mazagon dock shipbuilders limited certified – iso 9001 ... · type gland plate of 3.15 mm...
TRANSCRIPT
Page 1 of 70
MAZAGON DOCK SHIPBUILDERS LIMITED
(A Government of India Undertaking)
Dockyard Road, Mazgaon, Mumbai 400 010. INDIA
Certified – ISO 9001: 2015 for Shipbuilding Division Tel. No.: (022) 23763254, 3246. Fax: (022) 2373 8151
E mail:[email protected], Website: https://mazagondock.in [email protected] E-Procurement Website: https://eprocuremdl.nic.in
e-TENDER ENQUIRY (TWO- BID SYSTEM) FOR PURCHASE OF ITEMS
DIVISION-SHIP BUILDING DEPARTMENT-MATERIAL PROCUREMENT:
Tender No.: GM(M)/SCW/2000007555 Tender Date.: 24/01/2020
Tender Closing Date.:24/02/2020 Tender Closing Time at.: 1400 Hrs. (IST)
Tender Opening Date.: 25/02/2020 Tender Opening Time.: 1500 Hrs. (IST)
EMD: INR 2,91,960/- (Rupees Two Lakhs Ninety One Thousand Nine Hundred Sixty only)
MAZAGON DOCK SHIPBUILDERS LIMITEDINVITES ON-LINE COMPETITIVE BIDS from
reputed Bidders / Vendors in TWO BID SYSTEM (Part-I Techno Commercial Bid and Part-II Price
Bid) on our e-procurement portal, for the following Supplies:
Issue of Tender enquiry document: - The tender enquiry can be downloaded from our website
https://eprocuremdl.nic.in / https://mazagondock.in (Path:- Tenders->Shipbuilding->Material
Purchase) and from CPP portal / Government E- market Portal.
Note: -This Tender is to be filled through E- tendering mode only on E Procurement Portal. Online bids
on our E-procurement portal only will be accepted. Bids submitted in any form other than online
submission will not be accepted.
1. Description of work: Survey of site, design & manufacture, testing at manufacturer’s works,
installation at site, Testing and Commissioning of outdoor non-draw-out A.C. Distribution panels
as per scope work.
Sr. No.
Description of Item
Quantity Unit Delivery period #
1.
Survey of Site, Design and Manufacture, testing at
Manufacturer’s works, Packing &Forwarding, Testing and commissioning of 110V AC
Distribution Panels
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 1)
10 Set Within 5 Months
from PO date
2.
Survey of Site, Design and Manufacture, testing at Manufacturer’s works, Packing & Forwarding,
Testing and commissioning of Power Distribution
Panels.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 2)
1 SET Within 5 Months
from PO date
Page 2 of 116
3.
Dismantling of existing Panel, Installation, Testing
& commissioning of supplied Power Distribution
Panels with MCCBs
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 2)
1 AU Within 5 Months
from PO date
4.
Survey of Site, Design and Manufacture, testing at
Manufacturer’s works, packing & forwarding,
Testing and commissioning of 19 nos. OUT-DOOR
Non-Draw–out A.C. Distribution Panels, Cables
and Cable Trays.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 3)
1 SET Within 5 Months
from PO date
5.
Installation, Testing & commissioning of OUT-
DOOR Non-Draw–out A.C. Distribution Panels,
Cables and Cable Trays.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 3)
1 AU Within 5 Months
from PO date
6.
Survey of Site, Design and Manufacture, testing at
Manufacturer’s works, packing & forwarding,
Testing and Commissioning of Power Distribution
Panels with MCCB’s & Switches.
(Please refer Technical Specifications & S cope
of Supply below at Annexure - 4)
1 Nos. Within 5 Months
from PO date
7.
Dismantling of existing panel & switches,
Installation, Testing & Commissioning of Power
Distribution Panels with MCCB’s & Switches.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 4)
1 AU
Within 5 Months
from PO date
8.
Survey of Site, Design and Manufacture, testing at
Manufacturer’s works, packing & forwarding,
Testing and Commissioning of OUT-DOOR Non-
Draw-out A.C. Distribution Panels (25 Nos.) with
MCCB’s & Switches.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 5).
1 Set Within 5 Months
from PO date
9.
Dismantling of existing panel, Installation, Testing
& Commissioning of A.C. Distribution Panels with
MCCB’s & Switches.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 5).
1 AU Within 5 Months
from PO date
10.
Survey of Site, Design and Manufacture, testing at
Manufacturer’s works, packing & forwarding,
Testing and Commissioning of OUT-DOOR Non-
Draw-out A.C. Distribution Panels (10 Nos.) with
MCCB’s
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 6)
1 SET Within 5 Months
from PO date
11.
Dismantling of Existing panel, Installation, Testing
& Commissioning of A.C. Distribution Panels (10
Nos.) with MCCB’s.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 6)
1 AU Within 5 Months
from PO date
Page 3 of 116
12.
Survey of Site, Design and Manufacture, testing at
Manufacturer’s works, packing & forwarding,
Testing and Commissioning of the following: (i) 415 V LT Panel(PCC) – 1 Nos.
(ii) 1600 A, 65 kA, 4 P Schneider Electric make ACB
– 1 Nos.
(iii) 3.5 C x 400sq.mm. XLPE/PVC Al. cable (10
Nos.) with MCCB’s – 4 Nos.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 7)
1 SET Within 5 Months
from PO date
13.
Installation, Testing & Commissioning of the
following: (i) 415 V LT Panel(PCC) – 1 Nos.
(ii) 1600 A, 65 kA, 4 P Schneider Electric make ACB
– 1 Nos.
(iii) 3.5 C x 400sq.mm. XLPE/PVC Al. cable (10
Nos.) with MCCB’s – 4 Nos.
(Please refer Technical Specifications & Scope of
Supply below at Annexure - 7)
1 AU Within 5 Months
from PO date
# Delivery period covers complete scope including Survey of site, design & manufacture, testing at
manufacturer’s works, installation at site, Testing and Commissioning of outdoor non-draw-out
A.C. Distribution panels as per scope work. Bidder should upload online the properly filled,
stamped and signed “vendor declaration form” (Enclosure 10).
Page 4 of 116
2. TECHNICAL SPECIFICATION & SCOPE OF SUPPLY:
ANNEXURE – 1 (for Item 1)
1. INTENT OF SPECIFICATION:
This specification is intended to cover the Survey of site, Design and Manufacture, testing at manufacturer’s
works, Packing & Forwarding, Testing and commissioning of 10 nos. 110 V A.C. Distribution Panels. The
details of the panels are:
10 nos. OUT-DOOR Non-Draw-out A.C. Distribution panels consisting of: -
1 no. Incoming MCCB-: 110 VAC, 3 Pole, 400 A, Short circuit rating minimum 35 KA, with electronic
release having adjustable overload, short-circuit and earth fault protection and having variable depth rotary
handle & connecting rod.
4 nos. Outgoing MCCB-: 110 VAC, 3 Pole, 100 A, Short circuit rating minimum 35 KA, with thermal
magnetic release having adjustable overload, short-circuit protection and having variable depth rotary handle
& connecting rod.
These AC Distribution Panels shall be used for rated voltage of 110 V +/- 5 %, 3 phase, 4 wire, 50 Hz A.C.
2. SCOPE OF SUPPLY:
2.1. The scope of supply through this specification includes but not limited to the following:
2.1.1. Free standing A.C. Distribution Panels: 10 Nos. (With no. of I/C & O/G MCCBs as indicated in sr. no. 1
above.)
NOTE: The arrangement of Incoming & Outgoing feeders, Busbar chamber, Cable entry boxes and
Termination is detailed in the GA Drawing of this specification. Equipment shall be furnished in accordance
with the same.
2.1.2. The Incomer breaker of the panel shall have:
1. Phase indicating lamps - 3 Nos. (R Y B)
2. Ammeter (0-500A) suitable for CT ratio 500/5A - 1 No.
3. Volt meter (0-250V) - 1 No.
4. Ammeter Selector Switch - 1 No.
5. Voltmeter Selector Switch - 1 No.
6. CTs (for metering) with CT ratio 500/5A - 1 set.
2.1.3. The base channel frame with hardware.
2.1.4. Set of accessories required for the operation and handling of the breakers – 1Set.
2.1.5. Essential spares for trouble free operation of the MCCBs.
2.1.6. All relevant drawings and documents.
3. TECHNICAL REQUIREMENTS:
3.1. Enclosure and Protection
3.1.1. The A.C. Distribution Panels and the components like MCCB, measuring instruments etc. shall be fully
conforming to respective/relevant IS standard/equivalent International standards.
3.1.2. Each of the Distribution Panels shall be metal clad and shall comprise standard prefabricated, cold rolled, sheet
steel, enclosure, free standing, unitized Distribution Panel. The minimum thickness for walls/doors and for
internal partitions/barriers shall be 14 SWG and 16 SWG respectively.
Page 5 of 116
3.1.3. The distribution panels shall be totally enclosed, dust and vermin proof. The degree of enclosure protection
shall be IP-65. Enclosure of distribution panel must be having two nos. doors with inspection glass window.
3.1.4. All doors and openings shall be provided with gaskets of durable material. The gaskets shall be held in a groove
and shall be continuous with ends fixed with adhesive material. Outer door should be in two parts.
3.2. CONSTRUCTIONAL FEATURES:
3.2.1. The arrangement of Incoming & Outgoing feeders, Busbar chambers, Cable entry boxes and Termination is
detailed in the GA Drawing. Equipment shall be furnished in accordance with the same. 4 Nos fixed lifting
lugs shall be furnished on the panels. Access to all equipment, bus bars and cable terminations shall be from
front only and panel with back access is not acceptable.
3.2.2. The feeder modules shall be provided with compartment door with internal hinges. The compartment doors
shall be interlocked mechanically with the operating handles / knobs of MCCB’s such that the door cannot be
opened when the MCCB 4 is in ‘ON’ condition. Defeat feature for this interlock shall also be provided. Suitable
diameter but not less than 15 mm metallic rotating knobs minimum 2 nos. each door shall be provided.
3.2.3. All the equipment inside the feeder compartment shall be housed on a metallic plate which shall be bolted
within the compartment. All instruments, push buttons, indicating lamps etc. shall be located on the feeder
compartment doors.
3.2.4. All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized Zinc
passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured against loosening.
3.2.5. The Distribution Panels shall be designed to ensure maximum safety during operation, inspection, connection
of cables and maintenance. Means shall be provided to prevent shorting of power and/or control terminals due
to accidental dropping of maintenance tools etc. inside the distribution panels. Checking and removal of
components shall be possible without disturbing adjacent equipment.
3.2.6. All power and control cables shall enter the distribution panels from bottom as specified. Necessary bolted
type gland plate of 3.15 mm thickness shall be provided.
3.2.7. The complete distribution panel shall be mounted on a rectangular frame of C-channel with legs made of Angle
with suitable mode of fastening. The minimum size of the C–channel shall be 100 mm and the size of the angle
shall be 50x50x6 mm. The complete frame is to be supplied by the vendor duly fabricated and painted with
enamel paint of blue colour. The height of the base frame channel shall be 15 inches from the ground level.
3.2.8. At the time of bidding itself, firm shall submit the dimensional drawings of the distribution panel.
3.2.9. The height of the distribution panel shall not exceed 1200 mm in any case.
3.3. Busbars, Busbar Sizing, Connection and Supports
3.3.1. Busbars shall be made of high conductivity electrolytic grade copper, supported on insulators made of non-
hygroscopic, non-inflammable material. The busbars shall extend throughout the length of the distribution
panels and shall be of uniform cross-section. All bus joints as well as the supports shall be designed to withstand
the specified short circuit level for 1 second without permanent deformation. Dynamic stresses shall be
calculated on the basis of peak short circuit current.
Page 6 of 116
3.3.2. All Busbars shall be sleeved with Fire Resistant Low Smoke PVC Insulation. Identification rings of red,
yellow, blue and black colour to identify phase and neutral busbars shall be provided over busbar sleeves.
3.3.3. Minimum clearance between two live parts shall be 20 mm. Minimum clearance between live parts/neutral to
ground shall be 25 mm.
3.3.4. The current density for the bus bars shall not exceed 1000 A/sq. inch.
3.3.5. Bus connections shall be silver plated.
3.4. Power Connections
3.4.1. Power connections between the busbars and the incoming point of MCCB’s module shall be done using
suitably rated individual single core copper cable with FRLS PVC insulation/ sleeved bus bar of required size.
Bunching of cables to meet the current requirements are not acceptable. The cables shall be terminated on the
busbars and at the incoming point using crimping type tinned copper lugs of required design.
3.4.2. For all the O/G MCCBs, the terminals are to be brought at the bottom of the panel as shown in the GA
DRAWING of this specification. The terminations of the O/G cables shall be done at these terminals. This is
to bring all the cable terminations at the bottom of the distribution Panels. Horizontal Busbar arrangement (of
required current rating) with proper supports shall be provided at the bottom of the panel for Incoming &
Outgoing cable connections with suitable identification.
3.5. Control Wiring and Connections
3.5.1. All the distribution panels shall be pre - wired and ready for use after external cable connection. Inside the
panels, the control wiring shall be carried out using insulated copper conductors with PVC insulation. The
insulation shall be rated for minimum 600V grade irrespective of the distribution panel voltage rating. The
minimum size of conductor shall be 1.5 sq. mm. Wherever multi-strand wires are used, its ends shall be
crimped in a suitably sized lug before connection.
3.5.2. Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall match with the
terminal numbers of equipment device.
3.6. Control Circuit Protection
Circuit protection shall be provided by using MCBs. Use of fuses shall not be permitted.
3.7. Earthing connections
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts through a
copper earth bus. 2 nos., earthing bolts shall be provided on the distribution panels.
3.8. Name Plates
Nameplates of approved design shall be furnished for each panel. The material shall be anodized aluminium
of 3 mm thick with white letter on black background.
The nameplate shall be held by self-tapping screws. Nameplates shall be of suitable size but not less than
40mm x 100 mm for panels. Caution notice on suitable metal plate shall be affixed at the back to each
vertical panel.
3.9. Distribution Panel Components
A) Moulded Case Circuit Breakers (MCCBs)
3.9.1. The MCCBs shall be of reputed make. If the supplier is offering any make other than
Legrand/Siemens/L&T/Schneider Electric/GE/ABB/Crompton, then the firm shall also submit copies of IS
certification & Type Test reports as per the relevant IS code and copies of bulk order executed by the supplier
for the above item to prove the performance of the offered make.
Page 7 of 116
3.9.2. M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free mechanism.
3.9.3. M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload protection and
instantaneous characteristics for short circuit protection.
3.9.4. M.C.C.B. shall be rated for breaking the short circuit current specified for the distribution panels. Use of back-
up fuses for extending the breaking capacity is not acceptable.
3.9.5. The circuit breakers shall comply with the requirement of IEC 60947 / IS 13947:1993. The MCCBs shall be
suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
3.9.6. The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to be marked as
suitable for isolation / disconnection to facilitate safety of operating personnel while the breaker is in use.
3.9.7. The MCCBs shall be of double break contacts.
3.9.8. The terminals shall be of liberal design with adequate clearances.
3.9.9. The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indicators.
3.9.10. Earth fault protection wherever specified shall be an integral part of the breaker, direct operating type &
adjustable.
3.9.11. MCCBs shall be Fixed mounting type having front terminals connection.
B) Miniature Circuit Breakers (MCBs)
3.9.12. The MCBs shall be of 6 Amp, 10 KA rated.
3.9.13. The MCBs shall be conforming to IS 8828: 1996.
3.10 Measuring Instruments
All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
3.11 All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for ammeters and
voltmeters. The range shall be as indicated elsewhere. Selector switches for the meters also to be provided.
3.12 LED type Phase Indicating Lamps shall be provided on the Incoming MCCB Cubicle of each Distribution
Panel.
4. PAINTING
Surface Preparation: Prior to painting, surface should be free of any visible loose particles, welding spatters
or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks, cleaning of surface with
water in rising tank, acid treatment of surface with chromate and phosphate. Surface should be suitably cleaned
to achieve required finish as per relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of primer shall be
high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to be mixed as per manufacturer
specification. Paint to be applied to achieve minimum total 110-micron DFT.
5. Factory Tests and Inspection
The Distribution Panels shall be completely assembled, wired, adjusted and tested at the factory as per the
relevant standards.
Page 8 of 116
Type Tests
The design of the offered panels shall be type tested for IP-65 Enclosure protection and a copy of the test
report for the IP65 Type Test carried out on similar and identical panels shall be submitted at the time of offer
itself to prove the design.
Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
a) All wiring and current carrying part shall be given appropriate high voltage test.
b) Primary current and voltage shall be applied to all instruments.
c) Routine test shall be carried out on all equipment such as circuit breakers, instrument
transformers, meters etc.
d) Primary injection test to check the CT ratio and ammeter.
Test Witness
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least fifteen
(15) days advance notice of the date when tests are to be carried out. The Distribution Panels shall be
dispatched from the works only after clearance of the same by MDL.
6. Warranty
The vendor shall have final and total single point responsibility for the design and performance of the panels
and all components supplied under this specification. The supplier shall:
a) Warrant that the panels and all materials to be free from defects in design, material and workmanship
b) Warrant that the panels will satisfy the requirements of the intended use and be suitable for the application
c) Agree to repair or replace any component under this warranty, which proves to be defective within a
minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items purchased by the
supplier.
7. Work Completion Period
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing and
Commissioning of all the panels shall be completed within 5 months after receipt of order.
8. Deviation
The firm shall submit a DEVIATION SHEET at the time of offer clearly indicating any deviations from the
specifications and the clause no. against which the deviation is sought. If there is no deviation from the
specifications, the deviation sheet shall still be submitted stating NO DEVIATION from tender specifications
and duly signed & stamped. No deviation will be accepted after the placement of the order.
9. Functional checks & Commissioning
01. Functional checks shall be conducted by the supplier on each panel after delivery.
02. The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out field
checks on the panels and materials under his scope of work.
03. These checks shall be conducted in presence of MDL Engineer and according to his directions.
04. All temporary arrangements and connections required for checks shall be provided by the contractor.
05. All equipment’s will be kept under working conditions for minimum period of fifteen days. After
successfully functional working, this equipment’s declared as commissioned.
10. General Notes:
Any other activities which are not mentioned in this specification but required for the successful installation,
testing and commissioning of the distribution panels shall be in contractor’s scope.
Page 9 of 116
11. Standards & Codes:
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment and the
work covered by the scope of this contract.
(a) Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623.
(b) Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993(Part I, II, III, IV & V).
(c) Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147: 1962.
Page 10 of 116
ANNEXURE – 2 (for Item 2 & 3)
1. INTENT OF SPECIFICATION
This specification is intended to cover the Survey of site, Design and Manufacture, testing at manufacturer’s
works, Packing & Forwarding, Unloading, dismantling of existing panel, shifting of the new panel to the
installation site, Installation, Testing and commissioning of 1 no. Power Distribution Panel with MCCBs of
ratings specified below:
The no. of I/C and O/G MCCB shall be as follows:
1 no. Incoming MCCB -: 415VAC, 4 Pole, 1000 A, Short Circuit rating minimum 50 kA, with Microprocessor
based protection release having adjustable overload, short-circuit and earth fault protection and having variable
depth rotary handle & connecting rod.
2 nos. Outgoing MCCB-: 415VAC, 3 Pole, 800 A, Short circuit rating minimum 50 kA, with thermal magnetic
release having adjustable overload & short-circuit protection and having variable depth rotary handle &
connecting rod.
2 nos. Outgoing MCCB-: 415VAC, 3 Pole, 630 A, Short circuit rating minimum 50 kA, with thermal magnetic
release having adjustable overload & short-circuit protection and having variable depth rotary handle &
connecting rod.
1 no. Outgoing MCCB: - 415VAC, 3 Pole, 400 A, Short circuit rating minimum 50 kA, with thermal magnetic
release having adjustable overload & short-circuit protection and having variable depth rotary handle &
connecting rod.
The panel is to be installed outside Kasara Sub-station at NY of MDL.
2. SCOPE OF SUPPLY
2.1. The scope of supply through this specification includes but not limited to the following:
2.2. Free standing A.C. Distribution Panel: 1 No. (With no. of I/C & O/G MCCBs as indicated in Sr. No. 1
above.)
2.3. The Incomer breaker of the panel shall have:
1. Phase indicating lamps at Incoming Side - 3 nos. (R Y B)
2. Ammeter (0-1000A) suitable for CT ratio 1000/5A - 1 no.
3. Volt meter (0-500V) - 1 no.
4. Ammeter Selector Switch - 1 no.
5. Voltmeter Selector Switch - 1 no.
6. CTs (for metering) with CT ratio 1000/5 - 1 set.
The outgoing breakers of the panels shall have indicating lamps – 1 each for On, Off and Trip indication and
Ammeter (0-800A) with selector switch.
Page 11 of 116
2.4. All required double compression Nickel/Chromium plated brass cable glands and crimping type copper lugs.
2.5. The base channel frame with hardware. Base frame to have a rectangular frame top fixed on vertical stands.
2.6. Set of accessories required for the operation and handling of the breakers – 1 Set for each MCCB used in
the panel.
2.7. Essential spares for trouble free operation of the MCCBs. All relevant drawings and documents.
2.8. Cable entry boxes with required sized bus links for termination of Incoming Feeder cables & 1 outgoing
feeder. The cables for Incoming feeder and 1 no. outgoing feeder are short and will need a Cable Entry Box
with extension Bus-Links of suitable sizing. Same needs to be supplied with the panel.
3. TECHNICAL REQUIREMENTS
3.1. Enclosure and Protection
3.1.1. The A.C. Distribution Panel and the components like MCCB, MCB measuring instruments etc. shall be fully
conforming to respective/relevant IS standard/equivalent International standards.
3.1.2. The Distribution Panel shall be metal clad and shall comprise standard prefabricated, cold rolled, sheet steel,
enclosure, free standing, unitized Distribution Panel. The minimum thickness for walls/doors and for internal
partitions/barriers shall be 14 SWG and 16 SWG respectively.
3.1.3. The distribution panel shall be totally enclosed, dust and vermin proof. The degree of enclosure protection
shall be IP-65. The panel will be installed in open area exposed to rain. The S.C. withstand strength of the
panel shall be 50 kA.
3.1.4. All doors and openings shall be provided with gaskets of durable material. The gaskets shall be held in a
groove and shall be continuous with ends fixed with adhesive material.
3.1.5. Each section of the panel shall be provided with door switch operated lamp for illumination inside the panel.
The lamp shall be suitably located to ensure visibility while working in the panel.
3.2. CONSTRUCTIONAL FEATURES
3.2.1. Removable Eye bolt/lifting lugs shall be furnished on the panel. Access to all equipment, bus bars and cable
terminations shall be from front only and panel with back access is not acceptable.
3.2.2. The feeder modules shall be provided with compartment door with internal hinges. The compartment doors
shall be interlocked mechanically with the operating handles / knobs of MCCB’s such that the door
cannot be opened when the MCCB is in ‘ON’ condition. Defeat feature for this interlock shall also be
provided. Suitable diameter but not less than 15 mm, rotating knobs minimum 2 nos. per door shall be
provided for all doors.
3.2.3. All the equipment inside the feeder compartment shall be housed on a metallic plate which shall be bolted
within the compartment. All instruments, push buttons, indicating lamps etc. shall be located on the feeder
compartment doors.
3.2.4. All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized Zinc
passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured against loosening.
3.2.5. The Distribution Panel shall be designed to ensure maximum safety during operation, inspection, connection
of cables and maintenance. Means shall be provided to prevent shorting of power and/or control terminals
due to accidental dropping of maintenance tools etc. inside the distribution panel. Checking and removal of
components shall be possible without disturbing adjacent equipment.
3.2.6. Necessary bolted type gland plate of 3.15 mm thickness and Nickel/Chromium plated brass double
compression cable glands for all cable entries in the distribution panel shall be provided. Terminal blocks
shall not be used for supporting cables.
3.2.7. The complete distribution panel shall be mounted on an angle frame with suitable mode of fastening. The
minimum size of the angle shall be 50x50x6 mm. The complete frame is to be supplied by the vendor duly
fabricated and painted with Powder Coated paint with oven baking of grey/black color. The height of the base
frame channel shall be 400 mm or more from the ground level for easy entry and termination of cables.
Page 12 of 116
3.3. Busbars, Busbar Sizing, Connection and Supports
3.3.1. Busbars shall be made of high conductivity electrolytic grade copper, supported on insulators made of non-
hygroscopic, non-inflammable material. The busbars shall extend throughout the length of the two sections
of distribution panels and shall be of uniform cross-section. All bus joints as well as the supports shall be
designed to withstand the specified short circuit level for 1 second without permanent deformation. Dynamic
stresses shall be calculated on the basis of peak short circuit current.
3.3.2. Busbars shall be sleeved with Fire Resistant Low Smoke PVC for full voltage insulation. Identification rings
of red, yellow, blue and black colour to identify phase and neutral busbars shall be provided over busbar
sleeves.
3.3.3. Minimum clearance between two live parts shall be 20 mm. Minimum clearance between live parts/neutral
to ground shall be 25 mm.
3.3.4. The current density for the copper shall not exceed 1000 A/sq. inch.
3.4. Power Connections
3.4.1. Power connections between the busbars and the incoming point of MCCB’s module shall be done using
suitably sized Electrolytic Grade Copper Busbars.
3.5. Control Wiring and Connections
3.5.1. The distribution panels shall be pre - wired and ready for use after external cable connection. Inside the panels,
the control wiring shall be carried out using insulated copper conductors with PVC insulation. The insulation
shall be rated for minimum 600V grade irrespective of the distribution panel voltage rating. The minimum
size of conductor shall be 1.5 sq.mm. Wherever multi-strand wires are used; its ends shall be crimped in a
suitably sized lug before connection.
3.5.2. Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall match with
the terminal numbers of equipment device.
3.6. Control Circuit Protection
Circuit protection shall be provided by using MCBs. Use of fuses shall not be permitted.
3.7. Earthing connections
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts through a
copper earth bus. 2 nos. earthing bolts shall be provided on the distribution panel.
3.8. Name Plates
Nameplates of approved design shall be furnished for the panel. The material shall be lamicoid or anodized
aluminium of 3 mm thick with white letter on black background. The nameplate shall be held by self-tapping
screws. Nameplates shall be of suitable size but not less than 40 x 100 mm for panel. Caution notice on
suitable metal plate shall be affixed at the back to each vertical panel.
3.9. Distribution Panel Components
A) Moulded Case Circuit Breakers (MCCBs).
3.9.1. The MCCBs/MCBs shall be of reputed make. If the supplier is offering any make other than Legrand
/Siemens /L&T /Schneider Electric /GE /ABB /Crompton, then the firm shall also submit copies of IS
Page 13 of 116
certification & Type Test reports as per the relevant IS code and copies of bulk order executed by the supplier
for the above item to prove the performance of the offered make.
3.9.2. M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free mechanism.
3.9.3. M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload protection and
instantaneous characteristics for short circuit protection.
3.9.4. The circuit breakers shall comply with the requirement of IEC 60947 / IS13947:1993. The MCCBs shall be
suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
3.9.5. The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to be marked as
suitable for isolation / disconnection to facilitate safety of operating personnel while the breaker is in use.
3.9.6. The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indication.
3.9.7. Earth fault protection wherever specified shall be an integral part of the breaker, direct operating type &
adjustable.
3.9.8. MCCBs shall be Fixed mounting type having front terminals connection.
3.10. Miniature Circuit Breakers (MCBs) – For Control Circuit.
3.10.1. The MCBs shall be of 6 Amp, 10 KA rated.
3.10.2. The MCBs shall be conforming to IS 8828: 1996.
3.11. Measuring Instruments
3.11.1. All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
3.11.2. All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for ammeters and
voltmeters. The range shall be as indicated elsewhere. Selector switches for the meters also to be provided.
3.11.3. LED type Phase Indicating Lamps shall be provided on the Incoming MCCB Cubicle of each Distribution
Panel.
4. PAINTING
Surface Preparation: Prior to painting, surface should be free of any visible loose particles, welding
spatters or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks, cleaning of
surface with water in rising tank, acid treatment of surface with chromate and phosphate. Surface should be
suitably cleaned to achieve required finish as per relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of primer shall be
high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to be mixed as per manufacturer
specification. Paint to be applied to achieve minimum total 110-micron DFT.
5. Factory Tests and Inspection
The Distribution Panels shall be completely assembled, wired, adjusted and tested at the factory as per the
relevant standards.
Type Test Certificate:
Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
a) All wiring and current carrying part shall be given appropriate high voltage test.
b) Primary current and voltage shall be applied to all instruments.
c) Routine test shall be carried out on all equipment such as circuit breakers, instrument transformers,
meters etc.
Pre-Dispatch Inspection
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least fifteen
(15) days advance notice of the date when tests are to be carried out.
Page 14 of 116
Test Certificates
Certified reports of all the tests carried out at the works shall be furnished in 3 copies.
The Distribution Panel shall be dispatched from the works only after clearance of the same by MDL.
6. Warranty
The vendor shall have final and total single point responsibility for the design and performance of the
panels and all components supplied under this specification.
The supplier shall:
a) Warrant that the panels and all materials to be free from defects in design, material and
workmanship.
b) Warrant that the panel will satisfy the requirements of the intended use and be suitable for the
application.
c) Agree to repair or replace any component under this warranty, which proves to be defective within
a minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items purchased
by the supplier.
7. Packing and Transportation
The offered panel along with their accessories shall be transported to site properly packed and secured.
The same shall be unloaded by the contractor at MDL site. MDL will provide only the crane facility
for unloading and internal shifting (from unloading place) to the installation site. Labour/manpower
shall be in contractor’s scope.
8. Work Completion Period
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing and
Commissioning of the panel shall be completed within 5 months after receipt of order.
9. Deviation
In the event of any deviation from this specification the same shall be clearly indicated at the time of offer
itself. No deviation will be accepted after the placement of the order.
10. Detailed Requirement of Installation
a) Dismantling & removing of the existing Panel and SFU’s. Removal of the dismantled Panel/SFU’s from
the site to the scrap area at MDL.
Note: Dismantling the old Panel & erection of new Panel shall be done on Saturday, Sunday and Holiday
and the restoration of normal supply must be done before the beginning of the next working day.
b) All alignment, leveling, grouting, anchoring & adjustment, cable terminations shall be carried out in
accordance with manufacturer’s instructions and or as directed by MDL Engineers.
c) Lifting/shifting of the new panel to the location, erection of the panel shall be done by the contractor. All
connections in new panels shall be completed and checked to ensure safety & satisfactory operation of
the Panels.
d) While designing the panel, due care shall be taken considering the available length of Incoming and
Outgoing cables for termination. The 2 nos. Incoming Cables and 2 nos. Outgoing cables for 1 of the
outgoing feeders are short and will need a Cable Entry Box with extension Bus-Links of suitable sizing.
Same needs to be supplied with the panel.
Page 15 of 116
11. Site Inspection
After completion of erection/installation each distribution panel shall be thoroughly inspected in presence of
the MDL Engineer for correctness and completeness of erection and acceptability for switching ON.
12. Testing & Commissioning
1) After completion of erection work, tests shall be conducted by the supplier/erection contractor on
each panel.
2) The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out
field tests on the panels and materials under his scope of work.
3) These tests shall be conducted in presence of MDL Engineer and according to his directions.
4) All temporary arrangements and connections required for tests shall be provided by the contractor.
5) The contractor shall record the test results on approved format and furnish four (4) copies of the
results to MDL within a week of the date of test completed.
6) On successful inspection and testing, the equipment shall be commissioned and will be kept under
observation for a minimum period of 15 days before declaring as commissioned.
13. General Notes
Any other activities which are not mentioned in this specification but required for the successful installation,
testing and commissioning of the distribution panels shall be in contractor’s scope.
14. Standards & Codes
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment and the
work covered by the scope of this contract.
(a) Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623
(b) Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993 (Part I, II, III, IV & V).
(c) Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147: 1962
(d) IS: 4237-1982 General Requirements for Switchgear and Control gear for voltages not exceeding 1000V
A.C or 1200V D.C.
(e) IS: 2147-1962 Degree of Protection provided by enclosures for low voltage switchgear and control gear.
(f) IS: 1897-1983 Copper strips for Electrical purposes.
(g) IS: 3618-1966 Phosphate Treatment of Iron and Steel for protection against corrosion.
(h) IS: 6005 – 1998: Code of practice for phosphating iron and steel
(i) IS: 375-1963 and IS: 5578-1970 Marking and arrangement for Switchgear Main connections, Auxiliary
Wiring and Insulated Conductors.
