motor controllers1

Upload: prashurp

Post on 14-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Motor Controllers1

    1/33

    UNIT 17MOTOR CONTROL

    OBjECTIVESAfter studying this unit, the student will be able to

    list several methods of controlling a motor.

    describe the operation of a magnetic motor starter.

    explain overcurrent protection of a motor and motor circuit.

    determine the size of the components of a motor circuit.

    determine the size of wire for a group of motors.

    wire a start-stop station or a single-contact control device.

    identify common control devices from their schematic symbols.

    wire a simple control circuit from a control ladder diagram.

    discuss protection of motor control circuits.

    name the NEMA enclosure types and give an example of their applications.

    Electric motors present some special problems fromthe standpoint of control. An electric motor will try toprovide the power required by a load, even if it results inself-destruction. Therefore, a motor must be protectedfrom overloads. A motor draws up to six times as muchcurrent when the rotor is not turning as it does whenoperating at full speed. Control contacts, and wires mustbe capable of carrying this high current during startingwithout causing damage or excessive voltage drop. I f amotor should stall, the disconnect switch and controldevice must be capable of handling the high locked-rotorcurrent. For example, a 1 00-hp, 460- V, 3-phase electric

    motor powering an irrigation pump draws 124 A whenoperating at full load. The locked-rotor current of themotor, however, is nearly 750 A, NE C Table 430-151.The motor starter and disconnect switch must be capableof interrupting 750 A in the event the motor stalls. If thedisconnect or controller is not rated fo r this high level ofcurrent, it could explode the instant it is opened.

    Motor circuits will' be safe and motors will be protected provided the wiring procedures of NE C Article430 are applied. Proper sizing of motor overload protection will ensure many years of dependable service.

    Unit 17 Motor Control 347

  • 7/27/2019 Motor Controllers1

    2/33

    TYPES OF MOTOR CONTROLLERS

    A controller is simply a means of closing the circuitsupplying power to an electrical motor, NEC 430-81 (a).Controlling may be accomplished manually or automatically. The simplest motor controller is an attachmentplug and receptacle. This method is permitted only forportable motors rated at 1/1 hp and less, NEC Section430-81(c). Motors larger than 113 hp are permitted to becord connected, but the starting and stopping of themotor must be accomplished by one of the means discussed next.

    The branch-circuit protective device, such as a circuit breaker, may serve as the controller for stationarymotors, not larger than IJs hp, that are normally allowedto operate continuously. An example is a clock motor,NEC Section 430-8l(b). These motors are designed witha high impedance, and they cannot be overloaded even ifthe rotor stalls.

    A time-delay circuit breaker is permitted to serve as amotor controller, NEC Section 430-83, Exception No.2.This is frequently the case with farm machinery. Circuitbreakers are subject to failure after repeated on and offcycling and, therefore, they are not the best choice for acontroller. It is also difficult to size a circuit breakersmall enough to provide overload protection for themotor, and still not trip due to the high inrush startingcurrent of the motor.

    A fusible knife switch, Figure 17-1, can serve as amotor controller, provided the switch has a horsepowerrating sufficient for the motor supplied, NEC Section

    Figure 17-1 A fusible knife switch may be used as a motorcontroller.

    342 Unit 17 Motor Control

    430-90. Time-delay fuses can usually be sized smallenough to provide overload protection, and still not blowduring starting. The knife switch must be rated in horsepower, NE C Section 430-83. The switch must also havea voltage rating sufficient for the circuit. A 250-V switch

    is required for motors operating at 120 V, 208 V, a240 V. A 600-V switch is required for motors operatingat 277 V or 480 V.

    An ordinary snap switch rated in amperes or horsepower is permitted to be used as a controller for motorsrated at not more than 2 hp, and for circuits operatingnot more than 300 V, NEC Section 430-83, ExceptionNo.1 .

    The general-use snap switch must have an amperating twice that of the full-load current of the motor.1/1-hp motor, for example, draws 7. 2 A full-load curreat 115 V. A general-use snap switch with a 15-A ratingwould be required for this motor.

    7. 2 A X 2 = 14.4 A

    Switches rated for use only on alternating-current ccuits are permitted to control motors with a full-load crent of 80% of the current rating of the switch. Therefore, a 30-A ac switch is permitted to supply a motowhich draws 24 A.

    30 A X 0.8 = 24 A

    A 2-hp electric motor operating at 115 V draws 24 ASnap switches for motors are available which do pro

    vide overload protection, Figure 17-2. This type oswitch, rather than an ordinary switch, is preferredcontrolling motors up to 2 hp.

    A manual motor starter rated in horsepower providereliable control and overload protection for motors upabout 5 hp single phase, and 10 hp 3 phase, Figure 17A thermally activated trip mechanism opens the motecircuit automatically if an overload occurs. The overloaheaters are sized based upon the full-load current ratinof the motor. Manual motor starters are availableboth single- and 3-phase motors.

    Magnetic motor starters use an electric solenoid coto close the contacts and start the motor, Figure 17These motor starters may be operated by a person acttally activating a starting control, or they may be operateautomatically. Only the magnetic motor starter can bcontrolled automatically. Magnetic motor startersoperate motors of up to several hundred horsepowe

  • 7/27/2019 Motor Controllers1

    3/33

    Figure 17-2 A motor controller with a maximum rating of

    2 hp (Courtesy o f Square D Company)

    Thermally activated overload relays break the circuit tothe coil of the starter if a motor overload occurs. Theoverload heaters are sized for the nameplate full-loadcurrent of the motor.

    Figure 17-3 Manual motor star ter (Courtesy o f Square DCompany)

    Figure 17-4 Magnetic motor starter (Courtesy o f SquareD Company)

    MAGNETIC MOTOR STARTERCONSTRUCTION AN DOPERATION

    Understanding the operation and components of amagnetic motor starter is important when wiring a motorcircuit, as well as when performing repairs when there isa malfunction. Only one manufacturer's motor starter isshown in the text, but all have essentially the same features.

    The main contacts, Figure 17-5, are inside the mainpart of the starter. After many years of service, thesecontacts may become pitted and burned from the arcingas they open the circuit. Replacement kits for the maincontacts are available.

    Electrical power supplied to the coil of the solenoidcloses the motor-starter contacts. The coil must be ratedfor the voltage of the control circuit electrical supply,Figure 17-6. Typical voltages are 24, 120, 208, 240,277, and 480 volts. A coil is replaceable. If the coilbecomes damaged, only the coil need be replaced. The

    steel solenoid core fits all coils made for the particularsize and model of motor starter.An auxiliary holding contact, Figure 17-7, is sup

    plied with the motor starter. It is required when a startstop station is used as the control device. The holdingcontact is replaceable should a short circuit occur in thecontrol wiring, causing damage to the holding contact.

    Unit 17 Motor Control 343

  • 7/27/2019 Motor Controllers1

    4/33

    Figure 1 7-5 The main contacts in a motor starter can bereplaced if they become pitted and burned.

    An overload relay section is added to the motorstarter to sense motor current. This entire unit can beremoved from the motor starter, Figure 17-8. A normallyclosed contact is usually sealed inside the overload section. Some models have one normally closed contact,while others have two or three. I f this section becomesdamaged, the entire section usually must be replaced.

    Figure 17-6 The magnet ic coil of a motor starter must berated for the particular control voltage. The coil can bereplaced.

    34 4 Unit 17 Motor Control

    Figure 17-7 The holding contact or interlock may becomedamaged if a short circuit occurs in th e control circuit. Theholding contact can be replaced.

    Heating elements are added to this section sized for thenameplate full-load current of the motor. These overloadheaters are replaceable.

    NEMA SIZES

    The National Electrical Manufacturers Association(NEMA) has developed a standard numbering system fo;motor starter sizes. The same numbering system is useby all manufacturers. The sizes range from 00 to 8. Thelarger the number, the greater is the horsepower rating of

    Figure 1 7-8 Overload thermal units or heaters mustsized for th e full-load current of th e motor.

