Always On™ UPS Systems Canada Inc www.alwayson.com 2
Many years of experience working on high profile projects, combined with industry leading expertise, allows Always On™ UPS Systems Canada Inc. to design and manufacture the highest quality uninterruptible power supply and power conditioning products. All Always On™ designs incorporate the most efficient and robust devices and system components to provide the highest degree of protection possible for all critical and emergency equipment installations. Always On™ takes great pride in providing complete solutions. This includes all modes and levels of protection being designed into each and every system we build, eliminating the need for additional equipment to be added to address the total system requirements. We do not cobble together standard products like some of our larger competitors do, but instead provide a customized engineered solution to meet customer needs. Ensuring protection and power quality through every mode of operation requires coordination between all system components. This includes surge protection devices, inverters, batteries, battery chargers, bypass systems, transfer switches and power distribution units. Every employee and manager at Always On™ takes a personal interest to ensure that all stages of each product is designed, manufactured and tested to the highest degree of quality within our ISO 9001:2008 certified facility. This QMS certification, along with our numerous safety approvals (such as our various UL, CSA, CCMC, BMEC, or ABS listed products), gives us the confidence to set us apart as one of the leading UPS manufacturers in this industry. Always On™ products are put into service by many world renowned companies and users who rely on our expertise and the high reliability of our systems to protect their critical installations. These include industries such as the oil, gas and mining industries, airplane and other manufacturing plants, hospitals and operating rooms, rail and marine transportation systems, data centers, army, navy, air force and military installations, nuclear and other power generating plants, public utilities, and emergency systems for buildings. Some of our customers include: Boeing, Canadian Natural Resources Ltd., Siemens USA, GE Energy, Husky Oil, Sherritt Mines, Protrans Canada Line, Beghelli, Stanpro, the Department of National Defense, the US Navy, New Brunswick Nuclear Power, L‐3 Communications, Fortis BC, the RCMP, BC Hydro, and the Canadian Coast Guard. We hope you will visit our website: www.alwayson.com for more information, or call our inside sales and engineering support on our toll‐free telephone lines: 1‐877‐259‐2976 (Sales ext. 451). Or, you can email for support departments: [email protected], [email protected] Robert S. Adria, President
Catalogue version: AO‐2014052300
Always On™ UPS Systems Canada Inc www.alwayson.com 3
Engineered Solutions Always On™ UPS Systems Canada Inc. is not your typical manufacturer. In addition to providing standard product, we provide engineered solutions to fit unique applications and customer requests. Some of our solutions are shown below.
Transportable modular power - Canadian military hospital - Afghanistan - 100kVA
Canada Line - Rapid Transit - Vancouver, BC
Boeing - Moving assembly line crawler - 100kVA
John P. Tully - Canadian Coast Guard
Always On™ UPS Systems Canada Inc www.alwayson.com 4
Index
Engineered Solutions Page 3 Although Always On™ has a standard product offering, we are most recognized by providing engineered solutions. From sensitive telecommunication equipment to oil rig conditions, we can provide solutions to suit the needs of your environment.
NX Series three phase dual conversion on‐line Page 6 Always On™’s NX Series are dual conversion true on‐line UPS systems which provide the attached loads with isolation from the utility or generator supply and are designed for all critical applications. These critical loads are supplied power from the inverter, which is fed by the batteries. The NX Series is designed with a large input range and incorporates an output isolation transformer. These UPS systems are available from 10kVA to 250kVA with three phase input and three phase or single phase output with multiple voltage configurations.
N & TN Series single phase dual conversion on line Page 14 Always On™’s N & TN Series are dual conversion true on‐line UPS systems designed for critical applications which provide the attached loads with isolation from the utility or generator supply. At all times, the loads are supplied power from the inverter, which is fed by the batteries. The wide input range (gen. mode) is designed into these systems while maintaining output at various voltage and frequency configurations. The single phase systems are available from 700VA to 20kVA.
External Bypass Systems Page 20 Always On™ offers a separate cabinet to allow for complete removal of the UPS system from the load, while still supplying the load with conditioned power. These systems are recommended for maintenance purposes to prevent accidental removal of power from the loads and to allow for complete power removal from the UPS system for safety considerations.
ABS Marine Approved Units Page 21 Always On™ has a full complement line of ABS approved systems ranging from 700VA to 320kVA. We have installations on BC Ferries (Queen of Oak Bay, Queen of Capilano), Coast Guard vessels (Tully, Sir Wilfred Laurier), Transport vessels, Navy vessels and Drilling Platforms.
L Series line interactive true sine wave output Page 22 Always On™’s L Series are line interactive UPS systems with a true sine wave output on all modes of operation. They are ideal for commercial and industrial applications and range in size from 800VA to 3kVA. All L Series systems provide voltage regulation, noise, surge and spike protection, serial communication interface, network and modem protection, extended runtime options and additional communication interfaces.
Limousin II commercial protection Page 25 Always On™’s LIMOUSIN Series are transformer based UPS’s which provide lightning, surge, spike, transient and noise protection and feature constant Automatic Voltage Regulation (AVR) and blackout protection. They are designed for the home/office user to provide the maximum protection at a competitive price.
Monitoring & Control Software Page 26 Always On™ offers several different communication and connection options to manage your UPS through local or networked connections.
Always On™ UPS Systems Canada Inc www.alwayson.com 5
Index TTF/ILF isolating line filter Page 27 The Always On™ TTF/ILF combines a Low‐Pass Series filter with a toroidal isolation transformer. This unit provides attenuation of both normal and common mode noise and eliminates any troublesome constant voltage which may exist between neutral and ground in some electrical configurations. It is totally compatible with all operating loads, including high frequency switching power supplies. It re‐establishes the “0” volts ground reference point on the secondary.
ESE surge protection devices Page 28 The Always On™ “ESE” SPD filter is designed to protect your power grid. Installed at the power panel, it provides protection against externally and internally produced power aberrations, massive impulses, lightning induced effects and interference associated with low frequency harmonics and situations caused by accidents and/or failures in the electrical utility system. It is totally compatible with all operating loads including high frequency power supplies and constant current loads controlled by electronic switches.
PLC low‐pass series power filter Page 30 Always On™’s PLC filters are designed to provide noise, surge, spike, transient and overload protection to PLC power supplies and peripherals. Two different types are available: AC only and AC/DC with data line protection to ensure clean operation and transfer to all I/O interfaces, peripherals and power supplies. All systems include an on‐board resettable breaker, and a three colour LED for easy operation identification and diagnostics.
NFC Series frequency converters & voltage regulators Page 32 Always On™’s NFC Series Frequency Converters incorporate all the features of our dual conversion true on‐line UPS systems as well as the ability to lock the output frequency to the three major standards. The dual conversion technology allows the load to be supplied with 50Hz, 60Hz, or 400Hz, independent of the input. The NFC Series is designed with large input range and incorporates an isolation transformer. These NFC systems are available from 10kVA to 250kVA with three phase input and three phase output.
Aurora & Borealis central inverter systems (emergency lighting) Page 34 Always On™ ELI’s are designed for installation between your AC power supply (utility or generator) and your lighting equipment. It provides power to your equipment during major power events such as blackouts and brownouts, over‐voltage and under‐voltage conditions. The ELI provides a consistent supply of regulated AC power during these power events, allowing you to ensure safety and lighting for the period required.
Genie smart UPS power distribution system Page 40 The Genie is designed to distribute AC power while protecting the multiple critical loads supplied by the UPS. The Genie incorporates the Always On™ SDB breaker, which is specifically designed to clear in less than 1 cycle, eliminating multiple load trips. The Genie replaces the required retrofitting of standard panels with fast‐blow fuses. A communication option allows for remote status.
ALW Batteries & Battery Bank Units Page 41 Our ALW batteries are specifically designed for our UPS systems. Using official Always On™ batteries protects your UPS and allows us to guarantee our claimed backup times. Our battery cabinets have several useful features to facilitate setup and battery maintenance.
UPS Maintenance Page 42 Always On™’s UPS systems are designed for maximum reliability and peak performance. Even so, a regular maintenance program is necessary to identify and correct potential problems before they can occur. This helps to prevent unplanned and inopportune downtime and outages of critical systems, more rapidly addresses problems that can occur, and even extends battery lifespan.
Always On™ UPS Systems Canada Inc www.alwayson.com 6
True Sine Wave On‐Line UPS Always On™ NX Series UPS systems are designed to provide reliable, clean and consistent power to all critical loads and emergency applications. Power reliability is business reliability.
The NX Series UPS is a dual conversion, on‐line, three phase system for use as centralized power protection and distribution. The dual conversion process converts the utility AC supply into DC power, which is used to charge the batteries and supply power to the inverter. The Inverter then inverts the DC power back into a high quality, regulated and isolated AC power source. The wide operating range of the UPS system allows it remain online without discharging or depleting the battery capacity. This makes it fully compatible with poor quality industrial electrical environments, as well as unstable generators.
The UPS continually monitors and provides conditioning to the incoming electrical power, removing under‐voltages and over‐voltages, sags and spikes and other irregularities that are inherent within industrial power systems. The NX Series UPS system supplies clean, consistent power at the rated voltage with a low distortion pure sine wave for your sensitive electronic equipment. Blackouts, brownouts and other power interruptions, regardless of duration, can be protected against with additional battery cabinets to provide the necessary emergency power to safeguard your operation.
Always On™ provides a truly isolated output to eliminate all types of power aberrations as well as Common and Normal Mode noise, increasing the reliability and life of the loads connected.
Our High Quality Control Standards are ensured by testing at the component level, board level, function level and completed stage level as specified by our ISO 9001:2008 certification.
Redundant Applications for the highest standard of reliability: Mission critical applications such as hospital operating rooms, airport security, oil processing and refineries, and marine emergency systems require the highest availability of power. Always On™’s unique IPRO technology sets the highest standard for power reliability, with the IPRO 1+1 compatible NX Series UPS’s. Decentralized bypass, redundant control electronics and batteries provide matched load‐sharing and robust fault‐tolerant operations.
Features and Benefits Full Galvanic Isolation Full Galvanic Isolation provides a completely isolated and referenced output. This isolation protection provides a proven solution to problems created by induced voltages affecting the critical loads. Since the output circuit to the load is completely isolated and no noise induced on the neutral can permeate to the loads, systems operate in a more reliable fashion. Also, this type of protection increases the life span of equipment by eliminating noise, which breaks down components. Modular design Each major component (inverter, rectifier and static switch) on the NX Series are installed on slide‐out modules. This allows for quick repair (mean time to repair of <30 minutes) and easy field upgradeability. Fully digital DSP (Digital Signal Processor) and flash memory are the technology corner stones of the new age of power quality and reliability.
