lynwood lighting design review final draft report · lighting design review ... 11 5 assessment...
TRANSCRIPT
PREPARED BY:
WEBB AUSTRALIA GROUP (ACT) PTY LTD ABN 14 064 354 776 [email protected] www.webbaustralia.com.au
SUITE 3, 10-12 COLBEE COURT PHILLIP ACT 2606 AUSTRALIA T +61 2 6285 4365 F + 61 2 6285 4253
CONSULTING ENGINEERS ELECTRICAL LIGHTING MECHANICAL SECURITY COMMUNICATIONS AUDIO VISUAL
BRISBANE CANBERRA GOLD COAST MELBOURNE NEWCASTLE SUNSHINE COAST SYDNEY
LYNWOOD
LIGHTING DESIGN
REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 2 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
LYNWOOD
LIGHTING DESIGN
REVIEW
FINAL DRAFT REPORT
Copyright © 2015 Webb Australia Group (ACT) Pty Ltd. All rights reserved.
This report may not be reproduced or transmitted in any
form or by any means in part or in whole without written permission of
Webb Australia Group (ACT) Pty Ltd ABN 14 064 354 776.
Issued As: PRELIMINARY
DRAFT
FINAL
Authorised By: JOHN GRIGGS
Date: 7 JULY 2015
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 3 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
TABLE OF CONTENTS
1 EXECUTIVE SUMMARY .....................................................................................................................5
2 INTRODUCTION ................................................................................................................................6
3 METHODOLOGY .................................................................................................................................7
3.1 REVIEW OF DOCUMENTATION PROVIDED............................................................................................... 7
3.2 DAY TIME SITE INSPECTIONS ................................................................................................................. 7
3.3 DESK TOP ANALYSIS OF THE EXISTING SITE LIGHTING INSTALLATION .................................................. 7
3.4 PRESENTATION OF DRAFT REPORT ......................................................................................................... 8
4 SITE ANALYSIS FINDINGS ...............................................................................................................9
4.1 EXISTING LIGHTING INSTALLATION ........................................................................................................ 9
4.2 EXISTING LUMINAIRE TYPES ................................................................................................................... 9
4.3 PHOTO GALLERY OF LUMINAIRES INSTALLED ...................................................................................... 10
4.4 COMMENTS ON EXISTING LUMINAIRE SELECTION .............................................................................. 11
5 ASSESSMENT CRITERIA................................................................................................................. 13
5.1 STANDARDS GENERALLY ..................................................................................................................... 13
5.2 MINIMUM REQUIREMENTS .................................................................................................................. 13
5.3 OBTRUSIVE LIGHTING MAXIMUM RECOMMENDATIONS ..................................................................... 15
6 DESK TOP ANALYSIS OF EXISTING LIGHTING ............................................................................... 16
6.1 FINDINGS BASED ON DESK TOP ANALYSIS .......................................................................................... 16
6.2 OVERALL SITE LIGHTING ANALYSIS ...................................................................................................... 16
6.2.1 Overall Site Horizontal Illuminance (Eh)............................................................................................. 16
6.2.2 OVERALL SITE VERTICAL ILLUMINANCE (Ev) ................................................................................... 19
6.2.3 Site Luminous Intensity (I) ............................................................................................................... 22
6.3 ADMINISTRATION AREA CAR PARK ..................................................................................................... 23
6.3.1 Analysis of Existing Carpark Lighting ................................................................................................ 23
6.3.2 Discussion on Application of Australian Standards to Carpark Lighting ............................................ 23
6.3.3 Concerns Identified relating to the existing Carpark Lighting ............................................................ 24
6.3.4 Carpark Lighting Options .................................................................................................................. 25
6.3.5 Response to Community Proposals .................................................................................................. 30
6.4 12M HIGH POLE MOUNTED ROADWAY AND AREA/ SITE LIGHTING ..................................................... 31
6.4.1 Existing Installation .......................................................................................................................... 31
6.4.2 Assessment ..................................................................................................................................... 32
6.4.3 Discussion On Impact of Lower Mounting Heights ........................................................................... 32
6.4.4 Recommended Lighting Measures .................................................................................................. 33
6.4.5 Additional Lighting Recommended .................................................................................................. 33
6.5 TYPICAL CONVEYOR GANTRY LIGHTING ............................................................................................... 34
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 4 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.5.1 Existing Installation .......................................................................................................................... 34
6.5.2 Assessment of Existing Gantry Lighting ........................................................................................... 34
6.5.3 Recommend Lighting Measures ...................................................................................................... 35
6.6 TYPICAL STACKER AREA FLOOD LIGHTING ........................................................................................... 35
6.6.1 Existing Installation .......................................................................................................................... 35
6.6.2 Assessment ..................................................................................................................................... 36
6.6.3 Recommended Lighting Measures .................................................................................................. 36
6.7 AREA LIGHTS ON BUILDING FACADES .................................................................................................. 36
6.7.1 Existing Installation .......................................................................................................................... 36
6.7.2 Assessment ..................................................................................................................................... 36
6.7.3 Recommended Lighting Measures .................................................................................................. 37
6.8 RAIL SIDING .......................................................................................................................................... 37
6.8.1 Existing Installation .......................................................................................................................... 37
6.8.2 Assessment ..................................................................................................................................... 37
7 CONCLUSIONS AND RECOMMENDATIONS ................................................................................... 38
7.1 ADMIN CARPARK LIGHTING (TYPE B AND C) ........................................................................................ 38
7.1.1 Lighting Measures ........................................................................................................................... 38
7.1.2 Alternative Measures ...................................................................................................................... 38
7.2 12M HIGH POLE MOUNTED ROADWAY AND SITE/ AREA LIGHTING ..................................................... 38
7.3 CONVEYOR GANTRY LIGHTING ............................................................................................................. 39
7.4 STACKER FLOOD LIGHTS ....................................................................................................................... 39
7.5 AREA LIGHTS ON BUILDING FACADES .................................................................................................. 40
7.6 SCREENING METHODS ......................................................................................................................... 40
7.7 COMMENTS ON DEVELOPMENT CONSENT CONDITIONS ..................................................................... 41
8 THE LIGHTING QUESTION ............................................................................................................... 42
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 5 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
1 EXECUTIVE SUMMARY
This report provides an assessment of the existing site lighting at the Lynwood quarry, identifies sources of luminance
that may be viewed from off-site and provides recommendations to prevent and/ or minimise their corresponding off-
site lighting impacts.
The report addresses the requirements detailed in the Lynwood Quarry Full Site Lighting Review Project Brief 25
November 2014. The report reviews and provides advice on the conformance of the As-Constructed lighting across
the total Lynwood site to relevant standards / guidelines including AS1158, AS1680, AS4284, the Holcim
Development Consent (in particular, condition 50) and other relevant standards/ Guidelines.
The Lynwood quarry is located approximately 3 km from the township of Marulan, NSW and a similar distance from
the Hume Highway. The location is set in a pristine rural environment where the natural beauty and the views are
what attracts people to this region.
The facility will be a 24 hour operation and due to the height of the facility and the surrounding topography, it will be
visible from distances exceeding 10km in some directions. This report recognises that visual lighting impacts will be
experienced from the quarry at various locations in the surrounding areas, particularly those at elevated positions.
From inspection, consultation and evaluation, these issues have been investigated through computer generated
calculations which model the effects of current and proposed luminaires. Lighting has been assessed against the
requirements of the Development Consent conditions and Australian Standards to minimise the night time visual
impact from the quarry.