  • 7/27/2019 Motor Controllers1

    5/33

  • 7/27/2019 Motor Controllers1

    6/33

    Figure 17-10 N EMA 4X, corrosion-resistant enclosure forwe t or dusty areas

    NEMA 7: Explosionproof enclosure suitable for installation in Class I areas containing hazardous vapors. Mustalso be rated for the type of hazardous vapor, such asgasoline vapor, Group D, Figure 17-1 1.NEMA 9: Dust-Ignition-Proof enclosure suitable fo r installation in Class II hazardous areas, such as grain elevators. Must be rated fo r the type of dust, such as grain

    Figure 17-11 NEMA 7, expiosionproof enclosure for areaswhere hazardous vapors, such as gasoline vapor, arepresent

    34 6 Unit 17 Motor Control

    Figure 17-12 NEMA 9, dust-ignition-proof enclosure fareas where dust is suspended in th e air and may cause fire or explosion, such as a commercial grain elevator

    dust, Group G, Figure 17-12. Some manufacturers buion e enclosure rated as NEMA 7 and 9.NEMA 12: Dusttight, driptight, and oil-retardant enclosure suitable for machine tools and areas where there aflammable flying particles, such as in cotton gins andtextile processing and handling operations.

    SINGLE-MOTOR BRANCHCIRCUiT

    A motor branch circuit consists of several differenparts that must be sized properly. The motor is uniqu

    because it draws a very high starting current in comparison to the full-load running current. The motor also rnstall or break down while in operation. Means mustprovided to disconnect power, usually automatically, i

    failure occurs. The components of most motor c i r c

    are shown in a diagram at the beginning of NE C Articl430. Information supplied on the motor nameplatenecessary for sizing th e circuit components.

    Branch-circuit disconnect Branch-circuit short-circuit and ground-fault protec

    tion Branch-circuit wires Motor controllet Motor running overload protection Motor control circuit where a magnetic motor starte

    used.

    Sizing the motor branch circuit begins with the motonameplate. Consider the motor nameplate of Figure13. The motor is 3 phase, dual voltage. First, determin

  • 7/27/2019 Motor Controllers1

    7/33

    s

    r

    e

    @- L

    ~ i i i i i i i i i i i i i i i i i l $ ~ LgNM O D - FR WUiM:\ 'o11'!'1 2 3 T N

    HP . . PM lmiJ PH IJ HZm!J C A ~ L s ~ s Ev. . IEEJ P.F.IImJI AM8C II!l cV IIIliiJI A l iD EFF & J I DESIGN EJ

    0 0~

    1V - A - S . F . I D I CODE I I 0@d) 0 0~ ~ : : : : : .Mlt!: g ~ ~END M . . : . l f r ~ 4 U I I - - ( i) (2J (3 ) ~ ~DUTY Y ' Y y

    Figure 17-13 Information required for wiring a motorbranch circuit is contained on th e motor nameplate.

    the type of electrical supply available. Assume, in thiscase, that the electrical supply is 240 V, 3 phase. Themotor full-load current therefore, will be 19.2 A.

    The type of electrical equipment from which themotor circuit will originate must be determined. Com

    mon sources of electrical power for electric motors are:1. Circuit-breaker panelboards2. Fusible panelboards3. Fusible disconnects tapped from a feeder, Figure

    17-144. Fusible disconnects tapped from a bus duct

    MOTOR FULL - LOAD CURRENTThe motor full-load current that is used to determine

    the minimum size of motor circuit components is thecurrent listed in NEC Tables 430-148 and 430-150 (Tables 17-2 and 17-3 in this text), NEC Section 430-6(a).However, this value should be checked against the motornameplate ampere rating. Sometimes a farm motor mayhave an ampere rating higher than the value listed in theNE C Tables. In this situation, the higher of the values

    Feederin

    Fusibledisconnect

    Motor

    starters

    To motors

    Figure 17-14 A group of motors tapped from a singlefeeder, using fusible switches as disconnects

    should be taken for sizing components, (See notes toTables 17-2 and 17-3).

    The nameplate current rating must be used for selecting the maximum size motor running overload protection. This is important because the overload heaters must

    be sized for a specific motor. If motors are changed, thenthe overload heaters may have to be changed.The full-load current for a 3-phase, 208-V electric

    motor is not listed in NE C Table 430-150. The footnoteat the bottom of the table tells how to obtain the correctvalue. Actually, a 208-V motor usually operates at about200 V. The correct value is determined by multiplyingthe full-load current for a 230-V motor by 1.15. Forexample, a 200- V, 10-hp motor would draw 32 A.

    Table 17-2 (NEC Table 430-148) Full-load currents inamperes; single-phase alternating-current motors

    The following values of full-load currents are for motorsrunning at usual speeds and motors with normal torquecharacteristics. Motors built for especially low speeds orhigh torques may have higher full-load currents, and multi-

    . speed motors will have full-load current varying withspeed, in which case the name-plate current ratings shall beused.

    To obtain full-load currents of 208- and 200-volt motors, increase corresponding 230-volt motor full-load currents by 10 and 15 percent, respectively.

    The voltages listed are rated motor voltages. The currents I sted shall be permitted for system voltage ranges of110 to 120 and 220 to 240.

    HP 115 v 230 v1j6 4.4 2.21/4 5.8 2.91/3 7.2 3.61/2 9.8 4.9:% 13.8 6.9

    1 16 81 1j2 20 102 24 123 34 17

    5 56 287 1/2 80

    4010 100 50

    Reprinted with permission from NFPA 70-1984, National ElectricalCode, Copyright 1983, National Fire Protection Association,Quincy, Massachusetts 02269. This reprinted material is not the complete and official position of the NFPA on the referenced subject whichis represented only by the standard in its entirety.

    Unit 17 Motor Control 34 7

  • 7/27/2019 Motor Controllers1

    8/33

    Table 17-3 (NEC Table 430-150) Full-load current* 3-phase alternating-current motors

    Induction Type Synchronous TypeSquirrel-Cage and Wound-Rotor t Unity Power Factor

    Amperes Amperes

    HP 115 v 230 v 460 v 575 v 2300 v 230 v 460 v 575 v 2300 v1/2 4 2 1 .8% 5.6 2.8 1.4 1 1

    1 7.2 3.6 1.8 1.4

    1 1/2 10.4 5.2 2.6 2.12 13.6 6.8 3.4 2.73 9.6 4.8 3.9

    5 15.2 7.6 6.17 1/2 22 11 9

    10 28 14 11

    15 42 21 1720 54 27 2225 68 34 27 53 26 21

    30 80 40 32 63 32 2640 104 52 41 83 41 3350 130 65 52 104 52 42

    60 154 77 62 16 123 61 49 1275 192 96 77 20 155 78 62 15

    100 248 124 99 26 202 101 81 20

    125 312 156 125 31 253 126 101 25150 360 180 144 37 302 151 121 30

    1 48o 1 24o 1 192 49 1 4oo 1 201 161 40

    For full-load currents of 208- and 200-volt motors, increase the corresponding 230- volt motor full-loadcurrent by 10 and 15 percent, respectively.

    *These values of full-load current are for motors running at speeds usual for belted motors and motors

    with normal torque characteristics. Motors built for especially low speeds or high torques may requiremore running current, and multispeed motors will have full-load current varying with speed, in whichcase the nameplate current rating shall be used.

    t For 90 and 80 percent power factor the above figures shall be multiplied by 1 1 and 1 25 respectively.

    The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltageranges of 110 to 120, 220 to 240, 440 to 480, and 550 to 600 volts.

    Reprinted with permission from NFPA 70-1984, National Electrical Code, Copyright 1983, National FireProtection Association, Quincy, MA. This reprinted material is not the complete and official position of theNFPA on the referenced subject which is represented only by the standard in its entirety.

    DISCONNECT FO R ASINGLE MOTOR

    troller, NEC Section 430-102. The definition of ' ' in sigfrom" in NEC Article 100 means that the controllernot more than 50 ft (15. 24 m) from the disconnect, an'

    that the controller is actually visible when standing at tdisconnect location.

    A disconnect for a motor branch circuit must be capable of interrupting the locked-rotor current of themotor. This disconnecting means must disconnect boththe motor and the controller from all ungrounded supplyconductors, NEC Section 430-103. The disconnectingmeans must be located within sight from the motor con-

    34 8 Unit 17 Motor Control

    A fusible switch serving as the motor circuit disconnecting means must be rated in horsepower, NEC Section 430-109. A circuit breaker serving as a disconnecting means is not required to be rated in horsepower but

  • 7/27/2019 Motor Controllers1

    9/33

    instead will be rated in amperes, NE C Section 430-109.This circuit breaker must have an ampere rating not lessthan 115% of the motor full-load current, NE C Section430-110(a).

