national fire alarm and changes to the 2017_pdfs/a_electrical_engineering_sessio… · 72-2013 and...
TRANSCRIPT
![Page 1: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/1.jpg)
9/22/2017
1
CHANGES TO THE NATIONAL FIRE ALARM AND
SIGNALING CODE – 2010 TO 2013 EDITIONLarry D. Rietz, SET
16 October 2017
Copyright © 2017 by JENSEN HUGHES
Advancing the Science of Safety
� Determine which Code sections of NFPA 72 have changed.
� Learn how to apply the changed in your daily work and the impact the
changes will make on all new buildings.
� Learn how to apply the new inspection, testing, and maintenance
requirements of NFPA 72-2013.
� Learn the impact of Risk Analysis requirements of Chapter 24 of NFPA
72-2013 and how they interface with the new IBC and NFPA 101.
PRESENTATION LEARNING OBJECTIVES
2
Advancing the Science of Safety
Portions of this program are reprinted from NFPA 72 ® – 2016, National
Fire Alarm and Signaling Code, Copyright © 2015, National Fire
Protection Association, Quincy, MA and other previous editions of NFPA
72. This reprinted material is not the complete and official position of the
NFPA on the referenced subject, which is represented only by the
standard in its entirety.
NFPA 72 ® is a registered trademark of the National Fire Protection
Association, Quincy, MA 02169.
This presentation does not reflect the official position of the National Fire
Protection Association.
NFPA 72®
3
![Page 2: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/2.jpg)
9/22/2017
2
Advancing the Science of Safety
WHAT HAS CHANGED?
NFPA 72 – 2013 CHANGES
4
Advancing the Science of Safety
Organization of NFPA 72, 2013
Better organization
Easier to locate key requirements
Future growth
Administrative
Chapters
1 - 9
Support
Chapters
10 - 19
System
Chapters
20 - 29
Usability
Annexes
A - I
Advancing the Science of Safety
Administrative Chapters
1. Administration
2. Referenced Publications
3. Definitions
4. Reserved
5. Reserved
6. Reserved
7. Documentation
8. Reserved
9. Reserved
NEW
![Page 3: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/3.jpg)
9/22/2017
3
Advancing the Science of Safety
Support Chapters
10. Fundamentals
11. Reserved
12. Circuits and Pathways
13. Reserved
14. Inspection, Testing, and Maintenance
15. Reserved
16. Reserved
17. Initiating Devices
18. Notification Appliances
19. Reserved
Advancing the Science of Safety
System Chapters
20. Reserved
21. Emergency Control Functions and Interfaces
22. Reserved
23. Protected Premises Fire Alarm Systems
24. Emergency Communications Systems
25. Reserved
26. Supervising Station Alarm Systems
27. Public Emergency Alarm Reporting
28. Reserved
29. Single- and Multiple-Station Alarms and Household Fire Alarm Systems
Advancing the Science of Safety
Usability Annexes
A. Explanatory Material
B. Engineering Guide for Automatic Fire Detector Spacing
C. System Performance and Design Guide
D. Speech Intelligibility
E. NEMA SB 30, Fire Service Annunciator and Interface
F. Sample Ordinance Adopting NFPA 72
G. Wiring Diagrams and Guide for Testing Fire Alarm Circuits
H.Informational References
I. Cross-Reference Table
J. Index
![Page 4: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/4.jpg)
9/22/2017
4
Advancing the Science of Safety
NFPA 72 – 2013 Organization
Administrative
Chapters
1 - 9
Support
Chapters
10 - 19
System
Chapters
20 - 29
Usability
Annexes
A - I
1. Administration
2. Referenced Publications
3. Definitions
4. Reserved
5. Reserved
6. Reserved
7. Documentation
8. Reserved
9. Reserved
10.Fundamentals
11.Reserved
12.Circuits and Pathways
13.Reserved
14.Inspection, Testing, and
Maintenance
15.Reserved
16.Reserved
17.Initiating Devices
18.Notification Appliances
19.Reserved
20.Reserved
21.Emergency Control
Functions and
Interfaces
22.Reserved
23.Protected Premises Fire
Alarm Systems
24.Emergency
Communications
Systems
25.Reserved
26.Supervising Station
Alarm Systems
27.Public Emergency
Alarm Reporting
28.Reserved
29.Single- and Multiple-
Station Alarms and
Household Fire Alarm
Systems
A. Explanatory Material
B. Engineering Guide
for Automatic Fire
Detector Spacing
C. System Performance
and Design Guide
D. Speech Intelligibility
E. Sample Ordinance
Adopting NFPA 72
F. Wiring Diagrams and
Guide for Testing Fire
Alarm Circuits
G. Informational
References
Index
Advancing the Science of Safety
Accessible – four versions
Communications Cloud
Deficiency
ECS Emergency Command Center
Fire Command Center
Emergency Control Function
Interface
Impairment
Manufacturer’s Published
Instructions
Occupiable
Occupiable Area
System Designer
System Installer
Chapter 3 – New Definitions
Advancing the Science of Safety
Chapter 3 - Definitions
3.3.1 Accessible
3.3.4 Accessible Spaces
There are several new definitions relating to accessibility including
Accessible as applied to equipment
Accessible as applied to wiring methods
Readily accessible as applied to installation
Accessible spaces as applied to detection coverage
![Page 5: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/5.jpg)
9/22/2017
5
Advancing the Science of Safety
Chapter 3 - Definitions
3.3.57 Condition
3.3.244 Response
New concept for process of signals.