The recommendations are focused on the various types of lighting technologies employed, and include:
Modifications to mounting arrangements and back light shield of the major area and road lighting luminaire
to eliminate sources of high luminance.
Removal and/ or replacement options for the carpark area lighting, including a reduction in mounting height
Removal of specific luminaires identified as not required and a source of offending luminance
Replacement of luminaires with lower wattage fixtures
Replacement of luminaires with LED light sources
Fixing the tilt angle to minimise luminous intensity and spill light
Introduction of lighting controls to ensure lights are only on when required
Introduction of dimming to reduce intensity when full output is not required
Provision of means of screening luminous surfaces and light sources from view
Such recommendations are intended to provide Holcim with the tools from which they can select, as their preferred
options for satisfying the Development Consent conditions.
The report leaves the assessment of each recommendation up to Holcim to determine whether it is deemed
practicable, or otherwise.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 6 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
2 INTRODUCTION
Holcim Australia engaged the services of Webb Australia Group to undertake a review of all the existing external
lighting at Lynwood Quarry and identify all reasonable and feasible opportunities to reduce/ eliminate any potential
light spillage, obtrusive lighting, prevent and/ or minimise adverse off-site lighting impacts with respect to operations,
safety and legal requirements.
Provision of adequate illumination and the need to ensure a safe visual working environment is a challenge faced by
almost all industries. The primary objectives of lighting and illumination in the workplace are generally to provide a
safe working visual environment and increase production. Lighting is particularly important in the mining industry, as
visibility is paramount to safety where large machines operate in a dusty and a potentially dangerous environment,
often 24 hours a day.
Mine/ quarry sites are often in remote locations, but where such sites are surrounded by a pristine rural environment
such as Lynwood, in which the view and natural beauty are pivotal to the local inhabitants, constraints need to be
imposed on the obtrusive effects of any outdoor lighting. A typical dilemma lighting designers have to deal with is to
find the most appropriate balance between the apparent competing objectives of limiting obtrusive lighting to
acceptable levels while ensuring a visual environment is maintained.
Note Webb Australia were not the lighting designers for the site, but were engaged to provide an independent review
of the existing installed lighting.
This report addresses the requirements detailed in the Lynwood Quarry Full Site Lighting Review Project Brief 25
November 2014 and in summary, includes the following:
An assessment of compliance of all external lighting across the Lynwood site with regard to relevant
standards/ guidelines and condition 50 of the Holcim Development Consent conditions.
Recommendations of options for improvement with respect to the above.
Identification of practicable opportunities to eliminate and / or minimise off-site lighting impacts, with
respect for operations, safety and legal requirements.
An analysis of the lighting trial of November 2014 where lamps were removed and selected lights were not
energised.
A review of the proposed recommendations in the “Lighting Assessment Action Plan” prepared by Holcim
operations personnel in response to observations of the above lighting trial.
A response to the “Lighting Question” Holcim received from the local Community.
Inclusion of a Lighting Action Plan with assigned priorities.
The Draft Report was presented to the Towrang Community at a public meeting on 13 March. Responses to
questions arising from this presentation were incorporated into the Final report (dated 14 April 2015).
Subsequent comments were tabled by the Towrang Community Progress Group (TCPG)on the “Final Report”. Webb
Australia’s responses to those comments are incorporated into the text of this Final Draft report and also included
separately at Appendix P.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 7 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
3 METHODOLOGY
The methodology adopted in the preparation of this report has been summarised as follows:
3.1 REVIEW OF DOCUMENTATION PROVIDED
The documentation provided included:
GHD lighting design drawings as follows:
21-19682-E150 Rev: A dated 21.11.13
21-19682-E151 Rev: A dated 21.11.13
21-19682-E152 Rev: A dated 21.11.13
21-19682-E153 Rev: A dated 21.11.13
Lighting Trial drawings:
21-19682-E151.T
21-19682-E152.T
21-19682-E153.T
Plus 30 Metso plant drawings
3.2 DAY TIME SITE INSPECTIONS
Day time site inspections were conducted on:
29, 30 January 2015
5 February 2015
The daytime site inspections identified the drawings provided did not reflect the existing lighting installation. The
Road and area lighting installation was found to differ from design drawings provided.
A survey of light pole locations was conducted by a surveyor and an inspection conducted to determine installed
luminaire orientations.
Exterior flood lights on buildings, on the end of stackers and lights on the conveyors systems were also noted and
documented.
As no site lighting was turned on, no night time inspection was conducted.
3.3 DESK TOP ANALYSIS OF THE EXISTING SITE LIGHTING INSTALLATION
The desk top analysis was undertaken using:
AGi32 lighting modelling software
Perfect Lite Software
AutoCAD
More recent background drawings were provided for use in the model.
Details of luminaires, locations and orientation, etc obtained from the site inspections was entered into the computer
model for computation.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 8 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
A range of calculations were undertaken for various areas including:
Horizontal illuminance for the site
Vertical illuminance for the site
Carpark lighting compliance calculations
Pseudo colour images of calculated results
Rendered views from off-site locations
Illuminance calculation of the conveyor gantry and corresponding rendered image
Areas of non-compliance with minimum requirements were identified.
Areas where light levels were found to be excessive were identified.
A range of options were explored to provide recommendations to improve the lighting installation with respect to the
brief requirements, based on the desktop analysis.
3.4 PRESENTATION OF DRAFT REPORT
The draft report was presented to members of the Towrang Community Group and representatives from Holcim in a
public forum at the Towrang Community Hall on the evening of 13 March, 2015.
Questions were raised by members of the Community and subsequently compiled by Holcim and forwarded to Webb
Australia on 20 March, 2015. This correspondence is included in full at Appendix N.
This Final Draft report incorporates a response to the matters raised by the Community consultation process and is
further progressed to include a Lighting Action Plan (refer Appendix J).
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 9 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
4 SITE ANALYSIS FINDINGS
4.1 EXISTING LIGHTING INSTALLATION
Site survey information collected onsite has been documented in Appendix A.
4.2 EXISTING LUMINAIRE TYPES
Existing lamps and luminaire types identified on site are shown in the following table:
Legend
Item
Application Lamp type and Luminaire description Luminaire
classification as per
AS 4282 / AS 1158
Quantity
A Roadway and
Area Lighting
2 x 400W MH (1 lamp removed) full cut-off
floodlight mounted at 12m – Pierlite Tarmac
APR-2 x 400 MH fitted with back light shield
and tilted 50
Type C cut-off/ type 6 54
B Carpark Lighting
and Admin
Quadrangle
400W MH full cut-off flood light mounted at
10m – Pierlite Max Master GMRS 400 MH
fitted with back light shield and tilted 50
Type C cut-off/ type 6 10
C Carpark Lighting 150W MH full cut-off flood light mounted at
8.0m Pierlite Mini Master GMRA 150 MH (no
back light shield fitted)
Type C cut-off/ type 6 2
D Flood Light on
building facade
250W MH Eye Flood light or 400W MH
Pierlite full cut-off flood light – Maxi Master
GMRA 400 MHR
Type C / type 5 10
F Flood Light on
end of stacker
400W MH full cut-off flood light – Pierlite
Maxi Master GMRS 400 MH
Type C / type 5 11
G Stacker Gantry
Lighting
70W MH industrial luminaire with prismatic
diffuser Pierlite MRA 70 H2, or Philips Metro
HGC007
- / type 4 338
H Railway Siding
Lighting
2 x 24 W T5 linear fluorescent industrial
luminaire with prismatic diffuser mounted at
5m. Pierlite Green Street
- / type 4 10
J Stairs Lighting 2 x 18W and 2 x 36W T8 fluorescent
industrial luminaire with prismatic diffuser –
Pierlite PWP
- / - Not
known
Luminaire manufacturers’ data sheets of the various luminaire types have been incorporated at Appendix B for
additional information.
