modul 4-electrical distribution system
DESCRIPTION
Teori DistribusiTRANSCRIPT
ELECTRICAL POWER T&D SYSTEM
M O D U L E I V – E L E C T R I C A L D I S T R I B U T I O N S Y S T E M
POWER DISTRIBUTION SYSTEM
ANSI C84.1-1989 divides system voltages into “voltage classes.” 600 V and below are referred to as “low
voltage,” 600 V-69 kV are referred to as “medium
voltage,” 69 kV-230 kV are referred to as “high
voltage” 230 kV-1,100 kV are referred to as “extra
high voltage,” 1,100 kV also referred to as “ultra high
voltage.”
POWER DISTRIBUTION SYSTEM
POWER DISTRIBUTION SYSTEM
PRIMARY DISTRIBUTION SECONDARY DIST.
DISTRIBUTION SYSTEM
DISTRIBUTION SYSTEM
Standar PLN, SPLN 1 : 1995 tentang Tegangan- Tegangan Standar.
Pasal 2 ayat 3 Standar ini disebutkan batasan-batasan sbb.:
Tegangan Rendah antara 100 volt sampai 1.000 volt
Tegangan Menengah di atas 1.000 volt sampai dengan 35.000 volt.
Tegangan Tinggi di atas 35.000 votlt sampai dengan 245.000 volt.
DISTRIBUTION SYSTEM
Kemudian diskripsi tegangan menengah diperlihatkan pada Tabel 2 Pasal 3:
DISTRIBUTION SYSTEM
Saluran distribusi Primer, terletak pada sisi primer trafo distribusi, yaitu antara titik Sekunder trafo substation (Gardu Induk) dengan titik primer trafo distribusi. Saluran ini bertegangan menengah 20 kV.
Saluran Distribusi Sekunder, Terletak pada sisi sekunder trafo distribusi, yaitu antara titik sekunder dengan titik cabang menuju beban, yaitu: 220/380V
1-PHASE VS. 3-PHASE SYSTEM
1-PHASE VS. 3-PHASE SYSTEM
1st reason Three-phase machines and controls can be smaller, lighter in weight, and more efficient than comparable single-phase equipment. More power is supplied to them in the same period than can be supplied by a single-phase power circuit.
2nd reason Only about 75 percent as much copper wire is required for distributing three-phase power as is required for distributing the same amount of single-phase power.
1-PHASE VS. 3-PHASE SYSTEM
DISTRIBUTION SYSTEM CONFIGURATIONRadial LoopNet (Jaring)Spindle
DIST. SYSTEM CONFIG. -RADIAL
DIST. SYSTEM CONFIG.-LOOP
DIST. SYSTEM CONFIG.-NET
DIST. SYSTEM CONFIG.-SPINDLE
VOLTAGE DROP
VOLTAGE DROP
MV SWITCHGEAR
Switchgear is the combination of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment.
Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream.
This type of equipment is important because it is directly linked to the reliability of the electricity supply
MV SWITCHGEAR TYPE
OilOil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil through the arc.
MV SWITCHGEAR TYPEGas
Gas (SF6) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the SF6 to quench the stretched arc
MV SWITCHGEAR TYPEVacuum
Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the contact material), so the arc quenches when it is stretched by a small amount (<2–3 mm).
MV SWITCHGEARAir
Air circuit breakers may use compressed air (puff) or the magnetic force of the arc itself to elongate the arc. CBs are usually able to terminate all current flow very quickly typically between 30 ms and 150 ms depending upon the age and construction of the device.
MV SWITCHGEAR
MV SWITCHGEAR
MV- LOAD BREAK SWITCH
A load break switch is a disconnect switch that has been designed to provide making or breaking of specified currents. This is accomplished by addition of equipment that increases the operating speed of the disconnect switch blade and the addition of some type of equipment to alter the arcing phenomena and allow the safe interruption of the arc resulting when switching load currents.
OVERHEAD DISTRIBUTION SYSTEM
OVERHEAD DISTRIBUTION SYSTEM
OVERHEAD DISTRIBUTION SYSTEM
OVERHEAD DISTRIBUTION SYSTEM
UNDERGROUND DIST. SYSTEM
UNDERGROUND DIST. SYSTEM
UNDERGROUND DIST. SYSTEMConduits are hollow tubes running from manhole to
manhole in an underground transmission or distribution system. They can contain one or more ducts. They can be made of plastic (PVC), fiberglass, fiber, tile, concrete, or steel. PVC and fiberglass are most commonly used.
Duct runs are hollow tubes running from manhole to manhole inside a conduit. The sizes usually from 2 to 6 “ in diameter. Electrical cables are run through ducts and the ducts are sized accordingly. The diameter of a duct should be at least 1/2 to 3/4 inch greater than the diameter of the cable(s) installed in the duct. They can be made of plastic (PVC), fiberglass, fiber, tile, concrete, or steel. PVC and fiberglass are most commonly used.
UNDERGROUND DIST. SYSTEMA manhole is the opening in the underground duct
system which houses cables splices and which cablemen enter to pull in cable and to make splices and tests. Also called a splicing chamber or cable vault
UNDERGROUND DIST. SYSTEMHV underground cable are
constructed in many different ways, but are usually shielded cables. They are made with a conductor, conductor-strand shielding, insulation, semi-conducting insulation shielding, metallic insulation shielding, and a sheath.
The sheath can be metallic and may then serve as the metallic insulation shielding and be covered with a nonmetallic jacket to protect the sheath. This sheath helps to reduce or eliminate inductive reactance.
UNDERGROUND DIST. SYSTEMA transformer vault is a structure or room in which
power transformers, network protectors, voltage regulators, circuit breakers, meters, etc. are housed
UNDERGROUND DIST. SYSTEMA riser is a set of devices that connects an overhead
line to an underground line. A riser has a conduit from the ground up the pole where potheads are used to connect to the overhead lines
DISTRIBUTION TRANSFORMER
DISTRIBUTION TRANSFORMER
DISTRIBUTION TRANSFORMER
DISTRIBUTION TRANSFORMER
DIST. TRANSFORMER – SINGLE PHASE
DIST. TRANSFORMER – THREE PHASE
DIST. TRANSFORMER – THREE PHASE
DIST. TRANSFORMER – THREE PHASE
LOW VOLTAGE SYSTEM
1-phase, 3-wire 3-phase, 4-wire 3-phase, 3-wire
LOW VOLTAGE SYSTEM