    There are exceptions to these rules for motor disconnects. Motors with a horsepower rating not greater than1/s hp may use the branch-circuit overcurrent device asthe disconnect, NE C Section 430-109, Exception No. 1.If the motor is not larger than 2 hp, and operates at notmore than 300 V, a general-use switch may serve as thedisconnect, NE C Section 430-109, Exception N o . 2 . Theswitch must have an ampere rating at least twice that ofthe full-load current of the motor. An ac switch used onan ac circuit need only be rated at 1. 25 times the fullload current of the motor.

    Cord- and plug-connected motors may use an attachment plug and receptacle as the motor disconnect. Thistype of disconnect would be used for motors on portableor movable equipment used on the farm. The plug andreceptacle should have a horsepower rating not smallerthan the rating of the motor if it is intended to breakpower while operating, NE C Section 430-109, ExceptionNo. 5. The current rating of the attachment plug andreceptacle must be not less than 115% of the full-loadcurrent of the motor.

    A fusible switch or a circuit breaker is permitted toserve as both the controiler and disconnect, NE C Section430-111. However, the requirements for motor controllers discussed previously must be met.

    Assume that the motor of Figure 17-13 will have a

    fusible switch as the disconnect. The disconnect switchmust have a rating marked on the switch of at least71/2 hp. However, if a circuit breaker serves as the disconnect, the rating will be in amperes. The minimumampere rating of the circuit breaker is 1. 15 times thefull-load current, or 25 A. A 25-A or 30-A circuitbreaker would be chosen. A circuit breaker rated at 30 Aor more would most likely be chosen, because a 25-Abreaker would probably trip due to the high starting current. The value of current from NE C Table 430-150 isused, rather than the nameplate current of 19.2 A.

    1. 15 X 22 A = 25 A

    BRANCH-CIRCUIT WIRESThe wires supplying a single motor shall have an

    ampere rating not less than 1.25 times the full-load current of the motor. For a multispeed motor, the highest

    normal full-load current shall be used, NE C Section430-22(a).

    The minimum ampere rating of the circuit wires forthe motor of Figure 17-13 is 28 A.

    1 25 X 22 A = 28 A

    The minimum size copper branch-circuit wire is found inNEC Table 310-16 (included in Unit 9 of this text). I f thewire is THWN copper, the minimum size is No. 10AWG. The footnote at the bottom of NEC Table 310-16which specifies the maximum rating overcurrent devicefor wire sizes No. 14, 12, and 10 AWG does not apply inthe case of electric motor circuits, NE C Section 210-19( a). Aluminum wire is seldom used for motor circuits.Most terminals in motor starters are rate only for copperwire.

    Problem 17-1A single-phase, 5-hp, 230-V electric motor has a

    nameplate current rating of 26 A. Determine the minimum size copper THWN branch-circuit wire.

    SolutionLook up the full-load current of a 5-hp single-phase,

    230-V motor in NE C Table 430-148. The current value is28 A. The minimum ampere rating of the wire is 35 A.

    1.25 X 28 A = 35 A

    SHORT-CIRCUIT PROTECTIONA branch circuit supplying a single motor is only

    subjected to excessive current caused by motor overloadsor by ground faults and short circuits. Sometimes, a single overcurrent protective device protects against allthree conditions while, in many instances, overload protection and protection from ground faults and short circuits are provided separately. First, consider them separately, and size the short-circuit and ground-faultprotection for the branch circuit. The overcurrent device

    is either a fuse or a circuit breaker placed at the beginning of the circuit, Figure 17-15.

    The short-circuit and ground-fault protection must becapable of carrying the starting current of the motor,NE C Section 430-52. The maximum rating of a timedelay fuse or an inverse time circuit breaker is determined using NE C Table 430-152 (Table 17-4 in this

    Unit 17 Motor Control 34 9

  • 7/27/2019 Motor Controllers1

    10/33

    Wire sized at 125%of full-load current

    Motor controller

    1 1 - - ~ - - - : - ~ - - - - ~ ~l _ ~ _ r _ J

    . . . \ Overload protection

    Short-ctrcutt and Main contactsgrou nd-fau Itprotection

    Figure 17-15 Parts of a motor branch circuit

    text). An inverse time circuit breaker is an ordinary circuit breaker which provides short -circuit protection, butit will carry an overload for a limited period of time. Thecode letter given on the nameplate of the motor is neededto determine the maximum size short-circuit and groundfault protection. The motor of Figure 17-13 has a codeletter J. This is an ac 3-phase squirrel-cage motor; therefore from NE C Table 430-152, the maximum size timedelay fuse is 175% of the motor full-load current, or39 A. The motor full-load current must be taken fromNEC Table 430-150. The maximum size inverse timecircuit breaker would be 250% of the motor full-loadcurrent, or 55 A.

    The motor short-circuit and ground-fault protectivedevice should be sized as small as possible without causing nuisance tripping. Remember that the minimum sizein the case of a circuit breaker is 1.15 times the full-loadcurrent of the motor, NEC Section 430-58. The motor ofFigure 17-13 is shown in Figure 17-16 with all components sized within the limits of the National ElectricalCode. A suggested procedure is to determine the overcurrent protection size, using the value determined inNEC Table 430-152. I f the motor is not driving a hardstarting load, then choose the next smaller protectivedevice than the value determined. If this is too small,then choose the next size larger. In no case is the fusepermitted to be sized larger than 225% of the full-loadcurrent, NE C Section 430-52, Exception No. 2(b). Fo r acircuit breaker, the maximum size is not permitted toexceed 400% for a motor drawing 100 A or less, and300% for motors drawing more than 100 A, NE C Section 430-52, Exception No. 2(c).Fuse:

    1.75 X 22 A = 38 A

    (Use a 35-A or 40-A fuse.)

    35 0 Unit 77 Motor Control

    Disconnect switchrated 7 1/2 hp

    Time-delayfuse, 30 A or35 A

    Circuit breakE40 A or 50 A

    THWN No. 10 copper - - - . . . . . . q J' t ' - - - - wire, 30 A

    Motor controller,1-4- - - - - - NEMA Size 1 - - - J o o o j

    Motor,7 1/2 hp,3-phase,230 v.

    code letter Jnameplate amperes: 19NEC Table 430-7 50 amperes: 22

    Figure 17-16 Properly sized components of a motor circuit

    Circuit breaker:

    2.5 X 22 A = 55 A

    (Use a 50-A or 60-A breaker.)

    Problem 17-2A single-phase, 5-hp 230- V electric motor with

    nameplate full-load current of 26 A drives a normalstarting load and has a code letter G. Determine thproper size motor short-circuit protective time-delafuse.

    SolutionDetermine the full-load current from NE C Table 430

    148 and the fuse multiplier from NEC Table 430-152

    Full-load current: 28 AFuse multiplier: 175%1. 75 X 28 A = 49 A

    Use a 50-A fuse. The minimum wire size is No.AWG copper THWN with a rating of 35 A.

  • 7/27/2019 Motor Controllers1

    11/33

    Table 17-4 (NfC Table 430-152) Maximum rating or setting of motor branch-circuit shortcircuit and ground-fault protective devices

    Percent of Full-load Current

    DualElement In stan-

    Nontime (Time- taneous *InverseDelay Delay) Trip Time

    Type of Motor Fuse Fuse Breaker Breaker

    Single-phase, all typesNo code letter . . . . . . . . 300 175 700 250

    All ac single-phase andpolyphase squirrel-cage andsynchronous motorst withfull-voltage, resistor or reactorstarting:

    No code letter . . . . . . . 300 175 700 250Code letter F to V . . . . . 300 175 700 250Code letter B to E . . 250 175 700 200Code letter A 0 . . . 150 150 700 150

    All ac squirrel-cage andsynchronous motorst withautotransformer starting:

    Not more than 30 ampsNo code letter . . . . . . 250 175 700 200

    More than 30 ampsNo code letter . . . . . . 200 175 700 200Code letter F to V . . . . 250 175 700 200Code letter B to E . . . . . . 200 175 700 200Code letter A . . . . . . . . 150 150 700 150

    High-reactance squirrel-cageNot more than 30 amps

    No code letter .... . . 250 175 700 250More than 30 amps

    No code letter . . . . .. 200 175 700 200W o u n d - r o t o r ~

    No code letter ........ 150 150 700 150Direct-current (constant voltage)

    No more than 50 hpNo code letter . . .. 150 150 250 150

    More than 50 hpNo code letter . . . . 150 150 175 150

    For explanation of Code Letter Marking, see Table 430-7(b).For certain exceptions to the values specified, see Sections 430-52 through 430-54.

