module j1 water treatment - infomine · module j1 water treatment 1. ... a. backwash/feed pump ......
TRANSCRIPT
J1 (1)
MODULE J1 WATER TREATMENT
1. GENERALIZATION
This Chapter contains a description of the water treatment plant and its
operation
2. STANDARDS OF PERFORMANCE
The operator will understand the water treatment plant layout and
water flows
3. PERFORMANCE OBJECTIVES
The operator will be able to:
• Locate and identify system components
• Describe system flows
4. EVALUATION
After completion of the module, the operator shall be able to:
• Describe the system with the aid of a blank diagram
• Describe process flows
• List the protective devices and alarms
• Explain how to operate and monitor systems
J1 (2)
CONTENTS
CHAPTER 1 – GENERAL DESCRIPTION ....................................................... 7
1. FUNCTION ......................................................................................... 7
2. MAIN COMPONENTS ....................................................................... 9
CHAPTER 2 – DESIGN, CONSTRUCTION, CAPABILITIES ....................... 10
1. RAW WATER SUPPLY ..................................................................... 10
A. Pumps ........................................................................................... 10
B. Motors ........................................................................................... 10
C. Heater ........................................................................................... 11
2. ZEEWEED® MICROFILTRATION .................................................. 11
A. Air Blower .................................................................................... 11
B. Air Blower Motors ........................................................................ 12
C. Permeate/Backpulse Pumps ........................................................ 12
D. Permeate/Backpulse Motors ........................................................ 13
E. Level Control Valve ..................................................................... 13
F. Vacuum Pumps ............................................................................ 14
G. Vacuum Pump Motors ................................................................. 14
3. SOFTENER ....................................................................................... 15
A. Backwash/Feed Pump .................................................................. 15
B. Backwash/Feed Pump Motors ..................................................... 15
C. Brine Pump .................................................................................. 16
D. Brine Pump Motors ...................................................................... 16
4. RO ...................................................................................................... 17
A. RO #1 First Pass Pumps .............................................................. 17
B. RO #1 First Pass Pump Motors ................................................... 17
C. RO #1 Second Pass Pumps .......................................................... 18
D. RO #1 Second Pass Pump Motors ............................................... 18
E. RO #2 First Pass Pumps .............................................................. 19
F. RO #2 First Pass Pump Motors ................................................... 19
G. RO #2 Second Pass Pumps .......................................................... 20
H. RO #2 Second Pass Pump Motors ............................................... 20
5. CIP TANK .......................................................................................... 21
A. Circ Pump ..................................................................................... 21
B. Circ Pump Motor .......................................................................... 21
C. Heater ........................................................................................... 21
J1 (3)
6. EDI ..................................................................................................... 21
A. Pumps ........................................................................................... 21
B. Motors ........................................................................................... 22
7. PRODUCT LINE ............................................................................... 22
A. Outlet Pumps ............................................................................... 22
B. Motors ........................................................................................... 23
8. DRAIN SUMP ................................................................................... 23
A. Pumps ........................................................................................... 23
B. Motors ........................................................................................... 24
9. MAKEUP AIR UNIT ......................................................................... 24
10. SPARE PARTS LIST ......................................................................... 25
A. Chemicals ..................................................................................... 25
B. Consumables ................................................................................ 26
C. Mechanical ................................................................................... 26
CHAPTER 3 - FLOWS ...................................................................................... 27
1. SYSTEM FLOWS .............................................................................. 27
CHAPTER 4 – SAFETY .................................................................................... 29
1. GENERAL PERSONAL PROTECTIVE EQUIPMENT (PPE)........ 29
CHAPTER 5 – PROTECTION DEVICES AND PERMISSIVES .................... 30
1. ALARM/ALERT HANDLING ........................................................... 30
A. General ......................................................................................... 30
B. Alarms vs. Alerts.......................................................................... 31
C. Shutdown Alarms ........................................................................ 32
D. Multiple Alarms ........................................................................... 32
CHAPTER 6 – PLACE IN SERVICE / TAKE OUT OF SERVICE ................. 34
1. SEQUENCE CHARTS ...................................................................... 34
CHAPTER 7 – OPERATE AND MONITOR SYSTEM .................................... 36
1. OPERATING PROCEDURES .......................................................... 36
A. Equipment Layout ....................................................................... 36
B. Raw Water Feed System .............................................................. 36
C. Chemical Pretreatment ............................................................... 37
D. ZeeWeed® Microfiltration System ............................................... 38
E. Dual Softener System .................................................................. 46
F. Reverse Osmosis (RO) Pretreatment .......................................... 47
G. Reverse Osmosis (RO) System .................................................... 48
J1 (4)
H. Electrodeionization (EDI) System ............................................... 51
I. Dual Mixed Bed Ion Exchange Polishing Unit ........................... 51
J. Distribution Break Tank with Outlet Feed Pumps .................... 51
K. Reserve Feedwater ....................................................................... 52
L. Sump Pumps ................................................................................ 52
2. OPERATING PROCEDURES .......................................................... 53
A. ZeeWeed® Operation .................................................................... 53
3. STANDARD OPERATING PARAMETERS ..................................... 65
A. Chemistry ..................................................................................... 65
B. ZeeWeed® ..................................................................................... 66
C. Softener ........................................................................................ 68
D. RO Units ....................................................................................... 68
E. EDI Unit ....................................................................................... 69
F. Transfer System ........................................................................... 70
4. ALTERNATING BETWEEN PRODUCTION MODES ................... 70
A. Switch from normal to double mode. ........................................... 70
B. Switch from double to normal mode. ........................................... 71
C. To switch from one RO to the other during extended NORMAL
MODE operation. .............................................................................. 72
D. To perform a Silt Density Index (SDI) test. ................................ 72
E. ZeeWeed® ...................................................................................... 74
F. Softeners ....................................................................................... 76
G. Reverse Osmosis .......................................................................... 79
H. EDI ............................................................................................... 82
I. Transfer System ........................................................................... 85
5. PLANT OPERATING CONTROLS .................................................. 86
A. Plant Operating Controls ............................................................ 86
6. DESIGN OF AUTOMATIC PLANT CONTROL .............................. 92
A. Plant Indicators ........................................................................... 92
B. Raw Water Feed System .............................................................. 96
C. Chemical Pretreatment ............................................................. 100
D. ZeeWeed® Microfiltration System ............................................. 102
E. Dual Softener System ................................................................ 116
F. Reverse Osmosis (RO) Pretreatment ........................................ 120
G. Reverse Osmosis (RO) System .................................................. 122
H. Electrodeionization (EDI) System ............................................. 127
I. Dual Mixed Bed Ion Exchange Polishing Unit ......................... 128
J. Break Tank with Outlet Feed Pumps ....................................... 128
K. Reserve Feedwater Tanks ......................................................... 129
L. Sump Pumps .............................................................................. 131
J1 (5)
CHAPTER 8 – OPERATE UNDER UPSET CONDITIONS ......................... 133
1. INTRODUCTION ............................................................................ 133
A. Power Up/ Power Interruption .................................................. 134
CHAPTER 9 – TROUBLESHOOTING .......................................................... 135
1. GENERAL ....................................................................................... 135
2. LAB TESTS ..................................................................................... 135
3. FEEDWATER .................................................................................. 138
4. ZEEWEED® .................................................................................... 138
5. SOFTENER ..................................................................................... 140
6. REVERSE OSMOSIS ...................................................................... 143
7. ELECTRODEIONIZATION (EDI) ................................................. 146
8. TRANSFER SYSTEM ..................................................................... 149
CHAPTER 10 – CHECKLISTS AND/OR READINGS .................................. 151
1. BEGINNING OF SHIFT CHECKLIST .......................................... 151
2. OPERATOR LOGSHEETS ............................................................. 153
CHAPTER 11 – SELF CHECK QUESTIONS AND ANSWERS ............ Error!
Bookmark not defined.
1. SELF CHECK EXERCISE – QUESTIONS .ERROR! BOOKMARK
NOT DEFINED.
2. SELF CHECK EXERCISE – ANSWERS .....ERROR! BOOKMARK
NOT DEFINED.
APPENDICES
APPENDIX 1 – FLOW DIAGRAMS AND CONTROL SCREEN
APPENDIX 2 – CONTROL LOGIC SUMMARY, SEQUENCE
CHARTS AND LOG SHEETS
APPENDIX 3 – MSDS SHEETS
APPENDIX 4 – NAG-O-GRAMS
J1 (6)
FIGURES AND TABLES
Figure 3-1 Process and Flow Diagram for High Purity………………………27
Water System
Figure 7-1 ZeeWeed® Membrane Schematic ................................................ 40
Figure 7-2 ZeeWeed® 500 Cassette ............................................................... 42
Figure 7-3 Spiral Wound Module Design ..................................................... 48
Figure 7-4 Reverse Osmosis .......................................................................... 49
Figure 7-5 Reverse Osmosis Membranes ..................................................... 49
Figure 7-6 Transmembrane Pressure Control Schematic ......................... 108
Figure 7-7 Process Pump (P-35) Speed Control ......................................... 110
Table 7-1 Normal Operating Expenses ......................................................... 93
Table 7-2 Backpulse Analysis Chart .......................................................... 113
J1 (7)
CHAPTER 1 – GENERAL DESCRIPTION
1. FUNCTION
This Boiler Feedwater Pretreatment System is designed to treat water
required for TransAlta Utilities Wabamun Generating Station. The system
consists of a ZeeWeed® Microfiltration System, water softening, a dual train
Double Pass Reverse Osmosis (RO) System, Electrodeionization (EDI) skid
and Mixed Bed (MB) Ion Exchange Bottles. Each skid is separately mounted.
The system is capable of delivering 80 USgpm at normal flow and 160 USgpm
at peaking flow.
The first process step utilizes a ZeeWeed® microfiltration system to remove
suspended solids and organic material prior to further reverse osmosis
membrane treatment. To ensure ZeeWeed® system reliability, the process
tank has been divided into two compartments. Each compartment has its
own aeration blower and permeate extraction pump with an additional
shared standby.
Raw water is pumped, pre-chlorinated (to prevent microbial growth), and has
ferric chloride added to enhance Total Organic Carbon (TOC) removal. Direct
steam injection is used, if required, to elevate the temperature prior to the
ZeeWeed®treatment. The permeate flows to the backpulse/break tank. The
majority of lake water TOC can be removed across the ZeeWeed®
microfiltration process.
Co-current Regeneration Softening is the next process in the system, where it
is used to ensure optimum ion rejection at elevated pH across the RO.
Softening ensures meeting the EDI feedwater hardness specification of <0.1
ppm, during both normal and peak flow conditions. Using strong acid cation
J1 (8)
exchange resin (sodium form), the softeners remove calcium and magnesium
from the lake water in preparation for RO separation. The charge pumps
take suction from the ZeeWeed® backpulse/break tank and supply flow to the
softeners. Bisulfite is injected to reduce chlorine prior to the softener and the
effluent water flows on to the reverse osmosis system. Caustic is added to the
process only when the mixed beds are in service to increase the pH level prior
to the RO units.
The primary means of reducing the total dissolved solids (TDS) is by dual
train Double Pass Reverse Osmosis system.
In the Double Pass Reverse Osmosis (RO) System, the feedwater flows to the
RO unit which produces a concentrate (waste) stream, and a permeate
(product) stream. The concentrate is diverted to drain, while the permeate
flows to the EDI System or Polishing Mixed Bed Bottles the collected in a
12,000 US gallon break tank.
Caustic (Sodium Hydroxide) is included as pretreatment for the RO. The
membranes on the RO system will periodically become 'fouled' and will
require a 'Wash', in which the feedwater is flushed from the system, and
various cleaning chemicals are recirculated through the membrane system
for a period of time. While the entire system will run automatically with very
little operator attention, a 'Wash' cycle for the RO is a manual operation
which requires operator intervention. These cleaning chemicals are flushed
from the systems and the water to be treated is re-introduced to the system.
One Clean-In-Place (C.I.P.) unit each services the RO system (which requires
membrane cleaning) and EDI (when required).
The Electrodeionization (EDI) System further purifies the RO permeate. EDI
is a membrane desalination process that uses direct current as the energy
source for desalting. The permeate from this process flows to the break tank.
J1 (9)
The EDI (supplied by others) has its own separate Operating and
Maintenance Manual.
Non-Regenerable Mixed Bed (MB) Ion Exchange Bottles are used as an
alternative to the EDI System should it be out of service. This skid is
composed of two banks of six (6) bottles in a parallel configuration. The
permeate from this process flows to the break tank.
The Outlet Feed Pumps deliver the permeate from the break tank to the
Reserve Feedwater System (RFW) system and recirculates 80 USgpm to the
EDI to optimize its performance (single mode).
2. MAIN COMPONENTS
A. Raw water canal
B. Raw water supply pumps
C. Pick steam injection heater
D. ZeeWeed® Microfiltration membranes
E. Zeolite softeners
F. Brine Injection
G. Reverse Osmosis membranes
H. Electrodeionization system
I. Non-Regenerable Mixed Bed Ion Exchange Bottles
J1 (10)
CHAPTER 2 – DESIGN, CONSTRUCTION, CAPABILITIES
The water treatment plant is designed to transform lake water into
demineralized water, for use as boiler feedwater, at the rate of 80 USgpm in
single mode or 160 USgpm in double mode.
The following lists the equipment in the plant and its design/manufacturing
information and ratings. If at any time information is required on a piece of
equipment, this section can be used as a reference to obtain information.
1. RAW WATER SUPPLY
A. Pumps
i) Equipment #: P-101
Vendor: Chamco Ind.
Manufacturer: Peerless Pump Co.
Model Number: 8LB-4STG
GPM: 250
Feet: 118
RPM: 1760
ii) Equipment #: P-102
Vendor: Chamco Ind.
Manufacturer: Peerless Pump Co.
Model Number: 8LB-4STG
GPM: 250
Feet: 118
RPM: 1760
B. Motors
i) Equipment #: P-101
Vendor: Chamco Ind.
Manufacturer: U.S. Electric Motors
Model Number: 809 9709 4820 001 F
HP: 10
RPM: 1760
Frame: 215TP
J1 (11)
ii) Equipment #: P-102
Vendor: Chamco Ind.
Manufacturer: U.S. Electric Motors
Model Number: 809 9709 4820 001 F
HP: 10
RPM: 1760
Frame: 215TP
C. Heater
i) Vendor: Farrell Eng.
Manufacturer: Pick Heaters
Model Number 6X50-3153
Notes: 125-250 GPM, 32 F
2. ZEEWEED® MICROFILTRATION
A. Air Blower
i) Equipment #: B-85-1
Vendor: Zenon
Manufacturer: Hibon
Model Number XN2.5
ii) Equipment #: B-85-2
Vendor: Zenon
Manufacturer: Hibon
Model Number: XN2.5
iii) Equipment #: B-85-S
Vendor: Zenon
Manufacturer: Hibon
Model Number: XN2.5
J1 (12)
B. Air Blower Motors
i) Equipment #: B-85-1
Vendor: Zenon
Manufacturer: GEC Alsthom
Model Number: HOH32
HP: 10
RPM: 1765
Frame: 215T
ii) Equipment #: B-85-2
Vendor: Zenon
Manufacturer: GEC Alsthom
Model Number: HOH32
HP: 10
RPM: 1765
Frame: 215T
iii) Equipment #: B-85-S
Vendor: Zenon
Manufacturer: GEC Alsthom
Model Number: HOH32
HP: 10
RPM: 1765
Frame: 215T
C. Permeate/Backpulse Pumps
i) Equipment #: P-35-1
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X2-62/60 RV
Man. Part #: 40005-5929
ii) Equipment #: P-35-2
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X2-62/60 RV
Man. Part #: 40005-5929
J1 (13)
iii) Equipment #: P-35-S
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X2-62/60 RV
Man. Part #: 40005-5929
D. Permeate/Backpulse Motors
i) Equipment #: P-35-1
Vendor: Zenon
Manufacturer: Reliance
Model Number: 903011-JA
HP: 5
RPM: 3500
Frame: 184T
ii) Equipment #: P-35-2
Vendor: Zenon
Manufacturer: Reliance
Model Number: 966080-HA
HP: 5
RPM: 3500
Frame: 184T
iii) Equipment #: P-35-S
Vendor: Zenon
Manufacturer: Reliance
Model Number: 903011-JA
HP: 5
RPM: 3500
Frame: 184T
E. Level Control Valve
i) Vendor: Zenon
Manufacturer: Samson
Model Number: P161, 2.5”, 150#
Notes: c/w act. & pos.
J1 (14)
F. Vacuum Pumps
i) Equipment #: P-36-A
Vendor: Zenon
Manufacturer: Atlantic Fluidics
Model Number: A5
RPM: 3450
ii) Equipment #: P-36-B
Vendor: Zenon
Manufacturer: Atlantic Fluidics
Model Number: A5
RPM: 3450
G. Vacuum Pump Motors
i) Equipment #: P-36-A
Vendor: Zenon
Manufacturer: Baldor
Model Number: 34H456-3226
HP: 1
RPM: 3450
Frame: 56CZ
ii) Equipment #: P-36-B
Vendor: Zenon
Manufacturer: Baldor
Model Number: 34H456-3226
HP: 1
RPM: 3450
Frame: 56CZ
J1 (15)
3. SOFTENER
A. Backwash/Feed Pump
i) Equipment #: P-13-A
Vendor: Zenon
Manufacturer: Durco
Model Number 1K3X1.5-82/73 RV
Man. Part #: 400005-6041
GPM: 250
Feet: 172
RPM: 3600
ii) Equipment #: P-13-B
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X1.5-82/73 RV
Man. Part #: 400005-6041
GPM: 250
Feet: 172
RPM: 3600
B. Backwash/Feed Pump Motors
i) Equipment #: P-13-A
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number: P25G0398J
HP: 20
RPM: 3525
Frame: 256T
ii) Equipment #: P-13-B
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number: P25G0398J
HP: 20
RPM: 3525
Frame: 256T
J1 (16)
C. Brine Pump
i) Equipment #: P-29-A
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K1.5X1-62/53 RV
Man. Part #: 4500005-6045
GPM: 21
Feet: 119
RPM: 3600
ii) Equipment #: P-29-B
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K1.5X1-62/53 RV
Man. Part #: 4500005-6045
GPM: 21
Feet: 119
RPM: 3600
D. Brine Pump Motors
i) Equipment #: P-29-A
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number: P18G3345K
HP: 3
RPM: 3520
Frame: 182T
ii) Equipment #: P-29-B
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number P18G3345K
HP: 3
RPM: 3520
Frame: 182T
J1 (17)
4. RO
A. RO #1 First Pass Pumps
i) Equipment #: P-41A-1
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
ii) Equipment #: P-41B-1
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
B. RO #1 First Pass Pump Motors
i) Equipment #: P-41A-1
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
ii) Equipment #: P-41B-1
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
J1 (18)
C. RO #1 Second Pass Pumps
i) Equipment #: P-43A-1
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
ii) Equipment #: P-43B-1
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
D. RO #1 Second Pass Pump Motors
i) Equipment #: P-43A-1
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
ii) Equipment #: P-43B-1
Vendor: Zenon
Manufactuer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
J1 (19)
E. RO #2 First Pass Pumps
i) Equipment #: P-41A-2
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
ii) Equipment #: P-41B-2
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
F. RO #2 First Pass Pump Motors
i) Equipment #: P-41A-2
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
ii) Equipment #: P-41B-2
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
J1 (20)
G. RO #2 Second Pass Pumps
i) Equipment #: P-43A-2
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
ii) Equipment #: P-43B-2
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-80/7 U-G-G-AUUE
Man. Part #: B 9838 34130067
GPM: 130
Feet: 436
RPM: 3450
H. RO #2 Second Pass Pump Motors
i) Equipment #: P-43A-2
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
ii) Equipment #: P-43B-2
Vendor: Zenon
Manufacturer: Baldor
Model Number: 09E586X461G1
Man. Part #: 85-60025
HP: 20
RPM: 3525
Frame: 281TSC
J1 (21)
5. CIP TANK
A. Circ Pump
i) Equipment #: P-83
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X1.5-82/53 RV
Man. Part #: 4500005-6072
GPM: 200
Feet: 163
RPM: 3600
B. Circ Pump Motor
i) Equipment #: P-83
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number: P25G0397K
HP: 15
RPM: 3530
Frame: 254T
C. Heater
i) Equipment #: H-83
Vendor: Zenon
Manufacturer: Caloritech
Model Number CX1309F337MRTY
Man. Part #: T98-06104A
Notes: 460V, 9kW
6. EDI
A. Pumps
i) Equipment #: P1-4
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-20 U-G-G-AUUE
Man. Part #: D 9821 34136062E
GPM: 130
Feet: 119
RPM: 3450
J1 (22)
ii) Equipment #: P2-4
Vendor: Zenon
Manufacturer: Grundfos
Model Number: CRN30-30 U-G-G-AUUE
Man. Part #: A 9826 34136063E
GPM: 130
Feet: 178
RPM: 3450
B. Motors
i) Equipment #: P1-4
Vendor: Zenon
Manufacturer: Baldor
Model Number: 36H302W385C1
Man. Part #: 85-60017
HP: 7.5
RPM: 3450
Frame: 213TC
ii) Equipment #: P2-4
Vendor: Zenon
Manufacturer: Baldor
Model Number: 37F680X56F5
Man. Part #: 85-60022
HP: 10
RPM: 3450
Frame: 215TC
7. PRODUCT LINE
A. Outlet Pumps
i) Equipment #: P-71A
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X1.5-82/53 RV
Man. Part #: Military P4A
GPM: 160
Feet: 104
RPM: 3600
J1 (23)
ii) Equipment #: P-71B
Vendor: Zenon
Manufacturer: Durco
Model Number: 1K3X1.5-82/53 RV
Man. Part #: Military P4B
GPM: 160
Feet: 104
RPM: 3600
B. Motors
i) Equipment #: P-71A
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number: P21G4900 YZ
HP: 7.5
RPM: 3500
Frame: 123T
ii) Equipment #: P-71B
Vendor: Zenon
Manufacturer: Reliance Electric
Model Number: P21G4900 YZ
HP: 7.5
RPM: 3500
Frame: 123T
8. DRAIN SUMP
A. Pumps
i) Equipment #: P-103
Vendor: Chamco Ind.
