DWELLING ATTRIBUTES
- Floor Area less than 500sqm
- Standard concrete strip foundation
- No in-floor heating
FLOORS:
- Insulation to be installed around vertical edge of perimeter
- 300mm under finished ground level
- R-value to be 1,0 or more
- as per SANS 204-4.3.2
-by specialist
- No insulation installed under slab
ESTIMATED ENERGY CONSUMPTION
ELECTRICAL INSTALLATION ENDORSED BY SPECIALIST
EXISTING Low Voltage internal/external Light fitting - 14 Watt
NEW Low Voltage internal internal/external Light fitting - 14 Watt
Fluorescent light fitting (2 globes) - 36 Watt
SUBTOTAL: 534 Watt
Estimate Maximum Energy Demand as per SANS10420.
5 W/m² x 424m² = 2120W
Estimate Maximum Annual Energy Demand as per
SANS 10420.
5 W/m².a x 424m² = 2120W (a = 1 year)
Estimate Maximum Annual Energy Consumption:
Assume lights are on from 18:00 - 22:00 each day per year
(4h/day)
52 weeks x 7 days x 4 hours = 1456 hours/year
Lights = 534W or 0,534kW
0,534kW x 1456h.a = 777,5kWh.a
(less than 2120kWh.a)
QTY
24
9
2
House Area(NETT)
Watt/m² (permitted = 5 Watt/m²)
424,0m²
1,25W/m²
NOTE: The use of other light fittings permitted as per owner's approval on condition
that the Watt usage per light fitting does not change.
CONCLUSION: THE DESIGN COMPLIES WITH THE REQUIREMENT OF SANS
10400-XA:2011 FOR ENERGY CONSUMPTION.
ROOF ASSEMBLY THERMAL RESISTIVILY:
METAL ROOF SHEETING
ROOF TO BE ENDORSED BY ENGINEER
According to SANS10400-XA and SANS204 to min. thermal resistivity value is as follows:
To achieve the resistivity of 3,7one of the following is recommended.
Think Pink Aerolite thermal and acoustic ceiling insulation with a min. thickness of 135mm which has an R-value of 3,38.
CONCLUSION:
THE DESIGN COMPLIES WITH SANS 10400-ZA:20011 IF THE ABOVE CONDITION IS MET.
NOTES
Total R-Value is a combination of roof assembly and isolation
R-Value of roof & ceiling material calculated for metal roof
sheets & rhinoboard ceiling
Min. value of added thermal resistivity for required isolation
Climate Zone
4
Direction
UP
Total Required resistivity
R=(m².K/W)
3,7 (min required)
0.4
3.3
METAL ELEV./
SECT
FLOOR PLAN
WALL PLAN
CONCRETE
WALL ELEVATION
GLAZING
TIMBER ELEV./
SECTION
COUNCIL LEGEND
Existing House Ground Floor: 264,0sqm
Existing House 1st Floor: 126,0sqm
TOTAL EXISTING: 390,0sqm
New Additions: 70,0sqm
New Balcony 26,0sqm
TOTAL NEW: 96,0sqm
NEW TOTAL FOOTPRINT 486,0sqm
ERF AREA: 1053,0sqm
Coverage (new only): 9,2%
Total coverage(including existing): 46,1%
Coverage Allowed: 0.5 (50%)
AREAS
CALCULATIONS AS PER SANS10400-XA (4.4.3)
EXTERNAL WALL CALCULATIONS:
PARAMETERS
Occupancy
Climate Zone
Min R-Value
Wall Type
R-Value of Wall type achieved
CONCLUSION
H4 - Dwelling House
4
0,35
Double skin masonry with cavity,
plastered BOTH sides
0,36
Wall type complies with min. R-value
of 0.35 for walls
CALCULATION:
External plasterwork
Brickwork with cavity
Internal plasterwork
TOTAL
Conductivity(W/m.k)
0.6
0.7
0.6
Thickness (mm)
15
230
15
260
Resistivity (m²K/W)
0.03
0.33
0.03
0.39
HOT WATER SYSTEMS
Calculated as per SANS 10252-1:2004
HOT WATER SYSTEMS TO BE ENDORSED BY
SPECIALIST
ACCOMODATION TYPE
ASSUMED HOT WATER CONSUMPTION
NUMBER OF PERSONS
ASSUMED DAILY HOT WATER
CONSUMPTION
ASSUMED ANNUAL HOT WATER
CONSUMPTION
50% OF DAILY HOT WATER
CONSUMPTION
INSULATION REQUIREMENTS
Residential Low Rental 80-115L capital/day
115
4 persons per day
460
163,760kL (based on daily design occupancy/week
230L (to be provided by means other than electrical resistance
less than 80mm
1.0 (as per SANS 204 (4.5.2)
HOT WATER VESSEL
MINIMUM REQUIRED R-VALUE
FOR VESEL/TANK
2.0(additional insulation to manuf.'s may be req.)