Refer to drawings ES-01 and ES-02 at Appendix A for luminaire locations and arrangement.
Photos of typical examples of the various luminaire types are shown below:
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 10 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
4.3 PHOTO GALLERY OF LUMINAIRES INSTALLED
Type A Type B
Type C Type D
Type F Type G
Type H Type J
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 11 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
4.4 COMMENTS ON EXISTING LUMINAIRE SELECTION
Refer to manufactures luminaire data sheets at Appendix B for more details on luminaires installed.
Luminaire Type A
Type A luminaire is a 400W flat glass, full cut-off aeroscreen luminaire which emits no light above the
horizontal, even when tilted at 50
above the horizontal.
The light distribution is a forward throw with good back light control beyond 200
. This luminaire is
particularly suited to large area lighting applications where glare needs to be controlled.
It is not particularly suited to a roadway lighting application. Roadway lights typically have a wide side throw
asymmetric distribution to suit that application.
Type A luminaires have been installed along Lynwood Road, the access road to the Admin carpark and other
area lighting locations.
Luminaire Types B, D & F
Type B, D and F luminaires are 250W or 400W flat glass full cut-off aeroscreen luminaires, which emits no
light above the horizontal, even when tilted at 50
above the horizontal.
The Light distribution is asymmetric forward throw and is suited to area lighting. It has poor back lighting
control and is not suited to locations where back spill light may be undesirable.
This luminaire is also available with an asymmetric side throw distribution (GMRA), which is better suited to
carpark lighting than the model installed, however the entire luminaire would need to be replaced to change
over to this fixture.
Type B luminaires have been installed at the Admin building carpark. Types D and F have been installed on
building facades as area lights and at the end of stackers, to illuminate the product stack areas.
Luminaire Type C
Type C luminaire is a 150W flat glass, full cut-off aeroscreen luminaire, which emits no light above the
horizontal, even when tilted at 50
above the horizontal.
The light distribution is a symmetrical forward throw with good back light control beyond 400
.
Two only of these luminaires have been installed at the northern end of the Admin building carpark on 12.5m
poles.
Calculations have demonstrated these luminaires are suitable for the carpark lighting application. Refer
below for more detailed information on this topic.
Luminaire Type G
Two very similar luminaires from two different manufacturers are used for type G applications, i.e. conveyor
gantry lighting.
These fixtures are 70W industrial luminaires with a clear refractor lens, suited for this application.
The Pierlite model has a wide side throw asymmetric distribution with 1% UWLR.
When tilted and rolled, the upward waste light component increases, especially when the roll is more than
50
.
Emergency lights are typically the Philips model, as shown in the photo at section 4.3.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 12 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
Luminaire Type H
Type H luminaire is a 2 x 24W high output T5 fluorescent luminaire with a prismatic refractor lens and good
upward light control.
The light distribution is asymmetric wide side throw with poor back light control, suitable for applications
where backward spill lighting is desired.
These luminaires are located along the rail siding corridor.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 13 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
5 ASSESSMENT CRITERIA
5.1 STANDARDS GENERALLY
An investigation into lighting standards that are applicable to surface mines and quarries has identified that there is
no Australian Standard that is specifically dedicated to this application. However, there are lighting applications on
the Lynwood site to which minimum and maximum lighting design criteria are applicable, from a number of sources.
These sources are identified below.
5.2 MINIMUM REQUIREMENTS
Safety is identified as the primary purpose of lighting in Min Ex Guideline – Surface Mines and Quarries. Clause
7.1A states:
“The lighting provisions for all workplaces, travelling ways and fixed installations should be designed so that
all activities can be carried out safely”.
Note the document referenced above is a Surface Mining and Quarrying Industry Code of Practice, it is not a Lighting
Standard. The above quotation is a general principle with no quantifiable requirements stated. Other than a
reference to emergency lighting, the above document makes no further reference to lighting requirements, so this
report looks elsewhere for assessment criteria.
In the absence of any Australian Standard specifically dedicated to the lighting of quarries, this report provides an
assessment of the external lighting at the Lynwood quarry against the minimum requirements of the following:
AS 1158.2: Part 2 – Computer procedures for the calculation of light technical parameters for category V
and category P lighting
AS 1158.3.1: Part 3.1 – Pedestrian area (category P) lighting – performance and installation design
requirements
AS 1680.2.4 – Interior and workplace lighting Part 2.4 Industrial tasks and processes
AS 1680.5 – Interior and workplace lighting Part 5: Outdoor work place lighting
The assessment criteria for minimum requirements are summarised in the following table.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 14 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
Minimum Illuminance Requirements
Area
Minimum Average Maintained Horizontal Illuminance (Lux)
AS 1680.
2.4:1997
AS 1158
.3.1:2005
CIE129:
1998
BMA
Coal
GHD
Design
AS
1680.5:
2012
Assessment
Criteria
Adopted
Railway Freight track areas 10 10
Access roadways 7(Cat P1) 20 10 7
Intersections 40 40
Light vehicle carparks 7 (Cat
P11b)
10 7
Heavy vehicle areas 30 30
Stockpiles 30 30
Water Pumping Stations 40 40
Materials handling- wagon
loading & unloading
40 50 40
Weighbridge, refuelling, truck
wash
60-80 60
Open area, machines (site
inducted personnel)
10 10
Conveyors & gantries 40 40
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 15 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
5.3 OBTRUSIVE LIGHTING MAXIMUM RECOMMENDATIONS
The external lighting is also assessed against the maximum recommendations of the following:
AS 4282 Control of obtrusive effects of outdoor lighting
Holcim Development Consent Conditions (in particular, condition 50)
AS 4282 applicable recommendations:
The maximum values recommended by AS 4282 applicable to this site are summarised as follows:
Curfewed Hours Dark Surrounds
Illuminance in vertical plane (Ev) Limits apply in plane of windows of habitable
rooms or parallel to and set back from
property boundary
1 lux
Luminous Intensity emitted by
luminaires
Limits apply where views of bright surfaces
of luminaires are likely to be troublesome to
residents, from positions where such views
are likely to be maintained
500cd
Clause 5.3.1of the Standard stipulates the limiting value of luminous intensity during curfewed hours applies for each
luminaire.
Also no determination of luminous intensities need be made where the luminaires cannot be seen from direction of
concern due to physical obstructions.
Threshold Increment (TI) is another LTP criteria referred to in AS 4282 to measure obtrusive light. TI is a measure of
disability glare and is applicable to users of transport systems from relevant positions in the direction of travel. As the
scope of this report was concerned primarily with obtrusive lighting when viewed from off-site, TI has been ignored
and not been calculated.
Refer to Appendix K for the full text of the relevant portion of the Standard.
Holcim Development Consent Conditions, condition 50:
Condition 50 of the Holcim Development Consent Conditions states:
“The Applicant shall take all practicable measures to prevent and/ or minimise any off-site lighting impacts
from the development”.
Note: AS 4282 provides recommendations of minimum light technical parameters (LTPs) that are intended to restrict
limits to a degree of obtrusiveness that would be acceptable to the large majority of recipients. Condition 50 of the
Development Consent goes beyond this degree to “prevent and/ or minimise any off-site lighting impacts” by taking
all practicable measures to do so. The condition aims to reduce the LTPs to zero, wherever practicable and to a
minimum (less than AS 4282 levels) elsewhere. Satisfying condition 50 is more onerous than complying with AS
4282.