Manufacturer: Chamco
Model Number: 8LB-3STG
GPM: 125
Feet: 82
RPM: 1760
J1 (24)
ii) Equipment #: P-104
Vendor: Chamco Ind.
Manufacturer: Chamco
Model Number: 8LB-3STG
GPM: 125
Feet: 82
RPM: 1760
B. Motors
i) Equipment #: P-103
Vendor: Chamco Ind.
Manufacturer: U.S. Electric Motors
Model Number: 809 970947 89 001F
HP: 5
RPM: 1770
Frame: 184TP
ii) Equipment #: P-104
Vendor: Chamco Ind.
Manufacturer: U.S. Electric Motors
Model Number: 809 970947 89 001F
HP: 5
RPM: 1770
Frame: 184TP
9. MAKEUP AIR UNIT
A.
i) Vendor: Willowridge
Manufacturer: I.C.E. Manufacturing
Model Number: BMA112MODE
J1 (25)
10. SPARE PARTS LIST
The following material can be ordered from stores at the warehouse
unless otherwise specified. Material set up in the warehouse has a
stock code number which can be referenced when the material is
required.
A. Chemicals
Sodium hypochlorite Stock code # 80295
Order through the water lab
Metabisulphite Stock code # 80297
Order through the water lab
Caustic Ordered as ‘one time buy’ and can be
ordered through the water lab.
Ferric chloride Ordered as ‘one time buy’ and can be
ordered through the water lab.
Pneumatic salt
for brine tank
Ordered as ‘one time buy’ and can be
ordered through the water lab.
MC-1 Cleaning solvent Stock code # 87347
MC-4 Organic Cleaner Stock code # 87348
J1 (26)
B. Consumables
RO CIP skid micron filters Stock code # 80365
ZeeWeed® blowers inlet filters Stock code # 40224
Softener micron filters Stock code # 80317
Note: Procedure for installing RO CIP skid micron filters:
a) In order to replace the double ended style filters, remove
the hold down place and the tope end cap from each filter
element.
b) Lift the old elements up to clear the center rods and
discard the elements.
c) Install the new elements over the center rods and the end
caps and install the hold down plate.
C. Mechanical
EDI brine pump Stock code # 80382
EDI product pump Stock code # 80381
1400E panel view Stock code # 80272
Pick heater internals Stored in operator locker in
water treatment plant
J1 (27)
CHAPTER 3 - FLOWS
1. SYSTEM FLOWS
The process flow diagram shown in Figure 3-1 summarizes the
process flows in the water treatment plant.
J1 (28)
J1 (29)
CHAPTER 4 – SAFETY
1. GENERAL PERSONAL PROTECTIVE EQUIPMENT (PPE)
The following are mandatory when handling any of the chemicals in
the water treatment plant:
- face mask
- safety goggles
- boots (CSA approved)
- gloves
- overalls
One must also be familiar with and follow the Material Safety Data
Sheets (MSDS) for each chemical, located in Appendix 3 Material
Safety Data Sheets. The warehouse also has a copy available for
reference, and should be reviewed prior to job commencement.
J1 (30)
CHAPTER 5 – PROTECTION DEVICES AND PERMISSIVES
1. ALARM/ALERT HANDLING
A. General
a) All alarms/alerts are enunciated with a message, and/or
light and some audible indication (i.e. horn or steady
beep) at one or more of the MMIs, the PC or a Control
Panel. The alarms/alerts and corresponding times are
recorded.
b) The operator must clear (acknowledge) the alarm/alert to
clear the alarm banner before any push buttons on the
screen can be activated. The operator can, however,
silence the horn by pressing the Horn Silence push
button on the MMI. The Horn Silence push-button will
function without password access.
c) An Alarm Acknowledge ‘push-button’ is programmed
and accessible from the MMI. This push-button will
silence the horn and record the time the alarm/alert was
acknowledged. The Alarm Acknowledge ‘push button’
will not function without password access.
d) An Alarm Reset ‘push-button’ is also programmed, again
accessible from the screen. This push-button re-sets the
alarm/alert, presumably after the operator has done
something (mechanically or by adjusting a set point) to
clear the alarm/alert condition, preventing it from
immediately recurring. If the alarm condition still
J1 (31)
physically exists, the alarm horn will again sound and the
appropriate Alarm Message screen will again be
displayed. Touching the Alarm History button will
display previous alarms. The operator cannot reset the
alarm/alert without operator level password access.
B. Alarms vs. Alerts
a) All alarms shut off some devices to provide protection to
personnel and the major components such as the process
pump. Alerts do not shut down devices but only warn
that the plant needs attention. Alerts are provided to
protect less sensitive components. Rather than shutting
down equipment due to these alerts (e.g., low tank level),
continued operation is allowed with the intention that
immediate operator attention can provide uninterrupted
production of good quality water from this equipment.
Production quality and quantity will drop off quickly
without operator attention.
a) Alarms and alerts from instruments (e.g., pressure and
flow transmitters, or level instrumentation) that require a
pump or some device to be on (to generate the flow or
pressure, or protect a pump from running dry) will be
ignored if the device to be protected is not on. Some
devices may not be On or Open because they are
manually overridden or are awaiting the proper operation
sequence before being adjusted by the PLC.
J1 (32)
C. Shutdown Alarms
a) Some alarms shut down a Process unit or entire plant (i.e.
the appropriate valves will close and pumps will stop
running). Restarting after a shutdown will require:
(i) the alarm condition (cause) be physically cleared.
(ii) the alarm be reset via the Alarm Reset
‘push-button’.
The reader should refer to the Control Logic Summary
Chart in the Zenon Operations and Mainteance Manual,
Section 4, for all the unit shutdown alarms. Some of the
alarms / alerts only put a unit into Standby and allow
the unit to go back into Production once the alarm has
been cleared (e.g., if a blower shuts down on overload, the
PLC will put the ZeeWeed® units into Standby until flow
is once again detected at the flow switch).
D. Multiple Alarms
It is possible for two or more independent alarms to occur at the
same time. Multiple alarms / alerts can be silenced by touching
the Horn Silence or Alarm Acknowledge button multiple
times, and reset with one depression of the Alarm Reset Push-
button (this button clears all alarm conditions in the PLC); any
alarm conditions that still exist will, however, immediately re-
annunciate.
J1 (33)
Note: Horn Silence will disable the horn for all active alarms. When a new
alarm/alert condition is triggered or an existing alarm condition is
cleared then reset again, the horn is automatically re-activated.
J1 (34)
CHAPTER 6 – PLACE IN SERVICE / TAKE OUT OF SERVICE
1. SEQUENCE CHARTS
The tables presented in Appendix 2 define which pumps and actuated
valves will be running and open in any condition of operation
(automatically or manually controlled) as well as which manual valves
must be opened or closed for any of the same operating conditions.
This startup sequence chart shows the order in which the devices in
the plant will be started up after a power interruption or after an
emergency stop has been reset. Unless other wise indicated, there is a
5-second delay between each step.
1. Wait 60 seconds to allow transmitters to warm up and complete a
self-diagnostics.
2. Align all valves as per factory default (power up from E2 PROM) or
last position. Start B-85-1 if it was in Auto On.
4. Start B-85-2 if it was in Auto On.
5. Start B-85-S if it was in Auto On.
6. Start P-101 if it was in Auto On.
7. Start P-102 if it was in Auto On.
8. Start P-103 if it was in Auto On.
9. Start P-104 if it was in Auto On.
10. Start P-36A if it was in Auto On.
11. Start P-36B if it was in Auto On.
12. Start P-13A if it was in Auto On.
13. Start P-13B if it was in Auto On.
J1 (35)
14. Start P-29A if it was in Auto On.
15. Start P-29B if it was in Auto On.
16. Start P-71A if it was in Auto On.
17. Start P-71B if it was in Auto On.
18. Put RO Unit 1 into same mode as prior to power interruption or E-
Stop.
19. Put RO Unit 2 into same mode as prior to power interruption or E-
Stop.
20. Start P-83 if it was in Auto On.
21. Put ZeeWeed® Unit 1 into same mode as prior to power
interruption or E-Stop (enable P-35-1 or P-35-S when substituted).
Put ZeeWeed® Unit 2 into same mode as prior to power interruption or
E-Stop (enable P-35-2 or P-35-S when substituted).
J1 (36)
CHAPTER 7 – OPERATE AND MONITOR SYSTEM
1. OPERATING PROCEDURES
In this sub-section, major equipment functionality is described. This
subsection focuses on hardware and simple control of devices that are
not interlocked with other major equipment. At the end of this section,
the control of the plant and key devices is described.
The unit processes are consistent with and are more or less broken out
as per the P&IDs. Some devices such as pressure transmitters,
flowmeters, etc. are not described, as they are considered self-
descriptive.
A. Equipment Layout
Drawing 9348-P-001 shows the equipment layout and is located
in Appendix 1.
B. Raw Water Feed System
a) Raw Water Feed Pumps
Supply water is taken from the inlet canal south of the
Wabamun Generating Station. A pair of pumps P-101
and P-102 are used to provide feed to the ZeeWeed®
Microfiltration System. To prevent the pumps from
running dead-headed, a 3-way Yarway control valve FCV-
165 is installed at the common pump outlet to provide
bypass flow back to the sump. Pressure switch PSH-150
protects the feed pumps in case of malfunction of FCV-
165.
J1 (37)
b) Feed Temperature Control Devices
A stand alone steam injection system is installed on the
feed line to maintain the feed water temperature at 25º C.
The temperature control system is not connected to the
PLC and is not controlled by ZENON. An additional
temperature transmitter TT-7621 is installed for
membrane protection.
c) Feed Flow Control Devices
Since the feed pumps operate at a constant speed, a feed
control system is installed to control the level in
ZeeWeed® Membrane Tanks. The feed control system
consists of a flowmeter FIT-7620 and a flow control valve
FCV-7620.
C. Chemical Pretreatment
a) Hypochlorite Addition
Sodium Hypochlorite is added to the raw water feed to
inhibit any bacterial growth. This ensures there will be
no biological activity in the system. Sodium Hypochlorite
addition is achieved by the sodium hypochlorite inject
assembly complete with a chemical tank TK-24 and a pair
of metering pumps P-24A and P-24B.
b) Ferric Chloride Addition
Ferric Chloride is added to the raw water feed to promote
coagulation in the ZeeWeed® membrane tank. This
improves the TOC removal by the ZeeWeed®
Microfiltration System. Ferric Chloride addition is
achieved by the ferric chloride injection assembly
J1 (38)
complete with a chemical tank TK-26 and a pair of
metering pumps P-26A and P-26B.
D. ZeeWeed® Microfiltration System
The primary purpose of the ZeeWeed® Microfiltration System is
to remove suspended solids and organic material prior to further
hardness removal and Reverse Osmosis (RO) membrane
treatment.
a) ZeeWeed® Unit 1 and Unit 2
The reader should refer to the Process and
Instrumentation Diagrams 9348-D-001 to 9348-D-005
(located in Appendix 1) to follow the description of the
equipment described below. The plant includes two
membrane tanks that hold membrane cassettes for both
ZeeWeed® Unit 1 and ZeeWeed® Unit 2. The two
identical units (except for device tag suffixes -1 and -2) are
for the most part independent of each other.
i) Membrane Tank (TK-34)
The membrane tank holds the membrane aerators
and membrane cassettes. The tank is also
equipped the following devices:
• Level transmitter and switches to monitor tank
level.
• Cassette isolation valves.
J1 (39)
ii) Membrane Cassettes
The ZeeWeed® filtration surface is a neutral, strong
polymeric membrane cast on the outside surface of a
porous support fibre. Each membrane tank contains two
membrane cassettes. Each cassette is supplied with 6
membrane modules but can accommodate 8 membrane
modules. The membranes separate the feed stream into a
product (permeate) stream and a concentrate (reject or
waste) stream. The membranes (contained in cassettes)
are connected to a top and bottom headers that are used
to draw permeate from the membranes to the process
pump. The membrane racks also contain aerators that
maintain a turbulent flow pattern along the membrane
fibres. This helps to keep the filtration surface clear of
contaminant build-up, which would cause a reduction in
the efficient operation of the unit.
J1 (40)
Coarse BubbleDiffuser
Coarse BubbleDiffuser
PermeateTo Bottom
Header
PermeateTo TopHeader
Membrane
Bulk Fluid(containing solids)
Aeration Bubbles(for fluid agitation)
SupportMaterial
Figure 7-1 ZeeWeed® Membrane Schematic
Figure 7-1 shows a schematic of a ZeeWeed® membrane
fibre in operation. The filtrate (permeate) is drawn
through the membrane from the bulk fluid by a partial
vacuum applied within the membrane fibre lumens.
Periodically, the membranes are backpulsed by pumping
J1 (41)
a fraction of the permeate back into the membrane fibres,
forcing flow in the reverse direction, to remove fouling
material from the surface of the membrane.
The ZeeWeed®-500 membrane modules consist of
many hollow fibres which are coated on the outside
with the membrane and run vertically between top
and bottom permeate headers on the membrane
module. Figure 7-2 shows a typical module
assembly.
J1 (42)
Figure 7-2 ZeeWeed® 500 Cassette
iii) ZeeWeed® Process Pump (P-35)
Each ZeeWeed® unit has a dedicated process pump
P-35. In addition there is a backup process pump
P-35-S described later that can be used with either
ZeeWeed® Unit 1 or ZeeWeed® Unit 2.
J1 (43)
Each process pump draws permeate from the
membranes and then is used to backpulse the
membranes. During Production, the variable
frequency drives control pump speed to achieve
desired permeate flow without exceeding the
allowed transmembrane pressure (TMP). During
Backpulse a constant backpulse pressure is
maintained. Detailed pump control for these cases
is provided in Part 2 Chapter 2.
The variable frequency drive (VFD) is set up with a
maximum and minimum range of operation. This
will provide protection to both the motor and
ancillary equipment. The adjustable output range
on the PLC is programmed to be within this VFD
range.
The VFDs are protected from undervoltage or
overvoltage changes. If there is an unacceptable
voltage change, the VFD will cut out and send a
signal to the PLC. The PLC will attempt to restart
the process pump three times at 30 second
intervals before recording a pump fault. This delay
(not adjustable from the MMI) must be greater
than or equal to the delay programmed into the
VFD.
J1 (44)
iv) Membrane Aeration Blower (B-85)
Aeration agitates the membranes to improve
permeation. Each ZeeWeed® unit has a dedicated
membrane aeration blower B-85. In addition there
is a backup aeration blower B-85-S described later,
that can be used with either ZeeWeed® Unit 1 or
ZeeWeed® Unit 2.
b) ZeeWeed® Backpulse/Break Tank (TK-88)
The permeate from each ZeeWeed® Unit is stored in a
common tank where it is available as backpulse water
and Softener/RO feed. The tank is equipped with a level
transmitter used for pump protection and control of
ZeeWeed® and RO units.
c) ZeeWeed® Cip Tank (TK-81)
A Wash procedure is required when the membranes
become fouled and are not capable of producing the
designed permeate flow. The membranes can be cleaned
in place using the CIP tank TK-81 equipped with a set of
level switches for pump protection and control. A portion
of the permeate from a running ZeeWeed® Unit can be
sent into the common CIP tank, where it is available as
backwash solution once the cleaning chemicals are added
(manual addition).
J1 (45)
d) Spare Blower B-85-S
The spare blower B-85-S has a B-85-1 / B-85-2 / None
selector switch. The operator must select whether blower
B-85-S is to operate for ZeeWeed® Unit 1, Unit 2, or
None. This transfers all control logic (blower B-85-S will
show B-85-1 or B-85-2 at the MMI) from the normal
blower to B-85-S. Selecting blower B-85-S to operate for
another blower will also disable that blower.
e) Spare Process Pump P-35-S
The spare process pump P-35-S has a Unit 1 / Unit 2 /
None selector switch. The operator must select whether
process pump P-35-S is to operate for Unit 1, Unit 2, or
None. This transfers all control logic (process pump P-
35-S will show P-35-1 or P-35-2 at the MMI) from the
normal process pump to the spare process pump P-35-S.
Selecting process pump P-35-S to operate for a ZeeWeed®
unit will also disable the normal process pump for that
ZeeWeed® unit.
f) Vacuum Pumps (P-36A and P-36B)
The process pump (P-35-x) can lose its prime due to excess
air in the treated water. The system contains a pair of
vacuum pumps P-36A and P-36B. Only one pump is
required to remove air that is entrained in the permeate
before it is drawn into the process pumps for both
ZeeWeed® units. The air and water enter the Air
Separation Vessel TK-35-1 and TK-35-2 where the air is
allowed to separate from the water. The vacuum pump
removes the separated air from the water.
J1 (46)
One or two vacuum pumps can be operated at a time. The
first pump placed in Auto mode becomes the lead pump
and starts automatically. The other pump (when in
Auto) becomes the standby pump. If the operator presses
Stop for the pump that is running (or the pump fails), the
standby pump will become the lead pump and will come
on automatically. Start must be used for the second
(standby) pump to operate two pumps at the same time.
E. Dual Softener System
a) Bisulphite Addition
Sodium bisulphite is added to the softener feed water to
reduce any oxygen that may be present. Removing
oxygen makes the water less corrosive. Sodium bisulphite
addition consists of a tank (TK-23) and a pair of metering
pumps P-23A and P-23B.
b) Softeners
Softeners are provided to remove hardness (multivalent
cation removal) from the prefiltered water. These ions
are replaced with sodium and chloride. If hard water is
allowed to enter the Reverse Osmosis (RO) units, the
membranes would rapidly become fouled with
precipitated material. Two Softener units marked as unit
A and B are provided. Each Softener unit has a capacity
of approximately 185,000 gallons (24 hours during
NORMAL operating conditions). Only one Softener unit
J1 (47)
is On-line at a time (the other unit is either in Standby
or Regeneration).
c) Softener Regeneration System
A brine system is used to regenerate the softeners.