CONCLUSION
Dwelling to be provided with 1x 200L Hot solar powered water tank to comply with SANS
10254
Solar Panel to be installed by specialist to comply with SANS 10400
Optionally a hot water pump can be installed by a specialist to comply with SANS 10400.
The design complies with the requirement of SANS 10400-XA:2011 and SANS
10252-1:2004 for hot water calculations, and provides min. 50% alterative power source.
Ground Floor Level:
FENESTRATION CALCULATIONS: New Extensions
Nett Area Glazing
N/A N/A
%
N/A
As per SANS 204:2011 South African National Standard and
SANS 10400-XA:2011. "Buildings with up to 15% fenestration
area to nett floor area per storey comply with the minimum
energy performance requirements. Buildings with a fenestration
area per storey that exceeds 15% shall comply with the
requirements for fenestration in accordance with SANS 204
Total Area of Glazed Elements(Fenestration) allowed as per
NBR:
1st Floor: 15% of 62,2 = 9,33sqm
CONCLUSION:
SANS 204 DOES NOT apply
N E
W
S
45,945m
B
oundary Line
200
1100
97
0
FFL = 10.000
lintel = 12.100
EXIST. DWELLING
EXIST. ROOF
new glass &
timber window
South West Elevation(front)
scale 1:100
lintel = 12.100
FFL = 10.000
EXIST. DWELLING
EXIST. ROOF
new
roof over
North East Elevation(rear)
scale 1:100
re-used timber windows
where applicable
exist. window
removed,
new glass & timber
door
exist.
bedroom 4
exist.
en-suite
exist.
dressing
exist.
lounge
exist.
double
volume
exist.
study
d1-1
d1-3
bath
wc
wh
b's
d1-2
bic
dre
sse
r
New Bedroom 6
New
Study
re-used
window
w2
re-used
window
w1-1
remove exist. window & door,
brick up and make good
d2-1
existing roof space
converted into New Balcony
exist. roof light
exist. roof light
shr
tiling
New
Bathroom 3
re
-u
se
d la
min
ate
d tim
be
r
New
P
assage
carpet
carpet
remove exist. window,
re-use elsewhere, new door
S/Steel & cable balustrade to
be min. 1m high
E
X
I
S
T
I
N
G
D
W
E
L
L
I
N
G
-
1
s
t
S
t
o
r
e
y
3
,0
m
b
u
ild
in
g
lin
e
B
a
th
ro
o
m
3
to
b
e
m
e
c
h
a
n
ic
a
lly
v
e
n
tila
te
d
2
5
litre
s
p
e
r s
e
c
o
n
d
,
o
p
e
ra
te
d
o
n
s
w
itc
h
17,5sqm
20,5sqm
13,0sqm
12
,0
sq
m
ne
w b
ic
skylight
roof over
dre
sse
r
now New
Bedroom 5
carpet
19,0sqm
d1-4
display/bookshelf
w1-2
new
roof over
new glass
& timber
door
display/bookshelf
bic
skylight
roof over
1st Storey Plan
scale 1:100
CURRENT ZONING: Single Residential 1
Building usage: Residential Dwelling
Erf bigger than 650sqm
Building lines: Front/street - 3,5m
Common - 3,0m
plaster & paint
to match existing
plaster & paint
to match existing
1590
11
84
91
6
1100
15
50
55
0
Glass Note as per SABS 1037 & NBR Part N
Area Thickness
0 - 0,75sqm 3mm
- 1,5sqm 4mm
- 2,4sqm 5mm
- 3,2sqm 6mm
SAFETY GLASS IN ALL SLIDING DOORS AND OTHER GLASS DOORS. ALL GLASS
PANELS IN WINDOWS IN EXCESS OM 1SQM OR 500mm & LOWER ABOVE
FINISHED FLOOR LEVEL TO BE SABS APPROVED SAFETY GLASS.