NX Series NX31 & NX33
Three Phase In / Single or Three Phase Out Dual Conversion On-Line UPS
Industrial / Commercial
Always On™ UPS Systems Canada Inc www.alwayson.com 7
NX Series
High Efficiency Thanks to IGBT technology, the NX Series UPS’s have a high efficiency. This, combined with IPRO, results in the most cost‐efficient and reliable UPS solution in the industry. Convenient front panel design The LCD display and control switches are accessible through the up, down, and enter switches below the front panel window. All the viewable parameters can be read without opening the front door. The inverter on/off switch is protected from accidental operation by being located behind the locked front door. The inverter can still be switched on and off via the control switches on the front panel, but this feature is password protected. UPS monitoring and management via SNMP module (included) Direct access of remote UPS and active management of single modules in multi‐unit configurations are the keys to efficient and predictable power quality management. The SNMP Client/Agent structure, direct link, or remote connection enables a network manager or facility engineer to permanently monitor and control local or remote Always On™ UPS systems and the equipment and processes they protect. A real‐time graphical display of critical UPS parameters and environment information of multiple decentralized UPS’s, as well as statistical data and event log files, are available on every local computer display and network management system or on the Internet. Additionally, UPS status information changes can be sent to such varied information carriers as SMS, network management systems, email or fax. High Efficiency Mode The high efficiency function adds cost effectiveness, maximizes efficiency and reduces power consumption. Alternating between bypass and on‐line modes is achieved automatically and in accordance with the conditions of the AC supply power. On‐line mode may be used during times of intermittent power, and bypass mode when the utility is within user‐selectable parameters in order to obtain greatest efficiency. Irregularities can be detected in less than a second, and on‐line mode reactivated immediately. Extension of battery life Batteries are a critical part of every UPS solution, acting as the power supply in the event of an AC power failure. They are sensitive products that need to be handled and monitored continuously and carefully in order to increase their lifetime and predictability. Always On™ includes superior battery management within the entire NX Series family and is a comprehensive management and monitoring system that prevents batteries from overcharging and deep discharging. The NX Series features a ”no surprises” automatic battery test, and boost charging, which equalizes recharging of batteries. Protection Short circuit, over‐temperature and over‐voltage protection is built‐in to protect the NX Series UPS against any form of misuse. Back feed protection, complete protection circuits and excellent overload behavior provide outstanding user protection and application security on every UPS system. Full galvanic isolation is also included in the NX series. Extremely flexible The NX Series UPS offers tailor‐made power protection to comply with your individual installation requirements. Options include a 6‐pulse rectifier (instead of the standard 12‐pulse rectifier) for units under 80kVA and a Smart Panel (SP). In addition, a comprehensive software suite can be added for mission control and data protection.
For more information, visit www.alwayson.com
Always On™ UPS Systems Canada Inc www.alwayson.com 8
NX Series
Options
External Bypass System Always On™ offers an external ATS (Automatic Transfer Switch) which is fully programmable for automatic electronic operation. This will automatically switch to bypass (alternate source) in the event there is loss of power from the system for any reason. IPRO (Isolated Parallel Redundant Operation) For the highest standard of reliability. Mission critical applications such as hospitals, airports, oil industries, refineries, and marine require the highest availability of power. Always On unique IPRO technology sets the highest standard for power reliability, and IPRO 1+1 compatible NX Series UPS’s. Decentralized bypass, redundant control electronics and batteries offer perfect load‐sharing and robust fault‐tolerant operations. Redundancy With IPRO, the NX Series UPS’s are controlled in a true peer‐to‐peer configuration where all critical elements and functions (including bypass) being redundant. The IPRO 1+1 system has the benefit of redundant control electronics, active‐active system management and fault tolerant operation. Failure of one system component still allows redundancy on remaining components, which permits the complete maintenance and repair of one UPS while the other UPS remains on‐line. Remote LCD Display Panel Full monitoring and control of multiple UPSs from a common panel located up to 300M away. Top Cable Entry Module attached to the rear of the UPS cabinet to allow for convenient top cable termination. Emergency Power Off Switch Local or remote located switch to activate EPO function. Harsh Environment Protection Several NEMA and Ingress Protection (IP) rated options, as well as seismic mounting brackets, are available.
NX33’s with IPRO NX33 with BBU
Always On™ UPS Systems Canada Inc www.alwayson.com 9
NX Series
For more information, visit www.alwayson.com
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
True Sine Wave On-Line UPS 10kVA—250kVA General Data
Topology True On‐Line, Dual Conversion
Nominal output at PF=0.8 kVA 10 15 20 30 40 50 60 80 100 120 160 250
Overall efficiency 100% load, 0.8 PF % 90 90 90 90 90 90 90 90 90 90 90 90
True galvanic isolation from input to output YES
Audible noise level (at 1m) db (A) <65 at 1m <70 at 1m Operating
temperature range
UPS 0°C to 40°C (32°F to 104°F)
Battery Optimum: 20°C to 25°C (68°F to 77°F); higher temperatures reduce battery life expectancy
Relative humidity 0% to 95%, non‐condensing
Enclosure
Type Indoor (NEMA 1) [Drip shield and skirting included]
Safety Internal dead front construction
Cooling Forced air ‐ variable speed
Installation
Rigging Suitable for handling by forklift or overhead crane (eye hooks available)
Mounting Casters and leveling feet [optional seismic rated mounting available] Installation & maintenance
access Front access required for normal maintenance
Conduit access Bottom entry standard [optional top entry]
Standards UL 1778, CSA 107.3 listed, CSA 22.2 No. 60950, FCC Class A, [optional ABS or UL‐924 available]
Rectifier
Configuration 12 pulse rectifier
Input
Voltage 208/480/600, L‐L Vac, 3 phase, 4 (or 3) wire + ground (‐20% to 15% without battery discharge)
Frequency 45 ‐ 65 Hz
Power factor 0.8 at full load
Inrush current Limited by soft‐start circuit
Power walk‐in 20 seconds
Output Output voltage tolerance ±1%
DC ripple voltage ±0.5%
Current THD 12 pulse rectifier: 9%
Battery
Nominal output at F=0.8 kVA 10 15 20 30 40 50 60 80 100 120 160 250
Battery compatibility Sealed lead‐acid [optional NiCD or flooded]
Number of cells 174 cells
Voltage range 295 ‐ 410Vdc
Float voltage at 20°C (68°F) 392Vdc
Low voltage level 320Vdc
Minimum discharge voltage 295Vdc
Boost charge voltage 410Vdc
Maximum charge current (ADC) 5 7.5 10 15 20 25 30 40 50 60 80 125
Recharge time for 30 minute battery to 95% capacity 10 times the discharge time
Automatic and manual battery test Standard
Always On™ UPS Systems Canada Inc www.alwayson.com 10
NX Series
Inverter Nominal output at PF=0.8 kVA 10 15 20 30 40 50 60 80 100 120 160 250
DC voltage input range 295 ‐ 415Vdc Nominal output voltage 208/120 or 480/277 or 600/347, 3 phase, 4 wire + ground
Inverter bridge IGBT technology and Pulse Width Modulated Output isolation transformer Standard
Output power factor 0.8 Frequency lock range 50 / 60Hz, ±7% Output waveform True sine wave
Output voltage tolerance
Static ±1% Load step 0% ‐ 100% ‐ 0% ±3%, recovering to within ±1% in 1 cycle Load step 0% ‐ 50% ‐ 0% ±2%, recovering to within ±1% in 1 cycle
Output voltage distortion
100% linear load <2% THD maximum 100% non‐linear load <3% THD maximum
Crest factor capability Greater than 3:1 Phase
displacement 100% balanced load 120° ±1%
Output freq. Free running 50 / 60 Hz, ±0.1% synchronized with utility
Overload capability (on inverter)
<110% Continuous 110 ‐ 125% 15 minutes 125 ‐ 150% 5 minutes > 150% 30 seconds
Efficiency (100% load) 92% 92% 92% 92% 92% 92% 92% 92% 92% 92% 92% 92%
By‐pass Input configuration Common to rectifier [optional dual input] Primary Components Full load rated static switch, back‐feed protection and internal maintenance by‐pass
Voltage range ±20% of input voltage Frequency range 45 ‐ 55 Hz / 55 ‐ 65 Hz
Efficiency 98%
Transfer time Inverter to bypass 0 ms Bypass to inverter 0 ms
Overload capacity
200% of UPS rating 30 seconds 400% of UPS rating 1 second
Short circuit capability (on by‐pass) 1000% for 3 cycles (non‐repetitive) Isolation transformer YES
External interface
Alarm contacts 8 pre‐defined contacts (COM, BATL, BACKUP, BYPASS, SS, FAULT, OVL, INVON) Ethernet communications SNMP adapter Serial communication RS‐232 & RS‐485
Input signals Emergency power off contacts provided (optional switch available)
Interface controls and alarms Active mimic diagram
Represents the operational status of the UPS, with integrated LED's and power flow indicators
Audible alarm Audible signal active when any alarm condition is present
LCD/LED display Display of UPS metering functions, event history and fault conditions
Optional features
Marine approval ABS (American Bureau of Shipping) Emergency lighting UL‐924, BMEC and CCMC Mounting options Seismic rated mounting (seismic certification available)
Dual input Bypass and rectifier have separate inputs Warranty Extended warranty and services packages available
Redundant operation A+B Buss system and IPRO (Isolated Parallel Redundant Operation) Remote status panel Active mimic diagram w/ Stop Operation and Summary Alarms
Always On™ UPS Systems Canada Inc www.alwayson.com 11
NX Series
Backup Times (Battery Banks)
NX‐Series UPS Single Line Drawing
Specifications are subject to change without notice to reflect upgrades and improvement in technology. For more information or different runtimes, please contact CUSTOMER SERVICE toll‐free at 1‐877‐259‐2976, ext. 451.
Full load runtime calculations for NX Series UPS systems from 8kW (10kVA) to 128 kW (160kVA).
Load 4000W 8000W 12 000W 16 000W 24 000W 32 000W 5000VA 10 000VA 15 000VA 20 000VA 30 000VA 40 000VA
Model
BBU‐NX33D 22 min 8 min 4 min BBU‐NX33E 105 min 40 min 18 min 13 min 6 min BBU‐NX33KF 36 min 23 min 18 min 10 min 5 min BBU‐NX33KG 80 min 48 min 32 min 17 min 10 min BBU‐NX33KH 120 min 76 min 46 min 28 min 19 min BBU‐NX33KI 130 min 81 min 50 min 24 min BBU‐NX33KJ 130 min 80 min 60 min
Load 40 000W 48 000W 64 000W 80 000W 96 000W 128 000W 50 000VA 60 000VA 80 000VA 100 000VA 120 000VA 160 000VA
Model
BBU‐NX33KG 6 min BBU‐NX33KH 12 min 10 min BBU‐NX33KI 21 min 18 min 12 min 6 min BBU‐NX33KJ 33 min 30 min 18 min 10 min 6 min
2 x BBU‐NX33KI 66 min 50 min 24 min 21 min 18 min 2 x BBU‐NX33KJ 92 min 80 min 60 min 33 min 30 min 17 min
Always On™ UPS Systems Canada Inc www.alwayson.com 12
NX Series
System Dimensions The standard configurations presented are intended only to illustrate the general size of the enclosures. These units are shipped as separate components.
Drawings are not to scale.
