fire alarm control panel pinaco fire alarm

12
297mm FIRE ALARM CONTRO L PANEL 1 Zone Model : MPC-101 Pinaco MPC-101 Fire Alarm Control Panel with 1 detection zone is developed from a single-chip microprocessor, to meet the needs for a simple, stand-alone System to cater for small establishment, eg. Shop Units, Houses & Workshops,..etc., providing a Fire Alarm solution where only minimum functions are required. Design for ease in installation and operation, the control functions and programmi ng are enabled through a key switch to prevent unauthorized access. Operation of the Panel is made simple with frontal indications and switches. Design in compliance to EN54 Part 2 Standard. The Panel detection zone can cater up to 20 conventional devices. Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusive even when surface mounted. 210mm FRONT VIEW 90mm SIDE VIEW FEATURES :- Designed to EN54 Part 2 Standard LPCB Approved Fault Output for remote status indication 2 Sounder Output Key Switch Controlled Access Level The electronics components are mounted on the PCBs with the latest surface mount technologies. PCBs within the panel are easily accessible and connected by ribbon cable, with cable entry knockout holes provided for the ease of installation, replacement and mainten ance. Pinaco Fire Alarm

Upload: others

Post on 12-Jun-2022

66 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

29

7m

m

FIRE ALARM CONTROL PANEL

1 Zone Model : MPC-101

Pinaco

MPC-101 Fire Alarm Control Panel with 1 detection zone is developed from a single-chip microprocess or, to meet the needs for a simple, stand-alone System to cater for small establishment, eg. Shop Units, Houses & Workshops,..etc ., providing a Fire Alarm solution where only minimum functions are required. Design for ease in installation and operation, the control functions and programmi ng are enabled through a key switch to prevent unauthorized access. Operation of the Panel is made simple with frontal indications and switches. Design in compliance to EN54 Part 2 Standard. The Panel detection zone can cater up to 20 conventional devices. Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusive even when surface mounted.

210mm

FRONT VIEW

90mm

SIDE VIEW

FEATURES :-

Designed to EN54 Part 2 Standard LPCB Approved Fault Output for remote status indication 2 Sounder Output Key Switch Controlled Access Level

The electronics components are mounted on

the PCBs with the latest surface mount technologies. PCBs within the panel are easily accessible and connected by ribbon cable, with cable entry knockout holes provided for the ease of installation, replacement and mainten

ance.

Pinaco Fire Alarm

Page 2: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

TECHICAL SPECIFICATIONS :- 1. Operating Voltage

Mains Incoming : 230VAC ± 15% @ 50 Hz System : 24VDC ± 15%

2. Detection Circuit Parameters Output Voltage : 20 ~ 28VDC Static Current : 2.4mA ( Based on 20 conventional devices) Resistance for Alarm Activation : 150Ω - 1.5KΩ (nominal 470Ω) End-of-Line Resistor : 4.7KΩ

3. Output Circuit Parameters Sounder : Voltage Output 20~28VDC

Current Output 1A (Total) End-of-Line Resistor 4.7KΩ

4. Fault Output : Voltage-Free Contact Output, Rated 1A @ 24VDC 5. Cabinet Details

Size : 210mm Width x 297mm Height x 90 mm Depth Weight : Approximately 2kg (without standby battery) Recommended Standby Battery Size : 2 x 12V 4AH

6. Operating Environment Temperature : -10 to +40 C Relative Humidity : 95%

Page 3: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

FIRE ALARM PANEL

2 Zone Model : MPC-102

4 Zone Model : MPC-104

Pinaco MPC-102 and MPC-104 Fire Alarm

Control Panel with 2 detection zones are developed from single-chip microprocess or, to meet the needs for a comprehensive and versatile range of Fire Detection & Alarm Systems. Design for ease in installation and operation, the control functions and programming are enables through a key switch to prevent unauthorized access. Operation of the Panel is made simple with frontal indications and switches. Where Main and Sub Panels are networked as a System, the Main Panel is able to monitor the general alarm and fault conditions of every Sub Panels. Facilities are also provided to enable a general alarm to be generated or silenced at the Main or the respective Sub Panels. Design in compliance to EN54 Parts 2 & 4. The Panel also has 8 and 16 detection zones version, with each zone catering up to 20 conventional devices. Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusive even when surface mounted.

