national fire alarm and changes to the 2017_pdfs/a_electrical_engineering_sessio… · 72-2013 and...

27
9/22/2017 1 CHANGES TO THE NATIONAL FIRE ALARM AND SIGNALING CODE – 2010 TO 2013 EDITION Larry D. Rietz, SET 16 October 2017 Copyright © 2017 by JENSEN HUGHES Advancing the Science of Safety Determine which Code sections of NFPA 72 have changed. Learn how to apply the changed in your daily work and the impact the changes will make on all new buildings. Learn how to apply the new inspection, testing, and maintenance requirements of NFPA 72-2013. Learn the impact of Risk Analysis requirements of Chapter 24 of NFPA 72-2013 and how they interface with the new IBC and NFPA 101. PRESENTATION LEARNING OBJECTIVES 2 Advancing the Science of Safety Portions of this program are reprinted from NFPA 72 ® – 2016, National Fire Alarm and Signaling Code, Copyright © 2015, National Fire Protection Association, Quincy, MA and other previous editions of NFPA 72. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. NFPA 72 ® is a registered trademark of the National Fire Protection Association, Quincy, MA 02169. This presentation does not reflect the official position of the National Fire Protection Association. NFPA 72 ® 3

Upload: dangkhuong

Post on 18-Mar-2018

214 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

1

CHANGES TO THE NATIONAL FIRE ALARM AND

SIGNALING CODE – 2010 TO 2013 EDITIONLarry D. Rietz, SET

16 October 2017

Copyright © 2017 by JENSEN HUGHES

Advancing the Science of Safety

� Determine which Code sections of NFPA 72 have changed.

� Learn how to apply the changed in your daily work and the impact the

changes will make on all new buildings.

� Learn how to apply the new inspection, testing, and maintenance

requirements of NFPA 72-2013.

� Learn the impact of Risk Analysis requirements of Chapter 24 of NFPA

72-2013 and how they interface with the new IBC and NFPA 101.

PRESENTATION LEARNING OBJECTIVES

2

Advancing the Science of Safety

Portions of this program are reprinted from NFPA 72 ® – 2016, National

Fire Alarm and Signaling Code, Copyright © 2015, National Fire

Protection Association, Quincy, MA and other previous editions of NFPA

72. This reprinted material is not the complete and official position of the

NFPA on the referenced subject, which is represented only by the

standard in its entirety.

NFPA 72 ® is a registered trademark of the National Fire Protection

Association, Quincy, MA 02169.

This presentation does not reflect the official position of the National Fire

Protection Association.

NFPA 72®

3

Page 2: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

2

Advancing the Science of Safety

WHAT HAS CHANGED?

