ELECTRICAL POWER T&D SYSTEM
M O D U L E I V – E L E C T R I C A L D I S T R I B U T I O N S Y S T E M
![Page 2: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/2.jpg)
POWER DISTRIBUTION SYSTEM
ANSI C84.1-1989 divides system voltages into “voltage classes.” 600 V and below are referred to as “low
voltage,” 600 V-69 kV are referred to as “medium
voltage,” 69 kV-230 kV are referred to as “high
voltage” 230 kV-1,100 kV are referred to as “extra
high voltage,” 1,100 kV also referred to as “ultra high
voltage.”
![Page 3: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/3.jpg)
POWER DISTRIBUTION SYSTEM
![Page 4: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/4.jpg)
POWER DISTRIBUTION SYSTEM
PRIMARY DISTRIBUTION SECONDARY DIST.
![Page 5: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/5.jpg)
DISTRIBUTION SYSTEM
![Page 6: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/6.jpg)
DISTRIBUTION SYSTEM
Standar PLN, SPLN 1 : 1995 tentang Tegangan- Tegangan Standar.
Pasal 2 ayat 3 Standar ini disebutkan batasan-batasan sbb.:
Tegangan Rendah antara 100 volt sampai 1.000 volt
Tegangan Menengah di atas 1.000 volt sampai dengan 35.000 volt.
Tegangan Tinggi di atas 35.000 votlt sampai dengan 245.000 volt.
![Page 7: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/7.jpg)
DISTRIBUTION SYSTEM
Kemudian diskripsi tegangan menengah diperlihatkan pada Tabel 2 Pasal 3:
![Page 8: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/8.jpg)
DISTRIBUTION SYSTEM
Saluran distribusi Primer, terletak pada sisi primer trafo distribusi, yaitu antara titik Sekunder trafo substation (Gardu Induk) dengan titik primer trafo distribusi. Saluran ini bertegangan menengah 20 kV.
Saluran Distribusi Sekunder, Terletak pada sisi sekunder trafo distribusi, yaitu antara titik sekunder dengan titik cabang menuju beban, yaitu: 220/380V
![Page 9: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/9.jpg)
1-PHASE VS. 3-PHASE SYSTEM
![Page 10: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/10.jpg)
1-PHASE VS. 3-PHASE SYSTEM
1st reason Three-phase machines and controls can be smaller, lighter in weight, and more efficient than comparable single-phase equipment. More power is supplied to them in the same period than can be supplied by a single-phase power circuit.
2nd reason Only about 75 percent as much copper wire is required for distributing three-phase power as is required for distributing the same amount of single-phase power.
![Page 11: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/11.jpg)
1-PHASE VS. 3-PHASE SYSTEM
![Page 12: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/12.jpg)
DISTRIBUTION SYSTEM CONFIGURATIONRadial LoopNet (Jaring)Spindle
![Page 13: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/13.jpg)
DIST. SYSTEM CONFIG. -RADIAL
![Page 14: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/14.jpg)
DIST. SYSTEM CONFIG.-LOOP
![Page 15: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/15.jpg)
DIST. SYSTEM CONFIG.-NET
![Page 16: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/16.jpg)
DIST. SYSTEM CONFIG.-SPINDLE
![Page 17: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/17.jpg)
VOLTAGE DROP
![Page 18: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/18.jpg)
VOLTAGE DROP
![Page 19: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/19.jpg)
MV SWITCHGEAR
Switchgear is the combination of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment.
Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream.
This type of equipment is important because it is directly linked to the reliability of the electricity supply
![Page 20: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/20.jpg)
MV SWITCHGEAR TYPE
OilOil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil through the arc.
![Page 21: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/21.jpg)
MV SWITCHGEAR TYPEGas
Gas (SF6) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the SF6 to quench the stretched arc
![Page 22: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/22.jpg)
MV SWITCHGEAR TYPEVacuum
Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the contact material), so the arc quenches when it is stretched by a small amount (<2–3 mm).
![Page 23: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/23.jpg)
MV SWITCHGEARAir
Air circuit breakers may use compressed air (puff) or the magnetic force of the arc itself to elongate the arc. CBs are usually able to terminate all current flow very quickly typically between 30 ms and 150 ms depending upon the age and construction of the device.