(j) IS: 2032 Graphical Symbols used in electro technology.
Page 16 of 116
Technical Offer Details Format
(To be submitted by vendor)
Sr.No. Technical Particular Specification Deviation (if any)
1. Make of offered Panel
2. Make of MCCBs
3. Model & Cat. No. of :
I/C MCCB 1000 A, 4P, 50 kA
O/G MCCB 800 A, 3P, 50 kA
O/G MCCB 630 A, 3P, 50 kA
O/G MCCB 400 A, 3P, 50 kA
4. Protection Release catalogue no.
I/C MCCB 1000 A, 4P, 50 kA
O/G MCCB 800 A, 3P, 50 kA
O/G MCCB 630 A, 3P, 50 kA
O/G MCCB 400 A, 3P, 50 kA
5. Busbar material
Page 17 of 116
ANNEXURE – 3 (for Item 4 & 5)
1. INTENT OF SPECIFICATION
This specification is intended to cover the Survey of site, Design and Manufacture, testing at manufacturer’s works,
Packing & Forwarding, Installation at site, Testing and commissioning of 19 nos. OUT-DOOR (IP-65) Non-
Draw-out A.C. Distribution panels consisting of: -
a. For 440V Shore Supply Panels:
Sr. No. Description I/C MCCB O/G MCCB No. of panels Color of panel
01 440V panel 4P, 630 Amp 2X400 Amp 13 Red
b. For 110V Panels: Construction of panel shall be same as 415V supply panel and will be used for 110V
shore supply.
Sr. No. Description I/C MCCB O/G MCCB No. of Panels Color of panel
01 110V panel 3P,400 Amp 2X200 Amp 06 Blue
1.1. Incoming MCCB for 415V supply panel -: 415VAC, 4Pole, 630 Amp MCCB having Short circuit rating
minimum 50 kA, with Microprocessor release having adjustable overload, short-circuit and earth fault
protection and having variable depth rotary handle & connecting rod.
1.2. Outgoing MCCB for 415V supply panel -: 415VAC, 4 Pole, 400 Amp MCCB having Short circuit rating
minimum 35 kA, with thermal magnetic release having adjustable overload, short-circuit protection and having
variable depth rotary handle & connecting rod.
1.3. Incoming MCCB for 110V supply panel -: 415VAC, 3 Pole, 400 Amp MCCB having Short circuit rating
minimum 50 kA, with Microprocessor release having adjustable overload, short-circuit and earth fault
protection and having variable depth rotary handle & connecting rod.
1.4. Outgoing MCCB for 110V supply Panel -: 415VAC, 3 Pole, 200 Amp having Short circuit rating minimum
35 kA, with thermal magnetic release having adjustable overload, short-circuit protection and having variable
depth rotary handle & connecting rod.
2. SCOPE OF SUPPLY
2.1. The scope of supply through this specification includes but not limited to the following:
2.1.1. Free-standing A.C. Distribution panels: 19 Nos. (With no. of I/C & O/G MCCBs as indicated in table
above.). Minimum height of stand should be 500mm and max. height of panel shall not exceed 1300 mm.
Maximum depth of panel shall be 800mm.
2.1.2. The Incomer breaker of the panel shall have:
i) Phase indicating lamps - 3 nos. (R Y B)
ii) Ammeter (0-800/400A) suitable for CT ratio - 1 no.
iii) Volt meter (0-500V) - 1 no.
iv) Volt meter (0-250V) for 110V panel - 1 no.
v) Ammeter Selector Switch - 1 no.
vi) Voltmeter Selector Switch - 1 no.
vii) CTs (for metering) - 03 Nos.
2.1.3. All required double compression Nickel/Chromium plated brass cable glands and crimping type copper lugs.
2.1.4. The base channel frame with hardware.
2.1.5. All relevant drawings and documents.
Page 18 of 116
3. TECHNICAL REQUIREMENTS
3.1. Enclosure and Protection
3.1.1. The distribution boards and the components like MCCB, measuring instruments etc. shall be fully conforming
to respective/relevant IS standard/equivalent International standards.
3.1.2. Each of the 19 shore supply Panels shall be metal clad and shall comprise standard prefabricated, cold rolled,
sheet steel, enclosure, free standing, unitized Distribution Panel. The minimum thickness for walls/doors and
for internal partitions/barriers shall be 14 SWG and 16 SWG respectively.
3.1.3. The switchboards shall be totally enclosed, dust and vermin proof. The degree of enclosure protection shall be
IP-65. The bidder shall submit valid IP-65 type test reports carried out at Govt. approved labs like
CPRI/IRDA/NABL accredited lab of offered panel or similar panel having same type, size and design.
3.1.4. If the firm do not have Type tested panel of same type, size & design, then the firm has to carryout IP-
65 type test on one panel before starting manufacturing of balance panels after placement of purchase
order by MDL. This test shall be carried out at CPRI/IRDA/NABL accredited lab. After successful
completion of type test, remaining panels can be manufactured with the consent of maintenance dept.
Panel will not be accepted without type test reports. Bidders to clearly indicate, agree the same in
technical bid, Part-I.
3.1.5. All doors and openings shall be provided with gaskets of durable material. The gaskets shall be held in a groove
and shall be continuous with ends fixed with adhesive material.
3.2. CONSTRUCTIONAL FEATURES
3.2.1. The arrangement of Incoming & Outgoing feeders, Busbar chambers, Cable entry boxes and Termination is
detailed in the GA Drawing in this specification. Equipment shall be furnished in strict accordance with the
same. Removable Eye bolt/lifting lugs shall be furnished on the panels. Access to all equipment, bus bars and
cable terminations shall be from front only and boards with back access shall not be acceptable.
3.2.2. The feeder modules shall be provided with compartment door with internal hinges. The compartment doors
shall be interlocked mechanically with the operating handles / knobs of MCCB’s such that the door cannot be
opened when the MCCB is in ‘ON’ condition. Defeat feature for this interlock shall also be provided. Suitable
diameter but not less than 15 mm, rotating knobs minimum 2 nos. per door shall be provided for all doors.
3.2.3. All the equipment inside the feeder compartment shall be housed on a metallic plate, which shall be bolted
within the compartment. All instruments, push buttons, indicating lamps etc. shall be located on the feeder
compartment doors.
3.2.4. All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized Zinc
passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured against loosening.
3.2.5. The Distribution Panels shall be designed to ensure maximum safety during operation, inspection, connection
of cables and maintenance. Means shall be provided to prevent shorting of power and/or control terminals due
to accidental dropping of maintenance tools etc. inside the distribution panels. Checking and removal of
components shall be possible without disturbing adjacent equipment.
3.2.6. All power and control cables shall enter the distribution panels from bottom as specified. Necessary bolted type
gland plate of 3.15 mm thickness and Nickel/Chromium plated brass double compression cable glands for all
cable entries in the switchboard shall be provided. (Panel shall have cable entry of 400 sq. mm. for Incomer
Chamber & cable entry of 400/240 sq. mm for each Outgoing Chamber). Terminal blocks shall not be used for
supporting cables.
3.2.7. The complete distribution board shall be mounted on a C- channel and angle frame with suitable mode of
fastening. The minimum size of the C – Channel shall be 200 mm and the size of the angle shall be 50x50x6
mm. The complete frame is to be supplied by the vendor duly fabricated and painted with enamel paint of grey
colour. The height of the base frame channel shall be 500mm from the ground level.
Page 19 of 116
3.2.8. At the time of bidding itself, firm shall submit the dimensional drawings of the distribution panel.
3.3. Busbars, Busbar Sizing, Connection and Supports
3.3.1. Busbars shall be made of high conductivity electrolytic grade copper having current density not more than
1000 Amp per Square Inch, supported on insulators made of non-hygroscopic, non-inflammable material.
The busbars shall extend throughout the length of the distribution panels and shall be of uniform cross-section.
All bus joints as well as the supports shall be designed to withstand the specified short circuit level for 1second
without permanent deformation. Dynamic stresses shall be calculated on the basis of peak short circuit current.
3.3.2. Busbars shall be sleeved with Fire Resistant Low Smoke PVC for full voltage insulation. Identification rings
of red, yellow, blue and black colour to identify phase and neutral busbars shall be provided over busbar sleeves.
3.3.3. Minimum clearance between two live parts shall be 20 mm. Minimum clearance between live parts/neutral to
ground shall be 25 mm.
3.4. Power Connections:
3.4.1. Power connections between the busbars and the incoming point of MCCB’s module shall be done using suitably
rated individual single core copper cable with FRLS PVC insulation/ sleeved bus bar of required size. Bunching
of cables to meet the current requirements is not acceptable. The cables shall be terminated on the busbars and
at the incoming point using crimping type tinned copper lugs of required design.
3.4.2. For O/G MCCBs, the terminals are to be brought at the bottom of the panel. The terminations of the O/G cables
shall be done at these terminals. This is to bring all the cable terminations at the bottom of the Shore Supply
Panels. Busbar arrangement (of required current rating) with proper supports shall be provided at the bottom of
the panel for Incomer & Outgoing cable connections.
3.5. Control Wiring and Connections:
3.5.1. All the Shore Supply Boxes shall be pre - wired and ready for use after external cable connection. Inside the
Shore Supply Boxes, the control wiring shall be carried out using insulated copper conductors with PVC
insulation. The insulation shall be rated for minimum 600V grade irrespective of the distribution panel voltage
rating. The minimum size of conductor shall be 2.5 sq.mm. Wherever multi-strand wires are used its ends shall
be crimped in a suitably sized lug before connection.
3.5.2. Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall match with the
terminal numbers of equipment device.
3.6. Control Circuit Protection:
Control wiring protection shall be provided by using MCBs. Use of fuses shall not be permitted.
3.7. Earthing connections:
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts through a
copper earth bus. 2 nos. earthing bolts shall be provided on the shore supply boxes.
3.8. Name Plates:
Nameplates of approved design shall be furnished for each panel. The material shall be lamicoid or anodized
aluminium of 3 mm thick with white letter on black background. Current rating of each I/C and O/G should
be mentioned on panel cover.
The nameplate shall be held by self-tapping screws. Nameplate size shall be minimum 40 mm x 150 mm for
panels.
Caution notice on suitable metal plate shall be affixed at the back to each vertical panel.
Page 20 of 116
3.9. Shore supply Panel Components
A) Moulded Case Circuit Breakers (MCCBs)
3.9.1. The MCCBs shall be of reputed make. If the supplier is offering any make other than
Legrand/Siemens/L&T/Schneider Electric/GE/ABB, then the firm shall also submit copies of IS certification
& Type Test reports as per the relevant IS code and copies of bulk order executed by the supplier for the above
item to prove the performance of the offered make.
3.9.2. M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free mechanism.
3.9.3. M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload protection and
instantaneous characteristics for short circuit protection.
3.9.4. M.C.C.B. shall be rated for breaking the short circuit current specified for the switchboard. Use of back-up
fuses for extending the breaking capacity is not acceptable.
3.9.5. The circuit breakers shall comply with the requirement of IEC 60947 / IS 13947:1993. The MCCBs shall be
suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
3.9.6. The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to be marked as
suitable for isolation / disconnection to facilitate safety of operating personnel while the breaker is in use.
3.9.7. The MCCBs shall be of double break contacts.
3.9.8. The terminals shall be of liberal design with adequate clearances.
3.9.9. The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indicators.
3.9.10. Earth fault protection wherever specified shall be an integral part of the breaker, direct operating type &
adjustable.
3.9.11. MCCBs shall be fixed mounting type having front terminals connection.
B) Miniature Circuit Breakers (MCBs)
3.9.12. The MCBs shall be of 6 Amp, 10 KA rated.
3.9.13. The MCB’s of DB shall be 4P, 63 Amp, 10KA rated (D series).
3.9.14. The MCBs shall be conforming to IS 8828: 1996.
3.10. Measuring Instruments:
All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
3.11. All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for ammeters and
voltmeters. The range shall be as indicated elsewhere. Selector switch for all the meters also to be provided.
3.12. LED type Phase Indicating Lamps shall be provided on the Incoming MCCB Cubicle of each Shore Supply
Panel.
Page 21 of 116
4. PAINTING:
Surface Preparation: Prior to painting, surface should be free of any visible loose particles, welding
spatters or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks, cleaning of
surface with water in rising tank, acid treatment of surface with chromate and phosphate. Surface should
be suitably cleaned to achieve required finish as per relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of primer shall
be high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to be mixed as per
manufacturer specification. Paint to be applied to achieve minimum total 110-micron DFT.
5. CABLE TRAY:
Cables are to be laid on ladder type tray with protective cover. These trays should be laid below shore
supply panels. Cable trays should be galvanized (GI) and Size of cable tray shall be 600mm x 100mm &
3mm thick Qty.: 220 Meter. Cable tray shall be properly fixed on concrete surface by anchoring bolt and
support angles above ground level. All cables shall be secured tightly in the tray by plastic cable tie.
6. POWER CABLES:
6.1. Electrolytic grade of Aluminium, as per IS: 8130, XLPE insulation, all sector shaped cores laid up with PP filler
and PP tape, tapped/extruded PVC inner sheath as per IS:5831, armoured as per IS: 3975, 1100 V grade cable
as per IS 7098.
6.2. CONDUCTOR: Conductor shall be stranded 16 sq.mm should have 37 strands 185 to 300 and 61 strands for
400 to 630 sq.mm cables.
6.3. INSULATION: Insulation shall be of cross linked polyethylene with IR value more than 100 Mega Ohm/Km
for power cables and shall be of PVC type A with IR value more than 50 Mega Ohm/Km for PVC cables.
XLPE: Insulation having dielectric strength between (25-30 KV/MM)
6.4. INNER SHEATH: Inner sheath with Polypropylene (PP) fillers, in case of Taped Inner sheath. For extruded
PVC inner sheath PP fillers shall be provided with a binder of PP.
6.5. ARMOUR: ISI marked armour, as per IS: 3975 should be provided over inner sheath to guard against
mechanical damage. Armour should be galvanized steel wire/strip. Round steel wire should be used where
diameter over inner sheath is less than 13 mm and flat steel strip armour when diameter over inner sheath
exceed 13 mm. Round wire can be provided on specific request. Armour coverage to be more than 95% to
achieve better mechanical projection and low armour resistance.
6.6. OUTER SHEATH: Outer sheath shall be resistant to termite and rodent attack.
6.7. XLPE/PVC AL armoured power cable conforming to IS 7098 part-1 shall be of reputed make like Nicco/
Unistar / Universal/Finolex/RR Cables/ KEI. Bidder shall submit copies of IS certification, Type Test & routine
test reports as per the relevant IS code along with the supply of cables.
a. 3.5 CX 400 SQ.MM- 500 Meter
b. 3.5C x 240 SQ.MM- 500 Meter
6.8. Cables shall be inspected prior to laying, laid tested and commissioned in accordance with drawings,
specifications, relevant Indian Standards specifications and cable manufacturer’s instructions. The cable shall
be delivered at Site in original drums with manufacturer’s name clearly written in the drum. The
recommendations of cable manufacturer with regards to jointing and sealing shall be strictly followed.
Page 22 of 116
6.9. CABLE LAYING: Cables shall be laid on ladder type GI cable tray on concrete surface and on walls of the
slipway. When laid over bracket supports, the cables shall be clamped to prevent undue sag. Cable clamps shall
be made from materials such as mild steel or Aluminum only.
6.10. Testing: All cables before laying shall be tested with 500V megger for 1.1KV grade. The cable core shall be
tested for continuity, absence of cross phase, insulation resistance to earth/sheath/armour and insulation
resistance between conductors. All cables shall be subjected to above mentioned tests during laying before
covering the cables by protective covers. In the absence of facilities for pressure testing, it is sufficient to test
for one minute with 1000V megger.
7. TERMINATION: Termination of all existing and newly laid cables with proper sizes of lugs of Dowell’s
make and cables glands are in the scope of contractor.
8. FACTORY TESTS AND INSPECTION:
The Shore Supply Distribution Panels shall be completely assembled, wired, adjusted and tested at the
factory as per the relevant standards.
Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
a) All wiring and current carrying part shall be given appropriate high voltage test.
b) Rated voltage shall be applied to all instruments.
Test Witness (Pre-dispatch inspection)
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least fifteen
(15) days advance notice of the date when tests are to be carried out.
Test Certificates
Certified reports of all the tests carried out at the works shall be furnished in three (3) copies.
The Panels shall be dispatched from the works only after clearance of the same by MDL.
9. Warranty:
The vendor shall have final and total single point responsibility for the design and performance of the
panels and all components supplied under this specification.
The supplier shall:
a) Warrant that the panels and all materials to be free from defects in design, material and workmanship.
b) Warrant that the panels will satisfy the requirements of the intended use and be suitable for the
application.
c) Agree to repair or replace any component under this warranty, which proves to be defective within a
minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items purchased by
the supplier.
10. Packing and Transportation:
The offered panels along with their accessories shall be transported to site packed in wooden crates.
They shall be wrapped with polythene sheets before being placed in the crates to prevent damage to
finish. The crates shall have skid bottom for handling. The same shall be unloaded by the contractor
at MDL site. MDL will provide only the crane facility.
11. Work Completion Period:
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing and
Commissioning of all the panels shall be completed within 5 months after placement of order.
Page 23 of 116
12. Deviation:
In the event of any deviation from this specification the same shall be clearly indicated at the time of offer
itself. No deviation will be accepted after the placement of the order.
13. Detailed Requirement of Installation:
a) Erection of new Panels shall be done on Saturdays, Sundays and Holidays and the restoration of
normal supply must be done before the beginning of the next working day.
b) All alignment, leveling, grouting, anchoring & adjustment shall be carried out in accordance with
manufacturer’s instructions and or as directed by MDL Executives.
c) All connections in new panels shall be completed and checked to ensure safety & satisfactory
operation of the Panels.
14. Site Inspection:
After completion of erection/installation each shore supply distribution panel shall be thoroughly inspected
in presence of the MDL Executives for correctness and completeness of erection and acceptability for
switching ON.
15. Testing & Commissioning:
1) After completion of erection work, tests shall be conducted by the supplier/erection contractor on each
panel.
2) The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out
field tests on the panels and materials under his scope of work.
3) These tests shall be conducted in presence of MDL Executives and according to his directions.
4) All temporary arrangements and connections required for tests shall be provided by the
contractor.
5) The contractor shall record the test results on approved format and furnish four (4) copies of the results
to MDL within a week of the date of test completed.
6) On successful inspection and testing, the equipment shall be commissioned and will be kept under
observation for a minimum period of 15 days before declaring as commissioned.
16. General Notes:
Any other activities which are not mentioned in this specification but required for the successful installation,
testing and commissioning of the panels shall be in contractor’s scope.
17. Standards & Codes:
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment and
the work covered by the scope of this contract.
(a) Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623.
(b) Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993 (Part I, II, III, IV & V).
(c) Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147:1962.
18. General Terms and Conditions:
18.1. Contractor shall visit MDL site before quoting.
18.2. Contractor and his employs must comply with MDL’s safety and security regulations.
18.3. Making of entry passes before starting of the work is in contractor’s scope.
18.4. Contractor should bring all tools & tackles required for erection of panels.
18.5. The contractor should have valid electrical contractor’s license.
19. MDL’s Scope of supply: Free compressed air, drinking water and electricity.
20. Contractor’s scope of supply: Manpower, tool & tackles, measuring instruments.
Page 24 of 116
TABLE - I
Sr.
No. Description of Item Qty. Preferred make
1 I/C MCCB 630 Amp with Microprocessor release. 13 Legrand/Siemens/L&T/Schneider
Electric/GE/ABB
2 I/C MCCB 400Amp with Microprocessor release. 6 Legrand/Siemens/L&T/Schneider
Electric/GE/ABB
3 O/G MCCB 400 Amp with thermal magnetic release. 26 Legrand/Siemens/L&T/Schneider
Electric/GE/ABB
4 O/G MCCB 200 Amp with thermal magnetic release. 12 Legrand/Siemens/L&T/Schneider
Electric/GE/ABB
5 Ladder type Cable tray with cover (GI), Size-
600mmx100mm, 3 mm thick
220 M --
6 3.5Cx400 sq. mm XLPE/PVC AL power cable 500M Nicco/Unistar/Univesal/Finolex/RR
cables / KEI of make
7 3.5Cx240 sq. mm XLPE/PVC AL power cable 500 M Nicco/Unistar/Univesal/Finolex/RR
cable/ KEI of make
8 Ring type Al. crimping lugs for 3.5Cx400 sq. mm
cable
19 set Dowells make
9 Ring type Al. crimping lugs for 3.5Cx240 sq. mm
cable
38 set Dowells make
10 Cable gland for 3.5Cx400 sq. mm cable 19 Nos. --
11 Cable gland for 3.5Cx240 sq. mm cable 38 nos. --
12 Analog Ammeter 19 0-800 Amp: 13 Nos.
0-400 Amp: 6 Nos.
13 Analog Voltmeter 19 0-500 VAC: 13 Nos.
0-250 VAC: 6 Nos.
14 Selector Switch 38 kayce
Quantity indicated is for reference only. Any additional quantity required for commissioning is in the scope
of contractor.
Page 25 of 116
Technical Offer Details Format
TABLE - II
(To be submitted by vendor)
Sr.
No.
Technical Particular Specification Deviation (if any)
1. Make of offered Panel
2. Panel Dimensions & make
3. Make of MCCBs
4. Model & Cat. No. of :
a I/C MCCB 630 A, 4P, 50 kA
b I/C MCCB 400 A, 3P, 50 kA
C O/G MCCB 400 A, 4P, 35 kA
D O/G MCCB 200 A, 3P, 35 kA
5. Protection Release catalogue no.
A I/C MCCB 630 A, 4P, 50 kA
B O/G MCCB 400 A, 4P, 50 kA
C O/G MCCB 400 A, 3P, 35 kA
D O/G MCCB 200 A, 3P, 35 kA
6. Busbar material & Size
7 Make of Cables
Page 26 of 116
ANNEXURE – 4 (for Item 6 & 7)
1. INTENT OF SPECIFICATION
This specification is intended to cover the Survey of site, Design and Manufacture, testing at manufacturer’s
works, Packing & Forwarding, Unloading, dismantling of existing panel & switches, shifting of the new Auto-
changeover Cum Power Distribution Panel to the installation site, Installation, Testing and commissioning of
1 nos. Power Distribution cum Auto-changeover Panel with 2 nos. Incoming MCCBs, 2 nos. Auto
Transfer Switches with Control Device, 1 no. Spare I/C MCCB as Specified below:
Location: Mazagon Dock Residential Area, P&O Terrace Flats
The SLD/Schematics of the required Panel is given below:
I/C bus no. 1
I/C 1 ATS 1 O/G 1 200 A 250 A, 4 P, MCCB
I/C 2
O/G 2
250 A, 4 P, MCCB
ATS 2 200 A
I/C bus no. 2
SPARE I/C
250 A, 4 P, MCCB
Page 27 of 116
Tentative General Arrangement of the Panel
The ratings of MCCBs and Auto Transfer Switches shall be as follows:
I/C MCCB for Source 1: 250 A, 4 P, 25 kA, 415 V AC MCCB with Microprocessor release having adjustable O/L,
S/C and E/F protection.
I/C MCCB for Source 2: 250 A, 4 P, 25 kA, 415V AC MCCB with Microprocessor release having adjustable O/L,
S/C and E/F protection.
Auto Source Transfer Switch (Auto Changeover Switch) with digital control device: Suitable for 200 A, 415V
AC, 4 P; Quantity: 2 nos.
Spare MCCB: 250 A, 4 P, 25 kA, 415 V AC MCCB with Microprocessor release having adjustable O/L, S/C and
E/F protection.
CABLE
ALLEY
Auto Change over
Switch
Auto Changeover
Switch
CABLE
ALLEY
Busbar Chamber
MCCB
I/C 1
250 A, 4P
MCCB
I/C 2
250 A, 4P
MCCB
SPARE
250 A, 4P
Page 28 of 116
2. SCOPE OF SUPPLY:
2.1. The scope of supply through this specification includes but not limited to the following:
2.2. Free standing Auto-changeover Panel: 1 No. (With Auto Source Transfer Switches and MCCBs as
indicated in Para no. 1 above.)
2.3. Indicating Lamps for Incoming Supply from both Sources and Outgoing Supply.
2.4. Voltmeters for both incoming supply and Ammeter for the 2 Incoming & 3 outgoing feeders.
2.5. All required double compression Nickel/Chromium plated brass cable glands and crimping type copper
lugs.
2.6. The base channel frame with hardware.
2.7. All relevant drawings and documents.
3. TECHNICAL REQUIREMENTS:
3.1. Enclosure and Protection
3.1.1. The Auto-changeover Panel and the components like Auto Transfer Switches; MCCB etc. shall be
fully conforming to respective/relevant IS standard/equivalent International standards.
3.1.2. The Auto-changeover Panel shall be metal clad and shall comprise standard prefabricated, cold
rolled, sheet steel, enclosure, free standing, unitized Panel. The minimum thickness for walls/doors
and for internal partitions/barriers shall be 14 SWG and 16 SWG respectively.
3.1.3. The Auto-changeover Panel shall be totally enclosed, dust and vermin proof. The degree of
enclosure protection shall be IP-52.
3.1.4. All doors and openings shall be provided with gaskets of durable material. The gaskets shall be held
in a groove and shall be continuous with ends fixed with adhesive material.
3.1.5. Each section of the Auto-changeover Panel shall be provided with door switch operated lamp for
illumination inside the panel. The lamp shall be suitably located to ensure visibility while working in
the panel.
3.2. CONSTRUCTIONAL FEATURES
3.2.1. Removable Eye bolt/lifting lugs shall be furnished on the panel sections. Access to all equipment,
bus bars and cable terminations shall be from front only and panel with back access is not
acceptable.
3.2.2. The Auto Source Transfer Switches and MCCBs shall be housed on a metallic plate which shall be
bolted within the Panel/Enclosure. The indicating lamps for incoming supply from both sources and
outgoing supply shall be located on the feeder compartment doors.
3.2.3. All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized
Zinc passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured against
loosening.
3.2.4. The Panel shall be designed to ensure maximum safety during operation, inspection, connection of
cables and maintenance. Means shall be provided to prevent shorting of power and/or control
terminals due to accidental dropping of maintenance tools etc. inside the distribution panel.
Checking and removal of components shall be possible without disturbing adjacent equipment.
3.2.5. Necessary bolted type gland plate of 3.15 mm thickness and Nickel/Chromium plated brass double
compression cable glands for all cable entries in the distribution panel shall be provided. Terminal
blocks shall not be used for supporting cables.
3.2.6. The panel shall be mounted on an angle frame with suitable mode of fastening. The minimum size of
the angle shall be 50mm x 50mm x6mm. The complete frame is to be supplied by the vendor duly
fabricated and painted with Powder Coated paint with oven baking of grey color. The height of the
base frame channel shall be 400 mm or more from the ground level for easy entry and termination of
cables.
Page 29 of 116
3.3. Busbars, Busbar Sizing, Connection and Supports
3.3.1. Busbars shall be made of high conductivity electrolytic grade copper, supported on insulators made
of non-hygroscopic, non-inflammable material. The busbars shall extend throughout the length of the
two sections of distribution panels and shall be of uniform cross-section. All bus joints as well as the
supports shall be designed to withstand the specified short circuit level for 1 second without
permanent deformation. Dynamic stresses shall be calculated on the basis of peak short circuit
current.
3.3.2. Busbars shall be sleeved with Fire Resistant Low Smoke PVC for full voltage insulation.
Identification rings of red, yellow, blue and black colour to identify phase and neutral busbars shall
be provided over busbar sleeves.
3.3.3. Minimum clearance between two live parts shall be 20 mm. Minimum clearance between live
parts/neutral to ground shall be 25 mm.
3.3.4. The current density for the copper shall not exceed 1000 A/sq. inch.
3.4. Power Connections
3.4.1. Power connections between the busbars and the incoming point of MCCB’s and Auto Source
Transfer Switches shall be done using suitably rated individual single core copper cable with FRLS
PVC insulation/ sleeved bus bar of required size. Bunching of cables to meet the current
requirements is not acceptable. The cables shall be terminated on the busbars and at the incoming
point using crimping type tinned copper lugs of required design.
3.5. Control Wiring and Connections
3.5.1. The distribution panels shall be pre - wired and ready for use after external cable connection. Inside
the panels, the control wiring shall be carried out using insulated copper conductors with PVC
insulation. The insulation shall be rated for minimum 600V grade irrespective of the distribution
panel voltage rating. The minimum size of conductor shall be 1.5 sq.mm. Wherever multi-strand
wires are used its ends shall be crimped in a suitably sized lug before connection.
3.5.2. Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall match
with the terminal numbers of equipment device.
3.6. Control Circuit Protection
Circuit protection shall be provided by using MCBs. Use of fuses shall not be permitted.
3.7. Earthing connections
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts
through a copper earth bus. 2 nos. earthing bolts shall be provided on the distribution panels.
3.8. Name Plates
Nameplates of approved design shall be furnished for each panel. The material shall be lamicoid or
anodized aluminum of 3 mm thick with white letter on black background. The nameplate shall be
held by self-tapping screws. Nameplates shall be of suitable size but not less than 40 x 100 mm for
panels. Caution notice on suitable metal plate shall be affixed at the back to each vertical panel.
3.9. Auto Changeover Panel Components
A) Moulded Case Circuit Breakers (MCCBs):
(i) The MCCBs/MCBs shall be of reputed make. If the supplier is offering any make other than
Legrand /Siemens /L&T /Schneider Electric /GE /ABB/Crompton, then the firm shall also submit
copies of IS certification & Type Test reports as per the relevant IS code and copies of bulk order
executed by the supplier for the above item to prove the performance of the offered make.
Page 30 of 116
(ii) M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free
mechanism.
(iii) M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload
protection and instantaneous characteristics for short circuit protection.
(iv) M.C.C.B. shall be rated for breaking the short circuit current specified for the distribution panels.
Use of back-up fuses for extending the breaking capacity is not acceptable.
(v) The circuit breakers shall comply with the requirement of IEC 60947 / IS13947:1993. The MCCBs
shall be suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
(vi) The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to be
marked as suitable for isolation / disconnection to facilitate safety of operating personnel while
the breaker is in use.
(vii) The MCCBs shall be of double break contacts.
(viii) The terminals shall be of liberal design with adequate clearances.
(ix) The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indicators.
Earth fault protection wherever specified shall be an integral part of the breaker, direct operating
type & adjustable.
(x) MCCBs shall be Fixed mounting type having front terminals connection.
B) Auto Source Transfer Switches
i. The Auto Source Transfer Switches shall be of reputed make like
SOCOMEC/Siemens/Legrand/L&T/GE or any other reputed make.
ii. The Auto Source Transfer Switches shall be suitable for Mains/Mains Application.
iii. The Auto Source Transfer Switches shall have features like:
- Automatic monitoring of the 2 supply sources.
- Shall be equipped with integrated controller for operation with/without priority, Preferred Source
Selection.
- Manual override i.e. Auto and Manual operating modes.
- Shall Have Padlocking arrangement.
- Shall have handle arrangement for manual operation to put the switch in off position or selecting
the supply in Emergency.
3.10. Miniature Circuit Breakers (MCBs) – For Control Circuit
3.10.1. The MCBs shall be of 6 Amp, 10 KA rated.
3.10.2. The MCBs shall be conforming to IS 8828: 1996.
3.11. Measuring Instruments
3.11.1. All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
3.11.2. All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for
ammeters and voltmeters. The range shall be as indicated elsewhere. Selector switches for the
meters also to be provided.
3.12. LED type Phase Indicating Lamps shall be provided on both the Incoming MCCB Cubicle of the
Panel & outgoing feeders.
4. Nil.
Page 31 of 116
5. PAINTING:
Surface Preparation: Prior to painting, surface should be free of any visible loose particles, welding
spatters or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks, cleaning of
surface with water in rising tank, acid treatment of surface with chromate and phosphate. Surface should
be suitably cleaned to achieve required finish as per relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of
primer shall be high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to be
mixed as per manufacturer specification. Paint to be applied to achieve minimum total 110-micron
DFT.
6. Factory Tests and Inspection:
The Auto Changeover Panel shall be completely assembled, wired, adjusted and tested at the factory as
per the relevant standards.
Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
a) All wiring and current carrying part shall be given appropriate high voltage test.
b) Primary current and voltage shall be applied to all instruments.
c) Routine test shall be carried out on all equipment such as circuit breakers, instrument transformers,
meters etc.