Definitions Used
in Chapter 10
Advancing the Science of Safety
Chapter 3 - Definitions
3.3.91 Emergency Control Functions
3.3.137.1.2 Emergency Control Function Interface
Change in terminology – this
definition used to be known as
“FIRE CONTROL or SAFETY
FUNCTIONS”
Advancing the Science of Safety
Chapter 3 - Definitions
3.3.102.2.1 Dedicated Function FACU
3.3.105.4.2 Dedicated Function FAS
Dedicated function fire alarm systems
and dedicated fire alarm control units
are used when fire alarm systems are
not required but there is a need for a
fire alarm control panel for other code-
required functions.
![Page 6: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/6.jpg)
9/22/2017
6
Advancing the Science of Safety
Chapter 3 - Definitions
3.3.257 SignalThis definition was expanded to include a
number of different kinds of signals:
Alarm
Carbon Monoxide Alarm
Delinquency
Evacuation
Fire Alarm
Guard’s Tour Supervisory
Pre-Alarm
Restoration
Supervisory
Trouble
Advancing the Science of Safety
Chapter 3 - Definitions
3.3.307 Unwanted Alarm New definition with several types
of “unwanted alarms”
Malicious
Nuisance
Unintentional
Unknown
Advancing the Science of Safety
Chapter 7 – Documentation
Structure:
![Page 7: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/7.jpg)
9/22/2017
7
Advancing the Science of Safety
Chapter 7 - Documentation
Applies to new systems
� Design
� Acceptance
� Completion
Applies to existing systems
� Alterations
� Maintenance
� Testing
Does NOT apply to Single Station, Multiple Station and
Household Systems
Advancing the Science of Safety
Chapter 7 – Documentation
Minimum Requirements
Written Narrative
Riser Diagram
Floor Plan
Sequence of operation (matrix or narrative)
Equipment technical data sheets
Manufacturers published instructions
Identification of the person responsible for the
design or layout
Advancing the Science of Safety
Chapter 7 – Documentation
Minimum Requirements
Battery calculations
Voltage drop calculations for NACs
Completed record of inspection and testing
Completed record of completion
A copy of site specific software
Record (as-built) drawings
Use of NFPA 170 symbols or others acceptable to
the AHJ
![Page 8: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/8.jpg)
9/22/2017
8
Advancing the Science of Safety
Design Documentation
Fire Alarm Design Must Include:
• Ambient noise and audible design sound pressure levels (7.3.4.3)
• Documentation of acoustically distinguishable spaces (ADS) (7.3.4.5)
• Designation of spaces to have visual notification (7.3.4.6)
• Extensive ECS design document requirements (7.3.6)
Advancing the Science of Safety
7.7.2 Document Accessibility
With every new system, a documentation cabinet shall be installed at the system control unit or at another approved location at the protected premises
All record documentation shall be stored in the documentation cabinet
Where this documentation cabinet is not in the same location as the system control unit, its location shall be identified at the system control unit
The documentation cabinet shall be prominently
labeled SYSTEM RECORD DOCUMENTS
The contents of the cabinet shall be accessible by
authorized personnel only.