    *The values given in the last column also cover the ratings of nonadjustable inverse time types ofcircuit breakers that may be modified as in Section 430-52.

    tSynchronous motors of the low-torque, low-speed type (usually 450 rpm or lower), such as are usedto drive reciprocating compressors, pumps, etc. that start unloaded, do not require a fuse rating orcircuit-breaker setting in excess of 200 percent of full-load current.

    Reprinted with permission from NFPA 70-1984, National Electrical Code, Copyright 1983, National FireProtection Association, Quincy, MA. This reprinted material is not the complete and official position of theNFPA on the referenced subject which is represented only by the standard in its entirety.

    Unit 17 Motor Control 351

  • 7/27/2019 Motor Controllers1

    12/33

    Problem 17-3

    Determine the proper size inverse time circuitbreaker to provide ground-fault and short-circuit protection.

    Solution

    Circuit breaker multiplier: 250%2.5 X 28 A = 70 A

    Use a 60-A breaker, if possible. I f it is too small, thenchoose a 70-A breaker.

    It is permissible to have an overcurrent device sizedlarger than the allowable ampere rating of the wire. Forexample, a 70-A circuit breaker can protect a No. 10AWG copper THWN wire with a maximum rating of35 A. It must be remembered that the purpose of thiscircuit breaker is to protect against ground faults andshort circuits only. Overload protection not exceedingthe ampere rating of the wire is provided usually in theform of thermal overload heaters in the motor starter. Aslong as properly sized overload protection is providedsomewhere in the circuit, the short-circuit fuse or circuitbreaker protection is permitted to exceed the ampere rating of the motor branch-circuit wire.

    R U l \ J l \ 1 1 / " ~ GOVERCURRENTPROTECTION

    Electric motors are required to be protected againstoverload, NEC Section 430-32. Overload protection is

    usually p rovided as a device responsive to motor currentor as a thermal protector integral with the motor. A device responsive to motor current could be a fuse, a circuitbreaker, an overload heater, or a thermal reset switch inthe motor housing. An automatically resetting thermalswitch placed in the windings will sense winding temperature directly.

    The service factor or temperature rise must be knownfrom the motor nameplate when selecting the proper sizemotor overload protection. These are indicators of theamount of overload a motor can withstand. I f a motorhas a service factor of 1 15 or greater, the manufacturerhas designed extra overload capacity into the motor. In

    this case, the overload protection may be sized as largeas 125% of the nameplate full-load current. Internal heatis damaging to motor-winding insulation. A motor with atemperature rise of 40C ( 104 oF) or less has bee n designed to run relatively cool; therefore, it has greateroverload capacity. The ove rload protection may be sized

    35 2 Unit 17 Motor Control

    as large as 125% of the nameplate full-load current. Aservice factor of less than 1. 15 or a temperature rise omore than 40C ( 104 F) indicates little overload capacity. The overload protection unde r these circumstances issized not larger than 115% of the nameplate full-loacurrent.

    Size the motor overload protective device at not morethan these percents of nameplate full-load current:

    Service factor 1 15 or greater, 125% Temperature rise not greater than 40C (1 04 oF), 125% Service factor smaller than 1. 15, 115% Temperature rise greater than 40C (104F), 115%

    A time-delay fuse may serve as motor overload protection. Plug fuses or cartridge fuses are used for smallmotors. The fuse size is determined by selecting tproper multiplying factor, 1.15 or 1.2 5, based upon tservice factor and temperature rise. Standard fuse sizessmaller than 30 A are listed in Unit 6.

    Problem 17-4

    A %-hp, single-phase water pump motor is operatecat 230 V and full-load current of 6. 9 A. The motor hasservice factor of 1.15 and a code letter K. Determine t

    maximum size time-delay fuses permitted to serverunning overload protection.

    Solution

    The full-load current from NEC Table 430-1486.9 A. With a service factor of 1.15, the overload protective device may be 1. 25 times the full-load current

    1.25 X 6.9 A = 8. 6 A

    Choose an 8-A fuse (refer to fuse sizes listed in Unit 6I f an 8-A fuse will not work, then the next larger size.9 A, may be used provided it does not exceed 140%the motor nameplate current, 1. 4 X 6. 9 A 9. 7 ANEC Section 430-34.

    Circuit breakers could be used as running overloacprotection, but they are not available in small-ampensizes. I f they are used for large motors, they will usuall)trip on starting if they are sized small enough to provid'overload protection.

    Magnetic and manual motor starters have an overload relay or trip mechanism which is activated by ;heater sensitive to the motor current. Typical motor overload heaters are shown in Figure 17-17. The manufacturer of the motor starter provides a chart inside th'motor starter listing the part number for thermal overloa

  • 7/27/2019 Motor Controllers1

    13/33

    J

    Figure 17-17 Overload thermal sensing units or heaterstrip an overload relay if the motor current becomes excessive.

    heaters. The heaters are sized according to the actualfull-load current listed on the motor nameplate. Find theheater number from the manufacturer's list corresponding to the motor nameplate full-load current. A typicalmanufacturer's overload heat selection chart is shown inFigure 17-18.

    An example will help to learn how the overload

    (J)

    0..E('(jX

    L.J.J~

    MOTORFULLLOAD

    CURRENT(AMP.)

    0.28-0.300.31-0.340.3!>-0.370.38-0.440.45-0.530.54-0.590.60-0.640.65-0.720.73-0.800.81-0.900.91-1.031.04-1.141.15-1.271.28-1.431.441.621.63-1.771.78-1.971.98-2.32

    2.332.512.52-2.993.00-3.423.433.753.76-3.983.994.48

    MAXIMUMTHERMAL FUSEUNIT RATINGNO.(AMP.)

    B 0.44 0.6B 0.51 0.6B 0.57 0.6B 0.63 0.8B 0.71 1B 0.81 1.125B 0.92 1.25B 1.03 1.4B 1.16 1.6B 1.30 1.8B 1.45 2B 1.67 2.25B 1.88 2.5B 2.10 2.8B 2.40 3.2B 2.65 3.5B 3.00 4B 3.30 48 3.70 5B 4.15 5.6B 4.85 6.25B 5.50 7B 6.25 8B 6.90 8

    MOTORMAXIMUMFUll THERMAL

    FUSE ~OAD UNIT RATINGCURRENT NO.(AMP'.) :(AMP.)

    4.494.93 B 7.70 104.94-5.21 8 8.20 105.22-5.84 B 9.10 105.85-6.67 B 10.2 126.68-7.54 811.5' 157.55-8.14 B 12.8 158.15-8.72 8 14 17.58.73-9.66 8 15.5 17.59.67-10.5 8 17.5 20

    10.6-11.3 8 19.5 20600V 250VMax. Max.

    11.4-12.0 8 22 20 25Following Selactions for Size 1 Only11.4-12.7 B 22 25 2512.8-14.1 B 25 25 2514.2-15.9 8 28.0 30 30

    16.0-17.5 B 32 30 3517.6-19.1 B 36 30 3519.8-21.9 B 40 30 40

    22.0-24.4 B 45 30 4024.5-26.0 B 50 30 40

    Figure 1 7-18 Manuf actur er's chart for selecting overloadthermal sensing unit (Courtesy of Square D Company)

    heater chart is used. A 3-phase motor nameplate fullload current for 230-V operation is 1. 5 A. The properoverload heater to use is thermal unit No. B 2.40. TheNE C allows this heater to be sized at 125% of the motornameplate full-load current provided the service factor is1. 15 or larger, or the temperature rise is not greater than

    40C (104F). Th e manufacturer has taken this into consideration when setting up the chart. I f the service factoris less than 1.15 or if the temperature rise is greater than40C ( 104 F), then the heater will be 10% oversized.The motor is then vulnerable to burnout. I f the motorservice factor is less than 1.15, multiply the motor fullload curr ent on the nameplate by 0. 9 and use this newvalue to size the overload heater. For the example, multiplying 1.5 A by 0. 9 gives 1.35 A. Th e overload heatercorr espon ding to 1 .35 A is a thermal unit No. B 2.1 0.

    A thermal protector integral with the motor and installed by the manufacturer is permitted to serve as theoverload protection, NEC Section 430-32(a)(2). Th e

    manufacturer is required to size the thermal protectoraccording to the multiplying factors in the NEC.

    Th e number of overload protective devices requiredfor a motor is specified in the NEC. I f fuses are used, onefuse shall be placed in each ungrounded conductor supplying the motor, NE C Section 430-36. The number ofthermal overload heaters is specified in NEC Table 430-37. The minimum is one for a single-phase motor, andthree for a 3-phase motor.