NFPA 72 – 2013 CHANGES

4

Advancing the Science of Safety

Organization of NFPA 72, 2013

Better organization

Easier to locate key requirements

Future growth

Administrative

Chapters

1 - 9

Support

Chapters

10 - 19

System

Chapters

20 - 29

Usability

Annexes

A - I

Advancing the Science of Safety

Administrative Chapters

1. Administration

2. Referenced Publications

3. Definitions

4. Reserved

5. Reserved

6. Reserved

7. Documentation

8. Reserved

9. Reserved

NEW

Page 3: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

3

Advancing the Science of Safety

Support Chapters

10. Fundamentals

11. Reserved

12. Circuits and Pathways

13. Reserved

14. Inspection, Testing, and Maintenance

15. Reserved

16. Reserved

17. Initiating Devices

18. Notification Appliances

19. Reserved

Advancing the Science of Safety

System Chapters

20. Reserved

21. Emergency Control Functions and Interfaces

22. Reserved

23. Protected Premises Fire Alarm Systems

24. Emergency Communications Systems

25. Reserved

26. Supervising Station Alarm Systems

27. Public Emergency Alarm Reporting

28. Reserved

29. Single- and Multiple-Station Alarms and Household Fire Alarm Systems

Advancing the Science of Safety

Usability Annexes

A. Explanatory Material

B. Engineering Guide for Automatic Fire Detector Spacing

C. System Performance and Design Guide

D. Speech Intelligibility

E. NEMA SB 30, Fire Service Annunciator and Interface

F. Sample Ordinance Adopting NFPA 72

G. Wiring Diagrams and Guide for Testing Fire Alarm Circuits

H.Informational References

I. Cross-Reference Table

J. Index

Page 4: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

4

Advancing the Science of Safety

NFPA 72 – 2013 Organization

Administrative

Chapters

1 - 9

Support

Chapters

10 - 19

System

Chapters

20 - 29

Usability

Annexes

A - I

1. Administration

2. Referenced Publications

3. Definitions

4. Reserved

5. Reserved

6. Reserved

7. Documentation

8. Reserved

9. Reserved

10.Fundamentals

11.Reserved

12.Circuits and Pathways

13.Reserved

14.Inspection, Testing, and

Maintenance

15.Reserved

16.Reserved

17.Initiating Devices

18.Notification Appliances

19.Reserved

20.Reserved

21.Emergency Control

Functions and

Interfaces

22.Reserved

23.Protected Premises Fire

Alarm Systems

24.Emergency

Communications

Systems

25.Reserved

26.Supervising Station

Alarm Systems

27.Public Emergency

Alarm Reporting

28.Reserved

29.Single- and Multiple-

Station Alarms and

Household Fire Alarm

Systems

A. Explanatory Material

B. Engineering Guide

for Automatic Fire

Detector Spacing

C. System Performance

and Design Guide

D. Speech Intelligibility

E. Sample Ordinance

Adopting NFPA 72

F. Wiring Diagrams and

Guide for Testing Fire

Alarm Circuits

G. Informational

References

Index

Advancing the Science of Safety

Accessible – four versions

Communications Cloud

Deficiency

ECS Emergency Command Center

Fire Command Center

Emergency Control Function

Interface

Impairment

Manufacturer’s Published

Instructions

Occupiable

Occupiable Area

System Designer

System Installer

Chapter 3 – New Definitions

Advancing the Science of Safety

Chapter 3 - Definitions

3.3.1 Accessible

3.3.4 Accessible Spaces

There are several new definitions relating to accessibility including

Accessible as applied to equipment

Accessible as applied to wiring methods

Readily accessible as applied to installation

Accessible spaces as applied to detection coverage

Page 5: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

5

Advancing the Science of Safety

Chapter 3 - Definitions

3.3.57 Condition

3.3.244 Response

New concept for process of signals.

Definitions Used

in Chapter 10

Advancing the Science of Safety

Chapter 3 - Definitions

3.3.91 Emergency Control Functions

3.3.137.1.2 Emergency Control Function Interface

Change in terminology – this

definition used to be known as

“FIRE CONTROL or SAFETY

FUNCTIONS”

Advancing the Science of Safety

Chapter 3 - Definitions

3.3.102.2.1 Dedicated Function FACU

3.3.105.4.2 Dedicated Function FAS

Dedicated function fire alarm systems

and dedicated fire alarm control units

are used when fire alarm systems are

not required but there is a need for a

fire alarm control panel for other code-

required functions.

Page 6: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

6

Advancing the Science of Safety

Chapter 3 - Definitions

3.3.257 SignalThis definition was expanded to include a

number of different kinds of signals:

Alarm

Carbon Monoxide Alarm

Delinquency

Evacuation

Fire Alarm

Guard’s Tour Supervisory

Pre-Alarm

Restoration

Supervisory

Trouble

Advancing the Science of Safety

Chapter 3 - Definitions

3.3.307 Unwanted Alarm New definition with several types

of “unwanted alarms”

Malicious

Nuisance

Unintentional

Unknown

Advancing the Science of Safety

Chapter 7 – Documentation

Structure:

Page 7: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

7

Advancing the Science of Safety

Chapter 7 - Documentation

Applies to new systems

� Design

� Acceptance

� Completion

Applies to existing systems

� Alterations

� Maintenance

� Testing

Does NOT apply to Single Station, Multiple Station and

Household Systems

Advancing the Science of Safety

Chapter 7 – Documentation

Minimum Requirements

Written Narrative

Riser Diagram

Floor Plan

Sequence of operation (matrix or narrative)

