micromaster catalog da512 mm4 2005-6

Upload: vikrant

Post on 06-Jul-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    1/125

    MICROMASTER 410/420/430/440

    Inverters

    0.12 kW to 250 kW

          

       

      

     

         

        

    micromaster

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    2/125

    Related catalogs

    SINAMICS G110 D 11.1Converter Chassis Units0.12 kW (0.16 HP) to3 kW (4 HP)Order No.:German: E86060-K5511-A111-A2English: E86060-K5511-A111-A2-7600

    SINAMICS G130 D 11Converter Chassis UnitsSINAMICS G150Converter Cabinet UnitsOrder No.:German: E86060-K5511-A101-A3English: E86060-K5511-A101-A3-7600

    MICROMASTER/COMBIMASTER DA 51.3MICROMASTER 411 InvertersDistributed Drive SolutionsCOMBIMASTER 411Order No.:German: E86060-K5251-A131-A2English: E86060-K5251-A131-A2-7600

    Industrial Communication IK PIfor Automation and DrivesPart 6: Distributed I/Os ET 200Frequency Converter ET 200S FCOrder No.:E86060-K6710-A101-B4-7600

    Low-Voltage Motors M 11

    Order No.:German: E86060-K1711-A101-A3English: E86060-K1711-A101-A3-7600

    Geared Motors M 15Helical, Flat, Bevel-helical,Helical-wormand Worm Geared MotorsOrder No.:E86060-K1715-A101-A5(available in German only)

    Catalog CA 01 CA 01The Offline Mall of Automation and DrivesOrder No.:CD-ROM:E86060-D4001-A100-C4 (Germ.)CD-ROM:E86060-D4001-A110-C4-7600 (Engl.)DVD: E86060-D4001-A500-C4 (Germ.)

    A&D Mall

    Internet:http://www.siemens.com/automation/mall

    Catalog CA 01 – SD configurator selection aid

    The SD configurator selection aid will be available in combinationwith the CA 01 electronic catalog.

    On CD 2 of the selection and configuration aids you will find the SDconfigurator for low-voltage motors, MICROMASTER 4 inverters,inverter chassis units SINAMICS G110 and frequency converters fordistributed I/Os SIMATIC ET 200S FC including:

    • Dimension drawing generator for motors

    • Data sheet generator for motors

    • Starting calculation

    • 3D models in .stp format

    • Extensive documentation

    Hardware and software requirements

    • PC with Pentium II or comparable processor

    • Operating systems– Windows 98/ME– Windows 2000– Windows XP– Windows NT

    (Service Pack 5 upwards)

    • Minimum of 128 RAM

    • 1024 x 768 graphics with more than 256 colors / small fonts

    • CD-ROM drive

    • Windows-compatible sound card

    • Windows-compatible mouse

    Installation

     You can install this catalog directly from the CD-ROM as a completeor partial version on your hard disk or in the network.

    Hotline:

    For technical advice and hotline support concerning our CA 01catalog:

    Tel.: +49 (0) 180 50 50 22 2

    E-Mail: [email protected]

    Trademarks

    All product designations may be trademarks or product

    names of Siemens AG or supplier companies whoseuse by third parties for their own purposes couldviolate the rights of the owners.

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    3/125

     s 

    Supersedes:Catalog DA 51.2 · 2003/2004

    The products in this catalog are also includedin the CD-ROM catalog CA 01.Order No.:E86060-D4001-A110-C4-7600 (CD-ROM)

    Contact your local Siemens representativefor further information

    © Siemens AG 2005

    MICROMASTER410/420/430/440Inverters0.12 kW to 250 kWCatalog DA 51.2

    2005/2006

    The products and sys- 

    tems described in this

    catalog are manufac- 

    tured/distributed under

    application of a certified

    quality management

    system in accordance

    with DIN EN ISO 9001

    (Certified Registration

    No. 000357 QM) and

    DIN EN ISO 14001

    (Certified Registration

    No. 081342 UM and

    EMS 57390). The cer- tificate is recognized by

    all IQNet countries.

    Overview Welcome toAutomation and Drives

    Selection guideMICROMASTER inverters

    Overview of options

    MICROMASTER 410

    “The low-priced”

    0.12 kW to 0.75 kW

    MICROMASTER 420

    “The universal”

    0.12 kW to 11 kW

    MICROMASTER 430

    “The specialist for

    pumps and fans”

    7.5 kW to 250 kW

    MICROMASTER 440

    “The all-purpose”

    0.12 kW to 250 kW

    Appendix Certificates/Standards

    Demonstration case/ Training

    Overview of motors andinverters

    Siemens contacts

    Online services

    Service & SupportConditions of sale anddelivery

    Export regulations

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    4/125

    Siemens DA 51.2 · 2005/2006

    Welcome toAutomation and Drives

    We would like to welcome you to Automation and Drives

    and our comprehensive range of products, systems,

    solutions and services for production and

    process automation and building technology

    worldwide.

    With Totally Integrated Automation and Totally

    Integrated Power, we deliver solution platforms based

    on standards that offer you a considerable savings

    potential.

    Discover the world of our technology now. If you need

    more detailed information, please contact one of your

    regional Siemens partners.

    They will be glad to assist you.

    0/2

    Sprachumschaltung über

    Spezial - Bedingter Text -

    Ein-/Ausblenden

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    5/125

    Siemens DA 51.2 · 2005/2006   0/3

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    6/125

    Siemens DA 51.2 · 2005/2006

                                                            

     

     

     

    Totally Integrated Automation –innovations for more productivity

    With the launch of Totally Integrated Automation, we were the

    first ones on the market to consistently implement the trendfrom equipment to an integrated automation solution, and

    have continuously improved the system ever since.Whether your industry is process- and production-oriented ora hybrid, Totally Integrated Automation is a unique “common

    solution” platform that covers all the sectors.

    Totally Integrated Automation is an integrated platform for theentire production line - from receiving to technical processing

    0/4 Siemens DA 51.2 · 2005/2006

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    7/125

    Siemens DA 51.2 · 2005/2006

     

     

    and production areas to shipping. Thanks to the system-

    oriented engineering environment, integrated, open commu-nications as well as intelligent diagnostics options, your plant

    now benefits in every phase of the life cycle.In fact, to this day we are the only company worldwide that canoffer a control system based on an integrated platform for both

    the production and process industry.

    0/5Siemens DA 51.2 · 2005/2006

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    8/125Siemens DA 51.2 · 2005/20060/6

    MICROMASTER 410/420/430/440

      Overview

    MICROMASTER® 410/420/430/440

    ■ Selection guide

    Main characteristics “The low-priced” 

    for variable speeds with three-phase motorson single-phase networks, e.g. with pumps,

    fans, billboards, barriers, gate drives and

    automatic machines

    “The universal” 

    for three-phase networks and optionalfieldbus interfacing, e.g. for conveyor belts,

    material transport, pumps, fans and machine tools

    Power ranges 0.12 kW to 0.75 kW 0.12 kW to 11 kW

     Voltage ranges 1 AC 100 V to 120 V

    1 AC 200 V to 240 V 

    1 AC 200 V to 240 V

    3 AC 200 V to 240 V

    3 AC 380 V to 480 V

    Control methods • V/f  characteristic• Multipoint characteristic

    (programmable V/f  characteristic)• FCC (flux current control)

    • V/f  characteristic• Multipoint characteristic

    (programmable V/f  characteristic)• FCC (flux current control)

    Process control – Internal PI controller

    Inputs 3 digital inputs

    1 analog input

    3 digital inputs

    1 analog input

    Outputs 1 relay output 1 analog output

    1 relay output

    Interfacing to automation

    system

     The PLC partner for LOGO! and

    SIMATIC S7-200

     The ideal partner for your automation tasks,

    whether with SIMATIC S7-200,

    SIMATIC S7-300/400 (TIA) or SIMOTION

     Additional features • Natural ventilation (no fan unit)

    • Position of connections as with convention-al switching elements (e.g. contactors)

    • Variant with flat plate heatsink

    • BICO technology

    • Compound braking for controlled rapid braking

    MICROMASTER 410MICROMASTER 410 MICROMASTER 420MICROMASTER 420

    Section 1Section 1 Section 2Section 2

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    9/125Siemens DA 51.2 · 2005/2006   0/7

    MICROMASTER 410/420/430/440

    Overview

    “The specialist for pumps and fans” 

    with optimized OP (manual/automatic switchover), matchedsoftware functionality and optimized power yield

    “The all-purpose” 

    with advanced vector control (with and without encoder feedback)for versatile applications in sectors such as conveying systems,

    textiles, elevators, hoisting equipment and machine construction

    7.5 kW to 250 kW 0.12 kW to 250 kW

    3 AC 380 V to 480 V 1 AC 200 V to 240 V  

    3 AC 200 V to 240 V 

    3 AC 380 V to 480 V 

    3 AC 500 V to 600 V 

    • V/f  characteristic• Multipoint characteristic

    (programmable V/f  characteristic)• FCC (flux current control)

    • V/f  characteristic• Multipoint characteristic

    (programmable V/f  characteristic)• FCC (flux current control)

    • Vector control

    Internal PID controller Internal PID controller

    (autotuning)

    6 digital inputs2 analog inputs1 PTC/KTY input

    6 digital inputs2 analog inputs1 PTC/KTY input

    2 analog outputs3 relay outputs

    2 analog outputs3 relay outputs

     The ideal partner for your automation tasks, whether with

    SIMATIC S7-200, SIMATIC S7-300/400 (TIA) or SIMOTION

     The ideal partner for your automation tasks, whether with

    SIMATIC S7-200, SIMATIC S7-300/400 (TIA) or SIMOTION

    • Low-energy mode

    • Load torque monitoring(detects dry run of pumps)

    • Motor staging• Bypass mode• BICO technology

    • 3 selectable drive data kits

    • Integrated brake chopper (up to 75 kW)• Torque control• BICO technology

    MICROMASTER 430MICROMASTER 430 MICROMASTER 440MICROMASTER 440

    Section 3Section 3 Section 4Section 4

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    10/1250/8 Siemens DA 51.2 · 2005/2006

    MICROMASTER 410/420/430/440

    ■ Options

    Operator panels

    Modules

    Various options are availablefor the MICROMASTERinverters:

    ■ Filters

    ■ Chokes■ Operator panels

    ■ PROFIBUS module

    ■ DeviceNet module

    ■ CANopen module

    ■ Pulse encoder evaluationmodule

    ■ Gland plates

    ■ Mounting kits, etc.

