lz series - aaon · lz series chillers and outdoor mechanical rooms installation, operation, &...
TRANSCRIPT
-
LZ Series
Chillers and Outdoor Mechanical Rooms
Installation, Operation,
& Maintenance
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death or property damage. Be sure to read and understand the installation, operation and service instructions in this manual. Improper installation, adjustment, alteration, service or maintenance can cause serious injury, death or property damage. A copy of this IOM should be kept with the unit.
Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your
building. Leave the building immediately. Immediately call you gas supplier
from a phone remote from the building. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier call the fire department.
Startup and service must be performed by a Factory Trained Service Technician.
WARNING WARNING
-
Table of Contents
Codes and Ordinances ............................................................................................................... 19 Receiving Unit ........................................................................................................................... 19
Storage ....................................................................................................................................... 20 Outdoor Mechanical Room ....................................................................................................... 20 Wiring Diagrams ....................................................................................................................... 21 General Maintenance ................................................................................................................. 21 Chiller Primary Pumping .......................................................................................................... 21
Chiller Primary/Secondary Pumping ........................................................................................ 22 Condensing Boilers ................................................................................................................... 22 Makeup Water ........................................................................................................................... 23 Compression Tank ..................................................................................................................... 23
Pressure Relief Valve ................................................................................................................ 24 Automatic Air Vent ................................................................................................................... 24
Dual Pumps ............................................................................................................................... 24 Pressure Gauges and Thermometers ......................................................................................... 24
Pipe Insulation ........................................................................................................................... 25 Outdoor Mechanical Room Placement...................................................................................... 25 Curb and Steel Mount Installation ............................................................................................ 25
Lifting and Handling ................................................................................................................. 28 Vestibule Exhaust Fan ............................................................................................................... 29
Water Connection ...................................................................................................................... 30 Temporary Drain – Evaporative Condenser .............................................................................. 31 Access Doors ............................................................................................................................. 31
End Flashing Installation ........................................................................................................... 31
Boiler Gas Connection .............................................................................................................. 32 Boiler Air Intake / Vent Piping ................................................................................................. 32 Sidewall Direct Boiler Venting ................................................................................................. 35
Vertical Direct Boiler Venting .................................................................................................. 37 Boiler Condensate Drain ........................................................................................................... 41
Split Unit Assembly .................................................................................................................. 41 Unit Mounting Isolation ............................................................................................................ 41
Low Ambient Operation ............................................................................................................ 41 Electrical .................................................................................................................................... 42 Variable Speed Compressors .................................................................................................... 44 Condenser Fan Pitch Adjustment .............................................................................................. 47 Boiler System Startup ................................................................................................................ 50
Boiler Sequence of Operations .................................................................................................. 51 General ...................................................................................................................................... 51
Refrigerant Suction Line Filter ................................................................................................. 51 Suction Filter Removal Instructions .......................................................................................... 52 Refrigerant Liquid Line Filter Driers ........................................................................................ 52 Evaporator/Heat Exchangers ..................................................................................................... 53 Adjusting Refrigerant Charge ................................................................................................... 53 Lubrication ................................................................................................................................ 57
-
4
Air-Cooled Condenser ............................................................................................................... 57 E-Coated Coil Cleaning ............................................................................................................ 57 Microchannel Coil Cleaning ..................................................................................................... 59 Evaporative-Condensed Chiller ................................................................................................ 61
Severe Operating Conditions Service .................................................................................... 62 Safety ..................................................................................................................................... 62 Performance ........................................................................................................................... 62 Warranties .............................................................................................................................. 63 Condenser Tube Inspection ................................................................................................... 63
Freeze Protection ................................................................................................................... 63 Recirculating Water System .................................................................................................. 63 Startup .................................................................................................................................... 63 Cleanliness ............................................................................................................................. 63
Storage ................................................................................................................................... 63 Pump Operation ..................................................................................................................... 64
Running.................................................................................................................................. 64 Condenser Fan Motors ........................................................................................................... 64
Water Make Up Valve ........................................................................................................... 64 Water Treatment System ....................................................................................................... 65 Sequence of Operation for LZ Series units without Diagnostics .......................................... 65
Sequence of Operation for LZ Series units with Diagnostics ................................................ 66 Pump Maintenance ................................................................................................................ 67
Fan Motor Maintenance ......................................................................................................... 67 Access Doors ......................................................................................................................... 67 Bearings - Lubrication ........................................................................................................... 68
Recommended Monthly Inspection ....................................................................................... 68
Mist Eliminators .................................................................................................................... 68 Air Inlet .................................................................................................................................. 68 Stainless Steel Base Pan ........................................................................................................ 68
Propeller Fans and Motors ..................................................................................................... 68 Recommended Annual Inspection ......................................................................................... 68
Cleaning ................................................................................................................................. 68 Water Quality ......................................................................................................................... 69
Mechanical Cleaning ............................................................................................................. 70 Service ....................................................................................................................................... 70 Replacement Parts ..................................................................................................................... 70 Water Pressure Reducing Valve ................................................................................................ 71 Water Pressure Relief Valve ..................................................................................................... 73
Automatic Air Vent Valves ....................................................................................................... 73 Pumps - Installation and Operating Instructions ....................................................................... 75
Pump Piping - General .............................................................................................................. 77 Pump Operation ......................................................................................................................... 77 General Care .............................................................................................................................. 78 Dual Pump Specific Information ............................................................................................... 80 Horizontal and Vertical Expansion Tanks ................................................................................ 85 Suction Guides .......................................................................................................................... 86