10 to 50kVA UPS System 60 to 160kVA UPS System 250kVA UPS System 550mm (21.7") W 1100mm (43.3") W 2240mm (88.2") W 812mm (32") D 812mm (32") D 812mm (32") D 1600mm (63") H 1626mm (64") H 1626mm (64") H 380 ‐ 710kg 850 ‐ 1600kg 2700kg
D Battery Cabinet E Battery Cabinet K Series Battery Cabinet 235mm (9.25") W 400mm (15.75") W 1314mm (51.5") W 546mm (21.5") D 682mm (26.75") D 850mm (33.5") D 552mm (21.75") H 1008mm (39.75") H 1945mm (76.5") H
117kg 511kg 814 ‐ 1764kg
For more information, visit www.alwayson.com
Always On™ UPS Systems Canada Inc www.alwayson.com 13
NX Series
Module Interior Layout
NX33 UPS with Backup Battery Unit (BBU)
Plugin Rectifier Module
Plugin Inverter Module
Always On™ UPS Systems Canada Inc www.alwayson.com 14
N & TN11 Series Single or Multiple Phase Input / Single or Split Phase Output
Dual Conversion On-Line UPS Industrial / Commercial / Critical Loads
Description This dual conversion UPS system converts the incoming AC supply to DC. The DC power is used to charge the batteries and supply the inverter. The inverter then inverts the DC power into AC power that, in turn, is supplied to the load. This dual conversion isolates the line from AC supply and allows for wide input power variations on both frequency and voltage. Systems in single phase output configurations range from 700VA to 20kVA. Applications Among other applications, the N and TN11 Series can be applied to LAN file servers, personal computers, networks and workstations, Automatic Teller Machines, telecommunications, laboratory and medical equipment, test equipment, POS equipment, robotics, PLC’s, security and emergency systems and military & government applications. Advanced Features Features include utility input power factor correction, self‐diagnosis, an LCD display, a static bypass, smart power source monitoring and battery management, lightning, noise and surge protection, spike and transient protection, cold start/auto restart, a user selectable frequency, a generator mode and intelligent communications interface. SNMP and AS‐400 adapters are available for network management. User replaceable batteries, emergency power off control, an isolation transformer and maintenance bypass switches are standard on the TN11 Series. Complete Protection The N and TN11 Series UPS’s are designed with comprehensive spike, transient and surge protection, which prevents destructive hardware damage and extends system life. The high end EMI/RFI filtering design prevents electrical Common and Normal Mode noise from affecting computer operation, data or files, including when the UPS is in Bypass Mode. Operating Voltages And Frequencies The N and TN11 Series UPS’s are designed to function at wide voltage and frequency variations. This wide input range makes the systems ideal for generator and problematic area applications. Also available is a frequency converter option allowing the user to select the output frequency at 50 or 60Hz. Self‐Diagnosis And Information Indicators Each N and TN11 Series UPS is equipped with a microprocessor that performs a self‐diagnosis once a month to ensure continuous runtime. The microprocessor is able to identify failures, display the failure on the LCD display and send audio and visual alarms (off site monitoring).
Always On™ UPS Systems Canada Inc www.alwayson.com 15
Cold Start This feature allows the N and TN11 Series UPS’s to be powered up when the utility is not present. Auto Restart This user selectable feature allows the UPS to restart automatically when utility becomes available, provided it has been shutdown due to an extended blackout. Smart Power Source Monitoring And Battery Management Via microprocessor‐based electronics, the N and TN11 Series UPS’s produce a strict true sine wave output regardless of the input. It also controls the on‐battery and low battery shutdown, which prevents full discharge, thereby extending the battery performance and battery life. High Efficiency Mode The high efficiency function adds cost effectiveness, maximizes efficiency and reduces power consumption. Alternating between bypass and on‐line modes is achieved automatically and in accordance with the conditions of the AC supply power. On‐line mode may be used during times of intermittent power, and bypass mode when the utility is within user selectable parameters in order to obtain greatest efficiency. Irregularities can be detected in less than a second, and on‐line mode reactivated immediately. Intelligent Communication Interface Each N and TN11 Series UPS is equipped with a RS232 and dry contact interface port, for which we provide various powerful management software programs. For the more complex network environment, we support Simple Network Management Protocol (SNMP), AS400 relay contacts and other options, by adding a plug‐in module to the accessibility slot. Remote Shutdown and Emergency Stop Features include remote shutdown via communication port, emergency stop via contacts. An optional push button control is available. Optional Extended Runtimes To meet your back‐up time requirements, we offer increased back‐up time by simply adding additional hot pluggable battery cabinet(s). Optional USB Available at time of order. Optional External Bypass Allows the UPS to be completely shut down or even removed so that maintenance can be performed safely without any downtime. Available at time of order.
N & TN11 Series
For more information, visit www.alwayson.com
Always On™ UPS Systems Canada Inc www.alwayson.com 16
True Sine Wave On Line UPS 700VA—3kVA N Series Model number: GES‐701N GES‐102N GES‐152N GES‐202N GES‐302N
General Maximum capacity 700VA/490W 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W UPC order code 825433 30100 825433 30200 825433 30300 825433 30400 825433 30500
Input
Nominal voltage 120Vac (optional 220Vac available) Voltage range 60Vac/40% load, 70Vac/70% load, 80Vac/100% load ‐ 144Vac Bypass voltage ±10%, +10/‐15%, +15/‐20% (user selectable)
Phase Single phase (L‐N‐G) Frequency window 45‐65Hz (±2%, ±5%, ±7% ‐ user selectable)
Synchronization window ±3Hz Power factor 0.99
Output
Output voltage 100/110/115/120/127Vac (user selectable) Voltage regulation ±2%
Frequency regulation ±0.25Hz (battery or free run mode) Voltage distortion ‐ THD <3% linear load, <5% non‐linear load Max current @ 120Vac 5.8A 8.2A 12.4A 16.5A 24.7A Transient response 4% (100% load change) Overload capacity 125% for 1 min. / 150% for 10 sec
Crest factor 3:1 Efficiency >98% (high efficiency mode)
Transfer time Zero
Outlets 6 x 5‐15R 8 x 5‐15R 2 x 5‐20R
1 x L5‐20R
8 x 5‐15R 2 x 5‐20R, 1 x L5‐30R
Battery
Battery type Sealed lead acid, maintenance free ‐ Hot swappable cartridge Quantity 2 3 3 6 6 Voltage 24Vdc 36Vdc 36Vdc 72Vdc 72Vdc
Recharge time <4 hours to 90% recovery Advanced battery management Auto self‐test, temperature compensated 3 stage charging, load dependent discharge
Backup time ‐ full load 9 min 10 min 8 min 12 min 8 min Extended runtime Available
Protection
Output short YES Abnormal voltage YES
Abnormal frequency YES I/O noise protection Common & normal noise suppression
I/O spike and transient YES Telephone / network RJ11/RJ45
Interface
Display LCD/LED ‐ Status, readings and setup parameters Audible alarms On battery, low battery, overload, fault Communications RS232 / dry contact / (optional: USB, SNMP, AS400)
Emergency power OFF YES ‐ Via normally closed contact
Environment Operating temperature 0°C ‐ 40°C (32°F ‐ 104°F)
Humidity 0 ‐ 95% (non‐condensing) Audible noise <40 dBA at 1 meter
Conformance
Safety UL1778, CSA 107.3 Approval UL listed, cUL listed, (optional ABS [American Bureau of Shipping], see below)
Surge / transient IEEE C62.41 CAT.A EMI / RFI FCC Part 15 Warranty Two year factory warranty (optional extendable warranties available)
Physical data W x D x H mm (in) 152 x 413 x 238 (6" x 16.3" x 9.4") 225 x 410 x 358 (8.9" x 16.1" x 14.1") Weight in kg (lbs) 12 (26.4) 13 (28.6) 17 (37.4) 27 (59.4) 33 (72.6)
Rack‐mount models
Model # GES‐701NR GES‐102NR GES‐152NR GES‐202NR GES‐302NR UPC order code 825433 30111 825433 30202 825433 30301 825433 30403 825433 30501
W x D x H mm (in) 482 x 425 x 84 (19" x 16.7" x 3.3") [2U] 484 x 635 x 84 (19.1" x 25" x 3.3") [3U] Weight in kg (lbs) 18 (25.3) 20 (44.1) 25 (55) 28 (61.7) 32 (70.5)
Marine‐grade models
Model # GES‐701N‐ABS GES‐102N‐ABS GES‐152N‐ABS GES‐202N‐ABS GES‐302N‐ABS UPC order code 825433 30112 825433 30231 825433 30318 825433 30401 825433 30509
W x D x H mm (in) 152 x 413 x 238 (6.0" x 16.3" x 9.4")
Weight in kg (lbs) 20 (44.1) 42 (92.2) 47 (103.5) Approval ABS (American Bureau of Shipping); UL and cUL listed
Consult Always On™ for more information
Specifications are subject to change without notice to reflect upgrades and improvement in technology. Industrial containers are available (NEMA 12, NEMA 4, etc); consult manufacturer. External wrap‐around bypass modules are available for all models, permitting UPS maintenance without power interruption to the load.
N Series Single Phase Input and Output
Always On™ UPS Systems Canada Inc www.alwayson.com 17
N Series
Backup Times (Battery Banks) To meet your back‐up time requirements, we offer increased back‐up time by simply adding additional battery cabinets. To determine the battery bank part number, locate the UPS model number and additional runtime you want to add from the tables below. For alternate runtime or runtime calculations, please contact our factory.
For more information or different runtimes, please contact Customer Service toll‐free at 1‐877‐259‐2976, Ext. 451. Standard 5‐year pro rated warranty with 1‐year replacement. Extended warranties available.