Advancing the Science of Safety
Chapter 7 – Documentation Forms
www.nfpa.org/72forms
![Page 9: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/9.jpg)
9/22/2017
9
Advancing the Science of Safety
Chapter 10 - Fundamentals
Changes to circuit breaker
identification
FIRE ALARM
EMERGENCY COMMUNICATIONS
FIRE ALARM/ECS
10.6.5.2.2 Circuit Identification
Advancing the Science of Safety
Chapter 10 - Fundamentals
Requires circuit breaker lock under all
circumstances
10.6.5.4 Circuit Breaker Lock
NO, THE PADLOCK
IS NOT
REQUIRED!
Advancing the Science of Safety
Chapter 10 - Qualifications
All qualification requirements moved to Chapter 10
� System Designer
� System Installer
� Inspection Personnel
� Testing Personnel
� Service Personnel
� Programming
� Supervising Station Operators
![Page 10: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/10.jpg)
9/22/2017
10
Advancing the Science of Safety
Chapter 10 - Signal Priority
Signal Priority
� Carbon monoxide signals shall be permitted to take
precedence over supervisory and trouble signals.
� Pre-alarm signals shall take precedence over supervisory
and trouble signals.
Advancing the Science of Safety
Chapter 10 - Fundamentals
All required annunciation means
shall be located as required by
the AHJ to facilitate an efficient
response to the situation.
10.18.3.2 Annunciator
Location
Advancing the Science of Safety
Chapter 10 - Fundamentals
For the purpose of reporting, alarm
signals that are not the result of
hazardous conditions shall be
classified as Unwanted and sub
classified as one of the following:
Malicious
Nuisance
Unintentional
Unknown
10.22 Unwanted Alarm Reporting
![Page 11: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/11.jpg)
9/22/2017
11
Advancing the Science of Safety
Chapter 12 – Circuits and Pathways
All power-limited and non-power-limited circuits which enter or
exit are now required to have transient protection (12.2.4.2)
Advancing the Science of Safety
Chapter 12 – Circuits and Pathways
12.3 Pathway Class
Designation
In 2013 there is more clarification
for performance of Class A, Class
B, and Class X Pathways.
Also added updates to 12.3.7 on
Class A and X physical separation.
Credit: NFPA 72©-2013, Annex F
Advancing the Science of Safety
Chapter 12
12.5 Shared Pathway
Designations
Shared Pathways:
Level 0
Level 1
Level 2
Level 3
![Page 12: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/12.jpg)
9/22/2017
12
Advancing the Science of Safety
Shared Pathways
Level 0 – Level 0 pathways shall not be required to segregate or prioritize life safety data from non life safety data.
Level 1 – Level 1 pathways shall not be required to segregate life safety data from non life safety data but shall prioritize life safety data from non life safety data
Level 2 – Level 2 pathways shall segregate all life safety data from non life safety data
Level 3 – Level 3 pathways shall use equipment that is dedicated to the life safety system.
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
14.2.1 Purpose
• Initial and reacceptance inspections
• Initial and reacceptance tests
• Periodic inspections
• Periodic tests
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
14.2.2.2 Impairments/Deficiencies
� System deficiencies shall be corrected
� If not corrected at the time of the conclusion of ITM, owner shall be
notified within 24 hours in writing.
![Page 13: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/13.jpg)
9/22/2017
13
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
14.2.3.2 Delegation of Responsibility
� Property owner shall be able to delegate authority and responsibility to
the occupant
� Requires written lease, use agreement, or management contract!
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
14.2.10 Test Plan
� A test plan shall be written to clearly establish the scope of the testing
for the system.
� The test plan and results shall be documented in the testing records.
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
Format of Visual Inspection Table 14.3.1
� Combined Frequency with Method
� Expanded method details
![Page 14: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/14.jpg)
9/22/2017
14
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
Format of Testing Table 14.4.3.2
� Combined Frequency with Method
� Expanded method details
Advancing the Science of Safety
Chapter 14 – Inspection, Testing, and Maintenance
14.4.11 Voice Intelligibility
� Follow requirements of Chapter 18
� Intelligibility shall not be required to be determined through
quantitative measurements
� Quantitative measurements (Annex D) shall be permitted but not
required
Advancing the Science of Safety
New Text Added – Section 17.1.2
� Chapter 17 does not require detectors!
