lz series - aaon · lz series chillers and outdoor mechanical rooms installation, operation, &...

104
LZ Series Chillers and Outdoor Mechanical Rooms Installation, Operation, & Maintenance FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death or property damage. Be sure to read and understand the installation, operation and service instructions in this manual. Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage. A copy of this IOM should be kept with the unit. Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your building. Leave the building immediately. Immediately call you gas supplier from a phone remote from the building. Follow the gas supplier’s instructions. If you cannot reach your gas supplier call the fire department. Startup and service must be performed by a Factory Trained Service Technician. WARNING WARNING

Upload: others

Post on 21-May-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

  • LZ Series

    Chillers and Outdoor Mechanical Rooms

    Installation, Operation,

    & Maintenance

    FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death or property damage. Be sure to read and understand the installation, operation and service instructions in this manual. Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage. A copy of this IOM should be kept with the unit.

    Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your

    building. Leave the building immediately. Immediately call you gas supplier

    from a phone remote from the building. Follow the gas supplier’s instructions.

    If you cannot reach your gas supplier call the fire department.

    Startup and service must be performed by a Factory Trained Service Technician.

    WARNING WARNING

  • Table of Contents

    Codes and Ordinances ............................................................................................................... 19 Receiving Unit ........................................................................................................................... 19

    Storage ....................................................................................................................................... 20 Outdoor Mechanical Room ....................................................................................................... 20 Wiring Diagrams ....................................................................................................................... 21 General Maintenance ................................................................................................................. 21 Chiller Primary Pumping .......................................................................................................... 21

    Chiller Primary/Secondary Pumping ........................................................................................ 22 Condensing Boilers ................................................................................................................... 22 Makeup Water ........................................................................................................................... 23 Compression Tank ..................................................................................................................... 23

    Pressure Relief Valve ................................................................................................................ 24 Automatic Air Vent ................................................................................................................... 24

    Dual Pumps ............................................................................................................................... 24 Pressure Gauges and Thermometers ......................................................................................... 24

    Pipe Insulation ........................................................................................................................... 25 Outdoor Mechanical Room Placement...................................................................................... 25 Curb and Steel Mount Installation ............................................................................................ 25

    Lifting and Handling ................................................................................................................. 28 Vestibule Exhaust Fan ............................................................................................................... 29

    Water Connection ...................................................................................................................... 30 Temporary Drain – Evaporative Condenser .............................................................................. 31 Access Doors ............................................................................................................................. 31

    End Flashing Installation ........................................................................................................... 31

    Boiler Gas Connection .............................................................................................................. 32 Boiler Air Intake / Vent Piping ................................................................................................. 32 Sidewall Direct Boiler Venting ................................................................................................. 35

    Vertical Direct Boiler Venting .................................................................................................. 37 Boiler Condensate Drain ........................................................................................................... 41

    Split Unit Assembly .................................................................................................................. 41 Unit Mounting Isolation ............................................................................................................ 41

    Low Ambient Operation ............................................................................................................ 41 Electrical .................................................................................................................................... 42 Variable Speed Compressors .................................................................................................... 44 Condenser Fan Pitch Adjustment .............................................................................................. 47 Boiler System Startup ................................................................................................................ 50

    Boiler Sequence of Operations .................................................................................................. 51 General ...................................................................................................................................... 51

    Refrigerant Suction Line Filter ................................................................................................. 51 Suction Filter Removal Instructions .......................................................................................... 52 Refrigerant Liquid Line Filter Driers ........................................................................................ 52 Evaporator/Heat Exchangers ..................................................................................................... 53 Adjusting Refrigerant Charge ................................................................................................... 53 Lubrication ................................................................................................................................ 57

  • 4

    Air-Cooled Condenser ............................................................................................................... 57 E-Coated Coil Cleaning ............................................................................................................ 57 Microchannel Coil Cleaning ..................................................................................................... 59 Evaporative-Condensed Chiller ................................................................................................ 61

    Severe Operating Conditions Service .................................................................................... 62 Safety ..................................................................................................................................... 62 Performance ........................................................................................................................... 62 Warranties .............................................................................................................................. 63 Condenser Tube Inspection ................................................................................................... 63

    Freeze Protection ................................................................................................................... 63 Recirculating Water System .................................................................................................. 63 Startup .................................................................................................................................... 63 Cleanliness ............................................................................................................................. 63

    Storage ................................................................................................................................... 63 Pump Operation ..................................................................................................................... 64

    Running.................................................................................................................................. 64 Condenser Fan Motors ........................................................................................................... 64

    Water Make Up Valve ........................................................................................................... 64 Water Treatment System ....................................................................................................... 65 Sequence of Operation for LZ Series units without Diagnostics .......................................... 65

    Sequence of Operation for LZ Series units with Diagnostics ................................................ 66 Pump Maintenance ................................................................................................................ 67

    Fan Motor Maintenance ......................................................................................................... 67 Access Doors ......................................................................................................................... 67 Bearings - Lubrication ........................................................................................................... 68

    Recommended Monthly Inspection ....................................................................................... 68

    Mist Eliminators .................................................................................................................... 68 Air Inlet .................................................................................................................................. 68 Stainless Steel Base Pan ........................................................................................................ 68

    Propeller Fans and Motors ..................................................................................................... 68 Recommended Annual Inspection ......................................................................................... 68

    Cleaning ................................................................................................................................. 68 Water Quality ......................................................................................................................... 69

    Mechanical Cleaning ............................................................................................................. 70 Service ....................................................................................................................................... 70 Replacement Parts ..................................................................................................................... 70 Water Pressure Reducing Valve ................................................................................................ 71 Water Pressure Relief Valve ..................................................................................................... 73

    Automatic Air Vent Valves ....................................................................................................... 73 Pumps - Installation and Operating Instructions ....................................................................... 75

    Pump Piping - General .............................................................................................................. 77 Pump Operation ......................................................................................................................... 77 General Care .............................................................................................................................. 78 Dual Pump Specific Information ............................................................................................... 80 Horizontal and Vertical Expansion Tanks ................................................................................ 85 Suction Guides .......................................................................................................................... 86

  • 5

    Glycol Auto Fill Unit ................................................................................................................ 87 Flo-Trex Combination Valve .................................................................................................... 89

    Index of Tables and Figures

    Tables:

    Table 1 - Service Clearances......................................................................................................... 25 Table 2 - Unit Gas Pipe Information, Feature B4 = A-J ............................................................... 33

    Table 3 - Unit Gas Pipe Information, Feature B4 = K-N.............................................................. 34 Table 4- Tandem Circuited Variable Speed Compressor VFD Frequency Range ....................... 44 Table 5 - Air-Cooled Condenser Fan Pitch................................................................................... 47 Table 6 - Evaporative-Condensed Chiller Fan Pitch .................................................................... 47

    Table 7 - Condenser Fan Pin Location (Bushing Mount) ............................................................. 49 Table 8 - Condenser Fan Pin Location (Rotation Direction) ........................................................ 49

    Table 9 - Fan Assembly Bushing Torque Specifications.............................................................. 50 Table 10 - Filter Drier Maximum Pressure Drop.......................................................................... 52

    Table 11 - Acceptable Refrigeration Circuit Values..................................................................... 54 Table 12 - R-134a Refrigerant Temperature-Pressure Chart ........................................................ 55 Table 13 - R-410A Refrigerant Temperature-Pressure Chart ....................................................... 56

    Table 14 - Recirculating Water Quality Guidelines ..................................................................... 69

    Figures:

    Figure 1 - Backflow Preventer ...................................................................................................... 23

    Figure 2 - Pressure Relief Valve ................................................................................................... 24

    Figure 3 - Curb Mounting with Dimensions ................................................................................. 26 Figure 4 - Curb End Detail............................................................................................................ 26 Figure 5 - Steel Mounting Rail with Dimensions ......................................................................... 26