Visible markers at eye level on all glass doors. Frosted/obscured glass fitted in all
bathrooms & toilets.
PRECAST LINTELS ACROSS ALL OPENINGS AND 2100MM ABOVE FLOOR FINISH.
ALL WINDOWS 2100 ABOVE F.F.L. PC LINTELS TO HAVE MIN. 4 COURSES
BRICKWORK WITH BRICKFORCE IN EVERY COURSE OVER ALL OPENINGS NOT
MORE THAN 3,0m
exist.
study
New Bedroom 6
New
Study
New
Bathroom 3
New
P
assage
now New
Bedroom 5
Ceiling Light Point
Wall Light Point - exterior
ELECTRICAL LEGEND
Double Electrical 15A Socket with Hight AFFL
Light Switch 1300 AFFL
Recessed Downlighter
Extractor Fan
TV Connection Point
1st Storey
Electrical Plan
scale 1:100
gutter
& rwdp
gutter
& rwdp
Fa
ll @
3
de
g
EXIST. ROOF
Roof Plan
scale 1:100
230 5415
2028 1590 2028
5645
23
05
25
0
54
80
23
04
00
09
0
NGL
NGL
NGL
39
00
90
49
45
23
0
13
48
5
1100
90 3536
230 4583
304 900 1323 1100 1187
4813
21
70
23
0
24
00
2475
demolish exist.
and make good
for new opening
demolish exist.
and make good
for new door
North West Elevation(side)
scale 1:100
NGL
South East Elevation(side)
scale 1:100
line of roof
behind parapet
@ 3deg
EXIST. GARAGE
gutter
& rwdp
Fall @ 3deg
pa
ra
pe
t w
all w
ith
a
pp
ro
ve
d fla
sh
in
g
parapet wall with approved flashing
parapet wall with approved flashing
2475
18
50
30
0
13
02
6
5380
4618
d2-2
50mm
w/step
50mm
w/step
2000
900
1594
900
900
21
00
900
21
00
new glass
& timber
window
10
00
SIT
E B
OU
ND
AR
Y L
IN
E
plaster & paint
to match existing
FFL = 13.000
FFL = 13.000
FFL = 13.000
10
00
line of roof
behind parapet @ 3deg
EXIST. DWELLING
EXIST. ROOF
EXIST. ROOF
37
20
exist. windowexist. windowexist. window
exist. window
exist. window
exist. window
exist. windowexist. window
10
00
chimney to be extended
(min. 1m above roof level)
chimney to be extended
(min. 1m above roof level)
EXIST. GARAGE
plaster & paint
to match existing
EXIST. ROOF
FFL = 10.000
lintel = 12.100
FFL = 10.000
lintel = 12.100
A
F
F
L
=
1
3
.
0
0
0
FFL = 13.000
FFL = 12.950
24
00
FFL = 10.000
lintel = 12.100
FFL = 13.000
lintel = 15.100
wallplate = 15.400
SIT
E B
OU
ND
AR
Y L
IN
E
SIT
E
BO
UN
DA
RY
LIN
E
ROOF CONSTRUCTION:Metal roofsheeting on 76x50mm
SAP timber purlins @ 950mm centres on pre-manufactured
228x50mm SAP timber rafters Grade 4 @ 760mm centres
with steel hoop-irons built in min. 3
brick courses into wall on 114x38mm SAP timber
wallplate. Roofpitch=3°
CEILING CONSTRUCTION:
6,5mm Rhinoboard fixed to
38x38mm SAP
battens @ 400mm centre fixed
to underside of trusses with cove
cornice detail to match existing
with 135mm thk Think Pink
Aerolite ceiling insulation
FLOOR CONSTRUCTION:
Specified and approved floor finish on
25mm sand cement screed on 200mm
Reinforced concrete slab.