� Detectors are only required by other:
� Governing laws, regulations
� Codes
� Standards
� Another Section of NFPA 72
Examples
� NFPA 101, IBC
� NFPA 72 Section 10.4 (detector at the FACU)
Chapter 17 – Initiating Device
![Page 15: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/15.jpg)
9/22/2017
15
Advancing the Science of Safety
Chapter 17 – Initiating Device
Initiating devices shall be installed in a manner that provides accessibility for periodic inspection, testing and maintenance.
“Accessible Spaces”:
• Spaces or concealed areas of construction
• Space that can be entered via panel, door hatches, ceiling tiles
• Applies only for the purpose of determining extent of detector coverage, relevant when “Total Coverage” used
17.4.4 Accessible installation
required
Advancing the Science of Safety
Initiating Devices – Total Coverage
Section 17.5.3
• Detection in all places practical and that may present
combustible materials
• Spaces that can be accessed by doors, panels, ceiling tiles
• Recognizes conditions where it is not practical to install
detectors
• Recognizes where air movement is useful for detection
schemes
• Considers special conditions related to smoke detection and
smoke compartments
Advancing the Science of Safety
Total Coverage – Scenario 1
Combustible concealed space
Ceiling Line
Concealed
Space must
be made
accessible for
inspection
and
maintaining
of detectors
NOTE: combustible blind spaces meeting
17.5.3.1.2 DO NOT require detectors
Detector
( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)
![Page 16: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/16.jpg)
9/22/2017
16
Advancing the Science of Safety
Total Coverage – Scenario 2
Non-Combustible concealed space – No detectors required
Ceiling Line – Hard ceiling, no access
NOTE: combustible blind spaces meeting
17.5.3.1.2 DO NOT require detectors
Air Return
Detector
( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)
Advancing the Science of Safety
Total Coverage – Scenario 3
Non-Combustible concealed space
Ceiling Line – Accessible suspended ceiling
Because ceiling is accessible detectors are required above ceiling
Air Return
Detector
( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)
Advancing the Science of Safety
Total Coverage – Scenario 4
NFPA 90A compliant space – air return plenum
Ceiling Line – Accessible suspended ceiling
With duct detector in air return system plenum detectors are not required above ceiling
Air Return
Air returns to plenum Air returns to plenum
Detector
( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)
![Page 17: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/17.jpg)
9/22/2017
17
Advancing the Science of Safety
Total Coverage – Scenario 5, in Context of
17.7.5.4.2.2 & Smoke Compartments
Ceiling Line – may or may not be accessible
Evaluate space by Scenarios 1,2,3 (See 17.5.3.1) to determine if detectors needed above ceiling
Air Return
Air returns to duct Air returns to duct
Smoke
Detector
With Total Coverage Provided, then in context of
17.7.5.4.2.2 the air return duct detector can be
omitted if the Total Coverage detectors activate –
doors, dampers , etc.
( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)
Advancing the Science of Safety
Total Coverage – Scenario 6, in Context of
17.7.5.4.2.2 & Smoke Compartments
Ceiling Line – may or may not be accessible
Air Return
Evaluate space by Scenarios 1,2,3 (See 17.5.3.1) to determine if detectors needed above ceiling
With Total Coverage Provided, then in context of
17.7.5.4.2.2 the air return duct detector can be
omitted if the Total Coverage detectors activate –
doors, dampers , etc.
Smoke
Detector
( Source: Aon Fire Protection Engineering / Jensen Hughes Inc.)
Air returns to plenum Air returns to plenum
Advancing the Science of Safety
Chapter 17
Modified requirements for labeling of
remote indicators
17.4.8 Remote indicators
![Page 18: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/18.jpg)
9/22/2017
18
Advancing the Science of Safety
Chapter 17
Updated requirements for manual boxes
for fire and non-fire purposes
Comprehensively addresses both:
• Manually-actuated alarm-initiating
devices
• Manual fire alarm boxes
• Listed protective covers allowed over
single- or double-action devices
17.14 Manual Alarm Boxes
Advancing the Science of Safety
Chapter 18 – Notification Appliances
18.4.1.4.1 Designated audible areas
� Designer to designate where audible notification will be installed and
those areas where audible notification isn’t required.