Pretreated water is continuously fed to the brine tank TK-
29 which dissolves rock salt to make brine. A level control
valve maintains a constant level in the brine tank. A pair
of pumps (P-29A and P-29B) are provided to pump brine
through the softener during a regeneration cycle (brine is
diluted before entering the softener), which lasts
approximately 1 ½ hours.
F. Reverse Osmosis (RO) Pretreatment
The RO Pretreatment equipment consists of a pair of cartridge
filters, caustic feed system (TK-25, P-25A, P-25B, AIT-2520) and
RO feed conductivity analyzer AIT-4131. The cartridge filters
are used to remove any residual suspended solids or
demineralizer resin beads (5 µm nominal).
Inlet and outlet filter pressure indicators allow verification of
the filter condition.
The addition of caustic hydroxide improves the quality of the
product water by promoting elimination of dissolved CO2.
J1 (48)
G. Reverse Osmosis (RO) System
This water treatment system employs a dual pass Reverse
Osmosis (RO) system as the primary means to eliminate
dissolved material in the softened feed water. The membranes
used are a spiral wound module design (see Figure 7-3).
Anti-Telescoping Device
Concentrate
Permeate
Perforated CentralTube
Feed Solution
Carrier Material
Sealed Edge(glue)
Outer Layer SpacerMaterial
Membrane
Feed ChannelSpacer
Membrane Backing Material
Permeate Flow(after passing thru membrane)
Figure 7-3 Spiral Wound Module Design
RO is a pressure induced reversal of the natural flow
phenomenon of osmosis. Osmosis is the spontaneous passage of
a liquid through a semi-permeable membrane from a dilute to a
more concentrated solution (see Figure 7-4).
J1 (49)
PI
Figure 7-4 Reverse Osmosis
The membranes then separate the feed stream into a 'purified' product
stream (called Permeate) and a concentrate stream (called
Concentrate), in which the bulk of the mineral salts, bacteria etc.
from the feed stream are now located (see Figure 7-5).
Figure 7-5 Reverse Osmosis Membranes
The system contains two trains tagged as RO Unit 1 and RO
Unit 2 (all devices within each train have tags with a suffix –1
J1 (50)
and –2 respectively. Each pump within RO system is duplicated
(duplicated pumps have a suffix A and B).
a) First Pass RO
The process pump P-41A/B pressurizes the feed water to
the design pressure required by the First Pass RO
membrane array (4:2 configuration). The operating point
for the First Pass RO is set by two manually adjusted
valves HCV-4181 and HCV-4082 (refer to drawing 9348-
D-006 Appendix 1). First Pass RO permeate is fed to the
Second Pass RO and the First Pass RO reject stream is
send to drain.
b) Second Pass RO
The process pump P-43A/B pressurizes the First Pass RO
permeate to the design pressure required by the Second
Pass RO membrane array (2:1:1 configuration). The
operating point for the Second Pass RO is set by two
manually adjusted valves HCV-4381 and HCV-4282 (refer
to drawing 9348-D-007 Appendix 1). Second Pass RO
permeate (RO product) is sent to the EDI System and the
Second Pass RO reject stream is diverted to the First Pass
RO feed.
c) RO Clean in Place (CIP) System
The CIP (Clean in Place) system is used to clean the RO
membranes when they become fouled. It may also be
used to recirculate membrane preservatives into the
membrane housings if the membranes are to be stored for
extensive periods of time. Both of the above procedures
J1 (51)
require the operator to place an RO unit in Wash mode
and to adjust the position of manual valves to configure
the required recirculation loop. Tank TK-83 is used to
prepare the cleaning solution (or preservative). The built-
in electric heater H-83 maintains proper temperature of
the cleaning solution. This unit is also used to provide
Cleaning Solution to the EDI.
H. Electrodeionization (EDI) System
The Electrodeionization (EDI-150) System provided by Ionics is
a stand alone unit that will further purify the RO permeate by
removing any residual silica and carbon dioxide. It has its own
Operating and Maintenance Manual.
I. Dual Mixed Bed Ion Exchange Polishing Unit
The mixed bed ion exchange system is used as a polishing to
replace the EDI unit should it fail to produce quality water and
require cleaning. This is a stand alone passive unit with no
controls associated with the unit.
Note: Caustic injection must be started prior to putting mixed
beds in service.
J. Distribution Break Tank with Outlet Feed Pumps
a) Break Tank TK-71
Break Tank TK-71 serves as a reservoir of treated water.
The treatment system will maintain this tank level at
above LYH1-7126. During NORMAL operation the 80
J1 (52)
USgpm will be recirculated through the EDI system (FV-
7184).
b) Outlet Feed Pumps P-71A/B
The pair of outlet pumps provide pressurized feed for
boiler feed tanks and recirculate the contents of the
Distribution Break Tank through the EDI system. When
in DOUBLE capacity mode (peak flow) due to high water
production/consumption the recirculation loop is closed.
K. Reserve Feedwater
The treated water from the Distribution Break Tank will be fed
to the existing RFW tanks TK#1a, TK#1b, TK#2a, TK#2b, TK#3,
and TK#4. From the control point of view the pair TK#1a and
TK#1b can be treated as a single tank. The same applies to
tanks TK#2a and TK#2b.
Each tank is equipped with a corresponding high level switch
that indicates when the tank is full.
Pressure switch PSH-153 installed on the common tank feed
header protects outlet feed pumps P-71A and P-71B from
running dead-headed.
L. Sump Pumps
A pair of pumps P-103 and P-104 are used to empty the local
sump. To prevent the pumps from running dead-headed, a 3-
way Yarway control valve FCV-166 is installed at the common
pump outlet to provide bypass flow back to the sump. Pressure
switch PSH-155 protects the feed pumps in case of malfunction
J1 (53)
of FCV-166. Sump level is measured by level transmitter LIT-
156.
2. OPERATING PROCEDURES
A. ZeeWeed® Operation
a) Cleaning Of The ZeeWeed® Membranes
i) Materials Required
Sequence Chart and P&ID: The system
Sequence Chart (Appendix 2) and P&ID’s
(Appendix 1) are required.
Chemicals: Depending on the type of cleaning
required and the fouling on the membranes, a
sodium hypochlorite solution, MC-1 (citric acid)
cleaning solution may be required. ZENON will
advise the customer what chemicals are suitable.
ii) Safety
Always wear safety goggles, boots and gloves when
handling the cleaning chemicals. Overalls are
mandatory. Also, be familiar with and follow the
MSDS for each chemical, included in Appendix 3
Material Safety Data Sheets.
iii) Cleaning in General
The frequency of cleaning will depend on the
specific operating conditions (operating time, feed
flow rates, permeate flow rates) and on the
particular chemistry of the fluid being processed.
J1 (54)
During normal operation, membranes can become
fouled by mineral salts (CaCO3, CaSO4, MgSO4), as
well as iron (Fe), insoluble organics (e.g., oil) or
biological matter (bacteria or products from
bacterial action). Deposits build up on the
membrane surface during operation and cause a
loss in flux. It should be noted that flux will drop if
the feed temperature decreases. This is normal
and does not necessarily indicate fouling.
In order to maximize membrane life and operation,
the system automatically undergoes backpulse
cleaning periodically to remove deposits from the
surface of the ZeeWeed® membrane. This
minimizes fouling and increases the time required
between chemical cleanings of the system.
Chemical cleaning of the ZeeWeed® membranes is
required whenever the transmembrane (TMP)
reaches -45.0 kPa (14.0 “Hg”). If the ZeeWeed®
membrane cleaning is not done at the
recommended time, further fouling may be
irreversible. Cleaning is facilitated by increased
temperature and reverse permeation. With
chemical cleanings, the ZeeWeed® membrane
CAUTION:
Proper data normalization is required to analyze
the parameters
J1 (55)
permeability must be recorded before and after a
cycle in order to determine the effectiveness of the
cleaning.
1) Cleaning Chemicals
Normally, a sodium hypochlorite (NaOCl)
solution is sufficient if a chemical washing of
the ZeeWeed® membranes is required. For
more severe fouling that can not be removed
with this solution, ZENON offers specifically
designed and formulated cleaning chemicals
for ZENON ZeeWeed® membranes. These
approved cleaning chemicals should be used
with the wash procedures given in this
manual. Safety and handling instructions
for these cleaning chemicals can be found in
Appendix 3: Material Safety Data Sheets.
WARNING
NEVER APPLY BACKWASH OR BACKPULSE PRESSURES
GREATER THAN 10 PSIG (24.7 PSIA) ACROSS THE ZEEWEED®
MEMBRANE. DELAMINATION MAY OCCUR RESULTING IN
IRREVERSIBLE DAMAGE TO THE MEMBRANE.
NOTE
The greater the pressure during the cleaning, the greater the
reverse permeation flow rate of the wash solution into the process
tank. Also, no treated water is being produced during any cleaning
method.
J1 (56)
APPROVED CLEANING CHEMICALS
SODIUM
HYPOCHLORITE
An oxidation agent used to remove organic fouling on the
membranes.
ZENON MC-1 An acidic cleaning agent used to clean the membranes in the
event of fouling due to mineral scales, iron or other metals
fouling.
The concentrations, amounts and design pH
of the approved cleaning chemical solutions
are given below. The total required quantity
is based on a wash solution prepared with
100 US gallons of potable water. The
chemical quantities should be adjusted if the
actual pH of the solution is different from the
design pH or a different volume of water is
used to prepare the solution. Also, the
amount of sodium hypochlorite required is
based on a 12% solution, this amount must
be adjusted if a different sodium hypochlorite
solution is used.
NOTE
Other cleaning chemicals may contain materials incompatible with
the ZeeWeed® membranes and should NOT be used. Use of non-
approved cleaning chemicals voids any membrane warranties.
J1 (57)
CHEMICALS REQUIRED PER WASH OF THE MF SYSTEM
Chemical Purpose Design Wash
Concentration
Approx. Quantity
Required
Design pH
During Wash
Sodium
Hypochlorite
Organic Cleaner 250 mg/L 800 mL
(0.2 US gal.)
n/a
MC-1 Scale Removal 20 g/L 7.6 kg 2.5 - 3.5
2) Cleaning Chemical Selection
A cleaning chemical’s effectiveness in
removing a particular foulant can only be
determined through experience with
operation of the system. Occasionally it may
be necessary to use different types of
cleaners during a cleaning cycle to remove
foulant mixtures or to determine the best
cleaning chemical for the wash.
Initially, the system should be cleaned
monthly with sodium hypochlorite solution,
carefully recording the data on the cleaning
log sheet (see Appendix 2). This data should
be faxed to the ZENON Service Department,
at (905) 639-1812, for a review and
recommendation each month. Depending
SAFETY NOTE
Handle the cleaning chemicals with care (refer to Appendix 3
Material Safety Data Sheets). Wear a face mask, rubber apron and
rubber gloves when handling these chemicals.
J1 (58)
on the performance obtained, the
cleaning intervals may then be
increased from once per month to
correspond with a permeate flux
decline of 20%.
If cleaning with the sodium hypochlorite
cleaning solution does NOT correct for
fouling, cleaning with the other cleaning
chemicals should be performed. Either or
both alternate cleaning chemicals may be
required.
ZENON also recommends that the system be
cleaned thoroughly with sodium hypochlorite
(and possibly MC-1, if experience finds either
to be necessary), and sanitized prior to any
shutdown longer than 72 hours.
iv) Backpulse Cleaning
Backpulse cleaning uses permeate from the effluent
stream stored in the Backpulse Tank. Chlorine (in
the form of sodium hypochlorite) is automatically
added to the ZeeWeed® Membrane Tank Feed for
disinfecting purposes, and the permeate is pumped
back through the membranes at low pressures and
NOTE
Proper data normalization is required.
J1 (59)
high flow rates (up to 200% of the normal
permeation rate). During a backpulse, the
permeate is pumped to the inside of the membrane
fibres and pressed backwards through the fiber and
membrane to remove any particles that may have
adhered to the membrane surface.
Backpulse cleanings occur automatically during
normal operation of the system, at an operator set
frequency and duration. This frequency and
duration will be continually optimized by the
operator for changes in operating conditions and
the feed to the system. During periods of high
permeation, the backpulse duration can be limited
by the capacity of the Backpulse Tank. If the
system runs out of stored permeate during a
Backpulse, the system will automatically stop the
cleaning, reset the system and Backpulse timer and
return to normal operating mode.
A backpulse can also be initiated by the operator of
the system, by touching the “Initiate Backpulse”
button on the Man-Machine-Interface (MMI). This
will cause a backpulse to occur for the duration
already set by the operator, and the backpulse
timer will be reset so that future backpulses will
occur at the set frequency. The “Initiate
Backpulse” button is only active in RUN mode.
J1 (60)
v) BackWash Cleaning
A backwash is similar to a backpulse except that
backwash does not return to production after time
expires but goes to WASH Standby. A backwash
can also be run through the membranes for as long
as the operator wants by touching the “Initiate
Backwash” button, which is only active in WASH
mode. The system will then backwash the
membranes until the time expires or low level alert
on the CIP Tank is reached (which can be
prolonged by adding potable water to the CIP
Tank) whichever comes first. For improved
cleaning of the membranes, warm water (80 -
100oF) and cleaning chemicals can also be added to
the CIP Tank to be pumped through the
membranes. Potable water (and additional
chemicals, if being used) will have to be added to
the CIP Tank if more than one backwash is desired,
and this process may be repeated as often as
required. Remember to thoroughly flush the
system and drain and rinse the CIP Tank if
switching cleaning chemicals.
vi) Process Tank Soak Chemical Cleaning
A soak chemical cleaning should be used if the
automatic backpulsing of the system does not
maintain membrane performance above the
specified level, or if the automatic switching detects
that the membrane suction pressure is too high.
J1 (61)
This cleaning uses potable water with sodium
hypochlorite (NaOCl) at 200 to 300 ppm, MC-1
cleaner at a pH of 2.5 - 3.0. Better results are
achieved if the water is allowed to warm up to room
temperature overnight. Caution: The cleaning
solution using NaOCl should be limited to a
maximum pH of 10.5. The procedure is as follows:
1. Initiate a Backpulse of the system, and record
the operating data of the system before and
after the Backpulse.
2. Drain Process Tank and refill with clean water.
3. Prepare and add the appropriate chemical
solution required for the cleaning procedure in
both the CIP Tank and the Membrane Tank,
and, in WASH mode, initiate a backwash of the
membranes to fill the membrane lumens with
the cleaning solution.
4. Turn the system to OFF and add the required
amount of cleaning chemical to the Membrane
Tank.
5. Allow the ZeeWeed® membranes to soak in the
cleaning solution. For best results, this solution
should be allowed to warm to room temperature.
Periodic cycling of the aeration blower for
agitation is recommended.
J1 (62)
6. Drain and flush the CIP Tank to the waste
sump. Neutralize or dechlorinate the cleaning
chemicals as required. Refill the CIP Tank with
potable water.
7. Drain the Membrane Tank to the waste sump.
Refill Tank and cycle blower to rinse chemicals
out of the system. Drain. This step may be
repeated several times as needed. In WASH
mode, backwash the membranes several times
with potable water.
8. Refill Membrane Tank and confirm the chlorine
residual in the membrane tank is less than 1
mg/L before returning the system to operation.
9. After chemical cleaning is finished, the system
can be returned to RUN mode and placed in
AUTO.
10. Neutralize or dechlorinate the spent cleaning
chemicals as required prior to discharging them
to the waste sump.
11. Repeat Step 1 so that effectiveness of the soak
chemical cleaning may be evaluated.
vii) Membrane “Empty Tank” Chemical Cleaning
If required, chemical cleaning of the membranes
can also be enhanced by lowering the tank level
below the bottom of the cassette before performing
the wash procedure. Please contact ZENON’s
J1 (63)
service department at (905) 639-6320 before
proceeding with this type of cleaning method.
1) Empty the tank contents (at least until the
level is below the bottom of the membrane
cassettes).
2) Close valves (HV-3483-1A/1B or HV-3483-
2A/2B) to bottom membrane permeate
header.
3) Prepare a cleaning chemical solution in the
CIP Tank and pump a portion of the cleaning
solution through the membranes until it has
coated the outer membrane surface. Allow
this to soak on the membranes for a short
period of time. Repeat this cycle several
times.
4) This cleaning cycle may be repeated with
either another or a fresh chemical solution
until the cassette has been sufficiently
cleaned. Remember to thoroughly flush
the system and drain and rinse the CIP
Tank if switching between cleaning
chemicals. The cleaning log sheet must be
completed before and after any cleaning
sequence.
CAUTION
Extreme caution must be used when performing this procedure to
ensure that the membranes are not allowed to dry out or freeze.
J1 (64)
viii) Membrane Permeability Restoration Monitoring
Membrane permeability is a calculated operating
parameter (flux/TMP) and should be recorded
before and after every membrane cleaning, and
several times daily before and after a Backpulse
cleaning.
The effectiveness of each cleaning procedure can be
verified by comparing the membrane permeabilities
from before and after the cleaning procedure is
performed, but these values must be temperature
corrected in order to give a useful comparison of
the values. Water temperature directly affects
water viscosity and, therefore, the permeability
observed, as do changes in the operating pressure
of the system. The following method can be
employed to correct the membrane permeability.
• Record the permeate flow rate of the system (in
L/s) and the membrane pressure (in kPa), from the
MMI, and the operating temperature from the
permeate temperature gauge.
• Convert to membrane flux (in USgpm/ft2/day, or
GFD) by dividing the flow rate by the total
membrane surface area, and multiplying by
Flow (US gpm) = Flow L/s x60sminx 3.7854 L
1 USGal
J1 (65)
1440 minutes/day. For this system, the
membrane surface area per train is:
• The observed flux must be corrected for
variations in temperature between
measurements. All recorded fluxes should be
corrected to a common reference temperature so
that future comparisons will be valid. This
reference temperature, Tref, should be selected
as a typical process temperature that the
membranes will operate in. The following
formula and water viscosity table can be used to
obtain the temperature corrected flux.
Flux @ TRef= Flux @ T1 x viscosity @ T1
viscosity @TRef
3. STANDARD OPERATING PARAMETERS
A. Chemistry
a) Free chlorine at the ZeeWeed® sample points should have
a value of between 0.4 and 0.8 mg/l. Values less than this
result in the possibility of insufficient free chlorine to
prevent bacterial fouling. More than this is a waste of
bleach.
Membrane Surface Area = 500ft
modulex 6Modules= 3000 ft 2
2
J1 (66)
b) Free chlorine at either RO inlet should measure between
0.0 and 0.06 mg/l. These values may be considered as
zero for all intents and purposes. The sodium
metabisulfite injection is used to reduce the free chlorine.
c) Hardness should always be at a value of less than 4 mg/l
of total hardness. Experience shows that normal values
of hardness will be at 0.0 to 0.85 mg/l. When values are
found as high as 1 mg/l the softener should be considered
as being near exhaustion and will probably be at
exhaustion in the next 30 to 60 minutes.
B. ZeeWeed®
a) TMP values on the screen should generally not exceed a
value of –6.5 during the production run at a set point of
134 gpm. If the TMP value is greater than this, fouling of
the ZeeWeed® membranes should be suspected.
b) Production flow rate on the ZeeWeed® is normally set at
134 gpm. The exception to this rule is when tank 88
reaches 91% full. At this time the set point will ramp
down to 70 gpm and will stay there until the tank level
drops to 90%. At this time it will ramp back up to 134
gpm again. If the production flow does not achieve the
134 gpm flow rate at any time during the production run,
the membranes are probably fouled and require cleaning.
c) Feed Temperature to the ZeeWeed® should be kept
between 25 and 28ºC.
J1 (67)
d) ZeeWeed® tank operating levels should be at a level
greater than 82%. If the level drops below this point the
ZeeWeed® will shut down to protect the membranes from
drying out. The ZeeWeed® will not restart until the
water level in the tank has recovered to 85%.
e) Backpulse flow rate on the ZeeWeed® should be at 212
gpm. This is 1.5 times the normal production flow rate.
If the backpulse flow rate does not reach 212 gpm, the
ZeeWeed® membranes probably need cleaning.
f) Production Mode duration is normally set at 12 minutes.
This value may change from time to time, especially
downwards if there is an unusually high level of
suspended solids in the feed water. This is most likely to
occur for a short time during spring run off.
g) Backpulse Mode duration is normally set at 30 seconds.