-
5
Glycol Auto Fill Unit ................................................................................................................ 87 Flo-Trex Combination Valve .................................................................................................... 89
Index of Tables and Figures
Tables:
Table 1 - Service Clearances......................................................................................................... 25 Table 2 - Unit Gas Pipe Information, Feature B4 = A-J ............................................................... 33
Table 3 - Unit Gas Pipe Information, Feature B4 = K-N.............................................................. 34 Table 4- Tandem Circuited Variable Speed Compressor VFD Frequency Range ....................... 44 Table 5 - Air-Cooled Condenser Fan Pitch................................................................................... 47 Table 6 - Evaporative-Condensed Chiller Fan Pitch .................................................................... 47
Table 7 - Condenser Fan Pin Location (Bushing Mount) ............................................................. 49 Table 8 - Condenser Fan Pin Location (Rotation Direction) ........................................................ 49
Table 9 - Fan Assembly Bushing Torque Specifications.............................................................. 50 Table 10 - Filter Drier Maximum Pressure Drop.......................................................................... 52
Table 11 - Acceptable Refrigeration Circuit Values..................................................................... 54 Table 12 - R-134a Refrigerant Temperature-Pressure Chart ........................................................ 55 Table 13 - R-410A Refrigerant Temperature-Pressure Chart ....................................................... 56
Table 14 - Recirculating Water Quality Guidelines ..................................................................... 69
Figures:
Figure 1 - Backflow Preventer ...................................................................................................... 23
Figure 2 - Pressure Relief Valve ................................................................................................... 24
Figure 3 - Curb Mounting with Dimensions ................................................................................. 26 Figure 4 - Curb End Detail............................................................................................................ 26 Figure 5 - Steel Mounting Rail with Dimensions ......................................................................... 26
Figure 6 - Concrete Pad Mounting with Dimensions ................................................................... 27 Figure 7 - LZ Base ........................................................................................................................ 27
Figure 8 - Lifting Points ................................................................................................................ 28 Figure 9 - LZ Series Example Lifting Detail ................................................................................ 29
Figure 10 - Vestibule Exhaust Fan................................................................................................ 29 Figure 11 - Water Pipe Flashing Installation ................................................................................ 30 Figure 12 – Temporary Drain Components .................................................................................. 31 Figure 14 - Factory Supplied End Flashings................................................................................. 31 Figure 15 - Sidewall Vent Shipping Cover Removal ................................................................... 35
Figure 16 - Sidewall Vent Plate Installation ................................................................................. 35 Figure 17 - Typical Air Intake Piping ........................................................................................... 35
Figure 18 - Typical Flue Vent Piping ........................................................................................... 36 Figure 19 - Sidewall Vent Base .................................................................................................... 37 Figure 20 - Sidewall Vent Cap...................................................................................................... 37 Figure 21 - Roof Air Intake and Vent Piping Shipping Covers .................................................... 37 Figure 22 - Typical Vertical Air Intake Piping ............................................................................. 38 Figure 23 - Correct Joint Connection............................................................................................ 39
-
6
Figure 24 - Incorrect Joint Connection ......................................................................................... 39 Figure 25 - Typical Vertical Vent Piping ..................................................................................... 40 Figure 26 - Vertical Termination of Air Intake and Vent Piping ................................................. 40 Figure 27 - Evaporative-Condensed Chiller Section Layout ........................................................ 45
Figure 28 - Fan with the HUB on the top and RET on the bottom. .............................................. 48 Figure 29 - Bushing Mount Location............................................................................................ 48 Figure 30 - RET with Pin in Groove 4 .......................................................................................... 48 Figure 31 - Fan HUB and RET Castings ...................................................................................... 48 Figure 32 - Pitch Insert ................................................................................................................. 49
Figure 33 - Replaceable Core Filter Driers ................................................................................... 52 Figure 34 - Proper Unit Location .................................................................................................. 62 Figure 35 - Improper Unit Locations ............................................................................................ 62 Figure 36 - Water Makeup Valve ................................................................................................. 65
Figure 36 – Evaporative condenser access door ........................................................................... 67
V45100 · Rev. A · 190308
-
7
AAON LZ Series Features and Options Introduction
Energy Efficiency
• Staged or Variable Speed R-410A Scroll Compressors
• Oil-Free Magnetic Bearing R-134a Turbocor Centrifugal Compressors
• High Efficiency Air-Cooled Microchannel Condenser Coils
• AAON Evaporative-Condensed Chiller • VFD Controlled Pumping Packages • VFD Controlled Condenser Fan Head
Pressure Control
• ECM Low Sound Condenser Fan Head Pressure Control
• 98% Thermal Efficiency Boilers • Waterside Economizers • Factory Installed EXVs
Outdoor Mechanical Room • Chilled Water Applications up to
540 tons
• Hot Water Applications up to 6,000 MBH
• Lighted Walk-In Service Vestibule • Factory Engineered Primary or
Primary/Secondary Pumping Packages
• Factory Installed Three Chemical Water Treatment
• Factory Installed Compression Tank • Brazed Plate or Shell and Tube
Evaporators
• Factory Installed Option Boxes for Field Installed Accessories
Safety • Phase and Brownout Protection • Single Point Non-Fused Disconnect
Power Switch
• Factory Installed Refrigerant Leak Detector
• Water Piping Air Separator • Waterside Thermometer and Pressure
Gauge
Installation and Maintenance • Double Wall Rigid Polyurethane Foam
Injected Panel Construction
• Lighted Walk-In Service Vestibule • Access Doors with Full Length Stainless
Steel Piano Hinges
• Zinc Cast Lockable Handles • Factory Installed Convenience Outlet • Service Vestibule Heating and Cooling • Motorized Service Vestibule Fresh Air • Controls Diagnostics • Touchscreen Computer Controls
Interface
• Evaporative-Condensed Chiller De-Superheater
• Evaporative-Condensed Chiller Sump Heaters
• Liquid Line Sight Glass • Compressor Isolation Valves • Auto Glycol Feeder • Color-Coded Wiring Diagrams
System Integration • Complete System with AAON Chilled
Water Air Handling Units
• BMS Connectivity • Grooved End Water Piping Connections • Custom Color Paint Options
Environmentally Friendly • R-410A or R-134a Refrigerant
Extended Life • Optional 5 Year Compressor Warranty • Condenser Coil Guards • 2,500 Hour Salt Spray Tested Exterior
Corrosion Protection
• 6,000 Hour Salt Spray Tested Polymer E-Coated Condenser Coils
•
-
8
Safety
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in equipment
damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. Before servicing, disconnect all
electrical power to the unit. More than one disconnect may be provided.
When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing. Secure all doors with key-lock or nut and bolt.
WARNING
QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit.
WARNING
WHAT TO DO IF YOU SMELL GAS Do not try to turn on unit. Shut off main gas supply. Do not touch any electric switch. Do not use any phone in the
building. Never test for gas leaks with an
open flame. Use a gas detection soap solution
and check all gas connections and shut off valves.
CAUTION
-
9
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance.
WARNING
Electric shock hazard. Before servicing, shut off all electrical power to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures.
WARNING
During installation, testing, servicing, and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks. Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed.
WARNING
GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements.
WARNING
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in hand mode or manual bypass. Damage to personnel or equipment can occur if left unattended. When in hand mode or manual bypass mode VFDs will not respond to controls or alarms.
WARNING
Electric motor over-current protection and overload protection may be a function of the Variable Frequency Drive to which the motors are wired. Never defeat the VFD motor overload feature. The overload ampere setting must not exceed 115% of the electric motors FLA rating as shown on the motor nameplate.
CAUTION
-
10
UNIT HANDLING To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death.
WARNING
Always use a pressure regulator, valves and gauges to control incoming pressures when pressure testing a system. Excessive pressure may cause line ruptures, equipment damage or an explosion which may result in injury or death.
WARNING
Door compartments containing hazardous voltage or rotating parts are equipped with door latches to allow locks. Door latches are shipped with nut and bolts requiring tooled access. If you do not replace the shipping hardware with a pad lock always re-install the nut & bolt after closing the door.
CAUTION
Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death.
WARNING
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils that are used in R-410A and other refrigerant systems will cause stress cracking of PVC or CPVC piping, even if only present in trace amounts. This will result in complete piping system failure.
CAUTION
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 3 minutes.
3 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 3 minutes. The cycle rate must not exceed 6 starts per hour.
WARNING
To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than 8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution.
CAUTION
-
11
1. Startup and service must be performed by a Factory Trained Service Technician.
2. The unit is for outdoor use only. See General Information section for more
information.
3. Use only with type of the gas approved for the boiler. Refer to the boiler rating
plate.
4. Provide adequate combustion ventilation air to the boiler.
5. Every unit has a unique equipment nameplate with electrical, operational,
and unit clearance specifications. Always
refer to the unit nameplate for ratings
unique to the model you have purchased.