    Assignment of operator panels and modules to the inverter ranges

    Options Order No.   MICROMASTER

    410 420 430 440

    Operator panels

    OP 6SE6400-0SP00-0AA0   %

    BOP 6SE6400-0BP00-0AA0   % %

    BOP-2 6SE6400-0BE00-0AA0   %

    AOP 6SE6400-0AP00-0AA1   % %

    AAOP 6SE6400-0AP00-0AB0   % %

    Modules

    PROFIBUS 6SE6400-1PB00-0AA0   % % %

    DeviceNet 6SE6400-1DN00-0AA0   % % %

    CANopen 6SE6400-1CB00-0AA0   % % %

    Pulse encoder evaluation 6SE6400-0EN00-0AA0   % %

    % Possible combination

    OP/BOP AOPBOP-2 AAOP

    PROFIBUS DeviceNet Pulse encoder evaluationCANopen

    Overview

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    11/125Siemens DA 51.2 · 2005/2006   1/1

    InverterMICROMASTER 410

    1/2   Description

    1/4   Circuit diagrams

    1/6   Technical data

    1/7   Selection and ordering data

    1/8   Options

    1/10   Dimension drawings

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    12/1251/2 Siemens DA 51.2 · 2005/2006

    MICROMASTER 410

    ■ Application

    The MICROMASTER 410 in-verter is suitable for a varietyof variable-speed drive appli-cations.

    It is especially suitable for use

    with pumps and fans, as adrive in various sectors, e.g.food, textile and packaging in-dustries as well as for convey-or systems, factory gate andgarage door drives and as auniversal drive for moving bill-boards.

    It is the ideal low-cost frequen-cy inverter solution for the low-end performance range of theMICROMASTER product fam-ily.

    The inverter is especially char-

    acterized by its customer-ori-ented performance and ease-of-use.

    Versions for connecting to230 V and 115 V single-phasenetworks enable it to be usedall over the world.

    ■ Design

    The MICROMASTER 410 in-verter has a compact design.

    Heatsinks provide naturalcooling for the inverter. A fanunit is not used.

    The position of the connec-tions has been selected as forconventional contactors.

    The operator panel availableas an option can be easily fit-ted without requiring any tools.

    The design with flat plate heat-sink offers space-saving andfavorable heat dissipationsince an additional heatsinkcan be installed outside thecontrol cabinet.

    ■ Main characteristics

    ■ Simple selection from mini-mum range of types (only afew options)

    ■ Compact design

    ■ Natural cooling with heatsinks (no fan unit)

    ■ Simple connection similarto conventional switchingelements (e.g. contactors)

    ■ Versions with internal EMCfilter Class B

    ■ Fast, simple commission-ing with input of only a fewparameters (fast commis-sioning mode)

    ■ Integrated RS-485 commu-nications interface

    ■ Three programmable digi-tal inputs, non-floating (the

    analog input can be usedas a fourth binary input)

    ■ One analog input(0 V to 10 V)

    ■ One programmable relayoutput(30 V DC/5 A resistive load;250 V AC/2A inductiveload)

    ■ Low-noise motor operationresulting from high pulsefrequency

    ■ Integrated protection formotor and inverter.

    ■ Options (overview)

    ■ Line commutating chokes

    ■ Adapter for standardizedmounting on DIN rails

    ■ OP (Operator Panel) foruser-friendly parameteriza-tion of an inverter

    ■ Connection kit for PC to in-verter

    ■ PC startup program.

    ■ International standards

    ■ The MICROMASTER 410inverter complies with therequirements of the EU low-voltage guideline

    ■ The MICROMASTER 410inverter has the> mark-ing

    ■ u and cu listed (not for ver-

    sions with flat heat sinks)■ c-tick ●✔

    Note:

    See Appendix for standards.

    InverterFrame size AA

    InverterFrame size AB

    Inverterwith flat heat sink

    Description

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    13/125Siemens DA 51.2 · 2005/2006   1/3

    MICROMASTER 410

    ■ Mechanical features   ■ Performance features   ■ Protection features

    ■ Compact design

    ■ Heat dissipation throughself-ventilation (convection)

    ■ Operating temperature

    –10 °C to +50 °C(+14 °F to +122 °F)

    ■ Easy cable connection,mains and motor connec-tions are separated for opti-mal electromagnetic com-patibility and clearconnection

    ■ Detachable, optional oper-ator panels

    ■ Screwless control terminals

    ■ Side mounting possible,thus also usable with lowcabinet depth.

    ■ Latest IGBT technology

    ■ Digital microprocessorcontrol

    ■ Linear V/f  characteristic,

    with programmable voltageboosting

    ■ Quadratic V/f  characteristic

    ■ Multipoint characteristic(programmable V/f  charac-teristic)

    ■ Flying restart

    ■ Automatic restart aftermains failure or fault

    ■ Programmable ramp gener-ator (0 s to 650 s) with pos-sible rounding

    ■ Fast current limit (FCL) fortrip-free operation

    ■ Fast, repeatable digital in-put response time

    ■ Exact setpoint specificationusing a high-resolution

    10-bit analog input■ One skip frequency range

    ■ Removable Y cap for use inIT systems

    ■ Serial RS-485 interface withUSS protocol

    ■ LED for status information

    ■ Versions with internal EMCfilter Class B

    ■ Overload current 1.5 x rat-ed output current (i.e.150 %overload capability) for60 s, then 0.85 x rated out-

    put current for 240 s, cycletime 300 s

    ■ Overvoltage/undervoltageprotection

    ■ Inverter overtemperatureprotection

    ■ Earth fault protection

    ■ Short-circuit protection

    ■   I 2t  motor thermal protection

    ■ Stall prevention.

    Description

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    14/1251/4 Siemens DA 51.2 · 2005/2006

    MICROMASTER 410

    ■ General circuit diagram

         

     

     

     

         

       

     

     

    Circuit diagrams

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    15/125Siemens DA 51.2 · 2005/2006   1/5

    MICROMASTER 410

    ■ Terminal connection diagram

                                                           

     

       

     

     

          

    View A

    View A

    Motor connections

    Mains connections

    Circuit diagrams

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    16/1251/6 Siemens DA 51.2 · 2005/2006

    MICROMASTER 410

    ■ MICROMASTER 410 inverter

    ■ Derating data

    Pulse frequency 

    The current data apply to an ambient temperature of 50 °C/122 °F unless specified otherwise.

    Input voltages and power ranges 1 AC 200 V to 240 V ± 10 %1 AC 100 V to 120 V ± 10 %

    0.12 to 0.75 kW0.12 to 0.55 kW

    Power frequency 47 to 63 Hz

    Output frequency 0 Hz to 650 Hz

    Power factor   0.95Inverter efficiency 90 % to 95 %

    Overload capability Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s;then 0.85 x rated output current for 240 s, cycle time 300 s

    Precharge current Not higher than rated input current

    Control method Linear V/f  characteristic; quadratic V/f  characteristic; multipoint characteristic(programmable V/f  characteristic)

    Pulse frequency 8 kHz (standard)/2 kHz to 16 kHz (in 2 kHz steps)

    Fixed frequencies 3, programmable

    Skip frequency ranges 1, programmable

    Setpoint resolution 10 bit analog/0.01 Hz serial

    Digital inputs 3 programmable digital inputs, non-floating, PNP, SIMATIC-compatible

    Analog input 1, for setpoint (0 V to 10 V, scaleable or for use as 4th digital input)

    Relay outputs 1, programmable, 30 V DC/5 A (resistive load); 250 V AC/2A (inductive load)

    Serial interface RS-485, for operation with USS protocolMotor cable lengths Max. 30 m (shielded)/max. 50 m (unshielded)

    Electromagnetic compatibility Inverter available with internal EMC filter to EN 61 800-3 (defined limits to EN 55 011, Class B)

    Braking DC braking, compound braking

    Degree of protection IP20

    Operating temperature –10 °C to +50 °C (+14 °F to +122 °F)

    Storage temperature –40 °C to +70 °C (–40 °F to +158 °F)

    Relative humidity 95 % (non-condensing)

    Site altitude Up to 1000 m above sea level without derating

    Protection features for Undervoltage, overvoltage, overload, earth faults, short circuits, stall prevention, I 

    2t  motor thermal protection, inverter overtemperature

    Typical power losses (heatsink) atfull load and maximum operatingtemperature as specified

    20 W (with 0.37 kW inverter with flat plate heatsink)37 W (with 0.75 kW inverter with flat plate heatsink)

    Line-side and control electronicslosses (at 230 V, 50 Hz, 8 kHz) 18 W (with 0.37 kW inverter with flat plate heatsink)34 W (with 0.75 kW inverter with flat plate heatsink)

    Recommended thermal resistanceof heatsink

    1.8 K/W (with 0.37 kW inverter with flat plate heatsink)1.2 K/W (with 0.75 kW inverter with flat plate heatsink)

    Compliance with standards u, cu (not for versions with flat plate heatsink)>, c-tick ●✔

    > marking Conformity with low-voltage directive 73/23/EC

    Dimensions and weights (withoutoptions)

    Frame size (FS)AAAB0.37 kW inverter with flat plate heatsink0.75 kW inverter with flat plate heatsink

    H x W x D (mm)150 x 69 x 118150 x 69 x 138175 x 69 x 102175 x 69 x 102

    Weight, approx. (kg)0.81.00.780.8

    Output   Rated output current in Afor a pulse frequency of

    kW 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz

    0.12 0.9 0.9 0.9 0.8 0.7 0.6 0.5

    0.25 1.7 1.7 1.7 1.5 1.3 1.1 0.9

    0.37 2.3 2.3 2.3 2.0 1.7 1.5 1.3

    0.55 3.2 3.2 3.2 2.9 2.6 2.3 2.0

    0.55, 115 V (at 50 °C/122 °F) 3.0 3.0 2.7 2.5 2.2 2.0 1.7

    0.55, 115 V (at 40 °C/104 °F) 3.2 3.2 3.2 2.9 2.6 2.3 2.0

    0.75 (at 50 °C/122 °F) 3.9 3.9 3.6 3.2 2.9 2.6 2.3

    0.75 (at 40 °C/104 °F) 4.2 4.2 4.2 3.8 3.4 3.0 2.7

    Technical data

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    17/125Siemens DA 51.2 · 2005/2006   1/7

    MICROMASTER 410

    ■ Derating data (continued)

    Installation height above sea level 

    ■ MICROMASTER 410 inverter

    Output Rated inputcurrent 1)

    Rated output current Framesize

    Order No.

    kW hp A A (FS)MICROMASTER 410without filter 2)

    MICROMASTER 410with internal filter Class B

    Mains voltage 1 AC 100 V to 120 V, output voltage 200 V to 240 V 3-phase

    0.12 0.16 4.6 0.9 AA   6SE6410-2UA11-2AA0 –

    0.25 0.33 7.5 1.7 AA   6SE6410-2UA12-5AA0 –

    0.37 0.50 10.1 2.3 AA   6SE6410-2UA13-7AA0 –

    0.55 0.75 13.4 2.7 (3.2 at 40 °C/104 °F) AB   6SE6410-2UA15-5BA0 –

    Mains voltage 1 AC 200 V to 240 V, output voltage 200 V to 240 V 3-phase

    0.12 0.16 1.5 0.9 AA   6SE6410-2UB11-2AA0 6SE6410-2BB11-2AA0

    0.25 0.33 3.0 1.7 AA   6SE6410-2UB12-5AA0 6SE6410-2BB12-5AA0

    0.37 0.50 4.4 2.3 AA   6SE6410-2UB13-7AA0 6SE6410-2BB13-7AA0

    0.55 0.75 5.8 3.2 AB   6SE6410-2UB15-5BA0 6SE6410-2BB15-5BA0

    0.75 1.0 7.8 3.6 (4.2 at 40 °C/104 °F) AB   6SE6410-2UB17-5BA0 6SE6410-2BB17-5BA0

    Inverter with flat plate heatsink 

    0.37 0.5 4.4 2.3 AA   6SE6410-2UB13-7AB0 6SE6410-2BB13-7AB0

    0.75 1 7.8 4.2 (at 40 °C/104 °F) AB   6SE6410-2UB17-5BB0 6SE6410-2BB17-5BB0

    See Appendix for note on or-dering.

