neutral grounding resistor failure detection
DESCRIPTION
Neutral Grounding Resistor Failure Detection PPTTRANSCRIPT
NEUTRAL GROUNDING RESISTOR FAILURE
DETECTION
Guided by: Presented by:Asst. Prof. BINDU C.J NITHYA GOPINATH
EE 7 ROLL NO : 44
2
INTRODUCTION NEUTRAL GROUNDING RESISTOR (NGR) ADVANTAGES OF NGR NGR FAILURE TRIPPING RATIO AND NGR SELECTION CALCULATION OF NGR NGR FAILURE DETECTION CONTINUOUS NGR MONITORING CONCLUSION REFERENCES
CONTENTS
3
A grounded system is defined by a system with at least one conductor or point which is connected to ground either solidly or through impedance.
Resistance grounding is usually preferred by most of the electrical equipment systems.
NGR is usually employed as grounding element in resistance grounding systems.
INTRODUCTION
4
It is usually a resistor that is connected directly between the transformer or generator neutral and the system ground.
Used to limit the fault current in a generator or a transformer during earth faults.
“Current Sensing Ground Fault Protection‟ is the most commonly employed type in resistance grounded systems.
NEUTRAL GROUNDING RESISTOR (NGR)
NGR (cntd.)
A typical NGR is constructed of resistance wire or metal strips coiled and wrapped around porcelain insulators.
6
Properly applied resistance grounding can :
Limit point-of-fault damage
Eliminate transient over voltages
Reduce the risk of an arc flash
Provide continuity of service with a ground fault
Provide adequate current for ground-fault detection and selective coordination
ADVANTAGES OF NGR
7
NGR failure mode is usually open circuit.The desired fault current cannot flow and the ground
fault cannot be cleared.This results in an ungrounded system.
NGR FAILURE MODE
NGR
8
NGR IN SHORT-CIRCUTED MODE
A short-circuited NGR results in a grounded and stable electrical system.
Ground-fault current will flow during a ground fault.
The fault will be cleared by ground fault protection or over current protection.
NGR
9
As NGR is a mechanical component, mechanical failure can happen due to :
Lightning, storms and earthquakes
Overloads
Extended service life
CAUSES OF NGR FAILURE
10
Other causes of failure include :
Corrosive atmospheres
Extreme temperature changes
Triple n harmonic currents
Hail
Manufacturing defects
Vibration
CAUSES OF NGR FAILURE (cntd.)
11
NGR FAILURE
12
NGR failure converts a resistance-grounded system into an ungrounded system.
Operators would not be aware that
Current-sensing ground-fault protection is no longer operational
Risk of transient over voltages exists
CONSEQUENCES OF NGR FAILURE
13
SELECTION OF NGR
14
Tripping ratio is defined as the ratio of prospective ground fault current to the operating value of the ground fault protection.
It ensures that sufficient ground fault current is available for detection when the ground faults occur.
Tripping ratio of 7 is required to detect a two-phase-to-ground fault.
A higher tripping ratio is required to provide machine winding ground fault protection.
TRIPPING RATIO AND NGR SELECTION
15
CALCULATION OF NGRThree parameters are required to specify NGR
U :Rated line to line voltage or system voltage (kV)
If : Rated fault current (A)
Ts : Rated time (s) [Duration of fault]
NGR resistance value can be calculated using the formula
16
Measurement of NGR resistance during maintenance only provides a confirmation that
NGR was good at the time when the resistance was measured.
The NGR could fail at any time
after the measurement is taken or even not be reconnected after the measurement.
NGR checking during maintenance doesn’t guarantee it’s working.
NGR FAILURE DETECTION
17
An open NGR is not a condition that should be allowed to remain on the system for any length of time.
Examination of NGR preventative maintenance suggests that an automatic monitoring device is a better solution.
NGR FAILURE DETECTION (cntd.)
This ensures the need for continuous NGR
monitoring...