6. READ THE ENTIRE INSTALLATION, OPERATION AND MAINTENANCE
MANUAL. OTHER IMPORTANT
SAFETY PRECAUTIONS ARE
PROVIDED THROUGHOUT THIS
MANUAL.
7. Keep this manual and all literature safeguarded near or on the unit.
Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used with R-410A and R134a refrigeration systems. Refer to the compressor label for the proper compressor lubricant type.
CAUTION
Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil.
CAUTION
Rotation must be checked on ALL MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection.
CAUTION
Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturer’s usage instructions. Failure to follow instructions may result in equipment damage, injury or death.
WARNING
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJ
RE
V
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26C
26
D
26E
26
F
27
28
29
30
31
32
33
34
35
12
LZ Series Feature String Nomenclature
MODEL OPTIONS Series and Generation
LZ
Major Revision
A
Unit Size
Air-Cooled Evaporative-Condensed
045 = 45 ton Capacity 053 = 53 ton Capacity
055 = 55 ton Capacity 061 = 61 ton Capacity
060 = 60 ton Capacity 069 = 69 ton Capacity
075 = 75 ton Capacity 078 = 78 ton Capacity
090 = 90 ton Capacity 090 = 90 ton Capacity
095 = 95 ton Capacity 106 = 106 ton Capacity
105 = 105 ton Capacity 120 = 120 ton Capacity
120 = 120 ton Capacity 121 = 121 ton Capacity
140 = 140 ton Capacity 134 = 134 ton Capacity
170 = 170 ton Capacity 150 = 150 ton Capacity
181 = 181 ton Capacity 161 = 161 ton Capacity
200 = 200 ton Capacity 180 = 180 ton Capacity
181 = 181 ton Capacity
193 = 193 ton Capacity
239 = 239 ton Capacity
240 = 240 ton Capacity
274 = 274 ton Capacity
300 = 300 ton Capacity
319 = 319 ton Capacity
356 = 356 ton Capacity
360 = 360 ton Capacity
401 = 401 ton Capacity
441 = 441 ton Capacity
450 = 450 ton Capacity
478 = 478 ton Capacity
540 = 540 ton Capacity
Series - Scroll Compressor
Air-Cooled
A = 45-60 ton units
B = 75 ton unit
C = 95-140 ton units
D = 170-200 ton units
Evaporative-Condensed
A = 53-69 ton units
B = 78 ton unit
C = 106-161 ton units
D = 193-239 ton units
E = 274-319 ton units
F = 356-401 ton units
G = 441-478 ton units
Series - Turbocor Compressor
Air-Cooled
H = 90-120 ton units
K = 181 ton unit
Evaporative-Condensed
H = 90 & 120 ton units
J = 150 & 180 ton units
K = 181 ton unit
L = 240 ton unit
M = 300 & 360 ton units
N = 450 & 540 ton units
Minor Revision
A
Voltage
2 = 230V/3Φ/60Hz
3 = 460V/3Φ/60Hz
4 = 575V/3Φ/60Hz
8 = 208V/3Φ/60Hz
A1: Compressor Style
F = R-410A Tandem VFD Compatible Scroll
Compressor
H = R-134a Turbocor Centrifugal Compressor
J = R-134a Turbocor Centrifugal Compressor with
Economizer
A2: Condenser Style
A = Air-Cooled Microchannel Condenser
H = Evaporative-Condensed
A3: Evaporator Configuration
A = Brazed Plate
B = Oversized Brazed Plate
C = Shell & Tube
D = Oversized Shell & Tube
A4: Coating
0 = Standard
E = Polymer E-Coated Condenser Coil
A5: Staging
0 = Staged On/Off Compressors
E = All Circuits Variable Capacity Compressors
G = Half Circuits Variable Capacity Compressors
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJR
EV
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26C
26
D
26E
26
F
27
28
29
30
31
32
33
34
35
13
B1: Type
0 = No Boilers
B2: Boiler Quantity
0 = No Boilers
B3: Type and Pipe Size
0 = No Boilers
B4: Boiler Capacity
0 = No Boilers
UNIT FEATURE OPTIONS 1: Unit Orientation
E = Walk-in Vestibule Left Access Left Water
Connections
F = Walk-in Vestibule Left Access Right Water
Connections
G = Walk-in Vestibule Left Access Bottom Water
Connections
J = Walk-in Vestibule Right Access Left Water
Connections
K = Walk-in Vestibule Right Access Right Water
Connections
L = Walk-in Vestibule Right Access Bottom Water
Connections
2: Pumping Style
0 = No Pumps
A = Const. Primary Pumping System Small Pipe Size
B = Const. Primary Pumping System Large Pipe Size
C = Var. Primary Pumping System Small Pipe Size
D = Var. Primary Pumping System Large Pipe Size
E = Primary/Secondary Pumping System Small Pipe
Size
F = Primary/Secondary Pumping System Large Pipe
Size
3A: Building Pump Configuration
0 = No Building Pumps
A = 1 Pump + High Eff Motor
B = 1 Dual Pump + High Eff Motors
C = 2 Single Pumps + High Eff Motors
D = 1 Pump + VFD + High Eff Motor
E = 1 Dual Pump + 2 VFD's + High Eff Motors
F = 2 Single Pumps + 2 VFD’s + High Eff Motors
K = 1 Pump + Field Installed VFD + High Eff Motor
L = 1 Dual Pump + 2 Field Installed VFD's + High
Eff Motors
M = 2 Single Pumps + 2 Field Installed VFD’s +
High Eff Motors
3B: Building Pump Series and RPM
0 = No Building Pumps
A = 4360 (1,170 nominal rpm)
B = 4360 (1,760 nominal rpm)
C = 4360 (3,520 nominal rpm)
D = 4380 (1,170 nominal rpm)
E = 4380 (1,760 nominal rpm)
F = 4380 (3,520 nominal rpm)
G = 4300 (1,170 nominal rpm)
H = 4300 (1,760 nominal rpm)
J = 4300 (3,520 nominal rpm)
K = 4382 (1,170 nominal rpm)
L = 4382 (1,760 nominal rpm)
M = 4382 (3,520 nominal rpm)
N = 4302 (1,170 nominal rpm)
P = 4302 (1,760 nominal rpm)