This value is not very likely to be changed.
h) Backpulse break tank level should range between 91%
and 25%. When the level reaches 91%, the ZeeWeed®
unit set point will ramp down to 70 gpm. When the level
reaches 25%, the softeners, RO units and EDI will all
shut down until the backpulse break tank level achieves a
value of 40%. At this time, these components will restart.
It is not unusual for the backpulse break tank level to be
depleted during continuous DOUBLE MODE operation.
Do not take the ZeeWeed® readings if the ZeeWeed® flow
rates are switching from 134 to 70 gpm and back again as
the readings will not have any value. Only take them
J1 (68)
when the flow rate set point will continuously be at 134.
This is generally when the backpulse break tank has a
level of 87% or less.
C. Softener
a) Backwash flow rate should be set between 90 and 100
gpm.
b) Instrument air pressure must be available at a minimum
of 60 psi during a backwash. Pressure less than this will
prevent the brine inlet valve from opening up because the
brine inlet valve actuator is spring loaded to close.
c) Micron filter back pressure should never be allowed to
exceed 5 psi with both micron filters in service or 10 psi
when only one filter is in service. Both filters should be
kept in continuous service, even though they are both
capable of 100% flow, to prevent the build up of bacteria
in an idle filter. The filter elements are replaceable and
should be replaced when the pressure differential is
higher than that indicated above, or whenever the service
duration has reached two months, whichever comes first.
D. RO Units
a) Recovery for the first pass should be set at between 69
and 71%. The recovery rate for the second pass should be
between 84 and 86%. The recovery is adjusted by opening
or closing the appropriate reject valve until the desired
recovery rate is achieved.
J1 (69)
b) Product flow for the second pass should be at 88 gpm for
NORMAL MODE operation and at 84 gpm for DOUBLE
MODE operation. The reason for the difference is that
the EDI unit blows down approximately 8 gpm regardless
of the mode of operation. Therefore in order to have a net
80 gpm in NORMAL MODE, a single RO unit will have to
produce 88 gpm. The product flow of the first pass will be
whatever is required to provide the second pass with its
product flow rate plus its reject flow rate.
c) Inlet pressure should be set at whatever level is required
to produce 84 or 88 gpm at the second pass outlet. If the
temperature of the water is lower than normal, the inlet
pressure would have to increase.
E. EDI Unit
a) Product flow rate on the EDI unit should be set at
approximately 160 gpm regardless of the mode of
operation. This is solely dependent on RO output when
the plant is in DOUBLE MODE and, therefore, subject to
a large degree on the water temperature because the RO
units may not be capable of full flow if the water
temperatures are low. In NORMAL MODE operation, the
flow through the EDI is determined by both the RO
production and the amount of recirculation water being
routed back to the EDI.
b) Stack amperage should be limited to 4.0 amps on stack 1.
A split on either side of the 4 amp mark between stack 1
J1 (70)
and stack 2 is acceptable. It is normal for stack 1 to have
the highest current flow.
c) Product resistivity on the EDI should always be greater
than 10 mega ohms while it is running. It is not
uncommon for the resistivity to drop below 10 mega ohms
for a few seconds during startup. Normal values for
product resistivity will be 16.5 to 17.3.
d) Brine conductivity on the EDI should range from 150 to
200 uS. The brine injection pump on the EDI is set to
start and stop as required to maintain this conductivity.
F. Transfer System
a) Transfer tank level should range between 21% and 89%.
At 20% the transfer will be suspended in order for the
tank level to be restored. At 90% the EDI RO units and
softener will shut down until the product tank level drops
to 84%. At this time, the shut down equipment will
restart automatically. While this operation will occur
without intervention, it is good practice for the operator to
be present to observe the startup.
4. ALTERNATING BETWEEN PRODUCTION MODES
A. Switch from normal to double mode.
There is no need to shut off the EDI anymore. From the
panelview, select F15 to bring up the NORMAL/DOUBLE
MODE screen. Press F2 to select DOUBLE mode. Press F21 to
J1 (71)
select the MAIN screen again. Press F5 to select the RO
SYSTEM screen. If RO #1 is not running, press F1 to start the
unit. If RO #2 is not running, press F8 to select the screen for
RO #2 and then press F1 to initiate a start. The display will
indicate production mode and after a brief flushing period the
first pass RO process pump will start. After a delay of 5
seconds, the second pass RO process pump will start. The RO
will operate with its product going to waste until the second
pass product has shown a conductivity of less than 20 uS for 30
seconds. At this time the RO product flow will divert from waste
to EDI inlet and the recirculation valve at the transfer pumps
will close. The RO units should both be balanced to allow a
maximum production of 84 gpm per RO and the rejects should
be adjusted to 70% for the first pass and 85% for the second
pass. The EDI should now be balanced on the brine and product
flows and the transfer rate should be balanced with the EDI
production rate.
B. Switch from double to normal mode.
There is no need to shut off the EDI anymore. From the
panelview, select F15 to bring up the NORMAL/DOUBLE
MODE screen. Press F1 to select NORMAL MODE. Return to
the main screen and press F5 to bring up the RO SYSTEM
screen. Press F2 to shut RO1 down or press F8 to select the
screen for RO2 and then press F2 to shut RO2 down. At this
point, the system will be in NORMAL MODE and the
recirculation valve to the EDI will open. The RO unit should
now be adjusted to a maximum flow of 88 gpm and the rejects
J1 (72)
should be adjusted to 70% and 85% for the first and second
passes. The EDI should also be balanced as necessary.
C. To switch from one RO to the other during extended
NORMAL MODE operation.
During extended NORMAL MODE operation, the RO units
should be switched every shift to prevent microbial growth in
the membranes. In order to do this, first switch from NORMAL
MODE to DOUBLE MODE as described above. After this has
been completed, switch from DOUBLE MODE to NORMAL
MODE also as described above. When switching back to
NORMAL MODE, shut down the RO which was running
previously.
D. To perform a Silt Density Index (SDI) test.
The SDI test is done in order to determine the effectiveness of
the microfiltration process. It consists of measuring the time
required to flow two 500 ml samples of water through a 0.45
micron filter with the samples being taken at 15 minute
intervals and the pressure held constant at 30 psi. Water is
flowed through the filter for the entire 15 minutes.
First, remove the hose from the filter housing and unscrew the
filter housing from the attached piping. Open the inlet valve to
the pressure regulator and ensure that the system is free from
air by briefly opening the valve at the end of the horizontal run
of piping attached to the pressure regulator outlet. Close the
vent valve and crack the admission valve for the filter housing
and allow the water to run in order to flush out the piping and
J1 (73)
regulator. Take the filter housing to the WTP control room and
open the housing by removing the three plastic screws from the
housing and separating the two halves. Remove the o-ring and
set aside for re-use. Remove the old filter paper and discard.
Wipe the filter housing outlet with a clean rag where the filter
paper sits in order to remove any water present on the outlet
screen. Use the tweezers to get a new filter paper from the
container and lay it carefully over the screen of the outlet half of
the filter housing. Ensure that the paper is centered in the
holder and that there are no holes in the paper, especially where
the tweezers were in contact with the paper. There are two
types of papers, glossy on one side and the same on both sides.
With the first variety, the glossy side should be on the water
inlet side, the other variety does not matter. Be careful to not
touch the paper with your fingers as fingerprints on the
paper could seriously affect the test results. Re-install the
o-ring with the tweezers and place the inlet half of the filter
housing carefully over the outlet half. Install the three plastic
screws, tightening all of them evenly and ensuring that the
knobs on each screw are arranged to allow maximum clearance
around the inlet hole. Bring the filter housing back to the test
apparatus and shut the water admission valve. Screw the filter
housing on under the admission valve and attach the hose to the
end of the adapter attached to the filter housing. Re-open the
admission valve and adjust the regulator screw until the
pressure on the gage reads 30 psi. Using an empty 500 ml
container and a stop watch, measure the time required to flow
500 ml into the container. Empty the container and allow the
stop watch and the water to continue running until the end of
J1 (74)
the test. When the time on the stopwatch reaches 15 minutes,
refill the 500 ml container and record the time required to flow
the next 500 ml. Enter these figures into the Logsheets
spreadsheet on the SDI worksheet. The spreadsheet will
automatically calculate and display the SDI value for the times
that have been recorded.
E. ZeeWeed®
a) To start a ZeeWeed® unit.
Prior to starting the ZeeWeed® units, check the
lubrication levels in all pumps and blowers. The
appropriate oil for the pumps is Teresso 46, while the
blowers use Spartan synthetic EP320. Ensure that the
manual valves connecting the pump suctions and
discharges to the ZeeWeed® modules and the backpulse
break tank are in the appropriate positions. If in doubt,
trace the lines for flow path. Ensure that the manual
valves connecting the air blowers to the ZeeWeed® tank
module headers are in the appropriate positions.
Proceed to the panelview in the control room. From the
main screen, press the F3 button to bring up the
ZEEWEED® SYSTEM screen. The screen will default to
the ZeeWeed® 1 system. To select the ZeeWeed® 2
system, press the F8 button. From the appropriate
screen, press the F1 button to initiate a start on the
ZeeWeed® unit. The screen should indicate that the unit
is in STANDBY MODE and will time out for 5 seconds.
The vacuum pump and blower will start running at this
J1 (75)
time. The unit will then go into BACKPULSE MODE and
the unit will backpulse for 30 seconds. When the
backpulse is complete, the unit will go into
PRODUCTION MODE until the next backpulse.
b) To shut down a ZeeWeed® unit.
Proceed to the panelview in the control room. From the
main screen, press the F3 button to bring up the
ZEEWEED® SYSTEM screen. The screen will default to
the ZeeWeed® #1 system. To select the ZeeWeed® #2
system, press the F8 button. From the appropriate
screen, press the F2 button to initiate a stop on the
ZeeWeed® unit.
c) To perform a manual backpulse of a ZeeWeed®unit.
Proceed to the panelview in the control room. From the
main screen, press the F3 button to bring up the
ZEEWEED® SYSTEM screen. The screen will default to
the ZeeWeed® #1 system. To select the ZeeWeed® #2
system, press the F8 button. From the appropriate
screen, press the F5 button to initiate a manual backpulse
on the ZeeWeed® unit. The unit will backpulse as usual
and will go back into normal service as soon as the
backpulse cycle is completed. This step is useful if you
wish to stagger the backpulses between the units or if the
unit is starting to foul but water demand will not allow a
proper clean to be done.
d) To start the second ZeeWeed® with one running and plant
in NORMAL MODE.
J1 (76)
Proceed to the panelview in the control room. From the
main screen, press the F3 button to bring up the
ZEEWEED® SYSTEM screen. The screen will default to
the ZeeWeed® #1 system. To select the ZeeWeed® #2
system, press the F8 button. From the appropriate
screen, press the F1 button to initiate a start on the
ZeeWeed® unit. The unit will go to STANDBY MODE for
five seconds and will stay there. To complete the start,
press the F1 button again to complete the start. The unit
will now start up as described above.
F. Softeners
a) To start a softener.
Prior to starting the softener, check that all of the manual
valves are in the correct positions and that the softener
process pumps have adequate oil in them. The proper
lubricant for the pump is Teresso 46.
From the main screen on the panelview, press F4 to select
the SOFTENER SYSTEM screen. Press F1 or F6 to start
the appropriate softener. Once the appropriate button
has been pushed, the softener will go to STANDBY
MODE until the RO units call for water. When this
happens, one of the softener pumps will start and the unit
will flush for one minute prior to sending water to the
micron filters. For economy of salt consumption, select to
run the softener with the highest flow total which has not
exceeded the total gallons allowed. This value is 180,000
gallons. Do not choose to delay softener regenerations by
J1 (77)
switching softeners prior to reaching total gallons. This is
very bad operating etiquette and can lead to both
softeners being exhausted at the same time. If this
happens, the RO units must be shut down until at
least one of the softeners has been regenerated.
Also this can lead to poor regenerations because the brine
may not have time to reach full strength with back to
back regenerations.
b) To shut down a softener.
Prior to shutting off a softener, it is imperative that the
RO units, which are supplied by the softener, are not
running. From the main screen on the panelview, press
F4 to select the SOFTENER SYSTEM screen. Press F2 or
F7 to shut off the appropriate softener. The pump will
already be off because it will only run when called to do so
by RO or regeneration demand.
c) To regenerate a softener.
Prior to starting the softener, check that all of the manual
valves are in the correct positions and that the softener
process pumps have adequate oil in them. The proper
lubricant for the pump is Teresso 46. Also ensure that
there is at least 60 psi of instrument air pressure
available in order for the brine inlet valve to open, as this
valve is spring to close.
From the main screen on the panelview, press F4 to select
the SOFTENER SYSTEM screen. Press F2 or F7 to shut
off the appropriate softener. When the softener is in the
J1 (78)
OFF MODE, press F3 or F8 to initiate the regeneration
on the desired softener. The softener will immediately go
into BACKWASH MODE. During this period, it is
important that the backwash be observed through the
vessel window for bed lift. Also the backwash flow rate
should be at a value of 90 to 100 gpm. The BACKWASH
is followed by the REGEN BED SETTLE, BRINE
INJECTION, SLOW RINSE, and finally by the FAST
RINSE. At the end of the fast rinse, the regeneration is
complete and the unit will go to STANDBY MODE.
d) To switch from one softener in service to the other in
service.
From the main screen on the panelview, press F4 to select
the SOFTENER SYSTEM screen. One softener will be in
service and the other will be in either OFF MODE or
STANDBY MODE. If the softener is in OFF MODE,
press F1 or F6 to bring the softener to STANDBY MODE.
Then press F19 or F20 to bring the new softener online.
The new softener will flush for a short while and will then
go into PRODUCTION MODE. The original softener will
then go into STANDBY MODE. This method of switching
can only be done when the panelview is displaying the
alert TOTAL REACHED and can be done without taking
the RO units or the EDI unit out of service. It is not
normally recommended to switch softeners out of service
until the TOTAL REACHED alert has been displayed
unless the unit has exhausted prematurely. If this is the
J1 (79)
case, notify the Zenon representative on the next day
shift.
G. Reverse Osmosis
a) Start an RO unit.
This operation may be done in either the NORMAL
MODE or in the DOUBLE MODE. If it is desired to run
only one RO unit, the system should be set in NORMAL
MODE to allow for proper operation of the EDI unit. If
DOUBLE MODE is required, and no RO units are
running, RO #1 must be started first. The system may be
switched from NORMAL MODE to DOUBLE MODE and
back to NORMAL MODE at any time when the RO units
are running. It is preferred to leave the EDI running
during the switching process. The transfer/recirculation
valves are programmed to delay switching until the
appropriate RO functions have been completed. Prior to
starting an RO unit, ensure that all of the manual valves
are in the appropriate open or closed positions.
From the main screen on the panelview, press F5 to select
the RO SYSTEM screen. The panelview will default to
the RO-1 SYSTEM screen. If the RO-2 SYSTEM screen is
desired, press F8. To start an RO unit, press F1 from the
appropriate screen. This will initiate a softener process
pump to start flushing a softener unit and will cause the
inlet and reject bypass valves on the RO unit to open.
The softener will flush for one minute and then will start
to put flushing water to the RO unit. The RO will be in
J1 (80)
flush for a short while and then the first pass RO process
pump will start. After 5 seconds of running, the second
pass RO process pump will start. At the time of the
actual start up, the product water will dump to drain.
When the second pass product water conductivity has
been less than 20 uS for 30 seconds, the product water
will be sent to the EDI unit.
b) Start a second RO unit.
In order to start a second RO unit, it is essential that the
program be set to run in DOUBLE MODE. If the
DOUBLE MODE operation has not been selected, the
second RO unit will not start.
From the main screen on the panelview, press F5 to select
the RO SYSTEM screen. The panelview will default to
the RO-1 SYSTEM screen. If the RO-2 SYSTEM screen is
desired, press F8. To start the second RO unit, press F1
from the appropriate screen. The second RO unit will go
through the same start up sequence as indicated above.
The second unit will not initiate a start until the first unit
is producing water to the EDI unit rather than diverting
it to drain.
c) Stop an RO unit from NORMAL MODE Operation.
Whenever an RO unit is to be stopped during NORMAL
MODE operation, the EDI must be shut off prior to
stopping the RO to prevent unnecessary pressure surges
on the stacks.
J1 (81)
From the main screen on the panelview, press F5 to select
the RO SYSTEM screen. The panelview will default to
the RO-1 SYSTEM screen. If the RO-2 SYSTEM screen is
desired, press F8. To stop an RO unit, press F2 from the
appropriate screen.
d) Stop an RO unit from DOUBLE MODE Operation.
If only one RO is to be stopped from DOUBLE MODE
operation, refer to the topic “Switch from DOUBLE
MODE to NORMAL MODE”. If the intent is to shut
down both RO units, first switch the EDI to the off
position to prevent any unnecessary pressure surges to
the EDI stacks. From the main screen on the panelview,
press F5 to select the RO SYSTEM screen. Press F2 to
turn RO-1 off. Then press F8 to select the RO-2 SYSTEM
screen. Press F2 to turn RO-2 off.
e) Adjust the recovery rates for an RO unit.
The recovery on an RO unit is the ratio of production
water flow vs. the raw water flow. The target recovery
rates are 70% for the first pass and 85% for the second
pass. For general operating conditions, a range of plus or
minus 1% is considered acceptable on each of the values.
These values apply to both RO units and are displayed on
their respective panelview screens. The appropriate
reject flows for various product flow rates are also posted
on the second pass reject flow meters on each RO unit.
J1 (82)
In order to adjust the recovery rate, adjust the reject
valve for the appropriate RO pass until the reject flow
rate coincides with the appropriate product flow rate or
until the RECOVERY indicator on the RO system screen
is at the desired value. In order to increase recovery, the
reject valve would be closed in and to decrease recovery
the reject valve would be opened. In most cases, a very
small rotation of the valve handle will give the desired
reject flow change.
H. EDI
a) Start the EDI.
Prior to starting the EDI, check that all of the manual
valves are in the correct positions. One or both of the RO
units must be running, depending on the mode of
operation that has been selected.
From the main screen, press the F6 button to bring up the
EDI SYSTEM screen. Ensure that there are no alarms up
on the blue line at the top of the screen. If an alarm is up,
press F7 and F6 to silence and reset the alarms
respectively. This must be done with the
MANUAL/OFF/REMOTE switch on the EDI control panel
in the OFF position. Once the alarms are reset, the unit
may be switched to the REMOTE position.
Upon turning the switch to REMOTE, the inlet valve
should start to open. Once it has opened, both pumps
should start and the unit is on line. If no changes have
J1 (83)
been made to the RO operation or to the transfer valves,
the unit will required little or no balancing. If balancing
is required, refer to the paragraph below labeled “To
balance the EDI”.
b) Stop the EDI.
To stop the EDI unit, turn the MANUAL/OFF/REMOTE
switch to the OFF position. If the unit was at full rated
flow, it is likely that the relief valve on the pump skid will
function. This is normal.
c) To balance the EDI.
The purpose of the pump skid on the EDI is for hydraulic
balancing. It is very important for the ensured quality of
the product water that the product pressure is higher
than the brine pressure on both the inlet and outlet of the
stacks. The stacks are essentially made up of plastic
sheets compressed by six tie bolts. Any leakage which
occurs in the stacks will be of no consequence to the
product quality as long as the pressure differential is kept
between 60 and 100 inches as measured on the
differential pressure gage for both the stack in and stack
out headers.
If the pressure differential needs adjustment, turn the
selector valve for the differential pressure gage to the
STACK OUT position. Go to the product pump discharge
valve and open or close the valve in small increments,
checking the differential gage after each increment.
Continue to adjust as necessary until the desired
J1 (84)
differential is achieved. Closing the product pump
discharge valve will have the effect of increasing the
STACK OUT differential pressure. Turn the selector
valve to the STACK IN position. If the differential needs
adjustment, open or close the brine pump valve until the
desired differential is achieved. Opening the brine pump
valve will reduce the STACK IN differential. When the
plant is in NORMAL MODE adjustments to the pressure
differential can also be achieved by opening or closing the
product water transfer/recirculation valve. Opening this
valve will increase the water flow through the EDI unit
when the plant is operating in NORMAL MODE.
d) Add salt to the EDI brine makeup system.