Holcim Development Consent condition 50 does not include any assessable criteria against which compliance can be
assessed by Webb Australia.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 16 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6 DESK TOP ANALYSIS OF EXISTING LIGHTING
6.1 FINDINGS BASED ON DESK TOP ANALYSIS
As describe in Section 3 above, no night time/ visual inspections were conducted and Webb were limited to
undertake a desk top analysis based on day time, site observations and site information provided by Holcim.
The Webb findings did not have the benefit of a night time, visual assessment, either from within the site or from the
nominated off-site viewpoints. However, the results of the calculations undertaken as part of the disk top analysis
are considered accurate and the findings are considered reliable.
The desk top analysis examines and provides and assessment the following against the project brief criteria:
Overall site lighting
Overall site horizontal illuminance (Eh)
Overall site vertical illuminance (Ev)
Overall site luminous intensity (I)
Admin carpark lighting
12m high pole mounted roadway and site area lighting
Typical conveyor gantry lighting
Typical stacker area flood lighting
Area lights on building facades
Rail siding lighting
6.2 OVERALL SITE LIGHTING ANALYSIS
6.2.1 Overall Site Horizontal Illuminance (Eh)
The horizontal illuminance calculation for the existing site installation is with one lamp removed from all 58 of the 2 x
400W Pierlite Tarmac fixtures (type A), to be consistent with existing site conditions.
A rendered image and a pseudo-colour image of the horizontal illuminance of the existing lighting is included below.
The 1 lux vertical illuminance is a criterion for compliance with obtrusive lighting, but it is the horizontal illuminance
that can be seen by observation. Consequently, the 1 lux horizontal illuminance isoline is significant, as it
demonstrates that the horizontal illuminance falls away quickly generally within the site boundary and goes nowhere
near approaching a residence.
The notional site boundary is selected as the extremity of the site and if the levels satisfy AS 4282 requirements at
this location, then it also demonstrates compliance is achieved anywhere beyond that point.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 17 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
RENDERED IMAGE
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 18 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
PSEUDO-COLOUR IMAGE
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 19 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
The drawings ES-03 and ES-04 at Appendix C show the calculated isolux plot for the existing site horizontal
illuminance. The following observations are made:
1. Range: 0-225 lux
2. Highest value is located north of the Workshop building.
3. The 1 lux isoline is generally contained within the nominal site perimeter, with the following exceptions:
a. Extends up to 20m beyond the western perimeter, near the southern entry to the site
b. Extends up to 10m beyond Western perimeter near Admin carpark
c. Extends a few metres beyond the railway line along the southern site perimeter
4. The highest horizontal illuminance value at the nominal site perimeter is less than 10 lux, occurring near the
southern site entry, opposite the refuelling station.
5. The Upward Waste Light Ratio (UWLR) for the overall site is 2.3%. This is below the maximum value of 3%
for type 5 luminaires recommended by AS 1158.3.1. (Luminaire types A, B, C, D & F may be classified as
type 5 luminaires.)
Assessment
The calculated values of horizontal illuminance across the site have been assessed against the selected criteria.
The minimum horizontal illuminance requirements have generally not been achieved. Refer to Table at Appendix G
for details.
Note: This assessment is against minimum values. Holcim Consent Condition 50 relates to maximum levels so an
assessment against the condition is not provided here.
6.2.2 OVERALL SITE VERTICAL ILLUMINANCE (Ev)
The vertical illuminance calculation of the existing site installation is with one lamp removed from all 2 x 400W
Tarmac (type A) luminaires. The light loss factor used for the vertical calculation is unity (1.0).
The drawings ES-05 and ES-06 at Appendix C show the calculated vertical illuminance at 1.5m above the ground for
the four quadrants or points of the compass.
Rendered images of the existing site lighting when viewed from an elevated position from north, west, south and east
are shown below.
Note, the distance from the site of these viewpoints is undeterminable. The views below are zoomed in to enable
detail of the site lighting to be seen, but as they are magnified, they do not give an actual representation of what
would be seen by the unassisted viewer (i.e. without binoculars) located at any of the nominated off-site locations.
These views do however provide a more reliable impression than Community photographs as they incorporate the
contribution from all the external luminaires on the site. The views are magnified to provide more detail, as are the
community photographs.
For rendered images of views of the quarry site lighting from the nominated off-site locations, refer to Appendix D.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 20 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
NORTH WEST
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 21 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
SOUTH EAST
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 22 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
For further rendered images of the site when viewed from seven nominated off-site locations, refer to Appendix D2.
The locations are identified on drawing ES-07 at Appendix D1.
From a review of the vertical illuminance calculations shown on drawings at Appendix C2, the following observations
are made:
The 1 lux vertical illuminance isoline is generally contained within the nominal site perimeter, with the
following exceptions:
a) Extends up to 35m beyond the western perimeter near the southern entry to the site.
b) Extends up to almost 20m beyond the western perimeter near the Admin carpark.
c) Extends up to 20m beyond the railway line along the southern site perimeter.
The highest vertical illuminance at the nominal site perimeter is between 10 and 20 lux, occurring near the
southern site entry, opposite the refuelling station.
Assessment
The calculated values of Vertical illuminance across the site and beyond the site boundaries have been assessed
against the selected criteria.
The maximum value of vertical illuminance (1 lux) recommended by AS 4282 at residential viewpoints was found to
extend marginally beyond the notional site boundary but complies with the selected criteria at all off-site viewpoints.
Refer to Table at Appendix G for details.
6.2.3 Site Luminous Intensity (I)
The selected criteria for luminous intensity is 500 Cd. This criteria is applicable to residential areas with dark
surrounds during curfewed hours. The limits apply in directions where views of bright surfaces of luminaires are likely
to be troublesome to residents, from positions where views are likely to be maintained.
The limiting value of luminous intensity applies for each luminaire.
Provided ALL luminaires on the site are aimed such that the luminous intensity of each luminaire in the direction of
residents is controlled below 500 Cd, then the site lighting complies with the selected criteria.
As the peak intensity of all luminaires on the site exceeds 500 Cd, aiming of each luminaire is critical to satisfying this
criteria.
Assessment
As the luminous intensity criteria is applicable to each luminaire, the assessment for compliance against the selected
criteria can only be applicable to each luminaire and collectively, for each luminaire type. Consequently assessment
of compliance against the luminous intensity criteria is provided for each luminaire type in the sections that follow
that examine specific applications.
Calculations confirm the luminous intensity of all the site lighting luminaires are AS 4282 compliant beyond 1000m
from the plant area. As all the nominated viewpoints are much further from the site, the luminous intensity of these
luminaires is also compliant with the requirements of AS 4282. Refer to Table at Appendix G for details.
Holcim Development Consent condition 50 does not include any assessable criteria against which compliance can be
assessed by Webb Australia.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 23 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.3 ADMINISTRATION AREA CAR PARK
6.3.1 Analysis of Existing Carpark Lighting
The calculated Light Technical Parameters (LTPs) for the existing car park lighting are shown in the following table
with the minimum requirements of AS1158.3.1 for lighting subcategory P11a and P11b.
The recommended design criteria for the car park lighting is subcategory P11b.
Average Horizontal
Illuminance
(Eh)
Point Horizontal
Illuminance
(Eph
)
Illuminance
(horizontal)
Uniformity (UE2
)
Point Vertical
Illuminance
(Epv
)
P11a 14 3 10 3
P11b 7 1.5 10 1.5
Calculated values 40 3.6 1.9 5.6
The calculated values clearly demonstrate the existing car park lighting exceeds the minimum requirements for
lighting subcategory P11b and also achieves compliance with the minimum requirements of lighting subcategory
P11a.
