motor setting sheet
DESCRIPTION
Induction Motor Thermal Setting GuideTRANSCRIPT
Sheet1
Page 1
Current for Calculating Trip Time 166 AmpI2 for calculating trip time 20 Amp%I2 12.04819277 % of FLCK 8 ConstantIeq 175.3738863 Amp
166 AmpIeq / IƟ 1.056469195 RatioTe1 30 MinutesTe2 30 MinutesTe3 53 MinutesThermal Element Trip Time 14.20539267 Minutes
I2 12TIME 25
I (Thermal Trip Setting)Ɵ
Sheet1
Page 2
Calculation of Thermal State of Motor (Pre-Fault)
Normal Running Current (=I1) 160healthy I2 1.5Running current (Ieq) 160.0562401Healthy (Ieq/I )Ɵ 0.964194218Time lapsed since Start 1000Time Constant for Motor 35
Running Thermal state of Motor ( )Ɵ 0.929670489
Assumed constant
Assumed as 35min