motor protection - wmea papers/0517_motor_protection_ge_grid_may17.pdf• setting of the motor...

35
Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions

Upload: dangdieu

Post on 07-Apr-2018

223 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

Motor Protection May 31, 2017

Tom Ernst

GE Grid Solutions

Page 2: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

22

Motor Relay Zone of Protection

-Electrical Faults-Abnormal Conditions-Thermal Overloads-Mechanical Failure

Page 3: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

33

• Setting of the motor protection relay is based

on the motor datasheets information and

system configuration

• Datasheets are normally provided by motor

manufacturer

• System configuration data can be obtained

from single line diagram

Page 4: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

44

CT Selection

869

Page 5: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

55

Phase CTs

• The CT should be nominally sized at or

greater than motor FLA

• The CT must have an accuracy class high

enough so that the current waveform

presented to the relay will allow the

overcurrent to operate

• Higher CT ratio is generally better from a

saturation point of view than a lower CT ratio

Page 6: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

66

Phase CTs

• Our Motor has a FLA of 413 Amps

• Our maximum fault current is 22KA

Page 7: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

77

Phase CTs

C100 400/5

INPUT PARAMETERS: ENTER: CALCULATED:

Inverse of sat. curve slope = S = 16 --- Rt = Total burden resistance = Rw + Rb = 0.295

RMS voltage at 10A exc. current = Vs = 125 volts rms pf = Total burden pow er factor = 1.000

Turns ratio = n2/1= N = 80 --- Zb = Total burden impedance = 0.295

Winding resistance = Rw = 0.195 ohms Tau1 = System time constant = 0.027

Burden resistance = Rb = 0.100 ohms Lamsat = Peak flux-linkages corresponding to Vs 0.469

Burden reactance = Xb = 0.004 ohms w = Radian freq = 376.99

System X/R ratio = XoverR = 10.0 --- RP = Rms-to-peak ratio = 0.37410

Per unit offset in primary current = Off = 1.00 -1<Off<1 A = Coefficient in instantaneous ie

Per unit remanence (based on Vs) = lrem 0.00 --- versus lambda curve: ie = A * l̂ S : 4.89E+06

Symmetrical primary fault current = Ip = 22,000 amps rms dt = Time step = 0.000083

Lb = Burden inductance = 0.00001

Thick lines: Ideal (blue) and actual (black) secondary current in amps vs time in seconds.Thin lines: Ideal (blue) and actual (black) secondary current extracted fundamental rms value, using a simple DFT with a one-cycle window.

-600

-400

-200

0

200

400

600

800

-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

Vs

amps rms

slope= 1/S

log-log plot,equal

decadespacing

voltsrms

Ie

mfgr'sdataVe

10

Saturation Curve

Saturated Magnitude Trace

Page 8: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

88

Phase CTs

C100 600/5

Increase the ratio - less saturation

INPUT PARAMETERS: ENTER: CALCULATED:

Inverse of sat. curve slope = S = 16 --- Rt = Total burden resistance = Rw + Rb = 0.300

RMS voltage at 10A exc. current = Vs = 125 volts rms pf = Total burden pow er factor = 1.000

Turns ratio = n2/1= N = 120 --- Zb = Total burden impedance = 0.300

Winding resistance = Rw = 0.200 ohms Tau1 = System time constant = 0.027

Burden resistance = Rb = 0.100 ohms Lamsat = Peak flux-linkages corresponding to Vs 0.469

Burden reactance = Xb = 0.004 ohms w = Radian freq = 376.99

System X/R ratio = XoverR = 10.0 --- RP = Rms-to-peak ratio = 0.37410

Per unit offset in primary current = Off = 1.00 -1<Off<1 A = Coefficient in instantaneous ie

Per unit remanence (based on Vs) = lrem 0.00 --- versus lambda curve: ie = A * l̂ S : 4.89E+06

Symmetrical primary fault current = Ip = 22,000 amps rms dt = Time step = 0.000083

Lb = Burden inductance = 0.00001

Thick lines: Ideal (blue) and actual (black) secondary current in amps vs time in seconds.Thin lines: Ideal (blue) and actual (black) secondary current extracted fundamental rms value, using a simple DFT with a one-cycle window.