New
Bathroom 3
now New
Bedroom 5
exist.
study
Section A-A
scale 1:100
exist.
study
exist.
garage
New
P
assage
NOTE: EXIST. ROOF
TO BE MODIFIED
TO ACCOMODATE
NEW ROOF
& PARAPET
10
00
WINDOWS & DOORS
WINDOWS: QTY
W1 = 1590w x 1184h mm Glass & Timber window Swartland SB3FSP x1
W2 = 1100w x 1550h mm Glass & Timber Sliding window(re-used) x1
gutter
& rwdp
DOORS:
D1 = 813w x 2032h mm flush panel door with timber frame x4
D2 = 813w x 2032h mm Glass & Timber door x2
1st Floor Level: 62,2sqm 9,12sqm 14,6%
gutter
& rwdp
gutter
& rwdp
gutter
& rwdp
n
e
w
1
1
0
d
ia
u
P
V
C
so
ilp
ip
e
@
1
:6
0
fa
ll
1590
11
84
91
6
hardwood timber decking to fall
existing roof space
converted into New Balcony
23
10
FFL = 13.000
lintel = 15.100
wallplate = 15.400
lintel = 15.100
wallplate = 15.400
lintel = 15.100
wallplate = 15.400
parapet = 16.200
parapet = 16.200
parapet = 16.200
parapet = 16.200
existing
RC slab
FFL = 10.000
FFL = 13.000
lintel = 15.100
now New
Bedroom 5
exist.
study
Section B-B
scale 1:100
exist.
dining room
exist.
kitchen
New
P
assage
exist. roof light
dpc
dpc
dpc
gutter
& rwdp
24
00
NGL
wallplate = 15.400
ROOF CONSTRUCTION:Metal roofsheeting on 76x50mm
SAP timber purlins @ 950mm centres on pre-manufactured
114x38mm SAP timber rafters Grade 4 @ 760mm centres
with steel hoop-irons built in min. 3
brick courses into wall on 114x38mm SAP timber
wallplate. Roofpitch=3°
NOTE: EXIST. ROOF
TO BE MODIFIED
TO ACCOMODATE
NEW ROOF
& PARAPET
A
10
00
wallplate = 15.400
ss/vv
110dia FS drop to
level below
200x200 GMS angle
fixed to existing wall
& floor with chemical
anchors
FLOOR CONSTRUCTION: 22x112mm T & G
Hardwood flooring nailed to 152x50mm
Hardwood timber beams(timber grade 7) @ max.
450mm centres, built into walls and secured with
steel hoop irons. Timber beam ends to be
wrapped in approved waterproofing membrane.
All timber built into masonry shall be coated with
carbolineum or a similar preservative
FFL = 13.000
FFL = 13.000
EXIST. ROOF
exist.
study
exist.
entrance hall
exist.
bedroom 1
exist.
bedroom 2
exist.
bedroom 3
exist.
bathroom 1
exist.
bathroom 2
E
X
I
S
T
I
N
G
D
W
E
L
L
I
N
G
-
G
r
o
u
n
d
S
t
o
r
e
y
exist.
porch
exist.
dining room
exist.
kitchen
exist.
covered patio
exist.
garage
exist.
scullery
exist.
wc
exist.
tv room
exist.
guest bedroom
exist.
en-suite 2
10 S
ER
PE
NT
INE
RO
AD
N E
W
S
45,945m
B
oundary Line
17,425m
B
oundary Lin
e
21,029m
B
oundary Lin
e
45,153m
B
oundary Line
7,635m Boundary Line
Erf 2
77
1053sqm
3,0m
B
uildin
g Lin
e
3,0m
B
uilding Line
3
,0
m
B
u
ild
in
g
L
in
e
3,5m
B
uildin
g Lin
e
EXIST IC
EXIST IC
EXIST IC
exist.
swimming pool
exist. window exist. window
exist. windows & door
exist. window
exist. window
exist. w
in
do
w
exist. window
exist. window exist. window
a
d
jo
in
in
g
e
rf 2
7
6
adjoining erf 279
adjo
inin
g e
rf 4143
adjo
inin
g e
rf 275
F
F
L
=
1
0
.
0
0
0
EXIST.
Driveway
Site/Ground Storey Plan
scale 1:150
exist. 160dia uP
VC
soilpipe
@
1:60 fall
exis
t. 160dia
uP
V
C
soilpip
e
@
1:60 fall
e
xist. 1
6
0
d
ia
u
P
V
C
so
ilp
ip
e
@
1
:6
0
fa
ll
110dia FS drop from
level above
Depth: 550mm
Cover Level: 9.850
Invert level: 9.300
Depth: 670mm
Cover Level: 9.850
Invert level: 9.180
Depth: 900mm
Cover Level: 9.850
Invert level: 8.950
Depth: 550mm
Cover Level: 9.850
Invert level: 9.300
Depth: 660mm
Cover Level: 9.190
Invert level: 9.300
E
X
IS
TIN
G
T
R
E
E
S
EX
IS
TIN
G
T
RE
ES
EX
IS
TIN
G
T
RE
ES
EX
IST
ING
TR
EE
S
Burnt clay or sand/cement bricks only shall be used, unless specific
approval is obtained from the Architect for the use of an alternative
type of brick.