Equipment technical data sheets

Manufacturers published instructions

Identification of the person responsible for the

design or layout

Advancing the Science of Safety

Chapter 7 – Documentation

Minimum Requirements

Battery calculations

Voltage drop calculations for NACs

Completed record of inspection and testing

Completed record of completion

A copy of site specific software

Record (as-built) drawings

Use of NFPA 170 symbols or others acceptable to

the AHJ

Page 8: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

8

Advancing the Science of Safety

Design Documentation

Fire Alarm Design Must Include:

• Ambient noise and audible design sound pressure levels (7.3.4.3)

• Documentation of acoustically distinguishable spaces (ADS) (7.3.4.5)

• Designation of spaces to have visual notification (7.3.4.6)

• Extensive ECS design document requirements (7.3.6)

Advancing the Science of Safety

7.7.2 Document Accessibility

With every new system, a documentation cabinet shall be installed at the system control unit or at another approved location at the protected premises

All record documentation shall be stored in the documentation cabinet

Where this documentation cabinet is not in the same location as the system control unit, its location shall be identified at the system control unit

The documentation cabinet shall be prominently

labeled SYSTEM RECORD DOCUMENTS

The contents of the cabinet shall be accessible by

authorized personnel only.

Advancing the Science of Safety

Chapter 7 – Documentation Forms

www.nfpa.org/72forms

Page 9: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

9

Advancing the Science of Safety

Chapter 10 - Fundamentals

Changes to circuit breaker

identification

FIRE ALARM

EMERGENCY COMMUNICATIONS

FIRE ALARM/ECS

10.6.5.2.2 Circuit Identification

Advancing the Science of Safety

Chapter 10 - Fundamentals

Requires circuit breaker lock under all

circumstances

10.6.5.4 Circuit Breaker Lock

NO, THE PADLOCK

IS NOT

REQUIRED!

Advancing the Science of Safety

Chapter 10 - Qualifications

All qualification requirements moved to Chapter 10

� System Designer

� System Installer

� Inspection Personnel

� Testing Personnel

� Service Personnel

� Programming

� Supervising Station Operators

Page 10: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

10

Advancing the Science of Safety

Chapter 10 - Signal Priority

Signal Priority

� Carbon monoxide signals shall be permitted to take

precedence over supervisory and trouble signals.

� Pre-alarm signals shall take precedence over supervisory

and trouble signals.

Advancing the Science of Safety

Chapter 10 - Fundamentals

All required annunciation means

shall be located as required by

the AHJ to facilitate an efficient

response to the situation.

10.18.3.2 Annunciator

Location

Advancing the Science of Safety

Chapter 10 - Fundamentals

For the purpose of reporting, alarm

signals that are not the result of

hazardous conditions shall be

classified as Unwanted and sub

classified as one of the following:

Malicious

Nuisance

Unintentional

Unknown

10.22 Unwanted Alarm Reporting

Page 11: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

11

Advancing the Science of Safety

Chapter 12 – Circuits and Pathways

All power-limited and non-power-limited circuits which enter or

exit are now required to have transient protection (12.2.4.2)

Advancing the Science of Safety

Chapter 12 – Circuits and Pathways

12.3 Pathway Class

Designation

In 2013 there is more clarification

for performance of Class A, Class

B, and Class X Pathways.

Also added updates to 12.3.7 on

Class A and X physical separation.

Credit: NFPA 72©-2013, Annex F

Advancing the Science of Safety

Chapter 12

12.5 Shared Pathway

Designations

Shared Pathways:

Level 0

Level 1

Level 2

Level 3

Page 12: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

12

Advancing the Science of Safety

Shared Pathways

Level 0 – Level 0 pathways shall not be required to segregate or prioritize life safety data from non life safety data.

Level 1 – Level 1 pathways shall not be required to segregate life safety data from non life safety data but shall prioritize life safety data from non life safety data

Level 2 – Level 2 pathways shall segregate all life safety data from non life safety data

Level 3 – Level 3 pathways shall use equipment that is dedicated to the life safety system.

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

14.2.1 Purpose

• Initial and reacceptance inspections

• Initial and reacceptance tests

• Periodic inspections

• Periodic tests

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

14.2.2.2 Impairments/Deficiencies

� System deficiencies shall be corrected

� If not corrected at the time of the conclusion of ITM, owner shall be

notified within 24 hours in writing.

Page 13: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

13

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

14.2.3.2 Delegation of Responsibility

� Property owner shall be able to delegate authority and responsibility to

the occupant

� Requires written lease, use agreement, or management contract!