FEATURES :-

Designed to EN54 Parts 2 & 4 Standard

LPCB Approved

Fire Alarm Output for remote status

indication

Day / Night Mode selectable

With One-Man test feature

2 Sounder Output The electronics components are mounted on the PCBs by the latest surface mount technologi es. PCBs within the panel are easily accessible and connected by ribbon cable, with cable entry

Key Switch Controlled Access Level

Convenient Slot-in Zone Labeling

knockout holes provided for the ease of installation, replacement and maintenanc e.

Pinaco Fire Alarm

Page 4: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

TODI

SP

LA

YB

OA

RD

PW C O M C O M C O M C O M FLTO U T P U T ZO N EI N P U T 2 O U TPU T 1 1 2 3 4

FILTE R F7/2A

TECHICAL SPECIFICATIONS :-

1. Operating Voltage

Mains Incoming : 230VAC ± 15% @ 50 Hz System : 24VDC ± 15%

2. Detection Circuit Parameters Output Voltage : 20 ~ 28VDC Static Current : 2.4mA ( Based on 20 conventional devices) Resistance for Alarm Activation : 150Ω - 1.5KΩ (nominal 470Ω) End-of-Line Resistor : 4.7KΩ

3. Output Circuit Parameters Sounder : Voltage Output 20~28VDC

Current Output 1A (Total) End-of-Line Resistor 4.7KΩ

Alarm Output : 0.5A @ 24VDC, or NO/NC Voltage Free Contact Fault Output : Voltage-Free Contact Output, Rated 1A @ 24VDC Repeater Signal Output : 10mA Aux Power Output : 0.5A @ 20~28VDC

4. Cabinet Details Size : 380mm Width x 320mm Height x 100 mm Depth Weight : Approximately 6kg (without standby battery)

5. Operating Environment Temperature : 0 to 40 C Relative Humidity : 95%

SOUNDE R FIELD DEVI CE

+ -

AC 230V N E L

-

WIRED SIMILARLY

4.7K

WIRED SIMILARLY

+

EOL VOLT_FREE CONTACT

EA R TH

R EPEA T E R O U T P U T

A U X SU PP L Y

O N 0V D A Y FI R EI SO FLT Z4 Z3 Z2 Z1 - + N O C O M N C

A LA R M

SO U N D ER SO U N D ER D A Y

STA R T M O D E + - + - - + - + - + - + + - + -

+ -

XP1 EMI

PSU

F1 / F3/1A F2/1A 0.5A

BATT

12V 12V

TYPICAL WIRING TERMINATION DIAGRAM

Page 5: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

FIRE ALARM PANEL

8 Zone Model : MPC-108

16 Zone Model : MPC-116

Pinaco MPC-108 & MPC-116 Fire Alarm Control Panel are developed from single-chip microprocess or, to meet the needs for a comprehensive and versatile range of Fire Detection & Alarm Systems. Design for ease in installation and operation, the control functions and programming are enables through a key switch to prevent unauthorized access. Operation of the Panel is made simple with frontal indications and switches. Where Main and Sub Panels are networked as a System, the Main Panel is able to monitor the general alarm and fault conditions of every Sub Panels. Facilities are also provided to enable a general alarm to be generated or silenced at the Main or the respective Sub Panels. Design in compliance to EN54 Parts 2 & 4. The Panel has both 8 and 16 detection zones version, with each zone catering up to 20 conventional devices. Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusiv e even when surface mounted.

FEATURES :-

Designed to EN54 Parts 2 & 4 Standard

LPCB Approved

The electronics components are mounted on the PCBs by the latest surface mount technologi es. PCBs within the panel are easily accessible and connected by ribbon cable, with cable entry knockout holes provided for the ease of installation, replacement and maintenanc e.