Quality of all materials and workmanship to comply with the
relevant
Local Building Regulations, By-Laws and relevant specifications and
shall conform to the minimum standards specified in the Standard
Preambles in the Bills of Quantities or, in the absence of a Bill of
Quantities, available for persual at the offices of the Architects .
Contractor is responsible for correct setting out of the buildings, all
external and all internal walls with particular reference to
boundaries, building lines, etc.
Contractors to verify all levels, heights and dimensionson Site and
to check same against the drawings before putting any work in
hand.
All Contractors to check the details shown on this drawing for
compliance with standards of good building practice with particular
reference to special requirments necessitated by local and-or on
site conditions and to report any comment to the Architects.
Contractors are to ensure that all details shown on this drawing are
in complience with Local Authority bye-law and regulations.
Contractors are to locate and identify existing services on Site and
to protect these from damage throughout the duration of the
works.
Any errors, discrepancies or omissions to be reported to the
Architect immediately.
Contractor is to build in approved D.P.C.'s, whether or not these are
shown on drawings, to all external walls at each floor, beam or
parapet level and to all windows, doors, grilles or other openings in
external walls. Cavity walls to have stepped D.P.C.'s.
Any queries arising from all the above must be reported to the
Architects for clarification before any work is put in hand.
This drawing is not to be scaled. Figured dimensions to be used at
all times.
Provide in non-ventilated rooms extractor fan (25 litres per second)
ducted to exterior, operated by light switch.
Glazing to doors and windows in excess of 1 sqm or less that
300mm above FFL to be safety glazed in accordance with N.B.R.
part N.
Tie cavity wall together with 2,5 wire ties per square metre.
Damp-proof membrane is to be 150mm minimum above FGL.
Light areas : 10% of floor area (natural light), 5% ventilated.
All plumbing and drainage work and installation of sanitary fittings
to comply with the relevant Local Authority bye-laws, regulations
and requirments.
Provide inspection (rodding) eyes to all bends, junctions or every
15m with suitable markers at ground level
Minimum fall to all drainage pipes to be 1:60.
Provide approved reseal traps to all waste fittings.
Provide vent caps and-or vent valves to all stacks.
Inspection eyes to waste pipes to be fully accessible at all times.
All soil pipes passing under buildings, footings or traffic areas to be
encased in concreteof minimum 150mm thickness all round pipe.
SANS 10400 NOTES:
All new walls to be constructed in accordance with Part K of
SANS 10400
All new concr. foundations to be built in accordance with Part H of
SANS 10400 (no portion of footing to project beyond property
boundary)
All new floors to be constructed in accordance with Part J of
SANS 10400
All new roofs to be constructed in accordance with Part L of SANS
10400
Glazing to doors & windows to be safety glazing in accordance
with Part N SANS 10400
Drainage to be constructed (and protected where to be constructed
under any structure) in accordance with Part P of SANS 10400
DRAWN
DATE
SCALE
PROJECT DESCRIPTION:
PROJECT
NUMBER:
DRAWING:
PURPOSE OF ISSUE:
REV
CHECKED
brynn van zyl
PROPOSED ALTERATIONS TO EXISTING
HOUSE ON ERF 277, 10 SERPENTINE
ROAD, PINELANDS, WESTERN CAPE
CLIENT:
SITE/FLOOR PLANS, ELEVATIONS,
SECTIONS, SANS CALCULATIONS
24.08.2018
as shown @ A1
DRAWING
BRYNN
BRYNN
2018-018/001
professional architectural technologist
SACAP Reg. NO: PAT20763
physical address:
26 aroma park village
welgelee street
vredekloof, brackenfell
7560
cell: (+27) 078 263 7777
e-mail: [email protected]
0
SIGNATURES:
FOR COUNCIL APPROVAL
DESIGNER: CLIENT:
COUNCIL STAMP(S) HERE