Load
350W 490W 700W 1050W 1400W 2100W 500VA 700VA 1000VA 1500VA 2000VA 3000VA
Model UPC order code
BBU‐701NA 825433 60300 28 min 17 min BBU‐701NB 825433 60325 48 min 33 min
BBU‐102NA 825433 62600 30 min 25 min 17 min BBU‐102NB 825433 62610 50 min 33 min
BBU‐152NA 825433 62700 30 min 25 min 17 min 13 min BBU‐152NB 825433 62710 50 min 33 min 25 min BBU‐152NC 825433 62730 100 min 60 min 40 min
BBU‐202NA 825433 62800 30 min 25 min 18 min BBU‐202NB 825433 62810 150 min 100 min 60 min BBU‐202NC 825433 60365 100 min
BBU‐302NA 825433 62900 30 min 25 min 18 min 14 min BBU‐302NB 825433 62910 150 min 100 min 60 min 40 min BBU‐302NC 825433 62920 100 min 60 min
Model Cabinet style Dimensions (mm) Dimensions (in) Weight
BBU‐701NA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 20kg (44lbs) BBU‐701NB Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 26.5kg (58lbs) BBU‐102NA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 23kg (51lbs) BBU‐102NB Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 33kg (73lbs) BBU‐152NA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 23kg (51lbs) BBU‐152NB Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 33kg (73lbs) BBU‐152NC Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 49kg (108lbs) BBU‐202NA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 33kg (73lbs) BBU‐202NB Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 84kg (185lbs) BBU‐202NC Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 120kg (264lbs) BBU‐302NA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 33kg (73lbs) BBU‐302NB Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 84kg (185lbs) BBU‐302NC Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 120kg (264lbs)
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Always On™ UPS Systems Canada Inc www.alwayson.com 18
TN11 Series Single Phase Input and Output (2 or 3 Wire)
TN11 Series Model number: GES‐602TN11 GES‐103TN11 GES‐153TN11 GES‐203TN11
General Maximum capacity 6kVA / 4.2kW 10kVA / 7kW 15kVA / 10.5kW 20kVA / 14kW
UPC order code 825433 40030 825433 40200 825433 40400 825433 40500
Input
Rated voltage (nominal) 208 (or 240Vac)
Voltage range 160 ‐ 276Vac
Phase 1 Ø (2 wire + ground)
Frequency range 45‐65Hz
Power factor ≤0.98
Output
Voltage 120, 120/240, 110/220Vac (other configurations available)
Voltage regulation ±2%
Phase 1 Ø (3 wire + ground) (other configurations available)
Total current @ 240Vac 25A 41.7A 62.5A 83.3A
Frequency accuracy 50Hz / 60Hz ±0.5Hz (auto‐sensing)
THD <3% linear load, <5% rectified load
Load power factor 0.7
Slew rate 1Hz/second
Transient response ±4% (100% load change)
Overload capacity 105% ‐ 150% pour 10 secondes
Crest factor 3:1
Efficiency (AC‐AC) >85%
Transfer time 0ms
Outlets Hard‐wired (other configurations available)
Battery
Battery type Sealed lead acid ‐ maintenance free
Voltage 240Vdc
Recharge time 5‐8 hours; recovery = 90%, typically
Backup power time Full load >10min >4min >8min >4min
Half load >25min >13min >19min >13min
Extended run time Available ‐ Consult "Battery Banks"
Protection
Output short YES
Abnormal voltage YES
I/O noise protection Common & normal mode noise suppression
I/O spike & transient protection YES
Interface
Communication RS232 / dry contact / (optional SNMP or AS400)
Display LEDs and LCD status display
Audible alarms On battery, low battery, overload, fault
Environment
Operating temperature 0 ‐ 40°C (32 ‐ 104°F)
Humidity 0 ‐ 90% (non condensing)
Audible noise 55dBA at 1 meter from unit
Safety approval
Safety / Approvals UL1778, CSA C22.2, UL & cUL listed, ABS [American Bureau of Shipping]
EMI / RFI FCC Class A
Surge / Transient IEEE C62.41 CAT.A
Physical Data W x D x H mm
(in) 257 x 580 x 700
(10.1 x 22.8 x 27.6) 342 x 679 x 715
(13.5 x 26.7 x 28.2) 342 x 800 x 900
(13.5 x 31.5 x 35.4)
Weight in kg (lbs) 114 (251) 250 (551) 255 (562) 265 (584)
Specifications are subject to change without notice to reflect upgrades and improvements in technology.
Other voltages and configurations are available. For order codes, consult Always On. An external wrap‐around bypass module is available for all models, permitting UPS maintenance without power interruption to the load. Industrial containers are available (NEMA 12, NEMA 4, etc); consult Always On.
Always On™ UPS Systems Canada Inc www.alwayson.com 19
TN11 Series
Backup Times (Battery Banks)
To meet your back‐up time requirements, we offer increased back‐up time by simply adding additional battery cabinets. To determine the battery bank part number, locate the UPS model number and additional runtime you want to add from the tables below. For alternate runtime or runtime calculations, please contact our factory.
Specifications are subject to change without notice to reflect upgrades and improvement in technology. For more information or different runtimes, please contact CUSTOMER SERVICE toll‐free at 1‐877‐259‐2976, Ext. 451. For more information, visit www.alwayson.com
Load
6000VA 8000VA 10 000VA 12 000VA 15 000VA 20 000VA
4200W 5600W 7000W 8400W 10 500W 14 000W
UPC Cabinet
60592 Cabinet D 20min 16min 15min 11min
60600 Cabinet E 50min 40min 30min 18min 12min 7min
60940 Cabinet KA 60min 35min 30min 20min 15min 10min
60941 Cabinet KB 120min 90min 65min 45min 33min 20min
60942 Cabinet KC 170min 120min 90min 70min 50min 35min
60943 Cabinet KD 280min 200min 150min 130min 90min 60min
60944 Cabinet KE 410min 310min 260min 180min 130min 100min
UPC Cabinet Dimensions (W x D x H) Weight
60592 Cabinet D 235 x 546 x 552mm, 9.25” x 21.5” x 21.75” 80kg (177lbs)
60600 Cabinet E 400 x 682 x 1008mm, 15.7” x 26.8” x 39.7” 353kg (777lbs)
60940 Cabinet KA 812 x 863 x 1945mm, 32” x 34” x 76.6” 611kg (1347lbs)
60941 Cabinet KB 812 x 863 x 1945mm, 32” x 34” x 76.6” 740kg (1632lbs)
60942 Cabinet KC 812 x 863 x 1945mm, 32” x 34” x 76.6” 867kg (1912lbs)
60943 Cabinet KD 812 x 863 x 1945mm, 32” x 34” x 76.6” 1004kg (2214lbs)
90644 Cabinet KE 812 x 863 x 1945mm, 32” x 34” x 76.6” 1259kg (2776lbs)
Always On™ UPS Systems Canada Inc www.alwayson.com 20
NX, N & TN Series
External Bypass Systems
A separate cabinet to allow for complete removal of the UPS system from the load, while still supplying the load with conditioned power. Always On™ offers various systems which include isolation transformers for different voltage configurations, distribution panels, electro‐mechanical interlock protection to ensure proper operation, rotary switch operation and transient voltage surge suppression. Systems are supplied in a matching cabinet or wall mounted cabinet. These systems are recommended for maintenance purposes to prevent accidental removal of power from the loads and to allow for complete power removal from the UPS system for safety considerations.
Always On™ also offers an external ATS (Automatic Transfer Switch) which is fully programmable for automatic electronic operation. This will automatically switch to bypass (alternate source) in the event there is loss of power from the system for any reason.
Always On™ UPS Systems Canada Inc www.alwayson.com 21
ABS Marine Approved Units
Always On™ has a full compliment line of ABS approved systems ranging from 700VA to 250kVA. We have installations on BC Ferries, Canadian Coast Guard vessels across the country, Transport vessels, US Navy vessels and Drilling Platforms. We also offer bypass systems and extended runtime modules. Our systems provide complete power conditioning to increase product reliability for marine equipment.
Features Drip Shield: The addition of a drip shield ensures that liquids and other debris do not enter your UPS through the top cooling vents. Floor Mount: Your UPS can be secured to the floor, preventing it from moving or falling due to the movement of the vessel.
ABS: Who They Are “From its foundation in 1862, promoting maritime safety has been the core commitment of the American Bureau of Shipping (ABS). “Today, we strive to be the most efficient provider of marine and offshore classification services. We are achieving that goal through the innovative thinking, enthusiasm and professionalism of our staff. “At ABS, setting standards of excellence in marine and offshore classification is more than a motto ‐ it is the way we conduct business.”
Available Models ABS Approval is available on these UPS systems: • NX31 & NX33 Series: Three Phase In / Single or Three Phase Out, 10kVA‐250kVA • TN11‐Series: Single Phase Input & Output, 6kVA‐20kVA • N‐Series: Single Phase Input & Output, 700VA‐3kVA
Always On™ UPS Systems Canada Inc www.alwayson.com 22
Description Always On™’s L Series are line‐interactive UPS systems with a true sine wave output in all modes. These systems are ideal for commercial and light industrial applications and range in size from 800VA to 3kVA. All systems provide voltage regulation, a serial communication interface, network and modem protection, extended runtime options and additional communication interfaces. Applications Among other applications, the L Series can be applied to LAN file servers, personal computers, networks and workstations, Automatic Teller Machines, telecommunications equipment, POS equipment, robotics, test equipment, PLC’s, security and emergency systems and applications where additional runtime or SNMP are required. Advanced Features
Smart “Buck and Boost” Line Conditioning: The Always On™ transformer‐based (AVR) built‐in line conditioning provides stable voltage when the utility supply fluctuates. Lighting, Noise, Surge and Transient Protection: The L Series offers lightning and surge protection, common mode and normal mode noise protection and Low‐Pass Series filters on the input and output. Network and Modem Protection: The Always On™ high end multi‐component design provides ultimate protection and RJ11 and RJ45 connectivity. Intelligent Communications Interface: RS‐232 or dry contact interface ports act as the communication link between the computer and the UPS. Various management software is available. Cold Start: The cold start function allows start from battery when AC is not present. Auto Restart: This feature allows the UPS to restart automatically when the utility becomes available, provided the UPS has been shutdown due to an extended blackout. Auto Frequency Detection: The automatic frequency sensing function will synchronize the input and output frequency. Battery Replacement: User replaceable battery. SNMP Adapter: An optional SNMP adapter allows your network to easily manage the UPS, including remote control and status monitoring. Charging Current With Low Ripple and Low Harmonics A control circuit is used to provide a strict sine wave with low ripple and little harmonic distortion from the charging current. Value Added: Power Management and Shutdown Software, Communication Cable, Power Cable. USB Option: Available at time of order. Extended Runtime Options: Additional battery banks are available for all models.
Rack mount
L Series Intelligent Line Interactive UPS
True Sine Wave Communications / Industrial
Always On™ UPS Systems Canada Inc www.alwayson.com 23
L Series
Specifications are subject to change without notice to reflect upgrades and improvements in technology.
Additional battery banks are available for all models.
L Series Model GES‐801L GES‐102L GES‐152L GES‐202L GES‐302L
General Maximum capacity 800VA / 520W 1kVA / 650W 1.5kVA / 975W 2kVA / 1300W 3kVA / 1950W
UPC order code 825433 22100 825433 22200 825433 22300 825433 22400 825433 22500
Input
Nominal voltage 120Vac
Voltage range 90 ‐ 150Vac
Frequency range 45 ‐ 65Hz
Output
Nominal voltage 120Vac
Auto voltage regulation +15% for 90 ‐ 109Vac; ‐15% for 130 ‐ 150Vac
Current 6.6A 8.33A 11.65A 16.6A 25A
Frequency 50Hz / 60Hz (Auto detected)
Power factor 0.5 ‐ 1.0
Wave form (on battery) True sine wave
Load crest factor 3:1 (on battery)
Transfer time 2 ‐ 4ms (synchronized)
Outlets (5‐15R) 4 6 4 + Hardwired
Battery
Battery type Sealed lead acid ‐ maintenance free
Quantity 2 2 3 4 4x2
Voltage 24Vdc 36Vdc 48Vdc
Recharge time ≤2‐4 hours; recovery = 90%, typically
Backup power time
Full load ≥8min ≥7min ≥7min ≥7min ≥8min
Half load ≥20min ≥17min ≥25min ≥25min ≥25min Extended run
time Available
Protection
Output short YES
Abnormal voltage YES
Modem or network Single line (2 wire RJ11) / Network (UTP, RJ45) compatible jacks
I/O noise protection Common and normal mode noise suppression
I/O spike & transient protection YES
Interface
Communication RS232 / Dry contact / (optional SNMP)
LED display Normal / backup / low battery / fault / check battery / buck / boost
Audible alarms On battery, low battery, overload, fault
Environment
Operating temperature 0 ‐ 40°C (32 ‐ 104°F)
Humidity 0 ‐ 95% (non‐condensing)
Audible noise ≤40dBA at 1 meter from unit
Safety approval
Safety UL1778, CSA C22.2
EMI / RFI FCC Class B
Surge / Transient IEEE C62.41 CAT.A
Physical data
UPS W x D x H 140 x 436 x 210 (5.5 x 17.2 x 8.3) 168 x 436 x 225 (6.6 x 17.2 x 8.9)
External battery bank (if applicable) Internal batteries 168 x 570 x 225 mm
(6.6” x 22.4” x 8.9”)
Weight in kg (lbs) 14.5 (32) 15 (33) 25 (55.1) 30 (66.1) 46 (101.4) (including battery bank)
Rack‐mount models
Model # GES‐801LR GES‐102LR GES‐152LR GES‐202LR GES‐302LR
UPC order code 825433 22105 825433 22201 825433 22301 825433 22401 825433 22501
W x D x H mm (in) 483 x 560 x 175 (19 x 15 x 7) [4U]
Weight in kg (lbs) 18 (35.3) 20 (44) 26.1 (57.5) 28.4 (62.6) 46.4 (102.3)
555 x 438 x 102 [2U] (21.9 x 17.2 x 4)
438 x 378 x 130 [3U] (19 x 14.9 x 5.1)
Always On™ UPS Systems Canada Inc www.alwayson.com 24
L Series
Backup Times (Battery Banks) To meet your back‐up time requirements, we offer increased back‐up time by simply adding additional battery cabinets. To determine the battery bank part number, locate the UPS model number and runtime you want in the tables below. For additional runtime or for runtime calculations, please contact our factory.