-300

-200

-100

0

100

200

300

400

500

-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

Vs

amps rms

slope= 1/S

log-log plot,equal

decadespacing

voltsrms

Ie

mfgr'sdataVe

10

Saturation Curve

Page 9: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

99

Phase CTs

C200 600/5

Increase ratio & C-rating – almost no Saturation

INPUT PARAMETERS: ENTER: CALCULATED:

Inverse of sat. curve slope = S = 16 --- Rt = Total burden resistance = Rw + Rb = 0.300

RMS voltage at 10A exc. current = Vs = 300 volts rms pf = Total burden pow er factor = 1.000

Turns ratio = n2/1= N = 120 --- Zb = Total burden impedance = 0.300

Winding resistance = Rw = 0.200 ohms Tau1 = System time constant = 0.027

Burden resistance = Rb = 0.100 ohms Lamsat = Peak flux-linkages corresponding to Vs 1.125

Burden reactance = Xb = 0.004 ohms w = Radian freq = 376.99

System X/R ratio = XoverR = 10.0 --- RP = Rms-to-peak ratio = 0.37410

Per unit offset in primary current = Off = 1.00 -1<Off<1 A = Coefficient in instantaneous ie

Per unit remanence (based on Vs) = lrem 0.00 --- versus lambda curve: ie = A * l̂ S : 4.04E+00

Symmetrical primary fault current = Ip = 22,000 amps rms dt = Time step = 0.000083

Lb = Burden inductance = 0.00001

Thick lines: Ideal (blue) and actual (black) secondary current in amps vs time in seconds.Thin lines: Ideal (blue) and actual (black) secondary current extracted fundamental rms value, using a simple DFT with a one-cycle window.

-300

-200

-100

0

100

200

300

400

500

-0.017 0.000 0.017 0.033 0.050 0.067 0.083 0.100 0.117 0.133 0.150

Vs

amps rms

slope= 1/S

log-log plot,equal

decadespacing

voltsrms

Ie

mfgr'sdataVe

10

Saturation Curve

Page 10: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1010

Motor Performance Data Thermal Limit Curves

Motor Data Sheets

Page 11: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

11

Thermal Limit Curves:

B. Hot Running Overload B

A. Cold Running Overload A

D. Hot Locked Rotor CurveD

C

C. Cold Locked Rotor Curve

F. Acceleration curve @100%

voltage

F

E. Acceleration curve @ 80%

rated voltageE

Motor Thermal Limit Curves

Page 12: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

12

Motor Data Sheet Parameters

G. Temperature Rise, Insulation Class

G

J

J. Locked Rotor Time; Cold/Hot

K

K. Number of Starts per hour;

Cold/Hot

I. Locked Rotor Current

I

H. Full Load Current

H

Motor Thermal Parameters

Page 13: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1313

Information required to set Thermal

Model:

• Motor FLA

• Locked rotor current

• Locked rotor time hot & cold

• Stopped & running cool time constants

• Service factor

• Motor thermal damage curves

Motor Specifications

Page 14: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1414

Select CT Rating, Voltage Sensing Phase CT: The phase CT should be

chosen such that the FLA is 75% to 150%

of CT primary. Since the FLA is 297 a

300:5 CT may be chosen.

Ground CT: Zero sequence core balance

CT is used for high impedance grounded

systems. The primary rating should be

large enough to assure that the CT can

handle all potential fault ground levels

without saturating.

• 50 A >> systems with less than 50

amps of ground fault current.

• 200 A or 300 A >> systems with up to

300 amps of ground fault current.

• No ground CT required on low

impedance or solidly grounded

systems (Use neutral functions (3I0 is

calculated from the phase CTs).

• Secondary rating can be same as

phase CTs (1A/5A) or special 50:0.025

A.Voltage Sensing : Enter

the connection type,

secondary volts and ratio.

VTratio = 14400/120 =

120:1

Vsec = Vnom/VTratio =

13800/120 = 115 V

Settings Example

Page 15: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1515

Select FLA, Ground CTMotor FLA: Set as specified by the

data sheets.

Overload Factor: This is the pick-

up of the OL curve. Set 10-15%

above data sheet service factor.

NP Voltage, HP & Poles: Set as

specified in the data sheets.

Load Average Calc. Period: Set

this longer than the oscillatory

duration of oscillating loads like

reciprocal compressors. Set at 0

for non-oscillatory loads.

Max Acceleration Time: Set this to

the longest acceleration time

expected plus a margin (the

acceleration time trip function is

enabled separately - see

Protection > Group X >> Motor).

Settings Example

Page 16: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1616

Select Overload Curve for Thermal Model

Overload Curve

Set the overload curve below cold thermal limit and above hot thermal limit. If only hot curve

is provided by manufacturer, then must set at or below hot thermal limit

The best fitting curve is time dial multiplier 9 in this example.

Note that this is a 3 dimensional curve: f(A ,T, TCU), TCU = thermal capacity used. Curve

values given are for TCU = 0 (40 °C stator temp). The curve represents TCU = 100%.

Settings Example

Page 17: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1717

Select Overload Curve TD Multiplier for Thermal Model

Overload Curve

Set the overload curve TD multiplier below cold thermal limit and

above hot thermal limit. If only hot curve is provided by mfgr,

then must set at or below hot thermal limit. The best fitting curve

TD multiplier is 9 in this example.