    The rules for sizing components for a single-motorbranch circuit are summarized in Figure 17-19.

    Problem 17-5A single-phase, 3-hp electric motor operates at

    230 V, and draws 17 A full-load current. The servicefactor is 1. 2 and the code letter is M. The motor disconnect is a fusible switch and the controller is a magneticmotor starter. Determine the following:

    1 Minimum rating disconnect switch2. Minimum NEMA size motor starter3. Minimum size copper TH W wire4. Time-delay fuse size for short-circuit and ground

    fault protection5. Proper overload heater from the chart in Figure 17-18

    Solution1. The disconnect switch must be rated in horsepower;

    therefore, the minimum is 3 hp.2. Using Table 17-1 , the minimu m size motor starte r for

    a single-phase, 3-hp motor is NEMA Size 1.

    Unit 17 Motor Control 353

  • 7/27/2019 Motor Controllers1

    14/33

    Motor starterNEMA Size

    r " " \- - / - - - - - f r - - ~

    Circuit breakerfor short-circuitprotection anddisconnect, not moreth

  • 7/27/2019 Motor Controllers1

    15/33

    Next, the disconnect must be selected for the motorfeeder. The disconnect for a feeder serving a group ofmotors shall have a horsepower rating not less than thesum of the horsepower ratings of the motors served,NEC Section 430-112. For the example, a fusible disconnect switch must have a horsepower rating not less than5 + 3 + 1 + 2 = 11 hp. The disconnect to be chosenwould probably be rated at 15 hp.

    I f a circuit breaker serves as the disconnect, it musthave a current rating not less than 115% of the sum of thefull-load currents of all the motors served, NEC Section430-JJO(c)(2). For the example, this would be 75 A.

    1.15 X (28 + 17 + 8 + 12) = 1.15 X 65 = 75 A IThe minimum size standard circuit breaker would be80 A.

    Typically, feeders serving groups of motors will besized large enough to provide for future expansion.Therefore, the previous calculations serve only as a

    No.

    60 A~ - - - - - - - - - - ~ ~

    5 hp 3 hp

    40 A,--...,..

    guide. To make sure that the feeder is adequate for present and future needs, t h ~feeder in the example would notbe sized for the minimum, but rather for at least 100 A.The wire size could possibly be either No. 3 AWG copper TH W or No. 1 AWG THW aluminum. The overcurrent protection would then be sized according to theampere rating of the feeder, NEC Section 430-62(b).

    The short-circuit protection for a feeder supplying aspecific fixed motor load can be sized according to therules of NEC Section 430-62(a). This only applies to afixed motor load that will not be changed in the future.Consider the previous example, assuming that circuitbreakers serve as the disconnect and short-circuit protection for each motor. A fusible disconnect switch willserve as the short-circuit protection for the feeder. Figure17-20 shows the sizes of wire and overcurrent protectionfor each circuit.

    The maximum rating of short -circuit protection forthe feeder is determined by taking the maximum sizemotor branch-circuit short-circuit device and adding to itthe full-load current of all other motors served. The larg-

    No. 4 AW G copper THWN

    100-A circuit-breakerpanelboard without a mainbreaker

    1 hp 2 hp

    Figure 17-20 Feeder wire serving a specific group of single-phase, 230-V motors

    Unit 17 Motor Control 355

  • 7/27/2019 Motor Controllers1

    16/33

    est branch-circuit protection for the example is a 60-Acircuit breaker for the 5-hp motor. Ad d to this 60 A thefull-load currents for the 3-hp, 2-hp and 1-hp motors.The fuse si ze is 100 A maximum.

    60 + 17 + 12 + 8 = 97 A

    It must be remembered that the feeder overcurrentdevice is permitted to exceed the ampere rating of thefeeder only when the feeder is supplying a specific motorload. Th e panelboard is often used to serve other loads;therefore, the feeder then must be protected at its ampacity. Fo r the example, a No. 3 AWG copper wire instead of a No. 4 should be chosen.

    Fo r group motor installations, dual-element, timedelay fuses for each motor may be sized at 125% of themotor full-load current rating. This provides motorbranch-circuit protection, as well as running overloadprotection.

    Th e main feeder dual-element, time-delay fuse maygenerally be sized at llf2 times the ampere rating of thelargest motor of the group, plus the full-load current rating of the other motors of the group.

    ( 1. 5 X 28) + 17 + 8 + 12 = 79 A

    (Use 80-A fuses.)This fuse size would be a minimum.

    FEEDER TAPS

    A common practice is to tap motor branch circuitsdirectly from a motor feeder. This is permitted as long asthe branch-circuit wire is terminated at an overcurrentdevice sized properly for the circuit, NEC Section 430-28. Th e branch-circuit wire size may be smaller than thefeeder wire size. I f the tap wire from the feeder to theovercurrent device is not more than 10 ft (3.05 m), andis enclosed in raceway, the branch-circuit wire may be assmall as necessary to serve the motor load. However, ifthe tap is more than 10 ft (3. 05 m) but not more than25 ft (7 .62 m) in leng th, the br anch-c ircuit wire musthave an ampere rating at least one-third the rating of thefeeder conductors.

    Consider the example of a No. 4 AWG copper THWfeeder wire supplying the three motors of Figure 17-21.The tap wire from the feeder to the fusible disconnect forthe %-hp and 1 0-hp, 230-V, single-phase motors is notrequired to be a minimum size because the tap is notmore than 10f t (3.05 m) long. However, the ll/2-hp

    35 6 Unit 17 Motor Control

    motor tap is more than 10ft (3.05 m) long; therefore, itmust have an ampere rating not less than one-third that othe feeder wire, or a minimum rating of 28 A. I f thwires are copper THW, then the minimum size is No10 A WG . If the tap had not been more than 10 ft

    (3 .05 m) lo ng, th en the ll/2-hp motor circuit.could havebeen wired with No. 14 AWG TH W copper wire.

    85A 28 A . . f-

    3- = - m1mmum or 1If2-hp motor tap

    MOTOR CONTROL CIRCUIT

    A magnetic motor starter is operated with an electricsolenoid coil. A diagram of the power flow to the motorand the control circuit is included with each magnetimotor starter.

    A typical diagram is shown in Figure 17-22. Thheavy lines show the power flow to the motor. The naro w lines belong to the control circuit which is prewired

    No.copperTH W

    No. 4 AWG copper, 85 A, TH WNo. 10 AWG

    10 hp50 A

    l/4 hp6.9 A

    \ _ _ _ _ ( f . ~~ )lo. 14 AWG

    copperTH W

    Single-phase, 230-Vmotors

    1 1/2 hp10 A

    Figure 17-21 Motor branch-circuit taps from a feederThe motors are single phase.

  • 7/27/2019 Motor Controllers1

    17/33

    Motor

    starter

    Power supply

    Figure 17-22 Schematic diagram of a magnetic motorstarter

    by the manufacturer. The holding contact or interlock isthe set of contacts between terminals 2 and 3. Thesecontacts close at the same time the main contacts close.The control wire goes from terminal 3 to the coil whichcloses the contacts, then from the coil through a normally closed overload relay contact. Some motor startershave as many as three of these contacts in series. If themotor overloads, the thermal units will heat up and tripopen this overload relay contact, breaking the controlcircuit and deenergizing the coil. This opens the motorcircuit. From the normally closed overload relay contact,the control circuit wire goes to terminal L2. The terminals of the overload relay are shown in Figure 17-23.

    Figure 17-23 Overload relay terminals of a magneticmotor starter

    Consider the situation where a simple switching device, such as a thermostat, is used to control the motor,Figure 17-24. When the thermostat closes, it must complete the circuit to energize the motor starter coil. Poweris obtained from terminal 1, which is located next toterminal L l . The other side of the thermostat is connected to terminal 3. When the thermostat closes, electrical current flows from terminal 1 through the thermostatto the coil. From the coil, current flows through the overload relay contact to terminal L2. When the thermostatopens, the circuit is broken and the main contacts open.Only two wires are required when a simple switch deviceis used to control the motor starter; terminal 2 is notused.

    A start-stop station (also called a push-button station) is another common device used to control a motor.The start and stop push buttons are momentary contacts.They immediately return to their original position afterthey have been pressed. Figure 17-25 shows a momentary contact push-button station.

