murdoch university school of engineering and information ...active and passive filters, distribution...
TRANSCRIPT
Thesis Project: Power Quality Analysis at Murdoch University
ENG470: Engineering Honours Thesis
School of Engineering and Information Technology
Murdoch University
Written By: Abdullah Abdullah
Academic Supervisor: Dr. Ali Arefi
Unit Coordinators:
1. Prof. Parisa Bahri
2. Dr. Gareth Lee
A thesis submitted to the School of Engineering and Information Technology,
Murdoch University to fulfil the requirements for the degree of:
H1264: Bachelor of Engineering Honours [BE(Hons)]
1. Electrical Power Engineering
2. Renewable Energy Engineering
Date: 02/07/2018
Author’s Declaration
I, Abdullah Abdullah, do hereby declare that this thesis is an original work and in its entirety
is a product of my own efforts and commitment to the research of power quality analysis at
Murdoch University. This report signifies the final component of the mandatory requirements
for the achievement of a Bachelor’s Degree in Engineering (Honours) majoring in Electrical
Power and Renewable Energy Engineering. To the best of my ability, I have ensured that all
relevant sources which have contributed to the ideas within this thesis be it directly or
indirectly, have been credited and suitably acknowledged.
Name: . . . . . . . . . . . . . . . . . . . . . . . . . .
Date: . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature: . . . . . . . . . . . . . . . . . . . . . . .
Power Quality Analysis at Murdoch University
iii
Abstract
Introduction of new electronic technologies that are more sensitive to disturbances in the
power network has made it necessary to monitor the quality of power supplied. This project
presents a study of the power quality at Murdoch University, and aims at identifying the
causes of poor power quality and provide the solutions to these power quality problems. The
main objective of this project is to analyse the power quality of the electricity system of
Murdoch University in order to identify the causes of poor power quality and provide
solutions to improve the power quality. Furthermore, for all the specific goals that had been
set before the commencement of this project have all been accomplished. The most common
power quality issues in most electrical networks globally include voltage sags, voltage swells,
voltage transients, and frequency harmonics. Other power quality issues that can be
experienced include voltage flicker, voltage unbalance, inter-harmonics, brownouts, direct
current, short-term and long-term power interruption. A discussion of all these issues has
been conducted in this report with their impacts on equipment in the network identified to
be wear and tear, overheating, tripping of circuit breakers, and improper functioning of
equipment. The compensating devices that can be used for improving power quality such as
Active and Passive filters, Distribution Static Compensator, Dynamic Voltage Restorer, and
Unified Power Quality Conditioner have also been analysed in this report. The direct and
indirect costs of power quality have been reviewed in this project with the finding that 50 %
of the global turnover of the electricity sector equating to 500 billion Euros is lost annually
due to poor power quality. IEEE 519, AS/NZS 61000.3.2.2003, ANSI C84.1, IEEE 1459, EN
50160, and IEC 61000 are some of the power quality standards that have been discussed in
Power Quality Analysis at Murdoch University
iv
this project. Based on the data collected from Murdoch University, particularly from 1.330, in
substation 12, South Street Building 330, chancellery. Subsequently, the power quality
problems experienced at the institution include voltage unbalance of 0.295 or 0.3486 % based
on NEMA and IEC formula respectively, a 42.26 % current unbalance, distortions in current
angle, power factor, and harmonic distortion in the range of 1.8 to 2.8 %.
Power Quality Analysis at Murdoch University
v
Acknowledgements
This report could not have been conceived without the wise guidance and caring support of
those around me. It is here that I would like to express my deepest gratitude for their
unwavering and much needed support throughout the course of my education at Murdoch
University.
First of all, I would like to thank my supervisor Dr. Ali Arefi for his help in this project, through
his constant guidance and by sharing his expertise in Electrical Power Systems. Not only has
it been a pleasure to work with Dr. Ali Arefi, but his experience in Electrical Engineering was
invaluable to me as to improve as an Electrical Power Engineer. Moreover, his outstanding
work ethic, remarkable integrity, and the care he showed to me as his student encouraged
me to do my best in developing this project. It has been an honour Dr. Ali Arefi.
Secondly, I would like to extend my gratitude and love to my family and friends, who have
consistently pushed and supported me throughout my education. This would not have been
possible without them. Furthermore, I would like to thank the Government of Kuwait and
specifically the Ministry of Higher Education for believing in me and for sponsoring me with
this scholarship.
Last but certainly not least, I would like to thank all of the academic staff at Murdoch
University. In particular Prof. Parisa Bahri, Dr. Gareth Lee, Dr. Martina Calais, A/Prof. Graeme
Cole, Dr. David Parlevliet, Dr. Gregory Crebbin, Dr. Jonathan Whale, Dr. Farhad Shahnia, Dr.
Xiangpeng Gao, Dr. Manickam Minakshi, Dr. Linh Vu, and Dr. GM Shafiullah.
Power Quality Analysis at Murdoch University
vi
Table of Contents
Author’s Declaration ....................................................................................................................
Abstract ..................................................................................................................................... iii
Acknowledgements .................................................................................................................... v
List of Figures ............................................................................................................................. x
List of Tables ............................................................................................................................ xii
List of Abbreviations and Acronyms ....................................................................................... xiii
Chapter 1: Introduction ............................................................................................................. 1
1.1 Background Information about Power Quality ........................................................... 1
1.2 Aims and Objectives .................................................................................................... 3
1.3 Significance of the Project ........................................................................................... 3
1.3.1 Significance to Power Consumers ............................................................................. 3
1.3.2 Significance to the Electric Utility ............................................................................. 4
1.4 Thesis Project Outline ...................................................................................................... 5
Chapter 2: Literature Review ..................................................................................................... 6
2.1 Introduction into Power................................................................................................... 6
2.2 Power Quality Problems ................................................................................................ 10
2.2.1 Voltage Sags ............................................................................................................ 11
2.2.2 Voltage Swells ......................................................................................................... 12
Power Quality Analysis at Murdoch University
vii
2.2.3 Voltage Flicker ......................................................................................................... 13
2.2.4 Voltage Unbalance .................................................................................................. 15
2.2.5 Voltage Transients .................................................................................................. 16
2.2.6 Voltage Notching .................................................................................................... 17
2.2.7 Brownouts ............................................................................................................... 19
2.2.8 Short Interruptions of Power .................................................................................. 19
2.2.9 Long Interruptions of Power ................................................................................... 19
2.2.10 Direct Current ....................................................................................................... 20
2.2.11 Electrical Noise ...................................................................................................... 21
2.2.12 Harmonic Distortion.............................................................................................. 21
2.2.13 Interharmonics ...................................................................................................... 23
2.2.14 Electromagnetic Interference (EMI) ..................................................................... 24
2.3 Power Quality Standards ............................................................................................... 25
2.3.1 IEEE 519 Standard ................................................................................................... 25
2.3.2 IEEE 1459 Standard ................................................................................................. 25
2.3.3 ANSI C84.1 Standard ............................................................................................... 25
2.3.4 EN 50160 Standard ................................................................................................. 26
2.3.5 IEC 61000 Standard ................................................................................................. 26
2.3.6 AS/NZS 61000.3.2:2003 Standard ........................................................................... 27
2.4 Power Quality Monitoring ............................................................................................. 28
Power Quality Analysis at Murdoch University
viii
2.5 Using Compensating Devices to Improve Power Quality Disturbances ........................ 29
2.5.1 Active and Passive Filters ........................................................................................ 29
2.5.2 Distribution Static Compensator (D-STATCOM) ..................................................... 32
2.5.3 Dynamic Voltage Restorer (DVR) ............................................................................ 33
2.5.4 Unified Power Quality Conditioner (UPQC) ............................................................ 34
2.6 Power Quality Case Studies ........................................................................................... 35
2.7 Costs of Power Quality Problems .................................................................................. 38
Chapter 3: Methodology .......................................................................................................... 40
Chapter 4: Results and Discussion of Data Analysis ................................................................ 42
4.1 Voltage Unbalance ......................................................................................................... 42
4.2 Phase Distortion ............................................................................................................. 46
4.3 Harmonic Distortion ....................................................................................................... 47
4.4 Power Factor .................................................................................................................. 48
Chapter 5: Conclusion and Future Work ................................................................................. 57
5.1 Future Work Opportunities for the Power Quality Analysis at Murdoch University .... 59
Reference List ........................................................................................................................... 61
Appendix .................................................................................................................................. 68
Appendix Part A: EM133 Meter Manual .............................................................................. 68
Appendix Part B: Calculation of Apparent Power and Power Factor .................................. 70
Appendix Part C: Calculation of Voltage Unbalance ............................................................ 71
Power Quality Analysis at Murdoch University
ix
Appendix Part D: Risk Assessment ....................................................................................... 72
Power Quality Analysis at Murdoch University
x
List of Figures
Figure 1: Impedance Triangle [36] ............................................................................................. 7
Figure 2: Energy Consumption by Sectors in European Union Countries [12] .......................... 9
Figure 3: Most Common Power Quality Problems [16] ........................................................... 11
Figure 4: Waveform Illustrating Voltage Sags [19] .................................................................. 12
Figure 5: Waveform Showing Voltage Swells [19] ................................................................... 13
Figure 6: Waveform Indicating Voltage Flicker [23] ................................................................ 14
Figure 7: Voltage Unbalance between Three Phases [25] ....................................................... 15
Figure 8: Relationship between Voltage Unbalance and Increase in Temperature [24] ........ 16
Figure 9: Types of Transients [19] ............................................................................................ 17
Figure 10: Voltage Notching [27] ............................................................................................. 18
Figure 11: Direct Current Offset [29] ....................................................................................... 20
Figure 12: Electrical Noise [19] ................................................................................................ 21
Figure 13: Harmonic Distortion [34] ........................................................................................ 23
Figure 14: Passive Low Pass Filter [1] ...................................................................................... 30
Figure 15: High Pass Filter [1] .................................................................................................. 30
Figure 16: Ideal D-STATCOM [20] ............................................................................................ 33
Figure 17: Schematic of a DVR [20].......................................................................................... 33
Figure 18: UPQC Schematic [20] .............................................................................................. 35
Figure 19: System Operation Snapshot [1] .............................................................................. 37
Figure 20: Voltage versus Time for Three Voltage Lines ......................................................... 42
Figure 21: Voltage versus Time Including Average Voltage of the Three Phases ................... 43
Power Quality Analysis at Murdoch University
xi
Figure 22: Percent Voltage Unbalance for all Three Phases against Time of the Day ............ 44
Figure 23: Current Magnitude versus Time ............................................................................. 45
Figure 24: Percent Current Unbalance for all Three Phases against Time of the Day ............ 45
Figure 25: Voltage Angles for the Three Phases Plotted against Time .................................... 46
Figure 26: Current Angles for Three Phases Plotted against Time .......................................... 47
Figure 27: THD for all the Phases ............................................................................................. 48
Figure 28: Power Factor for all Phases .................................................................................... 49
Figure 29: Real Power for all Phases ........................................................................................ 50
Figure 30: Reactive Power for all Phases ................................................................................. 50
Figure 31: Apparent Power for all Phases ............................................................................... 51
Figure 32: Current Demanded by the Load in each Phase ...................................................... 52
Figure 33: Phase to Phase and Phase to Neutral Voltages at Varying Power Factors............. 53
Figure 34: Unbalance Voltage Factor ....................................................................................... 55
Figure 35: EM133 Meter Manual [65] ..................................................................................... 69
Power Quality Analysis at Murdoch University
xii
List of Tables
Table 1: Power Quality Standards ............................................................................................ 27
Table 2: Comparison between Active and Passive filter [43] .................................................. 32
Table 3: Power Data for the Phase A at 12:00:30 am .............................................................. 70
Table 4: Voltage Unbalance Using IEC 61000 Standard........................................................... 71
Power Quality Analysis at Murdoch University
xiii
List of Abbreviations and Acronyms
A Ampere
a Delay Angle
AC Alternating Current
ANSI American National Standard Institute
AS/NZS Australian/New Zealand Standard
ASDs Adjustable Speed Drives
C Capacitor
DC Direct Current
D-STATCOM Distribution Static Compensator
DVR Dynamic Voltage Restorer
EDC Theoretical Direct Voltage
EMI Electromagnetic Interference
EN European Standard
EPRI Electrical Power Research Institute
EX Direct Voltage Drop
fb Fundamental Frequency of the System
GPO General Purpose Outlet
Hz Hertz
IDC Direct Current in Per Unit on a Converter Base
IEC Electromagnetic Compatibility
IEEE Institute of Electrical and Electronic Engineers
Power Quality Analysis at Murdoch University
xiv
Is Current Source
IZ Current and Impedance
kHz Kilohertz
kVA Kilo Volt Ampere
kVA Kilovolt-Ampere
kVAr Kilo Volt Ampere Reactive
kW Kilowatt
L Inductor
NEMA National Electrical Manufacturers Association
NPL National Power Laboratory
P Real Power
PCC Point of Common Coupling
PQ Power Quality
PQM Power Quality Monitoring
PV Photovoltaic
Q Reactive Power
R Resistor
RFI Frequency Interference
RMS Root Mean Square
S Apparent Power
THD Total Harmonic Distortion
u Commutation Angle
UBF Unbalance Factor
Power Quality Analysis at Murdoch University
xv
UPQC Unified Power Quality Conditioner
UPS Uninterruptible Power Supply
V Volt
Vav Average Voltage
Vfrms RMS Voltage of Fundamental Frequency
Vnrms RMS Voltage of the nth Harmonic
Vs Voltage Source
VSC Voltage Source Converter
VSD Variable Speed Drive
VSIs Voltage Source Inverters
Vt Terminal Voltage
Xs System Reactance in Per Unit on a Converter Base
Xt Converter Transformer Reactance in Per Unit on a Converter Base
Power Quality Analysis at Murdoch University
xvi
Power Quality Analysis at Murdoch University
1
Chapter 1: Introduction
1.1 Background Information about Power Quality
According to Institute of Electrical and Electronic Engineers (IEEE), power quality is defined as
the idea of powering and grounding electronic equipment in such a way that it is fit for the
functioning of that equipment and well matched with the wiring system of the premises and
other connected equipment [1]. Grounding refers to a conducting connection through which
electrical equipment have a connection to earth [2].