This can be verified with Hot Stall Time of 30s at 540% FLA by

using the standard overload curve equation above.

Settings Example

Page 18: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1818

Select Overload Curve for Thermal Model

Settings Example

Select overload curve using Hot Stall Time and Locked Rotor Current when

Overload Curves are not available:

Example: For Hot Stall Time = 30s and LRA = 540% FLA

Substitute in the above equation:

30s = TD MULTIPLIER x 2.2116623

(0.02530337 x 4.42 + 0.05054758 x 4.4)

TD MULTIPLER = 30 x (0.02530337 x 4.42 + 0.05054758 x 4.4)

2.2116623

= 9.66

SELECT TDM 9 (which is below this intersection

point)

Page 19: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

1919

K=175/LRA 2 = 175/ 5.4 2 =

6

(Typical)

Determine Unbalance Bias K Factor for Thermal Model

Unbalance Bias Of Thermal Capacity

Enable the Unbalance Bias of

Thermal Capacity so that the heating

effect of unbalance currents is added

to the Thermal Capacity Used.

K=230/LRA 2 = 230/ 5.4 2 =

8

(Conservative)

Settings Example

Page 20: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2020

Stopped & Running Cool Time Constants

Stopped and Running Cool Time Constants

This information is usually supplied by the motor

manufacturer but is not part of the data that was given

with this motor. If RTD’s are present and will be wired to

the relay biasing of the thermal model will be used so it is

not critical to have these cooling times from the

manufacturer: the default values of 15 and 30 minutes can

be used for the running and stopped cool times

respectively.

Settings Example

Page 21: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2121

Hot/Cold Ratio =

30/35 = 0.86

Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 1)

Hot/Cold Curve Ratio

The hot/cold curve ratio is calculated by simply dividing the

hot safe stall time by the cold safe stall time or use the motor

thermal limits curve. For this example, both are available.

Using the data sheets the Hot/Cold Curve Ratio equals 30 / 35

= 0.86

COLD

HOT

LRT

LRTHCR

Settings Example

Page 22: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2222

Hot/Cold Curve Ratio

If the thermal limits curves are being used to determine

the

HOT/COLD ratio proceed as follows:

• From the thermal limits curves run a line perpendicular

to the current axis that intersects the hot and cold

curves at the stall point

• Draw lines from each points of intersection to the time

axis.

• Record the corresponding times. In this case, 6 and 8

seconds respectively.

• The Hot/cold ratio can now be calculated as follows:

= 6s/8s = 0.75

NOTE:

• If hot and cold times are not provided and only one

curve is given verify with the manufacturer that it is the

hot curve ( which is the worst case), then the Hot/ Cold

ratio should be set to 1.0

Overload Curve Method

LRC = 5.4FLA

LRTcold = 8sec

LRThot = 6sec

Determine Hot/Cold Safe Stall Ratio for Thermal Model (method 2)

Settings Example

Page 23: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2323

Determine RTD Bias Setpoints for Thermal Model

Enable RTD Biasing

This will enable the temperature from the Stator RTD sensors, to be

included in the calculations of Thermal Capacity. RTD bias model

determines the Thermal Capacity Used based on the temperature

of the Stator and is separate from the overload model for

calculating Thermal Capacity Used. RTD biasing is a back up

protection element which accounts for such things as loss of

cooling or unusually high ambient temperature. This measured

temperature is used to bias or modify the thermal capacity value

stored in the motor relay.

Settings Example

Page 24: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2424

RTD Bias Function

Set to Enabled/YES

RTD Bias Minimum

Set to 40 ° C which is the ambient temperature obtained from

the data sheets.

RTD Bias Center Point

The center point temperature is set to the motor’s hot running

temperature and is calculated as follows:

Temperature Rise of Stator + Ambient Temperature.

The temperature rise of the stator is 80 ° C + 10% hot spot

allowance, obtained from the data sheets.

Therefore, the RTD Center point temperature is set to 900C +

400C or 130 ° C.

RTD Bias Maximum

This setpoint is set to the rating of the insulation or slightly

less. A class F insulation is used in this motor which is rated at

155 ° C, so setting should be 155 ° C.

MAX POINT

TEMP: 155°C

TCU: 100%

MID POINT

TEMP: 130°C

TCU: 25%

MIN POINT

TEMP: 40°C

TCU: 0%

• Motor relay will use the calculated

thermal capacity unless the RTD thermal

capacity is higher.