    Figure 6 - Concrete Pad Mounting with Dimensions ................................................................... 27 Figure 7 - LZ Base ........................................................................................................................ 27

    Figure 8 - Lifting Points ................................................................................................................ 28 Figure 9 - LZ Series Example Lifting Detail ................................................................................ 29

    Figure 10 - Vestibule Exhaust Fan................................................................................................ 29 Figure 11 - Water Pipe Flashing Installation ................................................................................ 30 Figure 12 – Temporary Drain Components .................................................................................. 31 Figure 14 - Factory Supplied End Flashings................................................................................. 31 Figure 15 - Sidewall Vent Shipping Cover Removal ................................................................... 35

    Figure 16 - Sidewall Vent Plate Installation ................................................................................. 35 Figure 17 - Typical Air Intake Piping ........................................................................................... 35

    Figure 18 - Typical Flue Vent Piping ........................................................................................... 36 Figure 19 - Sidewall Vent Base .................................................................................................... 37 Figure 20 - Sidewall Vent Cap...................................................................................................... 37 Figure 21 - Roof Air Intake and Vent Piping Shipping Covers .................................................... 37 Figure 22 - Typical Vertical Air Intake Piping ............................................................................. 38 Figure 23 - Correct Joint Connection............................................................................................ 39

  • 6

    Figure 24 - Incorrect Joint Connection ......................................................................................... 39 Figure 25 - Typical Vertical Vent Piping ..................................................................................... 40 Figure 26 - Vertical Termination of Air Intake and Vent Piping ................................................. 40 Figure 27 - Evaporative-Condensed Chiller Section Layout ........................................................ 45

    Figure 28 - Fan with the HUB on the top and RET on the bottom. .............................................. 48 Figure 29 - Bushing Mount Location............................................................................................ 48 Figure 30 - RET with Pin in Groove 4 .......................................................................................... 48 Figure 31 - Fan HUB and RET Castings ...................................................................................... 48 Figure 32 - Pitch Insert ................................................................................................................. 49

    Figure 33 - Replaceable Core Filter Driers ................................................................................... 52 Figure 34 - Proper Unit Location .................................................................................................. 62 Figure 35 - Improper Unit Locations ............................................................................................ 62 Figure 36 - Water Makeup Valve ................................................................................................. 65

    Figure 36 – Evaporative condenser access door ........................................................................... 67

    V45100 · Rev. A · 190308

  • 7

    AAON LZ Series Features and Options Introduction

    Energy Efficiency

    • Staged or Variable Speed R-410A Scroll Compressors

    • Oil-Free Magnetic Bearing R-134a Turbocor Centrifugal Compressors

    • High Efficiency Air-Cooled Microchannel Condenser Coils

    • AAON Evaporative-Condensed Chiller • VFD Controlled Pumping Packages • VFD Controlled Condenser Fan Head

    Pressure Control

    • ECM Low Sound Condenser Fan Head Pressure Control

    • 98% Thermal Efficiency Boilers • Waterside Economizers • Factory Installed EXVs

    Outdoor Mechanical Room • Chilled Water Applications up to

    540 tons

    • Hot Water Applications up to 6,000 MBH

    • Lighted Walk-In Service Vestibule • Factory Engineered Primary or

    Primary/Secondary Pumping Packages

    • Factory Installed Three Chemical Water Treatment

    • Factory Installed Compression Tank • Brazed Plate or Shell and Tube

    Evaporators

    • Factory Installed Option Boxes for Field Installed Accessories

    Safety • Phase and Brownout Protection • Single Point Non-Fused Disconnect

    Power Switch

    • Factory Installed Refrigerant Leak Detector

    • Water Piping Air Separator • Waterside Thermometer and Pressure

    Gauge

    Installation and Maintenance • Double Wall Rigid Polyurethane Foam

    Injected Panel Construction

    • Lighted Walk-In Service Vestibule • Access Doors with Full Length Stainless

    Steel Piano Hinges

    • Zinc Cast Lockable Handles • Factory Installed Convenience Outlet • Service Vestibule Heating and Cooling • Motorized Service Vestibule Fresh Air • Controls Diagnostics • Touchscreen Computer Controls

    Interface

    • Evaporative-Condensed Chiller De-Superheater

    • Evaporative-Condensed Chiller Sump Heaters

    • Liquid Line Sight Glass • Compressor Isolation Valves • Auto Glycol Feeder • Color-Coded Wiring Diagrams

    System Integration • Complete System with AAON Chilled

    Water Air Handling Units

    • BMS Connectivity • Grooved End Water Piping Connections • Custom Color Paint Options

    Environmentally Friendly • R-410A or R-134a Refrigerant

    Extended Life • Optional 5 Year Compressor Warranty • Condenser Coil Guards • 2,500 Hour Salt Spray Tested Exterior

    Corrosion Protection

    • 6,000 Hour Salt Spray Tested Polymer E-Coated Condenser Coils

  • 8

    Safety

    Attention should be paid to the following statements:

    NOTE - Notes are intended to clarify the unit installation, operation and maintenance.

    CAUTION - Caution statements are given to prevent actions that may result in equipment

    damage, property damage, or personal injury.

    WARNING - Warning statements are given to prevent actions that could result in

    equipment damage, property damage, personal injury or death.

    DANGER - Danger statements are given to prevent actions that will result in equipment

    damage, property damage, severe personal injury or death.

    ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. Before servicing, disconnect all

    electrical power to the unit. More than one disconnect may be provided.

    When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.

    Verify proper operation after servicing. Secure all doors with key-lock or nut and bolt.

    WARNING

    QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.

    WARNING

    WHAT TO DO IF YOU SMELL GAS Do not try to turn on unit. Shut off main gas supply. Do not touch any electric switch. Do not use any phone in the

    building. Never test for gas leaks with an

    open flame. Use a gas detection soap solution

    and check all gas connections and shut off valves.

    CAUTION

  • 9

    FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance.

    WARNING

    Electric shock hazard. Before servicing, shut off all electrical power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.

    WARNING

    During installation, testing, servicing, and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks. Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.

    WARNING

    GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements.

    WARNING

    VARIABLE FREQUENCY DRIVES

    Do not leave VFDs unattended in hand mode or manual bypass. Damage to personnel or equipment can occur if left unattended. When in hand mode or manual bypass mode VFDs will not respond to controls or alarms.

    WARNING

    Electric motor over-current protection and overload protection may be a function of the Variable Frequency Drive to which the motors are wired. Never defeat the VFD motor overload feature. The overload ampere setting must not exceed 115% of the electric motors FLA rating as shown on the motor nameplate.

    CAUTION

  • 10

    UNIT HANDLING To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.

    WARNING

    Always use a pressure regulator, valves and gauges to control incoming pressures when pressure testing a system. Excessive pressure may cause line ruptures, equipment damage or an explosion which may result in injury or death.

    WARNING

    Door compartments containing hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latches are shipped with nut and bolts requiring tooled access. If you do not replace the shipping hardware with a pad lock always re-install the nut & bolt after closing the door.

    CAUTION

    Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death.

    WARNING

    PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils that are used in R-410A and other refrigerant systems will cause stress cracking of PVC or CPVC piping, even if only present in trace amounts. This will result in complete piping system failure.

    CAUTION

    COMPRESSOR CYCLING

    3 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 3 minutes.

    3 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 3 minutes. The cycle rate must not exceed 6 starts per hour.

    WARNING

    To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than 8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.

    CAUTION

  • 11

    1. Startup and service must be performed by a Factory Trained Service Technician.

    2. The unit is for outdoor use only. See General Information section for more

    information.

    3. Use only with type of the gas approved for the boiler. Refer to the boiler rating

    plate.

    4. Provide adequate combustion ventilation air to the boiler.

    5. Every unit has a unique equipment nameplate with electrical, operational,

    and unit clearance specifications. Always

    refer to the unit nameplate for ratings

    unique to the model you have purchased.