![Page 24: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/24.jpg)
MV SWITCHGEAR
![Page 25: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/25.jpg)
MV SWITCHGEAR
![Page 26: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/26.jpg)
MV- LOAD BREAK SWITCH
A load break switch is a disconnect switch that has been designed to provide making or breaking of specified currents. This is accomplished by addition of equipment that increases the operating speed of the disconnect switch blade and the addition of some type of equipment to alter the arcing phenomena and allow the safe interruption of the arc resulting when switching load currents.
![Page 27: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/27.jpg)
OVERHEAD DISTRIBUTION SYSTEM
![Page 28: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/28.jpg)
OVERHEAD DISTRIBUTION SYSTEM
![Page 29: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/29.jpg)
OVERHEAD DISTRIBUTION SYSTEM
![Page 30: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/30.jpg)
OVERHEAD DISTRIBUTION SYSTEM
![Page 31: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/31.jpg)
UNDERGROUND DIST. SYSTEM
![Page 32: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/32.jpg)
UNDERGROUND DIST. SYSTEM
![Page 33: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/33.jpg)
UNDERGROUND DIST. SYSTEMConduits are hollow tubes running from manhole to
manhole in an underground transmission or distribution system. They can contain one or more ducts. They can be made of plastic (PVC), fiberglass, fiber, tile, concrete, or steel. PVC and fiberglass are most commonly used.
Duct runs are hollow tubes running from manhole to manhole inside a conduit. The sizes usually from 2 to 6 “ in diameter. Electrical cables are run through ducts and the ducts are sized accordingly. The diameter of a duct should be at least 1/2 to 3/4 inch greater than the diameter of the cable(s) installed in the duct. They can be made of plastic (PVC), fiberglass, fiber, tile, concrete, or steel. PVC and fiberglass are most commonly used.
![Page 34: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/34.jpg)
UNDERGROUND DIST. SYSTEMA manhole is the opening in the underground duct
system which houses cables splices and which cablemen enter to pull in cable and to make splices and tests. Also called a splicing chamber or cable vault
![Page 35: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/35.jpg)
UNDERGROUND DIST. SYSTEMHV underground cable are
constructed in many different ways, but are usually shielded cables. They are made with a conductor, conductor-strand shielding, insulation, semi-conducting insulation shielding, metallic insulation shielding, and a sheath.
The sheath can be metallic and may then serve as the metallic insulation shielding and be covered with a nonmetallic jacket to protect the sheath. This sheath helps to reduce or eliminate inductive reactance.
![Page 36: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/36.jpg)
UNDERGROUND DIST. SYSTEMA transformer vault is a structure or room in which
power transformers, network protectors, voltage regulators, circuit breakers, meters, etc. are housed
![Page 37: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/37.jpg)
UNDERGROUND DIST. SYSTEMA riser is a set of devices that connects an overhead
line to an underground line. A riser has a conduit from the ground up the pole where potheads are used to connect to the overhead lines
![Page 38: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/38.jpg)
DISTRIBUTION TRANSFORMER
![Page 39: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/39.jpg)
DISTRIBUTION TRANSFORMER
![Page 40: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/40.jpg)
DISTRIBUTION TRANSFORMER
![Page 41: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/41.jpg)
DISTRIBUTION TRANSFORMER
![Page 42: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/42.jpg)
DIST. TRANSFORMER – SINGLE PHASE
![Page 43: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/43.jpg)
DIST. TRANSFORMER – THREE PHASE
![Page 44: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/44.jpg)
DIST. TRANSFORMER – THREE PHASE
![Page 45: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/45.jpg)
DIST. TRANSFORMER – THREE PHASE
![Page 46: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/46.jpg)
LOW VOLTAGE SYSTEM
1-phase, 3-wire 3-phase, 4-wire 3-phase, 3-wire
![Page 47: Modul 4-Electrical Distribution System](https://reader035.vdocuments.site/reader035/viewer/2022062310/55cf9146550346f57b8c3703/html5/thumbnails/47.jpg)
LOW VOLTAGE SYSTEM