• This feature will not trip the motor at the

max point temp unless the average

current is greater than the overload

pickup setting

Settings ExampleDetermine RTD Bias Setpoints for Thermal Model

Page 25: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2525

MAX POINT

TEMP: 155°C

TCU: 100%

MID POINT

TEMP: 130°C

TCU: 25%

MIN POINT

TEMP: 40°C

TCU: 0%

Settings ExampleDetermine RTD Bias Setpoints for Thermal Model

Page 26: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2626

Enable Start Inhibit

Enable Start Inhibit

This function will limit starts when the

motor is already hot. The motor relay

learns the amount of thermal capacity

used at start. If the motor is hot, thus

having some thermal capacity used, the

relay will not allow a start if the available

thermal capacity is less than the required

thermal capacity for a start.

If Start Inhibit is not used, must wait until

Thermal Capacity Used (TCU) falls below

15% before the motor can be re-started.

Using Start Inhibit allows one to start a

motor sooner.

Settings Example

Page 27: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2727

Thermal Capacity required to start

Thermal Capacity used due to

Overload

When the motor has cooled and the level of thermal

capacity used has fallen to 66%, a start will be

permitted.

If the motor had been running in an overload condition

prior to stopping, the thermal capacity would be some

value; say 80%.

For example, if the THERMAL CAPACITY USED for the

last 5 starts is 24, 23, 27, 25, and 21% respectively, the

LEARNED STARTING CAPACITY is 27% × 1.25 =

33.75% used.

If Motor is Stopped:

TCU / Start Inhibit Example

Page 28: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2828

Starts/Hr, Time Between Starts

Starts/Hour

Starts/Hour can be set to the # of cold starts as per the data sheet.

For this example, it is 2

Time Between Starts

In some cases, the motor manufacturer will specify the time between

motor starts. In this example, this information is not given so this

feature can be disabled or set at a typical 20 min between starts.

Settings Example

Page 29: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

2929

VFD Support Functions

Bypass Switch

If the VFD has a bypass switch then set this for the contact input that

is ON when the switch is closed.

Starting Frequency

Traditionally, the frequency tracking function started at 50/60 Hz and

then looked at zero crossings of several cycles to determine the

correct actual frequency. This caused the first 5 – 10 cycles of current

measurement to be wrong when the motor was started from a VFD.

Starting frequency feature allows the tracking to start at a more

realistic frequency (6 Hz in this case).

Settings Example

Page 30: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

3030

The Broken Rotor Bar element uses two different algorithms to

detect broken or cracked rotor bars:

Power Based Coherent Demodulation: This technique uses

multiplication of voltage and current samples thereby shifting

the fundamental to DC and fault frequency to lower closer to DC

value, to detect the broken rotor bar component. This method is

running when voltage is available and is meeting MOTOR

VOLTAGE SUPERVISION setting check.

Conventional current based FFT method: In case voltage is not

available or the voltage magnitude is lower than the MOTOR

VOLTAGE SUPERVISION setting value, the algorithm switches

to analyzing the frequency spectrum from current samples only,

to detect the broken rotor bar component.

Alarm settings are based on an increase in dB as each motor will

exhibit a different signature when healthy.

Broken Rotor Bar Detection

Advanced Diagnostics

Page 31: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

3131

FFT of Stator Current of

Induction Machine with

Rotor Bar Fault – signature

is only about 12 Hz off of

fundamental

Advanced Diagnostics - BRB

The FFT of the

resultant multiplied

signal – more

robust signature

than with the

current only FFT

method signal.

Page 32: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

3232

Pickup is set based on

initial in-service dB

measurements taken

when the motor is

known to be healthy

plus a change margin

(~15% increase).

Advanced DiagnosticsBRB

Page 33: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

3333

The Stator Inter-Turn Fault element uses sequence components to

detect stator turn failure of the induction machine.

Local heating caused by shorted turns can rapidly cause

additional damage to adjacent windings and stator iron

Alarm to avoid additional damage

Normalized cross-coupled impedance ratio:

Znp/Zpp = (V2 – Znn*I2)/V1 ~ 0 under balanced non-fault conditions

Zpp = positive sequence impedance

Znp = cross-coupled negative-to-positive sequence impedance

V1 = positive sequence voltage (motor terminals)

V2 = negative sequence voltage (motor terminals)

I2 = negative sequence current (motor terminals)

Znn = negative sequence impedance

Stator Inter-Turn Fault

Advanced Diagnostics

Page 34: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

3434

Operating quantity:

OP = Znp/Zpp –

ZUBbase

ZUBbase =

normalized

cross-coupled

impedance

ratio under

non-fault

conditions

Stator Inter-Turn Fault

Advanced Diagnostics

Page 35: Motor Protection - WMEA Papers/0517_motor_protection_ge_grid_may17.pdf• Setting of the motor protection relay ... volts rms pf = Total burden power factor = 1.000 Turns ratio = n2/1=

Thank You

Questions?