19
Detects an open NGR when the failure occurs
Active when control power is applied
Indicates NGR health whether or not the system is energized, with or without a ground fault
CONTINUOUS NGR MONITOR
20
Should detect NGR failure in spite of Ground Fault
Should work in tripping and alarm only systems
Monitoring neutral & ground connections
Monitor shouldn’t be capacitively/inductively coupled to NGR
Monitor should not be exposed to neutral voltage during ground fault
CONTINUOUS NGR MONITORING REQUIREMENTS
21
OVER VOLTAGE AND OVER CURRENT MEASUREMENT AS NGR MONITOR
(51N)- Over current measurement(59N)- Over voltage measurement
This is an ineffective NGR monitoring method.
The combination of these devices can detect an NGR failure only if there is a ground fault on the system.
This design is not continuous NGR monitoring because it relies on the presence of a ground fault to operate.
22
RESISTANCE MEASUREMENT AS AN NGR MONITOR
In this method, there is a possibility
for interference by external dc influences
that continuity through a ground fault may be recognized as NGR continuity
23
There are many possible sources of stray dc voltage in industrial electrical systems:
DC can be impressed on the system by sources like
a ground fault on the dc bus of an adjustable speed drive
obscure sources such as atmospheric electrical conditions
STRAY DC ON THE SYSTEM
24
CONTINUITY THROUGH GROUND FAULT
When a ground fault occurs, there are two parallel paths
a path through the NGR
another path through the transformer or generator winding of the faulted phase to, the fault, and back to the measuring device through ground
25
A BETTER SOLUTION IS....... Combination of an
overvoltage measurement (59N), an overcurrent measurement (51N) and a resistance measurement
It continuously monitors NGR continuity.
26
CONTINUOUS NGR MONITOR
27
It combinesmeasured NGR currenttransformer or generator neutral voltageNGR resistance
. When there is no ground fault on the system, a measurement of NGR
resistance is enough to confirm NGR continuity.
The monitor determines the presence of a ground fault through the voltage and current measurements.
Voltage on the neutral and current in the NGR indicates a ground fault.
CONTINUOUS NGR MONITOR (cntd.)
28
To confirm NGR continuity, the monitor constantly evaluates resistance, current, and voltage measurements.
The sensing resistor connects the monitor to the power system while isolating it from neutral voltage.
The sensing resistor limits the voltage transfer from the system neutral to the NGR monitor.
CONTINUOUS NGR MONITOR (cntd.)
29
NGR MONITOR
30
An open NGR is an undesirable situation.
A system with an open NGR is subject to transient over voltages, and so current sensing ground-fault protection will not indicate the presence of a ground fault.
A ground fault then remains on the system and might escalate to a phase-to-phase fault.
NGRs are subject to many failures.
A well-designed NGR monitor provides continuous protection against failures.
An NGR monitor provides confidence that current-sensing ground-fault protection will operate as designed on the next ground fault.
CONCLUSION
31
[ 1]D. Selkirk, M. Savostianik, K. Crawford, 2010, "The dangers of grounding resistor failure", IEEE Industry Applications Magazine, sept. /oct. 2010, 53-58.
[2]W. Labos, A. Mannarino, G. Drobnjak, S. Ihara, and J. Skliutas, “A possible mechanism for neutral grounding resistor failures,” in Proc. Power Engineering Society General Meeting, June 2005.
[3]G. E. Paulson, “Monitoring neutral-grounding resistors,” in Proc. IEEE Pulp and Paper Industry Committee Conf., June 1999, p. 240.
[4]P. Glover, “Neutral grounding resistors installation and maintenance instructions,” PGR Document #NG111-06.
[5] K. S. Crawford and N. K. Haggerty, “Test before touch—Easier said than done,” IEEE Ind. Applicant. Mag., vol. 14, no. 3, pp. 32–39, May/June 2008.
[6] IEEE Standard 142-1982, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems, The Institute of Electrical and Electronics Engineers, Inc.
[7] ANSI c62.92-1987, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems, Part I - Introduction, American National Standards Institute.
[8] PRSC-4E, System Neutral Grounding and Ground Fault Protection Guide, Westinghouse Industrial and Commercial Power Systems Applications Series, February 1986.
REFERENCES
32
THANK YOU