Test Witness
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least fifteen
(15) days advance notice of the date when tests are to be carried out. MDL representative may visit the
factory for stage inspection during painting of the panel to ensure that proper painting procedures are
followed by the manufacturer.
Test Certificates
Certified reports of all the tests carried out at the works shall be furnished in two (2) copies.
The Distribution Panels shall be dispatched from the works only after clearance of the same by MDL.
7. Warranty:
The vendor shall have final and total single point responsibility for the design and performance of
the panels and all components supplied under this specification.
The supplier shall:
a) Warrant that the panel and all materials to be free from defects in design, material and
workmanship.
b) Warrant that the panel will satisfy the requirements of the intended use and be suitable for the
application.
c) Agree to repair or replace any component under this warranty, which proves to be defective
within a minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items
purchased by the supplier.
8. Packing and Transportation:
The offered panel along with their accessories shall be transported to site packed in wooden crates.
It shall be wrapped with polythene sheets before being placed in the crates to prevent damage to
finish. The crates shall have skid bottom for handling. The same shall be unloaded by the contractor
at MDL site. MDL will provide only the crane facility for unloading and internal shifting (from
unloading place) to the installation site. Labour/manpower shall be in contractor’s scope.
Page 32 of 116
9. Work Completion Period:
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing and
Commissioning of the panel shall be completed within 5 months after receipt of order.
10. Deviation:
In the event of any deviation from this specification the same shall be clearly indicated at the time of offer
itself. No deviation will be accepted after the placement of the order.
11. Detailed Requirement of Installation:
a) Dismantling & removing of the existing Changeover Switches/Panel and SFU’s. Removal of
the dismantled Panels/SFU’s from the site to the scrap area at NY Power House.
b) All alignment, leveling, grouting, anchoring & adjustment, cable terminations shall be carried
out in accordance with manufacturer’s instructions and or as directed by MDL Engineers.
c) Lifting/shifting of the new panel to the location, erection of the panel shall be done by the
contractor. All connections in new panels shall be completed and checked to ensure safety &
satisfactory operation of the Panel.
12. Site Inspection:
After completion of installation, the panel shall be thoroughly inspected in presence of the MDL Engineer
for acceptability before switching ON.
13. Testing & Commissioning:
01. After completion of erection work, tests shall be conducted by the supplier/erection contractor on the
panel.
02. The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out
field tests on the panel and materials under his scope of work.
03. These tests shall be conducted in presence of MDL Engineer and according to his directions.
04. All temporary arrangements and connections required for tests shall be provided by the contractor.
05. The contractor shall record the test results on approved format and furnish four (4) copies of the
results to MDL within a week of the date of test completed.
06. On successful inspection and testing, the equipment shall be commissioned and will be kept under
observation for a minimum period of 15 days before declaring as commissioned.
14. General Notes:
Any other activities which are not mentioned in this specification but required for the successful
installation, testing and commissioning of the panel shall be in contractor’s scope.
15. Standards & Codes:
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment and
the work covered by the scope of this contract.
(a) Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623.
(b) Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993 (Part I, II, III, IV & V).
(c) Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147: 1962.
(d) IS: 4237-1982 General Requirements for Switchgear and Control gear for voltages not exceeding
1000V A.C or 1200V D.C.
(e) IS: 1897-1983 Copper strips for Electrical purposes.
(f) IS: 3618-1966 Phosphate Treatment of Iron and Steel for protection against corrosion.
(g) IS: 6005 – 1998: Code of practice for phosphating iron and steel.
(h) IS: 375-1963 and IS: 5578-1970 Marking and arrangement for Switchgear Main connections,
Auxiliary Wiring and Insulated Conductors.
(i) IS: 2032 Graphical Symbols used in electro technology.
Page 33 of 116
ANNEXURE – 5 (for Item 8 & 9)
Scope of Work and Technical Specifications for 25 nos. of OUT-DOOR Non-Draw-out A.C. Distribution
Panels
TYPES OF PANELS:-
I. Panel Type 1 (1 No. Auto-changeover Panel with 2 Nos. Incoming MCCBs and 5 Nos. of different
rating outgoing, Location: Near Plater Welder cabin (West side of RDD)):
The ratings of MCCBs and Auto Transfer Switches shall be as follows:
I/C MCCB for Source 1: 800 A, 4 P, 50 kA, 415 V AC MCCB with Microprocessor release having adjustable
O/L, S/C and E/F protection.
I/C MCCB for Source 2: 800 A, 4 P, 50 kA, 415 V AC MCCB with Microprocessor release having adjustable
O/L, S/C and E/F protection.
O/C MCCBs for Main Bus: 400 A, 4 P, 50 kA, 415 V AC MCCB with Microprocessor release having adjustable
O/L, S/C and E/F protection; Quantity: 3 nos.
O/C MCCB for Main Bus: 300 A, 4 P, 36 kA, 415 V AC MCCB with Microprocessor release having adjustable
O/L, S/C and E/F protection. Quantity: 2 nos.
Auto Source Transfer Switch with digital control device: Suitable for 800 A, 415 V AC, 4 P;
1. SCOPE OF SUPPLY:
1.1. The scope of supply through this specification includes but not limited to the following:
1.2. Free standing Auto-changeover Panel: 1 No. (With no. of Auto Source Transfer Switches and
MCCBs as indicated in Sr. No. I above).
1.3. Indicating Lamps for Incoming Supply from both Sources and Outgoing Supply.
1.4. Voltmeters for both incoming supply and Ammeter for the 2 Incoming & 3 outgoing feeders.
1.5. All required double compression Nickel/Chromium plated brass cable glands and crimping type copper
lugs.
1.6. The base channel frame with hardware. Base frame to have a rectangular frame top fixed on vertical
stands.
1.7. Set of accessories required for the operation and handling of the MCCBs and Auto Source Transfer
Switches.
1.8. Essential spares for trouble free operation of the MCCBs. All relevant drawings and documents.
2. TECHNICAL REQUIREMENTS:
2.1. Enclosure and Protection
2.1.1. The Auto-changeover Panel and the components like Auto Transfer Switches; MCCB etc. shall be
fully conforming to respective/relevant IS standard/equivalent International standards.
2.1.2. The Auto-changeover Panel shall be metal clad and shall comprise standard prefabricated, cold
rolled, sheet steel, enclosure, free standing/wall mounting, unitized Panel. The minimum thickness
for walls/doors and for internal partitions/barriers shall be 14 SWG and 16 SWG respectively.
2.1.3. The Auto-changeover Panel shall be totally enclosed, dust and vermin proof. The degree of
enclosure protection shall be IP-65.
2.1.4. All doors and openings shall be provided with gaskets of durable material. The gaskets shall be
held in a groove and shall be continuous with ends fixed with adhesive material.
2.1.5. Each section of the Auto-changeover Panel shall be provided with door switch operated lamp for
illumination inside the panel. The lamp shall be suitably located to ensure visibility while working
in the panel.
Page 34 of 116
2.2. CONSTRUCTIONAL FEATURES
2.2.1. Removable Eye bolt/lifting lugs shall be furnished on the panel sections. Access to all equipment,
bus bars and cable terminations shall be from front only and panel with back access is not
acceptable.
2.2.2. The Auto Source Transfer Switches and MCCBs shall be housed on a metallic plate which shall be
bolted within the Panel/Enclosure. The indicating lamps for incoming supply from both sources and
outgoing supply shall be located on the feeder compartment doors.
2.2.3. All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized
Zinc passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured
against loosening.
2.2.4. The Panel shall be designed to ensure maximum safety during operation, inspection, connection of
cables and maintenance. Means shall be provided to prevent shorting of power and/or control
terminals due to accidental dropping of maintenance tools etc. inside the distribution panels.
Checking and removal of components shall be possible without disturbing adjacent equipment.
2.2.5. Necessary bolted type gland plate of 3.15 mm thickness and Nickel/Chromium plated brass double
compression cable glands for all cable entries in the distribution panels shall be provided. Terminal
blocks shall not be used for supporting cables. Due to space constraint, the outgoing cable entry
may be done from top also.
2.2.6. The panel shall be mounted on an angle frame with suitable mode of fastening. The minimum size
of the angle shall be 50x50x6 mm. The complete frame is to be supplied by the vendor duly
fabricated and painted with Powder Coated paint with oven baking of grey color. The height of the
base frame channel shall be 400 mm or more from the ground level for easy entry and termination
of cables.
2.2.7. Approximate dimensions of this panel shall be 2m x 2m x 0.5m (length x width x depth) with
stand and Color of this panel shall be red. The supplier shall visit / inspect the site before
quoting and ensure that the offered panel can be accommodated in the available space. The
firm shall submit the dimensional drawings of the panel at the time of bidding itself.
2.3. Busbars, Busbar Sizing, Connection and Supports:
2.3.1. Busbars shall be made of high conductivity electrolytic grade copper, supported on insulators made
of non-hygroscopic, non-inflammable material. The busbars shall extend throughout the length of
the two sections of distribution panels and shall be of uniform cross-section. All bus joints as well
as the supports shall be designed to withstand the specified short circuit level for 1 second without
permanent deformation. Dynamic stresses shall be calculated on the basis of peak short circuit
current.
2.3.2. Busbars shall be sleeved with Fire Resistant Low Smoke PVC for full voltage insulation.
Identification rings of red, yellow, blue and black colour to identify phase and neutral busbars shall
be provided over busbar sleeves.
2.3.3. Minimum clearance between two live parts shall be 20 mm. Minimum clearance between live
parts/neutral to ground shall be 25 mm.
2.3.4. The current density for the copper shall not exceed 1000 A/sq. inch.
2.4. Power Connections
2.4.1. Power connections between the busbars and the incoming point of MCCB’s and Auto Source
Transfer Switches shall be done using suitably rated individual single core copper cable with FRLS
PVC insulation/ sleeved bus bar of required size. Bunching of cables to meet the current
requirements is not acceptable. The cables shall be terminated on the busbars and at the incoming
point using crimping type tinned copper lugs of required design.
Page 35 of 116
2.5. Control Wiring and Connections
2.5.1. The distribution panels shall be pre - wired and ready for use after external cable connection. Inside
the panels, the control wiring shall be carried out using insulated copper conductors with PVC
insulation. The insulation shall be rated for minimum 600V grade irrespective of the distribution
panel voltage rating. The minimum size of conductor shall be 1.5 sq.mm. Wherever multi-strand
wires are used; its ends shall be crimped in a suitably sized lug before connection.
2.5.2. Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall
match with the terminal numbers of equipment device.
2.6. Control Circuit Protection
Circuit protection shall be provided by using MCBs. Use of fuses shall not be permitted.
2.7. Earthing connections
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts
through a copper earth bus. 2 nos. earthing bolts shall be provided on the distribution panels.
2.8. Name Plates
Nameplates of approved design shall be furnished for each panel. The material shall be lamicoid or
anodized aluminum of 3 mm thick with white letter on black background. The nameplate shall be
held by self-tapping screws. Nameplates shall be of suitable size but not less than 40 x 100 mm for
panels. Caution notice on suitable metal plate shall be affixed at the back to each vertical panel.
2.9. Auto Changeover Panel Components
A) Moulded Case Circuit Breakers (MCCBs).
i) The MCCBs/MCBs shall be of reputed make. If the supplier is offering any make other than Legrand
/Siemens /L&T /Schneider Electric /GE /ABB/Crompton, then the firm shall also submit copies of IS
certification & Type Test reports as per the relevant IS code and copies of bulk order executed by
the supplier for the above item to prove the performance of the offered make.
ii) M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free
mechanism.
iii) M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload
protection and instantaneous characteristics for short circuit protection.
iv) M.C.C.B. shall be rated for breaking the short circuit current specified for the distribution panels. Use
of back-up fuses for extending the breaking capacity is not acceptable.
v) The circuit breakers shall comply with the requirement of IEC 60947 / IS13947:1993. The MCCBs
shall be suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
vi) The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to be
marked as suitable for isolation / disconnection to facilitate safety of operating personnel while the
breaker is in use.
vii) The MCCBs shall be of double break contacts.
viii)The terminals shall be of liberal design with adequate clearances.
ix) The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indicators.
x) Earth fault protection wherever specified shall be an integral part of the breaker, direct operating type
& adjustable.
xi) MCCBs shall be Fixed mounting type having front terminals connection.
B) Auto Source Transfer Switches
i) The Auto Source Transfer Switches shall be of reputed make like
SOCOMEC/Siemens/Legrand/L&T/GE or any other reputed make.
ii) The Auto Source Transfer Switches shall be suitable for Mains/Mains Application.
iii) The Auto Source Transfer Switches shall have features like:
- Automatic monitoring of the 2 supply sources.
Page 36 of 116
- Shall be equipped with integrated controller for operation with/without priority, Preferred Source
Selection.
- Manual override i.e. Auto and Manual operating modes
- Shall Have Padlocking arrangement.
- Shall have handle arrangement for manual operation to put the switch in off position or selecting
the supply in Emergency.
2.10. Miniature Circuit Breakers (MCBs) – For Control Circuit.
2.10.1. The MCBs shall be of 6 Amp, 10 KA rated.
2.10.2. The MCBs shall be conforming to IS 8828: 1996
2.11. Measuring Instruments
2.11.1. All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
2.11.2. All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for ammeters
and voltmeters. The range shall be as indicated elsewhere. Selector switches for the meters also to
be provided.
2.12. LED type Phase Indicating Lamps shall be provided on both the Incoming MCCB Cubicle of the Panel
& outgoing feeders.
3. PAINTING:
Surface Preparation: Prior to painting, surface should be free of any visible loose particles, welding
spatters or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks, cleaning of
surface with water in rising tank, acid treatment of surface with chromate and phosphate. Surface should
be suitably cleaned to achieve required finish as per relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of
primer shall be high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to be
mixed as per manufacturer specification. Paint to be applied to achieve minimum total 110-micron
DFT.
4. Factory Tests and Inspection:
The Auto Changeover Panel shall be completely assembled, wired, adjusted and tested at the factory as
per the relevant standards.
Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
a) All wiring and current carrying part shall be given appropriate high voltage test.
b) Primary current and voltage shall be applied to all instruments.
c) Routine test shall be carried out on all equipment such as circuit breakers, instrument transformers,
meters etc.
Test Witness
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least fifteen
(15) days advance notice of the date when tests are to be carried out. MDL representative may visit the
factory for stage inspection during painting of the panel to ensure that proper painting procedures are
followed by the manufacturer.
5. Test Certificates:
Certified reports of all the tests carried out at the works shall be furnished in six (6) copies.
The Distribution Panels shall be dispatched from the works only after clearance of the same by MDL.
Page 37 of 116
6. Warranty:
The vendor shall have final and total single point responsibility for the design and performance of
the panels and all components supplied under this specification.
The supplier shall:
a) Warrant that the panel and all materials to be free from defects in design, material and
workmanship.
b) Warrant that the panel will satisfy the requirements of the intended use and be suitable for the
application.
c) Agree to repair or replace any component under this warranty, which proves to be defective
within a minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items
purchased by the supplier.
7. Packing and Transportation:
The offered panel along with their accessories shall be transported to site packed in wooden crates.
It shall be wrapped with polythene sheets before being placed in the crates to prevent damage to
finish. The crates shall have skid bottom for handling. The same shall be unloaded by the contractor
at MDL site. MDL will provide only the crane facility for unloading and internal shifting (from
unloading place) to the installation site. Labour/manpower shall be in contractor’s scope.
8. Work Completion Period:
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing and
Commissioning of the panel shall be completed within 5 months after receipt of order.
9. Deviation:
In the event of any deviation from this specification the same shall be clearly indicated at the time of offer
itself. No deviation will be accepted after the placement of the order.
10. Detailed Requirement of Installation:
a) Dismantling & removing of the existing Changeover Switches/Panel and SFU’s. Removal of the
dismantled Panels/SFU’s from the site to the scrap area at NY Power House.
Note: Dismantling the old Panels & erection of new Panels shall be done on Saturdays, Sundays
and Holidays and the restoration of normal supply must be done before the beginning of the
next working day.
b) All alignment, leveling, grouting, anchoring & adjustment, cable terminations shall be carried out in
accordance with manufacturer’s instructions and or as directed by MDL Engineers.
c) Lifting/shifting of the new panel to the location, erection of the panel shall be done by the contractor.
All connections in new panels shall be completed and checked to ensure safety & satisfactory operation
of the Panel.
11. Site Inspection:
After completion of installation, the panel shall be thoroughly inspected in presence of the MDL Engineer
for acceptability before switching ON.
12. Testing & Commissioning:
01 After completion of erection work, tests shall be conducted by the supplier/erection contractor on the
panel.
02 The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out
field tests on the panel and materials under his scope of work.
03 These tests shall be conducted in presence of MDL Engineer and according to his directions.
04 All temporary arrangements and connections required for tests shall be provided by the contractor.
Page 38 of 116
05 The contractor shall record the test results on approved format and furnish four (4) copies of the results
to MDL within a week of the date of test completed.
06 On successful inspection and testing, the equipment shall be commissioned and will be kept under
observation for a minimum period of 15 days before declaring as commissioned.
13. General Notes:
Any other activities which are not mentioned in this specification but required for the successful
installation, testing and commissioning of the panel shall be in contractor’s scope.
14. Standards & Codes:
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment and
the work covered by the scope of this contract.
(a) Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623
(b) Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993(Part I, II, III, IV & V)
(c) Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147: 1962
(d) IS: 4237-1982 General Requirements for Switchgear and Control gear for voltages not exceeding
1000V A.C or 1200 V D.C.
(e) IS: 1897-1983 Copper strips for Electrical purposes
(f) IS: 3618-1966 Phosphate Treatment of Iron and Steel for protection against corrosion.
(g) IS: 6005 – 1998: - Code of practice for phosphating iron and steel
(h) IS: 375-1963 and IS: 5578-1970 Marking and arrangement for Switchgear Main connections,
Auxiliary Wiring and Insulated Conductors.
(i) IS: 2032 Graphical Symbols used in electro technology
Page 39 of 116
II. Panel Type 2 (8 nos. OUT-DOOR Non-Draw-out A.C. Distribution panels, Location around RDD:
8 nos. OUT-DOOR Non-Draw-out A.C. Distribution panels consisting of: -
1 no. Incoming MCCB-: 415VAC, 4Pole, 800 A, Short circuit rating minimum 50 kA, with electronic
release having adjustable overload, short-circuit and earth fault protection and having variable depth rotary
handle & connecting rod.
4 nos. Outgoing MCCB-: 415VAC, 4 Pole, 400 A, Short circuit rating minimum 35 kA, with thermal
magnetic release having adjustable overload, short-circuit protection and having variable depth rotary handle
& connecting rod.
These distribution boards shall be used for rated voltage of 415 V +/- 5 %, 3 phase, 4 wire, 50 Hz A.C.
Approximate dimensions of these type of panels shall be 2m x 1.5m x 0.5m (length x width x depth)
with stand
Color of these panel shall be red
GA DRAWING
2000mm
O/G 1
400 A
O/G 2
400 A
O/G 3
400 A
BUSBAR CHAMBER
INCOMER
800 A
O/G 4
400 A
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
Page 40 of 116
III. Panel Type 3 (4 nos. OUT-DOOR Non-Draw-out A.C. Distribution panels, Location: Ahead of
RDD Jetty and main incoming panel of Slipway):
4 nos. OUT-DOOR Non-Draw-out A.C. Distribution panels consisting of:-
1 no. Incoming MCCB-: 415VAC, 3 Pole, 1000 A, Short circuit rating minimum 65 kA, with electronic
release having adjustable overload, short-circuit and earth fault protection and having variable depth rotary
handle & connecting rod.
1 no. Outgoing MCCB-: 415VAC, 3 Pole, 800 A, Short circuit rating minimum 65 kA, with electronic
release having adjustable overload, short-circuit and earth fault protection and having variable depth rotary
handle & connecting rod.
1 no. Outgoing MCCB-: 415VAC, 4 Pole, 400 A, Short circuit rating minimum 35 kA, with thermal
magnetic release having adjustable overload, short-circuit protection and having variable depth rotary handle
& connecting rod.
These distribution boards shall be used for rated voltage of 415 V +/- 5 %, 3 phase, 4 wire, 50 Hz A.C.
1 no. Outgoing MCCB-: 415VAC, 3 Pole, 200 A, Short circuit rating minimum 36 kA, with thermal
magnetic release having adjustable overload & short-circuit protection having variable depth rotary handle
& connecting rod.
1 no. Outgoing MCCB-: 415VAC, 3 Pole, 100 A, Short circuit rating minimum 16 kA, with thermal
magnetic release having adjustable overload & short-circuit protection having variable depth rotary handle
& connecting rod.
These AC Distribution Panels shall be used for rated voltage of 415 V +/- 5 %, 3 phase, 4 wire, 50 Hz A.C.
The Panels shall be designed for Short Circuit Rating of 65 KA.
Approximate dimensions of these type of panels shall be 2m x 1.5m x 0.5m (length x width x depth)
with stand.
Color of these panel shall be red.
GA DRAWING
2000mm
O/G 1
800 A
O/G 2
400 A
O/G 3
200 A
BUSBAR CHAMBER
INCOMER
1000 A
O/G 4
100 A
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
Page 41 of 116
IV. Panel Type 4 (12 nos. Power Distribution Panel, Location: Around RDD for temporary lighting)
12 nos. Power Distribution Panel with MCCBs as mentioned below:
1 no. Incoming MCCB -: 415VAC, 4 Pole, 400 A, Short circuit rating minimum 50 kA, with electronic
release having adjustable overload, short-circuit and earth fault protection and having variable depth rotary
handle & connecting rod.
1 no. Outgoing MCCB-: 415VAC, 4 Pole, 200 A, Short circuit rating minimum 36 kA, with thermal
magnetic release having adjustable overload & short-circuit protection having variable depth rotary handle
& connecting rod.
12 nos. Outgoing MCCB-: 415VAC, 3 Pole, 63 A, Short circuit rating minimum 35 kA, with thermal
magnetic release having adjustable overload & short-circuit protection and having variable depth rotary
handle & connecting rod.
01 no. Outgoing MCCB: - 240VAC 2 Pole, 32A Short circuit rating minimum 36 kA, with thermal magnetic
release.
Approximate dimensions of these type of panels shall be 2m x 1.5m x 0.5m (length x width x depth)
with stand
Color of these panel shall be Blue.
GA DRAWING
2000mm
O/G 1
200 A
O/G 2
100 A
O/G 3
63 A
BUSBAR CHAMBER
INCOMER
400 A
O/G 4
32 A
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
HORIZONTAL
BUSBAR
CHAMBER
12 nos.
Outgoing
MCCB 3Pole
12 nos.
Outgoing
MCCB 2Pole
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
CABLE
ALLEY
Page 42 of 116
1. General Specification of All Panels (Panel type 2 to Panel type 4)
1.1. The scope of supply through this specification includes but not limited to the following:
NOTE: The arrangement of Incoming & Outgoing feeders, Busbar chamber, Cable entry boxes and
Termination is detailed in the GA Drawing shown in this specification. Equipment shall be furnished
in strict accordance with the same.
i) All Panels are free standing A.C. Distribution Panels, with specified no. of I/C & O/G MCCBs as
indicated in Panel type 2 to 4.
ii) All the incomer breaker of the panels shall have:
i) Phase indicating lamps - 3 nos. (R Y B)
ii) Suitable range ammeter with suitable range of CT
iii) Volt meter (0-500V) - 1 no.
iv) Ammeter Selector Switch - 1 no.
v) Voltmeter Selector Switch - 1 no.
vi) CTs (for metering) with CT ratio - 1 set.
iii) All required double compression Nickel/Chromium plated brass cable glands and crimping type
copper lugs.
iv) The base channel frame with hardware. Base frame to have a rectangular frame top fixed on vertical
stands.
v) Set of accessories required for the operation and handling of the breakers – 1Set for each rating of
MCCBs used in the panel.
vi) Essential spares for trouble free operation of the MCCBs.
vii) All relevant drawings and documents.
2. TECHNICAL REQUIREMENTS:
2.1. Enclosure and Protection
i) The A.C. Distribution Panel and the components like MCCB, measuring instruments etc. shall be
fully conforming to respective/relevant IS standard/equivalent International standards.
ii) The Distribution Panel shall be metal clad and shall comprise standard prefabricated, cold rolled,
sheet steel, enclosure, free standing, unitized Distribution Panel. The minimum thickness for
walls/doors and for internal partitions/barriers shall be 14 SWG and 16 SWG respectively.
iii) The distribution panels shall be totally enclosed, dust and vermin proof. The degree of enclosure
protection shall be IP-65.
iv) All doors and openings shall be provided with gaskets of durable material. The gaskets shall be held
in a groove and shall be continuous with ends fixed with adhesive material.
2.2. CONSTRUCTIONAL FEATURES
i) Removable Eye bolt/lifting lugs shall be furnished on the panels. Access to all equipment, bus bars
and cable terminations shall be from front only and panel with back access is not acceptable.
ii) The feeder modules shall be provided with compartment door with internal hinges. The compartment
doors shall be interlocked mechanically with the operating handles / knobs of MCCB’s such that the
door cannot be opened when the MCCB is in ‘ON’ condition. Defeat feature for this interlock shall
also be provided. Suitable diameter but not less than 15 mm, rotating knobs minimum 2 nos. per
door shall be provided for all doors. And main outdoor of panel shall have latch door locking
arrangement (stainless steel kundi with double locking arrangement).
iii) All the equipment inside the feeder compartment shall be housed on a metallic plate which shall be
bolted within the compartment. All instruments, push buttons, indicating lamps etc. shall be located
on the feeder compartment doors.
iv) All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized
Zinc passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured against
loosening.
Page 43 of 116
v) The Distribution Panels shall be designed to ensure maximum safety during operation, inspection,
connection of cables and maintenance. Means shall be provided to prevent shorting of power and/or
control terminals due to accidental dropping of maintenance tools etc. inside the distribution panels.
Checking and removal of components shall be possible without disturbing adjacent equipment.
vi) All power and control cables shall enter the distribution panels from bottom as specified. Necessary
bolted type gland plate of 3.15 mm thickness and Nickel/Chromium plated brass double compression
cable glands for all cable entries in the distribution panels shall be provided. Terminal blocks shall
not be used for supporting cables.
vii) The complete distribution panel shall be mounted on a C- channel and angle frame with suitable
mode of fastening. The minimum size of the C – Channel shall be 200 mm and the size of the angle
shall be 50x50x6 mm. This frame will be resting above the cable trench. The complete frame is to be
supplied by the vendor duly fabricated and painted with enamel paint of grey colour. The height of
the base frame channel shall be 15 inches from the ground level.
viii) The supplier shall visit / inspect the site before quoting and ensure that the offered panels can
be accommodated in the available space. The firm shall submit the dimensional drawings of
the distribution panel at the time of bidding itself.
2.3. Busbars, Busbar Sizing, Connection and Supports:
i) Busbars shall be made of high conductivity electrolytic grade copper, supported on insulators
made of non-hygroscopic, non-inflammable material. The busbars shall extend throughout the length
of the distribution panels and shall be of uniform cross-section. All bus joints as well as the supports
shall be designed to withstand the specified short circuit level for 1 second without permanent
deformation. Dynamic stresses shall be calculated on the basis of peak short circuit current.
ii) Busbars shall be sleeved with Fire Resistant Low Smoke PVC for full voltage insulation.
Identification rings of red, yellow, blue and black colour to identify phase and neutral busbars shall
be provided over busbar sleeves.
iii) Minimum clearance between two live parts shall be 30 mm. Minimum clearance between live
parts/neutral to ground shall be 35 mm.
iv) The current density for the copper shall not exceed 1000 A/sq. inch.
2.4. Power Connections:
i) Power connections between the busbars and the incoming point of MCCB’s module shall be done
using suitably rated individual single core copper cable with FRLS PVC insulation/ sleeved bus bar
of required size. Bunching of cables to meet the current requirements is not acceptable. The cables
shall be terminated on the busbars and at the incoming point using crimping type tinned copper lugs
of required design.
ii) For all the O/G MCCBs, the terminals are to be brought at the bottom of the panel. The terminations
of the O/G cables shall be done at these terminals. This is to bring all the cable terminations at the
bottom of the Shore Supply Panels.
Horizontal Busbar arrangement (of required current rating) with proper supports shall be provided at
the bottom of the panel for Incomer & Outgoing cable connections.
2.5. Control Wiring and Connections:
i) The distribution panels shall be pre - wired and ready for use after external cable connection. Inside
the panels, the control wiring shall be carried out using insulated copper conductors with PVC
insulation. The insulation shall be rated for minimum 600V grade irrespective of the distribution
panel voltage rating. The minimum size of conductor shall be 2.5 sq.mm. Wherever multi-strand
wires are used, its ends shall be crimped in a suitably sized lug before connection.
ii) Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall match
with the terminal numbers of equipment device.
Page 44 of 116
2.6. Control Circuit Protection:
Circuit protection shall be provided by using MCBs. Use of fuses shall not be permitted.
2.7. Earthing connections:
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts
through a copper earth bus. 2 nos. earthing bolts shall be provided on the distribution panels.
2.8. Name Plates:
Nameplates of approved design shall be furnished for each panel. The material shall be lamicoid or
anodized aluminium of 3 mm thick with white letter on black background. The nameplate shall be held
by self-tapping screws. Nameplates shall be of suitable size but not less than 40 x 100 mm for panels.
Caution notice on suitable metal plate shall be affixed at the back to each vertical panel.
2.9. Distribution Panel Components:
A) Moulded Case Circuit Breakers (MCCBs):
i) The MCCBs shall be of reputed make. If the supplier is offering any make other than
Legrand /Siemens /L&T /Schneider Electric /GE /ABB /Crompton, then the firm shall also
submit copies of IS certification & Type Test reports as per the relevant IS code and copies of
bulk order executed by the supplier for the above item to prove the performance of the offered
make.
ii) M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free
mechanism.
iii) M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload
protection and instantaneous characteristics for short circuit protection.
iv) M.C.C.B. shall be rated for breaking the short circuit current specified for the distribution
panels. Use of back-up fuses for extending the breaking capacity is not acceptable.
v) The circuit breakers shall comply with the requirement of IEC 60947 / IS13947:1993. The
MCCBs shall be suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
vi) The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to
be marked as suitable for isolation / disconnection to facilitate safety of operating personnel
while the breaker is in use.
vii) The MCCBs shall be of double break contacts.
viii) The terminals shall be of liberal design with adequate clearances.
ix) The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indicators.
x) Earth fault protection wherever specified shall be an integral part of the breaker, direct
operating type & adjustable.
xi) MCCBs shall be Fixed mounting type having front terminals connection.
B) Miniature Circuit Breakers (MCBs)
i) The MCBs shall be of 6 Amp, 10 KA rated.
ii) The MCBs shall be conforming to IS 8828: 1996.
2.10. Measuring Instruments
i) All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
ii) All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for
ammeters and voltmeters. The range shall be as indicated elsewhere. Selector switches for the
meters also to be provided.
2.11. LED type Phase Indicating Lamps shall be provided on the Incoming MCCB Cubicle of each
Distribution Panel.
Page 45 of 116
3. PAINTING:
Surface Preparation: Prior to painting, surface should be free of any visible loose particles,
welding spatters or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks,
cleaning of surface with water in rising tank, acid treatment of surface with chromate and phosphate.
Surface should be suitably cleaned to achieve required finish as per relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of
primer shall be high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to
be mixed as per manufacturer specification. Paint to be applied to achieve minimum total 110-
micron DFT.
4. Factory Tests and Inspection:
The Distribution Panels shall be completely assembled, wired, adjusted and tested at the factory as per
the relevant standards.
Type Tests
The offered panels / components shall be type tested for the following type tests and the copies of the
test reports for the type tests carried out on similar and identical type of panels / components shall be
submitted at the time of offer itself to prove the design.
a) Temperature rise test for panel / MCCBs.
b) Short Circuit withstand test for panel for 50 KA/ MCCBs.
c) Test for IP 65 for enclosure.
Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
d) All wiring and current carrying part shall be given appropriate high voltage test.
e) Primary current and voltage shall be applied to all instruments.
f) Routine test shall be carried out on all equipment such as circuit breakers, instrument transformers,
meters, etc.
g) Primary injection test to check the CT ratio and ammeter.
Test Witness
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least
fifteen (15) days advance notice of the date when tests are to be carried out. MDL representative may
visit the factory for stage inspection during painting of the panel to ensure that proper painting
procedures are followed by the manufacturer.
Test Certificates
Certified reports of all the tests carried out at the works shall be furnished in six (6) copies.
The Distribution Panels shall be dispatched from the works only after clearance of the same by MDL.