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

14.2.10 Test Plan

� A test plan shall be written to clearly establish the scope of the testing

for the system.

� The test plan and results shall be documented in the testing records.

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

Format of Visual Inspection Table 14.3.1

� Combined Frequency with Method

� Expanded method details

Page 14: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

14

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

Format of Testing Table 14.4.3.2

� Combined Frequency with Method

� Expanded method details

Advancing the Science of Safety

Chapter 14 – Inspection, Testing, and Maintenance

14.4.11 Voice Intelligibility

� Follow requirements of Chapter 18

� Intelligibility shall not be required to be determined through

quantitative measurements

� Quantitative measurements (Annex D) shall be permitted but not

required

Advancing the Science of Safety

New Text Added – Section 17.1.2

� Chapter 17 does not require detectors!

� Detectors are only required by other:

� Governing laws, regulations

� Codes

� Standards

� Another Section of NFPA 72

Examples

� NFPA 101, IBC

� NFPA 72 Section 10.4 (detector at the FACU)

Chapter 17 – Initiating Device

Page 15: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

15

Advancing the Science of Safety

Chapter 17 – Initiating Device

Initiating devices shall be installed in a manner that provides accessibility for periodic inspection, testing and maintenance.

“Accessible Spaces”:

• Spaces or concealed areas of construction

• Space that can be entered via panel, door hatches, ceiling tiles

• Applies only for the purpose of determining extent of detector coverage, relevant when “Total Coverage” used

17.4.4 Accessible installation

required

Advancing the Science of Safety

Initiating Devices – Total Coverage

Section 17.5.3

• Detection in all places practical and that may present

combustible materials

• Spaces that can be accessed by doors, panels, ceiling tiles

• Recognizes conditions where it is not practical to install

detectors

• Recognizes where air movement is useful for detection

schemes

• Considers special conditions related to smoke detection and

smoke compartments

Advancing the Science of Safety

Total Coverage – Scenario 1

Combustible concealed space

Ceiling Line

Concealed

Space must

be made

accessible for

inspection

and

maintaining

of detectors

NOTE: combustible blind spaces meeting

17.5.3.1.2 DO NOT require detectors

Detector

( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)

Page 16: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

16

Advancing the Science of Safety

Total Coverage – Scenario 2

Non-Combustible concealed space – No detectors required

Ceiling Line – Hard ceiling, no access

NOTE: combustible blind spaces meeting

17.5.3.1.2 DO NOT require detectors

Air Return

Detector

( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)

Advancing the Science of Safety

Total Coverage – Scenario 3

Non-Combustible concealed space

Ceiling Line – Accessible suspended ceiling

Because ceiling is accessible detectors are required above ceiling

Air Return

Detector

( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)

Advancing the Science of Safety

Total Coverage – Scenario 4

NFPA 90A compliant space – air return plenum

Ceiling Line – Accessible suspended ceiling

With duct detector in air return system plenum detectors are not required above ceiling

Air Return

Air returns to plenum Air returns to plenum

Detector

( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)

Page 17: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

17

Advancing the Science of Safety

Total Coverage – Scenario 5, in Context of

17.7.5.4.2.2 & Smoke Compartments

Ceiling Line – may or may not be accessible

Evaluate space by Scenarios 1,2,3 (See 17.5.3.1) to determine if detectors needed above ceiling

Air Return

Air returns to duct Air returns to duct

Smoke

Detector

With Total Coverage Provided, then in context of

17.7.5.4.2.2 the air return duct detector can be

omitted if the Total Coverage detectors activate –

doors, dampers , etc.

( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)

Advancing the Science of Safety

Total Coverage – Scenario 6, in Context of

17.7.5.4.2.2 & Smoke Compartments

Ceiling Line – may or may not be accessible

Air Return

Evaluate space by Scenarios 1,2,3 (See 17.5.3.1) to determine if detectors needed above ceiling

With Total Coverage Provided, then in context of

17.7.5.4.2.2 the air return duct detector can be

omitted if the Total Coverage detectors activate –

doors, dampers , etc.