For more information or different runtimes, please contact Customer Service toll‐free at 1‐877‐259‐2976, Ext. 451.
Specifications are subject to change without notice to reflect upgrades and improvements in technology.
Load
350W 490W 700W 1050W 1400W 2100W 500VA 700VA 1000VA 1500VA 2000VA 3000VA
Model UPC order code BBU‐801LA 825433 60000 42min 33min BBU‐801LB 825433 60025 70min 45min
BBU‐102LA 825433 60005 42min 33min 20min BBU‐102LB 825433 60030 70min 45min 30min
BBU‐152LA 825433 60010 30min 25min 17min 13min BBU‐152LB 825433 60035 90min 55min 40min
BBU‐202LA 825433 62300 72min 42min 30min BBU‐202LB 825433 60040 90min 50min
BBU‐302LA 825433 62400 50min 40min 27min 18min BBU‐302LB 825433 60045 90min 50min 40min
Model Cabinet Style Dimensions (mm) Dimensions (in) Weight
BBU‐801LA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 26.5kg (58lbs) BBU‐801LB Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 33kg (73lbs) BBU‐102LA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 26.5kg (58lbs) BBU‐102LB Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 33kg (73lbs) BBU‐152LA Cabinet S 170W x 450D x 225H 6.75" x 17.7" x 9" 23kg (51lbs) BBU‐152LB Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 49kg (108lbs) BBU‐202LA Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 39.5kg (87lbs) BBU‐202LB Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 61kg (134lbs) BBU‐302LA Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 37kg (81lbs) BBU‐302LB Cabinet B 260W x 540D x 740H 10.5" x 21.25" x 29" 61kg (134lbs)
Always On™ UPS Systems Canada Inc www.alwayson.com 25
The Limousin II is a transformer‐based UPS that provides lightning, surge, transient, and noise protection. The Limousin II Series provides for constant Automatic Voltage Regulation (AVR) and blackout protection. It is designed for the home/office user to provide the maximum protection at a competitive price. A shutdown/control software package, communication cable and telephone/network protection are all available with the Limousin II.
Limousin II & The Bull Home / Office / Commercial
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Limousin II
General Capacity 600VA / 360W
UPC order code 825433 00111
Input
Voltage 120V nominal, (220V option), ±25%
Frequency 50 or 60Hz ± 10% (auto sensing)
Input socket (1) IEC 320
Output
Voltage (on battery) 120Vac nominal ±15%, simulated sine wave
Frequency (on battery) 50 or 60Hz, ±0.5Hz
Auto voltage regulation ±10% of nominal
Waveform on battery Pulse Width Modulated (PWM)
Transfer time 4 milliseconds, including detection
Receptacles (3) NEMA 5‐15R (120V)
Protection & Filtering
Spike protection 480 joules, 2ms
Overload protection 110% for 60 seconds and 130% for 3 seconds
Short circuit Fuse protection or immediate shutdown
Battery
Type Sealed, maintenance‐free lead acid
Typical recharge time 6 hours (to 90% of full capacity)
Back‐up time (full load) 10‐30 minutes
Interface
Communications RS232
LED display Normal / Backup / Overload
Audible alarms On battery / Low battery / Overload
Environment
Temperature range 0‐40°C (32‐104°F)
Humidity 0‐95% (non‐condensing)
Audible noise <40dBA (1 meter from surface)
Safety approval
Safety cUL, UL1778, CSA C22.2
EMI / RF FCC Part 15 Class B
Surge / Transient IEEE C62.41 CAT.A
Physical data
Net weight kg (lbs) 6.2 (13.6)
Shipping weight kg (lbs) 6.7 (14.9)
W x D x H (mm) 97 x 320 x 135
Back view
Single line drawing
Always On™ UPS Systems Canada Inc www.alwayson.com 26
Power Management / Shutdown Software UPSmon Plus data and software protection UPSmon Plus prevents your computer from crashing during a power failure. If the UPS’s battery runs low, in the case of power failure, UPSmon Plus will detect this and perform an orderly shutdown of your computer before the battery runs out. The auto‐shutoff feature is also used to perform scheduled shutdown and startup of your computer during normal operations. With the use of your computer modem, UPSmon Plus can send an event code to your pager to notify you of a power related event on your system. A data recorder is also featured that records power data in a graphic form to facilitate analysis of power quality conditions. Communications: RS232 Bi‐Directional
UPSmon Plus Network data and network software protection UPSmon Plus Network lets you monitor and manage multiple UPS’s through your TCP/IP network from a central location. Using your network UPSmon Plus Network can auto‐shutdown an unlimited number of computers in the event of a power failure. The e‐mail and pager features can notify you of a power event. The Redundant UPS monitoring feature permits two or more redundant UPS’s to be monitored. If one redundant UPS fails or is taken off‐line for maintenance, UPSmon Plus Network still monitors the back‐up UPS and provides auto‐shutdown protection in the case of a power failure. Communications: RS232 Bi‐Directional and TCP/IP
Activity Monitoring Software Report Screens
.NetPower SNMP Adapter integrated intelligent power management (IIPM) The IIPM packages are comprised of the SNMP Agent, an SNMP adapter and onEvent. These are available to efficiently control and manage the GES series UPS’s. The excellent network management feature lets you easily manage over the Internet/Intranet using TCP/IP and Ethernet. IIPM features remote monitoring and control via a TCP/IP network and provides a hierarchical architecture to manage your UPS’s. It also features notification via e‐mail, pager, audible alarm or broadcast and graceful graphics for monitoring and displaying the real‐time status of your UPS. IIPM also provides remote shutdown, file saving and password protection.
Main UPS management screen
Individual UPS’s status can also be viewed
Main UPSmon software screen UPS power management
scheduler
Paging setup screen Power quality data analysis Set actions to
trigger on power events
Always On™ UPS Systems Canada Inc www.alwayson.com 27
TTF/ILF-12015 Isolating Line Filter
The Always On™ TTF/ILF (Toroidal Isolating Line Filter) combines a low‐pass series filter with a toroidal isolation transformer. The TTF/ILF provides for total protection against all power aberrations and eliminates any troublesome constant voltages which may exist between neutral and ground in some electrical configurations. It is totally compatible with all operating loads including high frequency switching power supplies. The TTF/ILF corrects ground fault problems and eliminates neutral voltages by re‐establishing the “zero” volt ground reference point. It provides excellent noise protection, eliminating problems caused by normal mode and common mode noise, as well as other electrical aberrations such as: transients, spikes, surges, harmonics and lightning induced voltages.
Applications Computers, Laser Printers, Copiers, Point of Sale Terminals, Medical Instruments, PLC’s, Process Instruments, CAD/CAM/CIM & Robotics. Protects From: Reverse Polarity, Spikes, Surges, Transients, RFI/EMI Interference, Common/Normal Mode Noise, Direct/Indirect Lightning Effects, and Voltage between Neutral and Ground.
TTF/ILF-12015: 120Vac 15A Isolating Line Filter UPC Order Code: 825433 00800 TTF/ILF-22007: 220Vac 7A Isolating Line Filter UPC Order Code: 825433 00850
Specifications are subject to change without notice to reflect upgrades and improvements in technology.
Some optional features that can be added are the manual by‐pass switch or an automatic bypass switch. The manual bypass switch will transfer the load from TTF/ILF supplied power to a filtered and isolated AC Utility upon user operated switching. This will allow for removal of the TTF/ILF system without powering down or exposing your critical loads. The automatic bypass switch will automatically transfer the load from TTF/ILF supplied power in the event of a premature shutdown for whatever reason without powering down your critical loads. Surge/Transient Suppression: ANSI/IEEE C62.41-1992 - REV.2 (Surge Test) TYPICAL: 120V Filter
Input: L‐L L‐N L‐G N‐G Category A3 Ringwave 100kHz 6000V 200A
Output (V) N/A 45V 47V 41V
Specifications Frequency 50 / 60 Hz
Voltage Up to 240V; 1; Wye
Amperage 15A @ 120V, 7A @ 220/240V
VA rating 1800VA maximum
Protection modes Normal mode (L‐N), Common mode (L‐G, N‐G)
Technology Dual hybrid series filter / Toroidal isolation transformer
Insertion loss Nominal 75dB, Mil‐Std‐220A @ 100kHz; Common mode 120dB
Bandwidth Normal mode: 10‐100kHz; Common mode: DC to 100mHz
Response time Instantaneous
Standards 15A, 120Vac
Total peak surge current 26 000A
Joules Up to 600 Joules
Leakage current Nominal <250mA (<90mA hospital grade)
Operating humidity 0‐97% (non‐condensing)
Operating temperature 0°C ‐ 40°C
Bypass mode (TTF/ILF‐12015‐BP only) All outputs are powered via utility power
Warranty 5 year
Dimensions 300 x 355 x 153mm (12" x 14" x 6")
Weight 20kg (44lbs) approximately
Wall mount Standard (tower model available)
Always On™ UPS Systems Canada Inc www.alwayson.com 28
*Products may not necessarily be as shown.
The Always On™ ESE SPD filter is designed to protect, at the power panel, against externally and internally produced power aberrations, massive impulses, lightning induced effects and interference associated with low frequency harmonics and situations caused by accidents and/or failures in the electrical utility system. It is also totally compatible with all operating loads, including high frequency power supplies and constant current loads controlled by electronic switches.
Applications Electrical Service Entrance filters protect the electronic and electrical equipment in the building by supplying power protection at the main and sub‐panel locations. Protection Our ESE’s offer high end protection for industrial and commercial environments and our specifically designed and tuned circuitry provides protection against all potentially dangerous electrical aberrations. They eliminate and attenuate to safe levels common and normal mode noise, massive surge impulses, indirect lightning strikes and their effects, interference associated with low frequency harmonics, spikes and transients, as well as problems associated with electrical utility failures caused by accidents, storms, etc. Electrical and electronic equipment create their own power aberrations, which creates problems for other loads and equipment ‘downstream’. These aberrations will travel down the power bus to the power panels, where they propagate to other loads via other branch circuits. By installing Always On™ ESE power panel protection devices, these problems will not occur.