Power quality can also be defined as the ability of a grid or electrical network to supply clean
stable power that is always available when required by a consumer. The cleanliness of the
power is in terms of the wave shape, which should be pure sinusoidal, noise-free, and within
the allowable tolerances for voltage and frequency [3].
The cost and reliability of any electrical system significantly depend on the supplied and
consumed power quality of the system. The demand for clean and reliable power in the world
has increased in the last several decades due to the introduction of new electronic
technologies [4]. There has been tremendous growth in the use of power electronics in almost
every type of electronic device making them more sensitive to the present disturbances in
the network. In most cases, there has not been an improvement in the quality of designs for
electronic devices to accompany its growth [5]. This has resulted in the distortion of the
distribution network. Therefore, the electronic devices may malfunction during operation
under the distorted distribution networks. For this reason, power quality monitoring and
analysis need to be conducted to predict the occurrence of a disturbance, its causes, and to
Power Quality Analysis at Murdoch University
2
develop a strategy in order to minimize the disturbance with the aim of protecting the devices
connected in the network.
Power quality monitoring (PQM) involves the collection, analysis, and interpretation of raw
power measured data into information that is useful. This process consists of measuring the
currents and voltages of the supply over a specified period and studying their waveforms.
Wiring, grounding, and equipment connections can be inspected throughout power quality
monitoring [6]. PQM is vital to detect potential and present power quality disturbances, which
may damage equipment or decrease their lifespans. Instruments that use monitoring power
quality include:
1) Power quality metre and analyser used for measuring, recording and storing signal
frequency, harmonics, real and apparent power, phase rotation, current, and voltage.
2) Oscilloscope for measuring and displaying harmonics, current, and voltage.
3) Circuit monitor for measuring voltage sag, swell, flicker, and harmonics.
4) Flicker meter for voltage flicker measurement.
5) Disturbance analyser for voltage transients, power outages, and voltage sags
measurement.
6) The in-plant power monitor used for monitoring voltage profile, voltage swells, sags,
flicker, and harmonics in the power system [6].
This project has attempted to perform a power quality analysis at Murdoch University. The
focus of this thesis is to identify the causes of poor power quality at the institution, to quantify
its impacts on equipment and operations and to provide a solution for the improvement of
the quality of power. An extensive study of various literature sources has been conducted to
get background information about power quality, monitoring techniques, disturbances,
Power Quality Analysis at Murdoch University
3
impacts, and mitigation strategies. Data has then been collected from the university and
analysed to determine the power quality issues affecting Murdoch University, and solutions
are introduced based on the literature reviewed. Afterward, the data is further analysed to
improve the power quality at the institution.
1.2 Aims and Objectives
The major objective of this project is to analyse the power quality of the electricity system of
Murdoch University to identify the causes of poor quality and provide possible solutions in
order to improve the power quality. This can be achieved through the following specific
objectives:
1. To identify power quality issues.
2. To investigate causes, effects, and proper ways of improving poor power quality.
3. To study the IEEE STD 519 standard and others power quality standards.
4. To obtain power data from Murdoch University and using it afterward for quality
analysis against the standards.
5. To calculate the power quality parameters based on collected data.
1.3 Significance of the Project
Monitoring, analysis, and mitigation of (PQ) are factors vital to various sections of the
economy as well as several industries. Subsequently, the significance of this project can be
divided into two main parts: to consumers and the electric utility.
1.3.1 Significance to Power Consumers
Through the collection and analysis of power quality data that has been conducted in this
research, the occurrence of recurrent power quality disturbances can be accurately predicted.
Power Quality Analysis at Murdoch University
4
This would be significant to consumers as accurate prediction and mitigation of the
disturbances would result in decreased malfunction of electronic devices connected to the
distribution network.
This project is also substantial to consumers, as it would help to decrease the costs associated
with repairs or replacement of malfunctioned electronic devices in the distribution network.
By providing a solution to the power quality disturbances, the likelihood of occurrence of
these disturbances and their impacts would be minimized significantly. Thus, there would be
fewer malfunctioned consumer devices.
The significance of this project to industrial consumers is in the form of experiencing lower
interruptions during production due to power quality issues. The effect of this is increased
production and reduced losses due to equipment damage. Moreover, this reduces the costs
based on idle personnel during interruptions.
1.3.2 Significance to the Electric Utility
Through this study, the primary power quality disturbance in a distribution network has been
identified. The important source of the disturbance either generation, distribution,
transmission, or consumer that can also be determined. These issues make this research
essential to the electric utility operators, as it would help them understand their network
better.
Power Quality Analysis at Murdoch University
5
1.4 Thesis Project Outline
This dissertation is divided into five chapters which consist of:
Chapter 1 contains the background information on power quality, a brief description
of the research problem and the research focus. Project objectives and significance of
the research are also found in this chapter.
Chapter 2 provides the present literature, the various ideas as well as issues in power
quality analysis. Specifically, it will consider the implementation of compensating
devices to mitigate the effects of power quality disturbances. In addition, the financial
repercussions of power quality problems, along with a multitude of power quality
standards will be examined. Finally, this chapter explores some power quality case
studies.
Chapter 3 describes the methodology of the project. Here the techniques employed in
the research and execution of the project is presented and discussed.
Chapter 4 discusses the data analysis and calculations done to determine the numerous
of power quality problems at the university. Then the results are presented and
reviewed to validate that indeed the power quality problems have been identified
correctly.
Chapter 5 will conclude the project and provide some future work opportunities for
the power quality analysis at Murdoch University.
Power Quality Analysis at Murdoch University
6
Chapter 2: Literature Review
2.1 Introduction into Power
An electric power system is made up of three main parts: a generation system, which is the
source of power; a delivery system made up of the transmission and distribution networks
and the load that can be transport (traction/railroad), residential, commercial, industrial, and
governmental consumers [7].
Electric power defined as the rate of converting electric energy [8] can be generated using
conventional methods such as hydroelectric power generation, thermal generating plants,
synchronous machinery, and distributed machinery. Moreover, electric power can be
generated using nonconventional methods such as photovoltaic (PV) modules, wind
generation, tidal generation, and advanced technologies like fuel cells [9].
In direct current (DC) systems, power is given as the product of current and voltage [8] thus:
Power (Watts) = Voltage (V) × Current (A) (1)
P = V × I
In alternating current (AC) systems, instantaneous power is given as the product of the
instantaneous current, and instantaneous voltage expressed mathematically as [10]:
p (t) = v(t)i(t) =VmIm
2[cos ϕ + cos(2ωt − ϕ)] (2)
Where: ϕ is the phase angle.
The resistor, inductor, and capacitor define the total impedance of an AC circuit, which affects
the current and voltage waveforms and hence their phase difference. In AC circuits, the
impedance of the circuit is defined as the ratio of the current and voltage phasors created by
Power Quality Analysis at Murdoch University
7
a circuit component. Both reactance and resistance make up the total impedance (Z) that
restricts the flow of current around the circuit. The following Figure 1 shows an impedance
triangle, which is used to demonstrate the geometric relationship between reactance,
resistance, and impedance [36]
From the impedance triangle, it is clear that the algebraic sum of the reactive and resistive
ohmic values is not equal to the impedance, as a 900 phase difference exists between a pure
reactance and a pure resistance. As a result, the impedance is a vector sum of the reactance
and the resistance and has both of phase angle (𝜃) and of magnitude (Z). When the frequency
of the AC supply changes, the reactance (X) changes but the resistance remains constant, thus
there will be a change in shape of the impedance triangle. The following relationships hold
between resistance, reactance, and impedance [37].
Z2 = R2 + jX2 (3)
cos θ =R
Z (4)
In AC systems, the average power consumed in a circuit is referred to as real power (also
referred to as active power or true power) and is dependent on the power factor (cosine of
the phase angle). The power supplying stored energy in reactive elements is known as the
Figure 1: Impedance Triangle [36]
Power Quality Analysis at Murdoch University
8
reactive power. As opposed to active power and reactive power, which reduces the power in
the circuit in order to create and reduce both the inductive magnetic fields and capacitive
electrostatic fields thereby decreasing the supply of true power to the load. The power stored
by a capacitors electrostatic field tries to control the voltage while the power stored in the
inductors magnetic field tries to control the current. This result in the generation of reactive
power by capacitors and consumption of the reactive power by inductors. Apparent power is
defined as the product of RMS values of current and voltage across a circuit [10]. These
mathematically are expressed as shown using the following equations 5-7 [11]:
Real Power: P = |V̅||I|̅ cos ϕ (5)
Reactive Power: Q = |V̅||I|̅ sin ϕ (6)
Apparent Power = |S̅| = |V̅||I|̅ = √P2 + Q2 (7)
Power factor defined as the ratio of the active power (P) to the apparent power (S) is an
essential part of an AC circuit [38]. Power factor defines the phase angle between the voltage
and current waveforms and is expressed mathematically as [38]:
Power Factor =P
S=
VI cos θ
VI= cos θ (8)
In a purely resistive circuit, there is zero phase difference between the real and the apparent
power as the voltage and current waveforms are in phase. Accordingly, the power factor will
be unity.