Q = 4302 (3,520 nominal rpm)
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJR
EV
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26C
26
D
26E
26
F
27
28
29
30
31
32
33
34
35
14
3C: Pump Size
0 = No Building Pumps
A = 1.5B
B = 2B
C = 2D
D = 3D
E = 1.5x1.5x6
F = 2x2x6
G = 3x3x6
H = 4x4x6
J = 6x6x6
K = 1.5x1.5x8
L = 2x2x8
M = 3x3x8
N = 4x4x8
P = 5x5x8
Q = 6x6x8
R = 8x8x8
S = 2x2x10
T = 3x3x10
U = 4x4x10
V = 6x6x10
W = 8x8x10
Y = 4x4x11.5
Z = 5x5x11.5
1 = 6x6x11.5
2 = 8x8x11.5
3 = 4x4x13
4 = 6x6x13
5 = 8x8x13
3D: Building Pump Motor Size
0 = No Building Pumps
A = 0.5 hp
B = 0.75 hp
C = 1 hp
D = 1.5 hp
E = 2 hp
F = 3 hp
G = 5 hp
H = 7.5 hp
J = 10 hp
K = 15 hp
L = 20 hp
M = 25 hp
3D: Building Pump Motor Size Continued
N = 30 hp
P = 40 hp
Q = 50 hp
R = 60 hp
S = 75 hp
4A: Recirculating Pump Configuration
0 = No Recirculating Pumps
A = 1 Pump + High Eff Motor
B = 1 Dual Pump + High Eff Motors
C = 2 Single Pumps + High Eff Motors
4B: Recirculation Pump Series & RPM
0 = No Recirculating Pumps
A = 4360 (1,170 nominal rpm)
B = 4360 (1,760 nominal rpm)
C = 4360 (3,520 nominal rpm)
D = 4380 (1,170 nominal rpm)
E = 4380 (1,760 nominal rpm)
F = 4380 (3,520 nominal rpm)
G = 4300 (1,170 nominal rpm)
H = 4300 (1,760 nominal rpm)
J = 4300 (3,520 nominal rpm)
K = 4382 (1,170 nominal rpm)
L = 4382 (1,760 nominal rpm)
M = 4382 (3,520 nominal rpm)
N = 4302 (1,170 nominal rpm)
P = 4302 (1,760 nominal rpm)
Q = 4302 (3,520 nominal rpm)
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJR
EV
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26C
26
D
26E
26
F
27
28
29
30
31
32
33
34
35
15
4C: Recirculating Pump Size
0 = No Recirculating Pumps
A = 1.5B
B = 2B
C = 2D
D = 3D
E = 1.5x1.5x6
F = 2x2x6
G = 3x3x6
H = 4x4x6
J = 6x6x6
K = 1.5x1.5x8
L = 2x2x8
M = 3x3x8
N = 4x4x8
P = 5x5x8
Q = 6x6x8
R = 8x8x8
S = 2x2x10
T = 3x3x10
U = 4x4x10
V = 6x6x10
W = 8x8x10
Y = 4x4x11.5
Z = 5x5x11.5
1 = 6x6x11.5
2 = 8x8x11.5
3 = 4x4x13
4 = 6x6x13
5 = 8x8x13
4D: Recirculating Pump Motor Size
0 = No Recirculating Pumps
A = 0.5 hp
B = 0.75 hp
C = 1 hp
D = 1.5 hp
E = 2 hp
F = 3 hp
G = 5 hp
H = 7.5 hp
J = 10 hp
K = 15 hp
L = 20 hp
M = 25 hp
4D: Recirculating Pump Motor Size Continued
N = 30 hp
P = 40 hp
Q = 50 hp
R = 60 hp
S = 75 hp
5A: Boiler Building Pump Configuration
0 = No Boiler Pumps
5B: Boiler Building Pump Series & RPM
0 = No Boiler Pumps
5C: Boiler Building Pump Size
0 = No Boiler Pumps
5D: Boiler Building Pump Motor Size
0 = No Boiler Pumps
6: Refrigeration Options
0 = None
A = Hot gas bypass on non-variable capacity
compressor circuits
B = Hot gas bypass on all circuits
7: Refrigeration Accessories
0 = Standard
A = Sight Glass
B = Compressor Isolation Valves
C = Option A + B
8A: Unit Disconnect Type
0 = Standard Single Point Power Block
A = Single Point Power Non-fused Disconnect
8B: Disconnect 1 Size
0 = Power Block
N = 100 amps
R = 150 amps
U = 225 amps
V = 250 amps
Z = 400 amps
3 = 600 amps
5 = 800 amps
7 = 1200 amps
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJR
EV
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10
C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26C
26
D
26E
26
F
27
28
29
30
31
32
33
34
35
16
8C: Blank
0 = Standard
9: Accessories
0 = None
B = Phase & Brown Out Protection
10A: Unit Control Sequence
0 = Standard AAON Controls
10B: Unit Control Supplier
E = MCS Controls
10C: Control Supplier Options
0 = None
A = Touchscreen Computer Interface
C = Modem
G = Option A + C
10D: BMS Connection & Diagnostics
0 = None
A = BACnet IP
B = BACnet MSTP
C = Modbus IP
D = Modbus RTU
E = LonTalk
H = No BMS Connection with Diagnostics
J = BACnet IP with Diagnostics
K = BACnet MSTP with Diagnostics
L = Modbus IP with Diagnostics
M = Modbus RTU with Diagnostics
N = LonTalk with Diagnostics
11: Cabinet Options
0 = None
B = Access Door Windows
12: Vestibule Accessories
0 = None
A = Refrigerant Leak Detector
B = Motorized Service Vestibule Fresh Air
C = Vestibule Heating (Electric)
D = Vestibule Cooling (Fan/Coil)
F = Option A + B
G = Option A + C
12: Vestibule Accessories Continued
H = Option A + D
K = Option B + C
L = Option B + D
N = Option C + D
R = Option A + B + C
S = Option A + B + D
U = Option A + C + D
Y = Option B + C + D
3 = Option A + B + C + D
13: Maintenance Accessories
0 = None
A = 115VAC Convenience Outlet Factory Wired
B = 115VAC Convenience Outlet Field Wired
C = Service Lights
F = Option A + C
J = Option B + C
14: Option Boxes
0 = None
A = 2 ft Option Box
B = 4 ft Option Box
C = 6 ft Option Box
D = 8 ft Option Box
F = 10 ft Option Box
G = 12 ft Option Box
15: Code Options
0 = Standard ETL U.S.A. Listing
A = Chicago Code
B = ETL U.S.A. + Canada Listing
16: Shipping Splits
0 = One Piece Unit
A = Two Piece Unit
17: Air-Cooled Condenser Accessories
0 = None (No Air-Cooled Condenser)
H = Cond Coil Guards + 3Φ Condenser Fan Motor +
Fan Cycling (35°F) J = Cond Coil Guards + 3Φ Condenser Fan Motor +
VFD Condenser Fan Head Pressure Control (0°F) S = Cond. Coil Guards + Low Sound ECM Cond.