    All MICROMASTER 410 invert-ers are supplied without anOperator Panel (OP). An OP orother options must be orderedseparately (see Page 1/9).

    ■ Motors forMICROMASTER 410

    Catalog M 11 contains selec-tion and ordering data for mo-tors which are particularly suit-able for operation with theMICROMASTER 410 inverters(see Appendix for overview).This catalog is suitable for IECmotors. For motors accordingto US standards (NEMA)please refer to:http://www.sea.siemens.com/ motors

                                

     

     

                                              

    Permissible output currentin % of the rated output current

    Permissible mains voltagein % of the max. possible mains voltage

    Selection and ordering data

    The current data apply to an ambient temperature of 50 °C/122 °Funless specified otherwise.

    1) The values apply to rated mains voltages of 115 V or 230 V.

    2) Generally suited to heavy industrial applications.

    For details please refer to Appendix on page A/4.

    Technical data

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    18/1251/8 Siemens DA 51.2 · 2005/2006

    MICROMASTER 410

    ■ Overview

    EMC filter, Class B 

    Variants with internal EMC fil-ter Class B are available for in-verters with a mains operating

    voltage of 1 230 V AC.

    • The requirements are satis-fied using: shielded cableswith a max. length of 5 m, or10 m with a low-capacitancemotor cable (core/core< 75 pF/m, core/shield< 150 pF/m). The limits com-ply with EN 55 011 Class B.

    An inverter with internal filtercan be used with a 30 mA re-sidual current operated cir-cuit-breaker, and is only suit-able for hardwired installation.

    A non-filtered inverter togetherwith the optional filter “FilterClass B with low leakage cur-rents” has a leakage current

    3.5 mA (shielded motorcable up to 5 m).

    Line commutating choke 

    Line commutating chokes areused to smooth voltage peaksor to bridge commutatingdips.

    In addition, line commutatingchokes reduce the effects ofharmonics on the inverter andthe power supply.

    If the ratio of inverter ratedpower to mains short-circuit

    power is less than 1 %, a linecommutating choke must beused in order to reduce thecurrent peaks.

    The line commutating chokesare designed as footprintchokes and are fitted betweenthe inverter and the mountingplate.

    In line with EN 61 000-3-2 reg-ulations “Limits for harmoniccurrents with device input cur-rent 16 A per phase”, thereare special aspects for driveswith 250 W to 550 W and 230 Vsingle-phase supplies whichcan be used in non-industrialapplications (1st environ-

    ment).

    For devices with 250 W and370 W, it is necessary either tofit the recommended inputchokes or to apply to the pow-

    er utility company for authori-zation to connect the devicesto the public power supply.No limits are currently definedin the EN 61 000-3-2 standardfor professionally used devic-es with a connected load> 1 kW, which means that theinverters with an output power 0.75 kW comply with theEN 61 000-3-2 standard.

    ■ Selection and ordering data

    The options listed here (filters,chokes, fuses and circuit-breakers) must be selected tomatch the inverter.

    The inverter and the associat-ed options have the same volt-age ratings.

    All variant dependent op- tions and the operator panelare certified to u except fus- es. Fuses of Type 3NA3 arerecommended for Europe.

    Use in America requires u-listed fuses such as theClass NON range fromBussmann.

    Mainsvoltage

    Output

    kW hp

    Inverterwithout filter

    Order No. of the options

    Filter Class B with lowleakage currents

    Line commutatingchoke

    Fuse(see CatalogLV 10)

    Circuit-breaker(see CatalogLV 10)

    1 AC 100 Vto 120 V 0.12 0.16 6SE6410-2UA11-2AA0 –   6SE6400-3CC01-0AB3 3NA3803 3RV1021-1GA100.25 0.33 6SE6410-2UA12-5AA0 –   3RV1021-1JA10

    0.37 0.50 6SE6410-2UA13-7AA0 *) –   6SE6400-3CC02-6BB3 3NA3805 3RV1021-1KA10

    0.55 0.75 6SE6410-2UA15-5BA0 *) –   3NA3807 3RV1021-4AA10

    1 AC 200 Vto 240 V

    0.12 0.16 6SE6410-2UB11-2AA0   6SE6400-2FL01-0AB0 6SE6400-3CC00-4AB3 3NA3803 3RV1021-1BA10

    0.25 0.33 6SE6410-2UB12-5AA0   3RV1021-1EA10

    0.37 0.50 6SE6410-2UB13-7AA0   6SE6400-3CC01-0AB3 3RV1021-1FA10

    0.55 0.75 6SE6410-2UB15-5BA0   3RV1021-1HA10

    0.75 1.0 6SE6410-2UB17-5BA0   3NA3805 3RV1021-1JA10

    Inverter with flat plate heatsink 

    0.37 0.50 6SE6410-2UB13-7AB0 *)   6SE6400-2FL01-0AB0 6SE6400-3CC01-0AB3   3NA3803 3RV1021-1FA10

    0.75 1.0 6SE6410-2UB17-5BB0 *)   3NA3805 3RV1021-1JA10

    Inverter with internal filter Class B

    1 AC 200 Vto 240 V 0.12 0.16 6SE6410-2BB11-2AA0 –   6SE6400-3CC00-4AB3 3NA3803 3RV1021-1BA100.25 0.33 6SE6410-2BB12-5AA0 –   3RV1021-1EA10

    0.37 0.50 6SE6410-2BB13-7AA0 –   6SE6400-3CC01-0AB3 3RV1021-1FA10

    0.55 0.75 6SE6410-2BB15-5BA0 –   3RV1021-1HA10

    0.75 1.0 6SE6410-2BB17-5BA0 –   3NA3805 3RV1021-1JA10

    Inverter with flat plate heatsink 

    0.37 0.50 6SE6410-2BB13-7AB0 *) –   6SE6400-3CC01-0AB3   3NA3803 3RV1021-1FA10

    0.75 1.0 6SE6410-2BB17-5BB0 *) –   3NA3805 3RV1021-1JA10

    *) With these inverters, the filter or choke cannot be mounted in the substructure. This option must be mounted upright.

    OptionsInverter dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    19/125Siemens DA 51.2 · 2005/2006   1/9

    MICROMASTER 410

    ■ Selection and ordering data

    ■ Overview

    Operator Panel (OP) 

    With the OP, individual param-eter settings can be made.

    Values and units are shown ona 5-digit display.

    An OP can be used for severalinverters. It is directly pluggedinto the inverter.

    Connection kit for PC to inverter 

    For controlling and commis-sioning an inverter directly

    from a PC if the appropriatesoftware has been installed(e.g. STARTER).

    The connection kit includesan RS-485/RS-232 interfaceconverter with a 9-pin Sub-Dconnector.

    Start-up tools 

    • STARTERis a graphic start-up soft-ware for guided start-up for

    MICROMASTER 410/420/ 430/440 frequency invertersunder Windows NT/2000/ XP Professional. Parameterlists can be read out, al-tered, stored, entered andprinted.

    • DriveMonitoris a start-up software for list-oriented programming offrequency inverters. Thisprogram executes underWindows 98/NT/2000/ME/ XP Professional.

    ■ Selection and ordering data

    The options listed here aresuitable for allMICROMASTER 410 inverters.

    Options Order No.

    Operator Panel (OP)   6SE6400-0SP00-0AA0

    Connection kit for PC to inverter   6SE6400-0PL00-0AA0Adapter for mounting on DIN rails   6SE6400-0DR00-0AA0

    Start-up tools STARTER and DriveMonitor 2),as well as multilanguage documentation on CD-ROM

    6SE6400-5EA00-1AG0

    Start-up tool STARTER on CD-ROM 2)   6SL3072-0AA00-0AG0

    Type of documentation Language Order No.

    Operating instructions 1)

    (paper version)

    German   6SE6400-5EA00-0AP0

    English   6SE6400-5EA00-0BP0

    French   6SE6400-5EA00-0DP0

    Italian   6SE6400-5EA00-0CP0

    Spanish   6SE6400-5EA00-0EP0

    Parameter list 1)(paper version)

    German   6SE6400-5EB00-0AP0

    English   6SE6400-5EB00-0BP0

    French   6SE6400-5EB00-0DP0

    Italian   6SE6400-5EB00-0CP0

    Spanish   6SE6400-5EB00-0EP0

    Getting Started Guide 1)(paper version), included with every inverter

    Multilanguage –

    Inverter with Operator Panel (OP)

    Documentation

    1) Available on the Internet athttp://www.siemens.com/

    micromaster

    2) Available on the Internet:DriveMonitor at

    http://www4.ad.siemens.de/ WW/view/com/10804984/ 133100

    STARTER athttp://www4.ad.siemens.de/ 

    WW/view/com/10804985/ 133100

    OptionsVariant independent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    20/1251/10 Siemens DA 51.2 · 2005/2006

    MICROMASTER 410

    ■ MICROMASTER 410 inverter

    ■ Filters and chokes

          

                 

              

           

             

              

           

             

       

                

          

                   

    Inverter frame size AA6SE6410-2 . . 11-2AA06SE6410-2 . . 12-5AA06SE6410-2 . . 13-7AA0

    Inverter frame size AB6SE6410-2 . . 15-5BA06SE6410-2 . . 17-5BA0

          

                  

                 

           

       

          

              

          

              

              

             

                           

      

       

                              

      

          

                  

         

              

          

                 

           

          

                 

           

       

       

    All dimensions in mm (values in brackets are in inches)

    Inverter with flat plate heatsink 6SE6410-2 . B13-7AB06SE6410-2 . B17-5BB0

    Footprint chokes

    6SE6400-3CC00-4AB36SE6400-3CC01-0AB3

    Choke for upright mounting

    6SE6400-3CC02-6BB3

             

              

          

       

                

          

                     

       

                

          

                     

              

          

             

    All dimensions in mm (values in brackets are in inches)

                                   

                       

       

                       

          

                       

          

                       

          

    Filter

    6SE6400-2FL01-0AB0

    Dimension drawings

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    21/125Siemens DA 51.2 · 2005/2006   2/1

    InverterMICROMASTER 420

    2/2   Description

    2/4   Circuit diagrams

    2/6   Technical data

    2/8   Selection and ordering data

    2/9   Options

    2/18   Dimension drawings

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    22/1252/2 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ Applications   ■ Main characteristics   ■ Options (overview)   ■ International standards

    The MICROMASTER 420 in-verter is suitable for a varietyof variable-speed drive appli-cations. It is especially suit-able for applications withpumps, fans and in conveyor

    systems.