Subject to acceptance of the recommendation to classify the minimum requirements of the car park lighting to
subcategory P11b, there is opportunity to reduce the existing lighting while maintaining compliance with P11 b
requirements.
6.3.2 Discussion on Application of Australian Standards to Carpark Lighting
As part of the lighting review, Webb Australia conducted an assessment of the car park to determine the appropriate
assessment criteria to apply to the existing lighting installation.
Our assessment for determination of the appropriate lighting subcategory for the car park was based on the
application of Table 2.5 (Lighting categories for outdoor car parks) of AS1158.3.1 (Lighting for roads and public
spaces), as follows:
Selection Criteria Assessment
Night time vehicle or pedestrian movements Medium
Night time occupancy rates (NTOR) More than 25%
Less than 75%
Risk of crime Low
Based on the above assessment, the application of lighting subcategory P11b was recommended.
The minimum average horizontal illuminance for a car park lighting installation to subcategory of P11b is 7 lux and the
minimum point horizontal and vertical illuminance is 1.5 lux.
The minimum average horizontal illuminance for a car park lighting installation to subcategory of P11c is 3.5 lux and
the minimum point horizontal illuminance is 0.7 lux. There is no minimum vertical illuminance criteria for subcategory
P11c.
Members of the Community challenged the position of treating the car park as a public car park, asserting that it was
a private car park and therefore, did not have to comply with the public lighting code.
In our professional opinion, if the function of the car park includes the provision of night time parking for visitors or
contractors or staff whom may be unfamiliar with the site, then the car park must be treated as a public car park and
AS1158 is applicable.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 24 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
From discussions with representatives from Holcim, we understand there will be truck drivers, maintenance
personnel and contractors using the car park at night, some of whom may be doing so for the first time and may be
unfamiliar with the site. There is also the possibility of visitors attending at night. With heavy vehicle traffic entering
and leaving the site on a regular basis, we understand there will be no security staff monitoring site entry and exit,
consequently members of the public will not be actively prevented from accessing the site or from using the car park
at night.
From our understanding of the access to and potential use of the car park, we believe Holcim are obliged to provide a
safe space for parking at night. The applicable Australian Standard is AS1158 Lighting for roads and public spaces
Part 3.1 Pedestrian area (Category P) lighting – Performance and design requirements.
The above standard defines three lighting subcategories relating to car parks, P11a, b and c.
As indicated above, our initial recommendation for the car park was P11b.
Holcim have confirmed the night time occupancy rate of the car park will exceed 25% and is more likely to be in the
order of 70% when the site is fully operational. Based on this information, we would not endorse the application of a
P11c lighting subcategory, as the occupancy rate of the car park is likely to exceed 25% at night.
Recommendation
In conclusion, it is the recommendation of this report that AS1158.3.1 is applicable to the Administration building car
park and the recommended lighting subcategory is P11b.
6.3.3 Concerns Identified relating to the existing Carpark Lighting
The existing car park lighting has been identified as a source of illumination that is contributing to the luminance of
the adjacent Admin building façade and to the roof of the nearby section of covered way.
The luminaire on pole L47 that faces the Admin building illuminates the roof of the Admin building to a level exceeding
30 lux, making it clearly visible from elevated positions off site. The contribution to the illumination of the Admin
building roof from L48 is considered minor and of little significance.
As the Administration building roof is clearly visible from a number of locations off-site, the strategy for reducing the
lighting of the car park must also consider the impact of the proposal on the luminance of these surfaces.
The technical solutions that are recommended in this section of the report are aimed at complying with the minimum
requirements of AS 1158.3.1 and preventing and/ or minimising any off-site lighting impacts to provide Holcim with
options to satisfy the Development Consent conditions.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 25 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.3.4 Carpark Lighting Options
Two options have been investigated to address the above concerns, as follows:
Carpark Option 1: Replace existing 400W luminaires with new 150W luminaires
Carpark Option 2: Remove alternate light poles L36, L38, L40, L42
AGi32 lighting calculations demonstrating compliance for both options 1 and 2 are at Appendices F and G
Rendered images and pseudo colour images are shown below to enable a comparison of the existing installation and
each of the two lighting options:
FIG. 1: CAR PARK - EXISTING INSTALLATION: RENDERED PLAN VIEW IMAGE
FIG. 2: CAR PARK – EXISTING INSTALLATION: RENDERED VIEW FROM WEST
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 26 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
Fig. 3: Car park – Existing installation: Pseudo colour view from west
An analysis of the above rendered and pseudo-colour images will identify high luminance on the nearby section of the
Admin building façade, on the far section of roof of the Admin building and the highest on the roof of the covered
way.
Carpark Option 1: Replace existing 400W luminaires with new 150W Mini Master luminaires
The car park lighting has been reviewed and found it is possible to maintain code compliance by replacing the 400W
luminaire with 150W luminaires. The major benefit of this is the reduction of spill light onto the Administration
building façade and roof.
Option 1 includes:
the removal of the existing 400W luminaires and
provision of new 150W Pierlilte GMRA Mini Master luminaires on existing poles
removal of one 400W Pierlite Maxi Master from Pole L47 (that faces the Admin building)
The following images have the luminaire on pole L48 that faces towards the Amenities building also turned off, but
the above images where it is on do not show this luminaire having a significant detrimental effect on the illumination
of the roof of the Amenities building. Consequently, this luminaire on L48 may remain and its impact be reassessed
by a visual inspection.
Refer to Appendix H1 for AGi32 calculation demonstrating compliance of Option 1 with AS1158.3.1 lighting
subcategory P11b requirements.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 27 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
FIG. 4: CAR PARK – OPTION 1: RENDERED PLAN VIEW IMAGE
FIG. 5: CAR PARK – OPTION 1: RENDERED VIEW FROM WEST
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 28 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
FIG. 6: CAR PARK – OPTION 1: PSEUDO COLOUR VIEW FROM WEST
The above views at Fig. 5 and fig.6 show a much improved installation with substantially reduced luminance of the
surfaces of concern when compared with the existing installation at Fig. 2 and Fig 3.
There is still some spill light noticeable from the light remaining on pole L47 that faces away from the admin building.
This may be addressed by:
providing a generous custom back light shield on this luminaire
or
replacing the existing 400W Pierlite Maxi Master with a 400W Pierlite Tarmac
(as the Tarmac has far superior back light control to the Maxi Master).
An added benefit of this choice would be the improved illumination of the area east of the Admin building, as the
Tarmac has a much more forward throw than the Maxi Master.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 29 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
Carpark Option 2: Remove alternate light poles L36, L38, L40, L42
Option 2 includes:
the removal of the existing 400W luminaires and poles at L36, L38, L40 and L42
removal of one 400W Pierlite Maxi Master from Pole L47 (that faces the Admin building)
The following images have the luminaire on pole L48 that faces towards the Amenities building also turned off, but
the above images where it is on do not show this luminaire having a significant detrimental effect on the illumination
of the roof of the Amenities building. Consequently, this luminaire on L48 may remain and its impact be reassessed
by a visual inspection.
Refer to Appendix H2 for AGi32 calculation demonstrating compliance of Option 2 with AS1158.3.1 lighting
subcategory P11b requirements.
FIG. 7: CAR PARK – OPTION 2: RENDERED PLAN VIEW IMAGE
This view demonstrates the lighting is noticeably patchy and the uniformity is not as good as it is in Option 1.