Fans – Head Pressure Control (0°F)
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJR
EV
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26
C
26
D
26E
26F
27
28
29
30
31
32
33
34
35
17
18: Evaporative-Condensed Chiller Accessories
0 = None (No Evaporative-Condenser)
A = No Sump Heat
B = Sump Heaters
19: Blank
0 = None
20: Blank
0 = None
21: Chiller Compression Tank
0 = None
A = AX-15V
B = AX-20V
C = AX-40V
D = AX-60V
E = AX-80V
F = AX-100V
G = AX-120V
H = AX-180V
J = AX-200V
K = AX-240V
L = AX-260V
M = AX-280V
22: Boiler Compression Tank
0 = None
23: Blank
0 = Standard
24: Chiller Accessories
0 = None
A = Glycol chiller
B = Air Separator
C = Thermometers & Pressure Gauges
D = Chemical Pot Feeder
E = Auto Glycol Feeder
F = Option A + B
G = Option A + C
H = Option A + D
J = Option A + E
K = Option B + C
L = Option B + D
24: Chiller Accessories Continued
M = Option B + E
N = Option C + D
P = Option C + E
Q = Option D + E
R = Option A + B + C
S = Option A + B + D
T = Option A + B + E
U = Option A + C + D
V = Option A + C + E
W = Option A + D + E
Y = Option B + C + D
Z = Option B + C + E
1 = Option B + D + E
2 = Option C + D + E
3 = Option A + B + C + D
4 = Option A + B + C + E
5 = Option A + B + D + E
6 = Option A + C + D + E
7 = Option B + C + D + E
8 = Option A + B + C + D + E
25: Blank
0 = Standard
26A: Blank
0 = Standard
26B: Blank
0 = Standard
26C: Blank
0 = Standard
26D: Blank
0 = Standard
26E: Blank
0 = Standard
26F: Blank
0 = Standard
-
LZ Series Feature String Nomenclature
Model Options : Unit Feature Options
GE
N
MJR
EV
SIZ
E
SE
RIE
S
MN
RE
V
VL
T
A1
A2
A3
A4
A5
B1
B2
B3
B4
1
2
3A
3B
3C
3D
4A
4B
4C
4D
5A
5B
5C
5D
6
7
8A
8B
8C
LZ A - 140 - C - A - 3 - F A C 0 E - 0 0 0 0 : E 0 - 0 0 0 0 - 0 0 0 0 - 0 0 0 0 - 0 0 - 0 0 0 0 - 0 E 0 0 - 0 0 C 0 0 - 0 J 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 - 0 0 D B
9
10
A
10B
10C
10
D
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
A
26B
26C
26
D
26E
26
F
27
28
29
30
31
32
33
34
35
18
27: Blank
0 = Standard
28: Blank
0 = Standard
29: Blank
0 = Standard
30: Blank
0 = Standard
31: Blank
0 = Standard
32: Blank
0 = Standard
33: Warranty
0 = Standard Warranty
D = Compressor Warranty Years 2-5
34: Cabinet Material
D = Galvanized Cabinet 6” Base Rail + Double Slope
Roof
H = Galvanized Cabinet 8” Base Rail + Double Slope
Roof
35: Paint & Special Pricing Authorizations
B = Premium AAON Gray Paint Exterior
E = Premium AAON Gray Paint Exterior + Shrink
Wrap
X = Special Pricing Authorization + Premium AAON
Gray Paint Exterior
1 = Option X + Shrink Wrap
4 = Special Pricing Authorization + Special Exterior
Paint Color
7 = Option 4 + Shrink Wrap
-
19
General Information
AAON LZ Series chiller outdoor mechanical
rooms are complete self-contained liquid
chilling units. They are assembled, wired,
charged, and run-tested. Models are available
for air-cooled and evaporative-condensed
applications. Chiller primary pumping
packages, primary/secondary pumping
packages, and boilers with pumping package
are available as optional features.
Codes and Ordinances
LZ Series units have been tested and
certified, by TL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with
the American Society of Heating,
Refrigeration and Air Conditioning
Engineers Handbook.
Installation of LZ Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the current National Electric Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once. Nameplate should be
checked to ensure the correct model sizes and
voltages have been received to match the job
requirements.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician.
WARNING
RISK OF ELECTRICAL SHOCK
Electrical raceways are located in the upper wall sections of the unit. DO NOT CUT OR DRILL into the wall sections of the unit that are within 12 inches of the roofline.
WARNING
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling, or reclaiming must be followed.
CAUTION
Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment.
WARNING
Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty.
WARNING
-
20
If repairs must be made to damaged goods,
then the factory should be notified before any
repair action is taken in order to protect the
warranty. Certain equipment alteration,
repair, and manipulation of equipment
without the manufacturer’s consent may void
the product warranty. Contact AAON
Technical Support for assistance with
handling damaged goods, repairs, and freight
claims: (918) 382-6450.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction traffic
and in the proper orientation as marked on the
packaging with all internal packaging in
place. Leave all internal packaging in place
and secure all loose-shipped items.
Outdoor Mechanical Room
Failure to observe the following instructions
will result in premature failure of your
system, and possible voiding of the warranty.
Never turn off the main power supply to the
unit, except for complete shutdown. When
power is cut off from the unit, any
compressors equipped with crankcase heaters
cannot prevent refrigerant migration. This
means the compressor will cool down, and
liquid refrigerant may accumulate in the
compressor. The compressor is designed to
pump refrigerant gas and damage may occur
when power is restored if liquid enters the
compressor.
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 3 minutes.
3 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 3 minutes. The cycle rate must not exceed 6 starts per hour.
WARNING
Before unit operation, the main power switch must be turned on for at least 24 hours for units equipped with crankcase heaters.
CAUTION
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. All motors, to include and not be limited to pump motors and condenser fan motors, should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection.
CAUTION
-
21
Always control the system from the building
management system, or control panel, never
at the main power supply (except for
emergency or for complete shutdown of the
system).
Scroll compressors must be on a minimum of
3 minutes and off for a minimum of 3
minutes. The cycle rate must be no more than
6 starts per hour.
The chiller is furnished with a flow switch
installed on the outlet of each heat exchanger.
This sensor must not be bypassed since it
provides a signal to the unit controller that
water flow is present in the heat exchanger
and the unit can operate without the danger of
freezing the liquid.
Compressor life will be seriously shortened
by reduced lubrication, and the pumping of
excessive amounts of liquid oil and
refrigerant.
Wiring Diagrams
A complete set of unit specific wiring
diagrams in both ladder and point-to-point
form are laminated in plastic and located
inside the control vestibule.
General Maintenance
When the initial startup is made and on a
periodic schedule during operation, it is
necessary to perform routine service checks
on the performance of the chiller and boiler.
This includes reading and recording suction
pressures and checking for normal sub-
cooling and superheat. See the evaporative-
condensed chiller and air-cooled chiller
sections in this manual for specific details.
Chiller Primary Pumping
Primary pumping uses a single pump to move
water (or glycol) through the chiller
evaporator and back to the building. This
pumping package provides a constant or
variable flow of water to the building. The
pump is activated whenever the chiller is
given a run signal.
Water enters the unit through the return water
piping, and then travels through an air
separator to remove any air that is entrapped
in the water. Following this, the water flows
through a suction guide with an integral
strainer. The end of the suction guide is
removable for strainer access. The strainer
assembly is composed of two parts, the
operational strainer and the startup strainer,
(located inside the operational strainer)
which is to be removed 24 hours after startup.
Scroll compressors are directional and will be damaged by operation in the wrong direction. High pressure switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should be made at the unit power connection.
CAUTION
FIELD WIRED CONNECTIONS
Some units may require field wired connections. Refer to the wiring diagrams contained within the unit to identify any components or controls requiring additional wiring in the field before placing the unit into service. All additional field wiring should be performed by a Factory Trained Service Technician.
CAUTION
-
22
The pump is installed after the suction guide,
and before a combination valve (Flo-Trex).
This combination valve acts as an isolation
valve, check valve, and flow balancing valve.
The evaporator is placed after the
combination valve in the water circuit, with a
flow switch installed at its inlet and outlet.
This flow switch closes when the velocity is
above 0.7 feet per second. The closing flow
switch signals the control system to indicate
flow through the heat exchanger and allow
cooling to activate as required to maintain the
setpoint. The water exiting the chiller
evaporator leaves the unit through the water
out connection.
Chiller Primary/Secondary Pumping
Primary/secondary pumping option provides
variable flow to the system. It consists of a
constant flow pump for the chiller heat
exchanger and a variable flow pump for the
building. The controls package senses
differential pressure across the pump with
pressure transducers installed at the suction
and discharge, and varies the speed of the
pump using a VFD in order to maintain a
given differential pressure across the pump.