    6. READ THE ENTIRE INSTALLATION, OPERATION AND MAINTENANCE

    MANUAL. OTHER IMPORTANT

    SAFETY PRECAUTIONS ARE

    PROVIDED THROUGHOUT THIS

    MANUAL.

    7. Keep this manual and all literature safeguarded near or on the unit.

    Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used with R-410A and R134a refrigeration systems. Refer to the compressor label for the proper compressor lubricant type.

    CAUTION

    Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.

    CAUTION

    Rotation must be checked on ALL MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection.

    CAUTION

    Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturer’s usage instructions. Failure to follow instructions may result in equipment damage, injury or death.

    WARNING

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJ

    RE

    V

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26C

    26

    D

    26E

    26

    F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    12

    LZ Series Feature String Nomenclature

    MODEL OPTIONS Series and Generation

    LZ

    Major Revision

    A

    Unit Size

    Air-Cooled Evaporative-Condensed

    045 = 45 ton Capacity 053 = 53 ton Capacity

    055 = 55 ton Capacity 061 = 61 ton Capacity

    060 = 60 ton Capacity 069 = 69 ton Capacity

    075 = 75 ton Capacity 078 = 78 ton Capacity

    090 = 90 ton Capacity 090 = 90 ton Capacity

    095 = 95 ton Capacity 106 = 106 ton Capacity

    105 = 105 ton Capacity 120 = 120 ton Capacity

    120 = 120 ton Capacity 121 = 121 ton Capacity

    140 = 140 ton Capacity 134 = 134 ton Capacity

    170 = 170 ton Capacity 150 = 150 ton Capacity

    181 = 181 ton Capacity 161 = 161 ton Capacity

    200 = 200 ton Capacity 180 = 180 ton Capacity

    181 = 181 ton Capacity

    193 = 193 ton Capacity

    239 = 239 ton Capacity

    240 = 240 ton Capacity

    274 = 274 ton Capacity

    300 = 300 ton Capacity

    319 = 319 ton Capacity

    356 = 356 ton Capacity

    360 = 360 ton Capacity

    401 = 401 ton Capacity

    441 = 441 ton Capacity

    450 = 450 ton Capacity

    478 = 478 ton Capacity

    540 = 540 ton Capacity

    Series - Scroll Compressor

    Air-Cooled

    A = 45-60 ton units

    B = 75 ton unit

    C = 95-140 ton units

    D = 170-200 ton units

    Evaporative-Condensed

    A = 53-69 ton units

    B = 78 ton unit

    C = 106-161 ton units

    D = 193-239 ton units

    E = 274-319 ton units

    F = 356-401 ton units

    G = 441-478 ton units

    Series - Turbocor Compressor

    Air-Cooled

    H = 90-120 ton units

    K = 181 ton unit

    Evaporative-Condensed

    H = 90 & 120 ton units

    J = 150 & 180 ton units

    K = 181 ton unit

    L = 240 ton unit

    M = 300 & 360 ton units

    N = 450 & 540 ton units

    Minor Revision

    A

    Voltage

    2 = 230V/3Φ/60Hz

    3 = 460V/3Φ/60Hz

    4 = 575V/3Φ/60Hz

    8 = 208V/3Φ/60Hz

    A1: Compressor Style

    F = R-410A Tandem VFD Compatible Scroll

    Compressor

    H = R-134a Turbocor Centrifugal Compressor

    J = R-134a Turbocor Centrifugal Compressor with

    Economizer

    A2: Condenser Style

    A = Air-Cooled Microchannel Condenser

    H = Evaporative-Condensed

    A3: Evaporator Configuration

    A = Brazed Plate

    B = Oversized Brazed Plate

    C = Shell & Tube

    D = Oversized Shell & Tube

    A4: Coating

    0 = Standard

    E = Polymer E-Coated Condenser Coil

    A5: Staging

    0 = Staged On/Off Compressors

    E = All Circuits Variable Capacity Compressors

    G = Half Circuits Variable Capacity Compressors

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJR

    EV

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26C

    26

    D

    26E

    26

    F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    13

    B1: Type

    0 = No Boilers

    B2: Boiler Quantity

    0 = No Boilers

    B3: Type and Pipe Size

    0 = No Boilers

    B4: Boiler Capacity

    0 = No Boilers

    UNIT FEATURE OPTIONS 1: Unit Orientation

    E = Walk-in Vestibule Left Access Left Water

    Connections

    F = Walk-in Vestibule Left Access Right Water

    Connections

    G = Walk-in Vestibule Left Access Bottom Water

    Connections

    J = Walk-in Vestibule Right Access Left Water

    Connections

    K = Walk-in Vestibule Right Access Right Water

    Connections

    L = Walk-in Vestibule Right Access Bottom Water

    Connections

    2: Pumping Style

    0 = No Pumps

    A = Const. Primary Pumping System Small Pipe Size

    B = Const. Primary Pumping System Large Pipe Size

    C = Var. Primary Pumping System Small Pipe Size

    D = Var. Primary Pumping System Large Pipe Size

    E = Primary/Secondary Pumping System Small Pipe

    Size

    F = Primary/Secondary Pumping System Large Pipe

    Size

    3A: Building Pump Configuration

    0 = No Building Pumps

    A = 1 Pump + High Eff Motor

    B = 1 Dual Pump + High Eff Motors

    C = 2 Single Pumps + High Eff Motors

    D = 1 Pump + VFD + High Eff Motor

    E = 1 Dual Pump + 2 VFD's + High Eff Motors

    F = 2 Single Pumps + 2 VFD’s + High Eff Motors

    K = 1 Pump + Field Installed VFD + High Eff Motor

    L = 1 Dual Pump + 2 Field Installed VFD's + High

    Eff Motors

    M = 2 Single Pumps + 2 Field Installed VFD’s +

    High Eff Motors

    3B: Building Pump Series and RPM

    0 = No Building Pumps

    A = 4360 (1,170 nominal rpm)

    B = 4360 (1,760 nominal rpm)

    C = 4360 (3,520 nominal rpm)

    D = 4380 (1,170 nominal rpm)

    E = 4380 (1,760 nominal rpm)

    F = 4380 (3,520 nominal rpm)

    G = 4300 (1,170 nominal rpm)

    H = 4300 (1,760 nominal rpm)

    J = 4300 (3,520 nominal rpm)

    K = 4382 (1,170 nominal rpm)

    L = 4382 (1,760 nominal rpm)

    M = 4382 (3,520 nominal rpm)

    N = 4302 (1,170 nominal rpm)

    P = 4302 (1,760 nominal rpm)

    Q = 4302 (3,520 nominal rpm)

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJR

    EV

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26C

    26

    D

    26E

    26

    F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    14

    3C: Pump Size

    0 = No Building Pumps

    A = 1.5B

    B = 2B

    C = 2D

    D = 3D

    E = 1.5x1.5x6

    F = 2x2x6

    G = 3x3x6

    H = 4x4x6

    J = 6x6x6

    K = 1.5x1.5x8

    L = 2x2x8

    M = 3x3x8

    N = 4x4x8

    P = 5x5x8

    Q = 6x6x8

    R = 8x8x8

    S = 2x2x10

    T = 3x3x10

    U = 4x4x10

    V = 6x6x10

    W = 8x8x10

    Y = 4x4x11.5

    Z = 5x5x11.5

    1 = 6x6x11.5

    2 = 8x8x11.5

    3 = 4x4x13

    4 = 6x6x13

    5 = 8x8x13

    3D: Building Pump Motor Size

    0 = No Building Pumps

    A = 0.5 hp

    B = 0.75 hp

    C = 1 hp

    D = 1.5 hp

    E = 2 hp

    F = 3 hp

    G = 5 hp

    H = 7.5 hp

    J = 10 hp

    K = 15 hp

    L = 20 hp

    M = 25 hp

    3D: Building Pump Motor Size Continued

    N = 30 hp

    P = 40 hp

    Q = 50 hp

    R = 60 hp

    S = 75 hp

    4A: Recirculating Pump Configuration

    0 = No Recirculating Pumps

    A = 1 Pump + High Eff Motor

    B = 1 Dual Pump + High Eff Motors

    C = 2 Single Pumps + High Eff Motors

    4B: Recirculation Pump Series & RPM

    0 = No Recirculating Pumps

    A = 4360 (1,170 nominal rpm)