5. Warranty:
The vendor shall have final and total single point responsibility for the design and performance
of the panels and all components supplied under this specification.
The supplier shall:
a) Warrant that the panels and all materials to be free from defects in design, material and
workmanship.
b) Warrant that the panels will satisfy the requirements of the intended use and be suitable for
the application.
Page 46 of 116
c) Agree to repair or replace any component under this warranty, which proves to be defective
within a minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items
purchased by the supplier.
6. Packing and Transportation:
The offered panels along with their accessories shall be transported to site packed in wooden
crates. They shall be wrapped with polythene sheets before being placed in the crates to prevent
damage to finish. The crates shall have skid bottom for handling. The same shall be unloaded
by the contractor at MDL site. MDL will provide only the crane facility for unloading and
internal shifting (from unloading place) to the installation site.
7. Work Completion Period:
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing
and Commissioning of all the panels shall be completed within 5 months after receipt of order.
8. Deviation:
In the event of any deviation from this specification the same shall be clearly indicated at the
time of offer itself. No deviation will be accepted after the placement of the order.
9. Detailed Requirement of Installation:
a) Dismantling the existing Panels.
Note: Dismantling the old Panels & erection of new Panels shall be done on Saturdays, Sundays
and Holidays and the restoration of normal supply must be done before the beginning of the next
working day.
b) All alignment, leveling, grouting, anchoring & adjustment, cable terminations shall be carried out
in accordance with manufacturer’s instructions and or as directed by MDL Engineers.
c) All connections in new panels shall be completed and checked to ensure safety & satisfactory
operation of the Panels.
10. Site Inspection:
After completion of erection/installation each distribution panel shall be thoroughly inspected in
presence of the MDL Engineer for correctness and completeness of erection and acceptability
for switching ON.
11. Testing & Commissioning:
01 After completion of erection work, tests shall be conducted by the supplier/erection contractor on
each panel.
02 The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out
field tests on the panels and materials under his scope of work.
03 These tests shall be conducted in presence of MDL Engineer and according to his directions.
04 All temporary arrangements and connections required for tests shall be provided by the contractor.
05 The contractor shall record the test results on approved format and furnish four (4) copies of the
results to MDL within a week of the date of test completed.
06 On successful inspection and testing, the equipment shall be commissioned and will be kept under
observation for a minimum period of 15 days before declaring as commissioned.
12. General Notes:
Any other activities which are not mentioned in this specification but required for the successful
installation, testing and commissioning of the distribution panels shall be in contractor’s scope.
Page 47 of 116
13. Standards & Codes:
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment
and the work covered by the scope of this contract.
(a) Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623.
(b) Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993(Part I, II, III, IV & V).
(c) Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147: 1962.
(d) IS: 4237-1982 General Requirements for Switchgear and Control gear for voltages not
exceeding 1000V A.C or 1200 V D.C.
(e) IS: 2147-1962 Degree of Protection provided by enclosures for low voltage switchgear and
control gear.
(f) IS: 1897-1983 Copper strips for Electrical purposes.
(g) IS: 3618-1966 Phosphate Treatment of Iron and Steel for protection against corrosion.
(h) IS: 6005 – 1998: Code of practice for phosphating iron and steel.
(i) IS: 375-1963 and IS: 5578-1970 Marking and arrangement for Switchgear Main connections,
Auxiliary Wiring and Insulated Conductors.
(j) IS: 2032 Graphical Symbols used in electro technology.
Summary Table for Type of Panels
Sr.
no.
Type of Panel No. of
Panels
No. of incomer
& current
rating
No. of Outgoing and
current rating
Colour of
Panel
1 1 No. Auto-changeover
Panel
01 (One ) 2nos. & 800A 5nos. (3nos. 400A & 2
nos. 300A)
RED
2 OUT-DOOR Non-
Draw-out A.C.
Distribution panels
8 (Eight) 1no. & 800A 4 nos. & 400A each RED
3 OUT-DOOR Non-
Draw-out A.C.
Distribution panels
4 (Four) 1no. & 1000A 4 nos. (1 no. 800A, 1no.
400A, 1no. 200A &
1no. 100A )
RED
4 OUT-DOOR Non-
Draw-out A.C.
Distribution panels
12
(Twelve)
1 no. & 400A 3 nos. (1 no.
200A,12no. 63A (12
way DB), & 1no. 32A )
Blue
Page 48 of 116
ANNEXURE – 6 (for Item 10 & 11)
Scope of Work
1. INTENT OF SPECIFICATION
This specification is intended to cover the Survey of site, Design and Manufacture, testing at manufacturer’s
works, Packing & Forwarding, Unloading, dismantling of existing panel, shifting of the new panel to the
installation site, Installation, Testing and commissioning of 10 nos. Power Distribution Panel with MCCBs
of ratings specified below:
The no. of I/C and O/G MCCB shall be as follows:
1 no. Incoming MCCB -: 415VAC, 4 Pole, 630 A, Short Circuit rating minimum 50 kA, with Microprocessor
based protection release having adjustable overload, short-circuit and earth fault protection and having variable
depth rotary handle & connecting rod.
3 nos. Outgoing MCCB-: 415VAC, 4 Pole, 200 A, Short circuit rating minimum 50 kA, with thermal magnetic
release having adjustable overload & short-circuit protection and having variable depth rotary handle &
connecting rod.
1 nos. Outgoing MCCB-: 415VAC, 4 Pole, 315 A, Short circuit rating minimum 50 kA, with thermal magnetic
release having adjustable overload & short-circuit protection and having variable depth rotary handle &
connecting rod.
The panels are to be installed at Mogul Dry Dock at South Yard of MDL.
2. SCOPE OF SUPPLY
2.1 The scope of supply through this specification includes but not limited to the following:
2.2 Free standing A.C. Distribution Panel: 10 Nos. (With no. of I/C & O/G MCCBs as indicated in sr. no.
1 above.)
2.3 The Incomer breaker of the panel shall have:
1. Phase indicating lamps at Incoming Side. - 3 nos. (R Y B)
2. Ammeter (0-800A) suitable for CT ratio 800/5A - 1 no.
3. Volt meter (0-500V) - 1 no.
4. Ammeter Selector Switch - 1 no.
5. Voltmeter Selector Switch - 1 no.
6. CTs (for metering) with CT ratio 800/5 - 3 nos.
The outgoing breakers of the panels shall have indicating lamps – 1 each for On, Off and Trip
indication.
Page 49 of 116
2.4 All required double compression Nickel/Chromium plated brass cable glands and crimping type copper
lugs.
2.5 The base channel frame with hardware.
2.6 Set of accessories required for the operation and handling of the breakers – 1 Set for each MCCB used in
the panel.
2.7 Essential spares for trouble free operation of the MCCBs. All relevant drawings and documents.
2.8 Cable entry boxes with required sized bus links for termination of Incoming Feeder cables. The cables for
Incoming feeder are short and will need a Cable Entry Box with extension Bus-Links of suitable sizing.
Same needs to be supplied with the panel.
2.9 Out of 10, 9 Panels will be of RED colour while 1 panel will have BLUE colour.
3. TECHNICAL REQUIREMENTS
3.1 Enclosure and Protection
3.1.1 The A.C. Distribution Panel and the components like MCCB, MCB measuring instruments etc. shall be
fully conforming to respective/relevant IS standard/equivalent International standards.
3.1.2 The Distribution Panel shall be metal clad, on MS Angle Iron framework and shall comprise standard
prefabricated, cold rolled, sheet steel, hot dip galvanized enclosure, free standing, unitized Distribution
Panel. The minimum thickness for walls/doors and for internal partitions/barriers shall be 14 SWG and 16
SWG respectively.
3.1.3 The distribution panel shall be totally enclosed, dust and vermin proof. The degree of enclosure protection
shall be IP-65. As the panel will be installed in open area exposed to rain, a canopy to be provided at the
top of the panel. The S.C. withstand strength of the panel shall be 50 kA.
3.1.4 All doors and openings shall be provided with gaskets of durable material. The gaskets shall be held in a
groove and shall be continuous with ends fixed with adhesive material.
3.2 CONSTRUCTIONAL FEATURES
3.2.1 Removable Eye bolt/lifting lugs shall be furnished on the panel. Access to all equipment, bus bars and
cable terminations shall be from front only and panel with back access is not acceptable.
3.2.2 The feeder modules shall be provided with compartment door with internal hinges. The compartment doors
shall be interlocked mechanically with the operating handles / knobs of MCCB’s such that the door
cannot be opened when the MCCB is in ‘ON’ condition. Defeat feature for this interlock shall also be
provided. Suitable diameter but not less than 15 mm, rotating knobs minimum 2 nos. per door shall be
provided for all doors. The door locking arrangement for panel main door shall be of latched type.
3.2.3 All the equipment inside the feeder compartment shall be housed on a metallic plate which shall be bolted
within the compartment. All instruments, push buttons, indicating lamps etc. shall be located on the feeder
compartment doors.
3.2.4 All hardware shall be corrosion resistant. All joints and connections shall be made by galvanized Zinc
passivated or cadmium plated high tensile strength steel bolts, nuts and washers secured against loosening.
3.2.5 The Distribution Panel shall be designed to ensure maximum safety during operation, inspection,
connection of cables and maintenance. Means shall be provided to prevent shorting of power and/or control
Page 50 of 116
terminals due to accidental dropping of maintenance tools etc. inside the distribution panel. Checking and
removal of components shall be possible without disturbing adjacent equipment.
3.2.6 Necessary bolted type gland plate of 3.15 mm thickness and Nickel/Chromium plated brass double
compression cable glands for all cable entries in the distribution panel shall be provided. Terminal blocks
shall not be used for supporting cables.
3.2.7 The complete distribution panel shall be mounted on an angle frame with suitable mode of fastening. The
minimum size of the angle shall be 50x50x6 mm. The complete frame is to be supplied by the vendor duly
fabricated and painted with Powder Coated paint with oven baking of grey/black color. The height of the
base frame channel shall be 500 mm or more from the ground level for easy entry and termination of
cables.
3.3 Busbars, Busbar Sizing, Connection and Supports
3.3.1 Busbars shall be made of high conductivity electrolytic grade copper, supported on insulators made of
non-hygroscopic, non-inflammable material. The busbars shall extend throughout the length of the two
sections of distribution panels and shall be of uniform cross-section. All bus joints as well as the supports
shall be designed to withstand the specified short circuit level for 1 second without permanent deformation.
Dynamic stresses shall be calculated on the basis of peak short circuit current.
3.3.2 Busbar Chambers: The Horizontal and Vertical Busbars shall be placed in busbar chambers and busbars
shall be easily accessible.
3.3.3 Busbars shall be sleeved with Fire Resistant Low Smoke PVC for full voltage insulation. Identification
rings of red, yellow, blue and black colour to identify phase and neutral busbars shall be provided over
busbar sleeves.
3.3.4 Minimum clearance between two live parts shall be 20 mm. Minimum clearance between live parts/neutral
to ground shall be 25 mm.
3.3.5 The current density for the copper shall not exceed 1000 A/sq. inch.
3.4 Control Wiring and Connections
3.4.1 The distribution panels shall be pre - wired and ready for use after external cable connection. Inside the
panels, the control wiring shall be carried out using insulated copper conductors with PVC insulation. The
insulation shall be rated for minimum 600V grade irrespective of the distribution panel voltage rating. The
minimum size of conductor shall be 1.5 sq.mm. Wherever multi-strand wires are used; its ends shall be
crimped in a suitably sized lug before connection.
3.4.2 Each wire shall be identified at both ends by PVC ferrules. The identifying wire numbers shall match with
the terminal numbers of equipment device.
3.5 Control Circuit Protection
Circuit protection shall be provided by using MCBs. Use of fuses shall not be permitted.
3.6 Earthing connections
Provision shall be provided for carrying out the earthing of all non-current carrying metallic parts through
a copper earth bus. 2 nos. earthing bolts shall be provided on both sides of the distribution panel.
Page 51 of 116
3.7 Name Plates
Nameplates of approved design shall be furnished for the panel. The material shall be lamicoid or anodized
aluminum of 3 mm thick with white letter on black background. The nameplate shall be held by self-
tapping screws. Nameplates shall be of suitable size but not less than 40 x 100 mm for panel. Caution
notice on suitable metal plate shall be affixed at the back to each vertical panel.
3.8 Distribution Panel Components
Moulded Case Circuit Breakers (MCCBs).
3.8.1 The MCCBs/MCBs shall be of reputed make. If the supplier is offering any make other than Legrand
/Siemens /L&T /Schneider Electric /GE /ABB /Crompton, then the firm shall also submit copies of IS
certification & Type Test reports as per the relevant IS code and copies of bulk order executed by the
supplier for the above item to prove the performance of the offered make.
3.8.2 M.C.C.B. shall be provided with spring assisted quick make/break manually operated trip free mechanism.
3.8.3 M.C.C.B. shall be provided with tripping device with inverse time characteristics for overload protection
and instantaneous characteristics for short circuit protection.
3.8.4 The circuit breakers shall comply with the requirement of IEC 60947 / IS13947:1993. The MCCBs shall
be suitable for nominal voltage of 3 phase, 415 VAC ± 5%, 50 Hz supply.
3.8.5 The circuit breaker shall comply with the isolation function of IEC 60947-2 section 7.1.2 to be marked
as suitable for isolation / disconnection to facilitate safety of operating personnel while the breaker is in
use.
3.8.6 The operating handle of the MCCBs shall have suitable ON, OFF & TRIPPED indication.
3.8.7 Earth fault protection wherever specified shall be an integral part of the breaker, direct operating type &
adjustable.
3.8.8 MCCBs shall be Fixed mounting type having front terminals connection.
3.9 Miniature Circuit Breakers (MCBs) – For Control Circuit.
3.9.1 The MCBs shall be of 6 Amp, 10 KA rated.
3.9.2 The MCBs shall be conforming to IS 8828: 1996
3.10 Measuring Instruments
3.10.1 All measuring instruments shall be 96 mm x 96 mm square pattern, flush mounting type.
3.10.2 All ammeters and voltmeters shall be moving iron type. Accuracy class shall be 1.5 for ammeters and
voltmeters. The range shall be as indicated elsewhere. Selector switches for the meters also to be provided.
3.10.3 LED type Phase Indicating Lamps shall be provided on the Incoming MCCB Cubicle of each Distribution
Panel.
4. PAINTING Surface Preparation: Prior to painting, surface should be free of any visible loose particles, welding
spatters or foreign bodies. 7/9 tank treatment for removal of grease in the degreasing tanks, cleaning of
surface with water in rising tank, acid treatment of surface with chromate and phosphate. Surface should
be suitably cleaned to achieve required finish as per relevant standards.
Page 52 of 116
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of primer
shall be high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to be mixed as
per manufacturer specification. Paint to be applied to achieve minimum total 110-micron DFT.
5. Factory Tests and Inspection
The Distribution Panels shall be completely assembled, wired, adjusted and tested at the factory as per the
relevant standards.
5.1 Routine Test (as per IS 13947:1993)
The tests shall include but not necessarily be limited to the following:
a) All wiring and current carrying part shall be given appropriate high voltage test.
b) Primary current and voltage shall be applied to all instruments.
c) Routine test shall be carried out on all equipment such as circuit breakers, instrument
transformers, meters etc.
5.2 Pre-Dispatch Inspection
All tests shall be performed in presence of MDL’s representatives. The contractor shall give at least fifteen
(15) days advance notice of the date when tests are to be carried out.
5.3 Test Certificates
Certified reports of all the tests carried out at the works shall be furnished in 3 copies.
The Distribution Panel shall be dispatched from the works only after clearance of the same by MDL.
6. Warranty
The vendor shall have final and total single point responsibility for the design and performance of the
panels and all components supplied under this specification. The supplier shall
a) Warrant that the panels and all materials to be free from defects in design, material and
workmanship.
b) Warrant that the panel will satisfy the requirements of the intended use and be suitable for the
application.
c) Agree to repair or replace any component under this warranty, which proves to be defective
within a minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items purchased
by the supplier.
7. Packing and Transportation
The offered panel along with their accessories shall be transported to site properly packed and secured. The
same shall be unloaded by the contractor at MDL site. MDL will provide only the crane facility for unloading
and internal shifting (from unloading place) to the installation site. Labour/manpower shall be in contractor’s
scope.
8. Work Completion Period
The Design, Manufacture, testing at factory, Packing & forwarding, Installation at site, Testing and
Commissioning of the panel shall be completed within 5 months after receipt of order.
Page 53 of 116
9. Deviation
In the event of any deviation from this specification the same shall be clearly indicated at the time of offer
itself. No deviation will be accepted after the placement of the order.
10. Detailed Requirement of Installation
a) Dismantling & removing of the existing Panel and SFU’s. Removal of the dismantled Panel/SFU’s
from the site to the scrap area at MDL.
Note: Dismantling the old Panel & erection of new Panel shall be done on Saturday, Sunday and Holiday
and the restoration of normal supply must be done before the beginning of the next working day.
b) All alignment, leveling, grouting, anchoring & adjustment, cable terminations shall be carried out
in accordance with manufacturer’s instructions and or as directed by MDL Executives.
c) Lifting/shifting of the new panel to the location, erection of the panel shall be done by the
contractor. All connections in new panels shall be completed and checked to ensure safety &
satisfactory operation of the Panels.
d) While designing the panel, due care shall be taken considering the available length of Incoming and
Outgoing cables for termination. Cable entry boxes with required sized bus links for termination of
Incoming Feeder cables. The cables for Incoming feeder are short and will need a Cable Entry Box
with extension Bus-Links of suitable sizing. Same needs to be supplied with the panel.
11. Site Inspection
After completion of erection/installation each distribution panel shall be thoroughly inspected in presence of
the MDL Engineer for correctness and completeness of erection and acceptability for switching ON.
12. Testing & Commissioning
01 After completion of erection work, tests shall be conducted by the supplier/erection contractor on each
panel.
02 The contractor shall provide all tools, materials, labour and supervisory personnel for carrying out field
tests on the panels and materials under his scope of work.
03 These tests shall be conducted in presence of MDL Engineer and according to his directions.
04 All temporary arrangements and connections required for tests shall be provided by the contractor.
05 The contractor shall record the test results on approved format and furnish four (4) copies of the results
to MDL within a week of the date of test completed.
06 On successful inspection and testing, the equipment shall be commissioned and will be kept under
observation for a minimum period of 15 days before declaring as commissioned.
13. General Notes
Any other activities which are not mentioned in this specification but required for the successful installation,
testing and commissioning of the distribution panels shall be in contractor’s scope.
14. Standards & Codes
Updated and current Indian Standard Specifications and Codes of Practice will apply to the equipment and
the work covered by the scope of this contract.
Low Voltage Switchgear Assemblies: IEC 60439 / IS 8623
Page 54 of 116
Low Voltage Switchgear & Control Gear: IEC60947 /IS 13947:1993 (Part I, II, III, IV & V)
Degree of Protection of Enclosures for Low Voltage Switchgear: IEC 60529 / IS 2147: 1962
IS: 4237-1982 General Requirements for Switchgear and Control gear for voltages not exceeding 1000V
A.C or 1200 V D.C.
IS: 2147-1962 Degree of Protection provided by enclosures for low voltage switchgear and control gear.
IS: 1897-1983 Copper strips for Electrical purposes.
IS: 3618-1966 Phosphate Treatment of Iron and Steel for protection against corrosion.
IS: 6005 – 1998: - Code of practice for phosphating iron and steel.
IS: 375-1963 and IS: 5578-1970 Marking and arrangement for Switchgear Main connections, Auxiliary
Wiring and Insulated Conductors.
IS: 2032 Graphical Symbols used in electro technology.
Technical Offer Details Form
Sr.No. Technical Particular Specification Deviation (if any)
1. Make of offered Panel
2. Make of MCCBs
3. Model & Cat. No. of :
I/C MCCB 630 A, 4P, 50 kA
O/C MCCB 315 A, 4P, 50 kA
O/G MCCB 200 A, 4P, 50 kA
O/G MCCB 200 A, 4P, 50 kA
O/G MCCB 200 A, 4P, 50 kA
4. Protection Release catalogue no.
I/C MCCB 630 A, 4P, 50 kA
O/G MCCB 315 A, 4P, 50 kA
O/G MCCB 200 A, 4P, 50 kA
O/G MCCB 200 A, 4P, 50 kA
O/G MCCB 200 A, 4P, 50 kA
5. Bus bar material & Size
6. Panel Dimensions
Page 55 of 116
ANNEXURE – 7 (for Item 12 & 13)
Scope of work
This specification is intended to cover the following:
PART I- Survey of Site, Design, Manufacture, testing at manufacturer’s works, Packing &
Forwarding, Installation at site, Testing and commissioning of 1 No. 415 V L.T Panel
(PCC).
PART II- Supply and installation of 1 no. 1600 A, 65 kA, 3 P Schneider Electric make ACB and
installation of the same in existing LT Panel of Schneider Electric make (Blokset) with
necessary busbar modification.
PART III- Supply, laying (including civil works, excavation & reinstating) and termination of 4 nos.
3.5 C x 400 sq. mm. PVC/XLPE Al. cable.
Detailed Specifications
PART I
SPECIFICATION FOR 415 VOLT POWER CONTROL CENTRE (PCC)
This specification is intended to cover the Survey of site, Design, Manufacture, testing at
manufacturer’s works, Packing & Forwarding, Installation at site, Testing and commissioning of
1 Nos. 415 V LT Switchboard consisting of:
1 no. Incoming ACB:- 415 V AC, 4 Pole, 1600 A, S.C. rating minimum 65 KA
2 nos. Outgoing ACB : - 415 V AC, 3 Pole, 1000 A, S.C. rating minimum 65 KA
1. Scope of Supply
2.1. One No. 415 Volts Power Control Centre (PCC).
2.2. The base channel frame of the Power Control Centre (PCC) with hardware.
The Channel frame will be mounted on a cable trench for easy cable entry. Preparation,
digging, brickwork etc. for the trench under the panel is in vendor’s scope.
2.3. Set of accessories required for the operation and handling of the breakers -1Set
2.5. Essential spares for trouble free operation of the panel for a period of 5 Years.
2.6. All relevant drawings, documents and instruction manuals.
2. Design Criteria
2.1. The 415V PCC will be used to supply power to Pipe Shop and nearby Office Buildings
at North yard.
2.2. The 415V PCC will be located in a clean but hot, humid and tropical atmosphere.
2.3. For continuous operation at specified ratings, temperature rise of the various PCC
components shall be limited to the permissible values stipulated in the relevant standards
and/or this specification.
2.4. The 415V PCC and components there of shall be capable of withstanding the Mechanical
forces and thermal stresses of the short circuit current level specified in this specification
without any damage or deterioration of material.
2.5. The 415V PCC shall be floor mounted, dead from the front, free standing, vertical, cubicle
/ panel type, completely wired having hinged access doors with locking type catch.
Page 56 of 116
3.0 Specification Requirement General
3.1 The LT switch boards shall be manufactured as per the relevant Indian and International
Standards. The Air Circuit Breakers and components in the Panel shall be of Siemens
/ABB /Crompton Greaves /Schneider/GE/ L&T. All the components in the panel like
meters, indicating lamps, instrument transformers, relays etc. shall be of reputed make.
The panel shall be manufactured with sheet steel prepared using CNC Machines for
accurate cutting, bending and drilling etc. The sheet metal shall be pre-treated before
painting. The assembly of the panels shall be with new techniques for easy removal and
refitting of the components. The panel shall have a high degree of reliability and safety
of the operating personnel.
For operator safety and for easy maintenance work, IP2X (touch proof) protection shall
be available even after opening the rear and side doors of the panel.
The components of identical feeders should be fully compatible to each other. The panel
manufactured shall be fully conforming to the following standards.
IS 8623-Part -1 1993: - Specification for low voltage switchgear and control gear
assemblies.
IEC: 439 -1 1985 Low Voltage Switchgear and Control gear Assemblies.
IS: 4237-1982 General Requirements for Switchgear and Control gear for voltages not
exceeding 1000V A.C or 1200 V D.C.
IS: 2147-1962 Degree of Protection provided by enclosures for low voltage switchgear
and control gear.
IS: 1897-1983 Copper strips for Electrical purposes.
IS: 3618-1966 Phosphate Treatment of Iron and Steel for protection against corrosion.
IS: 6005 – 1998:- Code of practice for phosphating iron and steel.
IS: 375-1963 and IS: 5578-1970 Marking and arrangement for Switchgear Main
connections, Auxiliary Wiring and Insulated Conductors.
IS: 2032 Graphical Symbols used in electro technology.
3.2 Constructional Features of Panels
The panel shall be of bolted construction, without any exposed welding to avoid rusting.
Heavy gauge “U” profile sheet steel shall be used for the framework to make the structure
sturdy. The various parts of the sheet metal enclosure shall be made out of sheet steel of
adequate thickness to have sufficient strength. The panel shall be with form 4B with
metallic shroud.
The sheet steel components shall be thoroughly degreased, derusted and hot dip
phosphatised before the painting. The paint shall be either alkyd melamine epoxy resin
based paint or epoxy based powder sprayed on the surface under electrostatic process at
60/90KV. The painted panels shall be oven dried to provide a smooth surface with
qualities like scratch resistance high corrosion resistance and ductility. The outside and
the inside surfaces of the panels shall be painted in a single tone shade pebble grey, RAL
7032 as per DIN / RAL 9002.
The 415V PCC shall be indoor, air insulated, metal clad, floor mounting, draw out type.
The design and construction shall be such as to allow extension at either end.
Page 57 of 116
PCC enclosure shall conform to the degree of protection IP-52. Minimum thickness of
sheet metal used for load bearing members shall be 2mm.Removable Eye bolt/lifting lugs
shall be furnished on the panels.
The design shall be fully compartmentalized execution with metal/insulating partition.
Working height shall be limited to 1800 mm from the floor level.
Each breaker shall be housed in a separate cubicle, complete with an individual front
access door. Each vertical section shall have a removable back cover.
Metal based neoprene gaskets shall be provided between adjacent units and beneath all
the doors and covers to render the panel dust and vermin proof and to provide a degree
of protection IP 52.
PCC cubicle shall be so sized as to permit closing of the front access door when the
breaker is pulled out to ISOLATED position.
All switches, lamps, indicating instruments shall be flush mounted on the respective
cubicle door whereas relays and other auxiliary devices may be mounted on a separate
cubicle.
Each vertical section shall be provided with a rear cable chamber housing the cable end
connections. There should be generous availability of space for ease of maintenance with
adequate safety for working in one vertical section without coming into contact with any
live parts.
3.3 Horizontal Busbar Chamber
The main horizontal bus bars shall run in a separate fully enclosed busbar compartment
provided at the top of each panel. The busbar compartment shall be fully segregated from
other compartments. The main busbars (R.Y.B & N) shall be arranged in horizontal
configuration one behind the other only. The earth busbar shall be provided at the bottom
of the panel. This compartment should be provided with bolted covers at the top, front
and rear.
The horizontal busbars shall be of hard drawn high conductivity, high strength and
electrolytic grade copper strips with maximum temperature limited to 850C (i.e. 350C rise
over 500C ambient). The current density of copper should not exceed 1000A/sq.inch. The
certification for conductivity of the copper shall be made available from third party
certifying agency.
The bus bars shall be easily accessible after unbolting the bolted covers for maintenance
like tightening of connections, etc.
The horizontal busbar compartment shall be completely independent from the other
feeder compartments for accessibility i.e. the other feeder compartments need not be
disturbed for approaching main bus bars.
Sufficient space shall be provided around and above bus bars for better heat dissipation
and also to ensure uniform temperature rise in all the busbars.
The total enclosure as well as the location shall rule out any possibility of an arc on the
busbars damaging any feeder modules or auxiliary equipment adjacent to bus bars.
Sufficient clearance as per IS/IEC Standard shall be maintained between phase busbars
and between phase busbars and ground.
Page 58 of 116
The main horizontal busbars shall be of electrolytic grade copper conforming to IS 1897 -1983.
The busbars shall be tinned.
These bus bars shall be supported at regular intervals by fiberglass reinforced polyester (FRP)
insulators which have the following properties:
a. High impact and tensile strength
b. Very high tracking index, class KA3C.
c. Withstand temperature up to 130-degree C.
d. Good fire retardance and self-extinguishing properties.
3.4 Vertical Busbars
The vertical busbars shall be located in a separate and totally enclosed chamber covered
from all sides. In the case of Draw out Modules the openings provided for incoming plug
in contacts to the various modules shall be fitted with safety non metallic shutters
operated by the movement of the individual feeder trolley thereby making vertical busbar
compartment fully enclosed.
The draw out modules shall be provided with lyra shaped plug in contacts, which directly
engages with the vertical busbars. These plug in contacts shall be fully shrouded, spring
loaded, made of copper with silver coating.
The vertical busbars shall be made of high conductivity, high strength, and electrolytic
grade of copper. These busbars also shall be tinned.
Vertical busbars shall be provided with insulator supports.
The vertical busbars shall be of hard drawn high conductivity electrolytic grade copper
strips with maximum temperature limited to 850C (i.e. 350C rise over 500C ambient). The
current density of copper should not exceed 1000A/sq.inch.
All bus connection shall be silver plated. Adequate contact pressure shall be ensured
by means of required No. of bolts with plain and spring washers and locknuts
Bimetallic connectors shall be furnished for connection between dissimilar metals.
Bus insulators shall be flame retardant, track resistance type with high creep age surface.
All buses and connections shall be supported and braced to withstand the stresses due to
maximum short circuit current and also to take care of any thermal expansion.
Busbars shall be colour coded for easy identification and so located that the sequence R-
Y - B - N shall be from left to right, top to bottom or front to rear, when viewed from the
front to switchgear assembly.
Bolted disconnection links shall be provided for all incoming and outgoing feeders for
isolation of neutral, if necessary.
3.5 Feeder Compartments
The feeders shall be arranged in a two tier system. All indicating and control components
of respective feeder shall be installed on a hinged door.
Each individual feeder shall be installed in separate compartments totally enclosed from
all sides. Compartment doors shall be provided with concealed hinge at one end and
fixing screw / lock on the other end.
For draw out feeders, the various equipments shall be fitted on a trolley which is capable
of being fully drawn out. To facilitate this, the incoming and outgoing power connections
shall be provided with fully shrouded self-aligning type lyra shaped plug in type auxiliary
Page 59 of 116
terminals. Further, each module shall be provided with central guide rails with integral
swiveling type racking levers.
All the power and control equipment like auxiliary contactors, indicating instruments,
push buttons, indicating lamps, control terminals, etc. shall be of latest generation
models. The control terminals provided shall be Finger Touch Proof type to avoid
accidental touching of contacts.
Each trolley shall be provided with a swing out instrument plate at the front on the right
hand side to accommodate the actuating and indicating equipment like push buttons,
indication lamps, bimetal reset cord etc, mounting of equipment and flexible wiring to
the door are not acceptable.
The incoming plug in contact arrangement is to be provided with a lifting arrangement
for opening the automatic shutters provided in the vertical busbar chamber. The
compartment design shall be such that the earthing contact will make before main contact
makes and shall break after the main contact breaks.
The power cables shall enter from the bottom and shall be terminated on the horizontal
busbars on the breaker outgoing terminals.
For all feeders separate and adequate compartments shall be provided for
accommodating instruments, indicating lamps, control contactors and control MCB’s
etc. These shall be accessible for testing and maintenance without any danger of
accidental contact with live parts of the circuit breaker, busbars and connections.
3.6 Air Circuit Breakers
The Air Circuit Breakers shall comply fully with IEC 60947-2 or IS 13947-2 or equivalent
IS Standard. Each breaker shall have microprocessor based tripping unit. The
breaker shall be of short circuit withstand capacity 65 KA & short circuit making
capacity of 130 KA. The Air Circuit Breakers shall be of Siemens /ABB /Crompton
Greaves /Schneider /GE /L&T.
The short time withstand capacity of the breaker shall be 65 KA for 1 sec. The circuit
breaker shall have moulded case design with class II front facia.
The accessories like closing coil, trip coil shall be easily accessible and shall require no
calibration for site fitting. These coils shall be of continuous duty. The breaker shall be
of trip free mechanism with anti-pumping features with mechanical indication for anti-
pumping front facia. The breaker should have following characteristics:
Breaking time should be less than 25 ms
Operating time should be 40 to 25 ms
Closing time should be between 50 to 60 ms
Electrical life should be minimum of 6000 maintenance free operations.
The circuit breaker cradle shall be designed and constructed to permit smooth
withdrawal and inspection. The movement shall be free of jerks and easy to operate.