The primary/secondary pumping package is
essentially composed of two piping loops
coupled together. The primary loop has a
constant flow rate in order to keep the chiller
heat exchanger from freezing, and the
secondary, variable flow loop, provides water
to the building. The two loops are coupled via
a water line that compensates for excess flow
in either loop. As the flow in the secondary
loop decreases below the flow in the primary
loop, excess flow bypasses the building loop
and circulates through the bypass water line.
On the other hand, as the flow in the
secondary loop increases above the flow in
the primary loop, excess flow bypasses the
chiller and circulates through the bypass
water line.
The secondary pump has its own suction
guide, combination valve, and isolation
valve, similar to the primary pump, with the
addition of an air separator to remove any air
that is entrapped in the water.
Condensing Boilers
AAON LZ chillers are available with factory
installed condensing boilers. All boiler
systems will include either fixed or variable
speed building pumps. All boiler building
pumps will be supplied with a suction guide
with a strainer and triple duty valve. The
suction guide contains both an operational
strainer and a startup strainer. The startup
strainer should be removed 24 hours after
startup. The triple duty valve functions as an
isolation valve, check valve, and flow
balancing valve.
The condensing boilers will be a water tube
design or a fire tube design. In a water-tube
boiler, the water flows through tubes with the
combustion products heating from the
outside. These boilers require a constant
water flow and will be provided with a
primary pump for each heat exchanger.
Some boilers have two heat exchangers and
will have two primary pumps. The primary
pump is controlled by the boiler and will only
come on when it has a call for heat. Water-
tube boilers are provided with flow switches,
which must make before the boiler can
operate.
In fire-tube boilers water flows through a
tank, with the combustion products inside
tubes. These boilers are capable of
significant water flow turn-down and do not
require individual primary pumps. A control
valve, operate by the boiler controls, is
provided with each boiler. A water flow
switch is not required with fire-tube boilers.
A low-level cutoff switch is used which will
prevent the boiler from operating when there
is not a sufficient water level present. Upon
-
23
initial startup, the boiler may have to be
cycled several times to generate an adequate
water level.
Makeup Water
A 3/4” FPT city make up water connection is
provided to replace water that is lost from the
system.
Glycol units require a glycol feeder (optional
factory installed or field installed) to replace
fluid that is lost in the system. Water should
not be directly added to glycol applications as
this would dilute the glycol concentration and
thereby increase the freezing temperature of
the fluid.
The makeup water connection is provided
with a backflow preventer that has isolation
valves on the inlet and outlet for service.
Figure 1 shows the pressure drop versus flow
rate for the backflow preventer.
Figure 1 - Backflow Preventer
There is a pressure-reducing valve after the
backflow preventer. This valve reduces the
city water pressure to maintain the operating
pressure of the system. This valve is
adjustable from 10-35 psig with a factory
setting of 30 psig. The system pressure varies
with the height of the system. The pressure-
reducing valve setting should be set so that
the pressure at the high point in the system is
high enough to vent air from the system
(usually 4 psig). There should be air vents at
all parts in the system where air could be
trapped. If the pressure is not high enough
throughout the system, flashing could occur
in the piping or the pump could cavitate.
There is an isolation valve on the inlet and
outlet of the pressure-reducing valve for
service.
The pressure reducing valve fills the system
at a reduced rate. There is a bypass around the
pressure reducing valve for the initial fill of
the system to increase the initial fill speed.
After the initial system fill, this valve should
be closed.
Compression Tank
As the water temperature in the system
increases, the volume that water displaces
increases. In order to compensate for these
expansion forces, a compression or
expansion tank must be used. The factory
installed tank option includes a pre-
pressurized diaphragm compression tank that
is preset for 12 psig.
The factory pre-charge pressure may need to
be field adjusted. The tank must be pre-
charged to system design fill pressure before
placing into operation. Remove the pipe plug
covering the valve enclosure. Check and
adjust the charge pressure by adding or
releasing air.
If the system has been filled, the tank must be
isolated from the system and the tank emptied
before charging. This ensures that all fluid
has exited the diaphragm area and proper
charging will occur.
If the pre-charge adjustment is necessary, oil
and water free compressed air or nitrogen gas
may be used. Check the pre-charge using an
accurate pressure gauge at the charging valve
and adjust as required. Check air valve for
leakage. If evident, replace the Schrader
valve core. Do not depend on the valve cap to
seal the leak. After making sure the air charge
-
24
is correct, replace the pipe plug over the
charging valve for protection.
Purge air from system before placing tank
into operation. All models have system water
contained behind the diaphragm.
It is recommended that the pre-charge be
checked annually to ensure proper system
protection and long life for the vessel.
Pressure Relief Valve
Required pressure relief valve is installed in
the unit. This valve is set at 125 psig. Figure
2 shows inlet pressure versus capacity for this
pressure relief valve. See appendix for
additional information.
Figure 2 - Pressure Relief Valve
Automatic Air Vent
There is an automatic air vent installed at the
high point of the system inside the pumping
package compartment. The air vent valve
must be in the proper position for operation.
Ensure that the small vent cap is loosened two
turns from the closed position, allowing air to
be vented from the system. It is advisable to
leave the cap on to prevent impurities from
entering the valve. See appendix for
additional information.
Dual Pumps
When redundant pumping is required, factory
installed dual pumps or two single pumps can
be ordered. A dual pump is a pump with two
independent motors and impellors in a single
casing. This dual pump has a swing split-
flapper valve in the discharge port to prevent
liquid recirculation when only one pump is
operating. Isolation valves in the casing allow
one pump to be isolated and removed for
service while the other pump is still
operating.
When redundant pumping is required with
high flow rates, two independent pumps may
be installed in parallel. Each pump will have
its own suction guide/strainer, combination
valve, and isolation valves.
The controls package will activate the pump
when the unit is given a run command. If the
controls do not recognize flow in 60 seconds
(factory default), the second pump will be
activated and an alarm signal will be
generated. If the second pump does not
activate, the cooling will be locked out. See
Appendix - Water Piping Component
Information for additional information.
Pressure Gauges and Thermometers
Pressure gauges and thermometers are
available as a factory installed option.
Thermometers are installed on the inlet and
outlet of the unit. One pressure gauge is
installed at each pump. This pressure gauge
is connected in three places to the water
piping before the suction guide/strainer, after
the suction guide and before the pump, and
after the pump. There is also a valve at each
of these points to isolate the pressure. To
measure the pressure at any given point, open
the valve at that point and close the other two
valves. One gauge is used so that the
calibration of the pressure gauge is irrelevant
in the calculation of the differential pressure.
-
25
Pipe Insulation
The water piping and components on units
with pumping packages are not insulated at
the factory. Insulation should be installed on
the water piping after the system has been
checked for leaks.
Installation
Outdoor Mechanical Room Placement
The AAON LZ Series is designed for outdoor
applications and can be mounted at ground
level or on a rooftop. It must be placed on a
level and solid foundation that has been
prepared to support its weight.
The placement relative to the building air
intakes and other structures must be carefully
selected. Be sure to observe the dimensions
that are on the rating plate of the chiller for
operational and service clearances.