Power Factor = cos(0) = 1 (9)
Unity power factor means that the actual power consumed is equal to the apparent power
consumed. In a purely reactive circuit, the voltage waveform and the current waveform are
90 degrees out of phase. Thus the power factor will be:
Power Quality Analysis at Murdoch University
9
Power Factor = cos(90) = 0 (10)
This means that the wattage consumed is zero, but there is a voltage and current supplying
the reactive load. Lagging power factor refers to an inductive circuit where the current lags
the voltage while a leading power factor refers to a capacitive circuit where the current leads
the voltage. Improving the power factor by decreasing the reactive power component is
therefore important to have efficient use of the power by the load.
Energy consumption is divided into four major sectors as illustrated in Figure 2 below for
European Union countries. From Figure 2, it is indicated that industry accounts for the highest
consumption of electrical power at 36 % followed by households at 31 %, commercial sectors
at 30 %, and finally transport at 3 % [12].
Figure 2: Energy Consumption by Sectors in European Union Countries [12]
Power Quality Analysis at Murdoch University
10
2.2 Power Quality Problems
Power quality issues are caused mainly by the use of sensitive electronic loads such as digital
controllers and computers. Some of these devices have problems due to either their proximity
to other electrical equipment or due to disturbances in the powerline since higher power
loads generate greater disturbances. Examples of devices that create high power loads:
electric variable speed drives, welders, and arc furnaces [1].
Impacts of poor power quality include accelerated tear and wear, overheating, improper
function of electrical and electronic equipment, tripping of circuit breakers, and this
sometimes results in hazardous conditions [13].
A survey by experts in power quality show that about half of all power quality problems are
associated with ground current, ground loops, neutral to ground voltages, ground bonds,
grounding, and other ground related issues [14].
Essential power parameters that affect the quality of power delivered include voltage sags,
voltage swells, voltage flicker, voltage unbalance, voltage transients, voltage notching,
brownouts, short-term and long-term power interruptions, direct current, electrical noise,
harmonic distortion, inter-harmonics, and electromagnetic interference. According to
research conducted by EPRI, power quality problems arising from customers premises
account for 70 % of all disturbances, while the network side accounts for 30 % [15]. From
these parameters, the most common power quality problems among American consumers
were identified as voltage sags, voltage swells, voltage transients caused by capacitor
switching, and harmonics among other related issues [16][17]. Figure 3 demonstrates the
most common power quality problems, and this is discussed below.
Power Quality Analysis at Murdoch University
11
2.2.1 Voltage Sags
Voltage sags, which are also known as voltage dips, define a decrease of the voltage supply
level by 10 -90 % of the normal voltage, over a short duration of time (half a cycle to 1 minute)
[18]. Voltage sags are usually caused by distribution and transmission system faults.
Moreover, faults in installations at the consumer premises, energization of the transformer
and large motors starts, may result in voltage sags [19]. The following Figure 4 represents a
voltage sag.
48%
22%
15%
6%
5%
2%1% 1%
Most Common Power Quality Problems
Voltage sags/swells
Harmonics
Wiring/Grounding
Capacitor Switching
Load Interaction
Other
EMF/EMI
Power Conditioning
Figure 3: Most Common Power Quality Problems [16]
Power Quality Analysis at Murdoch University
12
Voltage sags can result in crashing of data processing systems or computer systems and the
tripping, or malfunctioning of motors. These may lead to loss of production and idle personnel
that are costly to maintain. A UPS (Uninterruptible Power Supply) can be used to prevent the
crashes, however, it will introduce harmonics into the system [20]. A series active power filter
can be used for compensation of voltage sags from the AC supply and is preferred over the
UPS due to its reduced economic costs and lower component ratings [18].
2.2.2 Voltage Swells
This is referred to as a voltage surge and is an increase of the RMS supply voltage within a
short duration of time. Swells in voltage are usually caused by capacitor switching and faulty
operation of tap changing transformer on the load [21]. Figure 5 shows the voltage swells.
Figure 4: Waveform Illustrating Voltage Sags [19]
Power Quality Analysis at Murdoch University
13
Short duration voltage swells may result in computer data being erased, loss of production,
and shortening of lives of home appliances, as well as computers due to the stress it puts on
them. Additionally, it can cause tripping of the protective circuits of a Variable Speed Drive
(VSD). Voltage swells lasting for a long duration cause damage to home appliances [20]. To
mitigate this, surge suppressors are typically used to protect sensitive appliances against
transient voltage surges, while power conditioners can be used to shield equipment from
voltage surges [18].
2.2.3 Voltage Flicker
Voltage flicker or voltage fluctuations refer to rapid short-term changes in voltage levels
caused by sudden variations or switching of the load. The voltage levels increase when the
load decreases, and it similarly decreases when the load increases. Based on their frequency
of occurrence, flicker can be divided into four groups; cyclic flicker, cyclic low frequency,
noncyclic frequent, and noncyclic infrequent. Cyclic flicker is the flicker due to periodic
variations in voltage ranging between 10 every second to 2 every second. Cyclic low frequency
Figure 5: Waveform Showing Voltage Swells [19]
Power Quality Analysis at Murdoch University
14
has voltage variations in the range of 2 every second to 12 every minute. Noncyclic frequent
has voltage variations in the range of 12 every minute to 1 every minute. Noncyclic infrequent
has voltage variations in the range of 1 every minute to 3 every hour [22]. Arc welding
machines, arc furnaces, oscillating loads, reciprocating compressors, pumps, spot welders
both automatic and manual, drop hammers, saws, cranes, hoists, single elevators, and motor
starts are the most common causes of voltage fluctuations [19]. In addition, voltage flicker
decreases the lifespan of electronic equipment, lamps, and adversely affects human health
since it may cause migraines and headaches due to the strain it puts on the eyes. Voltage
stabilizers and motor starters can be used in correction of voltage fluctuations. Figure 6 below
indicates a waveform of voltage flicker.
Figure 6: Waveform Indicating Voltage Flicker [23]
Power Quality Analysis at Murdoch University
15
2.2.4 Voltage Unbalance
Voltage unbalance discusses the ratio of the negative sequence voltage to the positive
sequence voltage. It can also be defined as a condition where there is a difference between
the phase angle displacement and RMS voltage values of two consecutive phases [19]. This
may occur due to unbalanced phase loads in a distribution system, unbalanced customer
loads, or unbalanced network impedances. Voltage unbalance causes an increase in the
temperature of motors and can result in tripping of large motors. Unless the output DC of the
drive rectifier is filtered properly, AC variable speed drives may also be affected by voltage
unbalance. Voltage regulators are the devices used to correct voltage unbalance [18]. For
utility, voltage unbalance can be mitigated by redistribution of loads or by repairing of
malfunctioning equipment. For adjustable speed drives, DC link reactors and AC line reactors
can be used to decrease the effects of voltage unbalance [24]. The following Figure 7 shows
an example of voltage unbalance in the phase.
Figure 7: Voltage Unbalance between Three Phases [25]
Power Quality Analysis at Murdoch University
16
Figure 8 below demonstrates the relationship between the increase in temperature and
voltage unbalance. From Figure 8, it can be seen that temperature rises by approximately
twice the square of the percentage of voltage unbalance [24].
2.2.5 Voltage Transients
This refers to a rapid variation in frequency of the voltage in the steady state condition caused
by lightning or switching operations [26]. As a result, voltage transients are classified into
oscillatory and impulsive transients. Oscillatory transients are caused by capacitor switching,
commutation in power devices and resonant circuits which result in a sudden change of
polarity of the voltage lasting between 10 microseconds and 100 microseconds [18]. On the
other hand, impulsive transients are caused by lightning and last between 1 nanosecond and
1 millisecond [19]. These are illustrated in the following Figure 9.
Figure 8: Relationship between Voltage Unbalance and Increase in Temperature [24]
Power Quality Analysis at Murdoch University
17
Impulsive transients can result in oscillatory transients that may lead to power line insulator
damage as a result of transient overvoltage, caused by the oscillatory transients. Surge
arresters are usually used to suppress the impulsive transients [20].
2.2.6 Voltage Notching
Voltage notching is a repetitive power quality disturbance that occurs during current
commutation from one phase to another during normal working of power electronic devices
such as a rectifier. The difference between notching and harmonics is that notching happens
in steady state. Harmonic analysis starting point is the current waveform, therefore the IZ
drops of harmonic currents can be used for deriving voltage notching. The primary cause of
voltage notching is three phase converters or rectifiers that produce continuous DC. A short
circuit occurs shortly between two phases during the current commutation from one phase
to another [27].
Factors affecting depth of a notch at any point include the point being examined, isolating
inductance between converter/rectifier, and the source inductance. The commutation angle
is the width of the notch determined as [27]:
u = cos−1[cos a − (Xs + Xt)Idc] − a (11)
Figure 9: Types of Transients [19]
Power Quality Analysis at Murdoch University
18
This can be simplified to the following equation:
cos u = 1 − (2Ex
Edc) (12)
Where:
u: is the commutation angle.
𝑎: is the delay angle.
𝐼𝑑𝑐: is the direct current in p.u on a converter base.
𝑋𝑡: is the converter transformer reactance in p.u on a converter base.
𝑋𝑠: is the system reactance in p.u on a converter base.
𝐸𝑑𝑐: is the theoretical direct voltage.
𝐸𝑥: is the direct voltage drop due to commutating reactance.
Voltage notches introduce high non-harmonic and harmonic frequencies in the radio
frequency range that result in negative effects such as overloading electromagnetic
interference filters and other high frequency sensitive capacitive circuits when it is of
sufficient power and introduction of signal interference into communication and logic circuits.
The remedy for voltage notches involves isolating the critical and sensitive equipment from
the rectifiers. Figure 10 below shows a waveform with notches.
Figure 10: Voltage Notching [27]
Power Quality Analysis at Murdoch University
19
2.2.7 Brownouts
A brownout is a constant lower voltage condition caused by the loss of supply to one phase
of a distribution transformer with the two remaining phases maintaining their supply. This
results in low voltages between the phase and neutral of about 100 %, 50 %, and 50 % [28].
This can be corrected by using a voltage stabilizer [18].
2.2.8 Short Interruptions of Power
This refers to an event where there is zero voltage. Such a situation occurs for a short time of
approximately 30 seconds or less. These are caused by the automatic opening and closing of
the protective equipment to isolate a faulty area of the network. The leading causes of fault
in a system are insulator flashover, lightning, improper grounding, and insulation failure.
Short interruptions of power may result in data loss, tripping of protection devices, damage
to data processing equipment, and system crashing and lock up [18].
2.2.9 Long Interruptions of Power
This is a condition lasting for more than two cycles where the voltage is zero. It is also referred
to as a blackout and may be caused by utility power failure, fire, power distribution failure,
human error, storms or objects destroying lines and poles and bad coordination or tripping of
a circuit breaker. Long interruptions of power results in the complete shutdown of systems,
data loss, and loss of control of the systems. It may also lead to damage of electrical
appliances [18]. Generators can be used as power backups for this power quality problem.