    B = 4360 (1,760 nominal rpm)

    C = 4360 (3,520 nominal rpm)

    D = 4380 (1,170 nominal rpm)

    E = 4380 (1,760 nominal rpm)

    F = 4380 (3,520 nominal rpm)

    G = 4300 (1,170 nominal rpm)

    H = 4300 (1,760 nominal rpm)

    J = 4300 (3,520 nominal rpm)

    K = 4382 (1,170 nominal rpm)

    L = 4382 (1,760 nominal rpm)

    M = 4382 (3,520 nominal rpm)

    N = 4302 (1,170 nominal rpm)

    P = 4302 (1,760 nominal rpm)

    Q = 4302 (3,520 nominal rpm)

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJR

    EV

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26C

    26

    D

    26E

    26

    F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    15

    4C: Recirculating Pump Size

    0 = No Recirculating Pumps

    A = 1.5B

    B = 2B

    C = 2D

    D = 3D

    E = 1.5x1.5x6

    F = 2x2x6

    G = 3x3x6

    H = 4x4x6

    J = 6x6x6

    K = 1.5x1.5x8

    L = 2x2x8

    M = 3x3x8

    N = 4x4x8

    P = 5x5x8

    Q = 6x6x8

    R = 8x8x8

    S = 2x2x10

    T = 3x3x10

    U = 4x4x10

    V = 6x6x10

    W = 8x8x10

    Y = 4x4x11.5

    Z = 5x5x11.5

    1 = 6x6x11.5

    2 = 8x8x11.5

    3 = 4x4x13

    4 = 6x6x13

    5 = 8x8x13

    4D: Recirculating Pump Motor Size

    0 = No Recirculating Pumps

    A = 0.5 hp

    B = 0.75 hp

    C = 1 hp

    D = 1.5 hp

    E = 2 hp

    F = 3 hp

    G = 5 hp

    H = 7.5 hp

    J = 10 hp

    K = 15 hp

    L = 20 hp

    M = 25 hp

    4D: Recirculating Pump Motor Size Continued

    N = 30 hp

    P = 40 hp

    Q = 50 hp

    R = 60 hp

    S = 75 hp

    5A: Boiler Building Pump Configuration

    0 = No Boiler Pumps

    5B: Boiler Building Pump Series & RPM

    0 = No Boiler Pumps

    5C: Boiler Building Pump Size

    0 = No Boiler Pumps

    5D: Boiler Building Pump Motor Size

    0 = No Boiler Pumps

    6: Refrigeration Options

    0 = None

    A = Hot gas bypass on non-variable capacity

    compressor circuits

    B = Hot gas bypass on all circuits

    7: Refrigeration Accessories

    0 = Standard

    A = Sight Glass

    B = Compressor Isolation Valves

    C = Option A + B

    8A: Unit Disconnect Type

    0 = Standard Single Point Power Block

    A = Single Point Power Non-fused Disconnect

    8B: Disconnect 1 Size

    0 = Power Block

    N = 100 amps

    R = 150 amps

    U = 225 amps

    V = 250 amps

    Z = 400 amps

    3 = 600 amps

    5 = 800 amps

    7 = 1200 amps

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJR

    EV

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10

    C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26C

    26

    D

    26E

    26

    F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    16

    8C: Blank

    0 = Standard

    9: Accessories

    0 = None

    B = Phase & Brown Out Protection

    10A: Unit Control Sequence

    0 = Standard AAON Controls

    10B: Unit Control Supplier

    E = MCS Controls

    10C: Control Supplier Options

    0 = None

    A = Touchscreen Computer Interface

    C = Modem

    G = Option A + C

    10D: BMS Connection & Diagnostics

    0 = None

    A = BACnet IP

    B = BACnet MSTP

    C = Modbus IP

    D = Modbus RTU

    E = LonTalk

    H = No BMS Connection with Diagnostics

    J = BACnet IP with Diagnostics

    K = BACnet MSTP with Diagnostics

    L = Modbus IP with Diagnostics

    M = Modbus RTU with Diagnostics

    N = LonTalk with Diagnostics

    11: Cabinet Options

    0 = None

    B = Access Door Windows

    12: Vestibule Accessories

    0 = None

    A = Refrigerant Leak Detector

    B = Motorized Service Vestibule Fresh Air

    C = Vestibule Heating (Electric)

    D = Vestibule Cooling (Fan/Coil)

    F = Option A + B

    G = Option A + C

    12: Vestibule Accessories Continued

    H = Option A + D

    K = Option B + C

    L = Option B + D

    N = Option C + D

    R = Option A + B + C

    S = Option A + B + D

    U = Option A + C + D

    Y = Option B + C + D

    3 = Option A + B + C + D

    13: Maintenance Accessories

    0 = None

    A = 115VAC Convenience Outlet Factory Wired

    B = 115VAC Convenience Outlet Field Wired

    C = Service Lights

    F = Option A + C

    J = Option B + C

    14: Option Boxes

    0 = None

    A = 2 ft Option Box

    B = 4 ft Option Box

    C = 6 ft Option Box

    D = 8 ft Option Box

    F = 10 ft Option Box

    G = 12 ft Option Box

    15: Code Options

    0 = Standard ETL U.S.A. Listing

    A = Chicago Code

    B = ETL U.S.A. + Canada Listing

    16: Shipping Splits

    0 = One Piece Unit

    A = Two Piece Unit

    17: Air-Cooled Condenser Accessories

    0 = None (No Air-Cooled Condenser)

    H = Cond Coil Guards + 3Φ Condenser Fan Motor +

    Fan Cycling (35°F) J = Cond Coil Guards + 3Φ Condenser Fan Motor +

    VFD Condenser Fan Head Pressure Control (0°F) S = Cond. Coil Guards + Low Sound ECM Cond.

    Fans – Head Pressure Control (0°F)

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJR

    EV

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26

    C

    26

    D

    26E

    26F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    17

    18: Evaporative-Condensed Chiller Accessories

    0 = None (No Evaporative-Condenser)