Advancing the Science of Safety
Chapter 18 – Notification Appliances
18.4.1.4.3 Design Sound
Pressure Levels
� Design sound pressure levels
(SPL) SHALL be documented
by the system designer.
� Expected ambient SPL
� Use for acceptance testing
� Documented on submittals for
review and approval
![Page 19: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/19.jpg)
9/22/2017
19
Advancing the Science of Safety
Chapter 18
18.4.2.1 Temporal III used for more than evacuation
� Evacuate
� Relocate
Advancing the Science of Safety
Chapter 18
18.4.5.3 Low Frequency Sounders
� Required for Sleeping Rooms
� System activation
Advancing the Science of Safety
Chapter 18
18.5.5.2 Strobe mounting alternatives
� Low ceilings where 80-96” is not achievable
� Formula to determine rating of strobes when mounted in accordance
with this section
![Page 20: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/20.jpg)
9/22/2017
20
Advancing the Science of Safety
Chapter 18
18.9 Textual and Graphical Visible Appliances
� Section revised to include location (private and public modes),
performance, character and symbol requirements and viewing
distances
Advancing the Science of Safety
Chapter 21 –
Emergency Control Function Interfaces
Title Changed to “Emergency Control Function Interfaces”
� 21.2.4 Interface Devices – Revised Terms
� 21.3.7 Elevator pit sprinklers trigger detection
� 21.5 Fire Service Access Elevators
� 21.6 Occupant Evacuation Elevators
Advancing the Science of Safety
Chapter 21 –
Emergency Control Function Interfaces
21.2.4 Emergency Control Interface
� Revised to clarify terms, removing ‘relay’ and ‘appliance’
![Page 21: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/21.jpg)
9/22/2017
21
Advancing the Science of Safety
Chapter 21
21.3.7 Elevator pit sprinklers trigger detection
� When sprinklers are installed in elevator pits, automatic fire detection
shall be installed to initiate elevator recall.
Advancing the Science of Safety
Chapter 21
21.5 Fire Service Access Elevators
� Conditions for fire service access elevators where provided
Advancing the Science of Safety
Chapter 21
21.6 Occupant Evacuation Elevators
� Conditions for occupant evacuation elevators where installed
![Page 22: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/22.jpg)
9/22/2017
22
Advancing the Science of Safety
Chapter 23 – Protected Premises Fire Alarm Systems
23.6.1 Performance of SLC Requires a loss of no more than
50 addressable devices for a
signaling line circuit.
Courtesy: Canadian Consulting Engineer
Advancing the Science of Safety
Chapter 23
23.8.3.2 Interconnection of Bldg Fire Alarm System to a
Household Panel
Household
Fire
Alarm
System
Building
Fire Alarm
Panel
NAC
IDC or
SLC
Advancing the Science of Safety
Chapter 23
23.8.4.8 Carbon Monoxide Signals
� CO detection activation shall be indicated as carbon monoxide alarm
signals
� Exception allows Supervisory condition where permitted by the
building response plan
![Page 23: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/23.jpg)
9/22/2017
23
Advancing the Science of Safety
Chapter 23
23.8.5.6.3 Monitoring of Sprinkler System Valves
� Requires supervision if a valve is installed in the connection between
a sprinkler system and an initiating device
� Supervised/Monitored by:
�Building Fire Alarm System
�Dedicated Function Fire Alarm System
Courtesy: Potter
Advancing the Science of Safety
Chapter 23
23.8.6.1 Occupant Notification
� Revised to require one or more notification appliances in each
notification zone vs. each floor, so they meet the requirements of
Chapter 18, for public or private mode, as required.
Courtesy: Eaton Cooper Notification
Advancing the Science of Safety
Chapter 23
23.10 Fire Alarm Systems Using Tones
� Requires survivability for fire alarm systems using tones for partial
evacuation and relocation!