Mechanical latch to be provided to identify the isolated, test & service position of
breakers to prevent over racking.
All current carrying parts in the breaker shall be silver plated and suitable arcing
contacts shall be provided to protect the main contacts which shall be separate from
the main contacts and easily replaceable.
Page 60 of 116
The circuit breaker shall be trip free with independent manual spring operated and
motor wound spring operated mechanism and with mechanical ON/OFF indication.
The operating mechanism shall be such that the circuit breaker is at all times free to
open immediately the trip coil is energised. The breaker shall be provided with inbuilt
anti pumping feature.
There shall be mechanical indicator on the front panel for ‘ready to close’ situation
for the breaker by checking all interlocking.
The circuit breaker shall have the following interlocks.
1) It shall not be possible for the breaker to be withdrawn from the cubicle when in
‘ON’ position.
2) It shall not be possible for the breaker to be switched ‘ON’ until it is either in the
fully inserted position or for testing purposes, it is in the fully isolated position.
3) It shall not be possible for the circuit breaker to be plugged in unless it is in the
off position.
A safety latch shall be provided to ensure that the movement of the breaker, when it
is withdrawn, is checked before it is completely out of the cubicle, thus preventing
the accidental fall due to its weight.
Incomer Breaker
The 1 No. Incoming breakers shall be of 1600 A, 65 kA, 4P ACB
The incoming breakers shall be equipped with communication port & the circuit
breaker shall be capable of communicating the following data via a bus
Circuit – breaker status (open / closed), connected / disconnected / test, tripped
on a fault, ready to close;
Control Unit settings;
Tripping causes;
The measurements processed by the control: current, voltage, frequency, power.
It shall be possible to remotely control the circuit breaker.
It shall be possible to remotely modify circuit breaker settings, settings of the
protection functions and the alarms.
Communications functions shall be independent of the control unit.
The incomers shall have power meters which shall display A, V, PF, Hz, Kw, KVA,
KVAr, Kwh, Kvarh, average and maximum values, demand values, THD on current
and voltages. The power meter shall have additional features like RS485 Port with
modbus protocol, programmable contacts, analogue outputs to link to BMS / SCADA
system in future.
Multifunctional Numerical Relay
The incoming breaker shall be provided with multifunctional numerical relay with
RS-485 communication port and open protocol system. Relay shall be draw out design
with built in testing facilities. Small auxiliary relays may be in non-draw out execution.
Relays shall be rated for operation on 5 A secondary current and 24V supply voltage.
Number and rating of relays contacts shall suit the jobs requirements.
The contractor shall furnish, install & co-ordinate all relays to suit requirements of
protection and interlock.
The Multifunction Numerical Relay on incomer breaker shall have the following
digital control / monitoring / protection features.
a) Definite time over current protection.
Page 61 of 116
b) Inverse time over current protection
c) Earth fault protection
d) Short circuit protection
e) Disturbance recording
f) Event logging and fault recording facility
g) Monitoring and control system
h) Metering and signalling facility
i) Modbus communicating system
j) RS 485 interface unit.
Outgoing Breakers
The 2 Nos. Outgoing ACB shall be of 1000 Amp. 65 kA, 3P type.
The outgoing breakers shall have microprocessor based tripping units and shall
conform to the following features/facilities:
a) Long Time over Current Setting with adjustable Tripping Delay.
b) Over Load Signal (LED)
c) Short Time over current protection with Tripping Delay
d) Adjustable Instantaneous Pick up
e) Earth leakage or Earth Fault Pickup with Tripping Delay
f) Earth leakage or Earth Fault test Button
g) Testing facility for releases.
h) Lamp test, Battery test and fault indication reset facility.
i) Indication of tripping cause through LED
j) High Resolution Screen
k) Display of current measurements.
3.7 Control & Indication
The circuit breaker shall be wired up for local and remote operation. Each breaker
cubicle shall have
Two Nos. heavy duty, oil tight, push buttons for TRIP & CLOSE
Four Nos. indicating lamps on front of compartment to indicate the status of the
breaker
Breaker open - GREEN
Breaker closed - RED
Breaker Trip - AMBER
Breaker Spring charged - WHITE
Lamps shall be LED type
3.8 Current Transformers
Current transformer shall be cast-resin type. All secondary connections shall be
brought out to terminal blocks where wyes or delta connection will be made.
Accuracy class of the current transformer shall be: -
a. Class 5P10 for relaying/ suitable class for the offered relay.
b. Class 1.0, ISF < 5 for metering
3.9 Control Transformers
Control transformers shall be cast resin type and shall have an accuracy class of 1.0.
All secondary connections shall be brought out to terminal blocks.
Current limiting MCB’s shall protect the primary and secondary winding of the
transformers.
3.10 Meters
Indicating instruments (96x96mm) shall be switchboard type, with 2500 scale, anti-
glare glass and accuracy class of 1% full scale. Each meter shall have zero adjuster
on the front.
Page 62 of 116
3.11 Secondary Wiring
The PCC shall be fully wired at the factory to ensure proper functioning of control,
protection and interlocking schemes.
MCB’s shall be provided to permit individual circuit isolation from bus wires without
disturbing other circuits. All spare contacts of relays, switches and other devices shall
be wired upto terminal blocks.
Wiring shall be done with flexible, 1100 V grade PVC insulated switchboard wires
with stranded copper conductors of 1.5 mm2 for control, current & voltage circuits.
Each wire shall be identified, at both ends, with permanent markers bearing wire
numbers as per contractor’s wiring diagrams.
Wire termination shall be made with crimping type connectors with insulating
sleeves. Wire shall not be spliced between terminals.
3.12 Terminal Blocks
Terminal blocks shall be 660V grade box clamp type with marking strips, similar to
ELMEX 10mm2 or equal. Terminals for C.T. secondary leads shall have provision
for shorting.
Not more than two wires shall be connected to any terminal. Spare terminals equal
in number to 20% active terminals shall be furnished.
Terminal blocks shall be located to allow easy access. Wiring shall be so arranged
that individual wires of an external cable can be connected to consecutive terminals.
3.13 Cable Termination
The PCC shall be designed for cable entry from the rear bottom. Sufficient space
shall be provided for ease of termination and connection.
All provisions and accessories shall be furnished for termination and connection of
cables, including removable gland plates, cable supports, and crimp type tinned
copper/aluminum lugs, brass compression glands with tapered washer (Power cables
only) and terminal blocks.
Gland plates shall be minimum 3 mm thick.
The arrangement for termination of cables shall be such that the cables shall enter
from the bottom and get terminated on the horizontal busbars connected to the
outgoing terminals of the breaker. All the sides of these horizontal busbars shall be
covered with form plates so that it shall be possible to terminate cables on other
feeders while the panel is live and without any safety risk.
3.14 Ground Bus
A ground bus, rated to carry maximum fault current, shall extend full length of the
PCC. This bus shall be of 1 x 50 x 5 mm Copper
The ground bus shall be provided with two bolt drilling with G.I. bolts and nuts at
each end for earthing connection.
Each stationary unit shall be connected directly to the ground bus
C.T. secondary neutrals shall be earthed through removable links so that earthing can
be removed by disconnecting the links.
3.15 Name plates
Nameplates of approved design shall be furnished at each cubicle and at each
instrument & device mounted on or inside the cubicle.
The material shall be lamicoid or anodized aluminium of 3 mm thick with white letter
on black background.
The nameplate shall be held by self tapping screws. Nameplate size shall be minimum
20 x 75 mm for instrument / devices & 40 x 150 mm for panels.
Caution notice on suitable metal plate shall be affixed at the back to each vertical
panel.
3.16 Space Heaters, Plug Sockets and Illumination of Panel
Each vertical section shall be provided with thermostat controlled space heater and
5A, 3-pin plug socket.
Page 63 of 116
Cubicle heater, Plugs socket circuit shall have individual switch fuse units.
Each panel shall be provided with fluorescent tube or CFL fitting along with door
switch for illumination of the panel.
3.17 A.C. / D.C. Power Supply
The control supply for the control circuit shall be generated from the incoming side
of the incomer breaker
Isolating MCB units shall be provided at the PCC for the incoming supplies, 4 pole,
single throw for A.C. and 2 pole double throw for D.C.
Bus wires of adequate capacity shall be provided to distribute the incoming supplies
to different cubicles. Isolating switch fuse shall be provided at each cubicle for
A.C/D.C. supplies.
A.C. load shall be so distributed as to present a balance loading on three phase supply
system.
3.18 Tropical Protection
All equipment, accessories and wiring shall have fungus protection, involving special
treatment of insulation and metal against fungus, insects & corrosion.
Screens of corrosion resistant material shall be furnished on all ventilating louvers to
prevent the entrance of insects.
3.19 Painting
Surface Preparation: Prior to painting, surface should be free of any visible loose
particles, welding spatters or foreign bodies. 7/9 tank treatment for removal of grease in the
degreasing tanks, cleaning of surface with water in rising tank, acid treatment of surface with
chromate and phosphate. Surface should be suitably cleaned to achieve required finish as per
relevant standards.
Painting: (PU EPOXY): The primer shall be one coat of zinc phosphate and Second coat of
primer shall be high build MIO. Finish shall be with PU coat in not less than 2 coats. Paint to
be mixed as per manufacturer specification. Paint to be applied to achieve minimum total
110-micron DFT.
3.20 Accessories
The following accessories shall be furnished along with the PCC
a) Breaker racking in/out handle
3.21 Factory Tests and Inspection
The LT Switchboard shall be completely assembled, wired, adjusted and tested at the factory as
per the relevant standards.
Type Tests
The offered panels shall be type tested for the following type tests and the copies of the test reports
shall be submitted at the time of offer itself to prove the design. The Power distribution board
/Panels so tested shall be of minimum 1600 Amp rating and size as that is offered.
a) Temperature rise test.
b) Short Circuit withstand test
c) Test for IP 52 enclosure.
Routine Test
The tests shall include but not necessarily be limited to the following:
a) Operation under simulated service condition to ensure accuracy of wiring, correctness of
control scheme and proper functioning of the equipment.
b) All wiring and current carrying part shall be given appropriate high voltage test.
c) Primary current and voltage shall be applied to all instruments.
Page 64 of 116
d) Routine test shall be carried out on all equipment such as circuit breakers, instrument
transformers, relays, meters etc.
e) Primary injection test.
Test Witness
All tests shall be performed in presence of owner’s representatives. The contractor shall give at
least thirty (30) days advance notice of the date when tests are to be carried out.
Test Certificates
Certified reports of all the tests carried out at the works shall be furnished in six (6) copies for
approval.
The Panels shall be dispatched from the works only after clearance of the same by MDL.
4.0 Warranty
The vendor shall have final and total single point responsibility for the design and performance
of the panels and all components supplied under this specification.
The supplier shall
a) Warrant that the panels and all materials to be free from defects in design, material and
workmanship.
b) Warrant that the panels will satisfy the requirements of the intended use and be suitable
for the application.
c) Agree to repair or replace any component under this warranty, which proves to be defective
within a minimum period of 12 months after being placed in operation at site.
d) Assume responsibility for obtaining manufacturer’s performance warranty for all items
purchased by the supplier.
5.0 Packing and Transportation
The offered panels along with their accessories shall be transported to site packed in wooden
crates. They shall be wrapped with polythene sheets before being placed in the crates to
prevent damage to finish. The crates shall have skid bottom for handling. The same shall be
unloaded by the contractor at MDL site. MDL will provide only the crane facility.
6.0 Work Completion Period
The Design, Manufacture, Testing at factory, Packing & forwarding, Installation at site,
Testing and Commissioning of all the panels shall be completed within 5 months after receipt
of order
7.0 Deviation
In the event of any deviation from this specification the same shall be clearly indicated at the
time of offer itself. No deviation will be accepted after the placement of the order.
8.0 Detailed Requirement of Installation
a) All alignment, leveling, grouting, anchoring & adjustment shall be carried out in
accordance with manufacturer’s instructions and or as directed by MDL Engineers.
b) All connections in new panels shall be completed and checked to ensure safety &
satisfactory operation of the Panels.
c) The panel may be split up in sections for ease of transportation and handling. Necessary
mounting, wiring and connection shall be done by contractor.
Note: All Works for installation of new Panels shall be done on Saturdays, Sundays and Holidays.
9.0 Grounding
01 The contractor shall provide & install the earthing connection for his scope of equipment.
2 Earth Pits – complete with chamber, funnel and GI Plate to be prepared at a
suitable location near the installation site. 02. The earthing connection shall be done using 50 x 6 mm G.I strip to the earthing pits.
03 All ground conductor connections shall be made by electric arc welding unless otherwise
specified. All welding joints shall be covered with bitumen compound.
Page 65 of 116
04. Bolted grounding connection shall be used for equipment grounding. The contact surface
shall be thoroughly cleaned before connection. After connection bolted joints shall be
coated with cold galvanizing paint. Connection between dissimilar materials shall be
through suitable metallic connectors.
05 Equipment will generally be furnished with two separate ground pads with tapped holes,
bolts and spring washers. If however the same are not furnished, supplier /erection
contractor shall drill & tap holes and provide bolts and spring washers for grounding
connection.
10.0 Site Inspection
01 After completion of erection/installation each piece of equipment shall be thoroughly
inspected in presence of the MDL Engineer for correctness and completeness of erection
and acceptability for start up.
11.0 Testing & Commissioning
01 After completion of erection work, tests shall be conducted by the supplier/erection
contractor on each panel.
02 The contractor shall provide all tools, materials, labour and supervisory personnel for
carrying out field tests on the panels and materials under his scope of work.
03 These tests shall be conducted in presence of MDL Engineer and according to his
directions.
04 All temporary arrangements and connections required for tests shall be provided by the
contractor.
05 The contractor shall record the test results on approved format and furnish four (4) copies
of the results to MDL within a week of the date of test completed.
06 Before commissioning of the equipment, the contractor should set the relays to their
recommended values. The settings shall be conveyed to MDL in writing.
07 On successful inspection and testing, the equipment shall be commissioned and will be
kept under observation for a minimum period of 15 days before declaring as
commissioned.
12.0 Rectification
The contractor shall carry out all rectifications, repairs or adjustments work found
necessary during testing, commissioning and observation period.
13.0 Site Tests
The following tests shall be carried out at site before commissioning:
Switchgears, Panels:
a) Tests for satisfactory tripping, operation, control and indication.
b) Secondary injection test for relays and protective devices
c) Insulation test by Megger
d) HV test wherever necessary
Cables:
Power cables - Insulation and continuity test
Insulation and HV testing equipment:
The contractor shall arrange suitable high voltage test sets as well as the insulation tester up to
1000 volts.
14.0 General Notes
Any other activities which are not mentioned in this specification but required for the successful
installation, testing and commissioning of the panels shall be in contractor’s scope.
15.0 Training
Training shall be provided to SB-MTC personnel at the MDL installation site.
Page 66 of 116
16.0 Vendor data requirements.
The Vendor shall furnish 3 sets of following final / as built drawings.
a) GA Drawing of panels
b) Single Line Diagrams
c) Control Schematic with detailed control wiring
d) Bill of Materials
e) Manual of multifunctional numerical relays
f) Catalogues of all components.
g) Any other drawing required for operation and maintenance of the panels.
RATINGS & REQUIREMENTS
1. 415 V PCC
General
Type : Metal clad, Drawout
Service : Indoor
Enclosure : IP-52
System
Voltage : 415 Volt +/-10%
Phase : 3
Frequency : 50 Hz +/- 5%
System : Solidly grounded
Rated Current at 50o C
Bus bar : 1600 A
Circuit breaker : 1600 A and 1000 A
Short Circuit rating
Interrupting : 65 KA
Short time rating : 1 sec
Insulation level : 2.5 KV for 1 min
A.C./D.C. Power Supply
Control voltage : 110 V A.C / 24 V D.C. will be
generated by the supplier
Service voltage : 240V + 10%, 50 HZ + 5%, 1
phase.
2. Circuit Breaker
Duty cycle : 0-3’-co-3’-co
Breaking Current
A.C. Symmetrical : 65 KA
A.C. Asymmetrical : As per IEC
Making current : 2.55 times of A.C. Symmetrical
Auxiliary Voltage
Closing : 110V A.C. + 10% to -15%
Tripping : 110V A.C. + 10% to -15%
Spring charging : 230 V A.C
Indication : 24 V D.C
TECHNICAL PARTICULARS
(To be filled and submitted at the time of offer itself)
1.0 PCC
Make :
Type :
Page 67 of 116
Reference Standard :
Voltage (Nom/Max) KV:
Phase, Frequency :
Short Circuit Rating :
a) Interrupting Symmetrical KA :
a) Short time for 1 Sec. KA :
1-min. 50Hz Voltage withstand KV :
Metal enclosed Construction YES/NO :
Degree of Protection :
Minimum thickness of sheet metal used mm :
Switchgear completely assembled, :
wired & tested at factory(YES/NO)
2.0 Construction
Draw out features provided for
a) Circuit breaker with SERVICE, TEST & :
ISOLATED Position (YES/NO)
b) Protective Relays (YES/NO) :
Breaker Cubicle
a) Breaker cubicles restricted to :
two /three tiers only (YES/NO)
b) Cubicle door can be closed with :
breaker in ISOLATED position(YES/NO)
c) Working height limits from door level mm :
All meter, switch and relays flush mounted :
type (YES/NO)
Minimum clear space required at
a) Front for breaker withdrawal mm :
b) Rear mm :
Vertical Section Incomer Outgoing
a) Overall Dimension mm (LxBxH) :
b) Approximate Weight Kg :
3.0 Busbar
Material & Grade :
Make :
Reference, Standard :
Cross Sectional area mm2
a) Phase :
b) Neutral :
Continuous current (at site condition :
500C ambient and within cubicle) Amp
Max.temp. rise over 500C :
Short time current for 1 sec. KA ms :
Separate enclosure/phase barriers/ :
Shrouding provided for
a) Main busbar :
b) Vertical droppers :
c) ACB connections :
Page 68 of 116
Bus connections
a) Silver plated :
b) Made with anti oxide grease :
Minimum clearance of bare busbar
and connection
a) Phase to phase mm :
b) Phase to ground mm :
Busbar support spacing mm :
Busbars colour coded :
Bus support insulator
a) Make :
b) Type :
c) Reference Standard :
d) Voltage class KV :
e) Minimum creepage distance mm :
f) Cantilever Strength Kg/cm2 :
g) Net Weight Kg :
4.0 Circuit Breaker
Make :
Type :
Reference Standard :
Rated voltage KV :
Rated frequency Hz :
No. of poles No. :
Rated Currents:
a) Continuous (at site condition,500C :
ambient & within cubicle) Amp
b) Short–time Current for 1 sec KA rms :
Max temp. rise over 500C ambient 0C :
Rated Operating Duty :
Interrupting Capacity at rated voltage :
and operating duty
a) Symmetrical KA rms :
b) Asymmetrical KA rms :
Rated making current KA peak
Transient Recovery Voltage
a) Rate of Rise KV/ms :
b) Peak Voltage KV :
Insulation Level
1-minute 50HZ voltage withstand KV rms :
At 100% interrupting capacity
a) Opening time ms :
b) Arcing time ms :
c) Total tripping time ms :
Total closing time ms :
No. of beaker operations permissible,
Page 69 of 116
Without requiring inspection, replacement
Of contacts and other main parts:
a) At 100% rated current :
b) At 100% rated interrupting current :
Type of contacts
a) Main :
b) Arcing :
c) Whether contacts are silver plated :
d) Thickness of silver plating :
Contact pressure at no load Kg
Minimum clearance in air :
a) Between phases mm :
b) Between live parts & ground mm :
Type of arc control device :
Operating Mechanism :
a) Type :
b) No. of breaker operations stored :
c) Trip free or fixed trip :
d) Anti pumping features provided or not :
Spring Charging Motor :
a) Rating, KW :
b) Voltage, V :
c) Permissible Voltage variation % :
Closing coil :
a) Voltage V :
b) Permissible Voltage variation % :
c) Closing current at rated voltage A :
Tripping Coil
a) Voltage V :
b) Permissible Voltage variation % :
c) Trip current at rated voltage A :
Breaker / cubicle Accessories
Accessories such as control switch :
Indication lamps, relays furnished as
Specified
Breaker /breaker cubicle provided with following :
a) Mechanical safety interlock for incomers :
b) Automatic safety shutter for busbar :
c) Mechanical ON-OFF indicator :
d) Manual spring charging device :
e) Spring Charge/Discharge indication :
Net weight of the breaker Kg
Overall dimension (LxBxH) mm :
Type test report on identical breaker :
Furnished
Page 70 of 116
5.0. Multifunctional Numerical Relay
Make :
Model :
6.0 Control & Indications
Push Buttons
a) Make :
b) Type & Cat No. :
c) Contact rating
i) Make & continuous Amp :
ii)Break (inductive)Amp :
Lamps
a) Make :
b) Type & cat No. :
c) Watts / Voltage :
d) Series resistance in Ohm :
e) Lamp & Lens replace from front:
Manual /Remote Selector Switch
a) Make :
b) Type & Cat.No. :
c) Contact rating
i) Make & Continuous Amp :
ii)Break (Indicative) Amp :
d) Key interlock furnished? :
7.0 Current Transformers
Make :
Type :
Reference Standard :
C.T. Ratios :
Rated frequency :
Class/ALF or ISF/VA burden furnished for
a) For Relays :
b) For Metering :
Short circuit withstand
a) Short time current for 1 sec KA rms :
b) Dynamic current KA peak :
Class of insulation :
Temp. rise over 500C ambient :
8.0 Control Transformers
Make :
Type :
Reference standard :
Voltage ratio :
Rated frequency :
Accuracy class :
VA burden :
Over Voltage factor :
a) Continuous :
b) 30 seconds :
Class rise over 500C ambient :
Page 71 of 116
9.0 Meters
Make :
Type :
Reference standard :
Size :
Scale :
Accuracy class :
Meter switch
a) Make :
b) Type :
c) Cat No. :
10.0 Secondary wiring
Type of insulation :
Voltage grade :
Conductor material :
Conductor size (minimum) :
a) Potential Circuit :
b) Control & current circuit :
Wire identified at both ends with markers :
11.0 Terminal Block
Make :
Type :
Cat No :
Voltage grade :
20% spare terminals furnished :
12.0 Cable Termination
Cable Lugs
a) Make :
b) Type :
c) With tapered washer :
d) With armour clamp :
13.0 Cable Gland
Make :
Type :
Thickness of the plate :
14.0 Ground Bus
Ground bus furnished :
Material :
Size :
15.0 Name Plate Material :
Thickness :
Size for :
Panel :
Equipment / Device :
16.0 Space Heater, Plug & Socket and Panel Illumination
Cubicle Heater
Thermostal controlled :
Wattage :
Voltage :
Page 72 of 116
Plug Socket
Type :
Rating :
Cubicle heater & plug socket
circuit provided :
With individual MCB’s
Panel Illumination
a) Type of lamp :
b) Wattage :
c) Voltage :
17.0 A.C / D.C Supply
Isolating MCB’s provided for incoming supply
A.C. – Type & rating :
D.C. – type & rating :
Isolating MCB’s provided at each cubicle
A.C. – Type & rating :
D.C. – Type & rating :
18.0 Tropical protection
Any special treatment for tropical protection :
Screens are of corrosion resistant materials :
19.0 Painting
Finish of switchgear
Inside :
Outside :
Accessories Furnished
Racking in/out handle :
20.0 Tests
The test reports for the following type tests are
enclosed
a) Temperature rise test. :
b) Short Circuit withstand test :
c) Test for IP 52 enclosure :
d) Power frequency high voltage withstand test :
21.0 Drawings / Data
Typical drawing furnished for
General Arrangement :
Foundation Plan :
Breaker Control Schematic :
Bill of Material :
22.0 Dimensions and Weights
Overall Dimension :
Page 73 of 116
PART II
Supply of 1 no. 1600 A, 65 kA, 3 P Schneider Electric make MASTERPACT ACB and installation
of the same in existing LT Panel of Schneider Electric make (Blokset).
1. At Substation Kasara of North Yard at MDL, 1 no. LT Panel of Schneider Electric make, Blokset
is installed feeding power supply to different areas.
2. The Outgoing ACBs of the existing panels are of Schneider Electric make
MASTERPACT NW10 H1 of 1000 A, 65 kA, 3P type.
3. 1 no. of the existing outgoing MASTERPACT ACBs of 1000 A, 65 kA, 3 P model is to be
replaced with 1 no. MASTERPACT ACBs of 1600 A, 65 kA, 3 P type.
4. Supply of the new 1600 A ACB, Installation, Necessary modification of the existing outgoing
feeder cubicle, Testing and commissioning is in vendor’s scope.
5. The ACB shall be wired for local and remote operation. The breaker cubicle shall have Ammeter,
Voltmeter, 2 nos. heavy duty oil tight push buttons for TRIP & CLOSE, 04 Nos. indicating lamp
on front of compartment to indicate the status of the breaker. The indicators should be as follows:
Breaker open: GREEN
Breaker closed: RED
Breaker Trip: AMBER
Breaker Spring charged: WHITE
Breaker in Test Position: GREEN
Breaker in Service Position: RED
Page 74 of 116
PART III
Supply, laying (including civil works, excavation & reinstating) and termination of
4 Runs of 150 M (approx.) each, 3 ½ C x 400 Al. Armoured XLPE/PVC Power Cable (Conforming to IS 7098 P-
1/88).
Detailed Scope of Work:
1. Survey of the site, providing (Supply), Laying, Testing and Commissioning of heavy duty armored
cable, 1100 Volt grade, stranded Aluminum Conductor, PVC Sheathed, XLPE Insulated, Galvanized
steel strip or wire armoured and with an overall outer PVC Sheath and of following size. The cable
shall be of CCI/ Polycab /Unistar /Nicco /KEI /Finolex/ Unicable/ Rallison/ make conforming to IS
7098 & ISI marked.
Qty.- 4 Runs of 3.5C X 400 SQ.MM - 150 METER (Total Length of cable = 4 x 150 = 600 meters.)
Note: a) The length of the cables as given above is an approx. estimate. During the Survey of Site,
the vendor shall measure the exact length of cables required. The cables laid shall not have any
joints in between.
b) The length of the stretch to be excavated for laying the cable is approx. 100 m.
2. Cable to be laid from Kasara Substation at NY of MDL to Pipe Shop at NY. Termination of the
newly laid PVC cable with all necessary cable glands, cable lugs etc. One end of the cable is to be
terminated on the 1600 A, Schneider make ACB of BLOKSET at Kasara Substation (installed as
per PART II of this scope of work) and the other end is to be terminated on the PCC at Pipe Shop
(to be installed as per Part I of this scope of work).
3. Excavating the trenches and refilling, reinstatement of the same properly after the cable is laid in
approved manner (750 MM deep, 600 MM wide) in all type of soil.
The contractor shall visit the site before quoting.
4. The cable shall be laid underground. Excavation and refilling shall be carried out by the contractor.
Excavating hard rock or Bituminous road by chiseling for preparing for laying cables and clearing
the site by removing debris and making the site good. Removing of paver blocks, breaking of
PCC/Coba and finishing the same after cable laying as per the site requirements. A Sand Bed to be
provided under and above the cables laid to prevent any damage to the cable. For laying in the
existing cable trench cleaning of the trench shall be carried out by the contractor. Wherever required,
overhead laying the cable shall be secured and dressed neatly by PVC Cable Ties on cable trays.
5. After the completion of the laying and termination of the cable, the same shall be tested with L.T
Insulation Tester before energizing.
6. The firm shall submit the test reports from the cable manufacturer for the cable supplied.
Page 75 of 116
General notes:
1. The contractor shall ensure that skilled and qualified personnel are deputed for the work.
2. Request for permission for working on Saturdays/Sundays/Holidays if required should be submitted
minimum 3 working days prior to the date of holiday. The contractor has to comply with the MDL
Safety & Security regulations for working in normal as well as holidays.
3. If the contractor wants to carry out the work on normal days, he should plan the work in such a way
that the normal production activities of MDL are not affected. The contractor shall not claim for any
compensation for idle period if generated due to any reason whatsoever.
4. All the works executed in pursuance of the contract shall be inspected by the MDL representative before
certification of the work carried out.
5. All tools and tackles and materials required for the execution of the work shall be in Contractors scope.
MDL will provide only the power supply free of cost.
Page 76 of 116
3. Prequalification Criteria:
Bidders should upload following documents along with Part-I (Techno-Commercial Bid)
Commercial Prequalification Criteria
3.1.1 Bidders Registration Certificates as: -
i) GST Registration if registered under GST Act.
ii) Any one of the following documents.
a) Shop & Establishment registration certificate
b) Factory License
c) Certificate of Incorporation by registrar of company
d) NSIC Registration
e) MSME Registration
f) SSI Registration
g) Certification from registrar of firms
3.1.2 List of equipment held by them with model / year / working status along with details of their
manufacturing facilities and personnel with designation, qualification and experience to
determine their capabilities. SSI/NSIC units can alternatively submit valid certificate indicating
their capacity.
3.1.3 Audited / Certified Balance sheet, Profit / Loss account for past 3 years.
3.1.4 The bidder should have a minimum average turnover of at least for Rs. 72,99,000/- during the
last three years and shall submit last three years audited/certified balance sheet & profit/loss
account.
3.1.5 The bidder should have executed orders of similar supplies of value of at least for Rs. 72,99,000/-
during the last 3 years and shall submit Purchase order copies, work completion certificate.
Documents should be in English language.
Similar supplies defined as: “Supply, Installation, Testing & Commissioning of A.C.
Distribution Panels.”
3.1.6 Authorization letter from the Principal manufacturer/OEM, in case of bidders other than
Principal manufacturer /OEM clearly stating that the bidder is authorized by the OEM/ Principal
manufacturer to quote for the item that is being offered and OEM shall stand Guarantee/Warranty
for the items being offered.
Note:
a. Submission of documents mentioned above is mandatory for every bidder. Bidders need to submit
supporting documentary evidence in support of the Pre-Qualification Criteria Viz. Work Order, Work
Completion Certificate issued by the party for whom the work is done.
b. Bidders registered with MAZAGON DOCK SHIPBUILDERS LIMITED should furnish copy of valid
registration certificate and they are exempted only for submission of documents indicated 3.1.1 to 3.1.2.
c. MDL has a right to demand for hard copy of any of the above documents/ any other document & verify
/ cause verification of authenticity of the said documents whenever felt necessary or visit their site / works.
Bidders shall comply with the same. If the documents are not found satisfactory to MDL or/and on
verification if the documents are not found authentic to MDL, then offer is liable for rejection. MDL’s
decision in this regard will be final and binding on the bidder without stating any reason whatsoever it may
be.
4. Validity Period: Bids / Offers Shall have a validity period of 120 days from the tender closing date. A bid
valid for a shorter period will be liable for rejection by MDL as non-responsive. Incase shorter validity
quoted by bidders; technically accepted bidder will be given opportunity to accept the validity of tender.
In case of non-acceptance of validity as per tender term thereafter the firm offer will be rejected as non-
responsive.
Page 77 of 116
5. On-line submission of bids in Two-Bid System: Offer must be submitted in two parts through E-
tendering system. Bidders are requested to log on to https://eprocuremdl.nic.in for submission of bids
against above tender. Bids must be submitted in Two parts, i.e. Part-I (Techno-Commercial bid) and Part-
II (Price Bid), as appearing on-line.
5.1 Part I Bid (Techno-Commercial bid)
5. 1.1 Detailed Technical offer for technical scrutiny along with point-wise acceptance or
offered specifications against required specification. Technical details, catalogues,
drawings, data sheets, calculations, as applicable to be enclosed/attached in attachment
provision given online.
5.1.2 Bidders to carefully fill all listed online forms providing their
comments/Acceptance/deviations, if any, in the space provided online against
respective clauses of Tender terms & conditions (TEF), GT&C and STACS, etc.
Quoted or Not Quoted whichever is applicable must be selected from dropdown list in
un-price bid form and applicable taxes must be mentioned in respective tax column.
5.1.3 Pre-qualification documents as listed at Para 3 above.
5.1.4 Indigenous bidders to quote in INR & Foreign bidders to quote in respective foreign
currency.
5.1.5 The scanned image of proof of Electronic transfer / BG towards Earnest Money
Deposit (EMD) / BID BOND / SWIFT Message as stipulated in TEF clause no. 6
shall be uploaded. Bidders can submit EMD amount by using the payment gateway
facility for this online payment tab is made available on MDL website. Bidders can
electronically transfer the EMD amount through NEFT/RTGS. Receipt of EMD
payment through payment gateway/NEFT/RTGS is to be uploaded along with PART
-1 offer.