    A = No Sump Heat

    B = Sump Heaters

    19: Blank

    0 = None

    20: Blank

    0 = None

    21: Chiller Compression Tank

    0 = None

    A = AX-15V

    B = AX-20V

    C = AX-40V

    D = AX-60V

    E = AX-80V

    F = AX-100V

    G = AX-120V

    H = AX-180V

    J = AX-200V

    K = AX-240V

    L = AX-260V

    M = AX-280V

    22: Boiler Compression Tank

    0 = None

    23: Blank

    0 = Standard

    24: Chiller Accessories

    0 = None

    A = Glycol chiller

    B = Air Separator

    C = Thermometers & Pressure Gauges

    D = Chemical Pot Feeder

    E = Auto Glycol Feeder

    F = Option A + B

    G = Option A + C

    H = Option A + D

    J = Option A + E

    K = Option B + C

    L = Option B + D

    24: Chiller Accessories Continued

    M = Option B + E

    N = Option C + D

    P = Option C + E

    Q = Option D + E

    R = Option A + B + C

    S = Option A + B + D

    T = Option A + B + E

    U = Option A + C + D

    V = Option A + C + E

    W = Option A + D + E

    Y = Option B + C + D

    Z = Option B + C + E

    1 = Option B + D + E

    2 = Option C + D + E

    3 = Option A + B + C + D

    4 = Option A + B + C + E

    5 = Option A + B + D + E

    6 = Option A + C + D + E

    7 = Option B + C + D + E

    8 = Option A + B + C + D + E

    25: Blank

    0 = Standard

    26A: Blank

    0 = Standard

    26B: Blank

    0 = Standard

    26C: Blank

    0 = Standard

    26D: Blank

    0 = Standard

    26E: Blank

    0 = Standard

    26F: Blank

    0 = Standard

  • LZ Series Feature String Nomenclature

    Model Options : Unit Feature Options

    GE

    N

    MJR

    EV

    SIZ

    E

    SE

    RIE

    S

    MN

    RE

    V

    VL

    T

    A1

    A2

    A3

    A4

    A5

    B1

    B2

    B3

    B4

    1

    2

    3A

    3B

    3C

    3D

    4A

    4B

    4C

    4D

    5A

    5B

    5C

    5D

    6

    7

    8A

    8B

    8C

    LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B

    9

    10

    A

    10B

    10C

    10

    D

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    A

    26B

    26C

    26

    D

    26E

    26

    F

    27

    28

    29

    30

    31

    32

    33

    34

    35

    18

    27: Blank

    0 = Standard

    28: Blank

    0 = Standard

    29: Blank

    0 = Standard

    30: Blank

    0 = Standard

    31: Blank

    0 = Standard

    32: Blank

    0 = Standard

    33: Warranty

    0 = Standard Warranty

    D = Compressor Warranty Years 2-5

    34: Cabinet Material

    D = Galvanized Cabinet 6” Base Rail + Double Slope

    Roof

    H = Galvanized Cabinet 8” Base Rail + Double Slope

    Roof

    35: Paint & Special Pricing Authorizations

    B = Premium AAON Gray Paint Exterior

    E = Premium AAON Gray Paint Exterior + Shrink

    Wrap

    X = Special Pricing Authorization + Premium AAON

    Gray Paint Exterior

    1 = Option X + Shrink Wrap

    4 = Special Pricing Authorization + Special Exterior

    Paint Color

    7 = Option 4 + Shrink Wrap

  • 19

    General Information

    AAON LZ Series chiller outdoor mechanical

    rooms are complete self-contained liquid

    chilling units. They are assembled, wired,

    charged, and run-tested. Models are available

    for air-cooled and evaporative-condensed

    applications. Chiller primary pumping

    packages, primary/secondary pumping

    packages, and boilers with pumping package

    are available as optional features.

    Codes and Ordinances

    LZ Series units have been tested and

    certified, by TL, in accordance with UL

    Safety Standard 1995/CSA C22.2 No. 236.

    System should be sized in accordance with

    the American Society of Heating,

    Refrigeration and Air Conditioning

    Engineers Handbook.

    Installation of LZ Series units must conform

    to the ICC standards of the International

    Mechanical Code, the International Building

    Code, and local building, plumbing and

    waste water codes. All appliances must be

    electrically grounded in accordance with

    local codes, or in the absence of local codes,

    the current National Electric Code,

    ANSI/NFPA 70 or the current Canadian

    Electrical Code CSA C22.1.

    Receiving Unit

    When received, the unit should be checked

    for damage that might have occurred in

    transit. If damage is found it should be noted

    on the carrier’s Freight Bill. A request for

    inspection by carrier’s agent should be made

    in writing at once. Nameplate should be

    checked to ensure the correct model sizes and

    voltages have been received to match the job

    requirements.

    Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician.

    WARNING

    RISK OF ELECTRICAL SHOCK

    Electrical raceways are located in the upper wall sections of the unit. DO NOT CUT OR DRILL into the wall sections of the unit that are within 12 inches of the roofline.

    WARNING

    The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling, or reclaiming must be followed.

    CAUTION

    Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment.

    WARNING

    Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty.

    WARNING

  • 20

    If repairs must be made to damaged goods,

    then the factory should be notified before any

    repair action is taken in order to protect the

    warranty. Certain equipment alteration,

    repair, and manipulation of equipment

    without the manufacturer’s consent may void

    the product warranty. Contact AAON

    Technical Support for assistance with

    handling damaged goods, repairs, and freight

    claims: (918) 382-6450.

    Storage

    If installation will not occur immediately

    following delivery, store equipment in a dry

    protected area away from construction traffic

    and in the proper orientation as marked on the

    packaging with all internal packaging in

    place. Leave all internal packaging in place

    and secure all loose-shipped items.

    Outdoor Mechanical Room

    Failure to observe the following instructions

    will result in premature failure of your

    system, and possible voiding of the warranty.

    Never turn off the main power supply to the

    unit, except for complete shutdown. When

    power is cut off from the unit, any

    compressors equipped with crankcase heaters

    cannot prevent refrigerant migration. This

    means the compressor will cool down, and

    liquid refrigerant may accumulate in the

    compressor. The compressor is designed to

    pump refrigerant gas and damage may occur

    when power is restored if liquid enters the

    compressor.

    COMPRESSOR CYCLING

    3 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 3 minutes.

    3 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 3 minutes. The cycle rate must not exceed 6 starts per hour.

    WARNING

    Before unit operation, the main power switch must be turned on for at least 24 hours for units equipped with crankcase heaters.

    CAUTION

    Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. All motors, to include and not be limited to pump motors and condenser fan motors, should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.

    CAUTION

  • 21

    Always control the system from the building

    management system, or control panel, never

    at the main power supply (except for

    emergency or for complete shutdown of the

    system).

    Scroll compressors must be on a minimum of

    3 minutes and off for a minimum of 3

    minutes. The cycle rate must be no more than

    6 starts per hour.

    The chiller is furnished with a flow switch

    installed on the outlet of each heat exchanger.

    This sensor must not be bypassed since it

    provides a signal to the unit controller that

    water flow is present in the heat exchanger

    and the unit can operate without the danger of

    freezing the liquid.

    Compressor life will be seriously shortened

    by reduced lubrication, and the pumping of

    excessive amounts of liquid oil and

    refrigerant.

    Wiring Diagrams

    A complete set of unit specific wiring

    diagrams in both ladder and point-to-point

    form are laminated in plastic and located

    inside the control vestibule.

    General Maintenance

    When the initial startup is made and on a

    periodic schedule during operation, it is

    necessary to perform routine service checks

    on the performance of the chiller and boiler.

    This includes reading and recording suction

    pressures and checking for normal sub-

    cooling and superheat. See the evaporative-

    condensed chiller and air-cooled chiller

    sections in this manual for specific details.

    Chiller Primary Pumping

    Primary pumping uses a single pump to move

    water (or glycol) through the chiller

    evaporator and back to the building. This

    pumping package provides a constant or

    variable flow of water to the building. The

    pump is activated whenever the chiller is

    given a run signal.

    Water enters the unit through the return water

    piping, and then travels through an air

    separator to remove any air that is entrapped

    in the water. Following this, the water flows

    through a suction guide with an integral

    strainer. The end of the suction guide is

    removable for strainer access. The strainer

    assembly is composed of two parts, the

    operational strainer and the startup strainer,

    (located inside the operational strainer)

    which is to be removed 24 hours after startup.

    Scroll compressors are directional and will be damaged by operation in the wrong direction. High pressure switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should be made at the unit power connection.

    CAUTION

    FIELD WIRED CONNECTIONS

    Some units may require field wired connections. Refer to the wiring diagrams contained within the unit to identify any components or controls requiring additional wiring in the field before placing the unit into service. All additional field wiring should be performed by a Factory Trained Service Technician.

    CAUTION

  • 22

    The pump is installed after the suction guide,

    and before a combination valve (Flo-Trex).

    This combination valve acts as an isolation

    valve, check valve, and flow balancing valve.

    The evaporator is placed after the

    combination valve in the water circuit, with a

    flow switch installed at its inlet and outlet.

    This flow switch closes when the velocity is

    above 0.7 feet per second. The closing flow

    switch signals the control system to indicate

    flow through the heat exchanger and allow

    cooling to activate as required to maintain the

    setpoint. The water exiting the chiller

    evaporator leaves the unit through the water

    out connection.