Always On™ ESE Power protection offers TWO Methods of Protection
1) For all New Residential, Commercial and Industrial Construction: The ESE protects electronic equipment in new buildings (security, environmental, networking, communications, appliances, systems, etc.) from potentially destructive and disruptive externally generated power spikes and transients, massive surges, indirect lightning strikes, low frequency harmonics and common and normal mode noise. 2) For all Commercial and Industrial Retrofits: In commercial and industrial environments, the ESE offers the same features as above and protects ‘downstream’ branch panels from externally and internally generated power aberrations such as spikes,
transients, massive surges, low frequency harmonics and common and normal mode noise. Stop the problems before they can occur. Eliminate all potential problem‐causing and damaging power aberrations by having an Always On™ ESE filter installed. Features The ESE features self‐diagnostics, LED indicators and removable fuses per phase, which eliminate dedicated and costly 3 phase panel breakers.
Electrical Service Entrance Surge Protection Device
Always On™ UPS Systems Canada Inc www.alwayson.com 29
Description of Model Number
Electrical Service Entrance
Specifications are subject to change without notice to reflect upgrades and improvements in technology.
MODEL SURGE CURRENT VOLTAGE Y or D OPTION MODEL # ESE 60K 240 Y ESE‐60K‐240Y (SHP) ESE 250K 480 D ESE‐240K‐480D ESE 500K 600 Y FM ESE‐500K‐600Y‐FM
Surge current: 60K, 100k to 600k 208/240/480/600 VOLTS
Y ‐ Neutral wire required (Wye type transformer) EXAMPLES D ‐ Neutral wire not required (Delta type transformer FM ‐ Flush Mount Container *Optional Additional Cost
Model type ESE
SURGE CURRENT per phase 60K* 60kA per Phase 100K 100kA per Phase 120K 120kA per Phase 160K 160kA per Phase 200K 200kA per Phase 250K 250kA per Phase 300K 300kA per Phase 400K 400kA per Phase 500K 500kA per Phase 600K 600kA per Phase
*Note: 60K version is for residential use and comes in the 240Volt/Split phase configuration only. It is not recommended for commercial or industrial applications.
Voltages** 208 240 480 600
**Other voltage options available. Consult manufacturer.
Configuration Wye or Delta***
***Contact manufacturer for more information on Delta version.
For all UPC order codes, visit: www.alwayson.com
Flush Mount
ESE 200K 208 Y (FM) ‐ (Optional)
Specifications Frequency 50 / 60 Hz
Voltages 208, 240, 480, 600V (other voltages available)
Phases Wye or Delta ‐ three phase and single phase
Protection modes 10 for 3 Ø wye, 6 for 3 Ø delta, 5 for 2 Ø wye
Technology Bi‐directional parallel
Insertion loss Nominal 60dB, Mil‐Standard‐220A@100kHz
Bandwidth 10kHz ‐ 50MHz or 180Hz ‐ 50MHz
Response time Constant / Instantaneous
Standards UL1449 Rev 2009 (SPD) Peak
Surge Current 60kA to 600kA per phase
Sink current capacity / phase 25A
Operating humidity 0 ‐ 97% (non‐condensing)
Operating temperature ‐40°C ‐ 65°C
Warranty 10 years
Enclosure NEMA 12 (or optional NEMA 4) flange mount
Dimensions 14" x 12" x 6"
Weight 13.6kg / 30lbs (approximately)
Optional FM ‐ Flush mount container (DIM 12" x 12" x 6")
Always On™ UPS Systems Canada Inc www.alwayson.com 30
AC Power and Data Line Protection In One Convenient Box Today’s competitive markets require all industrial equipment to function at maximum performance. Lower profits require higher yields or production. This is achieved by maintaining production equipment to run at its optimum level. Increased production means increased profits.
The Always On™ PLC 2+2 and 2+0 Surge Protection Device (SPD) and data line filter will provide today’s users and OEM’s with the ultimate protection required by today’s automated industries. Always On™ has 25 years in the noise suppression and power quality industry, providing us the knowledge base required to remain on the cutting edge of the power protection industry. Applications: Among other applications, the PLC Protector can be applied to PLC’s, robotics, CAD/CAM, alarm systems, scanners, controllers, medical equipment and virtually all microprocessor‐based ”critical” equipment. Uses: Typical PLC Protector uses include the oil industry, refineries, the pulp and paper industry, the textile industry, water and sewer treatment plants, the petrochemical industry, the food processing industry and virtually all types of manufacturers.
Features / Benefits Series Hybrid Design: Sine wave tracking TVSS technology ensures fast and immediate attenuation of the harmful spikes, transients and both common and normal mode noise. The added data line filter ensures that the 2+2 Filter will protect the attached network/communication link from all potential problems. The Always On™ 2+2 filter is the only filter that offers all modes of protection on both the power line and the data line. The Always On™ 2+2 one‐two punch will guarantee maximum runtimes for your equipment, resulting in higher production and profits, while decreasing downtime and equipment repair costs. Suppression / Attenuation: The cutting edge technology contained in the Always On™ 2+2 and 2+0 filters allow normal mode noise attenuation up to 85dB and for common mode noise attenuation up to 50dB. It filters bandwidths of 10kHz to 100MHz, with a total peak surge current of 32,500 amps, while providing a response time of less than 1 nanosecond. Functioning Indicator: The easily seen three colour LED informs the user of the working status of the Always On 2+2 and 2+0 filter. Optional Communications: Form A, B or C contacts allow the user to monitor the status of the 2+2 or 2+0 filter from a remote location. Mounting Options: The 2+2 and 2+0 come standard with J‐Rail or an optional flange mounting is available. Product Warranty: Always On™ 2+2 and 2+0 filters are warranted against failure for two years (exchange or repair warranty). 5‐Year User Guarantee: Always On™ guarantees against electrical damage to the protected power supplies by power aberrations for 5 years.
Conclusion The PLC 2+2 and 2+0 filters increase up‐times to the maximum, which increases production and results in higher profits. It also offers substantial savings through decreased down‐time and decreased repair costs.
User resettable breaker on all models
PLC Two-Plus & Two-Plus-Two SPD Filters: Three-Wire Grounded / Two-Wire Ungrounded
& Data Line Filters: Three & Four Wire Data Bus Protection
Always On™ UPS Systems Canada Inc www.alwayson.com 31
Data Line Protection (Two‐Plus‐Two Only) This solid state semi‐conductor series offers surge protection for line to line and lines A, B, common and shield to ground. It is designed for 3 wire and 4 wire data bus communications that require approximately 5Vdc difference between line and line. It is compatible with DeviceNet, Data Highway Plus, Modbus Plus, Genius Bus, Simatic Net, Profibus, CompoBus/S, RS485, RS422, Twisted Pair, 3 Wire and Industrial Networks up to 100Mb/sec.
Two‐Plus & Two‐Plus‐Two 3 Wire Grounded Physical Data Operating voltage 120Vac single phase Container Din Rail / Flange Mount
Power rating 360VA/600VA/1200VA/1800VA Operating Temperature ‐40 to 60°C Amperage 5/10/15
Dimensions 110 x 75 x 110mm (4.375" x 2.75" x 4.375") Frequency 50 / 60Hz
Protection modes L‐N, L‐G, N‐G Weight 2kg / 4.5lbs Maximum clamping voltage 150V
Noise attenuation
Normal mode 85 dB @ 100kHz Common mode 50 dB @ 5MHz
Filter bandwidth 10kHz to 100MHz Total peak surge current Up to 32 500A
Joules Up to 750 Joules Response time < 1 nanosecond Indicators Status and fault LED Options Dry contacts (for remote monitoring)
Specifications are subject to change without notice to reflect upgrades and improvements in technology.
Two‐Plus‐Two Strike Breakdown Voltage 13V @ 100V/µSec, 10.5V @ 100V/Sec Max DC Operating Voltage 9.6Vdc
Clamping Voltage 81V Maximum Surge Current 1kA
Max Capacitance (A‐B Lines) L‐L 2.9pF, L‐G 73pF DeviceNet Includes 24Vdc Bus protection
PLC Two-Plus & Two-Plus-Two
AC Power Conditioning (in both Two‐Plus & Two‐Plus‐Two) Surge Protection Utilizing SPD / Hybrid Design
4 Types of High End Protection in One Box
PLC 2+2 120 15 AC DP DCA
Model Style PLC
Model Type 2+2 2+0
Voltage 120 240
Current Rating 5 10 15
AC Filter AC
Data and Vdc Filter DP (2+2 only)
Dry Contacts DCA DCB DCC (2+0 only)
Model Number Description
For more information, visit www.alwayson.com
Always On™ UPS Systems Canada Inc www.alwayson.com 32
NFC Series Three Phase In / Out
Frequency Converters & Voltage Regulators Industrial / Commercial
50 or 60Hz Input Frequency / 50, 60, or 400Hz User Defined Output Frequency
The Always On™ NFC Series Frequency Converters are manufactured to provide clean, regulated and controlled power at the customer specified voltage and frequency. Based on the Always On™ NX Series, the NFC Series provides clean, isolated, reliable and consistent power to all critical loads at the expected levels required.
The NFC Series Frequency Converters are intelligent, dual conversion, on‐line, three phase systems for centralized frequency conversion, power protection and distribution. The “dual conversion” means AC utility is converted into DC power which, in turn, charges the batteries and supplies the inverter, which inverts the DC power back into highly regulated and isolated AC power supplied at a frequency (50, 60, or 400Hz). This continuous on‐line Frequency Converter is available in models from 10kVA up to 250kVA. This dual conversion prevents power aberrations from affecting the connected loads. The NFC Series Frequency Converters provide reliable and robust protection and frequency conversion, allowing for reliable and protected power to be available for all specific and critical loads. Features and Benefits Frequency Conversion: This permits the user to configure a system with any input voltage (208, 480 or 600) and input frequency (50 or 60Hz) with any output voltage (208/120, 480/277 or 600/347) and output frequency (50, 60 or 400Hz), independent of the input configuration.
Full Galvanic Isolation: Full Galvanic Isolation provides a completely isolated and referenced output. This isolation protection provides a proven solution to problems created by induced voltages affecting the critical loads. Since the output circuit to the load is completely isolated and no noise induced on the neutral can permeate to the loads, systems operate in a more reliable fashion. Also, this type of protection increases the life span of equipment by eliminating noise, which breaks down components.
Modular Design: Each major component (inverter and rectifier) on the NFC Series Frequency Converters are installed on slide‐out modules. This allows for quick repair (mean time to repair of <30 minutes) and easy field upgradability.
High efficiency: Thanks to IGBT technology, the NFC Series Frequency Converters provide high efficiency.
Fully digital: DSP (Digital Signal Processor), flash memory and PWM strategy are the technology corner stones of the new age of power quality and reliability.
Extremely flexible: The NFC Series Frequency Converters offer tailor‐made power protection to comply with your individual installation requirements. Options include a 12‐pulse rectifier and a Smart Panel (SP). In addition, a comprehensive software suite can be added for mission control and data protection.
Optional Battery Banks: Always On™ has also allowed for the option of back‐up time to be added to the system to eliminate the need of purchasing a UPS system and a frequency converter. This runtime package will allow for UPS‐like operation at a user specified frequency (50, 60, or 400Hz).