Smoke

Detector

( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)

Air returns to plenum Air returns to plenum

Advancing the Science of Safety

Chapter 17

Modified requirements for labeling of

remote indicators

17.4.8 Remote indicators

Page 18: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

18

Advancing the Science of Safety

Chapter 17

Updated requirements for manual boxes

for fire and non-fire purposes

Comprehensively addresses both:

• Manually-actuated alarm-initiating

devices

• Manual fire alarm boxes

• Listed protective covers allowed over

single- or double-action devices

17.14 Manual Alarm Boxes

Advancing the Science of Safety

Chapter 18 – Notification Appliances

18.4.1.4.1 Designated audible areas

� Designer to designate where audible notification will be installed and

those areas where audible notification isn’t required.

Advancing the Science of Safety

Chapter 18 – Notification Appliances

18.4.1.4.3 Design Sound

Pressure Levels

� Design sound pressure levels

(SPL) SHALL be documented

by the system designer.

� Expected ambient SPL

� Use for acceptance testing

� Documented on submittals for

review and approval

Page 19: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

19

Advancing the Science of Safety

Chapter 18

18.4.2.1 Temporal III used for more than evacuation

� Evacuate

� Relocate

Advancing the Science of Safety

Chapter 18

18.4.5.3 Low Frequency Sounders

� Required for Sleeping Rooms

� System activation

Advancing the Science of Safety

Chapter 18

18.5.5.2 Strobe mounting alternatives

� Low ceilings where 80-96” is not achievable

� Formula to determine rating of strobes when mounted in accordance

with this section

Page 20: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

20

Advancing the Science of Safety

Chapter 18

18.9 Textual and Graphical Visible Appliances

� Section revised to include location (private and public modes),

performance, character and symbol requirements and viewing

distances

Advancing the Science of Safety

Chapter 21 –

Emergency Control Function Interfaces

Title Changed to “Emergency Control Function Interfaces”

� 21.2.4 Interface Devices – Revised Terms

� 21.3.7 Elevator pit sprinklers trigger detection

� 21.5 Fire Service Access Elevators

� 21.6 Occupant Evacuation Elevators

Advancing the Science of Safety

Chapter 21 –

Emergency Control Function Interfaces

21.2.4 Emergency Control Interface

� Revised to clarify terms, removing ‘relay’ and ‘appliance’

Page 21: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

21

Advancing the Science of Safety

Chapter 21

21.3.7 Elevator pit sprinklers trigger detection

� When sprinklers are installed in elevator pits, automatic fire detection

shall be installed to initiate elevator recall.

Advancing the Science of Safety

Chapter 21

21.5 Fire Service Access Elevators

� Conditions for fire service access elevators where provided

Advancing the Science of Safety

Chapter 21

21.6 Occupant Evacuation Elevators

� Conditions for occupant evacuation elevators where installed

Page 22: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

22

Advancing the Science of Safety

Chapter 23 – Protected Premises Fire Alarm Systems

23.6.1 Performance of SLC Requires a loss of no more than

50 addressable devices for a

signaling line circuit.

Courtesy: Canadian Consulting Engineer

Advancing the Science of Safety

Chapter 23

23.8.3.2 Interconnection of Bldg Fire Alarm System to a

Household Panel

Household

Fire

Alarm

System

Building

Fire Alarm

Panel

NAC

IDC or

SLC

Advancing the Science of Safety

Chapter 23

23.8.4.8 Carbon Monoxide Signals

� CO detection activation shall be indicated as carbon monoxide alarm

signals

� Exception allows Supervisory condition where permitted by the

building response plan

Page 23: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

23

Advancing the Science of Safety

Chapter 23

23.8.5.6.3 Monitoring of Sprinkler System Valves

� Requires supervision if a valve is installed in the connection between

a sprinkler system and an initiating device

� Supervised/Monitored by:

�Building Fire Alarm System

�Dedicated Function Fire Alarm System

Courtesy: Potter

Advancing the Science of Safety

Chapter 23

23.8.6.1 Occupant Notification

� Revised to require one or more notification appliances in each

notification zone vs. each floor, so they meet the requirements of

Chapter 18, for public or private mode, as required.

Courtesy: Eaton Cooper Notification

Advancing the Science of Safety

Chapter 23

23.10 Fire Alarm Systems Using Tones

� Requires survivability for fire alarm systems using tones for partial

evacuation and relocation!