    Chiller Primary/Secondary Pumping

    Primary/secondary pumping option provides

    variable flow to the system. It consists of a

    constant flow pump for the chiller heat

    exchanger and a variable flow pump for the

    building. The controls package senses

    differential pressure across the pump with

    pressure transducers installed at the suction

    and discharge, and varies the speed of the

    pump using a VFD in order to maintain a

    given differential pressure across the pump.

    The primary/secondary pumping package is

    essentially composed of two piping loops

    coupled together. The primary loop has a

    constant flow rate in order to keep the chiller

    heat exchanger from freezing, and the

    secondary, variable flow loop, provides water

    to the building. The two loops are coupled via

    a water line that compensates for excess flow

    in either loop. As the flow in the secondary

    loop decreases below the flow in the primary

    loop, excess flow bypasses the building loop

    and circulates through the bypass water line.

    On the other hand, as the flow in the

    secondary loop increases above the flow in

    the primary loop, excess flow bypasses the

    chiller and circulates through the bypass

    water line.

    The secondary pump has its own suction

    guide, combination valve, and isolation

    valve, similar to the primary pump, with the

    addition of an air separator to remove any air

    that is entrapped in the water.

    Condensing Boilers

    AAON LZ chillers are available with factory

    installed condensing boilers. All boiler

    systems will include either fixed or variable

    speed building pumps. All boiler building

    pumps will be supplied with a suction guide

    with a strainer and triple duty valve. The

    suction guide contains both an operational

    strainer and a startup strainer. The startup

    strainer should be removed 24 hours after

    startup. The triple duty valve functions as an

    isolation valve, check valve, and flow

    balancing valve.

    The condensing boilers will be a water tube

    design or a fire tube design. In a water-tube

    boiler, the water flows through tubes with the

    combustion products heating from the

    outside. These boilers require a constant

    water flow and will be provided with a

    primary pump for each heat exchanger.

    Some boilers have two heat exchangers and

    will have two primary pumps. The primary

    pump is controlled by the boiler and will only

    come on when it has a call for heat. Water-

    tube boilers are provided with flow switches,

    which must make before the boiler can

    operate.

    In fire-tube boilers water flows through a

    tank, with the combustion products inside

    tubes. These boilers are capable of

    significant water flow turn-down and do not

    require individual primary pumps. A control

    valve, operate by the boiler controls, is

    provided with each boiler. A water flow

    switch is not required with fire-tube boilers.

    A low-level cutoff switch is used which will

    prevent the boiler from operating when there

    is not a sufficient water level present. Upon

  • 23

    initial startup, the boiler may have to be

    cycled several times to generate an adequate

    water level.

    Makeup Water

    A 3/4” FPT city make up water connection is

    provided to replace water that is lost from the

    system.

    Glycol units require a glycol feeder (optional

    factory installed or field installed) to replace

    fluid that is lost in the system. Water should

    not be directly added to glycol applications as

    this would dilute the glycol concentration and

    thereby increase the freezing temperature of

    the fluid.

    The makeup water connection is provided

    with a backflow preventer that has isolation

    valves on the inlet and outlet for service.

    Figure 1 shows the pressure drop versus flow

    rate for the backflow preventer.

    Figure 1 - Backflow Preventer

    There is a pressure-reducing valve after the

    backflow preventer. This valve reduces the

    city water pressure to maintain the operating

    pressure of the system. This valve is

    adjustable from 10-35 psig with a factory

    setting of 30 psig. The system pressure varies

    with the height of the system. The pressure-

    reducing valve setting should be set so that

    the pressure at the high point in the system is

    high enough to vent air from the system

    (usually 4 psig). There should be air vents at

    all parts in the system where air could be

    trapped. If the pressure is not high enough

    throughout the system, flashing could occur

    in the piping or the pump could cavitate.

    There is an isolation valve on the inlet and

    outlet of the pressure-reducing valve for

    service.

    The pressure reducing valve fills the system

    at a reduced rate. There is a bypass around the

    pressure reducing valve for the initial fill of

    the system to increase the initial fill speed.

    After the initial system fill, this valve should

    be closed.

    Compression Tank

    As the water temperature in the system

    increases, the volume that water displaces

    increases. In order to compensate for these

    expansion forces, a compression or

    expansion tank must be used. The factory

    installed tank option includes a pre-

    pressurized diaphragm compression tank that

    is preset for 12 psig.

    The factory pre-charge pressure may need to

    be field adjusted. The tank must be pre-

    charged to system design fill pressure before

    placing into operation. Remove the pipe plug

    covering the valve enclosure. Check and

    adjust the charge pressure by adding or

    releasing air.

    If the system has been filled, the tank must be

    isolated from the system and the tank emptied

    before charging. This ensures that all fluid

    has exited the diaphragm area and proper

    charging will occur.

    If the pre-charge adjustment is necessary, oil

    and water free compressed air or nitrogen gas

    may be used. Check the pre-charge using an

    accurate pressure gauge at the charging valve

    and adjust as required. Check air valve for

    leakage. If evident, replace the Schrader

    valve core. Do not depend on the valve cap to

    seal the leak. After making sure the air charge

  • 24

    is correct, replace the pipe plug over the

    charging valve for protection.

    Purge air from system before placing tank

    into operation. All models have system water

    contained behind the diaphragm.

    It is recommended that the pre-charge be

    checked annually to ensure proper system

    protection and long life for the vessel.

    Pressure Relief Valve

    Required pressure relief valve is installed in

    the unit. This valve is set at 125 psig. Figure

    2 shows inlet pressure versus capacity for this

    pressure relief valve. See appendix for

    additional information.

    Figure 2 - Pressure Relief Valve

    Automatic Air Vent

    There is an automatic air vent installed at the

    high point of the system inside the pumping

    package compartment. The air vent valve

    must be in the proper position for operation.

    Ensure that the small vent cap is loosened two

    turns from the closed position, allowing air to

    be vented from the system. It is advisable to

    leave the cap on to prevent impurities from

    entering the valve. See appendix for

    additional information.

    Dual Pumps

    When redundant pumping is required, factory

    installed dual pumps or two single pumps can

    be ordered. A dual pump is a pump with two

    independent motors and impellors in a single

    casing. This dual pump has a swing split-

    flapper valve in the discharge port to prevent

    liquid recirculation when only one pump is

    operating. Isolation valves in the casing allow

    one pump to be isolated and removed for

    service while the other pump is still

    operating.

    When redundant pumping is required with

    high flow rates, two independent pumps may

    be installed in parallel. Each pump will have

    its own suction guide/strainer, combination

    valve, and isolation valves.

    The controls package will activate the pump

    when the unit is given a run command. If the

    controls do not recognize flow in 60 seconds

    (factory default), the second pump will be

    activated and an alarm signal will be

    generated. If the second pump does not

    activate, the cooling will be locked out. See

    Appendix - Water Piping Component

    Information for additional information.

    Pressure Gauges and Thermometers

    Pressure gauges and thermometers are

    available as a factory installed option.

    Thermometers are installed on the inlet and

    outlet of the unit. One pressure gauge is

    installed at each pump. This pressure gauge

    is connected in three places to the water

    piping before the suction guide/strainer, after

    the suction guide and before the pump, and

    after the pump. There is also a valve at each

    of these points to isolate the pressure. To

    measure the pressure at any given point, open

    the valve at that point and close the other two

    valves. One gauge is used so that the

    calibration of the pressure gauge is irrelevant

    in the calculation of the differential pressure.

  • 25

    Pipe Insulation

    The water piping and components on units

    with pumping packages are not insulated at

    the factory. Insulation should be installed on

    the water piping after the system has been

    checked for leaks.

    Installation

    Outdoor Mechanical Room Placement

    The AAON LZ Series is designed for outdoor

    applications and can be mounted at ground

    level or on a rooftop. It must be placed on a

    level and solid foundation that has been

    prepared to support its weight.