Always On™ UPS Systems Canada Inc www.alwayson.com 33
NFC Series Frequency Converters: 50 or 60Hz Input Frequency / 50, 60, or 400Hz User Defined Output Frequency 10kVA ‐ 250kVA
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
NFC Series Frequency Converter Single Line Drawing
For Always On™ UPC order codes, visit www.alwayson.com
General Data Topology True On‐Line, Dual Conversion
Nominal output at PF=0.8 kVA 10 15 20 30 40 50 60 80 100 160 250
Overall efficiency
100% load, 0.9 PF % 91 91 91 91 91.5 92 92 92.5 92.5 93 93
50% load, 0.9 PF % 89 89 89 89 89 91 91 91 91 92 92
True galvanic isolation from input to output YES
Heat rejection at 100% load, 0.9 PF and charged battery
BTU/hr (kW)
3070 (0.9)
3510 (1.0)
4440 (1.3)
6480 (1.9)
8870 (2.6)
10 200 (3.0)
11 900 (3.5)
15 700 (4.6)
18 400 (5.4)
29 700 (8.7)
44 460 (13)
Audible noise level (at 1m) dB (A) <65 at 1m maximum <67 at 1m maximum Operating
temperature range
UPS 0°C ‐ 40°C (32°F ‐ 104°F)
Battery Optimum 20°C ‐ 25°C (68°F ‐ 77°F); higher temperatures reduce battery life expectancy
Storage temperature
range
UPS ‐15°C ‐ 50°C (5°F ‐ 122°F)
Battery 0°C ‐ 40°C (32°F ‐ 104°F) (VRLA) Storage time is 6 months at 25°C (77°F); higher temperatures reduce battery storage time
Relative humidity 0 ‐ 90%, non‐condensing
Maximum altitude Without derating <1500m, (5000 ft), no derating
Enclosure
Type Indoor (NEMA 1) [Optional drip shield available] [Other configurations available] Safety Internal dead front construction
Cooling Forced air (bottom to top) Colour Manufacturer colour (ivory)
Installation
Rigging Suitable for handling by forklift
Mounting Casters and floor mounting brackets
Installation & maintenance access Front access required for normal maintenance
Conduit access Bottom entry standard [Optional top entry] Standards UL 1778, IEC 62040, FCC Class A, EN50091‐1, ‐2
Electrostatic discharge immunity 6kV
Configuration Standard Stand‐alone Optional IPRO (2 units working in parallel)
Always On™ UPS Systems Canada Inc www.alwayson.com 34
Aurora & Borealis Emergency Lighting Inverters
Single Phase / Three Phase
AURORA Series Emergency Lighting AC Inverters are among the most reliable central systems available for emergency lighting and other demanding critical applications. The AURORA Series Emergency Lighting AC Inverters are Dual Conversion, On‐line, single‐phase, intelligent systems for centralized power protection and distribution. The Dual Conversion means it converts the incoming AC power to DC, charges the batteries, then inverts the DC back into highly regulated isolated AC power. These continuous on‐line Emergency Lighting AC Inverters are available in models from 3kW to 15kW. The AURORA Series Emergency Lighting AC Inverters provide reliable and constant protection for life safety emergency lighting, and infrastructure applications such as airports, hospitals, and residences.
BOREALIS Series Emergency Lighting AC Inverters are among the most reliable systems available for emergency lighting and other demanding critical applications. The BOREALIS Series Emergency Lighting AC Inverters are Dual Conversion, On‐line, three‐phase, intelligent systems for centralized power protection. These continuous on‐line Emergency Lighting AC Inverters are available in models from 8kW up to 48kW. The BOREALIS Series Emergency Lighting AC Inverters provide reliable and constant protection for mission critical emergency lighting, and infrastructure applications such as airports, hospitals, and financial companies.
Always On™ UPS Systems Canada Inc www.alwayson.com 35
Aurora Single Phase ELI
Features And Benefits These ELI’s provide full time self‐diagnostics as well as two levels of audible alarms when the unit is operating in battery mode. A manual test function has been incorporated into the input/test breakers that make battery testing a simple and safe procedure. The internal bypass switch allows maintenance on the ELI’s to be performed without interruption of power to the load. The communications port, in conjunction with multi‐platform monitoring and control software, enables the unit to be connected to a local or networked computer system. Detailed operating information including voltages, currents, and alarm status is available to the monitoring system.
Full Galvanic Isolation: Provides a completely isolated and re‐reference output. This isolation protection provides a proven solution to problems created by induced voltages affecting the critical loads. Since the output circuit to the load is completely isolated and no noise induced on the neutral can permeate to the loads, systems operate in a more reliable fashion. Fully digital: CPU control, flash memory, and PWM strategy are the technology corner stones of the new age of power quality and reliability. Extremely flexible: The AURORA Series offers tailor‐made power protection to comply with your individual installation requirements. Options include additional runtime, remote monitoring panel, and distribution panels. In addition, a comprehensive software suite can be added for mission control and data protection‐covers all your application needs. IMBS: An internal maintenance bypass switch is standard with all AURORA single phase inverter units. EMI suppression: An EMI filter is added to meet the international EMC limits to ensure that no noise will effect or interfere with other equipment connected to the same AC source. High frequency design: The inverter design incorporates high frequency, high efficiency Insulated Gate Bi‐polar Transistors (IGBT). A PWM wave, synchronized to the bypass input, triggers the IGBT’s, which invert the DC into AC power required by the loads. This design decreases the number of required components, increases reliability and performance while decreasing acoustic noise, size and weight. Cold start function: The AURORA can be started without the utility AC supply being activated, or present at the input terminal strip because our system is designed with current limiting circuitry, which allows startup of the AURORA on battery DC power. Intelligent battery test: The batteries are tested monthly automatically. When an abnormal condition (low charge rating, or bad battery) is found the user will be informed immediately through alarms on the AURORA systems. MTBF of cooling fans: Long cycling fans will operate at variable speeds necessary which is dependent on the load of the inverter systems increasing the life expectancy of the fan motors. Options Output Circuit Breakers: Supports normally on or normally off circuit breakers. Additional Run Times: These can be 30, 60, 90, or 120 minutes, other configurations are available. EMBP: External Maintenance Bypass. This device allows the load power to be transferred from the inverter output to the AC supply. Thus the inverter can be completely removed or repaired without interruption of power to the load. RCMP: Remote Control and Monitoring Panel. This option provides remote alarms to indicate the inverter status. SNMP: SNMP adapter to remotely control and monitor the unit via a network or the Internet.
Consult Always On UPS for other features and options.
Always On™ UPS Systems Canada Inc www.alwayson.com 36
Aurora Single Phase ELI
3kW to 15kW
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Standard charger size: 3kW to 7.5kW is 5A / 10kW to 15kW is 10A.
Other voltage ratings and configurations are available; for order codes, consult manufacturer.
Consult Always On UPS for available runtimes and more information.
Model 3kW 5kW 7.5kW 10kW 15kW
Input
Phase / Frequency Single phase (2 wire + ground) 50 / 60Hz
Rated voltage 208 / 240 / 277 / 347 Vac
Voltage range ±15%
Input current
208/29A 240/25A 277/22A 347/18A
208/40A 240/35A 277/30A 347/24A
208/60A 240/53A 277/45A 347/36A
208/74A 240/64A 277/56A 347/45A
208/113A 240/98A 277/85A 347/66A
Output
Voltage / Phase 208 / 240 / 277 / 347 Vac (Single phase, 2 wire + ground)
Voltage regulation ±2%
Maximum current
208/14.4A 240/12.5A 277/10.8A 347/8.6A
208/24A 240/20.8A 277/18.1A 347/14.4A
208/36.1A 240/53A 277/27A 347/21.6A
208/48.1A 240/41.7A 277/36.1A 347/28.8
208/72.1A 240/62.5A 277/54.2A 347/43.2A
Frequency 50Hz / 60Hz ± 0.5%
THD <3% linear load; <5% rectified load
Slew rate 1Hz/second
Transient response ±4% (100% load change)
Overload capacity 110% ‐ 125% for 1 min, then switch to bypass 125% ‐ 150% for 10 sec, then switch to bypass
Crest factor 3:1
Efficiency (AC ‐ AC) >85%
Transfer time 0ms
Outlets Hard‐wired
DC System DC system voltage 240Vdc
Protection
Output short YES
Abnormal voltage YES
I / O noise protection Common & normal mode noise suppression
I / O spike and transient protection YES
Interface
Communication RS232 / Dry contact / (Optional SNMP)
Display LCD indicator status panel
Audible alarms On battery, low battery, overload, fault
Environment
Operating temperature 0 ‐ 40°C
Humidity 0% ‐ 95% (non‐condensing)
Audible noise 55 dBA at 1m from unit
Elevation 3500 meters maximum
Safety approval
Safety UL1778, UL924, CSA C22.2, CSA 107.3, NFPA111
EMI / RFI FCC Section 15 Class A
Surge / Transient IEEE C62.41 Cat.A
Physical data W x D x H (mm) 450 x 725 x 1026 1070 x 690 x 1705
Weight (kg) 130 150 150 431 760
Always On™ UPS Systems Canada Inc www.alwayson.com 37
Borealis Three Phase ELI
Features And Benefits These ELI’s provide full time self‐diagnostics as well as two levels of audible alarms when the unit is operating in battery mode. A manual test switch has been incorporated into the input/test breakers that make testing a simple procedure. The internal bypass switch allows maintenance on the ELI’s to be performed without interruption of power to the load. The communications port, in conjunction with multi‐platform monitoring and control software, enables the unit to be connected to a local or networked computer system. Detailed operating information including voltages, currents, and alarm status is available to the monitoring system.
Full Galvanic Isolation: Provides a completely isolated and re‐reference output. This isolation protection provides a proven solution to problems created by induced voltages affecting the critical loads. Since the output circuit to the load is completely isolated and no noise induced on the neutral can permeate to the loads, systems operate in a more reliable fashion. Fully digital: DSP (Digital Signal Processor), flash memory, and multi‐contact strategy are the technology corner stones of the new age of power quality and reliability. Extremely flexible: The BOREALIS Series offers tailor‐made power protection to comply with your individual installation requirements. Options include a 12‐pulse rectifier, and distribution panels. IMBS: An internal maintenance bypass switch is standard with all BOREALIS 3 phase inverter units. EMI suppression: An EMI filter is added to meet the international EMC limits to ensure that no noise will effect or interfere with other equipment connected to the same AC source. High frequency design: The three phase BOREALIS design incorporates a full bridge three‐phase inverter. This design makes the BOREALIS perform better than other Emergency Lighting AC Inverters in the market when an unbalanced load is connected. Cold start function: The BOREALIS can be started without the utility AC supply being activated, or present at the input terminal strip because our system is designed with current limiting circuitry, which allows Startup of the BOREALIS on battery DC power. Intelligent charger: The BOREALIS will perform an automatic monthly recharge (boost charge) of the batteries as well as automatically recharge (boost charge) the batteries when the battery voltage level decreases to approximately 2V/Cell. It makes the batteries stay in good condition. Intelligent battery test: The batteries are tested monthly automatically. When an abnormal condition (low charge rating, or bad battery) is found the user will be informed immediately through alarms on the BOREALIS systems. MTBF of cooling fans: Long cycling fans will operate at variable speeds necessary which is dependent on the load of the inverter systems increasing the life expectancy of the fan motors. SNMP: SNMP adapter to remotely control and monitor the unit via a network or the Internet. Options Output Circuit Breakers: Supports normally on or normally off circuit breakers. Additional Run Times: These can be 30, 60, 90, or 120 minutes, other configurations are available. EMBP: External Maintenance Bypass. This device allows the load power to be transferred from the inverter output to the AC supply. Thus the inverter can be completely removed or repaired without interruption of power to the load. RCMP: Remote Control and Monitoring Panel. This option provides remote alarms to indicate the inverter status.