Programmable Settings :-

4 Sounder Outputs

1 Alarm Output

1 Fault Output

Alarm Soundings

Alarm / Fault Time Delay Mode

Day / Night Mode

System Test

Provision of Repeater Status Output

Key Switch Controlled Access Level

Convenient Slot-in Zone Labeling

Pinaco Fire Alarm

Page 6: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

TODI

SP

LA

YB

OA

RD

EA R TH PW C O M C O M C O M C O M FLTO U T P U T O N 0V D A Y FI R EI S O F L T Z8 Z7 Z6 Z5 Z4 Z3 Z2 Z1 - + N O C O M N C

SO U N D E R O U TPU T ZO N EI N P U T 4 3 2 1 1 2 3 4 5 6 7 8

+ - + - + - - + - + - + - + - + - + - + - + + - + -

0.5A 0.5A F5/1A

TECHICAL SPECIFICATIONS :- 1. Operating Voltage

Mains Incoming : 220VAC ± 15% @ 50 Hz System : 24VDC ± 15%

2. Detection Circuit Parameters Output Voltage : 20 ~ 28VDC Static Current : 2.4mA ( Based on 20 conventional devices) Resistance for Alarm Activation : 150Ω - 1.5KΩ (nominal 470Ω) End-of-Line Resistor : 4.7KΩ

3. Output Circuit Parameters Sounder : Voltage Output 20~28VDC

Current Output 1A (Total) End-of-Line Resistor 4.7KΩ

Alarm Output : 0.5A @ 24VDC, or NO/NC Voltage Free Contact Fault Output : Voltage-Free Contact Output, Rated 1A @ 24VDC Repeater Signal Output : 10mA Aux Power Output : 0.5A @ 20~28VDC

4. Cabinet Details Size : 380mm Width x 320mm Height x 100 mm Depth Weight : Approximately 6kg (without standby battery)

5. Operating Environment Temperature : 0 to 40 C Relative Humidity : 95%

SOUNDE R OUTP UT

ALARM 4.7K FIELD DEVICE - EOL

OUTP UT - +

REPE AT E R 4K7

+ WIRED SIMILARLY

WIRED SIMILARLY VOLT_FREE

CONTACT

AC 230V

R EPEA T E R O U TPU T

A U X SU U PL Y

A LA R M

SO U N D ER D A Y STA R TE D M O D E

+ - + -

XP1 EMI

FILTER F7/2A

PSU

F1 F6 / / F4/1A F3/1A F2/1A

BATT

12V 12V

TYPICAL WIRING TERMINATION DIAGRAM

Page 7: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

FIRE ALARM PANEL

MP SERIES (MICRO-PROCESSOR BASED)

PINACO MP Series, Fire Alarm Control Panels

have been developed to meet the need for a comprehensive and versatile range of Fire Detection & Alarm Systems.

Design in compliance to BS 5839 PART 4 : 1988 &

Singapore CP10 requirements result in reliability and hence user confidenc e.

Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusive even when surface mounted. Operation of the Panel is made simple with frontal indications and control switches. Where Main and Sub Panels are networked as a System, the Main Panel is able to monitor the general alarm and fault conditions of every Sub Panels. Facilities are also provided to enable a general alarm to be generated, silence or reset at the Main or the respective Sub Panels.

CUSTOM MADE PANELS TO SUIT SPECIAL REQUIREMENTS ARE AVAILABLE UPON REQUEST.

FEATURES

DESIGN IN COMPLIANCE TO: BS EN 5839 PARTS 2 & 4 :1998.

COMPREHENSIVE FAULT MONITORING WITH INDIVIDUAL INDICATIONS

ZONE FAULT MONITORING (OPEN & SHORT CIRCUIT)

PROVISION FOR ZONE ISOLATION AUTOMATIC SCANNING OF ZONES

DURING ALARM OR FAULT SIMULATION TEST

2 MONITORED ALARM SOUNDER OUTPUT (OPEN & SHORT CIRCUIT)

EARTH FAULT MONITORING LAMP TEST.

POWER SUPPLY & CHARGER FAULT MONITORING

BATTERY FAILURE MONITORING ONE MAN TESTING & COMMISSIONING

FACILITY

MICRO PROCESSOR SELF CHECKING

WITH AUTOMATIC RESETING FOLLOWING ANY FAILURE

AUXILLARY RELAY CONTACTS PROVIDED

ELIMINATION OF FALSE ALARM BY THE

PROVISION OF A BRIEF DELAY FOR SIGNAL PROCESSING TO CONFIRM TRUE ALARM STATUS.

LOW POWER CONSUMPTION

Pinaco Fire Alarm

Page 8: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

TECHNICAL SPECIFICATIONS

1. Mains Supply : 240 VAC 100 WATTS 2. System Supply : 24 VDC Nominal

3. Fault Monitoring Features provided for :-

Detection Line Short / Open Circuit & Earth Fault. Mains Failure. Micro Processor Failure. Battery Fuse Blown. Battery Disconnected. Battery Low Voltage. Battery Polarity Inverted. Sounder Output Open / Short Circuit. ( EOL Resist or : 15K Ohm ) Sounder Wrong Polarity . ( Diode IN4001 to be added for non polarise d devices )

4. Output :-

Sounder ( Polarised ) : Dual Output, 24VDC 1 Amp per output Auxiliary Contact : 24V 1 Amp, Voltage Free Repeater LED Signal : 10mA Max.

5. Dectection Lines :-

Capacity per Zone : Max. Loop Resistance 100 Ohms, 2 Wire Current Consumption : Standby 1.5mA , Alarm 16mA Max.. End of Line Resistor : 15K Ohm Loop Resistor for

Switching Type Sensor : 1K Ohm ( Eg. Call Point, Flow Switch, etc...)

6. Panel Quiescent Load :-

8 Zone : 59 mA 16 Zone : 71 mA 24 Zone : 83 mA 32 Zone : 95 mA 40 Zone : 107 mA 48 Zone : 119 mA

Products are manufactured

under Certified ISO 9001 : 2000

Quality Management System

Page 9: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

TYPICAL PANEL FACIAL LAYOUT

1. Zone Indicators

1.1 Alarm LED blink in the event of an ‘Alarm’ in the respective zone.

1.2 Fault LED blink in the event of any Zone wiring breakage or short circuit.

1.3 Fault LED lights up continuously to indicate when zone is isolated.

2. ‘MAINS ON’ Indicator 2.1 Lights up when 230V incoming

supply is healthy.

3. ‘SYSTEM ON’ Indicator

3.1 Lights up when 24VDC supply to the system is healthy.

4. Fault Indicators

4.1 Indicate ‘System’, ‘Alarm Sounder ’, ‘Processor ’, ‘Earth’, ‘Mains’, ‘Charger ’ or ‘Battery Fault.

5. System Test

5.1 ‘Testing System’ LED lights up whenever testing is in progress.

5.2 ‘Simulate Alarm & Fault’ pushbutton to scan through all the Zone ‘Alarm & Fault’ indicators and lighting them up progressively, simulating ‘Alarm & Fault’ condition for every zone.

5.3 ‘Lamp Test’ pushbutton to light up all indicators on panel.

6. Zone Selection 6.1 ‘Zone Disabled’ LED lights up once any zone is isolated or disabled. 6.2 ‘Select Zone’ pushbutton to scan through all the zone during selection.

6.3 ‘Disable & Enable Zone’ pushbutton to disable & enable zone after selecting.

7. User Control 7.1 ‘Evacuate Sound Alarm’ pushbutton to activate Alarm Sounder & Fault buzzer. 7.2 ‘Silence Alarm & Fault Buzzer ’ pushbutton to silence Alarm Sounder

& Fault buzzer. 7.3 ‘Reset System’ pushbutton to reset alarm status to normal condition.

Power / Charger Module

This Module incorporate the

Power & Charger circuitry for

the System. One Unit shall be provided

for each Panel.