    It is the ideal cost-optimizedfrequency inverter solution.The inverter is especially char-acterized by its customer-ori-ented performance and ease-of-use. Its large mains voltagerange enables it to be used allover the world.

    ■ Design

    The MICROMASTER 420 in-verter has a modular design.The operator panels and com-munication modules can beeasily exchanged without re-quiring any tools.

    ■ Easy, guided start-up

    ■ Modular construction al-lows maximum configura-tion flexibility

    ■ Three fully programmable

    isolated digital inputs■ One analog input (0 V to

    10 V, scaleable) or for useas 4th digital input

    ■ One programmable analogoutput (0 mA to 20 mA)

    ■ One programmable relayoutput (30 V DC/5 A resis-tive load; 250 V AC/2A in-ductive load)

    ■ Low-noise motor operationthrough high pulse frequen-cy, adjustable (observe de-rating if necessary)

    ■ Complete protection formotor and inverter.

    ■ EMC filter, Class A/B

    ■ LC filter

    ■ Line commutating chokes

    ■ Output chokes

    ■ Gland plates

    ■ Basic Operator Panel(BOP) for parameterizingthe inverter

    ■ Advanced Operator Panel(AOP) with multi-languageplain text display

    ■ Asian Advanced OperatorPanel (AAOP) with Chineseand English plain text dis-play

    ■ Communication modules

    – PROFIBUS

    – DeviceNet

    – CANopen■ PC connection kits

    ■ Mounting kits for installingthe operator panels in thecontrol cabinet doors

    ■ PC start-up programs exe-cutable under Windows 98and NT/2000/ME/ XP Professional

    ■ TIA integration withDrive ES

    ■ The MICROMASTER 420inverter complies with therequirements of the EU low-voltage guideline

    ■ The MICROMASTER 420inverter has the> mark-ing

    ■ acc. to u and cu certified

    ■ c-tick ●✔

    Note:

    See Appendix for standards.

    Description

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    23/125Siemens DA 51.2 · 2005/2006   2/3

    MICROMASTER 420

    ■ Mechanical features   ■ Performance features   ■ Protection features

    ■ Modular design

    ■ Operating temperature–10 °C to +50 °C(+14 °F to +122 °F)

    ■ Compact housing as a re-sult of high power density

    ■ Easy cable connection,mains and motor connec-tions are separated for opti-mum electromagnetic com-patibility

    ■ Detachable operatorpanels

    ■ Screwless control terminals

    ■ Latest IGBT technology

    ■ Digital microprocessorcontrol

    ■ Flux Current Control (FCC)

    for improved dynamic re-sponse and optimized mo-tor control

    ■ Linear V/f  characteristic

    ■ Quadratic V/f  characteristic

    ■ Multipoint characteristic(programmable V/f  charac-teristic)

    ■ Flying restart

    ■ Slip compensation

    ■ Automatic restart followingmains failure or fault

    ■ Internal PI controller for sim-

    ple process control

    ■ Programmable accelera-tion/deceleration timesfrom 0 s to 650 s

    ■ Ramp smoothing

    ■ Fast Current Limit (FCL) fortrip-free operation

    ■ Fast, repeatable digital in-put response time

    ■ Fine adjustment using ahigh-resolution 10-bit ana-log input

    ■ Compound braking for con-trolled rapid braking

    ■ Four skip frequencies

    ■ Removable “Y” capacitorfor use on IT systems (withnon-grounded mains sup-plies, the “Y” capacitor

    must be removed and anoutput choke installed).

    ■ Overload current 1.5 x rat-ed output current (i.e.150 % overload capability)for 60 s, cycle time 300 s

    ■ Overvoltage/undervoltageprotection

    ■ Inverter overtemperatureprotection

    ■ Motor protection using PTCvia digital input (possiblewith supplementary circuit)

    ■ Earth fault protection

    ■ Short-circuit protection

    ■ I 2t  motor thermal protection

    ■ Locked motor protection

    ■ Stall prevention

    ■ Parameter interlock

    Description

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    24/1252/4 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ General circuit diagram

    PE

    SI

    PE L/L1, N/L2

    L/L1, N/L2, L3

    L1, L2, L3

    =

    3 ~

    PE U,V,W

    M

     A

    D

    +10 V

    0 V

    0 - 20 mA

    max. 500 Ω

    CPU

    RS485

    D

     A

    ~

    =

     ADC+

     ADC-

    DIN1

    DIN2

    DIN3

    DAC+

    DAC-

    P+

    N-

    RL1-B

    RL1-C

    1

    2

    3

    4

    5

    6

    7

    8

    9

    12

    13

    14

    15

    10

    11

    ≥ 4,7 kΩ

    DC+

    DC−

    DIN4

    2

    3

    4

    9

    24 V

     –+

    1 2

    60 Hz

    50 Hz

    150.00

    DIN1

    DIN2

    DIN3

    5

    6

    7

    9

    NPN

    PNP24 V

    +

     _ 

    BOP/AOP

    RS232

    1/3 AC 200 - 240 V3 AC 380 - 480 V

       G_

       D   A   5   1_

       E   N_

       0   0   0   1   1

    Not

    used

    Output 0 Vmax. 100 mA(isolated)

    30 V DC/5 A (resistive load)

    250 V AC/2 A (inductive load)

    Output +24 Vmax. 100 mA(isolated)

    or 

    or 

    automatic

    DC link

    The analog input can be used

    as an additional digital input

    (DIN4)

    DIP switch

    or 

    24 V external

    BOP link

    COM link

    Relay

    CB

    option

    Circuit diagrams

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    25/125Siemens DA 51.2 · 2005/2006 2/5

    MICROMASTER 420

    ■Terminal connection diagram

    5 7 86 9

    1 3 42

    10 11

    RL1-B RL1-C

    +10 V 0 V ADC+ ADC-

    12 14 1513

    DAC+ DAC- P+ N-

    DIN1 DIN2 DIN3 +24 V 0 V

    NPNPNP

    Output relayRL1

     Analog output RS-485(USS protocol)

    Voltagesupply 10 V

     Analog input

    Output relay contacts

    Digital inputs PNP or NPNpossible

    (isolated)

    G_DA51_EN_05106

    View A

    View A

    Mainsconnections

    Motorconnections

    DC linkterminals

    Example frame size A

    Circuit diagrams

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    26/1252/6 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ MICROMASTER 420 inverter

    Mains voltage andpower ranges

    1 AC 200 V to 240 V ± 10 %3 AC 200 V to 240 V ± 10 %3 AC 380 V to 480 V ± 10 %

    0.12 kW to 3 kW0.12 kW to 5.5 kW0.37 kW to 11 kW

    Power frequency 47 Hz to 63 Hz

    Output frequency 0 Hz to 650 HzPower factor    0.95

    Inverter efficiency 96 % to 97 %

    Overload capabil ity Overload current 1.5 x rated output current (i.e. 150 % overload capabil ity) for 60 s, cycle t ime 300 s

    Inrush current Less than rated input current

    Control method Linear V/f -characteristic; quadratic V/f  characteristic; multipoint characteristic(programmable V/f  characteristic); flux current control (FCC)

    Pulse frequency 16 kHz (standard with 1/3 AC 230 V)4 kHz (standard with 3 AC 400 V)2 kHz to 16 kHz (in 2 kHz steps)

    Fixed frequencies 7, programmable

    Skip frequency ranges 4, programmable

    Setpoint resolution 0.01 Hz digital0.01 Hz serial10 bit analog

    Digital inputs 3 fully programmable isolated digital inputs; switchable PNP/NPNAnalog input 1, for setpoint or PI controller (0 V to 10 V, scaleable or for use as 4th digital input)

    Relay outputs 1, programmable, 30 V DC/5 A (resistive load); 250 V AC/2A (inductive load)

    Analog output 1, programmable (0 mA to 20 mA)

    Serial interfaces RS-485, optional RS-232

    Motor cable lengthswithout output choke

    without output choke

    max. 50 m (shielded)max. 100 m (unshielded)see variant dependent options

    Electromagnetic compatibility Inverter available with internal EMC filter Class A;available as options are EMC filters to EN 55 011, Class A or Class B

    Braking DC braking, compound braking

    Degree of protection IP20

    Operating temperature –10 °C to +50 °C (+14 °F to +122 °F)

    Storage temperature –40 °C to +70 °C (–40 °F to +158 °F)

    Relative humidity 95 % (non-condensing)

    Site altitude Up to 1000 m above sea levelwithout derating

    Protection features for • Undervoltage• Overvoltage• Overload• Earth faults• Short circuit• Stall prevention• Locked motor protection• Motor overtemperature• Inverter overtemperature• Parameter interlock

    Compliance with standards u, cu,>, c-tick ●✔

    > marking Conformity with low-voltage directive 73/23/EEC

    Cooling-air volumetric flow required,

    dimensions and weights(without options)

    Frame size (FS)

    ABC

    Cooling-air volumetric

    flow required (l/s)/(CFM)4.8/10.224/5154.9/116.3

    H x W x D (mm)

    173 x 73 x 149202 x 149 x 172245 x 185 x 195

    Weight, approx. (kg)

    1.03.35.0

    CFM: Cubic Flow per Minute

    Technical data

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    27/125Siemens DA 51.2 · 2005/2006   2/7

    MICROMASTER 420

    ■ Derating data

    PWM frequency 

    Operating temperature 

    Installation height above sea level 

    Output(for 3 AC 400 V)

    Rated output current in Afor a pulse frequency of

    kW 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz

    0.37 1.2 1.2 1.2 1.2 1.2 1.2 1.1

    0.55 1.6 1.6 1.6 1.6 1.6 1.6 1.1

    0.75 2.1 2.1 2.1 2.1 1.6 1.6 1.1

    1.1 3.0 3.0 2.7 2.7 1.6 1.6 1.1

    1.5 4.0 4.0 2.7 2.7 1.6 1.6 1.1

    2.2 5.9 5.9 5.1 5.1 3.6 3.6 2.6

    3.0 7.7 7.7 5.1 5.1 3.6 3.6 2.6

    4.0 10.2 10.2 6.7 6.7 4.8 4.8 3.6

    5.5 13.2 13.2 13.2 13.2 9.6 9.6 7.5

    7.5 19.0 18.4 13.2 13.2 9.6 9.6 7.5

    11 26.0 26.0 17.9 17.9 13.5 13.5 10.4

                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        

     