Table 1 - Service Clearances
Location Unit Size
45-540 tons
Left 96”
Right
Compressor End 72”
Chiller HXC End
Top Unobstructed
Condenser coils and fans must be free of any
obstructions in order to start and operate
properly with a correct amount of airflow.
For proper unit operation, the immediate area
around condenser(s) must remain free of
debris that may be drawn in and obstruct
airflow in the condensing section.
Consideration must be given to obstruction
caused by snow accumulation when placing
the unit.
Curb and Steel Mount Installation
Make openings in the roof decking large
enough to allow for water piping, electrical,
and gas penetrations and workspace only. Do
not make openings larger than necessary. Set
the curb to coincide with the openings. Make
sure curb is level.
If an LZ with air-cooled condenser is
installed on a curb, use a curb cap for the
open area under the condenser section.
Unit specific curb drawing is included with
job submittal. See SMACNA Architectural
Sheet Metal Manual for curb installation
details.
When installed at ground level, a one-piece
concrete slab should be used with footings
that extend below the frost line. Care must
also be taken to protect the coil and fins from
damage due to vandalism or other causes.
If unit is elevated a field supplied catwalk is
recommended to allow access to unit service
doors.
This unit ships with a curb gasket that is 1¼”
wide and 1½” tall. It is recommended that this
or another similar gasket be used between the
curb and the unit to reduce vibration
transmission from the unit to the building.
All roofing work should be performed by competent roofing contractors to avoid any possible leakage.
CAUTION
-
26
Figure 3 - Curb Mounting with Dimensions
Figure 4 - Curb End Detail
Figure 5 - Steel Mounting Rail with Dimensions
-
27
Figure 6 - Concrete Pad Mounting with Dimensions
Figure 7 - LZ Base
-
28
Lifting and Handling
If cables or chains are used to hoist the unit
they must be the same length and care should
be taken to prevent damage to the cabinet.
See Figure 9 for additional information.
Before lifting unit, be sure that all shipping
material has been removed from unit. If the
unit is an evaporative-condensed chiller,
make sure the tank is empty before lifting.
Secure hooks and cables at all lifting points/
lugs provided on the unit.
Hoist unit to a point directly above the curb
or mounting rail. Be sure that the gasket
material has been applied to the curb or
mounting rail.
Carefully lower and align unit with utility
openings. Lower the unit until the unit skirt
fits around the curb. Make sure the unit is
properly seated on the curb and is level.
Do not push, pull or lift the unit from
anything other than its base.
Figure 8 - Lifting Points
-
29
Figure 9 - LZ Series Example Lifting Detail
Lifting slot locations are unit specific.
Unit must be rigged at all marked lifting points.
Vestibule Exhaust Fan
Prior to unit operation of units with service
vestibules the exhaust fan shipping support
must be removed from the exterior of the unit
The exhaust fan also includes a factory
provide exterior rain hood which must be
installed.
Figure 10 - Vestibule Exhaust Fan
-
30
Water Connection
Remove the shipping cover from the water
connection cutout in the post. Connect the
supply and return water lines. The standard
water connection is grooved end pipe. The
connection size is listed on the unit rating
sheet along with the designed volumetric
flow rate. The maximum operating pressure
for AAON LZ Series unit is 125 psi. Install
the flashing provided by AAON according to
the steps in Figure 11. Finished water
connection will be water tight.
Figure 11 - Water Pipe Flashing Installation
The chiller must be operated only with liquid flowing through the evaporators.
WARNING
Boilers must be operated only with liquid flowing through the boiler.
WARNING
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings. This will result in complete piping system failure.
CAUTION
Installing Contractor is responsible for proper sealing of the water piping and electrical entries into the unit Failure to seal the entries may result in damage to the unit and property.
CAUTION
-
31
Temporary Drain – Evaporative
Condenser
The evaporative condenser design allows
rainwater to enter the sump tank during
transportation. AAON provides a temporary
drain system while the unit is in transit. The
temporary drain consist of an adapter that
will connect a hose from the sump drain to
the base drain. This temporary drain must be
replaced by permanent draining piping once
on site.
Figure 12 – Temporary Drain Components
Once the unit is ready for the permanent
draining, close the valve and remove the
temporary draining system. The components
that must be removed are those with number
callouts in Figure 12. The drain connection
for the permanent draining is 2” FPT.
Access Doors
Lockable access doors are provided to the
compressor and control compartment. A
light switch is provided on the wall of the
compressor and control compartment.
A separate access door is also provided to the
evaporator and pumping package
compartment. See Figure 36 for information
on leak checking these doors.
End Flashing Installation
On all LZ Series units the cabinet width will
overhang the shipping trailer on each side.
In order to secure and protect the unit during
transit the sheet metal end flashings have
been removed from the unit. The slot created
at the base of each end of the unit allows the
unit to set firmly on the trailer deck.
Sheet metal flashings are shipped loose with
the unit and once the unit is set into place the
flashings must be installed on each end of the
unit to complete the finished seal at the base.
The flashings are unit specific and designed
to cover the slot at each end of the unit to
prevent water run-off into the curb.
Failure to attach and seal the end of unit with
the flashings may result in water leakage into
the curb.
Figure 13 - Factory Supplied End Flashings
In order to prevent water leakage into the roof curb, the factory provided sheet metal flashings MUST BE attached to the unit base to cover the shipping slots at both ends of the unit.
CAUTION
-
32
Boiler Gas Connection Before making gas connection, make sure the
boiler is being supplied with the type of fuel
shown on the boiler nameplate.
Table 2 and Table 3 show the gas connection
size and type (NPT or flanged) provided
along with the required inlet gas pressure for
the unit. Refer to feature B on the LZ Series
unit feature string to determine which line of
the table to use. For example, a unit with
feature B = A3CC will have a 2” NPT gas
connection and require an inlet gas pressure
in the range of 6-14” W.C.
Use only pipe sealing compound that is
compatible with propane gases on all
threaded connections. Apply sparingly only
to the male threads of the pipe joints so that
the pipe sealing compound does not block
any gas flow.
Before being placed in operation, the boiler
and all gas piping connections must be
checked for leaks. The boiler must be
disconnected from the gas supply piping
system during any pressure testing of the
system at pressures in excess of .5 psig (14”
W.C.). The boiler must be isolated from the
gas supply piping system by closing the
manual shutoff valve during any pressure
testing of the system at pressures equal to or
less than .5 psig (14” W.C.).
Some leak test solutions, including soap and
water, may cause corrosion. These solutions
should be rinsed off with water after testing.
Boiler Air Intake / Vent Piping Each boiler requires the installation of air
intake and vent piping. This piping has been
removed for shipping purposes. All piping
must be reinstalled according to the
instructions provided in this section prior to
boiler operation.
All boilers must be vented and supplied with
combustion and ventilation air as described
in this section and in the Lochinvar
Installation & Operation Manual included
with the boiler. Ensure the vent and air
piping and combustion air supply comply
with instructions regarding vent system, air
system, and combustion air quality.
Inspect finished vent and air intake piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.
Failure to apply sealing compound as detailed can result in property damage, personal injury, or death.
WARNING
DO NOT use matches, candles, open flames, or other ignition sources to check for gas leaks. Use only approved leak detection methods. Failure to comply with this warning can result in property damage, personal injury, or death.