    The placement relative to the building air

    intakes and other structures must be carefully

    selected. Be sure to observe the dimensions

    that are on the rating plate of the chiller for

    operational and service clearances.

    Table 1 - Service Clearances

    Location Unit Size

    45-540 tons

    Left 96”

    Right

    Compressor End 72”

    Chiller HXC End

    Top Unobstructed

    Condenser coils and fans must be free of any

    obstructions in order to start and operate

    properly with a correct amount of airflow.

    For proper unit operation, the immediate area

    around condenser(s) must remain free of

    debris that may be drawn in and obstruct

    airflow in the condensing section.

    Consideration must be given to obstruction

    caused by snow accumulation when placing

    the unit.

    Curb and Steel Mount Installation

    Make openings in the roof decking large

    enough to allow for water piping, electrical,

    and gas penetrations and workspace only. Do

    not make openings larger than necessary. Set

    the curb to coincide with the openings. Make

    sure curb is level.

    If an LZ with air-cooled condenser is

    installed on a curb, use a curb cap for the

    open area under the condenser section.

    Unit specific curb drawing is included with

    job submittal. See SMACNA Architectural

    Sheet Metal Manual for curb installation

    details.

    When installed at ground level, a one-piece

    concrete slab should be used with footings

    that extend below the frost line. Care must

    also be taken to protect the coil and fins from

    damage due to vandalism or other causes.

    If unit is elevated a field supplied catwalk is

    recommended to allow access to unit service

    doors.

    This unit ships with a curb gasket that is 1¼”

    wide and 1½” tall. It is recommended that this

    or another similar gasket be used between the

    curb and the unit to reduce vibration

    transmission from the unit to the building.

    All roofing work should be performed by competent roofing contractors to avoid any possible leakage.

    CAUTION

  • 26

    Figure 3 - Curb Mounting with Dimensions

    Figure 4 - Curb End Detail

    Figure 5 - Steel Mounting Rail with Dimensions

  • 27

    Figure 6 - Concrete Pad Mounting with Dimensions

    Figure 7 - LZ Base

  • 28

    Lifting and Handling

    If cables or chains are used to hoist the unit

    they must be the same length and care should

    be taken to prevent damage to the cabinet.

    See Figure 9 for additional information.

    Before lifting unit, be sure that all shipping

    material has been removed from unit. If the

    unit is an evaporative-condensed chiller,

    make sure the tank is empty before lifting.

    Secure hooks and cables at all lifting points/

    lugs provided on the unit.

    Hoist unit to a point directly above the curb

    or mounting rail. Be sure that the gasket

    material has been applied to the curb or

    mounting rail.

    Carefully lower and align unit with utility

    openings. Lower the unit until the unit skirt

    fits around the curb. Make sure the unit is

    properly seated on the curb and is level.

    Do not push, pull or lift the unit from

    anything other than its base.

    Figure 8 - Lifting Points

  • 29

    Figure 9 - LZ Series Example Lifting Detail

    Lifting slot locations are unit specific.

    Unit must be rigged at all marked lifting points.

    Vestibule Exhaust Fan

    Prior to unit operation of units with service

    vestibules the exhaust fan shipping support

    must be removed from the exterior of the unit

    The exhaust fan also includes a factory

    provide exterior rain hood which must be

    installed.

    Figure 10 - Vestibule Exhaust Fan

  • 30

    Water Connection

    Remove the shipping cover from the water

    connection cutout in the post. Connect the

    supply and return water lines. The standard

    water connection is grooved end pipe. The

    connection size is listed on the unit rating

    sheet along with the designed volumetric

    flow rate. The maximum operating pressure

    for AAON LZ Series unit is 125 psi. Install

    the flashing provided by AAON according to

    the steps in Figure 11. Finished water

    connection will be water tight.

    Figure 11 - Water Pipe Flashing Installation

    The chiller must be operated only with liquid flowing through the evaporators.

    WARNING

    Boilers must be operated only with liquid flowing through the boiler.

    WARNING

    PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings. This will result in complete piping system failure.

    CAUTION

    Installing Contractor is responsible for proper sealing of the water piping and electrical entries into the unit Failure to seal the entries may result in damage to the unit and property.

    CAUTION

  • 31

    Temporary Drain – Evaporative

    Condenser

    The evaporative condenser design allows

    rainwater to enter the sump tank during

    transportation. AAON provides a temporary

    drain system while the unit is in transit. The

    temporary drain consist of an adapter that

    will connect a hose from the sump drain to

    the base drain. This temporary drain must be

    replaced by permanent draining piping once

    on site.

    Figure 12 – Temporary Drain Components

    Once the unit is ready for the permanent

    draining, close the valve and remove the

    temporary draining system. The components

    that must be removed are those with number

    callouts in Figure 12. The drain connection

    for the permanent draining is 2” FPT.

    Access Doors

    Lockable access doors are provided to the

    compressor and control compartment. A

    light switch is provided on the wall of the

    compressor and control compartment.

    A separate access door is also provided to the

    evaporator and pumping package

    compartment. See Figure 36 for information

    on leak checking these doors.

    End Flashing Installation

    On all LZ Series units the cabinet width will

    overhang the shipping trailer on each side.

    In order to secure and protect the unit during

    transit the sheet metal end flashings have

    been removed from the unit. The slot created

    at the base of each end of the unit allows the

    unit to set firmly on the trailer deck.

    Sheet metal flashings are shipped loose with

    the unit and once the unit is set into place the

    flashings must be installed on each end of the

    unit to complete the finished seal at the base.

    The flashings are unit specific and designed

    to cover the slot at each end of the unit to

    prevent water run-off into the curb.

    Failure to attach and seal the end of unit with

    the flashings may result in water leakage into

    the curb.

    Figure 13 - Factory Supplied End Flashings

    In order to prevent water leakage into the roof curb, the factory provided sheet metal flashings MUST BE attached to the unit base to cover the shipping slots at both ends of the unit.

    CAUTION

  • 32

    Boiler Gas Connection Before making gas connection, make sure the

    boiler is being supplied with the type of fuel

    shown on the boiler nameplate.

    Table 2 and Table 3 show the gas connection

    size and type (NPT or flanged) provided

    along with the required inlet gas pressure for

    the unit. Refer to feature B on the LZ Series

    unit feature string to determine which line of

    the table to use. For example, a unit with

    feature B = A3CC will have a 2” NPT gas

    connection and require an inlet gas pressure

    in the range of 6-14” W.C.

    Use only pipe sealing compound that is

    compatible with propane gases on all

    threaded connections. Apply sparingly only

    to the male threads of the pipe joints so that

    the pipe sealing compound does not block

    any gas flow.

    Before being placed in operation, the boiler

    and all gas piping connections must be

    checked for leaks. The boiler must be

    disconnected from the gas supply piping

    system during any pressure testing of the

    system at pressures in excess of .5 psig (14”

    W.C.). The boiler must be isolated from the

    gas supply piping system by closing the

    manual shutoff valve during any pressure

    testing of the system at pressures equal to or

    less than .5 psig (14” W.C.).

    Some leak test solutions, including soap and

    water, may cause corrosion. These solutions

    should be rinsed off with water after testing.

    Boiler Air Intake / Vent Piping Each boiler requires the installation of air

    intake and vent piping. This piping has been

    removed for shipping purposes. All piping

    must be reinstalled according to the

    instructions provided in this section prior to

    boiler operation.

    All boilers must be vented and supplied with

    combustion and ventilation air as described

    in this section and in the Lochinvar

    Installation & Operation Manual included

    with the boiler. Ensure the vent and air

    piping and combustion air supply comply

    with instructions regarding vent system, air

    system, and combustion air quality.

    Inspect finished vent and air intake piping

    thoroughly to ensure all are airtight and

    comply with the instructions provided and

    with all requirements of applicable codes.