    A start-stop motor control circuit is shown in Figure17-26. This requires a 3-wire control circuit. Current canflow from terminal 1 through the normally closed stopbutton. As soon as the start button is depressed, currentflows to terminal 3 and then through the coil to completethe circuit. The main contacts and the holding contactbetween terminals 2 and 3 are now closed. When thestart button is released the start contact opens, but current now flows from terminal 2 to terminal 3 through the

    Power supply

    ~2- - - r

    IIIIIIIotor

    starter _ j

    Figure 17-24 Simple switch device, such as a thermosta t,controlling a magnetic motor starter

    Unit 17 Motor Control 35 7

  • 7/27/2019 Motor Controllers1

    18/33

    I I

    Figure 17-25 Start-stop station for a magnetic motorstarter (Courtesy o f Square D Company)

    holding contact, keeping the coil energized and the contacts closed. Now the only way to stop the motor is topress the stop button or open the overload relay. Diagrams for wiring comm on moto r control circuits are con-

    Stop

    Start

    Motorstarter

    Power supply

    ~ 2 - - - r l .0IIIIIIIIIII

    Figure 17-26 Start-stop station controlling a magneticmotor starter

    35 8 Unit 17 Motor Control

    t a i n ~ dinside the motor starter. It is a good idea to putnumbers on the control circuit wires to help keep themidentified. Figure 17-27 shows the start-stop station

    wires connected to the motor starter. Compare Figure17-27 with the diagram of Figure 17-26.

    Th e diagram of Figure 17-26 is a schematic controlwiring diagram for a motor control circuit. It is a littledifficult to visualize the operation of the complete control circuit. Examine Figure 17-28 where two separatestart-stop stations are wired independently to operate themotor. The schematic diagram can be confusing. A typeof diagram which helps to visualize easily the components and operation of a control circuit is called a ladderdiagram. Th e entire control circuit is drawn horizontallyacross the diagram between the two power wires L 1and L2.

    Figure 17-29 is a ladder diagram for the start-stopcontrol circuit of Figure 17-26. The flow of current can

    be traced easily from Ll to L2 through each component.Figure 17-30 is a ladder-type control diagram of the twostart-stop stations of Figure 17-28. Stop buttons arewired in series so that any one of them can break thecircuit. Th e start buttons must be wired in parallel so thatany one of them can energize the coil. Th e holding contact is always wired in parallel with the start buttons.

    INTERLOCKING MOTORSTwo electric motors can be interlocked so that the

    second one cannot run unless the first one is running.This ma y be necessary to prevent plugging of a materialhandling system. Fo r example, if a conveyer stops, itmay be desirable to shut down the silo unloader feeding

    Figure 17-27 Three wires are required to control a manetic motor starter with a start-stop station.

  • 7/27/2019 Motor Controllers1

    19/33

    Power supply

    Stop A Stop B

    Figure 17-28 Two start-stop stations controlling a magnetic motor starter.

    the conveyer. Another common interlock t ~ c h n i q u eisused to prevent two large motors from operating at thesame time. This may be desirable to keep the electricaldemand as low as possible in order to reduce the monthlyelectric bill. Extra interlock contacts ca n be added to amagnetic motor starter, Figure 17-31. Normally openand normally closed interlocking contacts are available.In Figure 17-32, motor B will operate only if motor A isoperating. In Figure 17-33, motor D cannot operate ifmotor C is operating. In ladder diagrams, only the con

    trol circuits are shown. All parts labeled A are insidemotor starter A, and similarly with parts B, C, and D. Aconfusing aspect of a ladder control diagram is that partsnormally located physically together in the actual wiringma y be located at any appropriate location on the ladderdiagram.

    Ll L2

    Holdingcontact /

    Figure 17-29 ladder diagram for a start-stop station controlling a magnetic motor starter

    THERMAL PROTECTION INMOTOR WINDINGS

    A motor may have a thermal protector in the windings to sense motor overheating. This thermal protectormay be required to be wired-in as a part of the controlcircuit wiring. In this case, the thermal protector is simply wired in series with the control circuit. I f the thermalprotector opens, the control circuit is broken and themotor stops. A ladder diagram of a thermal protector in acontrol circuit is shown in Figure 17-34.

    Ll

    Stop 8 Stop A

    Start A

    _l_

    Holdingcontact

    L2

    Figure 17-30 ladder diagram for two start -stop stationscontrolling a magnetic motor starter

    Unit 77 Motor Control 35 9

  • 7/27/2019 Motor Controllers1

    20/33

    Figure 17-31 Extra inter lock contacts may be added to amagnetic motor starter to sequence or coordinate othermotors.

    CONTROL DEVICESCommon control ladder diagrams and schematic wir

    ing diagrams use some basic symbols and terminology.Switches and contacts are the basic control components,and they take several different forms. Switches and contacts may be operated mechanically by a timer or bysome change in condition, such as temperature, pressure, flow, liquid level, or humidity.

    Switches and contacts are described by the number ofpoles and the number of throws. Th e number of poles isthe number of paths into a switch or contact. The numberof throws is the number of paths leaving each pole.

    360 Unit 17 Motor Control

    L1

    . Stop B

    Holdingcontact A

    Start B

    _l_~ \ B

    L

    InterlockingHolding normally open contact

    contact B installed in motorstarter A

    Figure 17-32 Motor B is interlocked with mo tor A so thamotor B cannot start unless motor A is running.

    It must also be known if the switch or contact is the open or closed position when it is in the unactivatestate. If the switch or contact is open when in the unactivated state, it is considered to be normally open (NO:when it is in the opposite position, it is said to be nmally closed (NC). Common single-pole, single-thrm

    L1

    Start D

    Figure 17-33 Motor D is interlocked with motor C so tmotor D cannot start if motor C is running.

  • 7/27/2019 Motor Controllers1

    21/33

    t

    nd=

    ;

    -N

    at

    L1

    protectorin motorwindings

    L2

    Figure 17-34 A thermal protector in the motor windingsmay be wired in series with the control circuit.

    (SPST) switch and contact symbols are shown in Figure 17-35.

    A single-pole, double-throw (SPDT) switch or con

    tact has one input wire and two output wires. One isnormally open, and the other is normally closed. Manycontrol devices use this type of contact so that one devicecan be used for many different purposes. Both outputwires may be used, but often only one is used. Commonsingle-pole, double-throw contacts are shown in Figure17-36. A 3-way toggle switch, for example, is actually asingle-pole, double-throw switch.

    Normally open, NO Normally closed, NC

    Momentary contact, NO Momentary contact, NC

    '(

    Figure 1 7-35 Single-pole, single-throw (SPST) contactschematic symbols for control systems

    o - - - N O ~ N O

    ----a----La__ NCFigure 17-36 Single-pole, double-throw (SPOT) contactschematic symbols for control systems

    Another very common and versatile switch or contactarrangement is the double-pole, single-throw (DPST)contact. Some of the most common types are shown inFigure 17-37. The double-pole, double-throw (DPDT)contacts are common with control switches and timing

    relays, Figure 17-38.The common types of switches and contacts are incorporated into various types of control devices. Onlysingle-pole, single-throw contacts are shown in the following diagrams; however, the other types of contactsdiscussed previously are available. Control device schematic symbols that are frequently used are shown in Figure 17-39. A limit switch is a device which is activatedwhen something presses against the lever arm or actuator. It may be of the two-position type or the momentary- .contact type, Figure 17-40. Limit switches are frequentlyused to sense material flow in an automatic materialshandling or processing system, such as a grain-drying

    system or an animal feeding system.A current-sensing relay is a magnetic coil which

    closes a set of contacts when the current reaches a presetlevel, Figure 17-41. An application of a current -sensingrelay is a feed grinder with an automatic conveyer sup-

    ~ o - ~ _ _ / , - N OII

    . ) . . / I I---

  • 7/27/2019 Motor Controllers1

    22/33

    Limit switch

    Thermostat

    Heating type Cooling type

    Flow switch

    Closes with reduced flow Closes with increased flow

    Pressure or vacuum switch

    Closes with pressure drop Closes with pressure rise

    Liquid-level switch

    Closes with rise in level Closes with fall in level

    Figure 17-39 Control device schematic symbols

    plying grain to the grinder. As long as the gr inder is fullyloaded, the conveyer is off. As soon as the grinder loadcurrent drops, indicating the grinder is not full, the current-sensing relay closes the contacts and turns on theconveyer. A ladder diagram of the control system isshown in Figure 17-42.