The original of the NEFT/RTGS/BG/Bid bond/ swift message shall be forwarded to
GM (M) in sealed envelope super scribing Tender Enquiry No. and Due date, so as to
reach within 7 MDL working Days from the tender closing date, addressed
To,
GM (M)
II FLOOR MOGUL HOUSE
SOUTH YARD
MAZAGON DOCK SHIPBUILDERS LTD.
DOCKYARD ROAD,
MUMBAI- 400010.
In case an exemption is sought, Documents towards which EMD exemption is being
sought must be uploaded.
5.2 Part-II (Price Bid)
5.2.1 Indigenous bidders to quote in INR on door delivery basis.
5.2.2 Bidder to fill their prices online, strictly, in the online price bid form only. Prices &
other charges (as listed in form) to be entered/filled in the applicable
head/cell/columns only, as prices in wrong head/cell/column which are not applicable
to you (bidder) will finally affect your (bidders) total landed cost & accordingly
ranking. Wherever any charges from the listed charges are not applicable to bidder,
then ‘zero’ to be entered in that respective head/cell/column.
Refer 'Illustrative format and guideline” at Enclosure-1 for quoting prices in online
price bid form.
5.2.3 In case of any discrepancy in the Blank Rate Schedule Format and actual On-line
Price Bid after opening of the Price Bids, the details (GST and any charges) mentioned
in the On-line Price bid shall prevail over the details in blank rate schedule format.
Page 78 of 116
However the negotiated commercial terms before price bid opening will be considered
for ranking and evaluation.
5.2.4 Bidders in their own interest are requested to upload their bids well in advance of
tender closing date to avoid the last minute difficulties in uploading the bids.
5.2.5 Problems in hardware/software, Internet connectivity, system configurations, Browser
setting etc., for whatsoever reason shall not be considered for extension of tender
closing date and time.
5.2.6 Bidders quoting on behalf of overseas principals should quote in INR (Indian Rupees)
on FOR, Door delivery basis, with their principal’s authorization letter.
5.2.7 No exemption towards Customs Duty is applicable, hence no exemption certificates
will be issued.
6. Earnest Money Deposit (EMD) / BID BOND:
6.1 EMD amounting to Rs.2,91,960/- (Rupees Two Lakhs Ninety One Thousand Nine Hundred
Sixty only) in the form of Direct Electronic transfer to MDL’s bank account electronically through
NEFT/RTGS before tender closing date and time for which the bank details are given at annexure
or in the form of Bank Guarantee drawn in favour of MAZAGON DOCK SHIPBUILDERS
LIMITED or bid bond/SWIFT Message of equivalent foreign currency for foreign bidders shall be
forwarded to GM (M) / HOD (M) in sealed envelope super scribing Tender Enquiry No. and due
date, so as to reach us within 7 MDL working days from the tender closing date.
a) It is mandatory that the scanned image of proof of Electronic transfer with bank
transaction/transfer reference / BG / Bid bond / SWIFT Message shall be uploaded at Part-I
tender stage. If the scanned image is not uploaded in Part-I stage, bid shall be rejected.
b) Bidder to note that the Direct Electronic transfer to be effected prior to tender opening date &
time. The scanned image of proof of Electronic transfer shall reflect bank transaction / transfer
reference.
c) The bid bond / Bank Guarantee should be valid for 120 Days + 4 weeks from the tender closing
date. Either of these instruments should be drawn from the list of banks approved by
SBI/Canara bank which is uploaded on MDL website payable at Mumbai.
d) Authorized Indian agent of the overseas bidders can submit EMD in the form of Direct
Electronic transfer to MDL’s bank account in Indian Rupees. Similarly authorized Indian agent
can submit BG from national/scheduled bank on behalf of foreign bidder.
e) Bidders to advise their bank/banker to send EMD directly to commercial department or through
SWIFT to dispense with additional step of verification of authenticity of signatories. In case
of EMD transmitted through SWIFT, it shall be the responsibility of the bidder that he directs
the receiving banker to forward the message duly authenticated to the concerned commercial
officer mentioned in the tender.
f) Bids without EMD/Bid Bond will not be considered.
g) EMD of unsuccessful bidders will be returned after finalization of the tender and shall be
interest free.
MDL bank details for Direct Electronic transfer is at Enclosure 9.
6.2 EXEMPTION FROM SUBMISSION OF EMD/BID BOND: Following bidders shall be exempt
from submission of EMD/Bid Bond;
6.2.1 State & central Government of India departments, Public sector Undertakings.
6.2.2 Firms registered with MAZAGON DOCK SHIPBUILDERS LIMITED (MDL) for
the items for which the offer is being submitted. To qualify for EMD exemption, firms
should necessarily upload VALID copy of the registration certificate issued by MDL in
Part-I offer/bid. Firms in process of obtaining MDL registration will not be considered
for EMD exemption.
Page 79 of 116
6.2.3 Firms registered with NSIC under its “Single Point Registration Scheme” Exemption will
apply only to items /services for which they are registered with NSIC). To qualify for
EMD exemption, Firms should necessarily upload VALID copy of the registration
certificate issued by NSIC in Part-I offer / Bid. Firms in process of obtaining NSIC
registration will not be considered for EMD exemption.
6.2.4
6.2.5
6.2.6
Micro & Small enterprises with Valid registration certificate from the competent
authority regarding their Micro/small industry status.
Common/Deemed DPSU registered vendors qualify for EMD exemption. Such firms
shall submit valid copy of the registration certificate issued by DPSUs (other than MDL)
for the items / services for which the offer is being submitted in Part-I offer/bid. Firms in
process of obtaining registration in other DPSUs will not be considered for EMD
exemption.
Green Channel Status vendors qualify for EMD exemption. Such firms shall submit valid
copy of the Green channel certificate issued by MoD for the items for which the offer is
being submitted in Part-I offer/bid. Firms in process of obtaining this certificate will not
be considered for EMD exemption.
7. Bid Rejection Criteria;
7.1 Following bids shall be categorically rejected;
7.1.1 Bids received without uploading scanned images of EMD in the form of either Direct
Electronic transfer/BG/SWIFT message OR EMD exemption certificate, as
applicable, in online Part-I technical bid.
7.1.2 Bidders not agreeing to provide assistance for installation, Testing, Commissioning &
other such Technical activities of equipment supplied by them.
7.1.3 Bids received in any form other than through e-Portal
7.1.4 If the date of issue of EMD (BG/DET/Swift Message) is later than the tender closing
date.
7.1.5 Bids received after tender closing date & time.
7.2 Following bid rejection criteria may render the bids liable for Rejection
7.2.1 Bidder’s failure to submit sufficient or complete details for evaluation of the bids
within the given period ranging in between 2-3 weeks depending on the deficiencies
noticed in the technical catalog / data / drawing which shall not however conflict within
validity period.
7.2.2 Incomplete / misleading / ambiguous bids in the considered opinion of TNC.
7.2.3 Bids with technical requirements and or terms not acceptable to MDL / Customers /
External agency nominated as applicable.
7.2.4 Bids received without pre-qualification documents where required as per the tender.
7.2.5 Bids not meeting the pre-qualification parameters stipulated in the tender enquiry.
7.2.6 Bidders not agreeing to supply spares / post sale product support / post work
completion support.
7.2.7 Unreasonably longer delivery period quoted by the firm
7.2.8 Validity period indicated by bidders is shorter than that specified in the tender enquiry.
Page 80 of 116
7.2.9 Bidders not agreeing to furnish required Security Deposit / Required Contract
Performance Guarantee till completion of the supplies / services as per contract.
7.2.10 Bidders not agreeing to furnish Performance Bank Guarantee for Equipment supplied
/ Services rendered or not agreeing for retention of equivalent amount by MDL up to
the period till completion of contractual & Guarantee / Warranty obligations.
7.2.11 Bidder Quoting rates with price variation clause.
7.2.12 High seas sales/ sales in transit.
7.2.13 Bidders not agreeing to MDL guarantee/warrantee terms
7.2.14 Bidder not agreeing to take single point responsibility for whole scope of work
(i.e. right from supply of system/equipment till commissioning, & training at
MDL site)
8. Pricing: The prices quoted shall remain firm and fixed during the currency of the order. Bidder shall
quote the prices of all items / services listed in the price sheet format of the tender enquiry for delivery
of the items in MDL store / completion of the work at MDL site. The prices quoted shall remain firm
and fixed during the currency of the order / contract unless agreed otherwise by MDL.
8.1 For Indigenous Bidders: Indigenous Bidder shall quote the prices of all items / services listed in
the price sheet format of the tender enquiry for delivery of the items in MDL store / completion of
the work at MDL site. The prices quoted shall remain firm and fixed during the currency of the
order / contract unless agreed otherwise by MDL
9. Terms of Payment: - MDL does not pay any advance Payment for Indigenous and Overseas
bidders.
9.1
For Indigenous Bidders: Payment for the values of the supplies and services (Item wise with complete scope including
commissioning), as reduced by any deductibles and/ or the amount leviable towards liquidated
damages, if any and after including taxes etc. as may be payable through RTGS /NEFT/ECS
between 15 to 20 days after receipt of complete set of the items / Equipment &
installation/commissioning of the same, work completion certificate (Certified by an officer of the
rank of CM or above) etc. as per the ordered terms and against submission of documents in
Triplicate including Delivery challan(s), Release note from the nominated Inspection Agency, Test
reports / Certificates, Packing Lists, Invoice, Performance Guarantee, Storage / Preservation /
Demonstration / Maintenance Procedures & other Technical documentation in requisite sets as
relevant and submission & subsequent confirmation of performance bank guarantee for 10% of the
total order value (excluding tax). i.e. (PBG). If bidder will not submit PBG, 10% amount will be
retained for complete guarantee period. Bidders shall furnish all the necessary details like name of
the bank / branch, branch code No, bank account no in their technical bid as per the
RTGS/NEFT/ECS format provided with the tender enquiry.
9.2 TReDS (Trade Receivable Discounting System) for MSME bidders: "Alternate MSME vendor payment through TReDS:
“In order to address the financial needs of MSME firms, GoI has introduced a platform for
facilitating the financing of trade receivables of MSMEs from buyers, through multiple financiers
which is termed as Trade Receivables Discounting System (TReDS). At TReDS, auctioning of
invoices at competitive & transparent environment is done by financers based on Buyer’s credit
profile.
MDL is registered on the "Invoicemart" TReDS platform and M1xchange of M/s Mynd Solutions
Pvt. Ltd.
MSME bidders desirous to receive payments through TReDS platform may avail the facility if
they are already registered on
1."Invoicemart" TReDS platform or by registering on it. Contact details at "Invoicemart" TReDS
platform are as below: 022 6235 7373 and a new mail id [email protected].
Page 81 of 116
2. "M1xchange" TReDS platform or by registering on it.
Contact details at "M1xchange" TReDS platform are as below:
+91 9920455374 Ms. Ashwathi Jayandran email id [email protected]
+91 8839915724 Ms. Prinyaka Shah email id [email protected]
Desirous MSME bidders/vendors, who want to receive payments through TReDS platform, have
to submit the invoice to MDL along with all the necessary requirements as per the PO and the
payment terms. Upon receipt and acceptance of the supplied material and receipt of invoices with
the mandated enclosures, after due certification of physical invoices with enclosures by
Commercial/Material Dept., Finance Dept. shall upload the invoices on the "Invoicemart" TReDS
platform and process the invoices for payment. Post uploading the platform, the financier would be
bidding for the invoices and respective MSME vendors would be accepting the bid, so that they
can get the disbursement from the Financier. Any unfinanced invoices / invoices of MSME bidders
seeking payment from MDL directly, shall be processed as per the standard payment terms agreed
in PO / contract.”
10. Guarantee/Warranty:
a. The Supplier shall guarantee the performance of the items for a period of 12 months after
commissioning. During this period, defects if any shall be attended free of cost within 10 working
days on being notified. For details please refer TSP clause of this tender.
b. During this period, all defects arising out of defective material and faulty workmanship will be
rectified by repairing or replacing part or whole material as necessary, free of charge on door
delivery basis. Any consequential damage/defect or loss of items due to poor workmanship/poor
material quality/negligence etc. attribute to the bidder to be rectified/ replaced by the bidder free
of cost.
11 Delivery Period / Completion Schedule and Delivery Term: -
The entire scope of work i.e. Supply, Installation and commissioning is to be completed within 5 months
from the date of order.
Delivery Term:
(1) Supply: For Indigenous bidder: Door Delivery, MDL GRS Stores.
(2) MODE OF DISPATCH: Road/Rail/Air/Sea.
(3) Commissioning, Installation & Training: -
For Indigenous & Overseas Bidders: At MDL site.
12 Security Deposit (SD): The successful bidder/s shall have to submit Security Deposit for an amount of
5% of the Order value excluding GST, electronically through NEFT / RTGS or in the form of Bank
Guarantee drawn in favor of MAZAGON DOCK SHIPBUILDERS LIMITED, Mumbai from the list of
Banks approved by SBI / Canara Bank published on MDL Website within 25 days from the date of Order
& must be valid up to contract period plus one month. No interest will be paid on Security Deposit. Please
note that MDL does not extend any concession such as exemption in payment of Security Deposit etc. to
any organization irrespective of their status, like registration with MDL, NSIC, SSI, and MSME etc. In
case of failure to submit Security Deposit within 25 days from the date of order placement, EMD submitted
will be encashed and risk purchase clause would be invoked. The Security Deposit will be returned only
after successful execution of the order and shall be interest free. In the event of failure to execute the order
satisfactorily, the Security Deposit will be encashed by MDL. If order is fully executed within 25 days
from the date of purchase order, submission of security deposit is not applicable. For delayed period of
submission of SD beyond 25 days from date of order, bidder has to pay applicable interest. In case the
bidder is Indian Public Sector Unit, they shall submit the indemnity bond instead of Security Deposit.
Bidders may advise their bank/banker to send BG directly to commercial department or through SWIFT to
dispense with additional step of verification of authenticity of signatories. In case of BG transmitted
through SWIFT, it shall be the responsibility of the bidder that he directs the receiving banker to forward
the message. For delayed period of submission of SD beyond 25 days from date of order, interest will be
recovered as mentioned below;
For Indian suppliers, it will be SLR plus 2%.
Page 82 of 116
13 Performance Bank Guarantee (PBG): The Successful bidders will have to submit PBG in the prescribed format from the list of Banks approved
by SBI / Canara Bank published on MDL Website for 10% of the Order value excluding taxes, duties, etc.,
along with supply of machine/item/equipment, valid for 12 months (validity 12 months + 1-month claim
period) from the date of commissioning. Bidders may advise their bank/banker to send BG directly to
commercial department or through SWIFT to dispense with additional step of verification of authenticity
of signatories. In case of BG transmitted through SWIFT, it shall be the responsibility of the bidder that he
directs the receiving banker to forward the message duly authenticated to the concerned commercial officer
mentioned in the tender. If bidder will not submit PBG, 10% amount will be retained for complete
guarantee period.
14 Bidder shall abide by all Standard Terms and Conditions of Supply (STACS), GT&C and Acceptance
formats as per Enclosures 2 & 3 contained therein should be properly filled, signed and returned by the
bidder along with techno-commercial (Part-I) bid. The bidder shall also abide statutory requirements,
Official Secret Act 1923 and Safety clause.
15 Taxes & Duties: The item-wise rates quoted in the Rate Sheet should exclude GST Taxes and Duties.
Page 83 of 116
15.1 GST as per GST Laws shall be payable extra as quoted and agreed.
For Indigenous Bidders: - The rate sheet to be enclosed with the tender will indicate the rates under
each tax head viz.: GST
a. Only those bidders who indicate the taxes & duties separately as above shall be entitled for
consideration of change in corresponding rates in case of variation in statutory levies.
b. Supplier / Bidder will not be entitled to any increase in rate of taxes occurring during the period
of extended delivery schedule if there is delay in supply / completion attributed to him. However,
if there is a decrease in taxes, the same must be passed on to MDL.
c. Wherever all-inclusive prices are quoted by the bidders without bifurcation of tax elements, no
escalation can be considered in respect of any variations in statutory levies arising subsequently
because of the absence of the required base figures in the purchase order / contract.
d. No Exemptions towards Custom duty is applicable & hence no exemptions certificates will be
issued. Bidders quoting on behalf of overseas principals should quote in INR (Indian Rupees) on
FOR, Door delivery basis, with their principals’ authorization letter. Overseas bidders to quote
directly in USD or EURO on CIF basis & also quote on FOB basis & installation/Commissioning
charges additionally.
e. GST as per GST Laws shall be payable extra as quoted and agreed.
f. In case of purchases of goods/services from unregistered dealers under GST laws, GST will be
paid by MDL under reverse charge mechanism
g. Benefits from reduction in rate of tax/ITC is required to be passed on to consumer. Where
“applicable GST” has been quoted as extra, Goods and service providers (except un-registered
dealers under GST Law) have to submit declaration that they have complied with ‘Anti –
profiteering clause’ under GST Law. Such declaration be given in technical bid.
h. If the vendor is registered under GST, vendor shall mention the HSN code for goods&/or \services
in their tax invoice, etc. These codes must be in accordance with GST Laws and responsibility of
specifying correct HSN code for goods&/or services is that of the vendor. MDL shall not be
responsible for any error in HSN code for goods&/or services specified by supplier/contractor.
Supplier/contractor shall pay penalty and/or interest imposed on MDL or any loss due to delay in
availing ITC by MDL or any loss of ITC to MDL due to error by vendors at any stage. MDL
reserve right to recover any such interest, penalty or loss from any amount due to supplier
/contractor or vendor shall reimburse /make good such loss within 15days after intimation by
MDL or otherwise.
i. In case, MDL is unable to avail ITC, supplier/contractor at their own cost shall rectify the
shortcoming in the returns to be filed immediately thereafter. Further, if the ITC is delayed /denied
to MDL/reversed subsequently as per GST Laws due to non/delayed receipt of goods and/or
services and/or tax invoice or expiry of timelines prescribed in GST Laws for availing ITC, non-
payment of taxes or non-filling of returns or any other reasons not attributable to MDL, supplier
/contractor shall pay any loss of amount along with interest and penalty on MDL under GST Laws
for the number of days the ITC was delayed. If the shortcoming is not rectified by
supplier/contractor and MDL ends up in reversal of credits and/or payments, supplier/contractor
is fully liable for making good all the loss incurred by MDL. MDL reserve right to recover any
interest, penalty or loss from any amount due to supplier/contractor or otherwise.
j. If the vendor is registered under GST, the GST registration number (15 digit GSTIN) issued by
GOI shall be mandatorily provided by the vendor. vendor having multiple business verticals
within state /at multiple states with separate GST registration numbers shall forward GSTIN of
only that vertical which is involved in supply of goods and/or services. MDL GSTIN is
27AAACM8029J1ZA and vendor shall mention the same while invoicing and avoid any data
entry error on GST portal.
k. If the vendor is registered under GST, vendor shall ensure timely submission of invoice as per the
provisions/requirements/timeline promulgated by GOI in relation to GST Laws with all required
supporting documents to enable MDL to avail input tax credit promptly. The vendors invoice
inter alia should contain GSTIN of vendor, GSTIN of MDL (i.e.27AAACM8029J1ZA), GST tax
rate separately, HSN code wise goods or services, Place of supply, signature of vendor etc.
Original invoice needs to be submitted to Bill Receipt Centre at MDL gate, and a copy of the
invoice should be given to the goods receiving section(GRS).
Page 84 of 116
l. If the vendor is registered under GST, vendor shall file all applicable returns under GST
Laws in the stipulated time and any losses of tax credit to MDL arising due to delay in
filling will be recovered from their invoice wherever MDL is eligible to avail tax credit.
Any default towards payment of tax and/or uploading of monthly returns by supplier
/contractors, MDL retains right to withhold payments towards tax portion until the same
is corrected and complied by the supplier/contractor with the requirement of GST along
with satisfactory evidence.
m. The rate sheet enclosed with the tender will indicate the rates to be entered under each
head wherever applicable. Bidder must clearly mention the applicable taxes & duties. The
item-wise rates (i.e. Basic+P&F+F&I) quoted in the rate sheet should exclude taxes &
duties. Bidder should indicate GST rates as applicable separately under each of the head
in the same rate sheet, which will be paid extra based on tax invoice to the extent
applicable. The GST will be applicable on total basic rate of each item (i.e. Basic +P&F
+F&I).
n. Income tax applicable on cost of services rendered in India in relation to the contract, shall
be payable by bidders (Indian & foreign).
o. In case of Indian Companies, TDS shall be carried out as per the existing Laws and Acts.
Page 85 of 116
16 Loading Criteria: Deviations sought by the bidder in respect of Custom Duty exemption, Freight,
Insurance, Payment terms shall be loaded on the bidder/s quoted prices during price evaluation by MDL.
Among the equal bids, bidders with ISO 9000 series accreditation over Non-ISO bidders, firstly
Manufacturers then their authorized dealers will be given preference. The loading criteria that will be
adopted are detailed below & also as per Enclosure-5:
16.1 It is desirable that the bidder accepts the Payment Terms indicated in clause 9 above. Varied
payment terms quoted by bidders as compared to the terms stated in the Tender document shall
be normalized by applying S.B.I. Prime Lending Rate (prevailing at the time of opening of Price
bid) plus 2% p.a. rate of interest for the period at variation. (For Indigenous bidder)
16.2 Delivery of the goods at MDL premises should be the responsibility of the vendor.
However, for unavoidable reasons, if bids are exclusive of transport and/or insurance,
the same will be loaded at the cost to be incurred by MDL.
16.3 For the additional delivery period sought by the bidder over the stipulated date of delivery as per
Tender, 0.50% per completed week will be loaded to the quoted price.
16.4 Deviations sought in respect of Liquidated Damages (L D) Deviations sought in respect of rate
per week and / or maximum ceiling in respect of liquidated damages shall be loaded to the quoted
price. For e.g. The maximum ceiling towards liquidated damages speculated in the tender is 5%
and the bidder seeks to limit it to, say 3.5% then the price quoted will be loaded by 1.5%. If the
rate of L.D per week is 0.5% per week or part thereof as per tender
and the bidder seeks it as, say, 0.4% per week or part thereof, the maximum ceiling on L D as
per tender will first be equated to weeks (10 weeks in this case) and the rate proposed by the
bidder i.e. 0.4% will be multiplied by the so equated maximum period (which works out to 4%)
and the quoted price will be loaded accordingly by 1%. Delivery being the essence of the
contract, it is desirable if the bidder/s adhere to the stipulated clause.
16.5
Deviations in respect of the period of Warranty shall be loaded to the quoted price @ 0.25% per
month or part thereof. This does not arise if the bidder quotes additional price for the differential
period.
16.6 The ranking of price bids shall be done on the basis of exclusive of GST. In these cases, the
variation in statutory levies etc. are not allowed unless the breakup in respect of taxes are clearly
and separately furnished in bid.
17 Ranking of Bids & Determination of L-1 Bidders: Ranking of price bids shall be done on “Item wise L1 basis (Item1 for Sr No 1, Item2 for Sr No 2&3,
Item3 for Sr No 4&5, Item 4 for Sr No 6&7, Item 5 for Sr No 8&9, Item 6 for Sr No 10&11 and Item
7 for Sr No 12&13)” with exclusive of GST.
If any variations in statutory levies, the break up in respect of any charges is clearly and separately
furnished in the bid and the MDL is satisfied that the rates of taxes indicated therein are in line with the
tax law, so that escalation due to variation in the taxes can be justifiably considered to the extent
legitimately allowable on the base amount(s) indicated in the bid. Therefore, bidder is requested to show
the break up regarding taxes as applicable in the bid.
Note:
1. Techno-Commercially Qualified Item wise L1 basis (Item1 for Sr No 1, Item2 for Sr No 2&3, Item3
for Sr No 4&5, Item 4 for Sr No 6&7, Item 5 for Sr No 8&9 and Item 6 for Sr No 10&11 and Item 7
for Sr No 12&13)) lowest bidder exclusive of GST will be considered for the placement of order.
2. On-line Ranking visible to the bidders after opening part II price bid is without loading parameters.
However, the L1 bidder will be evaluated offline after consideration of all applicable loading parameters
as mentioned in the tender document and commercial terms.
3. In case of any discrepancy in the Blank Rate Schedule Format and actual Online Price Bid after opening
of the Price Bids, the details (GST) mentioned in the On-line Price bids shall prevail over the details in
blank rate schedule format.
Page 86 of 116
18 Consignee: The Successful bidder/s shall arrange dispatch of goods by appropriate Rail / Road / Sea / Air
transport mode as per the order to ‘MDL STORES’ and further to User dept. on working days (Monday
to Friday) between 8.00 hrs. to 15.00 hrs. (Lunch Time 11.30 to 12.00 hrs.). In case truck/tempo reaches
our yard beyond above time the same may be retained over night at your risk & cost. Unloading and
stacking the receipt store shall be to bidders account.
An advance copy of invoices along with other relevant documents shall be forwarded to the purchaser
sufficiently in advance to enable clearance of cargo within allowed demurrage free days to avoid
demurrage. In case of door delivery orders, the supplier shall categorically direct the transporter to deliver
the ordered items without insisting for consignee copy of the Lorry Receipt.
19 Modifications to the Bids: - Bidder will not be allowed to bid after the closing time is over.
Bidder can change the submitted bid any number of times till the closing time and the last changed bid will
be considered for ranking of the bids.
20 Public Grievance Cell: A Public Grievance Cell headed by ED (East Yard) has been set up in the
Company. Members of public having complaints or grievances are advised to contact him at 022-
23762121/23759793 on Wednesday between 10.00 hours and 12.30 hours in his office or send their
complaints / grievances to him in writing for redressal.
21 Supply on MDL Holidays: Request for permission for delivery on Saturday / Sunday / holidays if required,
should be submitted 3 working days prior to the date of holiday, to Personnel department and Security
through concerned Dept.
22 Liquidated Damages: Time is an essence of the contract therefore the job, as ordered (Complete Scope
of supply), should be completed on the dates mutually agreed upon in accordance with the
delivery/completion schedule. In cases of delay not attributable to Purchaser beyond the agreed
schedule, the Successful bidder shall pay liquidated damages, a sum representing 0.5% (Half per cent) per
week or part thereof, subject to maximum of 5% of the final Order / Contract value (Item wise). LD will be
applicable for undelivered items complete in nature.
Vendor / Contractor (Seller) will also be liable to pay Liquidated Damages for late delivery of Manuals,
Drawings and Documentation as agreed to by Purchaser and Vendor / Contractor (Seller) and as stated in
the Purchase Order. The amount of such damages will be clearly defined in the Purchase Order and may
extend up to 5% of the Order Value.
Date of successful completion of entire scope as mentioned in tender/order (including, supply,
installation / erect, testing, commissioning and training, submission of documents, etc.) shall be considered
as date of delivery for purpose of levy of liquidated damages unless specifically mentioned otherwise.
In case of any delay attributable to MDL as certified by the officer in the rank of Chief Manager and above
from the concerned department, such period will not be considered for the purpose of levy of liquidated
damages.
Part levying LD on item-wise and/or quantity-wise may be considered at the sole discretion of MDL.
However, request for levying of LD on activity basis (i.e. separately for receipt of item in MDL,
installation & commissioning, training, submission of documents, etc.) shall not be considered.
23 Hindrance Register: All hindrances with date of occurrences and removal shall be noted in the Hindrance
Register. The Hindrance Register shall be signed by the reps of both MDL as well as Contractor.
24 Assistance for Installation & other Technical activities:
a. Services of engineers/Manpower in connection with assistance of delivery, loading/unloading,
installation, setting-in-work, testing, tuning, commissioning and training to be considered in the scope of
supply.
b. All machinery, equipment’s, Oxygen/other fuel gas for cutting, fork lift, welding, Tools & Tackles,
accessories, spares, Chemicals, consumables, Special tools, Fixtures and tackles, Workshop and
fabrication shop, Calibration facility and Local transportation, storage & preservation materials, Ist fill of
Page 87 of 116
Oil, lubricants, grease & other resources etc. required for Installation, commissioning work to be arranged
by contractor. Space, water & electricity will be provided by MDL.
c. The entire maintenance / repair job shall be carried out by experienced service engineers & technicians.
The supply of all necessary tools, tackles and instruments required for the preventive and breakdown
maintenance of the equipment covered by this contract shall be in contractor’s scope. No sub-contracting
will be allowed.
25 Spares / Post Sale Product Support:
a. The Bidder shall assure a continuous supply of spare parts for at least 10 years from the date of
commissioning of the machine at MDL.
b. List of Service centers & Setup details to be provided.
c. Standard accessories required for making item/equipment/machine operational & ready to use should
be included in the scope of supply.
d. All defective parts / spares can either be repaired or replaced by new parts. Spares replaced will be
either of same make or equivalent as suggested by the OEM after consultation with MDL. However, the
total responsibility of the quality of spares supplied or parts repaired, shall be with the Contractor.
e. If any defective part/item/equipment required to be taken out to the service center by the firm for the
further repairing, the firm shall be asked to submit the necessary indemnity bond/BG as required. Taking
out defective part/item/equipment from MDL and bringing back repaired part/ item/ equipment to MDL
is in the firm’s scope of work. The firm has to bear all the transportation charges & transit insurance.
26 Inspection -
(a) Pre Dispatch Inspection: Pre Dispatch inspection of the manufactured Distribution Panel will be
carried out at manufacturer’s works by MDL representative/s. Technical specification as per Scope
of work and Performance Parameters of Distribution Panel will be checked. During the Pre-Dispatch
Inspection. The Vendor shall give a 10 days’ prior intimation for the same. The Distribution Panel
along with accessories and fittings shall be dispatched only after dispatch clearance from MDL.
(b) Receipt Inspection: Inspection will be carried out by Inspection cell along with user department, on
receipt of material in MDL. MDL shall carry out necessary inspection of the items on receipt in the
MDL Yard on the basis of appropriate MDL Inspection system requirements along with the
representative of user dept. & the Inspection documents submitted by suppliers. Any objection raised
by MDL inspection team against quality of material or workmanship shall be satisfactorily corrected
by the supplier at his expenses including replacement as may be required within shortest possible time
within 30 days. Items damaged during transit shall also be rectified or replaced by the supplier within
shortest possible time.
(c) Rejection of the material: Any portion of the equipment found defective/rejected, the supplier shall
collect the same at his cost from the MDL Yard, all incidental charges being born by supplier,
(inclusive of custom duty, if payable), within 30 days from the date of intimation to the supplier of
such rejection. The MDL reserves the rights to dispose of the rejected item at the end of a total period
of 90 days in any manner, to the best advantage to the MDL& recover storage charges & any
consequential damages, from sale proceeds of such disposal.
(d) Final work completion certificate in respect of completion of entire scope of work will be certified
by MDL user dept. not rank below Chief Manager for payment purpose.
27 RISK PURCHASE & CANCELLATION OF ORDER:
(a) If the equipment / article / service or any portion thereof be not delivered / performed by the
scheduled delivery date / period, any stoppage or discontinuation of ordered supply / awarded
contract without written consent by Purchaser or not meeting the required quality standards the
Purchaser shall be at liberty, without prejudice to the right of the Purchaser to recover Liquidated
Damages / penalty as provided for in these conditions or to any other remedy for breach of contract,
Page 88 of 116
to terminate the contract either wholly or to the extent of such default. Amounts advanced or part
thereof corresponding to the undelivered supply shall be recoverable from the Contractor / Bidder
at the prevailing bank rate of interest.
(b) The Purchaser shall also be at liberty to purchase, manufacture or supply from stock as it deems
fit, other articles of the same or similar description to make good such default and or in the event
of the contract being terminated, the balance of the articles of the remaining to be delivered there
under. Any excess over the purchase price, cost of manufacture or value of any articles supplied
from the stock, as the case may be, over the contract price shall be recoverable from the Bidder /
Vendor / Contractor.
(c) The Purchaser reserves the right to cancel an order forthwith without any financial implications on
either side, if on completion of 50% of the scheduled delivery/Completion period the progress of
manufacture/Supply is not to the satisfaction of Purchaser and failure on the part of the
Bidder/Vendor/Contractor to comply with the delivery schedule is inevitable. In such an event the
Bidder/Vendor/Contractor shall repay all the advances together with interest at prevailing bank
rates from the date of receipt of such advances till date of repayment. The title of any property
delivered to Purchaser will be reverted to the Bidder/Vendor/Contractor at his cost.
(d) In case of breach / non-compliance of any of the agreed terms & conditions of order / contract.
MDL reserves the right to recover consequential damages from the vendor / contractor on account
of such premature termination of contract.