Nevertheless, it does not protect the equipment against power failure since the failure
actually occurs before the generator is turned on.
Power Quality Analysis at Murdoch University
20
2.2.10 Direct Current
Equipment at the customer's end that has characteristics of a non-linear load may inject direct
current in the low voltage neutral conductor of the distribution system. Failure of rectifiers
that are commonly used in many AC to DC conversion technologies of modern equipment can
also cause induction of direct current into an AC distribution system. Therefore, this may
result in earthing systems corrosion and the introduction of unwanted current to devices
working at their rated level [28]. Direct current has the effect of causing saturation in the
magnetic circuits of power transformers [18]. Transformer saturation leads to increase of
transformer temperature making the transformer unable to deliver full power to the load and
thus creates instability in electronic load equipment due to waveform distortion. The solution
to direct current is to use modular systems, which are easily replaceable by the user and by
replacing the problem causing equipment that is faulty [29]. Figure 11 below illustrates a
direct current offset.
Figure 11: Direct Current Offset [29]
Power Quality Analysis at Murdoch University
21
2.2.11 Electrical Noise
This refers to a persistent, oscillatory disturbance of the waveform that has a wide frequency
distribution of up to 200 kHz. Electrical noise is usually induced in the network by
electromagnetic fields and can also be caused by improper grounding [21]. The following
Figure 12 indicates the waveform distortion.
2.2.12 Harmonic Distortion
This refers to a frequent distortion of the sine wave pattern of the supply voltage or current
caused by variable speed drives and solid-state rectifiers that are loads with non-linear
characteristics. Furthermore, the waveform is equal to the total of different sine waves having
various phases and magnitudes and with frequencies, which are multiples of power system
frequency. The causes of harmonics include, non-linear loads (power electronics equipment)
such as data processing equipment, ASDs, switched mode power supplies, high-frequency
lighting, DC brush motors, rectifiers, welding machines, arc furnaces, and electric machines
operating above the magnetic saturation point (knee of the magnetization curve) [30]. The
level of harmonic distortion is usually expressed in terms of Total Harmonic Distortion (THD)
Figure 12: Electrical Noise [19]
Power Quality Analysis at Murdoch University
22
[31], which refers to the sum of all harmonics of current or voltage waveform divided by the
main component of the current or voltage. This can be expressed mathematically as [32].
THD =√∑ Vnrms
2∞n=2
Vfrms
(13)
Where:
𝑉𝑛𝑟𝑚𝑠: is the RMS voltage of the nth harmonic.
𝑉𝑓𝑟𝑚𝑠: is the RMS voltage of fundamental frequency.
Harmonic distortion may result in transformer heating and increased losses in the copper,
core, and the stray-flux hence may result in erratic tripping of thermal protections and relays.
Furthermore, it may cause cable losses [33], malfunctioning of traffic control or ripple control
systems, increased probability of resonance occurrence, degeneration or failing of power
factor correction capacitors, overload of the neutral conductors in 3 phase systems and loss
of efficiency in electric machines. Finally, it may cause losses in the distribution network due
to harmonic currents, a low power factor, electromagnetic interference (EMI), and
communication system interference [20]. A shunt active power filter can be used to inject an
opposite and equal compensating harmonic current to compensate for harmonic load current
[18]. From Figure 13 below, it can be seen that a base sine waveform, its third harmonic and
the distorted waveform, which is the sum of the base waveform and its third harmonic.
Power Quality Analysis at Murdoch University
23
2.2.13 Interharmonics
The existence of waveforms of a sinusoidal nature at frequencies that lie between 50 Hz
multiples of the supply frequency is referred to as inter-harmonic interference. These can
appear as a wide band spectrum or discrete frequencies. Spectral components in the quasi-
steady state can be used to define harmonics and inter-harmonics over a range of
frequencies. Mathematically, harmonics, inter-harmonics and sub harmonics can be
described as:
Harmonic: f = 0 ∗ fb where a is an integer > 0 (14)
Interharmonic: f ≠ a ∗ fb (15)
DC: f = a ∗ fb = 0Hz (a = 0) (16)
Sub harmonic: f > 0Hz and f < fb (17)
Where:
𝑓𝑏: is the fundamental frequency of the system.
Figure 13: Harmonic Distortion [34]
Power Quality Analysis at Murdoch University
24
Sub harmonic is a type of inter harmonic for frequencies less than the fundamental frequency
of the system. Indeed, Interharmonics are mainly caused by cycloconverters that are widely
used in static VAR generators, linear motor drives, and rolling mills. Other causes of inter-
harmonics include low-frequency power line carriers, integral cycle control, induction
furnaces, induction motors, and arcing loads such as arc furnaces and arc welders [35].
These impacts of inter-harmonics include vibrations in induction motors, heating effects
similar to those of harmonics, malfunctioning of ripple control receivers, the flickering of light,
and noise in audio appliances. Interharmonics can cause acoustic noise in power equipment,
malfunctioning of television receivers, and fluorescent lamps [20].
2.2.14 Electromagnetic Interference (EMI)
The interaction between magnetic and electric fields and sensitive electronic devices and
circuits is a high-frequency phenomenon referred to as EMI [2]. The interaction between radio
frequency fields and sensitive communication or data equipment is known as Radio
Frequency Interference (RFI). EMI and RFI result in inductance creation on data carrying
systems. The voltage that is in excess of the operating data levels can create data opposite or
data that is not the same as that travelling in the data line since data line signals are digital
signals in the form of zeros and ones. Therefore, EMI and RFI introduce noise to the system
hence affecting the power quality. The solution to this power quality issue is to employ
shielding of the data devices and their cables or to relocate the data cables and devices from
the EMI/RFI source [29].
Power Quality Analysis at Murdoch University
25
2.3 Power Quality Standards
Due to the massive costs associated with poor power quality, various standards have been
put in place to give guidelines, recommendations, and limits to assist in ensuring the user
equipment is compatible with the system where it is to be used [39]. These standards include
IEEE 519, IEEE 1459, ANSI C84.1, EN 50160, IEC 61000, and AS/NZS 61000.3.2:2003.
2.3.1 IEEE 519 Standard
IEEE 519 is an international standard drafted by the Institute of Electrical and Electronics
Engineers (IEEE) that gives recommendations to control harmonic distortion levels on the
overall power system. Other IEEE standards on power quality disturbances include IEEE 1100
(Powering and Grounding Sensitive Equipment) and IEEE 1159 (Monitoring and Definition of
Electric Power Quality) [39].
2.3.2 IEEE 1459 Standard
IEEE 1459 is a standard that gives definitions for the measurement of electric quantities under
sinusoidal and non-sinusoidal, single phase and polyphase and balanced and unbalanced
situations. This standard proposes the concepts and the definitions that are essential for
evaluating the quality of transmission of electrical energy. This is for the purposes of designing
measurement instrumentation, for billing, and development of measurement algorithms
[40].
2.3.3 ANSI C84.1 Standard
ANSI refers to American National Standards Institute and gives guidelines on power quality in
the United States based on the IEEE standards and other standards generated by the institute
Power Quality Analysis at Murdoch University
26
itself. The most common ANSI standard (ANSI C84.1) provides recommendations for steady
state voltage ratings [39].
2.3.4 EN 50160 Standard
The EN 50160 (European Standard) deals with supply quality necessities for European
services. This standard outlines the particular levels of voltage characteristics that must be
adhered to by the utilities and the techniques for assessing compliance. Moreover, the EN
50160 limits itself to voltage characteristics at the PCC (Point of Common Coupling), and
consequently does not stipulate requirements for power quality within the supply, or the
client's facilities. Regarding the limits in EN 50160, it is apparent that these are very similar to
the IEC 61000-3-6 compatibility levels for harmonic voltages with respect to the
corresponding medium and low voltage systems, with the absence of higher order harmonic
limits in EN 50160 being the exclusion [41].
2.3.5 IEC 61000 Standard
The IEC 61000 (Electromagnetic Compatibility (EMC) Standards) categorizes power quality
issues into six categories. Part 1 deals with terminology and definitions and part 2 describes
the environment where the equipment will be used. Part 3 recommends the limits of
disturbances that can be caused by equipment in the power system, while part 4 details the
guidelines and procedures for tests and measurement devices, and tests to confirm
compliance with the standards. Guidelines on how to install equipment that is to be used for
mitigating power quality disturbances are detailed in part 5. Finally, part 6 of the standard
deals with the standards for specific equipment, so that they can be immune to the
disturbance levels of the power system they are to be used in [39].
Power Quality Analysis at Murdoch University
27
2.3.6 AS/NZS 61000.3.2:2003 Standard
AS/NZS 61000 is an Australian/ New Zealand standard that is compatible with IEEE 519, and
it is similar to IEC 61000. This standard is made up of six parts that prescribe the limits for
harmonics and voltage disturbances produced by equipment whose input current is less than,
equal to or greater than 16 A per phase. It provides the limits for voltage disturbances in
equipment in low voltage systems that are rated less than or equal to 75 A. The standard also
provides the methods to confirm compliance with the set standards [42]. The following Table
1 is a summary of the power quality standards.
Table 1: Power Quality Standards
Power Quality Issue Standard
Harmonics IEEE 519 and AS/NZS 61000 (for Australia
and New Zealand)
Power and grounding IEEE 1100
Monitoring and definition of electric power
quality
IEEE 1159
Measurement of electrical quantities under
different situations
IEEE 1459
Steady state voltage ratings ANSI C84.1 (For America)
Electromagnetic compatibility IEC 61000
Voltage disturbance AS/NZS 61000
Voltage disturbance EN 50160
Power Quality Analysis at Murdoch University
28
2.4 Power Quality Monitoring
Power quality monitoring (PQM) refers to the process of collection, analysis, and
interpretation of raw measurement data about voltages and currents into useful information
[63]. PQM is done to quantify the power quality phenomena that occur in a specific site on
electric power equipment. It is sometimes conducted to forecast the performance of the load
equipment and to choose power quality attenuating systems. In some cases, PQM is
performed to identify the incompatibilities between the consumer loads and the supply. In
other case, it is done to test the electrical environment at a specific site for the equipment
and machinery required [64].
Appropriate monitoring equipment is required to perform power quality monitoring. The
input and output interface of the power quality monitoring equipment include; input
channels, analogue inputs/outputs, digital inputs and outputs and communication and
networks. Power quality monitoring equipment have the following functions [4]:
Capture of data by present thresholds. The capture of measured parameters is
conducted when a disturbance repeats at set time intervals or goes beyond a present
threshold (event logging) with the time intervals and thresholds being set up by the
user.
Capture of data by self-adjusting thresholds. A steady-state norm is used to set the
thresholds by a monitor.
Capture of data that is triggered externally. This is a feature provided by most
monitors.
Manual data capture. A manual trigger function is provided by the most monitor,
which is for a snapshot of the present situation.
Power Quality Analysis at Murdoch University
29
Time interval recording and data logging. Continuous monitoring of parameters is
done using data logging with capture achieved at user established time intervals.
Waveform capture. Certain monitors can capture waveforms for voltage and current.
They can then be downloaded to a PC or can be viewed by built-in displays.
Time synchronization. A radio signal, GPS or an external time signal can use for time
synchronization by some power quality monitors.