    Time-delay relays are used on many types of processes or machines where a time delay of a few seconds orminutes is desired. A typical example is a grain-dryercontrol. The time-delay relay consists of one or morecontacts and a timing device. Once power is supplied tothe timing relay, it begins timing. After the preset time

    period, the contact or switch is activated to the alternateposition. Th e schematic diagram for a time-delay relay isshown in Figure 17-43. After the timing is complete, theswitch moves in the direction of the arrow at the bottomof the schematic symbol. Some types of time-delay relays are shown in Figure 17-44.

    362 Unit 17 Motor Control

    Figure 17-40 A limit switch is activated by making contact with solid material.

    A typical timing relay may have an eight-pin socket,Figure 17-45. Th e timer voltage can be specified, but120 V is common. This timing relay is a double-pole,double-throw type. Only the required contacts are used.Figure 1 7-46 shows a ladder diagram for two electricmotors, one of which is operated with a timing relay.

    figure 17-41 A curren t-sensing relay will open or dosecontact upon rise or fall of current flow to a motor oother equipment.

  • 7/27/2019 Motor Controllers1

    23/33

    L1 L2

    Figure 17-42 ladder diagram of a current-sensing relaythat controls a conveyer supplying grain to a grinder

    The start-stop station activates motor A and the timer ofthe timing relay. After a 30-second delay, motor B operates.

    LOW-VOLTAGE CONTROL

    A magnetic motor starter may be operated from acontrol transformer-supplied 24-V or 120-V system.This is of importance particularly for a large 460-Vmotor. A control transformer may step down the 460-Vline voltage to 120 V. I f the transformer is an integralpart of the motor controller, it is permitted to be protected by fuses installed on the primary of the transformer, NEC Section 430-72 (c). Fuseholders are usuallysupplied as an integral part of the transformer. The wir-

    (time) (time)

    1 ~

    - - - - ; ~T1ming;;Brelay

    Figure 17-43 Schematic symbol for a time-delay relay

    Figure 17-44 Time-delay relays

    ing of a transformer-supplied control circuit is shown inFigure 17-47. The factory-installed jumper wire betweenterminals X2 and L2 must be removed. (TheX2 markingon the motor controller can be seen in Figure 17-23.)

    The control electrical supply may be completely external to the motor branch circuit. A typical example

    would be a programmable controller operating a group ofmotors. The programmable controller output would most

    Timer

    120 v

    8

    Figure 17-45 Schematic wiring diagram of a time-delayrelay with two single-pole, double-throw contacts

    Unit 77 Motor Control 36 3

  • 7/27/2019 Motor Controllers1

    24/33

    Ll

    Holdingcontact

    2

    N

    TR7

    Coil

    Figure 17-46 Time-delay relay will turn on motor B 30seconds after motor A has been started. (Refer to Figure17-45 to identify time-delay contacts.)

    Control

    F u s e ~

    Stop

    Start

    Figure 17-47 A control trans former steps down 480 V to120 V for the control circuit.

    36 4 Unit 77 Motor Control

    likely be 120 V to energize the motor starter coil. Figure17-48 shows a motor starter operated from an externalelectrical supply.

    PROTECTING THE CONTROLCIRCUIT

    The motor control circuit is considered a Class 1remote-control circuit, and it falls within the scope oNEC Article 725, as well as Part F of Article 430. Thmotor control circuit wire may be tapped directly fromthe motor circuit wires, usually L1 and L2. Further, thecontrol circuit wire carries only the current required bythe coil in the motor starter; therefore, it is permitted tbe a smaller wire size than is required for the motorcircuit. The sizes of the motor control circuit wires areusually Nos. 14 or 12 AWG copper.

    A start-stop station is often mounted in the cover othe motor controller. In this installation, the control cir

    cuit wires are completely within the motor controller.This wire need not be protected by a fuse, provided themotor circuit short-circuit and ground-fault protectivedevice has a rating not more than the value in Column Bof Table 17-5. Table 17-5 is derived from NEC Section430-72 and NE C Table 430-72(b).

    Consider the example of a 3-phase, 230- V, 15-hmotor which has a full-load current of 42 A, Figure 1

    Programmablecontroller

    Remove this wire

    1:=11IIIIII

    X2 i' - - - - - - t - - - e - - - --- J

    Figure 1 7-48 An external power source is used to controthe motor.

  • 7/27/2019 Motor Controllers1

    25/33

    Table 17-5 Maximum rating permitted for motor short-circuit and ground-fault protectivedevice if supplemental protection is not provided for th e control circuit wires (This table isderived from NEC Section 430-72 and NEC Table 430-72(b).

    Maximum Ampere Rating of MotorCircuit Short-Circuit and Ground-Fault

    Protective Device

    Wires Completely Wires ExtendWithin Motor Starter Outside Motor Starter

    Copper Control Enclosure Enclosure

    Wire Size, AWG Column B Column C

    18 25 716 40 1014 100 4512 120 6010 160 90

    For other situations, see NEC Section 430-73, 725-12, or 725-35.

    49. The motor circuit wire is No. 6 AWG THWN copper, and the motor circuit short -circuit protection is a70-A time-delay fuse. The control circuit wire inside thecontroller enclosure is permitted to be No. 14 AWG,according to .Column B of Table 17-5.

    The motor circuit in the example has a second controlstation remote from the controller. The control wires areconsidered protected by the motor circuit short-circuit

    and ground-fault protective device provided it does notexceed the value of Column C of Table 17-5 for the sizeof control circuit wire in use. The minimum size wire tothe remote station for the motor of Figure 17-49 is No.10 AWG , unless separate overcurrent protection is provided for the control circuit. Fuse holders are available toadd to the motor starter to protect the control circuitwires, Figure 17-50. Control circuit wire No. 18 AWG

    Fuses

    No. 14 AW Gcontrol wire

    completely withincontroller

    Start-stop )r:==:;=:::'Jstation

    70-A fuses

    No. 6 AWG THWN copper

    No. 10 AW Gis the minimum size

    15 hp, 230 V, 42 A3 phase

    Remotestart-stopstation

    Figure 17-49 The control circui t wires may be smaller than the motor circuit wires and still be tapped directly from themain wires.

    Unit 17 Motor Control 365

  • 7/27/2019 Motor Controllers1

    26/33

    ~

    Figure 1 7-50 The contro l circu it wires for large motorsmay require protection by a set of fuses in the motorstarter.

    and larger may be used if it is protected according to thewire ampacity as listed in NEC Tabl:e 310-16.

    Consider an example where a remote start-stop station controls a 7 lJ2-hp, single-phase, 230-V electricmotor with a full-load current of 40 A. The motor circuitwire is No. 8 AWG copper THW, and the short-circuitprotection is an 80-A circuit breaker. I f the control circuit wire is No. 14 AWG copper, then control circuit

    UL Class CC fuses

    fuses are required, according to Column C of Table 17-5Figure 17-51 shows the wiring of the control circuit wfuse protection added.

    Motor control circuit conductors are required toprovided with suitable mechanical protection where t h

    are subject to physical abuse, NEC Section 430-73. I fexternal source of power is used to control the motorsuch as is shown in Figure 17-48, the disconnect for tmotor circuit and control circuit must be adjacent, NESection 430-74. I f they are not adjacent, a warning labemust be placed at the motor controller indicating that twseparate disconnects are required to shut off power in tcontroller. The location of the control circuit disconnecmust be specified at the motor controllers so that maintenance personnel will know where to find it.

    REVERSING MOTOR STARTERS

    Electric motors may be called upon to drive a rnchine which must be reversible. An example is a feconveyer that operates in either direction to deliver feeto two batches of animals. A reversible motor starterrequired to select the desired direction. For a 3-phasmotor, only two lead wires to the motor must beversed. However, for a single-phase motor, the startinwinding leads must be reversed with respect to the rurning windings.

    The ieast expensive means of reversing electric fftors of small horsepower sizes is with a manually opated drum switch, Figure 17-52. The drum switch has

    Figure 17-51 Fuses protecting the control circuit wires

    366 Unit 17 Motor Control

  • 7/27/2019 Motor Controllers1

    27/33

    j

    j

    se:-

    gl-

    )-

    a

    '

    Figure 17-52 A manually operated drum controlle r can

    be used to reverse an electric motor.

    Forward Off ReverseA 0 0 ATl Tl

    T2 0 0 T2B Bc 0 0

    T3 T3c

    Figure 17-53 A drum controller connected to reverse a3-phase electric motor

    forward, a reverse, and an of f position. Figure 17-53shows the wiring of one type of drum switch to reverse a3-phase motor. Note the phase rotation at the motor forthe forward and the reverse positions. A single-phasemotor is more difficult to reverse.