Brine is used to replenish the dissolved minerals which
are blown down from the brine system. Without an
adequate brine concentration, current flow in the stacks
would be reduced and the ion transfer of the system
would be diminished. To make brine, add one bag of
Windsor 802 salt and 33 gallons of EDI product water.
Switch on the mixer, which is located on the top of the
brine tank, and allow it to run for about 30 minutes. This
will result in a saturated brine solution which will be fed
into the EDI as it is needed. Do not use any water
except EDI product water, as contaminants such as
Calcium and Magnesium will damage the EDI
stacks. Only use food grade salt such as Windsor
802.
J1 (85)
I. Transfer System
a) Initiate transfer to a low level tank.
Prior to starting the transfer system, check that all
manual valves are in the correct position and that the
pumps have adequate lubrication. The proper oil for the
pump is Teresso 46. From the main screen on the
panelview, press the F7 button to bring up the LLRFW
TRANSFER screen. Press the F1 or F2 buttons to move
the cursor to the low level tank that you intend to transfer
to. Press the F3 button when the appropriate tank is
indicated to enter the selection, then press the F7 and F6
buttons to initiate the transfer. The appropriate valve
will indicate open by turning from green to red. If the
system is already transferring and you wish to change the
destination, select the desired tank and press F3 to enter
the choice. Press F5 to abort the existing transfer and
then press F7 and F6 to initiate the new transfer. During
NORMAL MODE operation it is important to do the F5,
F7 and F6 sequence quickly as this will allow the transfer
change to be made without any large pressure swings on
the EDI unit.
b) Stop a transfer to a low level tank.
From the main screen on the panelview, press the F7 button to
bring up the LLRFW TRANSFER screen. Press the F5 button
to abort the transfer.
J1 (86)
5. PLANT OPERATING CONTROLS
A. Plant Operating Controls
The entire plant is controlled by the main PLC through the
MMI. Implemented security requires that the operator types in
a password to get access to control screens and make changes to
the system. The operator can only observe basic operating
parameters without the correct password.
a) Plant Control from the PanelView 1400E MMI
The Plant is controlled and monitored via two Allen-
Bradley PanelView 1400E screens – one in the plant, the
other in the water treatment plant control room. The
Process Summary Screen(s) on the MMI can be viewed
at any time (no password required). A screensaver will
blank the screen after ten minutes of inactivity. The
screen is reactivated by a single touch. Reactivation
cannot, however, select a device or operating mode.
In order to access the operator control screens, the
operator must enter a four digit password then press
enter on the Password Screen. This password is factory
set to be “9348”. This password is hard coded in the PLC;
it is not possible to modify it from the MMI. Once the
password is entered correctly, the operator has access to
the control screens for a period of 4 hours. If the operator
enters the wrong password, there is no limit to the
number of times another password can be attempted. If
an incorrect password is entered (or if the user presses
LOCK on the Main Screen), the operator can still move
J1 (87)
to (but only to) the Process Summary Screen(s) and back
to the Password Screen. Screen activity does not change
the password access time.
Note: Each of the two MMI screens requires a separate
log on (same password). Entering the password on one
MMI screen does not give access to the other.
After expiration of password access, the MMI will only
show the Process Summary Screen. The operator cannot
reset an alarm (the horn can however be silenced) if the
password has expired. The operator must re-enter the
password in order to use the MMI.
The MMI screens consist of at least the following:
i) A Main Screen - Shows mapping to other screens
available from the MMI.
ii) Process Summary Screen(s) - a tabular overview of
the entire plant showing status of each unit, plant
feed low, combined permeate flow, operating
pressures, etc.
iii) Process Unit Control Screens
iv) Setting Screens - allows the user to change some of
the alarms or alert set points. The user can step
through the screens by pressing the prompt in the
lower left corner.
v) ZeeWeed® Backpulse Data screen shows key
parameters at different phase of the
Production/Backpulse cycle.
J1 (88)
vi) An Alarm History screen shows the time of
alarms/alerts and when they were acknowledged.
A copy of each screen for this plant is included in Appendix 1.
b) Programmable Logic Controller
The PLC5/20 Programmable Logic Controller (PLC)
provides automated control of the plant. All the
programming for the control of the plant is stored in the
PLC. On initial plant startup or in the event that the
PLC memory is corrupted, the PLC will download the
program from the E2PROM (Electronically Erasable
Programmable Read Only Memory) module and sound an
alarm. All adjusted setpoints will be reset to their factory
default values. The operator should record all the
setpoints if they have been adjusted to ensure that those
setpoints can be easily adjusted to overwrite the default
setpoints if they have been reset. The plant will power up
with all process units in OFF mode. The operator must
select RUN on the MMI to activate each unit.
The PLC has a battery that needs to be replaced every
two to three years. The battery allows the PLC to retain
the program and any new setpoints in the event of an
extended power failure without having to download the
program from the E2PROM. If the battery needs
replacement, a message will be shown on the MMI (alert).
The length of time the plant can operate with a low
battery level will vary from plant to plant. The PLC has a
battery backup capacitor that will allow the user to
J1 (89)
remove and replace the battery with the power down
without loss of PLC memory (refer to the vendor data for
more information).
c) Control Panel Disconnect
A Control Panel Disconnect Switch on the face of the
Control Panel disconnects 120 V power to the Control
Panel and allows access to the interior of the Control
Panel. Disconnecting the power to the control panel also
disconnects the power to the CPU and therefore de-
energizes all CPU controlled devices on the entire plant.
d) Plant Shutdown
i) Plant Shutdown Push-button
The plant has shutdown software button on the
MMI. The shutdown button initiates an orderly
shutdown of the entire plant. The operator must
confirm the shutdown request. Upon
acknowledging and resetting this alarm, the plant
will be re-activated. The operator will have to
individually restart all process units.
ii) Local Emergency Stop Push-button
The Emergency Stop mushroom button, located on
the face of the control panel, will immediately de-
energize all PLC outputs and bring the devices on
the unit to the status shown in the Sequence Chart.
The last mode and sub-mode of operation will be
shown until the operator resets the alarm. The
devices will not, however, shut down in an orderly
J1 (90)
fashion. Upon resetting this mushroom button,
acknowledging the alarm and resetting the alarm,
all process units will be activated in OFF mode.
The devices will retain their settings. The
Emergency Stop should only be used in case of
emergency. The operator should remedy the
problem and reset the mushroom button (by pulling
on it) and PLC alarm.
iii) Individual Component Operation
Most controlled devices (pumps and valves) have a
manual override capability. Regardless of the
process unit mode, the capability exists to
manually override any pump running condition.
This is achieved by an Auto/Stop/Start selector
switch on the MCC panel for each pump. The
pump status for a pump is indicated as Auto On,
Auto Off, Failed, Local On, or Local Off. All
ALARMS/INTERLOCKS for each pump will
remain active even if a pump is locally started, but
can only annunciate an alarm.
Each air-operated valve can be manually opened by
using a manual override on the actuator. Since
there is no feedback from the valve (no limit
switches) the manual override can not be indicated
on the MMI screen. Valve status is always
indicated as Open or Closed based on automatic
operation (PLC output controlling the valve).
J1 (91)
The colour scheme for Panel View 1400E is defined
as per the table below:
i) Valve Closed Green
ii) Valve Open Red
iii) Pump Failed Green / Blinking
iv) Pump Auto Off Green/“A” displayed beside
the pump symbol
v) Pump Auto On Red/“A” displayed beside the
pump symbol
vi) Pump Local Off Green
vii) Pump Local On Red
The MMI panels do not provide manual override capabilities other than
described below.
i) All chemical addition pumps (P-22A, P-22B, P-23A, P-23B, P-
24A, P-24B, P-25A, P-25B, P-26A, and P-26B) have an Auto /
Manual / Off / Test selector switch. An Auto position indicates
that the pump is fully operational and can be used by the control
logic. The pump output is defined by the control logic. In
Manual mode the pump rate is defined by the operator (the
pump continues to start and stop as per control logic). These
devices may have a Proportional Integral Derivative (PID)
screen to allow the operator to control the device responsiveness
in Auto mode. Bumpless transfer between Manual and Auto
mode is always implemented. The Off position indicates that
the pump is not available. The Test mode is similar to Manual
mode with the exception that the pump is running regardless of
J1 (92)
any interlocks. After 20 minutes the pump mode is switched
from Test to Off mode.
ii) Other devices that accept a 4 to 20 mA analog signal such as
variable speed pumps or modulating valves have an Auto /
Manual selector switch. In Manual mode the operator can
control the pump speed or valve position manually. These
devices may have a Proportional Integral Derivative (PID)
screen to allow the operator to control the device responsiveness
in Auto mode. Bumpless transfer between Manual and Auto
mode is always implemented.
6. DESIGN OF AUTOMATIC PLANT CONTROL
Expected values for various process indicators are shown in Table 3-1
to provide the operator with rough guidelines as to how the equipment
should behave under normal operating conditions. The automatic
control of the plant is then described in the subsection after the
indicators are listed.
A. Plant Indicators
Table 3-1 shows typical production quality and flows (± 20%) for
the operating conditions with plant in Production. These
values will change with membrane life, water quality,
temperature, etc. Where parallel equipment (e.g. the two
ZeeWeed® units or two RO units) exists, and suffixes are not
shown (for the purpose of clarity), the operator should use the
same values for all those parameters with the same tag
numbers. If separate values are not shown for Production,
J1 (93)
Flush, and Backpulse then that parameter is not expected to
change by cycling between the three sub-modes.
J1 (94)
Indicator TAG Anticipated Value
Production Backpulse Flush
Transmembrane Pressure DPI-34231,2,3 -9 to -4 psid 2 to 8 psid N/A
Process Pump Flow
(instantaneous)
FIT-35201,2,3 100 to 500
gpm4
100 to 500 gpm 400 gpm
Pump/Membrane Header Pressure PI-35231,3 -12 to 0 psig 2 to 12 psig 8 - 20 psig
Process Pump Discharge Pressure PI-35403 A/B 0 to 5 psig 5 to 10 psig 8 - 20 psig
Membrane Blower Outlet Pressure PI-8540 ←------------------
-
3 to 5 psig 0 psig
Supplemental Blower Outlet
Pressure
psi. 6--------- ←------------------
-
5 to 7 psig 3 to 7 psig
Spare Blower Outlet Pressure PI-8740S ←------------------
-
3 to 7 psig -----------------
---→
Reactor Level LI-34261 ←------------------
-
164 to 206” 164 to 206”t
Vacuum PI-3641 ←------------------
---
10 to 25” Hg -----------------
---→
Production Regeneration
Softener Feed Flow FIT-1320 130 gpm 130 gpm
(Backwash,
Rinse)
Regeneration Feed Flow FIT-2943 N/a 60 gpm (Brining)
40 gpm (S. Rinse)
Dilution Feed Flow FIT-2942 N/a 40 gpm
Production
RO Feed pH AIT-2520 9.0
RO Feed Conductivity AIT-4131 950 µS
First Pass RO Membrane Inlet
Pressure
PT-4023 170psi
First Pass RO Reject Flow FT-4020 42 gpm
First Pass RO Permeate Flow FT-4021 100 gpm
First Pass RO Permeate Pressure PT-4024 50 psi
First Pass RO Permeate
Conductivity
AIT-4031 20 µS
Second Pass RO Membrane Inlet
Pressure
PT-4223 180psi
Second Pass RO Reject Flow FT-4220 15 gpm
Second Pass RO Permeate Flow FT-4221 84 gpm
Second Pass RO Permeate
Pressure
PT-4224 10 psi
Second Pass RO Permeate
Conductivity
AIT-4231 0.5 µS
Table 7-1 Normal Operating Expenses
J1 (95)
1. Parameter shown on the MMI.
2. These values are ± 20% and will change with temperature, feed water
quality, and membrane life.
3. For some instruments there are actually two of these indicators with
suffixes -1 and -2 on the two ZeeWeed® / RO Units. Only one is
shown (without suffix) in this table for purposes of clarity.
4. All flows in this table are USgpm.
a) NORMAL / DOUBLE Capacity Selector Switch
The water treatment system is designed to deliver 80 USgpm of
boiler feed water. This is considered the NORMAL mode of
operation. Occasionally (typically once a month) for a period of
up to 12 hours the system can be required to produce 160
USgpm of treated water. This is considered the DOUBLE
capacity mode of operation. The MMI screen has to provide the
above selector switch. This is a global switch that applies to
almost all process units.
i) NORMAL Mode of Operation
Assuming that all process units are in RUN mode
and not in Shutdown, during NORMAL mode of
operation only one ZeeWeed® Unit and one RO Unit
are in Production (the other ZeeWeed® Unit and
RO Unit are in Standby). Where there are
duplicate units (ZeeWeed® Unit 1 and 2 and RO
unit 1 and 2) the first unit placed in RUN mode
becomes the lead unit and goes into Production (if
required). If the second unit is placed in RUN
J1 (96)
mode it becomes the lag unit and goes into
Standby.
ii) DOUBLE Capacity Mode of Operation
Assuming that all process units are in RUN mode
and not in Shutdown, during DOUBLE Capacity
mode of operation both ZeeWeed® Units and both
RO Units go into Production. Softeners are
prevented from going into Regeneration. When the
capacity of the current softener is exhausted, the
softener will switch to the other unit but the
Regeneration of the exhausted unit is not triggered.
It is the operators responsibility to ensure that the
DOUBLE Capacity mode of operation is selected
when sufficient softener capacity exists (it is
recommended that the operator regenerate the
current softener, by switching to a fully
regenerated one, just before selecting the
DOUBLE Capacity mode).
Note: The operator is prevented from switching to
DOUBLE Capacity mode when Softener unit is in
Regeneration.
B. Raw Water Feed System
a) Raw Water Feed Pumps
The pair of feed pumps P-101 and P-102 provide
pressurized feed for the ZeeWeed® Microfiltration System.
A single pump can handle two ZeeWeed® units in
J1 (97)
DOUBLE Capacity mode or a single ZeeWeed® unit in
NORMAL mode. Only one pump is running at a time.
The first pump placed in Auto mode becomes the lead
pump and will start regardless of whether ZeeWeed® unit
is in Standby or not. The integrated 3-way Yarway
control valve FCV-165 is installed at the common pump
outlet to provide bypass flow back to the sump in case the
ZeeWeed® units do not accept feed water. The second
pump placed in Auto mode becomes the lag pump and is
not running. If both pumps are in Auto mode and not
Failed, at a time of day specified by KY-1010 the lag
pump should start and become the lead pump. After a 3
second delay the lag pump should stop. This alternating
operation will ensure that both pumps are used when
available. If the lag pump is not available (Failed or
OFF), the lead pump continues to run indefinitely.
b) Feed Temperature Control
The temperature control system is not connected to the
PLC and is not controlled by ZENON.
The additional temperature transmitter TT-7621 is used
for membrane protection. See Control Logic Summary
Chart for details (Appendix 2).
J1 (98)
c) Feed Flow Control
i) Normal Operating mode
Since the feed pumps operate at a constant speed, a
feed control system is required to control the level
in ZeeWeed® Membrane Tanks. The feed control
system consists of a flowmeter FIT-7620 and a flow
control valve FCV-7620. The primary purpose of
the feed flow control is to maintain ZeeWeed®
Membrane tank level at a setpoint defined by the
operator. This is achieved by two cascaded PID
loops. The fast acting Flow control loop and a slow
Level control loop that generates flow control
setpoint. The second loop is also used during
Backpulse to control the reject volume through
ZeeWeed® Membrane tank overflow. The following
diagram shows the ZeeWeed® Membrane Tank
level during a typical Production cycle.
ii) DOUBLE Capacity Operating mode
In DOUBLE Capacity mode both ZeeWeed® units
are running at the same time. The two ZeeWeed®
units are not synchronized as far as the Backpulse
/ Production cycle is concerned. The feed control
applies always to the ZeeWeed® Membrane Tank
with the lower level. The feed control is similar to
control in NORMAL mode during Production -
cascaded PID loop control. Flow control setpoint
FIC1-7620 adjusted by Level control loop to
maintain LIC-3426 level setpoint in a Membrane
J1 (99)
Tank with a lower level (adjustable by the
operator). The Backpulse cycles are ignored
(Backpulse will result in Membrane Tank level
increase - as a result the level control PID loop may
switch to the other Membrane Tank level). The
Membrane Tank with the higher tank level has no
impact on flow control. We are concerned only with
the Membrane Tank with the lower level.
Notes:
1. The level control PID loop is based on setpoint
and level measurement for the ZeeWeed® unit in
operation that has the lower Membrane Tank
level (switched from one tank to another as
required).
2. When ZeeWeed® units are in Standby (FV-7690
closed) both PID loops are disabled (“frozen”
outputs).
3. High temperature alarm TAH-7621 will cause
the flow control valve FCV-7620 to close.
d) Totalized Feed Flow
The feed flow FIT-7620 should be totalized over a 24 hour
period and during Backpulse and Production cycle.
The MMI provides access to:
FQI1-7620 Totalized feed flow since midnight.
FQI2-7620 Totalized feed flow over 24 hour period
(yesterday).
J1 (100)
FQI3-7620 Totalized feed flow during the last
Backpulse cycle.
FQI4-7620 Totalized feed flow during the last
Production cycle.
Note: Totalized Backpulse and Production flows are
applicable only during NORMAL operating mode.
Clear the indicators for DOUBLE Capacity mode.
C. Chemical Pretreatment
a) Hypochlorite Addition
Sodium Hypochlorite addition is based on the ZeeWeed®
feed flow FIT-7620. The Sodium Hypochlorite pump
dosing rate is calculated as follows:
SC-2400A/B [%] = (FT-7620) / (FYH1-7620) * 100
Where FYH1-7620 (field adjustable) is the feed flow at
which P-24A/B operates at its full capacity (100%).
The addition of Sodium Hypochlorite is achieved by using
one of the two metering pumps P-24A or P-24B. Only one
pump is running at a time. The flowmeter FT-7620 must
indicate flow above FYL-7620 for metering pump to be
enabled. The first pump placed in Auto or Manual mode
becomes the lead pump (the second pump becomes the lag
pump- if not in Off mode). Whenever the flow FIT-7620
drops below FYL-7620 and both pumps are available (not
in Off), pumps will toggle (the lead pump becomes the lag
one and vice versa).
J1 (101)
The Test mode is used for maintenance only (e.g. priming
the pump). In this mode the pump will be running with
all interlocks disabled with the ability to manually control
the pump rate. Note: After 20 minutes in Test mode, the
PLC will automatically switch the pump to Off mode.
In DOUBLE Capacity mode (both RO units and both
ZeeWeed® units running at the same time) only one
metering pump is running.
b) Ferric Chloride Addition
Ferric Chloride addition is based on the ZeeWeed® feed
flow FIT-7620. The Ferric Chloride pump dosing rate is
calculated as follows:
SC-2600A/B [%] = (FT-7620) / (FYH2-7620) * 100
Where FYH2-7620 (field adjustable) is the feed flow at
which P-26A/B operates at its full capacity (100%).
The addition of Ferric Chloride is achieved by using one of
the two metering pumps P-26A or P-26B. Only one pump
is running at a time. The flowmeter FT-7620 must
indicate flow above FYL-7620 for metering pump to be
enabled. The first pump placed in Auto or Manual mode
becomes the lead pump (the second pump becomes the lag
pump- if not in Off mode). Whenever the flow FIT-7620
drops below FYL-7620 and both pumps are available (not
in Off), pumps will toggle (the lead pump becomes the lag
one and vice versa).
J1 (102)
The Test mode is used for maintenance only (e.g. priming
the pump). In this mode the pump will be running with
all interlocks disabled with the ability to manually control
the pump rate. Note: After 20 min in Test mode, the PLC
will automatically switch the pump to Off mode.
In DOUBLE Capacity mode (both RO units and both
ZeeWeed® units running at the same time) only one
metering pump is running.