I/O Termination Card

This Card provides the

termination for signal to all the

Detectors, Call Points….etc, corresponding to their

respective zone.

Motherboard

This Micro-processor based Board provides

all control of the Alarm Panel. Provides indicating LEDs including general

fault, Zone Alarm and Zone Fault.

Page 10: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

TYPICAL WIRING TERMINATION

PINACO provides solutions from design and installation concepts, to the supply of products and systems….

Systems Design Equipment Supply Installation & Project Management Customers’ Training Maintenance Services

Page 11: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

Fire Alarm Panel Alarm

V5 HyBrid Series

The V5 HyBrid Fire Alarm Panel provides many flexible choices

from basic conventional (non-addressable) panel to advance hard-

wire addressable panel / systems. The basic conventional panels are available from 4 to 136 zones. The design is compact, attractive, user friendly and highly scalable. The panels are built with well proven solid state technology for long term cost effectiveness. Operation and maintenance of the panel are provided with general frontal

indications and colour coded switches. The specific fault indications are mounted behind the front indications. It is able to work with most conventional fire alarm system (panels & devices) thus allowing stage by stage system upgrades and eliminate vendor lock-in problems.

Applications:

V5 HyBrid Fire Alarm Panel is suitable for use in commercial complexes, schools, car parks, hospitals, hotels, warehouses, factories, data centers, condominiums etc

Benefits:

Compatibility : works with many other make of equipment, panels and devices

Flexibility : wide range of auxiliary panels to meet each requirement. e.g.: Fire Extinguishing, Smoke Control, Pre-action etc.

Wide range of detectors : works with all approved makes of conventional detectors

Low maintenance cost : system can be maintained and serviced by fire servicing contractors

Alarm interlocks : general sounder silencing and system resetting for system with multiple panels

System Control Module with AVF Alarm Counter Ease of use : simple one touch operation - easy to learn and reduces

errors

Diagnost ic facilities : informative diagnostic LED indicators for easy identification and rectification of faults

Reliability : system designed with proven solid state detection technology

Local manufacturer support : system designed and supported locally by highly experienced support team

Compliance : BS EN 54 Parts 2 & 4 :1998 and SS CP-10:2005

Approval : PSB Listed (4 to 136 zones) Solid State Technology

Page 12: FIRE ALARM CONTROL PANEL Pinaco Fire Alarm

V5 HyBrid Fire Alarm Panel Features

The V5 HyBrid Fire Alarm Panel provides many flexible, user friendly features that overcome the limitations found in today’s conventional fire alarm systems. Its Performance, Reliability, Versatility and Unique Features greatly improve operational efficiency and productivity. Various upgrade options are available to enhance the fire alarm system such as: Auxiliary Status and Control Module provides addition indicators and control switches to be added to the panel for easy identification and control. The Alarm Verification Feature greatly reduces the disruption caused by unwanted false alarms. The LCD Display Unit automatically records the fire and alarm events with date and time, eliminating inaccurate or missing records due to human errors. Networking facility of the LCD Unit allows up to 32 panels to be networked and monitored from one centralized location. Zone (and device address, if hardwire addressable option is implemented) can be identified from the Main Alarm Panel thus reducing response time. Graphic User Interface guides duty staff to area in alarm in the shortest time possible. The Graphics User Interface also records events with date, time and operator information. The event storage capacity is only limited by the capacity of the hard disk of the PC. Various reports can be generated for post event analysis to help identify the cause and take preventive measures against future disruptions .

Upgrade Options:

Auxiliary Status and Control Module

Provides additional indications Provides additional control switches

Alarm Verification Feature

Reduces false alarms Records the no. of intervention

Displays current status of AVF

HyBrid

LCD Display Unit

Records up to 999 alarm and fire events on site

Indicates panel, date & time of event

Stores events in memory Displays events in other Panels in networked panels

Password protected

Graphic User Interface Centralize remote display, logging and reporting

Displays location map of affected location

History log for alarm management