    Electric motors of large-horsepower sizes can onlybe reversed with a reversing magnetic motor starter. Thistype has two magnetic contactors, Figure 17-54. A threefunction, forward-stop-reverse, push-button station isrequired. Figure 17-55 shows the wiring of a reversingmagnetic starter for a 3-phase electric motor. The two

    magnetic contactors must be electrically or mechanically

    Figure 17-54 A reversing magnet ic motor star ter

    Unit 77 Motor Control 36 7

  • 7/27/2019 Motor Controllers1

    28/33

    Ll

    Stop

    R

    L2 starter will be installed at the same locati'on. These uni1

    are called combination motor starters. A typical combnation motor starter is shown in Figure 17-56.

    Figure 17-55 ladder diagram of the control circuit for areversing magnetic motor starter. The normally closed interlocking contacts prevent both contactors from beingclosed at the same time, causing a short circuit.

    interlocked to prevent both from being closed at onetime. Closing both at one time will cause a s hort circuit.

    COMBINATION MOTOR STARTER

    The motor circuit disconnect short -circuit andground-fault protection and the magnetic starter can becombined in one cabinet. These units are convenientwhen a fusible disconnect switch and magnetic motor

    Figure 17-56 A combination motor starte r contains botth e disconnect and the motor starter. (Courtesy o f SqualD Company)

    36 8

    REVIEW

    Refer to the National Electrical Code when necessary to complete the followingreview material. Write your answers on a separate sheet of paper.

    )I; 1. A plug and receptacle is permitted to serve as a motor controller for portable motorsrated at what horsepower and less?

    X 2. Th e locked-rotor current of a 5-hp, 230-V, single-phase motor is how many amperes?

    Unit 17

    3. According to the motor starter nameplate in the illustration at the top of the next page,

    this motor starter may be used to control a 25-hp, 460-V motor. Explain whichchange must be made to make the motor starter suitable for controlling a 460-Vmotor.

    4. Th e largest size single-phase, 230-V electric motor which is permitted to be controlled with the mot or starter in the illustration at the top of the next page is how manyhorsepower?

    Motor Control

  • 7/27/2019 Motor Controllers1

    29/33

    he

    5. In the upper left-hand comer of the motor starter nameplate in the illustration aboveare the numbers 3 and 2. These are the terminal num bers for which of the following?a. Main contactsb. Coilc. Holding contactsd. Overload relay

    6. The minimum size motor starter required for a 1 00-hp, 460-V, 3-phase electric motoris what NEMA size?

    7. A motor starter is to be installed within an area of an agricultural building subject todusty, damp, and corrosive conditions. The type of enclosure suitable for these conditions is what NEMA enclosure?

    8. The full-load current of a 3-hp, single-phase, 230-V electric motor is how manyamperes?

    9. The minim um size copper TH W branch-circuit wire for a 10-hp, 230-V, 3-phasemotor with a nameplate current of 24 A is No. ? AWG.a. 12b. 10c. 8d. 6

    10. The motor of Problem No. 9 has a service factor of 1.20, and code letter M. Th emaximum size time-delay fuse that can serve as running overcurrent protection is:a. 25 A

    b. 30 Ac. 40 Ad. 50 A

    11. The motor circuit disconnect is required to be within sight from the controller, whichmeans actually visible from the controller, and not more than how many feet (meters)from the controller?

    Unit 77 Motor Control 369

  • 7/27/2019 Motor Controllers1

    30/33

    370

    12. A circuit breaker will serve as the disconnect, as well as the short-ci rcuit and groundfault protection for a motor circuit. Th e motor is rated 2 hp, single-phase, 230 V,11 A with code letter H. The maximum size circuit breaker under normal starting

    conditions is:a. 15 Ab.

    20 Ac. 30 Ad. 40 A

    13. The electric motor in Problem No. 12 has a service factor of 1.10. Using the overloadthermal unit selection chart of Figure 17-18, the correct overload heater is thermal

    unit No.:a. B 17.5b. B 19.5c. B 22d. B 25

    14. Th e maximum size time-delay fuse used for short-circuit and ground-fault protectionfor a 75-hp, 460-V, 3-phase motor, code letter M, under normal starting condition-

    s is:a. 100 Ab. 125 Ac. 150 Ad. 175 A

    15. A 225-A, single-phase, feeder conductor No. 3/0 AWG THHN copper supplies several motors in a feed room of a beef farm. A 5-hp, 230-V motor is tapped directlyfrom the feeder with a fusible disconnect switch 15 ft (4.57 m) from the point of thetap. The minimum size copper THHN tap conductor permitted is No. ?AWG.a. 10b. 8c. 6d. 4

    Unit 17 Motor Control

    310 copper THHN

    CopperTHHN

    23 0 v5 hp

    single phase

    1 5 ft(4.57 m)

  • 7/27/2019 Motor Controllers1

    31/33

    16. On a separate sheet of paper, redraw and complete the control wiring diagram tooperate the magnetic motor starter with a start-stop station.

    L 1 L2

    Stop

    ~Start~

    0 0

    17. On a separate sheet of paper, redraw and complete the control wiring diagram tooperate the magnetic motor starter with a pressure switch.

    18. The schematic cont rol diagram has a start-stop push-button station operating a magnetic motor starterwith an emergency stop push button mounted on the machine. Ona separate sheet of paper, draw a ladder control diagram for the circuit.

    StopEmergency

    stop

    19. A magnetic motor starter coil is energized from a separate 115-V source. Show howto wire the control circuit. On a separate sheet of paper, redraw the motor controllerand control circuit wires. A control circuit wire in the motor starter must be removed.

    Unit 77 Motor Control 377

  • 7/27/2019 Motor Controllers1

    32/33

    37 2

    20. The start-stop push-button station turns on motor A and, after a time delay of 30seconds, motor B is turned on by the time-delay relay. The time-delay is the type thatinstantly resets when power to the timer is interrupted. On a separate sheet of paper,draw a ladder diagram of the control system.

    L1

    IL2 N

    IL1

    IL2

    I

    30 seconds

    T1 T2T2

    + Motor BMotor A

    Unit 17 Motor Control

  • 7/27/2019 Motor Controllers1

    33/33

    UNIT 18CORD- AND PLUG-CONNECTED

    EQUIPMENT

    OBJECTIVES

    After studying this unit, the student will be able to

    select an adequate type and size of flexible cord for supplying portable equipment.

    choose a cord plug and connector adequate for the current and voltage of the suppliedequipment.

    select and install controllers for electric motors on portable equipment.

    install a flexible cord, plug, and connector in a manner so as to prevent strain on thecord and moisture from entering the wiring or connections.

    Flexible cords are frequently used on farms to supplyportable electrical equipment and permanently connectedequipment which must be moved during normal operation. A top-unloading silo unloader is a typical exampleof permanently attached equipment which is moved during normal use, Figure 18-1. Cords supplying equipmentin agricultural locations are required to be approved forhard usage, NE C Section 547-J(b).

    CORD TYPES

    Types of flexible electrical cords are listed in NE CTable 400-4. Basically, several types of cords are suita

    ble for agricultural use. These types include junior hardservice cord Types SJ and SJT. These cords are permitted to be used for portable equipment in damp locations,and are classified by the NE C as hard-usage cords. Theyare available in sizes No. 18 to No. 10 AWG. They areavailable as 2-, 3-, or 4-conductor cord. If the cords aresuitable for use in areas where they will be exposed to oil

    and grease, they will have the letter 0 in the type, suchas SJO or SJTO. The conductors inside these cords areprotected by a tough outer covering.

    Judgment must be applied regarding the severity ofthe conditions of use for flexible cords. Most cords usedfor agricultural applications should be rated for the extrahard usage designation. Hard-service cord fits this classification and carries the Types S or ST. These types arealso suitable for use in damp locations. The oil-resistanttypes are SO and STO. Hard-service cord is available insizes No. 18 to No. 2 AWG. Cords are also availablewith two or more conductors.

    Portable electric heating equipment, such as infrared

    heat-lamp fixtures, may be called upon to operate continuously for days or weeks. Flexible cords also may besubjected to excessive heat from the heating unit as wellas continuous current flow. These cords must be capableof withstanding elevated operating temperatures withoutdeterioriation of the conductor insulation or the outerjacket. These are classified as jacketed heater cords

    Unit 18 Cord- and Plug-Connected Equipment 37 3