D. ZeeWeed® Microfiltration System
a) ZeeWeed® Unit Mode Selection - RUN/OFF/WASH
Each unit has a separate mode selector switch. With the
ZeeWeed® Unit Mode ‘Selector Switch’ the operator
(through the MMI with maintenance level password
access) can put each ZeeWeed® unit into one of four
general operating modes: RUN, OFF or WASH. The
ZeeWeed® unit modes are described below:
RUN OFF WASH
Unit responds to control logic.
Unit is shutdown. Unit responds to control logic.
b) ZeeWeed® Unit “RUN” Mode
RUN mode is the mode of operation that each ZeeWeed®
unit will be in for normal operation. The operation of
J1 (103)
each unit can best be described as automatic; that is,
during normal operation, no operator attention is
required unless an alarm/alert is activated. Each
ZeeWeed® unit is either in Production, Backpulse,
AutoWash, Flush or Standby at any given time. The
Production Cycle time, Backpulse duration as well as
Flush and AutoWash parameters can be adjusted by the
operator via the MMI. In AUTO, the PLC will start and
stop units based on the Membrane Tank levels.
c) ZeeWeed® Unit “OFF” Mode
The operator can shut off each ZeeWeed® unit by selecting
OFF from the MMI. As a unit is shut OFF, devices will
shut off in an orderly fashion. See the Operations
Sequence Chart (Appendix 2) for the device status and
sequence for the OFF procedure and status (some devices
may be On and valves may actually be Open).
d) ZeeWeed® “WASH” Mode
A Wash procedure is required when the membranes
become fouled and are not capable of producing the design
permeate flow. When an operator decides (criteria
discussed in the Wash section of the manual) that a
particular unit needs to be washed, the operator can
perform a Clean in Place (CIP) procedure. They must
first put the unit into WASH. The WASH selector switch
can only be activated if the unit is in OFF mode. After
putting the unit into WASH, the unit will be in Standby.
Manually overridden devices (except for equipment that
has interlocks) will, however, still be active.
J1 (104)
The Wash Procedure or Clean in Place (CIP) is described
in detail in Section D i). The Control Logic Summary
Chart shows the setpoints for this mode (refer to
Appendix 2).
Note: The operator is prevented from placing a ZeeWeed®
unit in WASH mode when the system is in DOUBLE
Capacity mode.
e) Vacuum Pumps (P-36A and P-36B)
One or two vacuum pumps can be operated at a time. The
first pump placed in Auto mode becomes the lead pump
and starts automatically. The other pump (when in
Auto) becomes the standby pump. If the operator presses
Stop for the pump that is running (or the pump fails), the
standby pump will become the lead pump and will come
on automatically. Start at the MCC must be used for the
second (standby) pump to operate two pumps at the same
time.
f) Alternating ZeeWeed® Units
During NORMAL operation only one ZeeWeed® unit can
be in Production. The first ZeeWeed® unit placed in
RUN mode becomes the lead unit and goes into
Production (if required). The second unit placed in
RUN mode becomes the lag unit and goes into Standby
regardless of the demand. If both ZeeWeed® units are in
RUN mode and not in Shutdown, every time the lead
ZeeWeed® unit goes into Standby due to lack of demand
(TK-88 above LYH3-8820) or no water to process (TK-34
J1 (105)
below LYLL-3426) it becomes the lag unit. This will
ensure that both ZeeWeed® units are used and no
stagnant water is kept within ZeeWeed® unit for extended
period of time.
Occasionally, when balanced demand exists, the lead
ZeeWeed® unit may never go into Standby. To ensure
that under normal conditions ZeeWeed® units are
alternated at least once per day, the time in Production
for the lead ZeeWeed® unit is measured. If at a time of
day defined by KY-3500 the runtime is greater than 12
hours, the lead unit should go into Standby and the lag
ZeeWeed® unit should become the lead unit and begin
Production.
Whenever the lead ZeeWeed® unit goes into Shutdown
due to an alarm condition, the lag unit will become the
lead unit and will go into Production.
In DOUBLE Capacity mode described earlier (both
ZeeWeed® units and both RO units operate at the same
time) the startup of the lag ZeeWeed® unit should be
delayed by 10 seconds (staggered startup).
g) Overall ZeeWeed® Production and Control
The PLC controls the flow from the ZeeWeed® units
according to the liquid level in the Backpulse Break Tank.
All the setpoints and thresholds are defined in the Control
Logic Summary Chart (Appendix 2).
J1 (106)
The process pump P-35 will draw up to 150 USgpm from
the membranes in Production. The process pump is
equipped with a variable speed drive controlled by the
PLC. The control of pump speed throughout the
Production cycle will depend on the various conditions
defined below.
The PLC controls the flow from the ZeeWeed® units to
maintain the operator adjustable flow setpoint (in
Manual flow control) or calculated flow setpoint (in Auto
flow control) based on Backpulse Break Tank level.
A timer shows how much time is left in a Production, or
Backpulse cycle. The operator can adjust the
Production cycle time (also referred to as Backpulse
frequency) and the Backpulse duration time from the
MMI.
The Production and Backpulse step gain parameters
can be adjusted, but will probably not need to be adjusted
after the equipment is commissioned.
i) ZeeWeed® Production Flow Control
The ZeeWeed® Production flow control is based on
the Backpulse Break Tank TK-88 level transmitter
(LT-8820) indication.
J1 (107)
When the Backpulse Break Tank level is between
LYH1-8820 and LYH2-8820 the flow setpoint is
calculated as follows:
3520)(FYL3520)](FYL3520)[(FYH*8820)(LYH18820)(LYH2
8820)(LYH18820)(LIT3520FIC −+−−−
−−−−−−=−
When the Backpulse Break Tank level is at or
below LYH1-8820 the flow setpoint FIC-3520
remains at FYH-3520.
When the Backpulse Break Tank level is at or
above LYH2-8820 the flow setpoint FIC-3520
remains at FYL-3520.
The above-presented scenario applies when the
Flow Control Switch is in Auto position. When in
Manual, the operator can set the desired flow
setpoint FIC-3520 from the MMI to anywhere from
FYL-3520 to FYH-3520.
ii) Transmembrane Pressure (TMP) Control
The Transmembrane Pressure referred as TMP (in
psid) shown as DPI-3423 is calculated by the
equation below. During Production this number
is negative, during Backpulse this number is
positive.
TMP = (PIT-3523)+A x C – [(LIT-3426) – B] x C
where:
PIT-3523 is the pressure measured in psig
J1 (108)
LIT-3426 is the reactor liquid level in inches
A is the elevation of the pressure transmitter PI-
3523 above the top of the membranes measured in
inches (7” at time of printing).
B is the height of the top of membranes in the
Membrane Tank measured in inches (85” at time of
printing).
C is a conversion factor (inches to psig) equal to
0.03612.
TMP is an absolute term and the reader should be
aware that in Production, increased TMP means
a larger pressure differential (see Control Logic
Summary Chart, Appendix 2), because the pressure
inside the membranes is lower than outside the
membranes.
ZeeWeed® Tank
Water Elevation
ZeeWeed®
Cassette
FlowPI-3523
LI-3426
A
B
Figure 7-6 Transmembrane Pressure Control Schematic
J1 (109)
During the Production cycle the PLC will try to
achieve the desired flow setpoint (either calculated
or set by the operator as described earlier) by
increasing the Process Pump speed. Increasing the
pump speed will result in decrease of the TMP
value (the higher the pump's speed the more
negative the TMP value). To protect the integrity
of the membranes, there is a limit beyond which
the TMP is not allowed to drop (DPCLL-3423). See
the Control Logic Summary Chart, Appendix 2, for
details. The TMP control limit has priority over
flow control. Even when the flow setpoint has not
been achieved, once the TMP reached the limiting
value, the pump speed will not be increased.
During the Backpulse cycle the PLC will try to
achieve the desired TMP pressure DPCHH-3423.
iii) Process Pump (P-35) Speed Control
The Process Pump speed is controlled in a ramp-up
mode. Initially the Process Pump is started at the
minimum pump speed as defined by SY-3500.
During the Production cycle the Production Step
Gain (SF1-3500) is used, while the Backpulse
cycle is using the Backpulse Step Gain (SF2-3500).
The pump speed is increased at 0.1 second
intervals (SK-3500).
J1 (110)
There are two distinctive phases of pump speed
control. The first phase is the fast approach when
the pump speed increase is defined by the Step
Gain parameter. Once the controlled parameter
(flow in Production) or limiting parameter (TMP
in Production) are close to their respective
setpoint, the final trimming begins, where the rate
of pump speed increase is limited to 10% of the fast
approach. Please note that the trimming phase
begins when either of the two parameters is above
its approach setting. Figure 7-7 below illustrates
typical scenarios:
Flow SetpointFIC-3520
Flow ApproachFICH-3520
Time
TMP ApproachDPCL-3423
TMP limitDPCLL-3423
FIT-3520
DPI-3423
Clean membrane scenario: Flowsetpoint achieved
Fouled membrane scenario: TMPlimit reached
Figure 7-7 Process Pump (P-35) Speed Control
To improve the response time when ZeeWeed® unit
is restarted in Production after Backpulse, the
pump speed in Production is recorded and at the
J1 (111)
beginning of the new Production cycle, the pump
is restarted at 90% of the previous Production
cycle pump speed. This speed is held for 5 seconds,
then control is released to the above control
algorithm.
Please refer to the Control Logic Summary Chart,
Appendix 2, for details.
iv) Putting a ZeeWeed® Unit to Standby
Several triggers (see the Control Logic Summary
Chart for these triggers) may cause a unit to go to
Standby (rather than shutting it down). These
include a low level of the Membrane Tank (LYLL-
3426) or high level of the Backpulse Break Tank. If
the Standby trigger no longer exists, the unit will
go back into Production when level (LYL-3426) is
triggered.
v) Starting a Unit in Production after Standby
If a Production cycle was interrupted by a
Standby condition, the ZeeWeed® unit will
eventually be put back into Production based on
the level trigger points or utility requirements
defined in the Control Logic Summary Chart
(Appendix 2). Every time the ZeeWeed® unit is
taken out of Standby, the ZeeWeed® unit starts
the Production cycle by performing Backpulse
first.
J1 (112)
vi) Permeate Discharge
All permeate will be discharged to the
Backpulse/Break Tank TK-81. Occasionally, when
the other ZeeWeed® unit is in Wash mode, the
permeate will be diverted to the CIP Tank TK-88.
See Operations Sequence Chart (Appendix 2) for
details.
h) ZeeWeed® Backpulse Control
i) Backpulse
The Backpulse frequency (Production cycle
time), duration, and pressure for each ZeeWeed®
Unit can be set (see Control Logic Summary Chart,
Appendix 2, for Factory Default Setpoints) by the
operator through the MMI. These settings should
be, but are not restricted to, the same for each unit.
The operator can initiate a backpulse from the
MMI for either ZeeWeed® Unit. Initiating a
backpulse will also initialize the backpulse timer.
The subsequent Production / Backpulse cycles
will now start from the end of the operator initiated
backpulse.
Note: Every time the ZeeWeed® unit is taken out of
Standby, it performs a Backpulse before going
into Production.
ii) Backpulse Pressure Control
J1 (113)
During a backpulse sequence, the pump speed will
be ramped up, in an expedited mode and then
trimmed to maintain the backpulse pressure. The
PLC will increase the pump speed in a step-wise
fashion. The rate of acceleration of the pump is
coded into the PLC.
When the backpulse pressure reaches the
backpulse pressure approach setpoint (DPCH-
3423), the PLC will trim (reduce the step size to
10%) the stepwise approach to achieve the
backpulse pressure setpoint (DPCHH-3423). The
PLC will adjust and control pump speed during the
remainder of the backpulse sequence to maintain
the backpulse pressure setpoint by increasing or
decreasing the pump speed by one step (trimmed)
every time interval.
If the backpulse pressure setpoint is not
approached, the pump speed will continue to be
ramped up to 100% and held there for the
remainder of the backpulse. This ensures that the
backpulse pressure and flow rates are maximized
for the duration of the backpulse.
iii) Backpulse Analysis
The operator may want to determine the
effectiveness of the backpulse procedure. To
J1 (114)
simplify this analysis, the MMI will show the
following information for each ZeeWeed® unit:
Point in Cycle Process Pump Flow
(FIT-3520)
gpm
TMP
(DPI-3423)
psi Before the last backpulse 127 -7.7
During the last backpulse 360 8.1
After the last backpulse 130 -6.9
After the previous
backpulse
130 -6.9
Table 7-2 Backpulse Analysis Chart
This information will allow the operator and
ZENON to determine if the backpulse was actually
effective in reducing the TMP to maintain a certain
flux and if the TMP is measurably changing from
one cycle to the next. To improve backpulse
effectiveness, the operator can increase frequency
and duration of the backpulse (this will however
reduce the Production time and cause the
membranes to work harder for a shorter period of
time). For “After Backpulse” conditions, the table
shows the flow and pressure 30 seconds after a
backpulse to allow the process parameters to
stabilize.
J1 (115)
i) Membrane Wash Procedure
A Wash procedure is required when the membranes
become fouled and are not capable of producing the
designed permeate flow, high pressure differential or
reduction in percent rejection. The clear indication of
fouled membranes is when during Production cycle the
flow setpoint cannot be achieved (the process pump speed
is limited by TMP limit). The membranes can be cleaned
in place by using the CIP Tank TK-81. If the operator
wants to carry out a Clean in Place procedure, they would
first put the unit into WASH. The WASH selector switch
can only be activated if the unit is in OFF mode. After
putting the unit into WASH, the unit will be in Wash
Standby. The operator must press the CIP Fill button
to divert the permeate from the ZeeWeed® unit in
Production to the CIP tank. Once the level switch LSH-
8105 is triggered the Fill routine is completed. The
operator must press the Initiate Backwash button to
start the process pump and perform the Backwash.
Note: The CIP Fill button applies to the ZeeWeed® unit
in Production not the ZeeWeed® unit being in Wash.
i) Backwash Pressure Control
Identical to Backpulse Pressure Control (same
settings and control).
J1 (116)
E. Dual Softener System
a) Bisulphite Addition
Sodium bisulphite addition is based on the softener feed
flow at the point of injection. A virtual flowmeter is
created:
FT-1321 = (FT-1320A) + (FT-1320B) + (FIT-2943)
The bisulphite pump dosing rate is calculated as follows:
SC-2300A/B [%] = (FT-1321) / (FYH-1321) * 100
Where FYH-1321 (field adjustable) is the feed flow at
which P-23A/B operates at its full capacity (100%).
The addition of bisulphite is achieved by using one of the
two metering pumps P-23A or P-23B. Only one pump is
running at a time. The virtual flowmeter FT-1321 must
indicate flow above FYL-1321 for metering pump to be
enabled. The first pump placed in Auto or Manual mode
becomes the lead pump (the second pump becomes the lag
pump- if not in Off mode). Whenever the flow FIT-1321
drops below FYL-1321 and both pumps are available (not
in Off), pumps will toggle (the lead pump becomes the lag
one and vice versa).
The Test mode is used for maintenance only (e.g. priming
the pump). In this mode the pump will be running with
all interlocks disabled with the ability to manually control
the pump rate. Note: After 20 minutes in Test mode, the
PLC will automatically switch the pump to Off mode.
J1 (117)
In DOUBLE Capacity mode (both RO units and both
ZeeWeed® units running at the same time) only one
metering pump is running.
b) Softener Unit Mode Selection - RUN/OFF
Each unit has a separate mode selector switch. With the
Softener Unit Mode Selector Switch the operator (through
the MMI with maintenance level password access) can put
each softener unit into one of two modes: RUN, or OFF.
The softener unit modes are described below:
RUN OFF
Unit responds tointerlocks and controllogic.
Unit is shutdown (alldevices deactivated).
i) Softener Unit “RUN” Mode
RUN mode is the mode of operation that each
softener unit will be in for normal operation. The
operation of each unit can best be described as
automatic; during normal operation, no operator
attention is required unless an alarm/alert is
activated. Each softener unit is either in
Production, Standby, Regeneration or
Shutdown at any given time. The MMI will
indicate different steps during each of the above
states and time to complete each step (if based on
timer). In RUN mode, when the softener unit is
J1 (118)
not in Regeneration, the PLC will start and stop
softener unit based on the RO feed requirement.
(See Control Logic Summary Chart, Appendix 2, for
details).
When a softener unit is in Standby for a prolonged
period of time, an equalization process occurs in the
softener bed. This requires a Service Flush before
the unit can produce quality water. If the softener
unit is in Standby for a short period of time (less
than KY7-1300 - user adjustable) the Service Rinse
will be skipped (see Operations Sequence Chart,
Appendix 2, for details).
Only one softener unit can be On-line at a time.
When both softeners are placed in RUN mode, the
first unit that has been activated will become the
lead unit and come On-line (if the RO feed is
required). The second unit will be the lag unit and
will go into Standby regardless of RO feed
requirement.
When the softener unit is in On-line, the PLC will
totalize the softener feed flow (FQI-1320A/B). The
capacity of each softener unit is approximately
185,000 gallons (user adjustable). Once the
capacity of the unit has been reached, an alert will
be issued to prompt the operator to select the other
unit by pressing ON-LINE button on the MMI
screen. The unit that is in Production (lead unit)
J1 (119)
will continue Production until the unit in
Standby (lag unit) completes its Service Rinse and
goes into Production. At that time the lead unit
becomes the lag unit and goes into Standby. Since
the capacity of the unit placed in Standby has
been exhausted, the operator should initiate
Regeneration of this unit.
Note: If the system operates in DOUBLE Capacity
mode (Peak Flow) the REGENERATION button
on the MMI screen is inactive (the softener can be
regenerated in NORMAL mode only). When the
regeneration process has been initiated in
NORMAL mode, the mode selector switch cannot
be placed in DOUBLE Capacity mode.
The regeneration procedure is fully automated (see
Operations Sequence Chart, Appendix 2, for
details). Each step of the regeneration procedure is
timer based (user adjustable). The step description
and time to complete is displayed on the MMI
screen. During the regeneration procedure the
operator may use a toggle pushbutton HOLD /
RELEASE on the MMI screen to prolong any step
of the regeneration procedure indefinitely. They
may also use a momentary button ADVANCE to
terminate/skip a step during the regeneration
procedure. These two control buttons should be
used with extreme caution as improper use of any
of them may produce undesirable results.
J1 (120)
ii) Softener Unit “OFF” Mode
The operator can shut off each softener unit by
selecting OFF mode from the MMI. As a unit is
shut OFF, devices will shut off in an orderly
fashion. See the Operations Sequence Chart,
Appendix 2, for the device status and sequence for
the OFF procedure and status.
c) Alternating Softener Feed Pumps
The pair of softener feed pumps P-13A and P-13B provide
pressurized feed for the softener and RO units. A single
pump can handle two RO units in DOUBLE Capacity
mode or a single RO unit and regeneration of the second
softener unit in NORMAL mode. Only one pump is
running at a time. The first pump placed in Auto mode
becomes the lead pump and will start whenever an RO
unit requires feed (or softener in Regeneration requires
feed). The second pump placed in Auto mode becomes the
lag pump and does not run. If both pumps are in Auto
mode and not Failed, at a time of day specified by KY-
1300 the lag pump should start and become the lead
pump. After a 3 second delay the lag pump should stop.
This alternating operation will ensure that both pumps
are used when available.
F. Reverse Osmosis (RO) Pretreatment
a) RO Feed Conductivity
J1 (121)
The RO feed conductivity analyzer AIT-4131 is used for
monitoring the quality of the RO Feed. No control is
associated with the Feed conductivity. See Control Logic
Summary Chart (Appendix 2) for details.
b) RO Feed pH Control
The addition of caustic hydroxide in NORMAL mode
(single RO running) is achieved by using one of the two
metering pumps P-25A or P-25B. PID control of P-25
pumps is implemented using AIT-2520 as the process
variable. The setpoint is defined from the MMI screen
(see Control Logic Summary Chart, Appendix 2, for
details). In the event of the pH probe or transmitter
failure the caustic dose rate can be set manually (pump in
Manual mode). Only one pump is running at a time. An
RO unit must be running for the metering pump to be
enabled. The first pump placed in Auto or Manual mode
becomes the lead pump (the second pump becomes the lag
pump if not in Off mode). Whenever an RO unit stops
and both pumps are available (not in Off), pumps will
toggle (the lead pump becomes the lag pump and vice
versa).
