/41.jpg)
Accessories for Ceiling and Floor
C: the accessories is optional, but it should be assembled in the factory;
S: the accessories is standard;
O: the accessories is optional, it can installed by the installer.
Accessories table:
Filter Additional drain pan
3-way valve
Connection kit
Controller
Exposed S S O O OConcealed / S O O O
![Page 42: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/42.jpg)
3-way valve, connection kit and additional drain pan
3-way valve-Optional
Connection kit-Optional
Accessories for Ceiling and Floor
![Page 43: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/43.jpg)
Wall Mounted
MKG-250MKG-300MKG-400MKG-500MKG-600
Model List:Model List:
1.1. Capacity: 2.24~4.5kW;Capacity: 2.24~4.5kW;
2.2. 3-way valve is inside the indoor unit;3-way valve is inside the indoor unit;
3.3. ON/OFF terminal for simple remote control ;ON/OFF terminal for simple remote control ;
4.4. Variable color for the panel;Variable color for the panel;
5.5. Multi direction of pipe connection.Multi direction of pipe connection.
MKG SeriesMKG Series
![Page 44: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/44.jpg)
3-way valve Controller Filter
MKG S S See in next page
S: the accessories are standard;
Accessories for Wall mounted
Accessories table:
![Page 45: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/45.jpg)
Bio filter Silver lon filterGTP filter Deodorization filterAnti- formaldehyde filter Silver lon filterHEAP filter Three-tier healthy filterHEPA air fresh filter Anti-acarus filtervitamin filter Active carbon filterNano photocatalyst filter Bio filterCompound air fresh filter
Accessories for Wall mounted
Filter list:
![Page 46: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/46.jpg)
Wireless Wired controller Central controller
Controllers for wall mounted
Standard Optional Optional
Remark: It doesn’t need NIM when choose CCM.
![Page 47: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/47.jpg)
Air Handle Unit
![Page 48: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/48.jpg)
Dual Skinned Horizontal Type
Dual Skinned Vertical Type
Dual Skinned Ceiling Suspended Type
![Page 49: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/49.jpg)
Standard AHU
Dual Skinned (56 Models)
Horizontal Vertical Ceiling Suspended
Models List
![Page 50: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/50.jpg)
◆ Horizontal Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020W ~ MKW2-600W
◆ Vertical Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020L ~ MKW2-600L
◆ Ceiling Suspended Type Air Volume: 2,000 ~ 15,000m3/h Model: MKS020D1 ~ MKS150D1
Specification
![Page 51: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/51.jpg)
Air Out Type
1 2
Ceiling suspended
V e r t ic a l
1 2
H o r iz o n t a l
3 4
![Page 52: New FCU Presentation](https://reader033.vdocuments.site/reader033/viewer/2022061508/577cb4901a28aba7118c867f/html5/thumbnails/52.jpg)