(e) In case of delay beyond agreed period for liquidated damages or 10weeks from contractual delivery
period whichever is earlier, MDL reserves the right to cancel the order and procure the order items
/ services from any available source at MDL’s option & discretion and entirely at your risk and
cost. Extra expenditure incurred by MDL in doing will be recoverable from Bidder/ Supplier/
Contractor.
28 INDEMNIFICATION:
The Bidder / Vendor / Contractor, his employees, licencees, agents or Sub-Vendor / Sub-contractor, while
on site of the Purchaser for the purpose of this contract, indemnifies the Purchaser against direct damage
and or injury to the property and or the person of the Purchaser or that of Purchaser's employees, agents,
Sub- Contractors / Suppliers occurring and to the extent caused by the negligence of the Bidder / Vendor /
Contractor, his employees, licencees, agents or Sub-contractor by making good such damages to the
property, or compensating personal injury and the total liability for such damages or injury shall be as
mutually discussed and agreed to.
29 In case of any clarifications, bidders are requested to contact the undersigned, before the closing date of
the tender. Bidders can also contact toll-free customer help line of e-procurement portal
https://eprocuremdl.nic.in
Training program is arranged in MDL Premises on every working Fridays in one session (1400 – 1600
hrs.) for prospective/willing Bidders. For any further details of e-tendering & digital signatures, please
contact on email id: [email protected], Ph. no. 0120-4200462, 0120-4001002
Bidders intending to witness the Tender opening shall log on to https://eprocuremdl.nic.in using
digital signatures for witnessing the opening
30 MDL reserves the right to consider placement of Order / Contract in part or in full against the tendered
quantity or item or scope of supply. MDL reserves the right to place order on FOB or CIF basis.
31 Bidders can participate in online bidding
By registering with above referred portal for User ID and password.
By obtaining class III DSC (Digital Signature Certificate) for secured bidding.
Page 89 of 116
32 In case Indian representative of overseas bidders are participating on behalf of their principal, an
Authorization letter from their principal stating, “they are authorized to quote on behalf of their
principal to this tender” should be uploaded with Part-I bid.
33 In case of improper on-line filling of Acceptance Formats for Tender Enquiry Form, General Terms &
Conditions (GT&C) and Standard Terms & Conditions (STACS), it shall be presumed that all our tender
terms & conditions are acceptable to you.
34 Invoices should be submitted immediately within two to three MDL working days (preferably the
invoices should accompany supply) after execution of the orders/expiry of contract. Thereafter any
discrepancies/pending claims regarding payment or any other matter related to this order/contract should
be brought to MDL’s notice in writing within 30 days of otherwise final payment by MDL, beyond which
no claims whatsoever will be entertained.
35 The contract will be governed by STACS and General Terms and conditions while executing work. In
case of discrepancy, clauses mentioned in Tender, Technical Scope and Rate sheet will override the
clauses mentioned in other annexure including STACS & GT&C.
36 MDL shall not be bound by any printed conditions or provisions in the sellers bid forms or
acknowledgement of contract, invoices, packing list and any other documents which purport to impose
any conditions at variance with the tender terms / final negotiated & accepted terms.
37
PURCHASE PREFERENCE TO MAKE IN INDIA:
As per Public Procurement Order Ref No. P-45021/2/2017-B. E-II dtd. 15.06.2017 issued by Govt. of India
to encourage “Make in India” policy, Purchase Preference shall be given to local suppliers in the following
manner.
(a) The terminology/ definitions used in the said order is as below:
(i) “Local content” means the amount of value added in India, be the total value of items
procured excluding net domestic indirect taxes) minus the value of imported content in
the item (including all customs duties) as a proportion of the total value in percent.
(ii) “Local Supplier” means a supplier or service provider whose product or service offered
for procurement meets the minimum local content, as prescribed under the said Order or
by the competent Ministries / Department in pursuance of said order.
A Local Supplier can be an Indian or Foreign bidder.
(iii) “Margin of Purchase Preference” means the maximum extent to which the price quoted
by local supplier may be above the L1 for the purpose of purchase preference. The margin
of purchase preference for the present tender is 20%.
(b) Minimum local content:
(i) The minimum local content in the offer is to be not less than 50% for the present tender
for a bidder to be considered as a Local Supplier.
(ii) The local content can be increased through partnerships, cooperation with local
companies, establishing production units in India or Joint Ventures (JV) with Indian
suppliers, increasing the participation of local employees in services and training them.’
(iii) On opening of the price bids, if it is identified that there is difference in price receive &
declaration made and local content is now not meeting the specified tender requirement
(i.e. only on the quoted price without any loading) then such case will be processed
without any purchase preference.
(c) Declaration by Local Supplier: Local Supplier should declare that the item and service offered
meets the minimum local content & indicate its percentage in their offer which shall meet (or even
offer more) required content as specified in tender. This declaration is necessary even if Custom Duty
Exemption and / or ERV (if applicable) are not being sought. Following documents are to be
submitted in technical offer -Part-I bid:
(i) Local Component list i.e. Items and services which are being procured / produced
domestically by supplier in the system / equipment / service offered against tender. This
list shall include all the components, raw materials, sub services etc.
Page 90 of 116
(ii) Foreign / Imported Component list i.e. Items and services which are being supplied by
bidder from outside India in the system / equipment / service offered against tender. This
list shall include all the components, raw materials sub services etc.
(iii) Bidders shall give the details of the location(s) at which the local value addition is made.
Additionally, location(s) details from where foreign / imported components are being
supplied be also informed.
(iv) Bidders shall give the price break-up in percentage for “Local Component” and “Foreign
/ Imported Component”.
(v) Custom duty applicable on FE component for all foreign items.
(vi) The Local Suppliers are required to provide self-certification as per Enclosure-11.
Note:
In cases of procurement for value in excess of Rs. 10 Crores, the local supplier shall be required
to provide a certificate from statutory auditor or cost auditor of the company (in case of
companies) or from a practicing cost accountant or practicing charted accountant (in respect
of supplier other than companies) giving the percentage of local content & applicable item
wise custom duty.
Once the declaration / certification is committed at tender submission stage, the same cannot
be altered at technical negotiation stage or after award of contract otherwise would be treated
/ considered as false declaration by bidder.
In the event of bidders not declaring or declaring less local content percentage in the offer,
MDL will consider quote / bid of such bidders with local content as “0” or “NIL” i.e. the offers
of such bidders will be treated as a “Non Local Supplier” where no purchase preference shall
be granted to these bidders.
(d) If the Local Supplier is also a MSE Vendor seeking the benefit of Public Procurement Policy for
MSEs –Order 2012, then such bidders should not seek benefits against the Preference to Make in
India policy – Order 2017. Such bidders should categorically seek benefits of only one policy which
cannot be modified subsequently, once declared in the Annexure-A referred above while submitting
the bid.
(e) Custom duty issue: Imported / FE content is inclusive of all custom duties which is required for
arriving local content. Bidders to note the following about declaration of FE Content.
(i) All bidders should upfront declare line item wise custom duty duly certified. Such declared
custom duty percentage will only be considered for arriving local content.
(ii) In the event if the rate of custom duty is found higher than the declared custom duty by
bidder, then the bidder’s declaration shall be final for arriving L1 bid. Also in such case the
difference in custom duty would be to bidders account. In case of foreign bidders, the same
would be to bidders account and shall not be borne or reimbursed by Shipyard.
(iii) In the event of rate of custom duty happens to be lower at the time of clearance of goods,
then actual custom duty shall be payable.
(iv) Notwithstanding above, local content shall be calculated based on the declared custom duty
by the bidder in techno-commercial bid.
(f) Preference to Local Supplier: The following procedure will be adopted for deciding on preference
to Local Supplier over a non-local supplier w.r.t. Public Procurement (Preference to Make in India)
order 2017.
(i) Among all qualified bids, the lowest bid will be termed as L1. If L1 is from a local supplier,
the contract will be awarded to L1.
(ii) If L1 is not from a local supplier, the lowest bidder among the local suppliers, will be invited
to match the L1 price subject to local supplier’s quoted price falling within the margin of
purchase preference and contract shall be awarded to such local supplier subject to matching
the L1 price.
Page 91 of 116
38
(iii) In case such lowest eligible local supplier fails to match the L1 price, the local supplier with
the next higher bid within the margin of purchase preference shall be invited to match the L1
price and so on and contract shall be awarded accordingly. In case none of the local suppliers
within the margin of purchase preference matches the L1 price, then the contract may be
awarded to the L1 bidder.
(g) Preference between LS and MSE Bidder: {This clause is applicable only if line items are
separable and MSE preference clause is also applicable} Between the MSE and Local Supplier,
the MSE bidder will be given preference to match with L1 bidder as per Public Procurement Policy
for MSEs Order 2012. MSE vendor will be evaluated with L1+15%. MSE doesn’t fall under Public
Procurement (Preference to Make in India) Order 2017
Local Supplier will be evaluated with L1+20% (Margin of Purchase Preference ordinary) as per
Public Procurement (Preference to Make in India) Order 2017.
(h) After the contract is awarded and the supplies are completed, each supplier shall provide the
supporting documentation towards realization of committed Local Content as per the contract / order
terms & conditions. In addition to these documents, a “Local content certificate” also shall be
submitted stating the percentage of local content in the items or services measured. The “Local
content certificate” shall be submitted along with the invoice.
Note: In cases of procurement for value in excess of Rs. 10 Crores, the local supplier shall be required
to provide a certificate from statutory auditor or cost auditor of the company (in case of companies)
or from a practicing cost accountant or practicing charted accountant (in respect of supplier other
than companies) giving the percentage of local content.
(i) False declaration will be in breach of Code of Integrity under Rule 175(1)(i)(h) of GFR 2017 for
which a bidder or its successor can be debarred for up to 2 years as per Rule 151(iii) of GFR 2017
along with such other actions as may be permissible under law.
(j) Complaints / Grievance: Any complaints / grievances relating to implementation of this order shall
be taken up by Public Grievance Cell of MDL headed by ED(EY). Fees for filing a complaint under
the order shall be Rs.10,000/- per case. The complaints shall be filed to the Chairman, Public
Grievance Cell. The fee shall be deposited in MDL’s Account by NEFT.
Freak Low Quotes: In case after opening of price bid of technically cleared firms, it is noted that L-1 firm
has quoted very low rates and indicates to withdraw from the tender then EMD shall be forfeited and firm
may be given tender holiday including intimation to other PSUs. If the rates quoted are less than MDL
estimates by 40% or so and if the difference in rate between L1 and L2 is 30% or more than the firm will have
to give additional BG of 20% of the PO value as additional security. Bank charges for this additional BG shall
be borne by MDL and reimbursed against proof of payment.
39 Option Clause: MDL retains the right to place orders for additional quantities up to a maximum of 50% of
the originally contracted quantity at the same rate and terms of the contract. Such an option shall be available
during the original period of contract. Optional quantity during extended Delivery period is limited to 50%
of balance quantity after original delivery period.
40 We look forward to your participation in on-line bidding by offering your most competitive and
reasonable bid against this tender.
e-tender enquiry acceptance form is uploaded at Stage Name: Part-I (Techno Commercial Bid)
Yours faithfully,
For MAZAGON DOCK SHIPBUILDERS LIMITED,
Saiprasad C. Waingankar
Manager (C-MP)
Page 92 of 116
Enclosure - 1 : Illustrative format & guideline for quoting prices in online Price Bid.
Enclosure 1A : Guidelines for EMD payment
Enclosure 2 : Instruction for e-tendering.
Enclosure - 3 : Standard Terms & Conditions (STACS)
Enclosure - 4 : General Terms & Conditions (GT&C)
Enclosure - 5 : Loading Factors
Enclosure - 6 : Bank Guarantee Format for EMD
Enclosure - 7 : Bank Guarantee Format for SD
Enclosure - 8 : Bank Guarantee Format for PBG
Enclosure - 9 : MDL bank details for NEFT/RTGS EMD/SD transfer
Enclosure - 10 : Vendor declaration Form
Enclosure - 11 : Declaration Certificate for Local Content
Note: * These documents to be down loaded from our Website. (www.mazdock.com Path Tenders
Ship Building-Material Purchase SB-MP STACS/Formats )
Page 93 of 116
Enclosure-1
Illustrative format & guideline for quoting prices in online Price Bid
Below format of price bid will appear online. Indigenous bidders to follow instructions given in each
respective cell while quoting their cost in online price bid:
Item Sr. no. 1 to 12
Material Description As per clause No 1
Quantity As per clause No 1
Unit of measurement Nos / AU
Currency INR
For Indian Bidder Basic Unit Rate in INR only.
For Foreign Bidder CIF Rate to be entered by the foreign
currency
To be quoted
% of CGST+SGST or IGST on Basic rate To be quoted
Installation / Commissioning Charges To be quoted
% of CGST+SGST or IGST on Installation / Commissioning
Charges To be quoted
Page 94 of 116
Enclosure -1A
Bidders can make online payment of EMD/Security deposit / Performance bank guarantee using following
links: -
(i) Go to www.mazagondock.in
(ii) Click on online payment tab available on home page.
(iii) 4 options viz. career, tender, security, scrap/disposal will be available.
(iv) Click on the respective tabs (i.e. tender) and make the payment online using debit cards, credit cards,
net banking, BHIM/UPI etc., after filling the required details.
In case bidder has any genuine difficulty with respect to online payment, the receipts through the
conventional method of NEFT/RTGS is also accepted.
Electronic Payment Mandate Form
(MDL Bank details)
Name of the Company/Firm Mazagon Dock Shipbuilders Ltd
Address with Phone no. Dockyard Road, Mumbai – 400010
E-Mail ID
Phone No. +91 22 23745310
Fax No.
Particulars of Bank Account
Name of the Bank State Bank of India
Name of the Branch Mazagon Dock Mumbai Branch
Branch Code 9054
Bank IFSC / NEFT Code SBIN0009054
Bank Address MBPT Workshop building, N.V Nakhwa Road, Mazagon -
400010
City Name Mumbai
Telephone No. of Bank +91 22 23752802
9 digit code no. of bank &
branch appearing on the MICR
cheque issued by your bank
400002120
Type of Account Current Account
Account No. 10005255246
Income Tax PAN No. AAACM8029J
Page 95 of 116
ENCLOSURE – 2
Instructions to the Bidders for uploading the Techno-Commercial Bid and the Price Bid through E-Procurement Portal:
Official service provider for the website is
NIC, E-mail: [email protected] Office Ph. No.: 0120-4200462, 0120-4001002, Ph. No.: +91-8826246593
Pre-requisites for up-loading the Techno-Commercial Bid
(i) Compatible computer hardware software set-up to access e-procure website.
(ii) “Digital Signature Certificate” class III B (DSC) is a must for downloading the tender and uploading the techno commercial offer from our website https://eprocuremdl.nic.in.
(iii) “Digital Signature Certificate” class III B (DSC) can be obtained from our service provider.
To ensure availability of above prerequisite is bidders responsibility
(i) It is mandatory to upload the complete techno-commercial offer and the price bid on e-procurement.
(ii) No part of the bid other than original EMD (if applicable) shall be accepted physically / hard copy outside e-procurement.
(iii) Price bids shall strictly be uploaded in appropriate / allotted place in the tender, available in e-procurement so that it remains secured encrypted unreadable in the system.
(iv) In no circumstances, the price bids shall be forwarded or uploaded in any other form.
(v) Entire responsibility of the uploading of the complete techno-commercial bid along with the price bid shall be that of the bidder.
(vi) No request / complaint shall be entertained after the due date/time of the tender.
(vii) Non availability of any of the prerequisites or last minute calls seeking clarifications / projecting problems shall not entitle a bidder to seek request for extension of due date.
(viii) Any problem with regard to uploading of the tender shall be intimated to NIC at least 24 hours in advance to the tender closing time & date. However, it will not be considered as reason for extension of due date of the tender.
(ix) Request for extension, if at all to be made, shall be forwarded at least 3 working days in advance to the tender closing date / time with proper reasoning. The request shall be put up to the competent authority for consideration on the merit of the case. MDL reserves all rights in this regard & decision of MDL shall be binding to the applicant.
It is important to note that the bidders can upload their bids right from the time the tender is available at website. It is advisable that the bidder uploads the bid well in time rather than wait till last minute to avoid situations wherein he is unable to successfully upload the bid for various reasons which cannot be addressed then due to lack of time.
Special instructions to Bidders for online bidding:
(i) Bidders should login well in advance to enable them to complete their bid submission before the closing time of the tender.
(ii) Bidders should submit their bid well in advance to avoid last minute frantic calls.
(iii) Bidders should follow all the instructions enlisted on the front page of e-procure web page.
(iv) Bidders should ensure Hardware & Software compatibility as well as Digital Signature available on front page of e-procure web site. Request for extension of due date shall not be entertained due to non-availability of these tools.
Bidders to participate in on-line bidding
(I) By registering with above referred portal for User ID and password.
(ii) By obtaining class III DSC (Digital Signature Certificate) for secured bidding
Page 96 of 116
NOTE: In case any vendor intending to respond against the tender and is not having the DSC to facilitate uploading of his bid, should approach the Service Provider at least 10 working days in advance of the tender closing date requesting DSC. The request so made to the Service Provider should simultaneously be forwarded to MDL Dealing Officer. In case the DSC is not received within 3 to 4 working days, the GM (M) be informed and the DSC if not received from the Service Provider three working days in advance, for suitable extension to tender closing date then only the tender due date shall be considered.
Page 97 of 116
Enclosure-3
STANDARD TERMS AND CONDITIONS (STACS)
101. The word 'Purchaser' refers to MAZAGON DOCK SHIPBUILDERS LIMITED, (MDL), a Company
registered under the Indian Companies Act, 1913 and it includes its successors or assignees.
102. The word 'Bidder/Vendor/Contractor' means the person / firm / Company who undertakes to
manufacture and or supply and or undertake work of any nature assigned by the Purchaser from time to
time and includes its successors or assignees.
103. The word 'Owner' means the person or authority with whom MAZAGON DOCK SHIPBUILDERS
LIMITED (Purchaser) has contracted to carry out work in relation to which orders are placed by the
Purchaser on the Bidder/Vendor/Contractor under this contract for supply or manufacture of certain items
and would include Department of Defence Production, Ministry of Defence, Government of India, the
Indian Navy, the Coast Guard and any other specified authority.
120. GENERAL
121. UNLESS OTHERWISE INDICATED SPECIFICALLY BY THE BIDDER / CONTRACTOR IN
HIS BID, IT SHALL BE CONSTRUED AS HIS ACCEPTANCE OF ALL THE CONDITIONS
MENTIONED IN THIS STACS.
200. COMMUNICATION & LANGUAGE FOR DOCUMENTATION
201. Any letter, facsimile message, e-mail intimation or notice sent to the Bidder/Vendor/Contractor at the
last known address mentioned in the offer / order shall be deemed to be valid communication for the
purpose of the order/contract. Unless stated otherwise by the purchaser, Language for communication &
all documentation shall be same, which the Purchaser has used, in the tender enquiry.
210. PURCHASER’S PROPERTY 211. All property (such as materials, drawings, documents etc) issued by the Purchaser or any other
individual or firm on behalf of the Purchaser in connection with the contract shall remain confidential,
being the property of the Purchaser and the Bidder/Vendor/Contractor shall undertake to return all such
property so issued and will be responsible for any or all loss thereof and damage thereto resulting from
whatever causes and shall reimburse the Purchaser the full amount of loss and damage.
212. On completion of work in any compartment / location of the purchaser’s premises, the
Bidder/Supplier/Contractor must ensure that the place is left in a reasonably clean state and all scrap is
transferred to nearby scrap-bins.
220. RISK PURCHASE
221. If the equipment / article / service or any portion thereof be not delivered / performed by the scheduled
delivery date / period, any stoppage or discontinuation of ordered supply / awarded contract without written
consent by Purchaser or not meeting the required quality standards the Purchaser shall be at liberty, without
prejudice to the right of the Purchaser to recover Liquidated Damages / penalty as provided for in these
conditions or to any other remedy for breach of contract, to terminate the contract either wholly or to the
extent of such default. Amounts advanced or part thereof corresponding to the undelivered supply shall be
recoverable from the Contractor / Bidder at the prevailing bank rate of interest.
222. The Purchaser shall also be at liberty to purchase, manufacture or supply from stock as it deems fit,
other articles of the same or similar description to make good such default and or in the event of the contract
being terminated, the balance of the articles of the remaining to be delivered there under. Any excess over
the purchase price, cost of manufacture or value of any articles supplied from the stock, as the case may
be, over the contract price shall be recoverable from the Bidder / Vendor / Contractor.
230. RECOVERY ADJUSTMENT PROVISIONS
Page 98 of 116
231. Payment made under one order shall not be assigned or adjusted to any other order except to the extent
agreed upon in writing by the Purchaser. During the currency of the contract, if any sum of money is
payable by the Bidder / Vendor / Contractor the same shall be deducted from any sum then due or thereafter
may become due to the Bidder / Vendor / Contractor under the contract or any other contract with the
Purchaser.
240. ADDITIONAL BANK GUARANTEE In case after opening of price bid of technically cleared firms, it is noted that L-1 firm has quoted very low
rates and indicates to withdraw from the tender then EMD shall be forfeited and firm may be given tender
holiday including intimation to other PSUs. If the rates quoted are less than MDL estimates by 40% or so
and if the difference in rate between L1 and L2 is 30% or more then the firm will have to give additional
BG of 20% of the PO value as additional security. Bank charges for this additional BG shall be borne by
MDL and reimbursed against proof of payment.
250. INDEMNIFICATION
251. The Bidder / Vendor / Contractor, his employees, licencees, agents or Sub-Vendor / Sub-contractor,
while on site of the Purchaser for the purpose of this contract, indemnifies the Purchaser against direct
damage and or injury to the property and or the person of the Purchaser or that of Purchaser's employees,
agents, Sub- Contractors / Suppliers occurring and to the extent caused by the negligence of the Bidder /
Vendor / Contractor, his employees, licencees, agents or Sub-contractor by making good such damages to
the property, or compensating personal injury and the total liability for such damages or injury shall be as
mutually discussed and agreed to.
260. TRANSFER OF VENDORS / CONTRACTOR’S RIGHTS:
261. The Bidder / Vendor / Contractor shall not either wholly or partly sell, transfer, assign or otherwise
dispose of the rights, liabilities and obligations under the contract between him and the Purchaser without
prior consent of the Purchaser in writing.
270. SUBCONTRACT & RIGHT OF PURCHASER
271. The Bidder / Vendor / Contractor under no circumstances undertake or subcontract any work / contract
from or to any other Sub-contractor without prior written approval of the Competent Authority of
Purchaser. In the event it is found that such practice has been indulged in, the contract is liable to be
terminated without notice and the Bidder / Vendor / Contractor is debarred all from future tender enquiries
/ work orders. However, in no circumstances a contractor is permitted to subcontract any part of the contract
to the bidders who had quoted for the concerned tender.
280. PATENT RIGHTS 281. The Bidder / Vendor / Contractor shall hold harmless and keep the Purchaser indemnified against all
claims arising as a result of infringement of any patent / copy rights on account of manufacture, sale or use
of articles covered by the order.
290. AGENTS / AGENCY COMMISSION:
291. The seller confirms and declares to the buyer that the seller is the original manufacturer or authorized
distributor/stockiest of original manufacturer of the stores referred to in this contract and has not engaged
any individual or firm, whether Indian or foreign whatsoever, to intercede, facilitate or in any way to
recommended to the Buyer or any of its functionaries, whether officially or unofficially , to the award of
the Contract / Purchase order to the Seller; nor has any amount been paid, promised or intended to be paid
to any such individual or firm in respect of any such intercession, facilitation or recommendation. The
Seller agrees that if it is established at any time to the satisfaction of the Buyer that the present declaration
is in any way incorrect or if at a later stage it is discovered by the Buyer that the Seller has engaged any
such individual/firm, and paid or intended to pay any amount, gift, reward, fees, commission or
consideration to such person, party, firm or institution, whether before or after the signing of this Contract
/ Purchase order, the Seller will be liable to refund that amount to the Buyer.
The seller will also be debarred from participation in any RFQ/Tender for new projects/program with Buyer
for a minimum period of five years.
Page 99 of 116
The buyer will also have a right to consider cancellation of the Contract either wholly or in part, without
any entitlement or compensation to the Seller who shall in such event be liable to refund all payments made
by the buyer in terms of the Contract along with interest at the rate of 2% per annum above LIBOR (London
Inter Bank Offer Rate) (for foreign vendors) and base rate of SBI plus 2% (for Indian Vendors).
The Buyer will also have the right to recover any such amount from any contracts concluded earlier with
Buyer.
300. USE OF UNDUE INFLUENCE / CORRUPT PRACTICES:
301. The Bidder / Supplier / Contractor undertakes that he has not given, offered or promised to give,
directly or indirectly any gift, consideration, reward, commission, fees, brokerage or inducement to any
person in service of the Purchaser or otherwise in procuring the contract or forbearing to do or for having
done or forborne to do any act in relation to the obtaining or execution of the Contract with the Purchaser
for showing or forbearing to show favour or disfavour to any person in relation to the Contract or any other
Contract with the Purchaser. Any breach of the aforesaid undertaking by the Bidder / Supplier / Contractor
or any one employed by him or acting on his behalf (whether with or without the knowledge of the Bidder
/ Supplier / Contractor) or the commission of any offence by the Bidder / Supplier / Contractor or any one
employed by him or acting on his behalf, as defined in Chapter IX of the Indian Penal Code, 1980 or the
Prevention of Corruption Act, 1947 or any other Act enacted or the prevention of corruption shall entitle
the Purchaser to cancel the contract and all or any other contracts with the Bidder / Contractor / Supplier
and recover from the Bidder / Supplier / Contractor the amount of any loss arising from such cancellation.
Decision of the Purchaser or his nominee to the effect that a breach of the undertaking has been committed
shall be final and binding on the Bidder / Supplier / Contractor.
302. The Bidder / Supplier / Contractor shall not offer or agree to give any person in the employment of
Purchaser any gift or consideration of any kind as "Inducement" or "reward" for doing or forbearing to do
or for having done or forborne to do any act in relation to the obtaining or execution of the contract/s. Any
breach of the aforesaid condition by the Bidder / Supplier / Contractor or any one employed by them or
acting on their behalf (whether with or without the knowledge of the Bidder / Supplier / Contractor) or the
commission of any offence by the Bidder / Supplier / Contractor or by any one employed by them or acting
on their behalf which shall be punishable under the Indian Penal Code 1980 and/or the Prevention of
Corruption by Public Servants, shall entitle Purchaser to cancel the contract/s and all or any other contracts
and then to recover from the Bidder / Supplier / Contractor the amounts of any loss arising from such
contracts' cancellation, including but not limited to imposition of penal damages, forfeiture of Security
Deposit, encashment of the Bank Guarantee and refund of the amounts paid by the Purchaser.
303. In case, it is found to the satisfaction of the Purchaser that the Bidder / Supplier / Contractor has
engaged an Agent or paid commission or influenced any person to obtain the contract as described in
clauses relating to Agents / Agency Commission and use of undue Influence, the Bidder / Supplier /
Contractor, on a specific request of the Purchaser shall provide necessary information / inspection of the
relevant financial document / information.
310. IMMUNITY OF GOVERNMENT OF INDIA CLAUSE
311. It is expressly understood and agreed by and between M/s. (Bidder / Supplier / Contractor) and
MAZAGON DOCK SHIPBUILDERS LIMITED, Dockyard Road, Mumbai - 400 010 (MDL) is entering
into this Agreement solely on its own behalf and not on the behalf of any person or entity. In particular, it
is expressly understood and agreed that the Government of India is not a party to this Agreement and has
no liabilities, obligations or rights hereunder. It is expressly understood and agreed that MDL is an
independent legal entity with power and authority to enter into contracts solely in its own behalf under the
applicable of Laws of India and general principles of Contract Law. The (Bidder / Supplier / Contractor)
expressly agrees, acknowledges and understands that MDL is not an agent, representative or delegate of
the Government of India. It is further understood and agreed that the Government of India is not and shall
not be liable for any acts, omissions and commissions, breaches or other wrongs arising out of the contract.
Accordingly, (Bidder / Supplier / Contractor) hereby expressly waives, releases and foregoes any and all
actions or claims, including cross claims, impleader claims or counter claims against the Government of
Page 100 of 116
India arising out of this contract and covenants not to sue Government of India in any manner, claim, cause
of action or thing whatsoever arising of or under this Agreement.
320. EXPORT LICENCE
321. The export licenses that may be required for delivery of the various items/equipment to MDL shall be
arranged by the Bidder / Supplier / Contractor from the concerned authorities in their country without any
time & cost implications on the Purchaser.
330. BANNED OR DE-LISTED CONTRACTORS / VENDORS.
331. The Bidder / Vendor / Contractor declares that they being Proprietors / Directors / Partners have not
been any time individually or collectively blacklisted or banned or de-listed by any Government or quasi
Government agencies or PSUs. If a bidder’s entities as stated above have been blacklisted or banned or de-
listed by any Government or quasi Government agencies or PSUs, this fact must be clearly stated and it
may not necessarily be a cause for disqualifying him.
340. DUTY OF PERSONNEL OF SUPPLIER/VENDOR
341. MDL being a Defence Organization, Bidder / Vendor / Contractor undertakes that their personnel
deployed in connection with the entrusted work will not indulge in any activities other than the duties
assigned to them.
350. DISPUTE RESOLUTION MECHANISM AND ARBITRATION
351. DISPUTE RESOLUTION MECHANISM (DRM) i) Any dispute/differences between the parties arising out of and in connection with the contract shall be
settled amicably by mutual negotiations.
ii) In case of non-settlement by (i) above, if at any time, before, during or after the contract period any
unsettled claim, dispute or difference arose between the parties, upon or in relation to or in connection with
or in any way touching or concerning this tender/agreement/order/contract, the same shall be referred to
the concerned Functional Director.
The Functional Director shall then nominate an Executive of the rank of General Manager whom he thinks
fit and competent or a Committee of Executives who/which shall then scrutinise the claims/disputes that
have been referred to the concerned functional Director and make efforts for amicable settlements by
mutual discussions/negotiations.
iii) In case no amicable settlement is arrived by (ii) above within a period of three months, then the
contractor shall approach Public Grievance Cell and address the disputes as per the provisions made under
the relevant clause of the contract.
iv) In case the issues/disputes do not get settled within a period of six months from the date of
submission of the dispute to the Grievance Cell, then the contractor may invoke Arbitration Clause of the
contract.
352. ARBITRATION: Unresolved disputes/differences, if any, shall then be settled by arbitration. The
Arbitration proceedings shall be conducted at Mumbai, India, in English Language, under the Arbitration
& Conciliation Act, 1996.
MDL prefers to have arbitration through Institutes such as Indian Council of Arbitration (ICA)/ICA-DR,
with the mutual consent of the parties.
353. In case of unresolved difference/dispute between the Purchaser and Supplier, being Central Public
Sector Enterprises/Central Govt. departments, the disputes shall be resolved firstly through mutual
discussion or through the empowered agencies of the Govt. or through arbitration by reference by either
party to the department of Public Enterprises, as per extant guidelines. If disputes/differences remain
unresolved/unexecuted, the same shall be referred first to the Cabinet Secretariat and then, if necessary to
the PMO.
354. Any changes to arbitration clause must be vetted by HOD (Legal) before incorporation in
contract/PO.
360. JURISDICTION OF COURTS
Page 101 of 116
361. All contracts shall be deemed to have been wholly made in Mumbai and all claims there under are
payable in Mumbai City and it is the distinct condition of the order that no suit or action for the purpose of
enforcing any claim in respect of the order shall be instituted in any Court other than that situated in
Mumbai City, Maharashtra State, India i.e. courts in Mumbai shall alone have jurisdiction to decide upon
any dispute arising out of or in respect of the contract.
-----------------------
Page 102 of 116
Enclosure-4
GENERAL TERMS & CONDITIONS (GT&C)
A10. Blank
A20. SECURITY DEPOSIT
A21. The successful bidder shall submit a Security Deposit @ 5 % of the contract / order value
(excluding taxes, duties, freight, service component) of the Order in the form of Demand Draft / Bank
Guarantee in the prescribed format in favour of Purchaser within 25 days from date of Contract. The
Security Deposit will be returned only after the successful execution of the order / contract. Refund of
Security Deposit whenever considered admissible by the Purchaser, shall be without interest only.