The Test mode is used for maintenance only (e.g. priming
the pump). In this mode the pump will be running with
all interlocks disabled with the ability to manually control
the pump rate. Note: After 20 minutes in Test mode, the
PLC will automatically switch the pump to Off mode.
J1 (122)
In DOUBLE Capacity mode (both RO units running at
the same time) only one metering pump is running.
G. Reverse Osmosis (RO) System
a) RO Unit Mode Selection - RUN/OFF/WASH
Each unit has a separate mode selector switch. With the
RO Unit Mode Selector Switch the operator (through the
MMI with maintenance level password access) can put
each RO unit into one of three general operating modes:
RUN, OFF, or WASH. The RO unit modes are described
below:
RUN OFF WASH
Unit responds to interlocks and control logic.
Unit is shutdown (all devices deactivated).
Very limited control.Most devices deactivated.
i) RO Unit “RUN” Mode
RUN mode is the mode of operation that each RO
unit will be in for normal operation. The operation
of each unit can best be described as automatic;
during normal operation, no operator attention is
required unless an alarm/alert is activated. Each
RO unit is either in Production, Standby or
Shutdown at any given time. In RUN mode, the
PLC will start and stop RO units based on the tank
levels in TK-88 and TK-71 (see Control Logic
Summary Chart, Appendix 2, for details).
J1 (123)
ii) RO Unit “OFF” Mode
The operator can shut off each RO unit by selecting
OFF mode from the MMI. As a unit is shut OFF,
devices will shut off in an orderly fashion. See the
Operations Sequence Chart (Appendix 2) for the
device status and sequence for the OFF procedure
and status.
Note: The operator cannot switch directly between
RUN and WASH mode. Each mode can be selected
when RO is in OFF mode.
iii) RO Unit “WASH” Mode
A Wash procedure is required when the membranes
become fouled and are not capable of producing the
designed permeate flow. When an operator decides
(criteria discussed in the Wash section of the
manual) that the RO unit needs to be washed, they
will place it in WASH mode. Wash mode has a
limited impact on the RO unit control (Permeate
Pressure Bleed valves activated to close).
Note: The WASH mode cannot be selected when
the system is in DOUBLE Capacity mode.
b) Alternating RO Units
As described earlier, during NORMAL operation only one
RO unit can be in Production. The first RO unit placed
in RUN mode becomes the lead unit and goes into
Production (if required). The second unit placed in
RUN mode becomes the lag unit and goes into Standby
J1 (124)
regardless of the demand. If both RO units are in RUN
mode and not in Shutdown, every time the lead RO unit
goes into Standby due to lack of demand (TK-71 above
LYH2-7126) or no water to process (TK-88 below LYL-
8820) it becomes the lag unit. This will ensure that both
RO units are used and no stagnant water is kept within
RO Unit for extended period of time.
Occasionally, when balanced demand exists, the lead RO
unit may never go into Standby. To ensure that under
normal conditions RO units are alternated at least once
per day, the time in Production for the lead RO unit is
measured. If at a time of day defined by KY-4100 the
runtime is greater than 12 hours, the lead units should go
into Standby and the lag RO unit should become the lead
Unit and begin Production.
Note: The lead RO unit should always be in Standby
before the lag unit goes into Production to prevent
Shutdown alarms due to low feed pressure if a Softener
unit is being rinsed as part of the Regeneration.
Whenever the lead RO unit goes into Shutdown due to
an alarm condition, the lag unit will become the lead unit
and will go into Production.
In DOUBLE Capacity mode described earlier (both RO
units operate at the same time) the startup of the lag RO
unit should be delayed by 10 sec (staggered startup).
J1 (125)
c) Alternating RO Process Pumps
Each RO unit has a pair of process pumps for the First
Pass (P-41A and P-41B) and the Second Pass (P-43A and
P-43B). During normal operation (both pumps in Auto)
only one pump is running from each pair. The first pump
from each pair placed in Auto mode becomes the lead
pump and will start whenever RO unit goes into
Production and a process pump is required (see
Operations Sequence Chart, Appendix 2). The second
pump from each pair placed in RUN mode becomes the
lag pump and is not running. If both pumps within a pair
are in Auto mode and not Failed, the RO unit goes into
Standby (or stops for any other reason) (lead becomes lag
and vice versa). This will ensure both pumps are used
when available.
When one of the RO units is not available (OFF, WASH,
or Shutdown) the other RO Unit will be permanently
designated as the lead unit. This may result in a
continuous operation of an RO unit for more than 24
hours. If at a time of day defined by KY-4100 the other
RO unit is not in Standby and both pumps within a pair
are in Auto mode and not Failed, the pair of pumps will
toggle while RO unit is running in Production. The lag
pump should come on, for 3 seconds both pumps should be
running together, then the lead pump should stop (as it
becomes the lag pump).
There should be a 10-second delay between alternating
pumps P-41A/B and P-43A/B.
J1 (126)
Whenever the lead pump fails due to an overload alarm,
the lag pump will become the lead pump and will restart
immediately.
d) RO Clean in Place (CIP) Control
When the RO membranes become fouled the permeate
flow will decline. The operator can modify settings for the
HCV-4181 and HCV-4082 (First Pass) or HCV-4381 and
HCV-4282 (second Pass) to compensate for some fouling
by increasing the membrane inlet pressure. At some
point the fouling of the membranes cannot be
compensated as the membrane inlet pressure reaches its
limit. To restore the membrane permeability a chemical
wash is required.
The Wash mode for an RO unit affects only two
components within this unit. Both Permeate Pressure
Bleed Valves are activated to close as long as the low
cross-membrane alarms are not active.
The operator must adjust the position of manual valves to
configure the required recirculation loop.
Tank TK-83 is used to prepare the cleaning solution (or
preservative). The built in electric heater H-83 maintains
proper temperature of the cleaning solution when the TK-
83 level is above LSL-8301 and the heater local selector
switch is in Auto.
The transition of the pump P-83 local selector switch from
Off to Auto starts the pump (if tank level above LSL-
J1 (127)
8301 and TSH-8303 not triggered) and runs it for a
duration defined by KY-8300 before stopping. To restart
the pump the operator must turn it Off then back to Auto
using the local switch or press the RECIRCULATION
button on the MMI screen (active only when local switch
is in Auto).
The details regarding preserving membranes and
washing the membranes are part of Zenon’s Operations
and Maintenance Manual.
H. Electrodeionization (EDI) System
The EDI System provided by Ionics is a stand alone unit. The
supplier provides the PLC code which is integrated into the
main PLC provided by ZENON. The supplier also provides MMI
screens for a standard user interface which are incorporated into
PanelView 1400e provided by ZENON.
a) CIP EDI
The EDI uses the RO CIP system for cleaning. The wash
pump is enabled from the EDI CIP screen on the MMI.
The pump P-83 local selector switch from Off to Auto
starts the pump (if tank level above LSL-8301 and TSH-
8303 not triggered) and runs it for time defined by KY-
8300 before stopping. To restart the pump the operator
must turn it Off then back to Auto using the local switch
or press the RECIRCULATION button on the MMI
screen (active only when local switch is in Auto).
J1 (128)
I. Dual Mixed Bed Ion Exchange Polishing Unit
The mixed bed ion exchange system is a stand alone passive unit
with no controls associated with the unit.
J. Break Tank with Outlet Feed Pumps
a) Break Tank TK-71
The Distribution Break Tank TK-71 serves as a reservoir
of high purity water.
During NORMAL operation the contents of the tank will
be recirculated through the EDI system at a rate of 80
gpm. The recirculation rate is adjusted manually by
using HCV-7183. Regardless of whether the RO unit is in
Production or Standby, as long as the tank level is
above LYL-7126, one of the outlet feed pumps P-71A/B is
running and the recirculation valve FV-7184 is open. If
the tank level drops below LYL-7126, the outlet feed
pump stops and 5-seconds later the recirculation valve
FV-7184 will close. The Distribution Tank Level must
rise above LYH-7126 to enable the outlet feed pumps and
the recirculation valve (the valve opens first, and after a 5
second delay the outlet feed pump starts).
In DOUBLE Capacity mode (peak flow) the recirculation
valve FV-7184 remains closed. The outlet feed pump is
controlled by levels LYL-7126 and LYH-7126 (disabled
J1 (129)
when level drops below LYL-7126, and enabled when level
rises above LYH-7126).
b) Outlet Feed Pumps P-71A/B
The pair of outlet pumps P-71A and P-71B provide
pressurized feed for boiler feed tanks and recirculate the
contents of the Distribution Break Tank through the EDI
system. Only one pump is running at a time. The first
pump placed in Auto mode becomes the lead pump and
will start whenever outlet feed pump is enabled. The
second pump placed in Auto mode becomes the lag pump
and is not running. If both pumps are in Auto mode and
not Failed, at a time of day specified by KY-7100 the lag
pump should start and become the lead pump. After a 3
second delay the lag pump should stop. This alternating
operation will ensure that both pumps are used when
available.
K. Reserve Feedwater Tanks
The MMI or external Bailey PCV operator station can send one
of six commands in a form of a single PLC word (binary). The
command will set the appropriate bit high, while the PLC detect
the positive transition of the bit. It will accept the command, set
the bit low, then execute the command. The commands are as
follows:
1. Transfer to Tank #1 (bit 00)
2. Transfer to Tank #2 (bit 01)
J1 (130)
3. Transfer to Tank #3 (bit 02)
4. Transfer to Tank #4 (bit 03)
5. Transfer to all tanks (bit 04)
6. Abort transfer (bit 05)
Notes:
1. Transfer to all tanks implies the following order: Tank #4,
Tank #3, Tank #2, Tank #1.
2. During transfer to one tank all other transfer requests are
ignored. Only the last request is remembered (transfer
request bit remains on) and accepted when current transfer
is completed.
a) Single tank transfer procedure
1. Accept transfer (clear transfer request bit).
2. Open tank transfer valve.
3. Continue transferring until tank high level switch
activated. Please note that one of the distribution
pumps is running all the time.
4. Close tank transfer valve.
5. Transfer completed (another transfer command can be
accepted).
b) Transfer procedure for all tanks
1. Accept transfer (clear transfer request bit).
2. Open tank #4 transfer valve.
3. Continue transferring until tank #4 high level switch
activated.
4. Open tank #3 transfer valve.
J1 (131)
5. Close tank #4 transfer valve.
6. Continue transferring until tank #3 high level switch
activated.
7. Open tank #2 transfer valve.
8. Close tank #3 transfer valve.
9. Continue transferring until tank #2 high level switch
activated.
10. Open tank #1 transfer valve
11. Close tank #2 transfer valve.
12. Continue transferring until tank #1 high level switch
activated.
13. Close tank #1 transfer valve.
14. Transfer completed (another transfer command can be
accepted).
Pressure switch PSH-153 installed on the common tank
feed header protects outlet feed pumps P-71A and P-71B
from running dead-headed. Since the outlet pumps can
be dead-headed only in DOUBLE capacity mode (no EDI
recirculation), the shutdown alarm associated with PSH-
153 is active only in this mode.
L. Sump Pumps
A pair of pumps, P-103 and P-104, are used too. To prevent the
pumps from running dead-headed, a 3-way Yarway control valve
FCV-166 is installed at the common pump outlet to provide
bypass flow back to the sump. Pressure switch PSH-155
J1 (132)
protects the feed pumps in case of malfunction of FCV-166.
Sump level is measured by level transmitter LIT-156.
The pair of sump pumps, P-103 and P-104, empty the local
sump. Both pumps are controlled according to sump level LIT-
156. The first pump placed in Auto mode becomes the lead
pump and will start when the sump level is above LAH-156.
When the sump level drops below LALL-156, the second pump
placed in Auto mode becomes the lag pump. When the lead
pump is running but the sump level is nevertheless increasing,
the lag pump will start once the sump level reaches LAHH-156.
Whenever both pumps are running or both pumps are not
running (but in Auto and not Failed) the lag pump becomes the
lead one and vice versa. When both pumps are running and the
sump level drops below LAL-156 the lag pump stops. The lead
pump stops when the sump level drops below LALL-156.
The integrated 3-way Yarway control valve FCV-166 is installed
at the common sump pump outlet to provide bypass flow back to
the sump in case the drain line is blocked. In case of FCV-166
failure and drain line blockage, the pressure switch PSH-155
protects the sump pumps (stops both pumps when tripped).
J1 (133)
CHAPTER 8 – OPERATE UNDER UPSET CONDITIONS
1. INTRODUCTION
The entire plant is programmed to be completely automatic if all the
devices are in Auto. The MMI (Man Machine Interface) is provided for
monitoring and control of the entire plant.
Each ZeeWeed® unit and RO unit has a unit mode selector switch,
which enables the operator to RUN each unit, turns the unit OFF, or
put a unit in WASH mode. Each softener has a unit mode selector
switch, which enables the operator to RUN a unit or turn the unit
OFF.
A detailed summary of the major components in the plant and a
description of their functionality is first presented in this section.
Overall plant control and how the major components operate together
is then discussed at the end of this section. The user should also refer
to the Process and Instrumentation Diagrams (P&IDs), the Control
Logic Summary and the Operations Sequence Charts to understand all
the controls and interlocks. Appendix 2 includes the Control Logic
Summary and the Operations Sequence Charts.
The two ZeeWeed® units and two RO units are identical including
agging (except Unit 1 devices have a -1 suffix and Unit 2 devices have
a -2 suffix). For clarity, the suffixes are dropped altogether and when
referring to these units, the reader should be aware that there are in
fact multiple devices and that are suffixed -1 and –2. The two Softener
units are referred to as Unit A and Unit B. The logic and sequence
J1 (134)
charts show which devices are common to both units and which are
dedicated to each. Shared devices have no suffix.
A. Power Up/ Power Interruption
The PLC stores all the settings, and status of the devices and
plant from the last time the plant was powered up. After a
power interruption, the plant will restart automatically in an
orderly fashion. The PLC will wait 60 seconds after power up
before turning on devices (that are in Manual or Auto) or
monitoring signals to allow transmitters to warm up and
complete any self-diagnostics. The PLC will stagger start up of
the pumps as defined in the Startup Sequence Chart to avoid
putting excessive load on the power grid. A Start Up Sequence
Chart lists the order in which devices will power up after an
Emergency Stop or a power failure (refer to Appendix 2).
On initial power up or if the PLC memory is corrupted and the
PLC program is loaded from the E2PROM (Electronically
Erasable Programmable Read Only Memory) module, the plant
will power up with all devices in Auto. The PLC will sound an
alarm and all the units will power up OFF. The operator must
press RUN on the Man Machine Interface (MMI) to activate
each unit.
J1 (135)
CHAPTER 9 – TROUBLESHOOTING
1. GENERAL
A. Panelview not responding to commands.
A dialogue box will appear across the bottom of the screen
indicating “PLC currently controls screen change”.
B. Password timer expired.
This occurs every four hours. To enter the new password, press
F7 - a new screen will appear. Press the select button and type
in the digits 9348. Press the return button (down and left
arrow) and press the cancel button. The panelview will indicate
“PASSWORD IS VALID FOR 4 HRS” and should now
respond to your commands.
2. LAB TESTS
Note: Any time a lab test shows results that vary from what you
suspect is normal, the test should be repeated immediately. There are
a number of factors which can affect a given test result. The following
is a description of some of the problems which can affect a test.
A. The chlorine content after the softener is higher than
normal.
a) When performing the free chlorine test after the softener,
it is important that the glassware is not contaminated
with free chlorine from another source. Possible sources
of contamination are rinsing the glassware with tap
water, or performing the free chlorine test on a running
J1 (136)
ZeeWeed® output prior to the test after the softener.
Rinse the glassware with EDI product water and repeat
the test. Normal results should be at the bottom end of
the detection range, approximately 0.00 to 0.06 mg/l. If
the readings are higher than that, check the red eye on
the Sodium Metabisulphite pump and ensure there is
chemical for the pump in the lower tote.
b) Check the cholorine test powder pillows – some are for 25
ml samples and others are for 10 ml samples. While we
normally use the 10 ml sample units, the 25 ml samples
are acceptable if the appropriate sized samples are taken.
B. The chlorine content in the ZeeWeed® output is lower
than normal.
a) The most common cause of low chlorine content is to lose
the prime on the Sodium Hypochlorite pump. This
chemical has a fairly high vapor pressure so it tends to
develop bubbles in the pump suction. The volumetric rate
of flow in this pump is so low that the bubble will cause it
to lose prime. Re-priming is done by opening the priming
knob located on the back side of the pump head. The
primary knob should be turned just far enough to
allow the pump to expel the air. The primary knob
should be kept in this slightly open position to
allow future air bubbles to be expelled. The pump
has enough capacity to allow the bleach to slip
stream like this. The excess bleach is routed back
into the bottom tote. It is also possible to re-prime the
J1 (137)
pump by turning the relief valve release knob located on
the left-hand side of the pump discharge. This method,
however, is not recommended as it allows bubbles to be
re-introduced in the pump suction.
C. The softener is showing higher amount of hardness than
normal.
a) A possible cause is the softener may have been recently
regenerated and its efficiency may not be at its maximum.
The efficiency can be increased by flushing the softener
for a longer time during the regeneration. However, for
every gallon of water flushed, a gallon of production is
lost. As long as the hardness is less than 2 mg/l after
regeneration, this is not a problem. If it is greater than 2
mg/l, re-do the test after the softener has put through
approximately 1000 gallons of water during the
production run. If the hardness is greater than 4 mg/l, re-
do the regeneration. Check the instrument air pressure -
if it is too low, the brine inlet valve will not open.
(a) The glassware may have been rinsed with tap water. If
this is true, the hardness in the tap water will
contaminate the sample and the reading will show high.
Rinse the glassware with EDI product water and re-do
the test.
J1 (138)
3. FEEDWATER
A. The feed water inlet temperature is too low.
a) Check the set point on the pick valve controller; it has a
tendency to migrate downward over time.
b) Check if the steam control valve is opened fully. If it is
and the flow is not extremely high (i.e. 270 gpm), the
heater internals need to be acid cleaned. Notify the lab as
soon as it is convenient.
4. ZEEWEED®
A. The ZeeWeed® has shut down and the alarm annunciator
is sounding.
a) One of the ZeeWeed® tanks has lost its water level to the
point of shutdown. This can be caused by running the
ZeeWeed® units in NORMAL MODE with the ZeeWeed®
tank balance valve closed.
b) One of the ZeeWeed® tanks has lost its water level to the
point of shutdown. This can be caused by insufficient raw
water flow. Check that the inlet flow is at least equal to
the permeate flow. If the inlet flow is less than the outlet
flow, check to make certain that the raw water pumps are
each capable of making the required amount of water.
Both pumps may have to be run. If this is the case,
backwash the pumps to clean the screens. If this does not
work, put in a notification to have the pump inlet screens
cleaned.
J1 (139)
c) The feed water temperature is greater than or equal to
40°C; it is possible for the temperature to spike high
enough to cause a high temperature trip. Close the
manual steam supply valve to the pick heater and fox
open one of the ZeeWeed® solenoid valves to allow water
to enter the tank. Proceed to the raw water pumps and
put one of them on hand control for 20 seconds. The
pump should start on hand and force the slug of high
temperature water into the ZeeWeed® tank. It will mix
with the water already present in the tank and will not
endanger the membranes. Place the raw water pump
back into automatic control and restart the ZeeWeed®
units. When flow has been established to the ZeeWeed®,
reopen the manual steam supply valve.
B. ZeeWeed® is shut down, the above procedures have been
completed, and it still will not start.
a) Clear any alarms that may be displayed. This can be
done by pressing F17 to acknowledge the alarm and F18
to reset the alarm.
b) In the case of normal mode operation when running both
ZeeWeed® units is desired, giving a command to “RUN”
the second ZeeWeed® will bring the unit from “OFF” to
“STANDBY”. It is then necessary to give the “RUN”
command again to bring the unit from “STANDBY” to
“BACKPULSE”.
J1 (140)
c) The ZeeWeed® unit is probably fouled. The first thing
that should be checked is the inlet flow to the ZeeWeed®.
If it has not been equal to the production flow for a while,
the solids content in the tank will increase dramatically.