The views at Fig. 8 and Fig.9 show a much improved installation with substantially reduced luminance of the surfaces
of concern when compared with the existing installation at Fig. 2 and Fig 3.
The luminance of the nearest section of the Admin building façade is to L41 is lower than from the existing lighting
but higher than Option 1. The provision of custom horizontal louvre type back light shield on pole L41 may address
this problem.
There is also some spill light noticeable from the light remaining on pole L47 that faces away from the admin building.
This may be addressed as described above for Option 1
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 30 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
FIG. 8: CAR PARK – OPTION 2: RENDERED VIEW FROM WEST
FIG. 9: CAR PARK – OPTION 2: PSEUDO COLOUR VIEW FROM WEST
From the above assessment, Option 1 is the preferred option.
6.3.5 Response to Community Proposals
Comments from the Community with respect to the alternative approaches to the carpark lighting have included the
following:
a) Use shorter poles in lieu of taller poles
b) Trial of 3 or so lights at reduced height (say 4m)
c) Use of ground mounted lights
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 31 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
Webb’s response to the above comments are as follows:
a) Pole heights could be reduced from 8m to a minimum of 5m and still satisfy Australian Standard (code)
requirements however this would require additional lights and the number of poles would increase from
eight (8) at least ten (10)
b) Code compliance could not be achieved using mounting heights below 5m, so a trail of 3 lights at 4m is not
recommended
c) Ground mounted lighting would not satisfy code requirements and is not recommended
6.4 12M HIGH POLE MOUNTED ROADWAY AND AREA/ SITE LIGHTING
6.4.1 Existing Installation
The 2 x 400W Pierlite Tarmac luminaire (type A) mounted on 12m poles is the typical luminaire installed for general
pole mounted area lighting and roadway/ intersection lighting and heavy vehicle parking areas.
The original lighting design included both 400W lamps, however, upon our inspection, we were advised one of the
400W lamps had been removed from all of these twin lamp luminaires.
The light output from these luminaires would have been reduced accordingly.
As there is no IES file available for these luminaires with only one lamp fitted, our calculations are an approximation
with the lumen output adjusted to reflect one lamp being removed.
As identified in Section 4, these luminaires are exceptionally well suited to large area lighting with a forward throw
distribution. With an UWLR of zero, no light is emitted above the horizontal and they have good back light control.
The Tarmac luminaire is not suited for roadway applications. The site lighting has been limited to targeted locations
so that there are parts of the site where there is no lighting. Not all roadways are provided with lighting and not all
open areas are illuminated. The existing site lighting has been selectively applied to suit the operational requirements
of the site. This would explain why the Tarmac luminaire was selected for this application.
12m Roadway/ site lighting has been installed to meet site night time operational requirements and does not appear
to have been designed to satisfy the requirements of Australian Standard AS 1158. The lighting installation appears
to have targeted areas of night time activity rather than applying lighting generally throughout the road network
across the site. For example, such lighting has been provided for the following areas:
Access roadway
Refuelling station
Vehicle weighbridge
Product weighbridge
Intersections
Areas of elevated pedestrian activity, such as around the Admin building, etc
Lighting has not been provided for substantial sections of Lynwood Road and subsidiary roadways.
As these luminaires are mounted on 12m poles, they are visible from virtually all directions off-site. Their sharp cut-
off characteristics mean that there is no direct view of the lamp, but as there is a pole and often other supporting
structure below the lens, these objects are what can be seen from off site. (Refer to the answer to the lighting
question in Section 8 for further explanation).
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 32 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.4.2 Assessment
The areas covered by the roadway and area/ site lighting include the following:
Access Roadway
Intersections
Heavy vehicle areas
Water Pumping Station
Weighbridge
Refuelling Station
Vehicle wash bay
Open areas
The existing lighting for many of these areas does not comply with the minimum lighting assessment criteria.
The provision of additional lighting in these areas is an operational matter for Holcim and is considered outside the
scope of this report. Refer to Table at Appendix G for more details.
6.4.3 Discussion On Impact of Lower Mounting Heights
Lighting may be provided at a lower mounting height, but this will require more lights and more poles than the
existing 12m mounting height arrangement to achieve the minimum required lighting design criteria.
For the heavy vehicle parking area to be illuminated using luminaires at a lower mounting height, additional luminaires
on the opposite side of the parking area will be required. These additional luminaires will need to be aimed toward
the western site boundary, exacerbating the off-site lighting impacts.
The above outcomes would be considered counterproductive with respect to the intended purpose of reducing off-
site lighting impacts.
As the main area/roadway (type A) luminaires are flat glass aero-screen type fixtures that emit no light above the
horizontal, it would be ideal if they could be located below the height of the off-site viewing positions to minimise
corresponding off-site lighting impacts.
By comparing topographical information with elevations of the surrounding off-site locations, it is evident that five (5)
of the seven locations are below the elevation of the highest pole mounted light on the site. (Refer to drawing ES-07
for more information.)
Point E is the lowest location at 57m below the level of the highest pole mounted luminaire. The actual angle relative
to the horizontal plane has been calculated for each site. The largest angle calculated (at point C) is 0.74O
below the
horizontal plane. Due to their distances from the site, all of the off-site locations are less than 1O
below the highest
pole mounted luminaire or above it.
Due to the elevation of the off-site locations relative to the site, it would not be possible to locate the luminaires at an
elevation below these points simply by reducing the luminaire mounting height.
An examination of type A luminaire I-Table was conducted and over laid on drawing ES-07 to check luminous
intensities directed toward the nominated off-site locations at their respective elevations. It was concluded that no
light emitted directly from the existing type A luminaires would reach any of the nominated off-site viewpoints.
The only light that would be visible from these locations would be indirect or reflected light. Subject to resolving the
mounting arrangements as recommended, the most significant source of reflected light visible from the nominated
off-site viewpoints would be the poles.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 33 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
Reducing the height of the poles would reduce the length of the poles that may be visible, however, the brightest,
most visible section of the pole would be at the top, nearest the luminaire. Where the upper section of the poles are
still within view, reducing the height of the poles would only remove the bottom section from view by lowering the
upper section. The brightest section at the top of the pole would remain in view. Consequently, the reduction in off-
site lighting effects due to highly illuminated pole surfaces achieved by reducing the height of the poles is considered
minor to inconsequential.
In summary, the impact of lowering the mounting height of the luminaires currently installed along the access road
and car park has been considered and the following comments are provided:
The off-site locations range from 2.8km away to over 9km distance from the site.
The existing type A luminaires mounted on 12m high poles emit no direct light component that would reach
any of the nominated off-site locations.
Reducing the mounting height of the type A fixtures would have no effect on direct light emitted toward the
off-site locations.
The surfaces that may be most visible from the nominated off-site locations would be the poles. Where still
within view, reducing the height of the poles would only have a minor impact on reducing their visibility, as
the brightest part would still be visible, at the top of the pole.
Reducing the mounting height of the access road lights would mean different luminaires would be required
to achieve the required illumination levels and potentially more of them. That may mean more poles which
would have a counter-productive effect on reducing the off-site lighting impacts.
6.4.4 Recommended Lighting Measures
The following measures are recommended to minimise luminance of surfaces that may be visible from off-site
viewpoints:
Remove back light shields on luminaires that face towards the nearby site boundary
Rearrange mounting brackets of luminaires so the luminaire is below any bracket or cross arm structure
Remove luminaires facing West from poles L47 and L48
Paint the top section of the light poles black to 4m above ground level
Replace existing ballasts with a two set dimming ballast and provide a lighting control system that
communicates by Wi-Fi to dim the lights during periods of inactivity
Erect screen to mask the view of the Admin and Amenities buildings from off-site view points to the West
and North
The above technical measures are aimed at providing solutions to satisfy the Development Consent conditions.