WARNING
Failure to provide a properly installed vent and air system can result in property damage, personal injury, or death.
WARNING
-
33
Table 2 - Unit Gas Pipe Information, Feature B4 = A-J
Heating Feature Boiler
Inlet Gas
Pressure
Gas Header
B1 B2 B3 B4 Size Qty
Input
Capacity
(CFH)
Pipe
Size
Conn.
Type
A 1 C or D A
KBN400
1 400 6-14” W.C. 1 NPT
A 2 C or D A 2 800 6-14” W.C. 1 1/2 NPT
A 3 C or D A 3 1,200 6-14” W.C. 2 NPT
A 4 C or D A 4 1,600 6-14” W.C. 2 NPT
A 1 C or D B
KBN501
1 500 6-14” W.C. 1 1/2 NPT
A 2 C or D B 2 1,000 6-14” W.C. 1 1/2 NPT
A 3 C or D B 3 1,500 6-14” W.C. 2 NPT
A 4 C or D B 4 2,000 6-14” W.C. 2 NPT
A 1 C or D C
KBN601
1 600 6-14” W.C. 1 1/2 NPT
A 2 C or D C 2 1,200 6-14” W.C. 2 NPT
A 3 C or D C 3 1,800 6-14” W.C. 2 NPT
A 4 C or D C 4 2,400 2-5 psi 2 NPT
A 1 C or D D
KBN701
1 700 6-14” W.C. 1 1/2 NPT
A 2 C or D D 2 1,400 6-14” W.C. 2 NPT
A 3 C or D D 3 2,100 2-5 psi 2 NPT
A 4 C or D D 4 2,800 2-5 psi 2 NPT
A 1 C or D F
KBN801
1 800 6-14” W.C. 1 1/2 NPT
A 2 C or D F 2 1,600 6-14” W.C. 2 NPT
A 3 C or D F 3 2,400 2-5 psi 2 NPT
A 4 C or D F 4 3,200 2-5 psi 2 NPT
A 1 C or D G
SBN1000
1 1,000 6-14” W.C. 1 1/2 NPT
A 2 C or D G 2 2,000 2-5 psi 2 NPT
A 3 C or D G 3 3,000 2-5 psi 2 NPT
A 4 C or D G 4 4,000 2-5 psi 2 NPT
A 1 C or D H
SBN1300
1 1,300 6-14” W.C. 2 NPT
A 2 C or D H 2 2,600 2-5 psi 2 NPT
A 3 C or D H 3 3,900 2-5 psi 2 NPT
A 4 C or D H 4 5,400 2-5 psi 2 NPT
A 1 C or D J
SBN1500
1 1,500 6-14” W.C. 2 NPT
A 2 C or D J 2 3,000 2-5 psi 2 NPT
A 3 C or D J 3 4,500 2-5 psi 2 NPT
A 4 C or D J 4 6,000 2-5 psi 2 NPT
-
34
Table 3 - Unit Gas Pipe Information, Feature B4 = K-N
Heating Feature Boiler
Inlet Gas
Pressure
Gas Header
B1 B2 B3 B4 Size Qty
Input
Capacity
(CFH)
Pipe
Size
Conn.
Type
A 1 C or
D K
FBN2000
1 2,000 2-5 psi 1 1/2 NPT
A 2 C or
D K 2 4,000 2-5 psi 2 NPT
A 3 C or
D K 3 6,000 2-5 psi 2 NPT
A 4 C or
D K 4 8,000 2-5 psi 3 Flange
A 1 C or
D L
FBN2500
1 2,500 2-5 psi 1 1/2 NPT
A 2 C or
D L 2 5,000 2-5 psi 2 NPT
A 3 C or
D L 3 7,500 2-5 psi 3 Flange
A 4 C or
D L 4 10,000 2-5 psi 3 Flange
A 1 C or
D M
FBN3000
1 3,000 2-5 psi 1 1/2 NPT
A 2 C or
D M 2 6,000 2-5 psi 2 NPT
A 3 C or
D M 3 9,000 2-5 psi 3 Flange
A 4 C or
D M 4 12,000 2-5 psi 3 Flange
A 1 C or
D N
FBN3500
1 3,500 2-5 psi 2 NPT
A 2 C or
D N 2 7,000 2-5 psi 3 Flange
A 3 C or
D N 3 10,500 2-5 psi 3 Flange
A 4 C or
D N 4 14,000 2-5 psi 3 Flange
-
35
Sidewall Direct Boiler Venting
For units with Lochinvar Knight XL and
SYNC boilers (feature B4 = A, B, C, D, E, F,
G, H, or K), the air intake and vent piping
runs from each boiler through the sidewall of
the unit into the supplied sidewall vent
termination.
1. On the sidewall above the boiler access
door, remove the shipping cover and attach
the sidewall vent plate shipped with the unit.
Figure 14 - Sidewall Vent Shipping Cover
Removal
Figure 15 - Sidewall Vent Plate Installation
2. Attach air intake piping to the air inlet
connector on the boiler at one end and run
through the sidewall of the unit at the other
end. All air intake pipes and fittings are
PVC.
Figure 16 - Typical Air Intake Piping
Use only primer and cement approved for use with PVC (ANSI/ASTM D2564).
WARNING
-
36
Figure 17 - Typical Flue Vent Piping
-
37
3. Attach vent piping to the flue pipe adapter
on the boiler at one end and run through the
sidewall of the unit at the other end. All Vent
pipes and fittings are CPVC. Vent piping
must be pitched at a minimum of 1/4 inch per
foot back to the boiler.
4. Install the vent and air intake piping
through the wall into the sidewall vent base.
Use RTV silicone sealant to seal the air
intake pipe. Mount and secure the sidewall
vent base using stainless steel screws. Seal
all gaps between the pipes and the sidewall.
Seal around the sidewall vent base to the wall
ensuring no air gaps.
5. Assemble vent cap to vent base and
securely attach using stainless steel screws.
Figure 18 - Sidewall Vent Base
Figure 19 - Sidewall Vent Cap
Vertical Direct Boiler Venting
For units with Lochinvar Crest boilers
(feature B4 = K, L, M, or N), the air intake
and vent piping is installed to run vertically
through the roof of the unit.
1. Remove shipping covers from openings in
the roof.
Figure 20 - Roof Air Intake and Vent Piping
Shipping Covers
Use only primer and cement approved for use with CPVC (ANSI/ASTM F493).
WARNING
-
38
2. Attach air intake piping to the air inlet
connector on the boiler and run vertically
through the roof of the unit. The air intake
pipes and fittings will either be all PVC or all
stainless steel components.
Figure 21 - Typical Vertical Air Intake Piping
For units with PVC piping, use only primer and cement approved for use with PVC (ANSI/ASTM D2564).
WARNING
JOINT CONNECTIONS The female end of each component incorporates a sealing gasket and a mechanical locking bond. Examine all components prior to installation. Gaskets must be in proper position to prevent leakage.
CAUTION
For units with stainless steel piping, all components must be installed in accordance with the manufacturer’s instructions to ensure all joints are secure and sealed correctly.
WARNING
-
39
3. Insert the male end into the female section.
Push the units together and turn them until
half of the bead on the male end is c