Simply increasing the inlet flow to maximum (around 300
gpm) for a few hours may be all that is needed. If this is
not the case, notify the Zenon representative so that a
clean may be done as soon as possible.
5. SOFTENER
A. The softener has been given a command to “RUN” but
will not go past “STANDBY”.
a) In order for the softener to go into full production, there
must be a RO unit calling for water. In order for the RO
to demand water, the RO must be in “STANDBY” and the
finished product tank must be at less than 90%. In the
softener startup cycle, the pump starts and flows water
up to, but not through, the softener for approximately one
minute before the RO inlet valves open.
b) The breaker has tripped for the softener process pump.
c) The softener process pump switch is in the off position.
B. The softener makes a loud noise.
a) The noise is coming from the relief valve. Limit stops are
installed on the service inlet valves and inlet bypass
valves to the softener vessels, and may be in need of
adjustment. If the noise occurs immediately after the
J1 (141)
pump starts, adjust the inlet bypass valve to limit the
inlet pressure to the softener, during the initial flushing
stage, to just under 100 psi. If the noise occurs when only
one RO unit is running, adjust the service inlet valve so
that the inlet pressure to the softener is just under 100
psi. These steps should not be required frequently.
b) The softener pump switch is selected to hand with no flow
through the softener or the bypass piping. Shut the pump
off or establish flow.
C. There is no brine flow during a softener regeneration.
a) The instrument air pressure is low. The instrument air
pressure is required because the brine inlet valve is
spring return. If the air pressure is below 60 psi the brine
inlet valve may not open.
D. The Backpulse break tank goes empty during a softener
regeneration.
a) During a softener regeneration, the plant must be
running in normal mode and second ZeeWeed® must be
running to supply water for the regeneration flows.
Otherwise, the tank will draw down and the softener
pump will trip. Remember to open the ZeeWeed® raw
water control valve bypass slightly until the backpulse
break tank reaches 89%. Otherwise ZW#1 will probably
trip on low tank level.
J1 (142)
E. The softener has a high pressure drop across it.
a) About 5 months after the commissioning of the water
treatment plant, a high pressure drops across the softener
vessels was noted. It was eventually discovered that
bacteria had begun to grow inside the softener vessel.
The bacteria caused a slime buildup covering the internal
vessel surfaces and probably also coated a significant
portion of the resin beads. The problem was attacked
through several methods, but the one that proved
successful was to drain the softener vessel, refill it with
brine from the brine tank by starting a regeneration and
advancing through to the brine cycle. Once the vessel was
full of brine, the top cover was removed and 20 liters of
12% bleach were added. The resin and chemical mixture
were air-lanced for one hour. This procedure was followed
by a normal regeneration. An improvement in the
softener pressure drop was immediately noticed. One side
effect of this procedure was that a lot of loose slime was
released and the micron filters were subject to rapid
plugging for the next several days. It should be noted
that at no time should the micron filter pressure
differential be allowed to exceed 10 psi.
J1 (143)
6. REVERSE OSMOSIS
A. One RO unit is running and the other one will not start
up.
a) The plant is running in single mode. Start the switching
process by shutting the EDI unit off. Switch to double
mode by selecting F15 from the main screen and select F2
to switch to double mode. Once the second RO unit has
been started and the offspec product to drain valve has
closed, the EDI can be restarted and balanced out.
b) The pump hand/off/auto switches are in the off position.
c) A softener regeneration is in progress. While a softener
regeneration may be started in DOUBLE MODE, it is not
possible to go into DOUBLE MODE while a softener
regeneration is in progress.
B. When starting the second RO, both of the ROs trip off.
a) The RO inlet pressure to the first stage may have gone
below 20 psi. This will trip the RO units to protect the
process pumps. The inlet valves on both ROs may have to
be closed somewhat. After closing them, readjust the
pressures to provide the desired second pass permeate
flow rates.
b) The inlet pressures on the RO second pass process pumps
may have dropped below 20 psi. In this case, re-initiate
the start and adjust the RO second pass inlet valve
J1 (144)
towards the closed position just enough to get the second
pass inlet pressure to above 20 psi.
C. When adjusting an RO inlet valve, the RO tripped off.
a) The first pass back pressure limits were exceeded. The
back pressure on the first pass of the RO must run
between 20 and 80 psi. It is possible to exceed these
limits when adjusting either the first or second pass inlet
valves. Check the alarm on the panel view or go from the
MAIN SCREEN to F10 DIAGNOSTIC SCREEN and
determine which alarm appeared. Reset the alarm and
readjust the valve that you were working with, usually in
the opposite direction that you were going, and attempt to
restart the RO. Remember that if the alarms are not
reset, the RO unit will not restart.
D. RO unit starts up but trips when the EDI unit is started.
second pass inlet pressure high alarm comes up.
a) This problem can occur when the temperature has been
dramatically reduced, say if the steam supply has been
removed from the pick heater. The reason for this is the
second pass of the RO may not be able to process the
water from the first pass quickly enough. This is
especially true if the first pass has been recently cleaned
and the second pass has not. Also, the EDI presents more
back pressure under cold conditions and this will
aggravate the water consumption of the second pass of
the RO. To correct the problem, reduce the inlet pressure
J1 (145)
to the first pass of the RO. If the inlet valve is getting
very close to fully closed, increase the amount of reject
flow to allow better control from the first pass inlet valve.
E. Not possible to run both RO units at the same time
without running both softener process pumps
simultaneously.
a) Check the micron filters for a high pressure differential.
The pressure differential across the micron filters should
not be in excess of 10 psi. If the differential is high,
switch to the spare micron filter and notify the Zenon
representative during the next day shift so the old filter
elements can be replaced.
b) Check the softener differential pressure. In single mode
operation, it is normal for the differential to be around 7
to 10 psi. In double mode, normal differential is around
20 to 30 psi. If the differentials are higher than this,
notify the Zenon representative as soon as possible so that
corrective action may be taken.
c) Check if there is a softener regenerating. If a softener is
regenerating during a high flow double mode operation,
one pump will not be able to maintain flow. Reduce the
flow through the RO units or run in single mode as you
will quickly run out of water in the backpulse break tank.
J1 (146)
7. ELECTRODEIONIZATION (EDI)
A. The EDI unit will not start.
a) If the plant is set to operate in single mode, check that
one of the RO units is running and the product water is
available as supply to the EDI unit. Upon RO start up,
valve FV4264 will be closed and FV4261 will be open to
divert RO product water away from the EDI until the
product quality from the RO is stabilized. It takes a few
seconds for the quality to stabilize and the EDI will hold
out until then.
b) If the plant is set to run in double mode, check to see if
both RO units are running and that the product quality is
stabilized. Sometimes one RO unit can trip and not be
readily noticeable.
c) Ensure there are no alarms on the EDI screen. An alarm
on the top band of the EDI screen (F6) on the panelview
will prevent the EDI from starting. Acknowledge and
reset the alarm. The “Manual, Off, Remote” switch on the
unit control must be set to the “Off” position to reset the
alarm.
d) If EDI inlet valve MOV1-4, will not actuate, or is
actuating erratically, check the contacts on the back of the
“Manual, Off, Remote” switch. The contacts may be loose.
If that fails, verify the contacts on the output card relay
are not stuck. The Zenon representative must be
contacted in the event of an output card problem. If that
J1 (147)
does not work, the relays inside the EDI junction box may
have fused relays. Replace the faulty relay with a spare.
B. The EDI unit crashes, and Motor Operated Valves 1-4 and
2-4 are both in the open position.
a) If this problem occurs, open the back of the PLC cabinet
and look to the right directly inside the door enclosure.
The problem is a blown fuse and it should be indicated
with a glowing red light adjacent to the fuse location. The
fuse is number FU16. Correct the cause of the blown fuse
and replace it with a 3 amp slow blow fuse.
C. The EDI unit runs but the display for the stack amps is
only showing stars.
a) There are two breakers which supply control power to the
EDI unit. This condition will occur when either of the
breakers are tripped. The first breaker is number 18A
and is located in the 110 volt panel situated in the MCC
panel. The second breaker is located in the upper left side
of the rectifier cabinet. Reset the breakers if they are
tripped.
D. The EDI unit starts, but trips off after a short time with
an alarm showing “MOV 2-4 Failure to Open”.
a) The failure to open is probably caused by the failure of the
relay which controls the operation of MOV 2-4. In the
event of this happening, go to the EDI screen and press
the F5 button to access the EDI set points. Reset the EDI
J1 (148)
Resistivity Setpoint to 18. This setpoint is virtually
impossible to achieve, therefore the MOV 2-4 will not try
to open to allow product to Tank 71. Once this is done,
remove the actuator for MOV 2-4 from the valve body and
actuate the valve with a wrench. Leave the valve in this
position unless the conductivity of the EDI is suspect.
Contact the Zenon representative immediately to notify
them of the situation.
E. The temperature of the inlet water is low, combined RO
output is too low to allow the EDI to run at its minimum
flow rate of 105 gpm in Double Mode, and the plant needs
all the water it can get.
a) It is possible under these conditions to “fool” the PLC into
believing that it is in “NORMAL MODE” and still allow
for both RO units to operate. To do this, first shut off the
EDI. Switch from “NORMAL MODE” to “DOUBLE
MODE”. At this time, the second RO unit may be
started. When the second RO is running stable, switch
back to “NORMAL MODE”. Both RO units will continue
to operate. The EDI unit may now be started with the
recirculation capability associated with “NORMAL
MODE” operation. Remember that the second pass RO
inlet pressure must be fairly low because starting the EDI
at low temperature will cause a considerable back
pressure increase. It is a good idea to open the product
flow valve on the EDI slightly and to close the
recirculation valve to the EDI slightly to compensate for
J1 (149)
the increased flow that the EDI will have to endure. Once
the EDI is running it may be re-balanced. Also, the
transfer to low level tankage in this circumstance should
be done by manually opening valves to the individual low
levels so that a high reading in a low level tank will not
terminate the transfer. Always remember to open one
valve before closing the next one so that the pressure does
not increase on the EDI and cause a trip. Ensure that a
good balance exists between the product tank inlet and
output so that the transfer pump will not trip on product
tank low level. When operating in this method, any trip
will cause the system to “realize” that it is in “NORMAL
MODE” and only one of the RO units will restart,
therefore, it is essential that nuisance tripping be
minimized.
8. TRANSFER SYSTEM
A. The transfer pumps will not function with the selector
switch in the “AUTO” position. They will work in the
“HAND” position.
a) The transfer system could be being held out by a BOILER
FEED HIGH PRESSURE (PAH-135) fault. This fault is
external to the Zenon system and is only shown on the
F10 screen under EXTRA FAULTS. This alarm can come
up while switching from NORMAL to DOUBLE mode if
the transfer of water to the low level tanks is interrupted
during the switch. For example, if transfer has been sent
to #1 low level tank and the tank has shut down the
J1 (150)
transfer due to high level, the transfer pump will still be
running as long as the plant is in NORMAL MODE.
When the switch is made to DOUBLE MODE, either to
run that way, or to switch RO units, the transfer pump
will briefly dead head and the high pressure alarm will
come up. The pumps will not run in auto until the alarm
has been acknowledged and reset, even if the pressure is
no longer high. The pressure switch is located adjacent to
the PLC cabinet on the product water line going to the
low level tanks.
J1 (151)
CHAPTER 10 – CHECKLISTS AND/OR READINGS
1. BEGINNING OF SHIFT CHECKLIST
As Of January 21, 2000
A. Check the temperature on the ZeeWeed® pump outlets. This
gives a longer term trend on the performance of the Pick heater.
Adjust the Pick heater setpoint as required. If the temperature
is too low, it will strongly affect the RO outputs. It seems that
the setpoint on the Pick heater controller will migrate
downwards over a period of a few hours.
B. Check the lubricant levels in the ZeeWeed® blowers (B85).
C. Check the lubricant levels in the ZeeWeed® process pumps
(P36).
D. Test the hardness of the output of softener in service. If it is
greater than 4 mg/l, or if the softener has reached total flow,
engage the other softener. Test the fresh softener after it has
flowed for a minimum of 1000 gallons to assure that the water
being tested is a representative sample.
E. Check the lubricant level in the softener process pumps (P13).
F. Check to ensure water is flowing through both micron filter
vessels. To do this, simply close the discharge valve on one of
the filters while observing the discharge gage. There should be
a noticeable dip in the pressure indication. Re-open the valve
and repeat the procedure on the other micron filter discharge
valve. The same pressure gage dip should be noticed.
J1 (152)
G. Check the indicators (red eye) on the chemical injection pumps.
If the indicator flashes when the pump strokes, the pump is
primed and sending chemical. If the indicator does not flash,
the pump is air bound and the priming port should be opened
until liquid comes out of the tube located on the right side of the
pump head. In the case of the sodium hypochlorite pump, the
priming port has been tied back into the bottom tote. If the
pump becomes air bound, open the priming port just enough to
re-establish flow (red eye indication) and leave the port open by
that amount. This will allow a continual release for trapped air
bubbles without significantly reducing the bleach flow to the
raw water.
H. Check the volume of the chemical in the bottom tote. If the
volume is getting low, open the valve between the top and
bottom totes to refill the bottom tote. If the top tote is empty,
notify the shift supervisor so more chemical can be ordered.
I. Check the operation of the RO units. Ensure that the pumps are
running fine and the reject flows are suitable for the production
flows. Flow rate charts are attached to each RO second pass
reject flow meter. Run in single mode whenever the plant
reserves are suitably high. Run in double mode when they are
not. The output of each RO should be approximately 84 USgpm
when the water temperature is 25ºC. Lower operating
temperatures will reduce the maximum RO output.
J1 (153)
J. Check the operation of the EDI unit. Balance the flows as
necessary. The recommended differential pressures are 60 to
100 inches on both stack in and stack out. The brine makeup
flow should be 7.5 to 8 gpm. The flow rate for the electrode
makeup should be 5.5 gpm. The brine blowdown should equal
the brine makeup minus the electrode makeup. The EDI stack
current should be limited to 4 amps, and the current peaks
should not exceed 6 amps. It is normal for Stack 1 to have the
highest current. The stack amperage is controlled by the stack
voltage.
2. OPERATOR LOGSHEETS
Logsheets are to be filled out during each shift. The logsheets cover
the ZeeWeed®, Softener, Reverse Osmosis and EDI units and are
described as follows.
A. ZeeWeed® - Note: If the backpulse break tank is at 87%
or higher, do not attempt to do the ZeeWeed® readings
because the set point will ramp down to 70 gallons per
minute as the break tank level climbs. This will cause
the readings on the log sheet to be meaningless.
a) Enter the current date.
b) Enter the time that the test was taken.
c) Raw water temperature refers to the inlet water to the
ZeeWeed® unit. It is available from the panelview screen,
however, it is best taken on the thermometers located on
the discharge lines located above the ZeeWeed® process
J1 (154)
pumps because the panelview reading is not buffered
against short term temperature fluctuations.
d) Process mode will always be “MF”. This stands for micro
filtration.
e) Vacuum pump pressure is read on the pressure gage
directly above the vacuum pumps. The gage can fluctuate
quite a bit, depending on whether the pump is currently
drawing air out of the system or not. The purpose of this
reading is to verify that the vacuum pump is working.
f) BP frequency is the duration in minutes between
backpulses. The number is displayed, in seconds,
immediately to the right of the “PRODUCTION MODE”
indicator when it is on. This variable is not likely to be
changed often.
g) BP duration is the length of time that the backpulse will
occur. This is indicated immediately to the right of the
“BACKPULSE MODE” indicator when it is on.
h) Raw feed pH is found on the water feed system screen.
The sensor is not currently operational.
i) Raw water flow. The raw water flow reading is found
near the upper left hand corner of the screen. During low
demand periods, this flow rate has a tendency to fluctuate
greatly. Pick an average reading.
j) Permeate flow rate. The permeate flow rate should match
the set point flow rate to within plus or minus 3 gallons
per minute. If the actual flow rate matches the set point
flow, simply record the set point flow. If the permeate
J1 (155)
flow does not closely match the set point flow rate, notify
the Zenon representative at the earliest possible chance.
Deviation in this flow could indicate the need for
membrane cleaning. If the backpulse break tank is at
87% or higher, do not attempt to do the ZeeWeed®
readings because the set point will ramp down to 70
gallons per minute as the break tank level climbs. This
will cause the readings on the log sheet to be meaningless.
k) BP flow rate. The backpulse flow rate is also controlled
by flow set point, however, it is set at 1.5 times the
permeate set point. In other words, if the permeate flow
rate is 134 gallons per minute, the backpulse should be at
1.5 x 134 or 212 gallons per minute. As with the
permeate flow, the value indicated here should be 212
gallons per minute unless there is a significant variance
from that value. If this occurs, record the measured flow
rate and notify the Zenon representative as soon as
possible. Deviation in this flow could indicate the need for
membrane cleaning.
l) TMP before BP. This is a measure of the amount of effort
required to draw water through the ZeeWeed®
membranes just prior to a backpulse. This value should
be negative. A large value for this variable can indicate
fouling of the ZeeWeed® membranes. This reading
should be taken approximately 10 seconds before the
beginning of a backpulse.
J1 (156)
m) TMP during BP. This is a measure of the amount of effort
required to push the water backwards through the
membranes at 1.5 times the normal production flow rate.
This reading should be taken as soon as the backpulse
flow rate reaches 1.5 times the normal flow rate. In the
case of a set point of 134 gallons per minute, backpulse
should be at 212 gallons per minute.
n) TMP after BP. This is a measure of the amount of effort
required to dray water through the ZeeWeed®
membranes just after a backpulse. It gives an indication
of the effectiveness of the backpulse for cleaning the
membranes. This reading should be taken as soon as the
flow rate reaches the production flow rate setpoint.
o) Blower discharge pressure. This is a misprint and should
read Blower discharge volume, measured in cfm. The
design flow for this is 20 cfm and is measured at the
rotometers located on each side of the ZeeWeed® box. In
order to achieve the initial 20 cfm, the air inlet valves to
the rotometers are opened wide and the air inlets to the
membrane cassettes are throttled back until 20cfm is just
exceeded on each side. The rotometer inlets are then
adjusted to control air flow to 20 cfm. If a significant
reduction of air flow is noted during the readings, it may
be assumed that inlet filters for the ZeeWeed® blowers
are plugging and need to be replaced.
J1 (157)
B. Softener Logsheets. Note: The softener logsheets are
currently set up for both softeners. We have set the
binder up for softener 1 and 2 to be kept in separate
locations in the log sheet binder.
a) PI1340A. This is the inlet pressure to number 1 softener.
b) PI1341A. This is the pressure on the number 1 softener
outlet. When considered against the inlet pressure, we
can determine if there is a high pressure loss across the
softener resin bed.
c) FI1320A. This is the flow indicator for #1 softener vessel.
The reading is available locally at the flow meter or it can
be found on the panelview on the F4 screen.
d) PI2940A. This gage is for the softener brine pump
discharge. It should only be read and recorded during the
brine injection portion of a regeneration.
e) PI2941A. This gage is also for softener regenerations. It
measures the pressure of the brine dilution water. It is
only meaningful during the brine injection portion of the
regeneration.
f) PI 1340B. This is the inlet pressure to number 2 softener.
g) PI1341B. This is the pressure on the number 2 softener
outlet. When considered against the inlet pressure, we
can determine if there is a high pressure loss across the
softener resin bed.
J1 (158)
h) FI1320B. This is the flow indicator for #2 softener vessel.
The reading is available locally at the flow meter or it can
be found on the panelview on the F4 screen.
i) PI8040. This is the pressure on the inlet to the micron
filters.
j) PI8041. This is the pressure on the outlet side of the
micron filters. When compared to the reading of -PI8040,
a good indication of the degree of plugging that exists in
the micron filter may be found.
k) AE2520. This is a pH indicator. The pH reading taken at
this point has an effect on the normalized flow
calculations for the RO membranes. This meter is not
functioning properly at the time of this writing. The lab
personnel are currently taking this reading.
l) AE4131. This is a conductivity meter. Like the pH
meter, this reading is important for the calculation of
normalized flow in the RO units. It is also not currently
in service and the lab is collecting and recording this data.
J1 (159)