    Permissible output currentin % of the rated output current

    2000

    60

    0 40000

    20

    40

    80

    DA51-5018c

    100

    1000

    %

    3000 m

       R  a   t  e   d  o  u   t  p  u   t  c  u  r  r  e  n   t

    Operational altitude

     A

    2000

    60

    0 40000

    20

    40

    80

    DA51-5019b

    100

    1000

    %

    3000 m

    77

       M  a   i  n  s  v  o   l   t  a  g  e

    Operational altitude

     A

    Permissible mains voltagein % of the max. possible mains voltage

    Technical data

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    28/1252/8 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ MICROMASTER 420 inverter

    Output Rated inputcurrent 1)

    Rated outputcurrent

    Frame size Order No.

    kW hp A A (FS)

    MICROMASTER 420without filter 3)

    MICROMASTER 420with internal filterClass A 2)

    Mains operating voltage 1 AC 200 V to 240 V

    0.12 0.16 1.8 0.9 A 6SE6420-2UC11-2AA1 6SE6420-2AB11-2AA1

    0.25 0.33 3.2 1.7 A   6SE6420-2UC12-5AA1 6SE6420-2AB12-5AA1

    0.37 0.50 4.6 2.3 A   6SE6420-2UC13-7AA1 6SE6420-2AB13-7AA1

    0.55 0.75 6.2 3.0 A   6SE6420-2UC15-5AA1 6SE6420-2AB15-5AA1

    0.75 1.0 8.2 3.9 A   6SE6420-2UC17-5AA1 6SE6420-2AB17-5AA1

    1.1 1.5 11.0 5.5 B   6SE6420-2UC21-1BA1 6SE6420-2AB21-1BA1

    1.5 2.0 14.4 7.4 B   6SE6420-2UC21-5BA1 6SE6420-2AB21-5BA1

    2.2 3.0 20.2 10.4 B   6SE6420-2UC22-2BA1 6SE6420-2AB22-2BA1

    3.0 4.0 35.5 13.6 C   6SE6420-2UC23-0CA1 6SE6420-2AB23-0CA1

    Mains operating voltage 3 AC 200 V to 240 V

    0.12 0.16 1.1 0.9 A   6SE6420-2UC11-2AA1 –

    0.25 0.33 1.9 1.7 A   6SE6420-2UC12-5AA1 –

    0.37 0.50 2.7 2.3 A   6SE6420-2UC13-7AA1 –

    0.55 0.75 3.6 3.0 A   6SE6420-2UC15-5AA1 –

    0.75 1.0 4.7 3.9 A   6SE6420-2UC17-5AA1 –

    1.1 1.5 6.4 5.5 B   6SE6420-2UC21-1BA1 –

    1.5 2.0 8.3 7.4 B   6SE6420-2UC21-5BA1 –

    2.2 3.0 11.7 10.4 B   6SE6420-2UC22-2BA1 –

    3.0 4.0 15.6 13.6 C   6SE6420-2UC23-0CA1 6SE6420-2AC23-0CA1

    4.0 5.0 19.7 17.5 C   6SE6420-2UC24-0CA1 6SE6420-2AC24-0CA1

    5.5 7.5 26.5 22.0 C   6SE6420-2UC25-5CA1 6SE6420-2AC25-5CA1

    Mains operating voltage 3 AC 380 V to 480 V

    0.37 0.50 2.2 1.2 A   6SE6420-2UD13-7AA1 –

    0.55 0.75 2.8 1.6 A   6SE6420-2UD15-5AA1 –0.75 1.0 3.7 2.1 A   6SE6420-2UD17-5AA1 –

    1.1 1.5 4.9 3.0 A   6SE6420-2UD21-1AA1 –

    1.5 2.0 5.9 4.0 A   6SE6420-2UD21-5AA1 –

    2.2 3.0 7.5 5.9 B   6SE6420-2UD22-2BA1 6SE6420-2AD22-2BA1

    3.0 4.0 10.0 7.7 B   6SE6420-2UD23-0BA1 6SE6420-2AD23-0BA1

    4.0 5.0 12.8 10.2 B   6SE6420-2UD24-0BA1 6SE6420-2AD24-0BA1

    5.5 7.5 15.6 13.2 C   6SE6420-2UD25-5CA1 6SE6420-2AD25-5CA1

    7.5 10.0 22.0 19.0 C   6SE6420-2UD27-5CA1 6SE6420-2AD27-5CA1

    11 15.0 32.3 26.0 C   6SE6420-2UD31-1CA1 6SE6420-2AD31-1CA1

    See Appendix for note on or-dering.

    All MICROMASTER 420 invert-ers are supplied with a StatusDisplay Panel (SDP). A BOP,AOP or other options have tobe ordered separately (seePages 2/12 to 2/16).

    ■ Motors forMICROMASTER 420

    Catalog M 11 contains selec-tion and ordering data for mo-tors which are particularly suit-able for operation with theMICROMASTER 420 inverters(see Appendix for overview).

    This catalog is suitable for IECmotors. For motors accordingto US standards (NEMA)

    please refer to:http://www.sea.siemens.com/ motors

    1) Supplementary conditions:Input current at rated operating

    point, applicable at short-circuit voltage of the supplyU sc = 2 % with reference to the

    inverter rated power and ratedmains voltage of 240 V or 400 V

    without a line commutatingchoke.

    2) Use of MICROMASTER invert-ers with internal filter is not per-

    missible on non-grounded (IT)mains supplies.

    3) Generally suited to heavyindustrial applications. For

    details please refer to Appen-dix on page A/4.

    Selection and ordering data

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    29/125Siemens DA 51.2 · 2005/2006   2/9

    MICROMASTER 420

    ■ Overview

    EMC filter, Class A

    Filter for inverters without aninternal filter for

    – 3 AC 200 V to 240 V,

    frame sizes A and B

    – 3 AC 380 V to 480 V,frame size A.

    All other inverters can be sup-plied with an internal Class Afilter.

    The requirements are fulfilledusing shielded cables with amax. length of 25 m.

    EMC filter, Class B 

    Filter for inverters without aninternal filter for

    – 3 AC 200 V to 240 V,frame sizes A and B

    – 3 AC 380 V to 480 V,frame size A.

    With this filter, the invertercomplies with the emissionstandard EN 55 011, Class B.

    The requirements are fulfilledusing shielded cables with amax. length of 25 m.

    Additional EMC filter,Class B 

    Available for inverters with aninternal Class A EMC filter.

    With this filter, the invertercomplies with the emissionstandard EN 55 011, Class B.

    The requirements are fulfilledusing shielded cables with amax. length of 25 m.

    Filter Class B with lowleakage currents 

    EMC filter for 1 AC 200 V to240 V inverters, frame sizes A

    and B, without an internal EMCfilter Class A.

    With this filter, the invertercomplies with the emissionstandard EN 55 011, Class B.The leakage currents are re-duced to < 3.5 mA.

    The requirements are fulfilledusing shielded cables with amax. length of 5 m.

    Leakage currents:

    The leakage currents of the in-verters with/without filter (inter-

    nal/external) may exceed30 mA. Typical values in prac-tice are between 10 mA and50 mA. The exact values de-pend on the design, environ-ment and cable lengths. Inter-ference-free operation with re-sidual current operated devic-es with a trigger value of30 mA cannot be guaranteed.However, operation with resid-ual current circuit-breakerswith a trigger value of 300 mAis possible. Please refer to theInstruction Manual for details.

    LC filter 

    The LC filter limits the rate ofrise of voltage and the capac-itive charge/discharge cur-

    rents which usually occur withinverter operation. This meansthat much longer shielded mo-tor cables are possible whenusing LC filters and the ser-vice life of the motor achievesvalues similar to those withdirect mains operation.Use of an output choke isn’trequired with that.

    Please note when usingLC filters:

    • Only V/f , FCC control per-missible

    • Please observe the deratingof 15 % when selecting theappropriate inverter

    • Operation only permissiblewith 4 kHz pulse frequency

    • The output frequency is lim-ited to 150 Hz.

    The LC filters can be used forall MICROMASTER 420 invert-ers of frame sizes A to C.

    Line commutating choke 

    Line commutating chokesare used to smooth voltagepeaks or to bridge commutat-ing dips. In addition, line com-mutating chokes reduce theeffects of harmonics on the in-verter and the power supply. Ifthe line impedance is 1 kW which means that theinverters with an output power

    0.75 kW comply with theEN 61 000-3-2 standard.

    Output choke 

    Output chokes can be sup-plied for reducing the capaci-tive currents and dV  /dt  in thecase of motor cables > 50 m(shielded) or > 100 m (un-shielded).

    For max. permissible cablelengths, see Technical Data.

    Gland plate 

    The gland plate facilitates theshield connection of powerand control cables and en-sures optimum EMC perfor-mance.

    OptionsVariant dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    30/1252/10 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ Technical data

    LC filter 

    Max. permissible cable lengths from the motor to the inverter when using output chokes 

    Mains voltage 3 AC 380 V to 480 V

    Current (at 40 °C/50 °C) for frame size A

    for frame size Bfor frame size C

    4.5 A/ 4.1 A

    11.2 A/10.2 A32.6 A/29.7 A

    Limiting of motor overvoltage    1078 V

    dV  /dt  limiting    500 V/  s

    Pulse frequency 4 kHz

    Max. motor frequency 150 Hz

    Max. permissible motor cablelengths

    shieldedunshielded

    200 m300 m

    Insulation strength Overvoltage category III to VDE 0110

    Electromagnetic compatibility Up to 200 m motor cable length with emissions to Class A according to EN 55 011 inconjunction with filtered inverters and unshielded cables

    Conformity CE according to the low-voltage directive 73/23/EEC

    Approvals UL available soon

    Strain resistance EN 60 068-2-31

    Humidity 95 % humidity, non-condensing

    Degree of protection IP20 (to EN 60529)

    Insulation class H (180 °C)

    Permissible temperature Operation

    Storage

    –10 °C to +40 °C (+14 °F to +104 °F) 100 % P nto +50 °C (to +122 °F) 80 % P n

    –25 °C to +70 °C (–13 °F to +158 °F)

    Operational altitude up to 2000 m2000 to 4000 m

    100 % P n62.5 % P n

    Mounting position Footprint or suspended

    Free space TopBottom

    Side

    100 mm100 mm100 mm

    Connection system Input, l itz wire or terminalOutput, terminals

    1U1, 1V1, 1W11U2, 1V2, 1W2

    Torque for power conductor connections 1.5 Nm to 1.8 Nm

    Weight, approx. for frame size A

    for frame size Bfor frame size C

    7 kg

    11 kg29 kg

    The following table shows themaximum permissible cablelengths from the motor to theinverter when using outputchokes.