    Failure to apply sealing compound as detailed can result in property damage, personal injury, or death.

    WARNING

    DO NOT use matches, candles, open flames, or other ignition sources to check for gas leaks. Use only approved leak detection methods. Failure to comply with this warning can result in property damage, personal injury, or death.

    WARNING

    Failure to provide a properly installed vent and air system can result in property damage, personal injury, or death.

    WARNING

  • 33

    Table 2 - Unit Gas Pipe Information, Feature B4 = A-J

    Heating Feature Boiler

    Inlet Gas

    Pressure

    Gas Header

    B1 B2 B3 B4 Size Qty

    Input

    Capacity

    (CFH)

    Pipe

    Size

    Conn.

    Type

    A 1 C or D A

    KBN400

    1 400 6-14” W.C. 1 NPT

    A 2 C or D A 2 800 6-14” W.C. 1 1/2 NPT

    A 3 C or D A 3 1,200 6-14” W.C. 2 NPT

    A 4 C or D A 4 1,600 6-14” W.C. 2 NPT

    A 1 C or D B

    KBN501

    1 500 6-14” W.C. 1 1/2 NPT

    A 2 C or D B 2 1,000 6-14” W.C. 1 1/2 NPT

    A 3 C or D B 3 1,500 6-14” W.C. 2 NPT

    A 4 C or D B 4 2,000 6-14” W.C. 2 NPT

    A 1 C or D C

    KBN601

    1 600 6-14” W.C. 1 1/2 NPT

    A 2 C or D C 2 1,200 6-14” W.C. 2 NPT

    A 3 C or D C 3 1,800 6-14” W.C. 2 NPT

    A 4 C or D C 4 2,400 2-5 psi 2 NPT

    A 1 C or D D

    KBN701

    1 700 6-14” W.C. 1 1/2 NPT

    A 2 C or D D 2 1,400 6-14” W.C. 2 NPT

    A 3 C or D D 3 2,100 2-5 psi 2 NPT

    A 4 C or D D 4 2,800 2-5 psi 2 NPT

    A 1 C or D F

    KBN801

    1 800 6-14” W.C. 1 1/2 NPT

    A 2 C or D F 2 1,600 6-14” W.C. 2 NPT

    A 3 C or D F 3 2,400 2-5 psi 2 NPT

    A 4 C or D F 4 3,200 2-5 psi 2 NPT

    A 1 C or D G

    SBN1000

    1 1,000 6-14” W.C. 1 1/2 NPT

    A 2 C or D G 2 2,000 2-5 psi 2 NPT

    A 3 C or D G 3 3,000 2-5 psi 2 NPT

    A 4 C or D G 4 4,000 2-5 psi 2 NPT

    A 1 C or D H

    SBN1300

    1 1,300 6-14” W.C. 2 NPT

    A 2 C or D H 2 2,600 2-5 psi 2 NPT

    A 3 C or D H 3 3,900 2-5 psi 2 NPT

    A 4 C or D H 4 5,400 2-5 psi 2 NPT

    A 1 C or D J

    SBN1500

    1 1,500 6-14” W.C. 2 NPT

    A 2 C or D J 2 3,000 2-5 psi 2 NPT

    A 3 C or D J 3 4,500 2-5 psi 2 NPT

    A 4 C or D J 4 6,000 2-5 psi 2 NPT

  • 34

    Table 3 - Unit Gas Pipe Information, Feature B4 = K-N

    Heating Feature Boiler

    Inlet Gas

    Pressure

    Gas Header

    B1 B2 B3 B4 Size Qty

    Input

    Capacity

    (CFH)

    Pipe

    Size

    Conn.

    Type

    A 1 C or

    D K

    FBN2000

    1 2,000 2-5 psi 1 1/2 NPT

    A 2 C or

    D K 2 4,000 2-5 psi 2 NPT

    A 3 C or

    D K 3 6,000 2-5 psi 2 NPT

    A 4 C or

    D K 4 8,000 2-5 psi 3 Flange

    A 1 C or

    D L

    FBN2500

    1 2,500 2-5 psi 1 1/2 NPT

    A 2 C or

    D L 2 5,000 2-5 psi 2 NPT

    A 3 C or

    D L 3 7,500 2-5 psi 3 Flange

    A 4 C or

    D L 4 10,000 2-5 psi 3 Flange

    A 1 C or

    D M

    FBN3000

    1 3,000 2-5 psi 1 1/2 NPT

    A 2 C or

    D M 2 6,000 2-5 psi 2 NPT

    A 3 C or

    D M 3 9,000 2-5 psi 3 Flange

    A 4 C or

    D M 4 12,000 2-5 psi 3 Flange

    A 1 C or

    D N

    FBN3500

    1 3,500 2-5 psi 2 NPT

    A 2 C or

    D N 2 7,000 2-5 psi 3 Flange

    A 3 C or

    D N 3 10,500 2-5 psi 3 Flange

    A 4 C or

    D N 4 14,000 2-5 psi 3 Flange

  • 35

    Sidewall Direct Boiler Venting

    For units with Lochinvar Knight XL and

    SYNC boilers (feature B4 = A, B, C, D, E, F,

    G, H, or K), the air intake and vent piping

    runs from each boiler through the sidewall of

    the unit into the supplied sidewall vent

    termination.

    1. On the sidewall above the boiler access

    door, remove the shipping cover and attach

    the sidewall vent plate shipped with the unit.

    Figure 14 - Sidewall Vent Shipping Cover

    Removal

    Figure 15 - Sidewall Vent Plate Installation

    2. Attach air intake piping to the air inlet

    connector on the boiler at one end and run

    through the sidewall of the unit at the other

    end. All air intake pipes and fittings are

    PVC.

    Figure 16 - Typical Air Intake Piping

    Use only primer and cement approved for use with PVC (ANSI/ASTM D2564).

    WARNING

  • 36

    Figure 17 - Typical Flue Vent Piping

  • 37

    3. Attach vent piping to the flue pipe adapter

    on the boiler at one end and run through the

    sidewall of the unit at the other end. All Vent

    pipes and fittings are CPVC. Vent piping

    must be pitched at a minimum of 1/4 inch per

    foot back to the boiler.

    4. Install the vent and air intake piping

    through the wall into the sidewall vent base.

    Use RTV silicone sealant to seal the air

    intake pipe. Mount and secure the sidewall

    vent base using stainless steel screws. Seal

    all gaps between the pipes and the sidewall.

    Seal around the sidewall vent base to the wall

    ensuring no air gaps.

    5. Assemble vent cap to vent base and

    securely attach using stainless steel screws.

    Figure 18 - Sidewall Vent Base

    Figure 19 - Sidewall Vent Cap

    Vertical Direct Boiler Venting

    For units with Lochinvar Crest boilers

    (feature B4 = K, L, M, or N), the air intake

    and vent piping is installed to run vertically

    through the roof of the unit.

    1. Remove shipping covers from openings in

    the roof.

    Figure 20 - Roof Air Intake and Vent Piping

    Shipping Covers

    Use only primer and cement approved for use with CPVC (ANSI/ASTM F493).

    WARNING

  • 38

    2. Attach air intake piping to the air inlet

    connector on the boiler and run vertically

    through the roof of the unit. The air intake

    pipes and fittings will either be all PVC or all

    stainless steel components.

    Figure 21 - Typical Vertical Air Intake Piping

    For units with PVC piping, use only primer and cement approved for use with PVC (ANSI/ASTM D2564).

    WARNING

    JOINT CONNECTIONS The female end of each component incorporates a sealing gasket and a mechanical locking bond. Examine all components prior to installation. Gaskets must be in proper position to prevent leakage.

    CAUTION

    For units with stainless steel piping, all components must be installed in accordance with the manufacturer’s instructions to ensure all joints are secure and sealed correctly.

    WARNING

  • 39

    3. Insert the male end into the female section.

    Push the units together and turn them until

    half of the bead on the male end is c