Firmware. New releases of firmware by some monitor manufacturing companies are
done periodically. This new firmware is used to improve the existing set of the meter
and for correcting errors in metering algorithm without the need for buying new
hardware.
2.5 Using Compensating Devices to Improve Power Quality Disturbances
2.5.1 Active and Passive Filters
An active filter is an electronic filter device that uses active components such as transistors or
operational amplifiers, both of which require an external power source. However, a passive
filter does not require an external power source, and it is made from passive elements mostly
linear elements such as transformers, inductors, capacitors, and resistors or nonlinear
elements or complex linear elements such as transmission lines [43].
A passive filter is a device that is made up of passive elements and therefore requires an
external power source for its operation. Passive filters are mainly used for frequencies in the
range 100-500 kHz [44]. Filters can be classified into five types based on the transfer function
coefficients. These are low pass, high pass, band pass, notch, and all pass [44].
Low pass filter transfer function is [1]:
Power Quality Analysis at Murdoch University
30
TFLP(s) =a0
s2 + b1s+b0=
KωP2
s2 + (ωP
QP) s + ωP
2 (18)
Figure 14 below represents the different low pass filter designs and characteristics.
High pass filter transfer function is [1]:
TFHP(s) =a2s2
s2 + b1s + b0=
Ks2
s2 + (ωP
QP) s + ωP
2 (19)
Figure 15 below indicates the high pass filter design and characteristics.
Figure 14: Passive Low Pass Filter [1]
Figure 15: High Pass Filter [1]
Power Quality Analysis at Murdoch University
31
Band pass filter transfer function is [1]:
TFBP(s) =a1s
s2 + b1s+b0=
K (ωP
QP) s
s2 + (ωP
QP) s + ωP
s (20)
Notch filter transfer function is [1]:
TFN(s) =a2s2 + a0
s2 + b1s + b0=
K(s2 + ωz2)
s2 + (ωP
QP) s + ωP
2 (21)
All pass filter transfer function is [1]:
TFAP(s) =a2s2 + a1s + a0
s2 + b1s + b0=
K [s2 − (ωP
QP) s + ωP
2]
s2 + (ωP
QP) s + ωP
2 (22)
Active filters can be high pass, low pass, band pass, and notch filters. Passive filters can be
only high pass, low pass, and bandpass filters. Active and Passive filters are used in
attenuation of frequencies that are not within their cut off points. Consequently, find
applications in the load compensating devices, telephone systems for decoding of dual tone,
instrumentation, and in data acquisition systems [43]. Table 2 below summarizes the
comparison between active and passive filter.
Power Quality Analysis at Murdoch University
32
Table 2: Comparison between Active and Passive filter [43]
Active Filter Passive Filter
Requires an external power source Requires no external power source
Made of active components Made of passive components R, L, and C
Has high input and low output impedance Has low input and high output impedance
Has power gain in output signal Has no signal gain
Has oscillations and noise due to feedback
loops for regulating active components
Has low noise due to thermal noise in
elements
Does not consume energy of signal Consumes energy of signal
Does not use inductors Uses inductors
Has stable tuning, accuracy, and high
immunity to EMI
Has self-regulation of voltages driving loads
and has no bandwidth restrictions, thus
operates at higher frequencies
2.5.2 Distribution Static Compensator (D-STATCOM)
Low power factor, harmonic distortion, voltage swells, and voltage sags can be enhanced
using current injected by a Distribution Static Compensator (D-STATCOM) [45]. The D-
STATCOM is a device that is used to limit the reactive power flow in a distribution system
through compensation and can be based on a voltage source converter (VSC) [46]. A VSC is
capable of generating a sinusoidal voltage of any desired phase angle, frequency, and
magnitude. The VSC relies on energy storage devices such as capacitors that supply it with a
DC Voltage that is then used to switch the solid-state electronics inside the VSC. Then it injects
the voltage difference or completely replaces the voltage. The voltage difference refers to the
difference between the actual voltage and the nominal voltage [46]. The following Figure 16
demonstrates a distribution system compensated by an ideal D-STATCOM connected in a
shunt configuration.
Power Quality Analysis at Murdoch University
33
From Figure 16, the D-STATCOM is functioning in current control mode and hence is
represented by a current source Is.
2.5.3 Dynamic Voltage Restorer (DVR)
Sensitive loads can be protected from voltage sags, surges, or disturbances using a dynamic
voltage restorer (DVR). A voltage source injecting a voltage Vf can be used to represent an
ideal DVR for protection of sensitive loads as illustrated in Figure 17.
Figure 16: Ideal D-STATCOM [20]
Figure 17: Schematic of a DVR [20]
Power Quality Analysis at Murdoch University
34
This device can be constructed so that it is able, or not able to supply or absorb real power.
Voltage control of the DVR is done by regulation of the bus voltage to any value by measuring
the terminal voltage Vt. Then the balance is supplied through of for a DVR which is designed
to be able to absorb or supply real power. If the DVR is not able to absorb or supply any real
power during steady state, it will perform this throughout transients [20].
2.5.4 Unified Power Quality Conditioner (UPQC)
A UPQC uses a common capacitor for DC energy storage when connected to two voltage
source inverters (VSIs). One of the VSIs is connected in shunt with the AC line whereas the
other is connected in series with this same AC line. A UPQC is used to compensate for
harmonics, reactive power, negative sequence current, voltage imbalance, and voltage flicker
[47]. Voltage imbalance and voltage flicker are eliminated from the load terminal voltage by
the series VSI that injects a series voltage at the point of common coupling. A series voltage
proportional to the line current can be injected into the distribution line to attenuate current
harmonics [20]. The shunt VSI is employed in this device to provide a path for the real power
to flow to help in the functioning of the VSI connected in series [20]. It can be seen from Figure
18, which represents a UPQC in right shunt compensation configuration.
Power Quality Analysis at Murdoch University
35
2.6 Power Quality Case Studies
Power Quality monitoring research has been a topic that has attracted considerable interest
in recent times. Some of the consequential research includes: a study in Buffalo New York
sponsored by Niagara Mohawk Power Corporation in mid- 1989. This study showed that most
power quality problems originate from the end user’s equipment [48]. Moreover, a five-year
study of single phase electrical disturbances in normal mode in 1990 by the National Power
Laboratory (NPL), indicated the effects of capacitor switching which was observed in most
locations under study with the magnitude of maximum voltage not being so severe at these
sites [49].
A survey by Electrotek Concepts Inc. who were contracted by the Electrical Power Research
Institute (EPRI) in 1990 showed harmonic distortions, transients, voltage sags, and short
power interruptions as the most common type of power disturbances [50].
Other case studies include the Wisconsin Public Power Inc. [51] that installed power quality
meters at the input of equipment to identify the cause of circuits tripping. This was later found
to be capacitor banks. Filters and chokes were then added at these inputs to solve the
Figure 18: UPQC Schematic [20]
Power Quality Analysis at Murdoch University
36
problem. The same company installed meters to identify the cause of flickering light and
computer problems for an industrial consumer. This was identified to be the several large
single-phase welders in the company. This issue was solved by installing a more massive
transformer with larger conductors at the industrial company. A recommendation was also
provided to the company to add a second service line for the welders [51].
Power quality research was performed for a manufacturing plant [52] that had experienced a
failure of a recently bought test instrument when it was plugged into a GPO (General Purpose
Outlet). The problem was discovered to be the rated RMS voltage of 245 V of the test
instrument that was lower than the Australian Standards RMS voltage of 253 V. This was
solved by using a constant voltage transformer between the test equipment and the GPO that
would both suppress the voltage spikes and lower the RMS voltage.
Another case study conducted on a commercial office building involved utilizing two banks of
AC motors with variable speed drives (VSDs) for control of heating, ventilation and air
conditioning [1]. A 45 kVA transformer was used in order to service each of the banks. The
following Figure 19 indicates the snapshot of the system operation.
Power Quality Analysis at Murdoch University
37
From Figure 19, it can be seen that after reaching peak voltage, the variable speed drives
demand peak current with the neutral current shown in the second figure made up of 180 Hz
current that peaks above 150 Amperes. The neutral current is a 3rd harmonic that is a common
occurrence when there is a concentration of single- phase electronic loads. For this site,
heating of the service transformer was the main problem due to the third harmonic. The
transformer was not correctly sized for the load, therefore, calculations were done based on
IEEE 519 harmonics guidelines, and it was found that there was at least 5 kVA load on the
transformer above its nominal de -rated capacity. For this site, neutral current limiting devices
or phase shifting transformers were not required because of the low neutral to the ground
voltage and the isolated nature of the VSDs. New rated transformers for every bank was the
solution to the power quality problem for this site [1].
Figure 19: System Operation Snapshot [1]
Power Quality Analysis at Murdoch University
38
2.7 Costs of Power Quality Problems
Quantifying the cost of power quality problems is not an easy task as there are both direct
and indirect costs. Direct costs are directly related to disturbances and include production
loss costs, damage to equipment expenses, environmental or financial penalties, restart of
process costs, salary expenditures during downtimes, and resources and downtime that is not
recoverable. In addition, it describes the human health and safety direct costs, loss of quality
of semi-finished products, financial penalties due to breached contracts, and utility costs due
to power interruptions. Organizations incur indirect costs, and it includes the cost of restoring
a brand, loss of market share and postponement of income or revenue of an organization
[53].
Various studies have been conducted to provide the quantitative economic costs of poor
power quality. The cost was estimated at a few tens of billions of dollars in early 1990s, and
this had grown to a few hundreds of billions of dollars by 2003 [4]. It is estimated that globally,
500 billion euros amounting to 50 % of the electricity sector global turnover is lost annually
because of poor power quality [54]. Another study [55] indicates that the US economy loses
between 104 billion dollars and 164 billion dollars per year due to outages alone. Moreover,
6.7 billion dollars are lost by industrial economies and the digital economy in the US due to
disturbances excluding voltage sags with a further 15 billion to 24 billion dollars lost to other
power quality problems. An estimated 100 billion euros is lost annually in the world due to
harmonics according to a Eurelectric report [56]. Another study also showed that different
industries experience different costs due to poor power quality. For instance, a
telecommunications company losses up to 30 000 euros every minute due to power outages,
Power Quality Analysis at Murdoch University
39
while as high as 3.8 million euros is lost by a semiconductor facility due to one power quality
disturbance [57].
Power Quality Analysis at Murdoch University
40
Chapter 3: Methodology
The approach used in this project involved using of actual current and voltage data in the
analysis of power quality issues experienced at Murdoch University. The current and voltage
data was measured using an EM133 meter installed at 1.330, in substation 12, South Street
Building 330, chancellery.
Data measured from the electrical systems at Murdoch University, especially from 1.330
South Street Building 330, Chancellery, and Substation T12, and it was saved in the form of
spreadsheets in order to perform the analysis. Then the data was extracted from these
spreadsheets and were used to plot graphs for all the measured variables in order to obtain
a visual impression of the data. Calculations were performed where applicable (voltage and
current unbalance) and graphs for the calculated variables were plotted to show the trend
existing in the electrical network.
There are two significant methods were used in the calculation of voltage unbalance. The first
method involves calculation of the negative phase sequence voltage and positive phase
sequence voltage from the phase voltage phasors. The voltage unbalance is then the ratio of
the negative phase sequence to the positive phase sequence multiplied by one hundred. This
method is based on IEC 61000 standards. The second method that is related to National
Electrical Manufacturers Association (NEMA) is determined by finding the maximum
deviation from the average line voltage and multiplying this deviation by one hundred.
Afterward, the graphs were compared to the theoretical charts for each power quality issue
to identify the PQ issues existing at the institution. After identification of the power quality
issues, its effects on the other parameters such as temperature, phase, current, voltage, or
Power Quality Analysis at Murdoch University
41
power were investigated. This was conducted by plotting graphs of these measured
parameters throughout the occurrence of the power quality problem then the trend
analysed. In other cases such as in voltage disturbance, calculations were done to indicate its
effect on the temperature rise due to loading. Finally, the results of this analysis were
compared with theoretical knowledge from journal publications and literature focusing on
power quality problems.
In order to test the power quality devices, there are three imperative objectives that have
been taken into account include:
1) To determine the types and magnitude of power quality disturbances, which
produced by a device connected to the power system.
2) To test power quality mitigation devices for their ability in order to reduce
disturbances.
3) To test electrical devices for their performance in terms of disturbances of power
quality.
Power Quality Analysis at Murdoch University
42
Chapter 4: Results and Discussion of Data Analysis
4.1 Voltage Unbalance
The following Figure 20 illustrates the voltages of three-phase to neutral lines. From Figure
20, it can be seen that the magnitude of voltage A-N is lower than the magnitudes of voltage
B-N and C-N. Further investigation and calculations were therefore carried out to prove the
level of voltage unbalance.
The average voltage magnitude at the various times is given as
Vav =VL1 + VL2 + VL3
3 (23)
Plotting this average value together with the three voltages gives the graph in Figure 21
below.
234
235
236
237
238
239
240
241
242
243
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
Vo
ltag
e (
V)
Time of the Day
Voltage Magnitude versus Time
Voltage A-N Magnitude Voltage B-N Magnitude Voltage C-N Magnitude
Figure 20: Voltage versus Time for Three Voltage Lines
Power Quality Analysis at Murdoch University
43
The difference between each phase voltage and the average voltage was determined for all
times given. The largest unbalance was determined to be 0.7 V in line voltage A-N. The
percent voltage unbalance consequently is [58]:
% Voltage Unbalance =0.7
236.9∗ 100 = 0.295 % (24)
Figure 22 below shows the percent voltage unbalance for each phase plotted against time.
234
235
236
237
238
239
240
241
242
243
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
Vo
ltag
e (
V)
Time of the Day
Voltage Magnitude versus Time for a Three Phase System
Voltage A-N Magnitude Voltage B-N Magnitude
Voltage C-N Magnitude Average Voltage magnitude
Figure 21: Voltage versus Time Including Average Voltage of the Three Phases
Power Quality Analysis at Murdoch University
44
Since the percent voltage unbalance is less than 2 %, the voltage can be used safely with
three-phase equipment [58]. The temperature rise due to this voltage unbalance would also
be low as indicated in equation 25 below.
% Temperature Rise = 2 ∗ (% Voltage Unbalance)2 (25)
= 2 ∗ (0.295)2 = 0.174 Degree Celsius
By plotting the line current magnitudes with time, Figure 23 was obtained. From Figure 23,
the current unbalance can be determined using an equation similar to equation 24. The
largest unbalance was determined as 11.2233 Amps in line current A.
% Current Unbalance =11.2233
26.5567∗ 100 = 42.26 % (26)
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
% V
olt
age
Un
bal
ance
Time of the day
Percent Voltage Unbalance
%Unbalance A %Unbalance B % Unbalance C
Figure 22: Percent Voltage Unbalance for all Three Phases against Time of the Day
Power Quality Analysis at Murdoch University
45
The percent current unbalance for each phase was plotted against time of the day as
illustrated in Figure 24 below.
0
50
100
150
200
250
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
Cu
rre
nt
Mag
nit
ud
e (
A)
Time of the Day
Current Magnitude versus Time
Current A Magnitude Current B Magnitude Current C Magnitude
Figure 23: Current Magnitude versus Time
0
5
10
15
20
25
30
35
40
45
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
% C
urr
en
t U
nb
alan
ce
Time of the Day
Percent Current Unbalance
% Unbalance current A % Unbalance Current B % Unbalance Current C
Figure 24: Percent Current Unbalance for all Three Phases against Time of the Day
Power Quality Analysis at Murdoch University
46
The current unbalance of 42.26 % is very high and unacceptable. This may cause heating in
the load such as in the motor or transformer winding that degrades the load. Besides, due to
this unbalance I2R, losses in the cables increase, and this may lead to lower efficiency of the
load.
4.2 Phase Distortion
As it can be seen from Figure 25, for voltage angle shows that there is no phase distortion
during the duration of the measurement. All phases remain 120 electrical degrees apart
during the entire measurement period. As a result, phase distortion is not a power quality
issue experienced at Murdoch University.
On the other hand, Figure 26 demonstrates the current angle for the different line currents.
From Figure 26, it can be seen that all three phases have distortions in the current angle. The
phase angle for Current A fluctuates between -10.2 to -41.8 electrical degrees, the angle for
-150
-100
-50
0
50
100
150
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
Vo
ltag
e A
ngl
e
Time of the Day
Voltage Angle versus Time
Voltage A-N Angle Voltage B-N Angle Voltage C-N Angle
Figure 25: Voltage Angles for the Three Phases Plotted against Time
Power Quality Analysis at Murdoch University
47
current B fluctuates between -97.8 to -157 electrical degrees, and the phase angle for current
C fluctuates between 79.6 to 141.7 electrical degrees. This variation in current angles can be
due to the varying reactance of the load, or it may be due to the unbalanced degradation in
the windings of the three-phase loads in the system.
4.3 Harmonic Distortion
Figure 27 demonstrates the variation of the Total Harmonic Distortion (THD) of each phase
voltage with time.
-200
-150
-100
-50
0
50
100
150
200
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM
Cu
rre
nt
An
gle
Time of the Day
Current Angle versus Time
Current A Angle Current B Angle Current C Angle
Figure 26: Current Angles for Three Phases Plotted against Time
Power Quality Analysis at Murdoch University
48
From Figure 27, it is clear that all the three phases have a THD that lies between 1.8 to 2.8 %.
According to IEEE STD 519 and AS/NZS 61000 standards, the recommended value of THD
should not exceed 5 % for the operation of computers and other associated equipment such
as programmable controllers [59][42].
4.4 Power Factor
The power factor affects the reactive power, the real and the apparent power in an electrical
system. An increase in power factor results in a decrease in the reactive and apparent power,
but an increase in the real power [2]. This is showed in Figures 28, 29, 30, and 31 generated
from experimental data.
0.00
0.50
1.00
1.50
2.00
2.50
3.00
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
Tota
l Har
mo
nic
Dis
tort
ion
Time of the Day
Total Harmonic Distortion
THD Voltage V1 (%) THD Voltage V2 (%) THD Voltage V3 (%)
Figure 27: THD for all the Phases
Power Quality Analysis at Murdoch University
49
From Figure 28, it can be seen that the power factor for the neutral line is 1 while that for
phases B and C is -1 between 12:00:00 am and 1:00:30 am. At this time, the power factor for
phase A lies between 0.5 and 1. Indeed, a negative power factor means that power is
returning to the source. Between 1:00:30 am and around 3:00:30 am, the power factor for
phase B, C, and the neutral line is 1. This means the load supplied by these phases was purely
resistive (there were no inductive loads connected to these phases).
Throughout these times, the real and apparent powers are very low while the reactive power
is zero as can be seen from figures 29, 30, and 31. Between 5:00:00 am to 1:41:00 pm the
real, reactive, and apparent powers increase, which results in a power factor decrease during
this time. This proves the argument that an increase in the power factor results in a reduction
of the reactive power. It is worth noting that the real power at all times is always higher than
the reactive power during the time of measurement.
-1.50
-1.00
-0.50
0.00
0.50
1.00
1.50
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
Po
we
r Fa
cto
r
Time of the Day
Power Factor
Power Factor A (%) Power Factor B (%) Power Factor C (%) Power Factor (%)
Figure 28: Power Factor for all Phases
Power Quality Analysis at Murdoch University
50
0.00
20.00
40.00
60.00
80.00
100.00
120.00
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
Re
al P
ow
er
(kW
)
Time of the Day
Real Power
Real Power A (kW) Real Power B (kW) Real Power C (kW) Real Power (kW)
Figure 30: Reactive Power for all Phases
-10.00
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
Re
acti
ve P
ow
er
(kV
Ar)
Time of the Day
Reactive Power
Reactive Power A (kVAr) Reactive Power B (kVAr)
Reactive Power C (KVAr) Reactive Power (kVAr)
Figure 29: Real Power for all Phases
Power Quality Analysis at Murdoch University
51
The effect of a low power factor is an increase in current demanded by the load. By comparing
Figures 32 and Figure 28, it is clear that phase A has the lowest power factor and the highest
current demanded by the load followed by phase C and finally phase B.
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
Ap
par
en
t P
ow
er
(kV
A)
Time of the Day
Apparent Power
Apparent Power A (KVA) Apparent Power B (kVA)
Apparent Power C (kVA) Apparent Power (kVA)
Figure 31: Apparent Power for all Phases
Power Quality Analysis at Murdoch University
52
Figure 32: Current Demanded by the Load in each Phase
As a result, the power factor has the effect of increasing the voltage drop in transmission and
distribution lines because of the increase in current demanded by the load. This is evidenced
by Figure 33 below, where the phase-to-phase voltages, as well as the phase to neutral
voltages, decrease as the power factor decreases for all the three phases.
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
160.00
180.00
200.00
12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM
De
man
d C
urr
en
t (A
)
Time of the Day
Demand Current of the Load
Demand Current A (A) Demand Current B (A) Demand Current C (A)
Power Quality Analysis at Murdoch University
53
According to IEC 61000 standard, voltage unbalance is calculated as [60]:
UBF =V−
V+∗ 100 (27)
Where:
𝑉−: is the negative phase sequence voltage.
𝑉+: is the positive phase sequence voltage.
The negative phase sequence and positive phase sequence voltage are calculated from the
phase voltage phasors using the following equation [60]:
V− =1
3(Vr + a2Vy + aVb) (28)
V+ =1
3(Vr + aVy + a2Vb) (29)
While the zero sequence, voltage is calculated as [60]:
0.00
50.00
100.00
150.00
200.00
250.00
300.00
350.00
400.00
450.00
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
Vo
ltag
es
(V)
Time of the Day
Phase to Phase and Phase to Neutral Voltages
Voltage A-B (V) Voltage A-N (V) Voltage B-C (V)
Voltage B-N (V) Voltage C-A (V) Voltage C-N (V)
Figure 33: Phase to Phase and Phase to Neutral Voltages at Varying Power Factors
Power Quality Analysis at Murdoch University
54
V0 =1
3(Vr + Vy + Vb) (30)
Where:
a = 1∠1200
Vr: is the red phase.
Vy: is the yellow phase.
Vb: is the blue phase.
The voltage unbalance factor can also be calculated using the equation below [60]:
UBF = √1 − √3 − 6β
1 + √3 − 6β∗ 100 (31)
Where:
β =|Vry|4 + |Vyb|4 + |Vbr|4
(|Vry|2 + |Vyb|2 + |Vbr|2)2 (32)
The IEC 61000 voltage unbalance factor was calculated, and refer to Appendix Part C for more
information. This was repeated for all the values of voltages collected every half second
between 12:00:30 am up to 1:45:30 pm. Due to the huge amount of data, excel spreadsheet
was used in order to compute the voltage unbalance and to plot the voltage unbalance
variation with time. A large amount of data from the spreadsheet could also not be included
in this section.
Power Quality Analysis at Murdoch University
55
From the data given, the voltage unbalance experienced by the system during the duration of
the test is indicated in Figure 34 below.
From Figure 34, it can be seen that the largest voltage unbalance is 0.3486 %, which is
experienced at 12:41:00 pm. In fact, voltage unbalance at this time may be due to higher load
on one phase compared to the load on the other phases. For example, if most people use the
library and labs at this time of the day and both of these facilities are on one phase say the
yellow phase, then it means the load on the red and blue phases would be less thus there
would be a voltage unbalance. It all depends on the trend in the institution, and probably at
this time also the cafeteria is at full capacity meaning more power consumed at this time of
the day. At night or early in the morning, the voltage unbalanced may be lower because it is
not the peak time of power consumption. Not all facilities are working at optimal condition,
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
12:00:00 AM 2:24:00 AM 4:48:00 AM 7:12:00 AM 9:36:00 AM 12:00:00 PM 2:24:00 PM 4:48:00 PM
% U
nb
alan
ce V
olt
age
Fac
tor
Time of the Day
UBF
UBF(sqrt((1-a)/(1+a))*100)
Figure 34: Unbalance Voltage Factor
Power Quality Analysis at Murdoch University
56
therefore, there may a voltage unbalance. Nevertheless, it definitely must be lower than
when facilities at working at the almost optimal condition.
In comparison, voltage unbalance according to National Electrical Manufacturers Association
(NEMA) is defined as the maximum deviation from the average line voltage referred to the
average of the line voltages times 100 [61]. Mathematically, this is given as [62], and it was
calculated using equation (24):
Vav − VL
Vav∗ 100 (33)
Where:
Vav =VL1 + VL2 + VL3
3 (34)
Power Quality Analysis at Murdoch University
57
Chapter 5: Conclusion and Future Work
To summarize, this project has discussed and analysed about power quality analysis at
Murdoch University, in particular from 1.330, in substation 12, South Street Building 330,
chancellery. From the literature in this project, the most common type of power disturbances
was identified to be harmonic distortion, voltage transients, voltage sags, and short power
interruptions. In addition, from the literature, it was found that most of the power quality
problems originate from the end user’s equipment.
Costs that are associated with poor power quality are classified into direct costs and indirect
costs. Direct costs include production losses, costs associated with damage to equipment,
environmental and financial penalties, costs based on restarting the process, expenditure on
salary during down times, resources and unrecoverable downtime. Moreover, costs including
human health and safety, financial penalties due to a breach of contracts, utility costs because
of a power interruption and loss of quality of semi-finished products. On the other hand,
indirect costs include costs of restoring a brand, loss of market share and postponement of
income or revenue of the organization.
In this project, power data was measured from the electrical system at Murdoch University
and saved in the form of spreadsheets. From these spreadsheets, calculations were done and
graphs plotted in order to identify the power quality issues experienced at the institution.
After identification of the power quality issues, the effect of these issues on parameters such
as voltage angle and phase, current angle and phase, temperature of the equipment was
determined either by calculation or visually from the plots of these parameters. These results
were then compared to the theoretical principles contained in the literature review section.
Power Quality Analysis at Murdoch University
58
The results indicate that at the institution the power quality factors experienced are voltage
unbalance, current unbalance, distortion in current angle, harmonic distortion, and power
factor. Using both the IEC and NEMA methods, the percentage voltage unbalance was found
to be lower than the maximum set value of 2 %. As a result, this voltage unbalance would not
affect three-phase equipment in the system. However, the current unbalance was found to
be extremely high, and this is not safe for the equipment as it can result in heating and thus
degradation in windings of motor and transformers and a reduction of their efficiency. The
harmonic distortion measured from the institution that ranges between 1.8 and 2.8 % is lower
than the 5 % limit, and therefore is also safe for use with equipment. From these results, it is
clear that the power received at the institution is of high quality, and hence safe for use with
equipment. The major problem is the high current unbalance and the distortions in the
current angle. In fact, by using compensating device UPQC consequently should be employed
in the institution electrical network in order to decrease current unbalance and distortions of
the current angle.
The significant goal of this project of performing a power quality analysis at Murdoch
University to identify the causes of poor power quality and provide solutions to improve the
power quality as well as all the specific objectives that had been set before the
commencement of this research have all been achieved. Accordingly, both power consumers
and the electric utility will find this project of considerable significance. There will be a
decrease in the occurrence of power quality disturbances as through this project these
disturbances can be identified monitored, predicted, and mitigated thus power consumers
will benefit from less malfunctions of electronic devices. Less malfunctioned devices translate
to cost savings for the consumers because of the reduced repair and maintenance costs
Power Quality Analysis at Murdoch University
59
required for malfunctioned devices. Since the power quality disturbances can be identified,
monitored, predicted, and mitigated through this project. Subsequently, industrial consumers
will benefit from lower interruptions of production. This translates to higher quality of
products, cost savings since idle time of personnel throughout the interruption would be
decreased, and the industry also benefits from less equipment damage. The electric utility
may gain considerable knowledge regarding their transmission, distribution network, and
sources of power quality disturbances in the electricity grid through this project. Therefore,
this project is of great significance to them.
5.1 Future Work Opportunities for the Power Quality Analysis at Murdoch
University
First of all, in the project presented in this thesis report, data was collected from the electrical
network of the institution and used to identify the power quality issues experienced at the
institution. Further work that can be conducted involves taking a detailed study of each power
quality issue identified and proposing a solution to decrease the power quality issue. After
installation of the proposed solution to the network, more tests should be carried out and
analysis of the test results done in order to prove the effectiveness of the proposed solution.
In addition, another further work that can be performed finds out the individual harmonic
order such as even order (2, 4, 6, 8) and odd order (3, 5, 7, 9). By doing this for all the power
quality issues identified, then we can conclusively say a problem was identified and a practical
and working solution presented to solve the problem. The conclusion will not be based on
theoretical information, but on proved and tested information.
Power Quality Analysis at Murdoch University
60
Because of the increased adoption of the internet of things and automation in the world
currently. An algorithm can be developed that automatically computes and plots the power
quality issues from the data it receives from a power quality meter. The automated system
then transmits the computed data and plotted graphs to a power quality expert for further
action. In this system, the power quality meters will automatically send the data it measures
to a computer containing the algorithm. After processing the data, the computer will transmit
the processed information to an expert for further action. This algorithm can be designed in
such a way that it can be trained to monitor and even predict the occurrence of a power
quality issue. Furthermore, the algorithm can be designed to have additional functionalities
such as predicting failure of equipment in the network due to a reoccurrence of a power
quality issue.
Power Quality Analysis at Murdoch University
61
Reference List
[1] CEA Technologies Inc. (CEATI), “Power Quality: Energy Efficiency Reference,” CEA
Technologies Inc. (CEATI), Ontario, 2007.
[2] C. Sankaran, Power Quality, Florida: CRC Press, 2002.
[3] "Why is good power quality necessary," MERUS POWER, 13 October 2016. [Online].
Available: http://www.meruspower.fi/why-is-good-power-quality-necessary/. [Accessed 3
January 2018].
[4] A. Baggini, Handbook of Power Quality, West Sussex- England: John Wiley and Sons,
2008.
[5] M. M. Canteli, “Power Quality Monitoring,” in Power Quality Mitigation Technologies in a
Distributed Environment, New York, Springer, 2007, pp. 15-40.
[6] O. D. Johnson and K. A. Hassan, "Issues of Power Quality in Electrical System,"
International Journal of Energy and Power Engineering, vol. 5, no. 4, pp. 148-154, 2016.
[7] J. Casazza and F. Delea, Understanding Electric Power Systems: An Overview of the
Technology and the Marketplace, New Jersey: The Institute of Electrical and Electronics
Engineering, 2003.
[8] G. B. Arfken, D. F. Griffing, D. C. Kelly and J. Priest, University Physics, Florida: Academic
Press Inc, 1984.
[9] L. L. Grigsby, The Electric Power Engineering Handbook: Electric Power Generation,
Transmission and Distribution, Third Edition, Boca Raton, Florida: CRC Press, 2012.
Power Quality Analysis at Murdoch University
62
[10] M. E. El -Hawary, Introduction to Electrical Power Engineering, The Institute of Electrical
and Electronics Engineers Inc., 2008.
[11] S. N. Singh, Electric Power Generation, Transmission and Distribution, Second Edition,
New Delhi: PHI Learning, 2011.
[12] L. Wilson, "How do we use electricity?," Shrink That Footprint , 21 July 2013. [Online].
Available: https://grist.org/climate-energy/how-do-we-use-electricity/. [Accessed 06
February 2018].
[13] S. Chattopadhyay, M. Madhuchhanda and S. Samrjit, Electric Power Quality, New York:
Springer, 2011.
[14] S. Khalid and B. Dwivedi, "Power Quality Issues, Problems, Standards & their Effects in
Industry with Corrective Means," International Journal of Advances in Engineering &
Technology, vol. 1, no. 2, pp. 1-11, 2011.
[15] A. E. Emanuel and J. A. McNeil, "Electric Power Quality, Annual Rev. Energy Environ, Ref
no. 1997.22:263-303," Worcester Polytechnic Institute, Massachusetts, USA, 1997.
[16] S. McNulty, Primen and B. Howe, "Power Quality Problems and Renewable Energy
Solutions," Massachusetts Renewable Energy Trust, 2002.
[17] C. J. Melhorn, A. Maitra, W. Sunderman, M. Waclawiak and A. Sundaram, "Distribution
System Power Quality Assessment Phase-II: Voltage sag and Interruption analysis," IEEE,
paper no. PCIC-2005-13, 2005.
[18] V. Anand and S. K. Srivastava, "Causes, Effects and Solutions of Poor Quality Problems in
the Power Systems," Journal of Engineering Research and Applications, vol. 4, no. 5, pp. 67-
74, 2014.
Power Quality Analysis at Murdoch University
63
[19] Energy Networks Association Limited, ENA Customer Guide to Electricity Supply,
Barton- Australia: Energy Networks Association (ENA), 2008.
[20] A. Ghosh and G. Ledwich, Power Quality Enhancement Using Custom Power Devices,
New York: Springer Science and Business Media, 2002.
[21] A. de Almeida, L. Moreira and J. Delgado, "Power Quality Problems and New Solutions,"
ISR-Department of Electrical and Computer Engineering, UNiversity of Coimbra, Coimbra -
Portugal.
[22] S. Khan, S. Khan and G. Ahmed, Industrial Power Systems, Florida: CRC Press, 2008.
[23] Slideshare, "My Thesis Presentation," Slideshare, [Online]. Available:
https://www.slideshare.net/GigaF/my-thesis-presentation-36343405. [Accessed 20
December 2017].
[24] Power Quality World, "Power Quality Basics: Voltage unbalance," Power Quality World,
[Online]. Available: http:www.powerqualityworld.com/2011/06/voltage-unbalance-power-
quality-basics.html. [Accessed 20 December 2017].
[25] Janitza, "Current/ Voltage Unbalance," Janitza, [Online]. Available:
https://www.janitza.com/current-voltage-unbalance.html. [Accessed 21 January 2018].
[26] R. Barnett, "Power Quality Measurement and Analysis Basics," Electrical Construction &
Maintenance Magazine (EC&M), [Online]. Available: http://www.ecmweb.com/power-
quality/power-quality-measurement-and-analysis-basics. [Accessed 4 September 2017].
[27] Power Quality World, "Power Quality Basics: Voltage Notching," Power Quality World,
January 2012. [Online]. Available: http://www.powerqualityworld.com/2012/01/voltage-
notching-power-quality-basics.html. [Accessed 20 March 2018].
[28] Essential Energy, Supply Standards: Electricity Supply Standard, Essential Energy, 2011.
Power Quality Analysis at Murdoch University
64
[29] J. Seymour, "The Seven Types of Power Problems," Schneider Electric.
[30] R. K. Rojin, "A review of Power Quality Problems and Solutions in Electrical Power
System," International Journal of Advanced Research in Electrical Electronics and
Instrumentation Engineering, vol. 2, no. 11, pp. 5605-5614, 2013.
[31] S. H. Laskar and Mohibullah, "Quality Issues and Need of Intelligent PQ Monitoring in
the Smart Grid Environment," International Journal of Emerging Technology and Advanced
Engineering, vol. 2, no. 9, pp. 63-69, 2012.
[32] Commercial Energy, "Total Harmonic Distortion (THD)," Commercial GEM Energy, 21
July 2015. [Online]. Available: https://www.gemenergy.com.au/total-harmonic-distortion-
thd/. [Accessed 04 September 2017].
[33] F. C. Pereira, J. C. de Oliveira and P. F. Ribeiro, "An Analysis of Costs Related to the Loss
of Power Quality," IEEE, 1998.
[34] Electricity, "Harmonic Distortion Analysis," Selectricity, [Online]. Available:
http://selectricity.com/harmonicdistortionanalysis.html. [Accessed 20 April 2018].
[35] IEEE, "Interharmonics," IEEE, 2001.
[36] Electronics Tutorials, "Power Triangle and Power Factor," Electronics Tutorials, [Online].
Available: https://www.electronics-tutorials.ws/accircuits/power-triangle.html. [Accessed
29 May 2018].
[37] K. N. Srinivas, Basic Electrical Engineering, New Delhi- India: I.K. International Publishing
House Pvt. Ltd., 2007.
[38] S. W. Fardo and D. R. Patrick, Electrical Power Systems Technology, Third Edition,
Georgia-USA: The Fairmont Press Inc, 2009.
[39] M. McGranaghan, "Power Quality Standards," Electrical Contractor Magazine, pp. 1-25.
Power Quality Analysis at Murdoch University
65
[40] J. L. Willems, "The IEEE Standard 1459: What and why?," in IEEE Xplore, 2010.
[41] R. C. D. /. M. F. McGranaghan and S. S. /. H. W. Beaty, "Applied Harmonics," in Electrical
Power Systems Quality, New York, McGraw-Hill, 2003, pp. 292-293.
[42] Standards Australia/ Standards New Zealand, Electromagnetic Compatibility (EMC),
Sydney- Australia, Wellington-New Zealand: Standards Australia/ Standards New Zealand,
2003.
[43] S. A. Pactitis, Active Filters: Theory and Design, Florida: CRC Press, 2007.
[44] A. Antoniou, "General Characteristics of Filters," in Passive, Active and Digital Filters,
Second Edition, Florida, Taylor and Francis Group, 2009, pp. 1-1 to1-29.
[45] S. K. K. Sivakoti, N. Y. Kumar and D. Archana, "Power Quality Improvement In
Distribution System Using D-statcom In Transmission Lines," International Journal of
Engineering Research and Applications, vol. 1, no. 3, pp. 748-752.
[46] V. A. Awasth and V. A. Huchche, "Reactive Power Compensation using D_STATCOM," in
Energy Efficient Technologies for Sustainability (ICEETS) international Conference, Nagercoil-
India, 2016.
[47] C. Benachaiba, O. Abdelkhalek, S. Dib, M. Allali and D. Dib, "The Unified Power Quality
Conditioner (UPQC): The Principle, Control and Application," in Quatrieme Conference
Internationale sur le Genie Electrique CIGE'10, Algerie, 2010.
[48] P. P. Barker, "Power Quality Monitoring of a Distribution System," IEEE Transactions On
Power Delivery, vol. 9, no. 2, pp. 1136-1142, 1994.
Power Quality Analysis at Murdoch University
66
[49] D. S. Dorr, "Interpreting Recent Power Quality Surveys to Define the Electrical
Environment," IEEE Transactions On Industry Applications, vol. 6, no. 6, pp. 1480-1487,
1997.
[50] E. W. Gunther and H. Mehta, "A Survey of Distribution System Power Quality-
Preliminary Results," IEEE Transactions On Power Delivery, vol. 10, no. 1, 1993.
[51] M. Dolinac, "Power Quality Metering and Case Studies," in Engineering & Operations
Technical Conference, Sacramento, California -USA, 2006.
[52] A. D. Francesco, "Power Quality Report Prepared for A Manufacturing Plant," CHK
Power Quality Pty Ltd, Sydney- Australia, 2016.
[53] S. Elphick, P. Ciufo, V. Smith and S. Perera, "Summary of the Economic Impacts of Power
Quality on Consumers," in Australasian Universities Power Engineering Conference (AUPEC),
Wollongong Australia, 2015.
[54] H. D. Keulenaer, "The hidden cost of Poor Power Quality," ResearchGate publication,
pp. 1-7, 31 October 2004.
[55] D. Lineweber and S. McNulty, "The Cost of Power Disturbances to Industrial and Digital
Economy Companies," EPRI's Consortium for Electric Infrastructure for a Digital Society
(CEIDS), 2001.
[56] Eurelectric, "Power Quality in European Electricity Supply Networks- 1st Edition,"
Eurelectric, 2002.
[57] D. Chapman, "The Cost of Poor Power Quality," In Power Quality Application Guide 2-1,
April 2002. [Online]. Available: www.Ipqi.org.
Power Quality Analysis at Murdoch University
67
[58] D. Wirz, Commercial Refrigeration For Air Conditioning Technicians, Third Edition,
Boston USA: Cengage Learning, 2018.
[59] IEEE, "IEEE Standard 519- 2014 -IEEE Recommended Practice and Requirements for
Harmonic Control in Electr power Systems," IEEE Standards Association, [Online]. Available:
https://standards.ieee.org/findstds/standard/519-2014.html. [Accessed 15 May 2018].
[60] F. Ghassemi and M. Perry, Review of Voltage Unbalance Limit in The GB Grid Code
CC.6.1.5 (b), GCRP, 2014.
[61] M. H. J. Bollen, "Definitions of Voltage Unbalance," IEEE Power Engineering Review, pp.
49-50, 2002.
[62] Advanced Manufacturing Office, Energy Efficiency and Renewable Energy, U.S
Department of Energy, "Eliminate Voltage Unbalance," Advanced Manufacturing Office,
Energy Efficiency and Renewable Energy, U.S Department of Energy, [Online]. Available:
https://www.energy.gov/sites/prod/files/2014/04/f15/eliminate_voltage_unbalanced_mot
or_systemts7.pdf. [Accessed 30 April 2018].
[63] A. McEachern, "Roles of Intelligent Systems in Power Quality Monitoring, Past, Present
and Future," in 2001 Power Engineering Society Summer Meeting. Conference Proceedings,
Vancouver- Canada, 2001.
[64] B. Singh, A. Chandra and K. Al-Haddad, Power Quality Problems and Mitigation
Techniques, West Sussex- UK: John Wiley and Sons Ltd, 2015.
[65] "EM133-R," Modbus Communications Protocol, Western Australia, 2018.
Power Quality Analysis at Murdoch University
68
Appendix
Appendix Part A: EM133 Meter Manual
Power Quality Analysis at Murdoch University
69
Figure 35: EM133 Meter Manual [65]
Power Quality Analysis at Murdoch University
70
Appendix Part B: Calculation of Apparent Power and Power Factor
Taking the data for real power, apparent power, reactive power, and power factor for the
time 12:00:30 am, the authenticity of the measured results can be confirmed using the power
triangle.
Table 3: Power Data for the Phase A at 12:00:30 am
Parameter Value
Apparent power A 6.12 kVA
Reactive power A 2.37 kVAr
Real Power A 5.64 kW
Power factor 0.922
Apparent Power A = √(Real Power)2 + (Reactive Power)2 (35)
= √5.642 + 2.372 = 6.1177 kVA
Power Factor =Real Power
Apparent Power (36)
=5.64
6.12= 0.92157
Accordingly, the data from the meter is authentic and can be used for analysis of the power
quality issues.
Power Quality Analysis at Murdoch University
71
Appendix Part C: Calculation of Voltage Unbalance
Based on the following equations:
UBF = √1 − √3 − 6β
1 + √3 − 6β∗ 100 (37)
Where:
β =|Vry|4 + |Vyb|4 + |Vbr|4
(|Vry|2 + |Vyb|2 + |Vbr|2)2 (38)
The IEC 61000 voltage unbalance was calculated as
Taking data 12:00:30 am, where
VA−B = 416.90, VB−C = 418.10, and VC−A = 417.50
Each of the phase to phase voltages above were raised to power 4 and to power 2 as detailed
by Table 4 below.
Table 4: Voltage Unbalance Using IEC 61000 Standard
Phase to Phase Voltage Voltage (x) (x)2 (x)4
VA-B 416.90 173,805.6100 30,208,390,067.4721
VB-C 418.10 174,807.6100 30,557,700,513.9121
VC-A 417.50 174,306.25 30,382,668,789.0625
From the values of Table 4, therefore using the equations in (37) and (38):
β =|VA−B|4 + |VB−C|4 + |VC−A|4
(|VA−B|2 + |VB−C|2 + |VC−A|2)2
=30,208,390,067.4721 + 30,557,700,513.9121 + 30,382,668,789.0625
(173,805.6100 + 174,807.6100 + 174,306.25)2
= 0.999994
Power Quality Analysis at Murdoch University
72
Voltage unbalance thus is:
UBF = √1 − √3 − 6β
1 + √3 − 6β∗ 100 = √
1 − √3 − 6(0.999994)
1 + √3 − 6(0.999994)∗ 100 = 0.165984523 %
This was repeated for all the values of voltages collected every half second between 12:00:30
am up to 1:45:30 pm. Due to the huge amount of data, excel spreadsheet was used to
compute the voltage unbalance and to plot the voltage unbalance variation with time. A large
amount of data from the spreadsheet could also not be included in this section.
Appendix Part D: Risk Assessment
Various risks are associated with conducting this research. The major risk when conducting
this project is the risk of electric shock. Indeed, during the data collection stage, when
measuring the current, voltage, or frequency. There will be direct exposure to electricity thus
the risk of electrocution. Considerable care must therefore be taken and appropriate personal
protective equipment used throughout the measurement of the different electrical
parameters. Damaged and exposed live parts of the circuits must also be repaired.
Other risks related to the project include the use of computers during research and writing of
reports where there is a risk of losing data, illness, eye, and back strains because of the
computer glare and bad sitting posture. Treatment for these risks includes having a back up
of the research on external drives and cloud storage, using a portable computer when ill to
minimize movement to the laboratories and library and decreasing the computer brightness
in order to reduce eye strain cases due to computer glare. Taking frequent breaks and using
adjustable chairs is a solution to back strains caused by bad sitting posture.