A30. FORFEITURE OF EMD / BID BOND
A31. In cases of withdrawal of bid during validity period or during any extension granted thereof, non-
acceptance of agreed conditions of Technical and or Commercial and or Price Negotiations, non-
submission of the security deposit and / or non-acceptance of the order the EMD or bid security will be
forfeited or encashed as the case may be.
A40. FORFEITURE OF SECURITY DEPOSIT
A41. Non-performance of agreed terms and or default/breach by Bidder/Vendor/Contractor will result in
forfeiture of security deposit with application of risk purchase provisions as felt appropriate by the
Purchaser.
A50. FORFEITURE OF PERFORMANCE GUARANTEE
A51. In the event of Bidder/Vendor/Contractor failure to attend the Guarantee defects within a reasonable
period of time, the Performance Bank Guarantee will be encashed by the Purchaser. The Purchaser’s
decision shall be final and binding on Bidder/Vendor/Contractor
A60. SUPPLIES
A61. The equipment / products / items / Services to be supplied shall be strictly in accordance with the
Drawings / Specifications / Requirements indicated in the Tender Enquiry / Order with deviations, if any,
as mutually accepted.
A70. PROGRESS REPORTING & MONITORING
A71. Where so stipulated in the order, the Bidder / Supplier / Contractor shall render such reports from
time to time as regards the progress of the contract and in such a form as may be called for by the Purchaser.
A80. CANCELLATION OF ORDER
A81.The Purchaser reserves the right to cancel an order forthwith without any financial implications on
either side, if on completion of 50% of the scheduled delivery/Completion period the progress of
manufacture/Supply is not to the satisfaction of Purchaser and failure on the part of the
Bidder/Vendor/Contractor to comply with the delivery schedule is inevitable. In such an event the
Bidder/Vendor/Contractor shall repay all the advances together with interest at prevailing bank rates from
the date of receipt of such advances till date of repayment. The title of any property delivered to Purchaser
will be reverted to the Bidder/Vendor/Contractor at his cost.
A82. In case of breach / non-compliance of any of the agreed terms & conditions of order / contract. MDL
reserves the right to recover consequential damages from the vendor / contractor on account of such
premature termination of contract.
A83. In case of delay beyond agreed period for liquidated damages or 10weeks from contractual delivery
period whichever is earlier, MDL reserves the right to cancel the order and procure the order items /
services from any available source at MDL’s option & discretion and entirely at your risk and cost. Extra
expenditure incurred by MDL in doing will be recoverable from Bidder/ Supplier/ Contractor.
Page 103 of 116
A90. # PRESERVATION AND MAINTENANCE A91. Should any material require any preservation till its final installation/fitment, the detailed procedure
(Long term & short term) for the same as also the time of interval after which the state of preservation
needs to be reviewed is to be stated by the Bidder/Vendor/Contractor.
A92. Further the de-preservation prior to the material/equipment being commissioned and the maintenance
procedure together with its periodicity is also to be indicated by the Bidder / Vendor / Contractor.
A93. The Bidder / Vendor / Contractor in their offer must confirm that indigenous oil; lubricants and
preservatives, etc. can be used in the equipment. The bidder must also give assurance that the equipment
performance will not be downgraded by use of indigenous equivalents
A100. FREIGHT & INSURANCE
A101. For Indigenous Bidders: In cases where the offers are for 'Door Delivery to Purchaser,' transit
freight & Insurance charges shall be borne by the Bidder / Supplier / Contractor. In other agreed cases of
Ex-works / Ex-Transporter's warehouse or Railway go down offers, the Bidder / Supplier / Contractor on
dispatch, shall give details of materials with dispatch particulars and their value in time to Purchaser's
Insurance Company on the contact details as provided in the order. In such agreed cases, the freight &
insurance charges will be paid by the purchaser directly to the parties concerned.
A102. For Foreign Bidders: For overseas supplies on CIF port of dispatch basis, Transit Insurance shall
be arranged by the Purchaser. The Bidder / Supplier / Contractor shall immediately on dispatch of
the items, inform all relevant details of dispatch such as Order number, Bill of Lading/AWB number
marked as Freight Paid, Insurance policy/document, number of packages, value of consignment,
invoice number in time directly to Purchaser's Insurance company & Purchaser on the contact
details as provided in the order. In case of delivery term other than CIF/CIP, the freight & insurance
charges will be paid by the purchaser directly to the parties concerned.
A110. TAXES & DUTIES / STATUTORY LEVIES
A111. Taxes and duties applicable, if any, shall be regularized by MDL by issuing necessary exemption
certificates in respect of procurement for Defence Projects. Bidder shall indicate separately the GST and
duties applicable in their offer. When the items qualify for exemption partly/fully but the supplier did not
avail of the same, the amount of taxes and duties on such supplies shall be to supplier’s account. In cases
where exemption certificates are not issued for any reason, taxes shall be paid as indicated in the Purchase
Order/Contract. Tax deduction at source will be effected wherever applicable (e.g. TDS under Income Tax
Act, TDS on Works Contract under GST Act etc.) from the bills of the Supplier as per statutes. Similarly,
where payment of Custom duty is agreed to and stipulated in the Purchase Order / Contract, the same will
be paid by the Purchaser on receipt of supplier’s bills along with Custom Certified Duty Paid Challan-
Money Receipt in original or carbon copy as relevant. These Challans/ Receipts, Bill of Entry are to be
drawn/ issued in the name of ‘MAZAGON DOCK SHIPBUILDERS LIMITED’ only. Where payment of
GST is agreed to and stipulated in the Purchase Order / Contract, the same will be paid by the Purchaser
on the basis of Suppliers' TAX INVOICE wherein the GST Number along with HSN / SAC code is
indicated in the Invoice.
A120 DEMURRAGE
A121. Storage and Demurrage charges will be payable by the Bidder / Vendor / Contractor for all shipments
that reach purchaser without proper dispatch documentations, Lorry Receipts not accompanied by packing
lists, invoices etc. The Supplier shall be responsible for fines due to errors or omissions in description,
weight or measurements and for increased handling charges due to improper packing.
A130. INSPECTION, TESTING
A131.The ordered items will be inspected either by Classification Society / Nominated Agency and or by
Inspection Officer nominated by Purchaser at stages defined in the tender / Purchase Order or as agreed to
be defined subsequently in terms of the Purchase Order.
Page 104 of 116
A132. The decision of the Inspecting Authority or their representatives, as the case may be, on any question
of the intent, meaning and the scope of Specifications / Standards shall be final, conclusive and binding on
the Bidder/ Vendor / Contractor.
A133. The Bidder / Vendor / Contractor shall accord all facilities to Purchaser's Inspectors / Nominated
Agency to carry out Inspection / Testing during course of manufacture / final testing.
A140. RECEIPT INSPECTION BY MDL
A141. MDL shall carry out necessary inspection of the items on receipt, on the basis of an appropriate
quality assurance system and inspection system requirements along with representative of the Owner. Any
objection raised by MDL Quality Control Team against quality of materials or workmanship shall be
satisfactorily corrected by the Contractor at his expense including replacement as may be required within
shortest possible time within 30 days. Items damaged during transit shall also be rectified / replaced by the
Contractor within shortest possible time, payment for which shall be made at mutually agreed rates .
A150. REJECTION OF MATERIALS A151. Should the articles, or any portion thereof of the equipment be found defective / rejected, the Bidder
/ Vendor / Contractor shall collect the same from the Purchaser's Stores, all incidental charges being borne
by him (inclusive of Custom duty, if payable), within 30 days from the date of intimation to the Bidder /
Vendor / Contractor of such rejection. The Purchaser reserves the right to dispose of the rejected items at
the end of a total period of 90 days in any manner to the best advantage to the Purchaser and recover storage
charges and any consequential damages, from sale proceeds of such disposal.
A160. # TECHNOLOGICAL DEVELOPMENTS / MODIFICATIONS
A161. The Bidder / Supplier / Contractor shall unconditionally and free of cost to the Purchaser transfer
information on technological developments / innovations / modifications which the Bidder/Supplier /
Contractor would evolve in future (within 3 years) in relation to the supplied equipment. To enable this,
the Purchaser's address shall be added to the Bidder / Supplier / Contractor’s mailing list or database or
any other document maintained for dissemination of product information and the Purchaser shall be
informed of the action taken in this regard. If such improvements / modifications are brought in by the
Bidder / Supplier / Contractor’s Design Department in the course of manufacture of equipment ordered by
the Purchaser, the Bidder / Supplier / Contractor shall incorporate such improved versions in the equipment
without any extra cost to the Purchaser under Purchaser’s prior consent.
A162. If the Purchaser be desirous of getting incorporated all post supply modifications / improvements
arising out of technological developments to the original equipment supplied by the Bidder / Supplier /
Contractor, the Bidder / Supplier / Contractor, shall quote for and carry out all such modifications to the
equipment.
A163. Where the whole or a portion of the equipment has been specifically developed by the Bidder /
Supplier / Contractor for the Owner and the latter would through the Purchaser be bearing the entire or part
of the development cost incurred by the Bidder / Supplier / Contractor, the design rights for the whole or
portion thereof, of the equipment as appropriate, shall vest in the Owners.
A164. Prior approval of the Owner should be obtained before similar articles are sold / supplied to any
other party other than the Owner. If such approval is given and sale is effected, the Bidder / Supplier /
Contractor shall pay to the Owner royalty at the rate mutually agreed to.
A165. The Sub-contractor / Supplier / Supplier shall continue to support the equipment for a minimum
period of 20 years from the date of supply by making available spare parts and assemblies of the equipment
supplied. Should the Sub-contractor / Supplier / Supplier decide to discontinue the product, for any reason
whatsoever, adequate notice shall be given to the Purchaser / Owner to enable procurement of the requisite
lifetime spares.
A170. PURCHASER’S RIGHT TO ACCEPT ANY BID, PART OF BID AND TO REJECT ANY
OR ALL BIDS.
A171. The Purchaser reserves the right to accept and or reject any or all tenders and or to withdraw the
tender in Toto and or award the contract / order in full or part to more than one vendor / contractor without
Page 105 of 116
assigning any reason whatsoever and without thereby incurring any liability to the affected Bidder or
Bidders or any obligations to inform the affected Bidder or Bidders of the grounds for MDL action.
A180. # BANK GUARANTEE / INSURANCE COVER FOR FREE ISSUE MATERIAL
A181. The Bidder / Supplier / Contractor shall furnish Bank Guarantee / insurance Cover equivalent to the
value of materials supplied by MDL free of cost valid up to the execution of the contract / delivery of
material, inspected / accepted and receipt at MDL together with the material reconciliation statement
whichever is later.
A190. BIDDER’S RESPONSE IN CASE OF NO PARTICIPATION
A191. The Sub-contractor / Supplier / Vendor shall inform the Purchaser in advance in case he is unable
to participate in the tender for whatsoever reason. Failure to comply with this will be viewed seriously and
consecutive three failures on the part of Sub-contractor / Supplier / Vendor to do so is liable for
disqualification / debarring of the Sub-contractor / Supplier / Vendor from all future tender enquiries and
or delisting from the list of 'Approved Registered Vendors.
A230. PREFERENCETIAL PURCHASE FROM MSE VENDORS – Not Applicable MDL has right to place order on MSE firm meeting following criteria:
In tenders, if participating MSEs quoted prices are within price band of L1+15%, such MSEs shall also be
allowed to supply a portion up to 20% of requirement by bringing down their prices to L1 price where L1
is non MSEs. If more than 1 MSEs fall under such criteria, then this 20% shall be distributed proportionally.
This preference shall not be applicable where MSE firm is L1 firm. % out of 20 percent target of annual
procurement from Micro and Small Enterprises, a sub-target of 20 percent (i.e. 4 percent out of 20 percent)
shall be earmarked for procurement from Micro and Small Enterprises owned by the Scheduled Caste or
the Scheduled Tribe Entrepreneurs. In respect of items reserved for MSE, extant guidelines shall be
followed. Presently Circular No. S.O. 581(E) dated 23.03.2012 is applicable.
------------------------
Page 106 of 116
Enclosure-5
LOADING FACTORS FOR RANKING OF BIDS
(ILLUSTRATIVE FORMAT)
A
Sr.No. Description Foreign
Supplier with
100% Import
Content
Indigenous
Supplier with part
Import Content
Indigenous
Supplier without
Import Content
1
Basic price Quoted
CIF
a) Ex Works
b) Delivered to MDL
stores
a) Ex Works
b) Delivered to MDL
stores
2
Add: insurance charges
Nil
In case of 1(a)
In case of 1(a)
3 Add Sea/Air Freight charges /
Inland Road Transport
Nil
In case of 1(a)
In case of 1(a)
4 Customs Clearance / Port
Handling / Transportation to
Yard
Applicable
NIL
NIL
5 Cost (ex-MDL) excluding
taxes & duties without
loading towards any
deviations
CIF price +
Sr.No.4
Sr. Nos. (1+2+3)
Sr. Nos. (1+2+3)
B Loading due to variations in Financial Term.
Sr.No. Description Foreign Supplier Indigenous Supplier
6 Variation in payment Terms
7 Income Tax & Service Tax on
Technical Services / Service
engineers liability to MDL.
8 Production Norms such as Scrap %,
output-input ratio
9 Base date for price variation clause
10 Cost (ex-MDL) excluding taxes &
duties after loading for variations in
financial term.
Sr. Nos. 5 + 6+7+8+9
C Loading on Account of deviations in following commercial terms
Sr.No. Description Foreign Supplier Indigenous Supplier
11 Security Deposit / Contract
performance guarantee.
Mandatory
12 Equipment Performance guarantee Mandatory
13 Additional delivery period sought
over stipulated period as per Tender
14 Additional time sought for
supplying binding data.
15 Liquidated damages per week rate /
maximum ceiling
16 Warranty / Guarantee
17 Cost (ex-MDL) excluding taxes &
duties after loading for variations on
account of financial and commercial
terms.
Sr. Nos. 10 +11+ 12 +13 +14 +15 +16
D. Landed Cost:
Sr.No. Description Foreign Supplier Indigenous Supplier
18 GST
19 Landed Cost Sr.Nos.17+18
Page 107 of 116
Enclosure-6
PROFORMA BANK GUARANTEE FOR BID BOND / EMD
(On Non-Judicial stamp paper of value Rs. 100/-)
IN CONSIDERATION OF MAZAGON DOCK SHIPBUILDERS LIMTED, a company incorporated
under the Companies Act 1956 and having its registered office at Dockyard Road, Mumbai 400010
(hereinafter referred to as the “the Company” which expression shall, unless it be repugnant or contrary to
the subject or context thereof, be deemed to mean and include its successors and assigns) having agreed to
accept the Earnest Money Deposit (EMD) of Rs--------------------------- -------(Rupees-------------------------
----only) in the form of Bank Guarantee from Messers ............................ a partnership firm/sole proprietor
business/a company registered under the Companies Act, 1956 having its office at
...............................(hereinafter called " the tenderer" which expression shall, unless it be repugnant or
contrary to the subject or context thereof, be deemed to mean and include its successors and assigns) for
participating in the Tender no..................................dated.............. (hereinafter called "the tender" which
expression shall include any amendments/alterations to "the tender" issued by "the Company") for the
supply, delivery at site, installation and commissioning of certain equipment, item/services/civil works etc.,
We, ........................... ......................... Bank having office at ............................................ (hereinafter
referred to as “the Bank” which expression shall include its successors and assigns) hereby agree to pay to
the Company without any demur on first demand an amount not exceeding Rs...................
(Rupees.............................only) against any loss or damage, costs, charges and expenses caused to or
suffered by the Company by reason of non-performance and non-fulfilment or for any breach on the part
of the tenderer of any of the terms and conditions of the said tender.
2. We, ............................. Bank further agree that the Company shall be sole judge whether the said tenderer
has failed to perform or fulfil the said tender in terms thereof or committed breach of any terms and
conditions of the tender the extent of loss, damage, cost, charges and expenses suffered or incurred or
would be suffered or incurred by the Company on account thereof and we waive in the favour of the
Company all the rights and defences to which we as guarantors may be entitled to.
3. We, ................................. Bank further agree that the amount demanded by the Company as such shall
be final and binding on the Bank as to the Bank 's liability to pay and the amount demanded and the Bank
undertake to pay the Company the amount so demanded on first demand and without any demur
notwithstanding any dispute raised by the tenderer or any suit or other legal proceedings including
arbitration pending before any court, tribunal or arbitrator relating thereto, our liability under this guarantee
being absolute and unconditional.
4. We, .................................. Bank further agree with the Company that the Company shall have the fullest
liberty without our consent and without affecting in any manner our obligations hereunder to vary any of
the terms and conditions of the said tender/or to extend time of performance by the tenderer from time to
time or to postpone for any time to time any of the powers exercisable by the Company against the tenderer
and to forbear to enforce any of the terms and conditions relating to the tender and we shall not be relieved
from our liability by reason of any such variation or extension being granted to the tenderer or for any
forbearance, act or omission on the part of the Company or any indulgence by the Company to the tenderer
or by any such matter or things whatsoever which under the law relating to sureties would have the effect
of relieving us.
5. We, ........................................ Bank further undertake not to revoke this guarantee during its currency
except with the previous consent of the Company in writing.
6. We, ......................................... Bank also agree that the Bank’s liability under this guarantee shall not be
affected by any change in the constitution of the tenderer or dissolution or winding up of the business of
the tenderer.
7. Notwithstanding anything contained herein above:
Page 108 of 116
i) Our liability under this guarantee shall not exceed Rs..........
ii) This Bank Guarantee shall be valid up to and including .......; and
iii) We are liable to pay the guarantee amount or any part thereof under this Bank Guarantee only and only
if you serve upon us a written claim or demand on or before ……… (validity + --- weeks from the date of
expiry of this guarantee).
8. This Guarantee shall be governed by Indian laws and the Courts at Mumbai, India shall have the
exclusive jurisdiction.
IN WITNESS WHEREOF the Bank has executed this document on this............................. day
of ...........................
For ........................ Bank
(by its constituted attorney
or the person authorized to sign)
(Signature of a person authorized
to sign on behalf of "the Bank")
Page 109 of 116
Enclosure-7
PROFORMA BANK GUARANTEE FOR SECURITY DEPOSIT (ILLUSTRATIVE FORMAT)
(On Non-Judicial stamp paper of value Rs. 100)
IN CONSIDERATION OF MAZAGON DOCK SHIPBUILDERS LIMTED, a company incorporated
under the Companies Act 1956 and having its registered office at Dockyard Road, Mumbai 400010
(hereinafter referred to as the “the Purchaser” which expression shall, unless it be repugnant or contrary to
the subject or context thereof, be deemed to mean and include its successors and assigns) having placed an
order on Messers
............................ a partnership firm/sole proprietor business/a company registered under the Companies
Act, 1956 having its office at ...............................(hereinafter called " the Contractor/ Supplier" which
expression shall, unless it be repugnant or contrary to the subject or context thereof, be deemed to mean
and include its successors and assigns) vide order No....................... dated.............. (hereinafter called "the
order" which expression shall include any amendments/alterations to "the order" issued by "the Purchaser")
for the supply , delivery at site, installation and commissioning of certain equipment, item/services/civil
works etc. as stated in the said Order and the Purchaser having agreed with the Contractor/Supplier to
accept a Bank Guarantee in lieu of Security Deposit payable under the said order for the fulfilment and
performance of the said order, We, .................................................... Bank having office at
............................................ (hereinafter referred to as "the Bank" which expression shall include its
successors and assigns) hereby agree to pay to the Purchaser without any demur on first demand an amount
not exceeding Rs........... (Rupees.............................only) being 5% of the order value against any loss or
damage, costs, charges and expenses caused to or suffered by the Purchaser by reason of non performance
and non-fulfilment or for any breach on the part of the Contractor / Supplier of any of the terms and
conditions of the said order.
2. We, ............................. Bank further agree that the Purchaser shall be sole judge whether the said
contractor/Supplier has failed to perform or fulfil the said order in terms thereof or committed breach of
any terms and conditions of the order and the extent of loss, damage, cost, charges and expenses suffered
or incurred or would be suffered or incurred by the Purchaser on account thereof and we waive in the
favour
of the Purchaser all the rights and defences to which we as guarantors may be entitled to.
3. We, ................................. Bank further agree that the amount demanded by the Purchaser as such shall
be final and binding on the Bank as to the Bank 's liability to pay and the amount demanded and the Bank
undertake to pay the Purchaser the amount so demanded on first demand and without any demur
notwithstanding any dispute raised by the Contractor/Supplier or any suit or other legal proceedings
including arbitration pending before any court, tribunal or arbitrator relating thereto, our liability under this
guarantee being absolute and unconditional.
4. We, .................................. Bank further agree with the Purchaser that the Purchaser shall have the fullest
liberty without our consent and without affecting in any manner our obligations hereunder to vary any of
the terms and conditions of the said order/or to extend time of performance by the Supplier from time to
time or to postpone for any time to time any of the powers exercisable by the Purchaser against the
Contractor/ Supplier and to forbear to enforce any of the terms and conditions relating to the order and we
shall not be relieved from our liability by reason of any such variation or extension being granted to the
Contractor/ Supplier or for any forbearance, act or omission on the part of the Purchaser or any indulgence
by the Purchaser to the Contractor/Supplier or by any such matter or things whatsoever which under the
law relating to sureties would have the effect of relieving us.
5. We, ........................................ Bank further undertake not to revoke this guarantee during its currency
except with the previous consent of the Purchaser in writing.
6. We, ......................................... Bank also agree that the Bank’s liability under this guarantee shall not be
affected by any change in the constitution of the Contractor / Supplier or dissolution or winding up of the
business of the contractor/ supplier.
Page 110 of 116
7. Notwithstanding anything contained herein above:
i) Our liability under this guarantee shall not exceed Rs..........
ii) This Bank Guarantee shall be valid up to and including .......; and
iii) We are liable to pay the guarantee amount or any part thereof under this Bank Guarantee only and only
if you serve upon us a written claim or demand on or before …………. (validity + ---weeks from the date
of expiry of this guarantee).
8. This Guarantee shall be governed by Indian laws and the Courts at Mumbai, India
shall have the exclusive jurisdiction.
IN WITNESS WHEREOF the Bank has executed this document on
this............................. day of ...........................
For ........................ Bank
(by its constituted attorney)
(Signature of a person authorised
to sign on behalf of "the Bank")
Page 111 of 116
Enclosure-8
PROFORMA BANK GUARANTEE FOR PERFORMANCE (ILLUSTRATIVE FORMAT)
(On Non-Judicial stamp paper of value Rs. 100/-)
IN CONSIDERATION OF MAZAGON DOCK SHIPBUILDERS LIMTED, a company incorporated
under the Companies Act 1956 and having its registered office at Dockyard Road, Mumbai 400010
(hereinafter referred to as the “the Purchaser” which expression shall, unless it be repugnant or contrary to
the subject or context thereof, be deemed to mean and include its successors and assigns) having placed an
order on Messers ........................... a partnership firm/sole proprietor business/a company registered under
the Companies Act, 1956 having its Registered office at ...............................(hereinafter called the
Contractor/ Supplier which expression shall, unless it be repugnant or contrary to the subject or context
thereof, be deemed to mean and include its successors and assigns) vide order No.......................
dated.............. (hereinafter called "the order" which expression shall include any amendments/alterations
to "the order" issued by "the Purchaser") for the supply , delivery at site, installation and commissioning
of certain equipment, item/services/civil works etc. as stated in the said Order and the Purchaser having
agreed that the Contractor / Supplier shall furnish a security for the performance of the Contractor’s /
Supplier's obligations and/or discharge of the Contractor’s / Supplier's liability in connection with the said
order and the Purchaser having agreed with the Contractor/Supplier to accept a performance guarantee,
We, .................................................... Bank having office at ............................................ (hereinafter
referred to as "the Bank" which expression shall include its successors and assigns) hereby agree to pay to
the Purchaser without any demur on first demand an amount not exceeding Rs...........
(Rupees.............................only) being 10% of the order value against any loss or damage, costs, charges
and expenses caused to or suffered by the Purchaser by reason of non-performance and non-fulfilment or
for any breach on the part of the Contractor / Supplier of any of the terms and conditions of the said order.
2. We, ............................. Bank further agree that the Purchaser shall be sole judge whether the said
Contractor/Supplier has failed to perform or fulfil the said order in terms thereof or committed breach of
any terms and conditions of the order and the extent of loss, damage, cost, charges and expenses suffered
or incurred or would be suffered or incurred by the Purchaser on account thereof and we waive in the
favour of
the Purchaser all the rights and defences to which we as guarantors may be entitled to.
3. We, ................................. Bank further agree that the amount demanded by the Purchaser as such shall
be final and binding on the Bank as to the Bank 's liability to pay and the amount demanded and the Bank
undertake to pay the Purchaser the amount so demanded on first demand and without any demur
notwithstanding any dispute raised by the Contractor/Supplier or any suit or other legal proceedings
including arbitration pending before any court, tribunal or arbitrator relating thereto, our liability under this
guarantee being absolute and unconditional.
4. We, .................................. Bank further agree with the Purchaser that the Purchaser shall have the fullest
liberty without our consent and without affecting in any manner our obligations hereunder to vary any of
the terms and conditions of the said order/or to extend time of performance by the Supplier from time to
time or to postpone for any time to time any of the powers exercisable by the Purchaser against the
Contractor/Supplier and to forbear to enforce any of the terms and conditions relating to the order and we
shall not be relieved from our liability by reason of any such variation or extension being granted to the
Contractor/ Supplier or for any forbearance, act or omission on the part of the Purchaser or any indulgence
by the Purchaser to the Contractor/Supplier or by any such matter or things whatsoever which under the
law
relating to sureties would have the effect of relieving us.
5. We, ........................................ Bank further undertake not to revoke this guarantee during its currency
except with the previous consent of the Purchaser in writing.
Page 112 of 116
6. We, ......................................... Bank also agree that the Bank’s liability under this guarantee shall not be
affected by any change in the constitution of the Contractor / Supplier or
dissolution………………………………………………
7. Notwithstanding anything contained herein above:
i) Our liability under this guarantee shall not exceed Rs..........
ii) This Bank Guarantee shall be valid up to and including .......; and
iii) We are liable to pay the guarantee amount or any part thereof under this Bank Guarantee only and only
if you serve upon us a written claim or demand on or before ……… (validity + ---weeks from the date of
expiry of this guarantee).
8. This Guarantee shall be governed by Indian laws and the Courts at Mumbai, India shall have the
exclusive jurisdiction.
IN WITNESS WHEREOF the Bank has executed this document on
this............................. day of ...........................
For ........................ Bank
(by its constituted attorney)
(Signature of a person authorised
to sign on behalf of "the Bank")
Page 113 of 116
Enclosure-9
Electronic Payment Mandate Form
(MDL Bank details)
Name of the Company/Firm Mazagon Dock Shipbuilders Limited
Address with Phone no. Dockyard Road, Mumbai – 400010
E-Mail ID
Phone No. +91 22 23745310
Fax No.
Particulars of Bank Account
Name of the Bank State Bank of India
Name of the Branch Mazagon Dock Mumbai Branch
Branch Code 9054
Bank IFSC / NEFT Code SBIN0009054
Bank Address MBPT Workshop building, N.V Nakhwa Road, Mazagon - 400010
City Name Mumbai
Telephone No. of Bank +91 22 23752802
9 digit code no. of bank &
branch appearing on the MICR
cheque issued by your bank
400002120
Type of Account Current Account
Account No. 10005255246
Income Tax PAN No. AAACM8029J
Page 114 of 116
Enclosure-10
VENDOR DECLARATION
Sub: - Survey of site, design & manufacture, testing at manufacturer’s works, installation at site,
Testing and Commissioning of outdoor non-draw-out A.C. Distribution panels as per scope
work.
We have visited the installation site at MDL on _______(date) to measure the available space &
compliance to statutory requirement as per relevant Indian Electricity Safety Rules & Regulations.
We hereby confirm that we have understood the Scope of Work and Technical Specifications and
requirements given in Tender and our quoted price/rates are in line with the above scope of work.
M/s. .............................................................
SIGNATURE.........................................
NAME.............................................
DESIGNATION
STAMP
DATE:
(To be submitted by vendor on Company’s Letter head, duly signed by Authorized Signatory)
Page 115 of 116
Enclosure – 11
DECLARATION CERTIFICATE FOR LOCAL CONTENT
(Before completing this declaration, bidders must study the General Conditions, Definitions,
Govt. Directives applicable in respect of Local Content & prescribed tender conditions).
1. General Conditions
1.1. The local content (LC) as a percent must be calculated in accordance with the definition provided
at clause 2 of Public Procurement (preference to Make in India) Order 2017.i.e. “Local content is
the amount of value added in India which shall be total value of items procured (excluding net
domestic indirect taxes) minus the value of imported content in the items (including all customs
duties) as a proportion of the total value in percent.”
1.2. A bid will be disqualified if:
• the bidder fails to achieve the stipulated minimum threshold for local content indicated in tender;
and.
• this declaration certificate is not submitted as part of the bid documentation.
(Note: Clause no. 1.2 above is applicable only for tenders below Rs. 50Lakhs.)
2. Definitions
2.1. “Imported content” means that portion of the bid price represented by the cost of components,
parts or materials which have been or are still to be imported (whether by the supplier or its
subcontractors) and whose costs are inclusive of the costs abroad, plus freight and other direct
importation costs, such as landing costs, dock duties, imprt duty, sales duty or other similar tax or
duty at the port of entry in India i.e Mumbai in case of MDL;
2.2. “local content” means that portion of the bid price which is not included in the imported content,
provided that local manufacture does take place;
3. The stipulated minimum threshold(s) for local content for this bid is/are as follows:
Description of services, works or goods Local Content Custom Duty
_______________________________ _______% _______%
_______________________________ _______% _______%
_____________________________ ______ % ________%
4. Does a bidder seeks benefit of Public Procurement Policy for YES / NO
MSEs –Order 2012. If yes, bidders should not seek benefits against this policy & should categorically
seek benefits of only one policy which cannot be modified subsequently.
4.1 Does any portion of the services, works or goods offered have any imported content? YES / NO
4.2 If yes, the rate(s) of exchange to be used in this bid to calculate the local content. Indicate
the rate(s) of exchange against the appropriate currency in the table below:
Currency Rates of exchange
US Dollar
Euro
Others
Page 116 of 116
LOCAL CONTENT DECLARATION BY CHIEF FINANCIAL OFFICER OR OTHER
LEGALLY RESPONSIBLE PERSON NOMINATED IN WRITING BY THE CHIEF
EXECUTIVE OR SENIOR MEMBER/PERSON WITH MANAGEMENT RESPONSIBILITY
(CORPORATION, PARTNERSHIP OR INDIVIDUAL)
IN RESPECT OF BID / TENDER No. .................................................................................
ISSUED BY: (Name of Firm): .......................................................................................
NB: The obligation to complete, duly sign and submit this declaration cannot be transferred to an
external authorized representative, auditor or any other third party acting on behalf of the bidder.
I, the undersigned, …………………………….................................................... (full names), do hereby
declare, in my capacity as …………………………………………….……….……. of
...............................................................................................................(name of bidder entity), the
following:
(a) The facts contained herein are within my own personal knowledge.
(b) I have satisfied myself that the goods/services/works to be delivered in terms of the above-
specified bid comply with the minimum local content requirements as specified in the tender, and as
measured in terms of Public Procurement (preference to Make in India) Order 2017.
(c) The local content has been calculated using the definition given in clause 2 of Public Procurement
(preference to Make in India) Order 2017, the rates of exchange indicated in paragraph 4.2 above
and the following figures: (Actual figures are to be indicated in online Price Bid only)
Bid price, excluding net domestic indirect taxes Quoted / Not Quoted
Imported content including all custom duties Quoted / Not Quoted
Stipulated minimum threshold for Local content (paragraph 3 above) Quoted / Not Quoted
Local content %, as calculated Quoted / Not Quoted
NB: If the bid is for more than one product or the product offered has components / raw material /
sub-assemblies, a schedule of the local content by product or product break-up including applicable
custom duties of shall be attached.
(d) I accept that the Procurement Authority / Institution / MDL has the right to request that the
local content be verified in terms of the requirements of Public Procurement (preference to Make in
India) Order 2017.
(e) I understand that the awarding of the bid is dependent on the accuracy of the information
furnished in this application. I also understand that the submission of incorrect data, or data that
are not verifiable as described in Public Procurement (preference to Make in India) Order 2017,
may result in the Procurement Authority / Institution / MDL imposing any or all of the remedies as
provided for in Clause 9 of the Public Procurement (preference to Make in India) Order 2017.
SIGNATURE: DATE: ___________
WITNESS No. 1 DATE: ___________
WITNESS No. 2 DATE: ___________