    Frame size Output choke   Max. permissible motor cable lengths (shielded/unshielded)for a mains voltage of

    (FS) Type 200 V to 240 V ± 10 % 380 V to 400 V ± 10 % 401 V to 480 V ± 10 %

    A 6SE6400-3TC00-4AD3 200 m/300 m – –

    A 6SE6400-3TC00-4AD2 200 m/300 m 150 m/225 m 100 m/150 m

    B 6SE6400-3TC01-0BD3 200 m/300 m 150 m/225 m 100 m/150 m

    C 6SE6400-3TC03-2CD3 200 m/300 m 200 m/300 m 100 m/150 m

    OptionsVariant dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    31/125Siemens DA 51.2 · 2005/2006   2/11

    MICROMASTER 420

    ■ Design

    General installation instructions 

    Availability of the options as footprint components 

    Recommended combinations of inverters and options 

    ■ A maximum of two footprintcomponents plus inverterare permissible.

    ■ If an LC filter is used, it mustbe mounted directly on thewall of the control cabinetdue to weight reasons.If an LC filter of frame size Cis used, therefore, only onefootprint component is per-missible. If a line choke andLC filter are used, the linechoke must be located onthe left of the inverter.Required spacing: 75 mm.

    ■ The EMC filter must bemounted directly below thefrequency inverter if pos-

    sible.

    ■ If mounted on the side, theline-side components are tobe mounted to the left of thefrequency inverter whereasthe output-side compon-ents are to be mounted tothe right of the frequencyinverter.

    Frame size

    A B C

    Line commutating choke   ✓ ✓ ✓

    EMC filter   ✓ ✓ ✓

    LC filter   ✓ ✓ ✓

    Output choke   ✓ ✓ ✓

    Frequency inverter Footprint Mounted on side

    Frame size Position 1 Position 2 To the left of the inverter(for line-side components)

    To the right of the inverter(for output-side compon-ents)

    A and B EMC filter Line commutating choke – Output choke

    EMC filter orLine commutating choke

    Output choke orLC filter

    – –

    C EMC filter Line commutating choke – Output choke

    EMC filter or

    Line commutating choke

    Output choke – –

    LC filter – EMC filter and/orLine commutating choke

       

                

          

                      

    Example of installation with frequency inverter,EMC filter (position 1) and line choke (position 2)

    OptionsVariant dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    32/1252/12 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ Selection and ordering data

    The options listed here (filters,chokes, gland plates, fuses,and circuit-breakers) must beselected to match the inverter.

    The inverter and the associat-ed options have the same volt-age ratings.

    All options are certified tou, except fuses.The fuses of Type 3NA3 arerecommended for Europe.

    Use in America requires u-listed fuses such as the ClassNON range from Bussmann.

    Mains voltage Output

    kW hp

    Inverterwithout filter

    Order No. of the options

    EMC filterClass A

    EMC filterClass B

    Additional EMC filter,Class B

    1 AC 200 V to 240 V 0.12 0.16 6SE6420-2UC11-2AA1 –   6SE6400-2FL01-0AB0with low leakagecurrents

    0.25 0.33 6SE6420-2UC12-5AA1 – –

    0.37 0.50 6SE6420-2UC13-7AA1 – –

    0.55 0.75 6SE6420-2UC15-5AA1 – –

    0.75 1.0 6SE6420-2UC17-5AA1 – –

    1.1 1.5 6SE6420-2UC21-1BA1 –   6SE6400-2FL02-6BB0with low leakagecurrents

    1.5 2.0 6SE6420-2UC21-5BA1 – –

    2.2 3.0 6SE6420-2UC22-2BA1 – –

    3.0 4.0 6SE6420-2UC23-0CA1 – – –

    3 AC 200 V to 240 V 0.12 0.16 6SE6420-2UC11-2AA1   6SE6400-2FA00-6AD0 6SE6400-2FB00-6AD0 –0.25 0.33 6SE6420-2UC12-5AA1 –

    0.37 0.50 6SE6420-2UC13-7AA1 –

    0.55 0.75 6SE6420-2UC15-5AA1 –

    0.75 1.0 6SE6420-2UC17-5AA1 –

    1.1 1.5 6SE6420-2UC21-1BA1   6SE6400-2FA01-4BC0 6SE6400-2FB01-4BC0 –

    1.5 2.0 6SE6420-2UC21-5BA1 –

    2.2 3.0 6SE6420-2UC22-2BA1 –

    3.0 4.0 6SE6420-2UC23-0CA1 – – –

    4.0 5.0 6SE6420-2UC24-0CA1 – – –

    5.5 7.5 6SE6420-2UC25-5CA1 – – –

    3 AC 380 V to 480 V 0.37 0.50 6SE6420-2UD13-7AA1   6SE6400-2FA00-6AD0 6SE6400-2FB00-6AD0 –

    0.55 0.75 6SE6420-2UD15-5AA1 –

    0.75 1.0 6SE6420-2UD17-5AA1 –

    1.1 1.5 6SE6420-2UD21-1AA1 –

    1.5 2.0 6SE6420-2UD21-5AA1 –

    2.2 3.0 6SE6420-2UD22-2BA1 – – –

    3.0 4.0 6SE6420-2UD23-0BA1 – – –

    4.0 5.0 6SE6420-2UD24-0BA1 – – –

    5.5 7.5 6SE6420-2UD25-5CA1 – – –

    7.5 10.0 6SE6420-2UD27-5CA1 – – –

    11 15.0 6SE6420-2UD31-1CA1 – – –

    Inverterwith internal filter Class A

    1 AC 200 V to 240 V 0.12 0.16 6SE6420-2AB11-2AA1 – –   6SE6400-2FS01-0AB0

    0.25 0.33 6SE6420-2AB12-5AA1 – –

    0.37 0.50 6SE6420-2AB13-7AA1 – –

    0.55 0.75 6SE6420-2AB15-5AA1 – –

    0.75 1.0 6SE6420-2AB17-5AA1 – –

    1.1 1.5 6SE6420-2AB21-1BA1 – –   6SE6400-2FS02-6BB0

    1.5 2.0 6SE6420-2AB21-5BA1 – –

    2.2 3.0 6SE6420-2AB22-2BA1 – –

    3.0 4.0 6SE6420-2AB23-0CA1 – –   6SE6400-2FS03-5CB0

    3 AC 200 V to 240 V 3.0 4.0 6SE6420-2AC23-0CA1 – –   6SE6400-2FS03-8CD0

    4.0 5.0 6SE6420-2AC24-0CA1 – –

    5.5 7.5 6SE6420-2AC25-5CA1 – –

    3 AC 380 V to 480 V 2.2 3.0 6SE6420-2AD22-2BA1 – –   6SE6400-2FS01-6BD0

    3.0 4.0 6SE6420-2AD23-0BA1 – –

    4.0 5.0 6SE6420-2AD24-0BA1 – –

    5.5 7.5 6SE6420-2AD25-5CA1 – –   6SE6400-2FS03-8CD0

    7.5 10.0 6SE6420-2AD27-5CA1 – –

    11 15.0 6SE6420-2AD31-1CA1 – –

    OptionsVariant dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    33/125Siemens DA 51.2 · 2005/2006   2/13

    MICROMASTER 420

    ■ Selection and ordering data (continued)

    Mains voltage Output

    kW hp

    Inverterwithout filter

    Order No. of the options

    Line commutatingchoke

    LC filter Output choke

    1 AC 200 V to 240 V 0.12 0.16 6SE6420-2UC11-2AA1   6SE6400-3CC00-4AB3 –   6SE6400-3TC00-4AD3

    0.25 0.33 6SE6420-2UC12-5AA1 –

    0.37 0.50 6SE6420-2UC13-7AA1   6SE6400-3CC01-0AB3 –

    0.55 0.75 6SE6420-2UC15-5AA1 –

    0.75 1.0 6SE6420-2UC17-5AA1 –

    1.1 1.5 6SE6420-2UC21-1BA1   6SE6400-3CC02-6BB3 –   6SE6400-3TC01-0BD3

    1.5 2.0 6SE6420-2UC21-5BA1 –

    2.2 3.0 6SE6420-2UC22-2BA1 –

    3.0 4.0 6SE6420-2UC23-0CA1   6SE6400-3CC03-5CB3 –   6SE6400-3TC03-2CD3

    3 AC 200 V to 240 V 0.12 0.16 6SE6420-2UC11-2AA1   6SE6400-3CC00-3AC3 –   6SE6400-3TC00-4AD30.25 0.33 6SE6420-2UC12-5AA1 –

    0.37 0.50 6SE6420-2UC13-7AA1   6SE6400-3CC00-5AC3 –

    0.55 0.75 6SE6420-2UC15-5AA1 –

    0.75 1.0 6SE6420-2UC17-5AA1 –

    1.1 1.5 6SE6420-2UC21-1BA1   6SE6400-3CC00-8BC3 –   6SE6400-3TC01-0BD3

    1.5 2.0 6SE6420-2UC21-5BA1   6SE6400-3CC01-4BD3 –

    2.2 3.0 6SE6420-2UC22-2BA1 –

    3.0 4.0 6SE6420-2UC23-0CA1   6SE6400-3CC01-7CC3 –   6SE6400-3TC03-2CD3

    4.0 5.0 6SE6420-2UC24-0CA1   6SE6400-3CC03-5CD3 –

    5.5 7.5 6SE6420-2UC25-5CA1 –

    3 AC 380 V to 480 V 0.37 0.50 6SE6420-2UD13-7AA1   6SE6400-3CC00-2AD3 6SE6400-3TD00-4AD0 6SE6400-3TC00-4AD2

    0.55 0.75 6SE6420-2UD15-5AA1

    0.75 1.0 6SE6420-2UD17-5AA1   6SE6400-3CC00-4AD3

    1.1 1.5 6SE6420-2UD21-1AA1

    1.5 2.0 6SE6420-2UD21-5AA1   6SE6400-3CC00-6AD3

    2.2 3.0 6SE6420-2UD22-2BA1   6SE6400-3CC01-0BD3 6SE6400-3TD01-0BD0 6SE6400-3TC01-0BD3

    3.0 4.0 6SE6420-2UD23-0BA1

    4.0 5.0 6SE6420-2UD24-0BA1   6SE6400-3CC01-4BD3

    5.5 7.5 6SE6420-2UD25-5CA1   6SE6400-3CC02-2CD3 6SE6400-3TD03-2CD0 6SE6400-3TC03-2CD3

    7.5 10.0 6SE6420-2UD27-5CA1

    11 15.0 6SE6420-2UD31-1CA1   6SE6400-3CC03-5CD3

    Inverterwith internal filter Class A

    1 AC 200 V to 240 V 0.12 0.16 6SE6420-2AB11-2AA1   6SE6400-3CC00-4AB3 –   6SE6400-3TC00-4AD3

    0.25 0.33 6SE6420-2AB12-5AA1 –

    0.37 0.50 6SE6420-2AB13-7AA1   6SE6400-3CC01-0AB3 –

    0.55 0.75 6SE6420-2AB15-5AA1 –

    0.75 1.0 6SE6420-2AB17-5AA1 –

    1.1 1.5 6SE6420-2AB21-1BA1   6SE6400-3CC02-6BB3 –   6SE6400-3TC01-0BD3

    1.5 2.0 6SE6420-2AB21-5BA1 –

    2.2 3.0 6SE6420-2AB22-2BA1 –

    3.0 4.0 6SE6420-2AB23-0CA1   6SE6400-3CC03-5CB3 –   6SE6400-3TC03-2CD3

    3 AC 200 V to 240 V 3.0 4.0 6SE6420-2AC23-0CA1   6SE6400-3CC01-7CC3 –   6SE6400-3TC03-2CD3

    4.0 5.0 6SE6420-2AC24-0CA1   6SE6400-3CC03-5CD3 –

    5.5 7.5 6SE6420-2AC25-5CA1 –

    3 AC 380 V to 480 V 2.2 3.0 6SE6420-2AD22-2BA1   6SE6400-3CC01-0BD3 6SE6400-3TD01-0BD0 6SE6400-3TC01-0BD3

    3.0 4.0 6SE6420-2AD23-0BA1

    4.0 5.0 6SE6420-2AD24-0BA1   6SE6400-3CC01-4BD3

    5.5 7.5 6SE6420-2AD25-5CA1   6SE6400-3CC02-2CD3 6SE6400-3TD03-2CD0 6SE6400-3TC03-2CD3

    7.5 10.0 6SE6420-2AD27-5CA1

    11 15.0 6SE6420-2AD31-1CA1   6SE6400-3CC03-5CD3

    OptionsVariant dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    34/1252/14 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ Selection and ordering data (continued)