![Page 24: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/24.jpg)
9/22/2017
24
Advancing the Science of Safety
Chapter 24 – Emergency Communications Systems
24.3.8 Mass Notification Layers
Layer 1 – means of notification of occupants
by systems installed inside a building
Layer 2 – means of notification of occupants
on the exterior of a building
Layer 3 – means of notification of personnel
through distributed recipient MNS
Layer 4 – means of notification of personnel
by public measures (public broadcast radio,
TV, etc)
Advancing the Science of Safety
Layer 3 - Individual
� Personal Alerting
� SMS Text (Cell Phones)
Messages
� Computer Pop-Ups
� Smartphone Apps
� Email Broadcast (Internet)
� Automated Voice Dialing & Text
Messaging (Reverse 911)
Layer 4 - Public
� Public Alerting
� Sat/AM/FM Radio Broadcasts
� Sat/Off-Air TV Broadcasts
� Location/Coverage Specific
� Locally Relevant Alerting
� Handheld Bullhorns71
Layer 1 - Indoor
� Immediate & Intrusive
� Fire Voice Evacuation (EVACS)
� One-Way Voice (PA)
� Two-Way Voice (RA)
� Visible Notification
� Textual/Digital Signage/Displays
� Code Compliant
Layer 2 - Outdoor
� Sirens, Indoor/Outdoor Loudspeakers
� Wide-Area Outdoor MNS
� High Power Loudspeaker Arrays (HPLSA)
CHAPTER 24 – ECS/MNS LAYERS
Advancing the Science of Safety
Chapter 24
24.3.11 Risk Analysis for MNS
� Specifies risk analysis design requirements for mass notification
systems.
![Page 25: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/25.jpg)
9/22/2017
25
Advancing the Science of Safety
Chapter 24 – Emergency Communications Systems
4.4 One-Way Emergency Communications Systems
• The concept of message templates is now introduced into the Code and requires that the messages be developed for each scenario developed in the emergency response plan
• For all evacuation messages, a tone in accordance with Chapter 18 must be used with 2 cycles before and after the message as a minimum.
• All test messages must clearly state: “This is a Test.”
• 24.4.2.2 Voice Evacuation Messages: In occupancies where sleeping accommodations are provided and the voice message is intended to communicate information to those who could be asleep, a low-frequency tone that complies with 18.4.5 shall be used for the 2 cycles before and after the message.
Advancing the Science of Safety
Chapter 26 – Supervising Station Alarm Systems
26.2.7 Change of Service
� Requires subscribers and AHJs to be notified within 30 days of
change of monitoring service where supervising station changes.
Protected
by
XYZ Alarm
Advancing the Science of Safety
Chapter 26
26.6.3.1.5 Single Path Supervision Interval
26.6.3.1.6 Multiple Path Supervision Intervals
� Single transmission path shall be permitted, and path shall be
supervised at an interval of not more than 60 minutes
� If multiple transmission paths are used, each path shall be supervised
within not more than 6 hours
![Page 26: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/26.jpg)
9/22/2017
26
Advancing the Science of Safety
Chapter 26
26.6.3.1.15 Secondary Power Requirements
� Secondary power capacity for all equipment necessary for the
transmission of O signals located at the protected premises shall
have a secondary power capacity of 24 hours.
Advancing the Science of Safety
Chapter 26
26.6.3.2.1.4 DACT Transmission Channels
� The first transmission means shall be a telephone line (number).
� The second transmission means shall be a one way private radio, two
way RF multiplex radio system, or a performance based transmission
method as specified in 26.6.3.1.
� This means that only one telephone line may be used!
� Each transmission means shall automatically initiate and complete a
test signal transmission sequence to its associated receiver at least
once every 6 hours.
Advancing the Science of Safety
Chapter 29
29.7.3 Resistance to Nuisance Alarms
� Effective 1/1/19, smoke alarms and smoke detection used in
household fire alarm systems shall be listed for resistance to common
nuisance sources.
![Page 27: NATIONAL FIRE ALARM AND CHANGES TO THE 2017_pdfs/A_Electrical_Engineering_Sessio… · 72-2013 and how they interface with the new IBC and NFPA 101. ... fire alarm control panel for](https://reader031.vdocuments.site/reader031/viewer/2022030502/5aae9b187f8b9a6b308c436e/html5/thumbnails/27.jpg)
9/22/2017
27
Advancing the Science of Safety
ContactLarry D. Rietz, SET
+1 303-439-0485
For More Information Visit
jensenhughes.com
QUESTIONS?
79Content is Copyright 2017 © Jensen Hughes, Inc. All Rights Reserved
Wayne Moore
604-242-0081wmoore@jensenhughes
Warwick, RI