Consult Always On UPS for other features and options.
Always On™ UPS Systems Canada Inc www.alwayson.com 38
Borealis Three Phase ELI
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
8KW to 48KW Rectifier 8kW 12kW 16kW 24kW 32kW 40kW 48kW
Input voltage 120/208V 277/480V 347/600V 3 phase, 4 wire + ground
Input range ±15%
Input frequency 45 ‐ 65Hz
Input power factor <1
Normal input current (based on 208Vac) 31 47 62 93 124 155 186
Maximum input current (based on 208Vac) 36 54 71 107 142 178 213
THD 6 pulse: 30% 12 pulse with filter: 9%
Power walk‐in (adjustable) 0% ‐ 100% : 20 seconds
Efficiency 98%
Voltage regulation 1%
Ripple voltage 0.50%
Battery 8kW 12kW 16kW 24kW 32kW 40kW 48kW
Battery type Maintenance free sealed lead acid
Number of cells 174
Voltage range 295 ‐ 410Vdc
Maximum charge current (ADC) 5 7.5 10 15 20 25 30
Battery low voltage 320Vdc
Battery low stop 295Vdc
Inverter 8kW 12kW 16kW 24kW 32kW 40kW 48kW
DC input range 295 ‐ 415Vdc
Wave form Sinusoidal
Output voltage (adjustable) 120/208V, 277/480V, 347/600V, 3 phase, 4 wire + ground
Crest factor 3:1
Output power factor 0.8
Voltage regulation 100% unbalance load ±1%
Frequency lock range 50 / 60Hz, ±7%
Output frequency (free running) 50 / 60Hz, ±0.1Hz
Output voltage tolerance Static ±1%
Load step 0% ‐ 100% ‐ 0% Recovering to within ±1% in 4 cycles
THD (linear load) <2%
Overload
<110% Continuous
110 ‐ 125% 15 minutes
125 ‐ 150% 5 minutes
150 ‐ 170% 30 seconds
>170% 10 seconds
Efficiency (100% load) 92%
Maximum output wattage (kW) 8 12 16 24 32 40 48
Always On™ UPS Systems Canada Inc www.alwayson.com 39
8KW to 48KW
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
The input voltages are WYE or Delta, but the output voltages are 3 phase 4 wire plus ground (WYE) configuration.
Other voltage ratings and configurations are available.
For order codes, consult Always on UPS. Consult Always On UPS for available runtimes and more information.
Borealis Three Phase ELI
Static switch 8kW 12kW 16kW 24kW 32kW 40kW 48kW Voltage range ±20% of input voltage (line to neutral)
Frequency range 45 ‐ 55Hz / 55 ‐ 65Hz Efficiency 99.50%
Transfer time Mains ‐> Inverter 0ms Inverter ‐> Mains 0ms
Isolation with output YES
Overall characteristics 8kW 12kW 16kW 24kW 32kW 40kW 48kW Overall efficiency 90%
Maximum heat dissipation (kW) 0.89 1.32 1.76 2.64 3.52 4.40 5.28
Operating environment Temperature 0 ‐ 40°C (32 ‐ 104°F) Humidity 0 ‐ 90% (non‐condensing) Altitude <1500m above sea level
Protections
Short circuit YES Lightning MOV EMC filter Input & output
Galvanic isolation Between input & output Indications and alarms LED, LCD, Buzzer
Dry contact YES Battery start YES
Data display by LCD YES Audible noise < 65dBA (at 1m)
Standards UL 924, UL1778, NFPA111, CSA 107.3, CCMC, BMEC, CSA 22.2 60950
Physical data W x D x H (mm) 550 x 812 x 1600 Weight (kg) 380 415 450 580 650 710 850
Always On™ UPS Systems Canada Inc www.alwayson.com 40
Genie Smart Panel / Cabinet UPS Powered Fault Protected System (One Cycle Clearing) The Genie is designed to supply AC power and isolate multiple critical loads fed by one panel. Genie is manufactured in our ISO 9001:2008 certified facilities and incorporates the Always On™ Specifically Designed Breaker (SDB). GENIE protects the connected loads from reacting to problems caused by short circuits, i.e. momentary loss of voltage (opening contacts, re‐boots etc) and high current spikes creating a possible hazard at the failed or shorted loads. During
short circuit condition with a standard distribution panel, the UPS will be automatically transferred to static bypass mode allowing the input utility to supply dangerously high currents (approximately 1000% of the maximum UPS current) for 18 to 22 cycles (the normal amount of time a standard breaker requires to clear). Also during the time the load breaker is being cleared a large transient will be created resulting in possible damaged equipment. In the event the faulted load breaker is not cleared, the UPS will shut‐down, due to extended overload, or the UPS input breaker will clear causing a power loss. • Genie is designed to identify an overload condition and clear the SDB in advance of a total load failure
preventing damaging and/or dangerous short circuits and high current conditions. • Genie SDB’s are designed to clear or open in less than one cycle eliminating the “time window” (18 to 22
cycles of standard breakers) which allows the short circuit evolution of problems to begin. • Genie SDB’s intelligent design distinguishes the difference between normal inrush current for equipment
and a short circuit or overload condition. • Genie SDB’s are simple plug‐in breaker design, for easy upgrade or replacement.
Options Communication port: GENIE can incorporate a relay communication interface and alarms to allow for notification of an open SDB. Power Protection: SPD protection 200kA surge current to 600kA surge current protection is available. Remote Panel with Audible Alarm: Configured with notification Display and Alarms function to identify open SDB. Compatibility: The GENIE is designed specifically for Always On™ UPS products but can be utilized to support other manufactured UPS products.
Patented in Canada: Patented in the USA: # 2 496 365 # 7 557 468
Complete custom
configurations available!
Always On™ UPS Systems Canada Inc www.alwayson.com 41
ALW Batteries & Battery Bank Units ALW Batteries Always On UPS Systems Canada Inc takes great pride in our ALW Series batteries. Years of research and development, along with ISO 9001:2008 quality management systems and UL Listing, ensure the highest quality and performance from our battery systems. The range of battery sizes and capacities is unique in the industry, and their specifications are optimized to ensure maximum performance for our broad range of UPS backup power and Emergency Lighting Inverter Systems. Our tough standards during manufacturing, quality control and testing
ensure that only batteries meeting the tight specifications of the product are integrated into the rest of our system designs. Our special process of grouping
battery types during transport and storage maintenance allows us to easily match our batteries during assembly of our battery cabinets. As part of our certification by CSA and listing by UL, each battery, charger and inverter of a fully assembled system is accurately calibrated and vigorously tested through each mode of operation, including battery discharge and recharge cycles. This is done to ensure that the complete system is in compliance with the required safety standards.
Battery Cabinets Our battery cabinets come in a variety of sizes to suit your backup time needs. For even longer runtimes, multiple cabinets can be used to increase storage capacity. The cabinets themselves have several useful features, such as: • Heavy duty casters. • Convenient battery cable with Anderson quick connects. • Retractable battery trays, making battery testing and replacement easy.
ALW Batteries ALW36‐12UPS ALW56‐12UPS ALW85‐12UPS ALW110‐12UPS ALW160‐12UPS Capacity (25°C/77°F) 36Ah 56Ah 85Ah 110Ah 160Ah
Voltage 12V 12V 12V 12V 12V Weight 12.6kg / 27.7lbs 17.5kg / 38.5lbs 26.0kg / 57.2lbs 32.0kg / 70.4lbs 45.5kg / 100.1lbs
Dimensions KA, KB, KC, KD, KE cabinets KF, KG, KH, KI, KJ cabinets mm 812W x 863D x 1945H 1314W x 850D x 1945H
inches 32W x 34D x 76.6H 51.7W x 33.5D x 76.6H
Always On™ UPS Systems Canada Inc www.alwayson.com 42
UPS Preventative Maintenance Program
Always On™’s UPS systems are designed for maximum reliability and peak performance. Even so, a regular maintenance program is necessary to identify and correct potential problems before they can occur. This helps to prevent unplanned and inopportune downtime and outages of critical systems, more rapidly addresses problems that can occur, and even extends battery lifespan. A regular program that involves inspecting, cleaning, calibration and functional testing of all modes of operation ensures factory‐specified performance through the lifecycle of the UPS System. Record keeping is a snapshot in time for tracking and analysis of the results, to trend the components’ performance as the system ages. Maintenance takes into account the actual age of the specific devices, comparing expected performance to the lifespan. This allows us to monitor the health of the UPS system, and take corrective actions as necessary under pre‐planned conditions. The UPS automatic monthly self test can be enhanced with increased functionality through remote monitoring and testing. Specific parameters can be programmed to take into account the actual system design requirements, and log the results for analysis. Secured remote access to all the UPS’s in the network allow for comprehensive control and monitoring from one centralized location. To accurately assess battery backup capacity, however, a load test and measurement must be performed as part of a regular maintenance program. An annual UPS maintenance program (or semi‐annually in challenging environmental conditions) should be implemented as part of a user’s regular maintenance program, and is highly recommended as part of the overall equipment budget and lifecycle planning.
Always On™ UPS Systems Canada Inc www.alwayson.com 43
Project:
Company:
Contact:
Phone:
Email:
Fax:
If tender available send with information above.
Power Requirements (Please fill in load requirements) _____kVA or ______kW or ______A Back up time requirements
_______minutes
Applications (Circle one, or fill in other) Commercial Telecom Industrial Marine Medical Other: ____________
Type of load to be powered (Circle one, or fill other) Motor, Pump (HP:_______ PC Telecom PLC Lighting Electronic Life support (or Medical) Other:________________
Environmental considerations Temperature range: 0 – 40 degree C standard
Other:_______
Space considerations? Yes No If Yes, What? _____________________
Vibration (earthquake): Yes No What standard:____________
Enclosure rating: NEMA IP
Other:___________
Peripheral equipment:
Remote Panel External Bypass Redundancy (3 phase only) Extended Warranty 24/7 Warranty On‐site Warranty Replacement Warranty Extended Battery Warranty Ethernet Communication (3 phase standard) Relay communication (3 phase standard)
UPS Specification Questions
Input Voltage (Circle one, or fill in other) 1 Phase 3 Phase 2 Wire 3 Wire 4 Wire 120Vac 208Vac 120/208Vac 240Vac 480Vac 277/480Vac 208Vac 600Vac 347/600Vac
Other:
Output Voltage (Circle one, or fill in other)
1 Phase 3 Phase
2 Wire 3 Wire 4 Wire
120Vac 120/240Vac 120/208Vac
240Vac 277/480Vac
208Vac 347/600Vac
Other: