MOYLE HVDC INTERCONNECTOR CASE STUDY WHAT ARE THE CHALLENGES FOR MOYLE? High-voltage direct current (HVDC) interconnector staons are substaons for long-distance transport of electricity. These sta- ons (293.217 GW of power installed, under construcon or plan- ned worldwide) present heat losses (around 1%), parcularly in transformers (50% of heat losses) and thyristor valves (30%). The project was based on the quanficaon of the heat sources avai- lable and evaluaon of the best technologies for their recovery and use. Temperature and humidity control is fundamental in thyristor valve halls to ensure the working of the HVDC staon. Temper- ature in the hall must be kept lower than 40 °C to avoid overhea- ng of the thyristor valves, which can result in malfunconing and possible shutdown of the system. Relave humidity (RH) must be kept lower than 45% to avoid malfunconing, increase of losses for corona effect and rusng. Currently a fan-coil unit is used for temperature and humidity control, which removes the moisture by cooling and condensaon. The process is not energy efficient. WHAT ARE THE MOYLE’S OBJECTIVES? The main objecve of the Moyle interconnector (two poles with transmission capacity of 250 MW each) heat recovery project is the recovery of waste heat for the air-condioning of the thyristor valve hall. Once the heat available in thyristor valves and transformers was quanfied, the use of heat recovery from the transformers’ coolant fluid (temperature ranging between 55 and 85 °C) was considered the most promising approach to drive the H-DisNet technology. IS THE H-DISNET TECHNOLOGY A SOLUTION? The moisture removal ability of H-DisNet is attractive for the Moyle use case. Under the yearly outdoor air conditions, the moisture content is higher than the humidity threshold in the hall, meaning humidity removal is required most of the year to avoid malfunconing. Only the hoest days of summer require addional sensible cooling that can be performed by electrical or evaporave cooling. Given the heat available in HVDC staons and the worldwide use of the technology, use of the transformer’s waste heat to drive H-DisNet technology in this newly designed project for a thyristor valve hall’s air-condioning system is considered promising. Beer economic performance will be obtained in hoer and more humid climates. PAYBACK PERIOD: 8.7 years for retrofing project 6.1 years for new project with electric chiller 5 years for new project with evaporave chiller Figure: Moyle yearly outdoor air condion and thyristor valve hall requirements Figure: Current soluon of venlaon air system of thyristor valve hall LIMIT VALUES FOR TEMPERATURE AND HUMIDITY IN THRYSTOR VALVE HALL: Temperature lower than 40 °C (currently kept at 15 °C) Relave humidity lower than 45% Connuous flux of outdoor air is required CONTACT DETAILS Andrew Smallbone|[email protected] | Alessandro Giampieri | [email protected] Sir Joseph Swan Centre for Energy Research | [email protected] | www.H-DisNet.eu This project has received funding from the European Union’s Horizon 2020 research and innovaon programme under grant agreement 695780. 2018 © designed by accelopment AG

Upload: others

Post on 09-Feb-2022

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MOYLE HVDC INTERCONNECTOR

MOYLE HVDC INTERCONNECTORCASE STUDY

WHAT ARE THE CHALLENGES FOR MOYLE?High-voltage direct current (HVDC) interconnector stati ons are substati ons for long-distance transport of electricity. These stati -ons (293.217 GW of power installed, under constructi on or plan-ned worldwide) present heat losses (around 1%), parti cularly in transformers (50% of heat losses) and thyristor valves (30%). The project was based on the quanti ficati on of the heat sources avai-lable and evaluati on of the best technologies for their recovery and use.

Temperature and humidity control is fundamental in thyristor valve halls to ensure the working of the HVDC stati on. Temper-ature in the hall must be kept lower than 40 °C to avoid overhea-ti ng of the thyristor valves, which can result in malfuncti oning and possible shutdown of the system. Relati ve humidity (RH) must be kept lower than 45% to avoid malfuncti oning, increase of losses for corona effect and rusti ng. Currently a fan-coil unit is used for temperature and humidity control, which removes the moisture by cooling and condensati on. The process is not energy effi cient.

WHAT ARE THE MOYLE’S OBJECTIVES?The main objecti ve of the Moyle interconnector (two poles with transmission capacity of 250 MW each) heat recovery project is the recovery of waste heat for the air-conditi oning of the thyristor valve hall. Once the heat available in thyristor valves and transformers was quanti fi ed, the use of heat recovery from the transformers’ coolant fl uid (temperature ranging between 55 and 85 °C) was considered the most promising approach to drive the H-DisNet technology.

IS THE H-DISNET TECHNOLOGY A SOLUTION?The moisture removal ability of H-DisNet is attractive for the Moyle use case. Under the yearly outdoor air conditions, the mois ture content is higher than the humidity threshold in the hall, meaning humidity removal is required most of the year to avoid malfuncti oning. Only the hott est days of summer require additi onal sensible cooling that can be performed by electrical or evaporati ve cooling.

Given the heat available in HVDC stati ons and the worldwide use of the technology, use of the transformer’s waste heat to drive H-DisNet technology in this newly designed project for a thyristor valve hall’s air-conditi oning system is considered promising. Bett er economic performance will be obtained in hott er and more humid climates.

PAYBACK PERIOD:– 8.7 years for retrofitti ng project– 6.1 years for new project with electric chiller – 5 years for new project with evaporati ve chiller

Figure:Moyle yearly outdoor air conditi on and thyristor valve hall requirements

Figure:Moyle yearly outdoor air conditi on and thyristor valve hall requirements

Figure:Current soluti on of venti lati on air system of thyristor valve hall

LIMIT VALUES FOR TEMPERATURE AND HUMIDITY IN THRYSTOR VALVE HALL:– Temperature lower than 40 °C (currently kept at 15 °C)– Relati ve humidity lower than 45%– Conti nuous fl ux of outdoor air is required