    Mains voltage Output

    kW hp

    Inverterwithout filter

    Order No. of the options

    Gland plate Fuse(see Catalog LV10)

    Circuit-breaker

    1 AC 200 V to 240 V 0.12 0.16 6SE6420-2UC11-2AA1   6SE6400-0GP00-0AA0 3NA3803 3RV1021-1DA10

    0.25 0.33 6SE6420-2UC12-5AA1   3RV1021-1GA10

    0.37 0.50 6SE6420-2UC13-7AA1   3RV1021-1HA10

    0.55 0.75 6SE6420-2UC15-5AA1   3RV1021-1JA10

    0.75 1.0 6SE6420-2UC17-5AA1   3NA3805 3RV1021-4AA10

    1.1 1.5 6SE6420-2UC21-1BA1   6SE6400-0GP00-0BA0 3NA3807 3RV1021-4BA10

    1.5 2.0 6SE6420-2UC21-5BA1   3RV1021-4DA10

    2.2 3.0 6SE6420-2UC22-2BA1   3NA3812 3RV1031-4FA10

    3.0 4.0 6SE6420-2UC23-0CA1   6SE6400-0GP00-0CA0 3NA3817 3RV1031-4HA10

    3 AC 200 V to 240 V 0.12 0.16 6SE6420-2UC11-2AA1   6SE6400-0GP00-0AA0 3NA3803 3RV1021-1AA100.25 0.33 6SE6420-2UC12-5AA1   3RV1021-1DA10

    0.37 0.50 6SE6420-2UC13-7AA1   3RV1021-1EA10

    0.55 0.75 6SE6420-2UC15-5AA1   3RV1021-1GA10

    0.75 1.0 6SE6420-2UC17-5AA1   3RV1021-1HA10

    1.1 1.5 6SE6420-2UC21-1BA1   6SE6400-0GP00-0BA0 3NA3805 3RV1021-1KA10

    1.5 2.0 6SE6420-2UC21-5BA1   3RV1021-4AA10

    2.2 3.0 6SE6420-2UC22-2BA1   3NA3807 3RV1021-4BA10

    3.0 4.0 6SE6420-2UC23-0CA1   6SE6400-0GP00-0CA0 3NA3810 3RV1021-4CA10

    4.0 5.0 6SE6420-2UC24-0CA1   3NA3812 3RV1031-4EA10

    5.5 7.5 6SE6420-2UC25-5CA1   3NA3814 3RV1031-4FA10

    3 AC 380 V to 480 V 0.37 0.50 6SE6420-2UD13-7AA1   6SE6400-0GP00-0AA0 3NA3803 3RV1021-1CA10

    0.55 0.75 6SE6420-2UD15-5AA1   3RV1021-1DA10

    0.75 1.0 6SE6420-2UD17-5AA1   3RV1021-1EA10

    1.1 1.5 6SE6420-2UD21-1AA1   3RV1021-1GA10

    1.5 2.0 6SE6420-2UD21-5AA1   3RV1021-1HA10

    2.2 3.0 6SE6420-2UD22-2BA1   6SE6400-0GP00-0BA0 3NA3805 3RV1021-1JA10

    3.0 4.0 6SE6420-2UD23-0BA1   3RV1021-1KA10

    4.0 5.0 6SE6420-2UD24-0BA1   3NA3807 3RV1021-4AA10

    5.5 7.5 6SE6420-2UD25-5CA1   6SE6400-0GP00-0CA0 3RV1021-4CA10

    7.5 10.0 6SE6420-2UD27-5CA1   3NA3810 3RV1031-4EA10

    11 15.0 6SE6420-2UD31-1CA1   3NA3814 3RV1031-4GA10

    Inverterwith internal filter Class A

    1 AC 200 V to 240 V 0.12 0.16 6SE6420-2AB11-2AA1   6SE6400-0GP00-0AA0 3NA3803 3RV1021-1DA10

    0.25 0.33 6SE6420-2AB12-5AA1   3RV1021-1GA10

    0.37 0.50 6SE6420-2AB13-7AA1   3RV1021-1HA10

    0.55 0.75 6SE6420-2AB15-5AA1   3RV1021-1JA10

    0.75 1.0 6SE6420-2AB17-5AA1   3NA3805 3RV1021-4AA10

    1.1 1.5 6SE6420-2AB21-1BA1   6SE6400-0GP00-0BA0 3NA3807 3RV1021-4BA10

    1.5 2.0 6SE6420-2AB21-5BA1   3RV1021-4DA10

    2.2 3.0 6SE6420-2AB22-2BA1   3NA3812 3RV1031-4FA10

    3.0 4.0 6SE6420-2AB23-0CA1   6SE6400-0GP00-0CA0 3NA3817 3RV1031-4HA10

    3 AC 200 V to 240 V 3.0 4.0 6SE6420-2AC23-0CA1   6SE6400-0GP00-0CA0 3NA3810 3RV1021-4CA10

    4.0 5.0 6SE6420-2AC24-0CA1   3NA3812 3RV1031-4EA10

    5.5 7.5 6SE6420-2AC25-5CA1   3NA3814 3RV1031-4FA10

    3 AC 380 V to 480 V 2.2 3.0 6SE6420-2AD22-2BA1   6SE6400-0GP00-0BA0 3NA3805 3RV1021-1JA10

    3.0 4.0 6SE6420-2AD23-0BA1   3RV1021-1KA10

    4.0 5.0 6SE6420-2AD24-0BA1   3NA3807 3RV1021-4AA10

    5.5 7.5 6SE6420-2AD25-5CA1   6SE6400-0GP00-0CA0 3RV1021-4CA10

    7.5 10.0 6SE6420-2AD27-5CA1   3NA3810 3RV1031-4EA10

    11 15.0 6SE6420-2AD31-1CA1   3NA3814 3RV1031-4GA10

    OptionsVariant dependent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    35/125Siemens DA 51.2 · 2005/2006   2/15

    MICROMASTER 420

    ■ Overview

    Basic Operator Panel (BOP) 

    With the BOP, individual pa-rameter settings can be made.Values and units are shown on

    a 5-digit display.

    Basic Operator Panel (BOP)

    A BOP can be used for severalinverters. It can be directlymounted on the inverter or in acontrol cabinet door using amounting kit.

    Advanced Operator Panel(AOP) 

    The AOP enables parameterkits to be read out of the invert-er or to be written into the in-verter (upload/download) Dif-

    ferent parameter kits can bestored in the AOP. It has aplain text display with the pos-sibility of switching betweenseveral languages.

    Advanced Operator Panel (AOP)

    Up to 30 inverters can be con-trolled from an AOP via USS. Itcan be directly mounted onthe inverter or in a control cab-inet door using a mounting kit.

    Asian Advanced OperatorPanel (AAOP) 

    The AAOP is the Chinese ver-sion of the AOP operator pan-

    el. It has an enhanced displayand supports the operatinglanguages of Chinese (simpli-fied) and English.

    Asian Advanced Operator Panel(AAOP)

    PROFIBUS module 

    For a complete PROFIBUSconnection with up to

    12 Mbaud. Remote controlof the inverter is possible withthe PROFIBUS module. Re-mote control and operation atthe inverter can be combinedusing an operator panelplugged onto the PROFIBUSmodule. The PROFIBUS mod-ule can be supplied by an ex-ternal 24 V DC power supplyand is thus also active whenthe inverter is disconnectedfrom the power supply.

    Connection by means of a9-pin Sub-D connector (avail-able as an option).

    DeviceNet module 

    For networking the inverters tothe DeviceNet fieldbus systemwidely used on the American

    market. A maximum transmis-sion rate of 500 Kbaud is pos-sible. Remote control of the in-verter is possible with the De-viceNet module. Remote con-trol and operation at the invert-er can be combined using anoperator panel plugged ontothe DeviceNet module.

    The connection to the De-viceNet bus system is madeusing a 5-pin connector withterminal strip.

    CANopen module Using the CANopen commu-nications module, an invertercan be linked to the CANopenfieldbus system and remotecontrol is then possible.

    Remote control and operationat the inverter can be com-bined using an operator panelplugged onto the CANopenmodule.

    The module is connected tothe bus system through a9-pin Sub-D connector.

    Connection kit forPC to inverter 

    For controlling an inverter di-rectly from a PC if the appro-priate software has been in-stalled (e.g. STARTER).Isolated RS-232 adapter mod-ule for reliable point-to-pointconnection to a PC. Includes aSub-D connector and anRS-232 standard cable (3 m).

    Connection kit for PCto AOP 

    For connecting a PC to anAOP or AAOP. Offline pro-

    gramming of inverters and ar-chiving of parameter kits pos-sible. Includes a desktop at-tachment kit for an AOP orAAOP, an RS-232 standardcable (3 m) with Sub-D con-nectors and a universal powersupply unit.

    Operator panel door mount- ing kit for single inverter 

    For mounting an operator pan-el in a control cabinet door.Degree of protection IP56.

    Contains a cable adaptermodule with screwless termi-nals for use with user’s ownRS-232-cables 1).

    AOP door mounting kit formultiple inverters (USS) 

    For mounting an AOP or AAOPin a control cabinet door.Degree of protection IP56. TheAOP or AAOP can communi-cate with several inverters bymeans of the RS-485 USSprotocol. The 4-pin connect-ing cable from the AOP orAAOP to the RS-485 terminalsof the inverter and to the 24 Vuser terminal strip is notincluded 2).