6.4.5 Additional Lighting Recommended
It is noted a common pedestrian route exists between the Administration Building, the Control Room and the Process
Plant Area. The lighting in this area is poor with horizontal illuminance falling to below 1 lux for some distance.
It is recommended additional lighting be installed to provide a safer illuminated notional pathway for pedestrian
access at night.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 34 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.5 TYPICAL CONVEYOR GANTRY LIGHTING
6.5.1 Existing Installation
The gantries that align each side of the conveyors are illuminated by 70W luminaires (Type G). While the majority of
type G luminaires are the Pierlite MineMaster, there are a number of Philips Metro luminaires also installed on the
gantries.
There are over 300 gantry lights on the site, some of which are the highest elevated lighting on the site and their
visibility from off-site would be attributed to a number of factors, including:
Their elevated position
The quantity of lights
Their close proximity to each other
Their close proximity to the conveyor covers
The tilt of the luminaires
The slope of the gantry causing the luminaires to roll
6.5.2 Assessment of Existing Gantry Lighting
Minimum Criteria
The minimum criteria for conveyors and gantries as recommended by AS 1680.2.4 is 40 lux average horizontal
illuminance.
Refer to Appendix E for details of a lighting calculation of a typical section of an existing conveyor gantry lighting
installation. The gantry is illuminated to approximately 50 lux (average) and 15 lux (minimum), while the vertical
surface of the conveyor covers are illuminated to approximately 30 lux (average) and 7.5 lux (minimum).
It is concluded the existing gantry lighting complies with the minimum illuminance criteria. Refer to Table at Appendix
G for details.
Luminous Intensity Assessment
The AGi calculations undertaken confirm the luminous intensity of all the Gantry lights are AS 4282 compliant beyond
approximately 1000m from the plant area.
As all the nominated viewpoints are much further from the site the luminous intensity of these luminaires is also
compliant with the requirements of AS 4282 at those locations. Refer to Table at Appendix G for details.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 35 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
FIG. 10: RENDERED IMAGE OF SECTION OF TYPICAL GANTRY LIGHTING
6.5.3 Recommend Lighting Measures
Methods to minimise the off-site lighting impacts from the gantry lights may include the following:
Provision of local lock-out switching to suit operational requirements.
NB: As these fixtures are HID, the following features must be taken into account:
They are not instant ON and will take time to warm up to reach normal operating output
Switching must ensure they are NOT turned OFF inadvertently. When turned off they will take
several minutes to cool down before they can restrike and return gradually to full brilliance, leaving
the gantry with no lighting for some time.
Modification of the distribution of the existing luminaires to limit their distribution above the horizontal by
using a shield system has been considered and discounted as an option as minimum illumination
requirements would not be achieved by this method.
Replacement of the existing lights with LED hand rail lighting – LEDs could provide uniform light on gantry
from low wattage point sources that may be less visible from a distance than the existing luminaires.
LED lighting has become a common method of illuminating pedestrian bridges, steps, etc. in the public
domain where spill light is a concern (such as Eastern Valley Way Inlet pedestrian bridge in Belconnen, ACT).
Install a cover that conceals the lights and illuminated surfaces of the conveyor covers from view on all
gantries that are above the horizon and in plain view from the off-site locations of concern
The above technical measures are aimed at providing lighting solutions to satisfy the Development Consent
conditions.
6.6 TYPICAL STACKER AREA FLOOD LIGHTING
6.6.1 Existing Installation
400W Flood lights have been installed at the highest point of the stackers, so their elevated position makes them
highly visible form off-site.
We understand these fittings were not aimed as the lighting designer intended at the time of the inspection, and if
energised in their aiming position would have exceeded the minimum luminous intensity recommendations in AS
4282 for obtrusive light.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 36 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.6.2 Assessment
Minimum Criteria
The assessment criteria for illumination of the stockpiles is 30 lux minimum average. It is noted that not all stackers
have a flood light at the end to illuminate the product stock pile. Where lights are installed, the levels generally vary
from less than 20 lux to over 40 lux.
It is concluded that although some stock pile areas may be illuminated to levels that achieve compliance with the
minimum illuminance requirements of BMA Coal, a number of these areas do not achieve compliance with selected
minimum lighting criteria. Refer to Table at Appendix G for details.
Maximum Criteria
Calculations have demonstrated these flood lights must be aimed at no more than 100
above the horizontal. This is
considered the maximum tilt to maintain AS 4282 compliance. Refer to Table at Appendix G for details.
6.6.3 Recommended Lighting Measures
Tilt luminaires to maximum 10 degrees above the horizontal with a mechanism preventing the ability to tilt
above 100
when maintenance is conducted
Provide remote and/or local ON/OFF control, subject to operational requirements, to limit the ON period to
only when it is required
Provide two step dimming ballast that may be remote controlled by Wi-Fi back at the control room or hand
held remote control devices operated by the staff in the vicinity
The above lighting measures are aimed of providing technical solutions to ensure compliance with AS 4282 and
satisfy the Development Consent conditions.
6.7 AREA LIGHTS ON BUILDING FACADES
6.7.1 Existing Installation
The buildings on the site generally have no flood lights on their facades except where there is process plant. The only
exception identified was the Workshop, which is likely to have pedestrians accessing the building at night, so lighting
is provided for that purpose. The height of these lights vary, as they are generally over roller doors which vary in
height. The luminaires include:
Pierlite 250W and 400W MH flat glass flood lighting (type ‘D’) and 250W Eye flood lights, generally aimed 0
to 100
tilt.
6.7.2 Assessment
The peak horizontal illuminance achieved by these luminaires is high due to the relatively high lamp wattage
luminaires and corresponding low mounting heights. The maximum level calculated for the entire site (225 lux) is
directly below one of these fixtures.
The Workshop building is not near the perimeter of the site and is surrounded by a number of other buildings, and
because the tilt is set close to zero, no direct light from these luminaires would reach any of the off-site viewpoints
and AS 4282 compliance is achieved subject to maintaining the existing tilt arrangements. Refer to Table at
Appendix G for details.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 37 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
6.7.3 Recommended Lighting Measures
Replace 400W luminaires with 250W luminaires where the mounting height is below 6m
Ensure the tilt of each luminaire does not exceed 100
above horizontal
The above lighting measure are aimed at satisfying the Development Consent conditions.
6.8 RAIL SIDING
6.8.1 Existing Installation
Rail siding is illuminated by 2 x 26W T5 fluorescent luminaires, type H on 8m poles. As the siding is in a valley, these
lights are generally not seen from off-site.
6.8.2 Assessment
Minimum Criteria
Lighting levels achieved are very poor, with horizontal illuminance less than 1 lux in between luminaires. The selected
lighting criteria for railway freight track area is 10 lux minimum average.
The existing installation does not achieve compliance with the assessment criteria and additional lighting may be
required, pending the outcome of a safety risk assessment by the Developer. Refer to Table at Appendix G for
details.
Maximum Criteria
No recommendations are provided, nor considered necessary, to satisfy the Development Consent conditions.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 38 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
7 CONCLUSIONS AND RECOMMENDATIONS
This section brings the findings from the desk top analysis to a conclusion and provides recommendations for
consideration. Refer also to Appendix J for a tabulated Lighting Action Plan.
