minimum melting time–current characteristic curves single

1
March 8, 2021 © S&C Electric Company 1985–2021, all rights reserved TCC Number 410-7 BASIS–The minimum tripping time-current characteristic curves shown above are applicable over the entire Fault Fiter Electronic Power Fuse operating temperature range of -40°C to +55°C (-40°F to +131°F). No adjustments must be made to these curves for ambient temperatures within this temperature range or to reflect self-heating caused by the flow of load current. TOLERANCES –Curves are plotted to minimum test points; maximum variations expressed in current values are plus 10%. APPLICATION–The maximum continuous current-carrying capability of Fault Fiter Electronic Power Fuses is 600 amperes RMS, regardless of the control module selected. Because Fault Fiter Electronic Power Fuse time-current characteris- tics are electronically derived, they are not subject to change caused by aging, transient overcurrents, or fault currents. It is, therefore, unneces- sary to replace Fault Fiter control modules following a fault-clearing operation. Only blown Fault Filer interrupting modules must be replaced. IMPORTANT: Fault Fiter Electronic Power Fuse control modules must be selected by qualified persons knowledgeable in equipment protection and time-current coordination and who understand the consequences of improperly coordinated overcurrent protective devices. Failure to achieve complete coordination between Fault Fiter Electronic Power fuses and source-side or load-side protective devices may result in improper operation of one or more Fault Fiter Fuses. Minimum Melting Time–Current Characteristic Curves Single Fault Fiter ® Electronic Power Fuses Inverse-Curve–Type Control Modules 400 500 600 700 800 1000 1200 1500 AVAILABLE CONTROL MODULES Minimum Pickup, Amperes, Rms Catalog Numbers 400 500 600 700 800 1000 1250 1500 814040 814050 814060 814070 814080 814100 814125 814150

Upload: others

Post on 23-Feb-2022

11 views

Category:

Documents


0 download

TRANSCRIPT

March 8, 2021

© S&C Electric Company 1985–2021, all rights reserved TCC Number 410-7

BASIS–The minimum tripping time-current characteristic curves shown above are applicable over the entire Fault Fiter Electronic Power Fuse operating temperature range of -40°C to +55°C (-40°F to +131°F). No adjustments must be made to these curves for ambient tempera tures within this temperature range or to reflect self-heating caused by the flow of load current.

TOLERANCES–Curves are plotted to minimum test points; max imum variations expressed in current values are plus 10%.

APPLICATION–The maximum continuous current-carrying capability of Fault Fiter Electronic Power Fuses is 600 amperes RMS, regardless of the control module selected.

Because Fault Fiter Electronic Power Fuse time-current characteris-tics are electronically derived, they are not subject to change caused by aging, transient overcurrents, or fault currents. It is, therefore, unneces-sary to replace Fault Fiter control modules following a fault-clearing operation. Only blown Fault Filer interrupting modules must be replaced.

IMPORTANT: Fault Fiter Electronic Power Fuse control modules must be selected by qualified persons knowledge able in equipment protection and time-current coordination and who understand the consequences of improperly coordinated overcurrent protective devices. Failure to achieve complete coordination between Fault Fiter Electronic Power fuses and source-side or load-side protective devices may result in improper operation of one or more Fault Fiter Fuses.

Minimum Melting Time–Current Characteristic CurvesSingle Fault Fiter® Electronic Power Fuses

Inverse-Curve–Type Control Modules

400

500

600

700

800

1000

1200

1500

AVAILABLE CONTROL MODULESMinimum Pickup,

Amperes, RmsCatalog Numbers

400 500 600 700 800 1000 1250 1500

814040 814050 814060 814070 814080 814100 814125 814150