Page 24: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

24

Advancing the Science of Safety

Chapter 24 – Emergency Communications Systems

24.3.8 Mass Notification Layers

Layer 1 – means of notification of occupants

by systems installed inside a building

Layer 2 – means of notification of occupants

on the exterior of a building

Layer 3 – means of notification of personnel

through distributed recipient MNS

Layer 4 – means of notification of personnel

by public measures (public broadcast radio,

TV, etc)

Advancing the Science of Safety

Layer 3 - Individual

� Personal Alerting

� SMS Text (Cell Phones)

Messages

� Computer Pop-Ups

� Smartphone Apps

� Email Broadcast (Internet)

� Automated Voice Dialing & Text

Messaging (Reverse 911)

Layer 4 - Public

� Public Alerting

� Sat/AM/FM Radio Broadcasts

� Sat/Off-Air TV Broadcasts

� Location/Coverage Specific

� Locally Relevant Alerting

� Handheld Bullhorns71

Layer 1 - Indoor

� Immediate & Intrusive

� Fire Voice Evacuation (EVACS)

� One-Way Voice (PA)

� Two-Way Voice (RA)

� Visible Notification

� Textual/Digital Signage/Displays

� Code Compliant

Layer 2 - Outdoor

� Sirens, Indoor/Outdoor Loudspeakers

� Wide-Area Outdoor MNS

� High Power Loudspeaker Arrays (HPLSA)

CHAPTER 24 – ECS/MNS LAYERS

Advancing the Science of Safety

Chapter 24

24.3.11 Risk Analysis for MNS

� Specifies risk analysis design requirements for mass notification

systems.

Page 25: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

25

Advancing the Science of Safety

Chapter 24 – Emergency Communications Systems

4.4 One-Way Emergency Communications Systems

• The concept of message templates is now introduced into the Code and requires that the messages be developed for each scenario developed in the emergency response plan

• For all evacuation messages, a tone in accordance with Chapter 18 must be used with 2 cycles before and after the message as a minimum.

• All test messages must clearly state: “This is a Test.”

• 24.4.2.2 Voice Evacuation Messages: In occupancies where sleeping accommodations are provided and the voice message is intended to communicate information to those who could be asleep, a low-frequency tone that complies with 18.4.5 shall be used for the 2 cycles before and after the message.

Advancing the Science of Safety

Chapter 26 – Supervising Station Alarm Systems

26.2.7 Change of Service

� Requires subscribers and AHJs to be notified within 30 days of

change of monitoring service where supervising station changes.

Protected

by

XYZ Alarm

Advancing the Science of Safety

Chapter 26

26.6.3.1.5 Single Path Supervision Interval

26.6.3.1.6 Multiple Path Supervision Intervals

� Single transmission path shall be permitted, and path shall be

supervised at an interval of not more than 60 minutes

� If multiple transmission paths are used, each path shall be supervised

within not more than 6 hours

Page 26: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

26

Advancing the Science of Safety

Chapter 26

26.6.3.1.15 Secondary Power Requirements

� Secondary power capacity for all equipment necessary for the

transmission of O signals located at the protected premises shall

have a secondary power capacity of 24 hours.

Advancing the Science of Safety

Chapter 26

26.6.3.2.1.4 DACT Transmission Channels

� The first transmission means shall be a telephone line (number).

� The second transmission means shall be a one way private radio, two

way RF multiplex radio system, or a performance based transmission

method as specified in 26.6.3.1.

� This means that only one telephone line may be used!

� Each transmission means shall automatically initiate and complete a

test signal transmission sequence to its associated receiver at least

once every 6 hours.

Advancing the Science of Safety

Chapter 29

29.7.3 Resistance to Nuisance Alarms

� Effective 1/1/19, smoke alarms and smoke detection used in

household fire alarm systems shall be listed for resistance to common

nuisance sources.

Page 27: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for

9/22/2017

27

Advancing the Science of Safety

ContactLarry D. Rietz, SET

+1 303-439-0485

[email protected]

For More Information Visit

jensenhughes.com

QUESTIONS?

79Content is Copyright 2017 © Jensen Hughes, Inc. All Rights Reserved

Wayne Moore

604-242-0081wmoore@jensenhughes

Warwick, RI