    Start-up tools 

    • STARTERis a graphic start-up soft-ware for guided start-up forMICROMASTER 410/420/ 430/440 frequency invertersunder Windows NT/2000/XPProfessional. Parameter listscan be read out, altered,

    stored, entered and printed.

    • DriveMonitoris a start-up software for list-oriented programming offrequency inverters. Thisprogram executes underWindows 98/NT/2000/ME/ XP Professional.

    Both programs are includedon the Docu CD which is pro-vided with every inverter.

    1) A shielded cable of typeBelden 8132 (28 AWG) is

    recommended. The maximumcable length is 5 m for RS-232.

    2) A shielded cable of typeBelden 8132 (28 AWG) is

    recommended. The maximumcable length is 10 m forRS-485.

    OptionsVariant independent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    36/1252/16 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ Selection and ordering data

    ■ Technical data of the communication modules

    The options listed here aresuitable for allMICROMASTER 420 inverters.

    Options Order No.

    Basic Operator Panel (BOP)   6SE6400-0BP00-0AA0

    Advanced Operator Panel (AOP)   6SE6400-0AP00-0AA1

    Asian Advanced Operator Panel (AAOP)   6SE6400-0AP00-0AB0

    PROFIBUS module   6SE6400-1PB00-0AA0

    DeviceNet module   6SE6400-1DN00-0AA0

    CANopen module   6SE6400-1CB00-0AA0

    RS485/PROFIBUS bus connector   6GK1500-0FC00

    Connection kit for PC to inverter   6SE6400-1PC00-0AA0

    Connection kit for PC to AOP   6SE6400-0PA00-0AA0

    Operator panel door mounting kit for single inverter   6SE6400-0PM00-0AA0

    AOP door mounting kit for multiple inverters (USS)   6SE6400-0MD00-0AA0

    Start-up tool STARTER on CD-ROM   6SL3072-0AA00-0AG0 Available on the Internet at:http://www4.ad.siemens.de/WW/view/com/10804985/133100

    PROFIBUS module6SE6400-1PB00-0AA0

    DeviceNet module6SE6400-1DN00-0AA0

    Size (height x width x depth) 161 mm x 73 mm x 46 mm

    Degree of protection IP20

    Degree of pollution 2 to IEC 60 664-1 (DIN VDE 0110/T1), no condensation permitted during operation

    Strain resistance• Stationary

    • Transport

    DeflectionAccelerationDeflectionAcceleration

    to DIN IEC 60 068-2-6 (if module is installed correctly)0.15 mm in the frequency range of 10 Hz to 58 Hz19.6 m/s2 in the frequency range of 58 Hz to 500 Hz3.5 mm in the frequency range of 5 Hz to 9 Hz9.8 m/s2 in the frequency range of 9 Hz to 500 Hz

    Climatic category (during operation) 3K3 to DIN IEC 60 721-3-3

    Cooling method Natural air coolingPermissible ambient or cooling agent temperature• Operation• Storage and transport

    –10 °C to +50 °C (+14 °F to +122 °F)–25 °C to +70 °C (–13 °F to +158 °F)

    Relative humidity(permissible humidity rating)• Operation• Storage and transport

     85 % (non-condensing) 95 %

    Electromagnetic compatibility EmissionInterference

    to EN 55 011 (1991) Class Ato IEC 60 801-3 and EN 61 000-4-3

    Power supply 6.5 V ± 5 %, max. 300 mA,internal from inverter or24 V ± 10 %, max. 350 mA, external

    6.5 V ± 5 %, max. 300 mAinternal from inverter or24 V, max. 60 mA from DeviceNet-Bus

    Output voltage 5 V ± 10 %, max. 100 mA,galvanically isolated supply• for terminating the serial interface bus or• for supplying the OLP (Optical Link Plug)

    Data transmission rate max. 12 Mbaud 125, 250 and 500 Kbaud

    OptionsVariant independent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    37/125Siemens DA 51.2 · 2005/2006   2/17

    MICROMASTER 420

    ■ Technical data of the communication modules (continued)

    ■ Selection and ordering data

    CANopen module6SE6400-1CB00-0AA0

    Size (height x width x depth) 161 mm x 73 mm x 46 mm

    Degree of protection IP20

    Degree of pollution 2 to IEC 60 664-1 (DIN VDE 0110/T1), no condensation permitted during operation

    Strain resistance• Stationary

    • Transport

    DeflectionAccelerationDeflectionAcceleration

    to IEC 60 068-2-6 (if module is installed correctly)0.15 mm in the frequency range of 10 Hz to 58 Hz19.6 m/s2 in the frequency range of 58 Hz to 500 Hz3.5 mm in the frequency range of 5 Hz to 9 Hz9.8 m/s2 in the frequency range of 9 Hz to 500 Hz

    Climatic category (during operation) 3K3 to DIN IEC 60 721-3-3

    Cooling method Natural air cooling

    Permissible ambient or cooling agent temperature• Operation• Storage• Transport

    –10 °C to +50 °C (+14 °F to +122 °F)–40 °C to +70 °C (–40 °F to +158 °F)–25 °C to +70 °C (–13 °F to +158 °F)

    Relative humidity(permissible humidity rating)• Operation• Storage and transport

     85 % (non-condensing) 95 %

    Power supply The CAN bus is supplied from the inverter power supply

    Data transmission rate 10, 20, 50, 125, 250, 500, 800 Kbaud and 1 Mbaud

    Type of documentation Language Order No.

    Docu pack , supplied with each inverter,containing CD-ROM 1) and Getting Started Guide 2)(paper version)

    Multilanguage   6SE6400-5AD00-1AP1

    Operating instructions

    2

    )(paper version) German   6SE6400-5AA00-0AP0English   6SE6400-5AA00-0BP0

    French   6SE6400-5AA00-0DP0

    Italian   6SE6400-5AA00-0CP0

    Spanish   6SE6400-5AA00-0EP0

    Parameter list 2)(paper version)

    German   6SE6400-5BA00-0AP0

    English   6SE6400-5BA00-0BP0

    French   6SE6400-5BA00-0DP0

    Italian   6SE6400-5BA00-0CP0

    Spanish   6SE6400-5BA00-0EP0

    Documentation

    1) The CD-ROM contains operat-ing instructions, parameter list,

    commissioning tools STARTERand DriveMonitor, multilan-guage.

    Available on the Internet:DriveMonitor at

    http://www4.ad.siemens.de/ WW/view/com/10804984/ 133100

    STARTER athttp://www4.ad.siemens.de/ 

    WW/view/com/10804985/ 133100

    2) Available on the Internet athttp://www.siemens.com/ 

    micromaster

    OptionsVariant independent options

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    38/1252/18 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ MICROMASTER 420 inverter

    With the communications module, the mounting depthincreases by 23 mm (0.91 inches).

    Frame size 1/3 AC 200 V to 240 V 3 AC 380 V to 480 V

    A 0.12 kW to 0.75 kW 0.37 kW to 1.5 kW

    B 1.1 kW to 2.2 kW 2.2 kW to 4 kW

    C 3 kW to 5.5 kW 5.5 kW to 11 kW

                                   

                       

          

          

              

          

                       

          

                       

          

          

                   

    Inverter frame size A

    Fixing with2 x M4 bolts, 2 x M4 nuts, 2 x M4 washers,or snap onto the DIN rail

    Tightening torque with washers fitted:2.5 Nm

    Ventilation clearance required at top andbottom: 100 mm

                                   

                       

          

    Inverter frame size Awith gland plate

                                    

                       

          

           

                  

             

              

          

    Fixing with4 x M5 bolts, 4 x M5 nuts, 4 x M5 washers

    Tightening torque with washers fitted:3.0 Nm

    Ventilation clearance required at topand bottom: 100 mm

    Inverter frame size C

                                    

                          

          

    Inverter frame size Cwith gland plate

       

                

          

                      

                       

          

                       

          

           

                    Fixing with

    4 x M4 bolts, 4 x M4 nuts, 4 x M4 washers

    Tightening torque with washers fitted:2.5 Nm

    Ventilation clearance required at top andbottom: 100 mm

    Inverter frame size B

                                    

       

                       

          

    Inverter frame size Bwith gland plate

    All dimensions in mm (values in brackets are in inches)

    Note:The inverters must not be mounted horizontally.But the inverters can be mounted without lateral spacing.

    Dimension drawings

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    39/125Siemens DA 51.2 · 2005/2006   2/19

    MICROMASTER 420

    ■ Filters and chokes

                                

      

    Line commutating choke for frame size A For frame sizes B and C

       

                

          

                     

      

    Line commutatingchoke for

    Dimensions Weight(max.)

    a b c kg

    Frame size A 200(7.87)

    75.5(2.97)

    50(1.97)

    0.8

    Frame size B  213(8.39)

    150(5.91)

    50(1.97)

    1.3

    Frame size C 280

    (11.02)

    185

    (7.28)

    50

    (1.97)

    2.3

                                   

                       

       

                       

          

                       

          

                       

          

    Filter frame size A For frame size B

                                   

                       

          

                       

          

                       

          

                       

          

                                   

                       

          

                       

          

                       

          

                       

          

    For frame size C

    All dimensions in mm (values in brackets are in inches)

                              

      

    Output choke for frame size A6SE6400-3TC00-4AD26SE6400-3TC00-4AD3

    For frame sizes B and C6SE6400-3TC01-0BD36SE6400-3TC03-2CD3

       

                

          

                     

      

    Output choketype 6SE6400-

    Dimensions Weight(max.)

    a b c kg

    3TC00-4AD2 200(7.87)

    75.5(2.97)

    110(4.33)

    1.95

    3TC00-4AD3 200(7.87)

    75.5(2.97)

    50(1.97)

    0.8

    3TC01-0BD3 213(8.39)

    150(5.91)

    70(2.76)

    3.4

    3TC03-2CD3 245(9.65)

    185(7.28)

    80(3.15)

    5.6

    Dimension drawings

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    40/1252/20 Siemens DA 51.2 · 2005/2006

    MICROMASTER 420

    ■ LC filter

       

                

          

                   

                          

          

                          

          

       

                

          

                   

                          

          

                          

          

    LC filter for frame size A LC filter for frame size B

    Fixing with M4 bolts Fixing with M4 bolts

       

                

          

                   

                          

       

       

                

          

                   

                          

          

    All dimensions in mm (values in brackets are in inches)

       

                

          

                     

                          

          

                          

          

    LC filter for frame size C

    Fixing with M5 bolts

       

                

          

                   

                          

       

    Dimension drawings

  • 8/18/2019 Micromaster Catalog DA512 MM4 2005-6

    41/125Siemens DA 51.2 · 2005/2006   3/1

    InverterMICROMASTER 430

    3/2   Description

    3/4   Circuit diagrams

    3/6   Technical data

    3/9   Selection and ordering data

    3/10   Options

    3/19   Dimension drawing