The technical solutions recommended in the report are aimed at preventing and/or minimising any off-site lighting
impacts and achieving compliance with the Development Consent conditions.
Some of the recommendations are clearly quite achievable and others are more difficult. Because of the element of
subjectivity in determining what is “practicable”, the Report reserves judgement on whether the recommendations
are “practicable”.
The Report leaves the assessment of each recommendation up to Holcim to determine whether it is deemed
practicable, or otherwise.
The recommendations included in this section do not constitute a design, but are conceptual in nature, to be
developed further, where appropriate, independent of this report.
7.1 ADMIN CARPARK LIGHTING (TYPE B AND C)
7.1.1 Lighting Measures
Minimise the off-site lighting impacts from the carpark lighting by the following measures:
Remove existing 400W type B luminaires from carpark light poles
Replace the above with new 150W GMRA luminaires
Remove one luminaire from pole L47 and L48(the fixtures that face west)
Install custom louvred back light shield to the remaining luminaires on L47 and 148 to control light spill onto
the roof of the Admin and Amenities building.
The above lighting measures are aimed at minimising off-site lighting impacts by minimising the luminance of the
illuminated surfaces of the buildings and so satisfy the Development Consent conditions.
7.1.2 Alternative Measures
As an alternative to the above measures, a screen may be erected to mask the view of the Admin and Amenities
buildings and carpark lighting from view from the western and northern off-site viewpoints. This would eliminate
these highly illuminated surfaces from view and so prevent such off-site lighting impacts, further satisfying the
Development Consent conditions.
7.2 12M HIGH POLE MOUNTED ROADWAY AND SITE/ AREA LIGHTING
Options recommended to minimise off-site lighting impacts include the following:
Remove back light shields on luminaires that face towards the nearby site boundary
Consider the installation of custom louvre type back light shields, to L47 and L48 (identified in 7.1.1 above)
Rearrange so that the luminaire is mounted below any bracket or cross arm structure
Removal of west facing luminaires from L47 and L48
Replace existing ballasts with two step dimming ballasts and provide a motion sensor on each pole that
interfaces with adjacent lights, to control the lights by Wi-Fi
Provide local isolating switches on poles that do not need to be on all night, including L64 and L50
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 39 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
The visibility of the poles may be reduced by reducing the reflectance of the pole surface, thereby reducing their
luminance. The highly reflective surface of the galvanised steel poles may be substantially reduced by painting them
black, so reducing their luminance and making them much less visible from a distance.
Paint the top sections of the poles (above 2.5m AFGL) with a flat matt black paint suitable for application on
galvanised steel, or equivalent treatment of the pole surface.
Provide additional lighting for safe pedestrian access between Admin building, Control Room and Process
Plant area
The above lighting measures are aimed at minimising off-site lighting impacts by removing highly illuminated surfaces
from view, turning lights off when not required and dimming lighting when possible. These measures provide Holcim
with a range of options to satisfy the Development Consent conditions.
As an alternative to the above options, a screen may be erected to mask the view of the majority of the area/ site
lighting from the western and northern off-site viewpoints. Reducing the mounting height of the luminaires would
reduce the height of the screen required to accomplish these objectives.
This option would eliminate the view of such lighting and so prevent such lighting impacts from western and northern
off-site viewpoints. These lighting measures are aimed at further satisfying the Development Consent conditions.
7.3 CONVEYOR GANTRY LIGHTING
Methods to reduce or minimise the off-site lighting impacts of the conveyor gantry lighting include:
Provide local switching to enable the gantry lights to be turned off when not required (note considerations
described in Section 6.5)
One light nearest the entry and exit points to each gantry must remain ON, uncontrolled by local switching.
Other gantry lights below RL 673m may also remain ON, uncontrolled by local switching.
Replace existing lights with LED type hand rail lighting
Install a cover to screen the view of conveyor covers and lights above RL 673m. This could be constructed
from securely fastened, light weight perforated material to minimise additional weight and wind loading on
the structure.
The above lighting measures are recommended options that are aimed at eliminating and minimising off-site lighting
impacts from the conveyor gantry lighting and satisfying the Development Consent conditions.
7.4 STACKER FLOOD LIGHTS
Methods to reduce or minimise the off-site lighting impacts from the stacker flood lights include:
Adjust tilt of luminaires to maximum 100
above the horizontal
Provide mechanism that enables the luminaires to be serviced and aimed but permanently prevents the tilt
of the fixture exceeding the above 100
Provide switching so that lights can be turned off when not required
Develop a work place procedure to ensure lights are only ON when required
Switching may be remote (from control room) or local, subject to operational requirements
Provide dimming ballasts to existing luminaires to enable them to be switch dimmed when full intensity is
not required. Dimming could be controlled remotely from control room, via Wi-Fi or locally by hand held
infrared remote devices.
The above lighting measures are recommended options that are aimed at eliminating and/ or minimising off-site
lighting impacts from the stacker flood lights and satisfying the Development Consent conditions.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 40 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
7.5 AREA LIGHTS ON BUILDING FACADES
Where applicable, the following measures may be adopted to minimise the off-site lighting impacts of the flood light
on building(s):
Adjust tilt to maximum 100
above horizontal
Replace 400W luminaires with 250W luminaires where mounting heights are less than 6m
The above lighting measures are recommended options that are aimed at eliminating and/ or minimising off-site
lighting impacts from the area lights on the building facades and satisfying the Development Consent conditions.
7.6 SCREENING METHODS
Non-lighting solutions include the provision of screening which would be most effective on the western site boundary.
The ground level falls away to the east making this method less practicable on the eastern side of the site.
Major screening initiatives to eliminate or minimise off-site lighting impacts could include methods such as :
Construction of a wall or screen to mask lighting from view
Construction of an earth mound and / or
Establishment of a dense plantation of suitable trees
Based on the highest lights being at an approximate RL of 696m, it has been estimated any one, or any combination
of the above methods would have to be at least 25m higher than the ground level of the Admin building car park and
approximately 800m long to totally eliminate the lighting impacts from the plant lighting to the nominated western
off-site locations.
It was estimated that a further 400m of screening at the southern end of the site, to a height of approximately 10m
above the car park level (or an RL of 681m), would also be required to totally eliminate the lighting impacts from the
existing roadway lighting to the nominated western off-site locations.
Further site analysis has subsequently been undertaken in conjunction with Holcim and the proposal of a screen
combined with reducing the height of the site/ area/ roadway lighting and carpark lighting luminaires has been further
developed.
The outcome of this proposal would provide the following benefits to off-site lighting impacts from viewpoints to
north and west:
Prevent the direct view of Admin and Amenities building
Prevent the direct view of the access roadway lighting
Prevent the direct view of the majority of the site/ area lighting
Prevent the direct view of the majority of the stacker flood lights
Prevent the direct view of the conveyor gantry lights below the corresponding RL. Those mounted above
that RL could be switched off when not required
Prevent the direct view of the lights on the building facades
This screening solution is aimed at satisfying the Development Consent conditions.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 41 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
7.7 COMMENTS ON DEVELOPMENT CONSENT CONDITIONS
As identified above, the Report provides technical recommendations aimed at preventing and/or minimising any off-
site lighting impacts from the development and satisfying the Development Consent conditions.
The solutions identified in the Report provide Holcim with the measures to enable the site to fully comply with the
regulatory Standards and the Development Consent conditions.
Some of the recommendations are clearly quite achievable and others are more difficult. Because of the element of
subjectivity in determining what is “practicable”, the Report reserves judgement on whether the recommendations
are “practicable”.
The Report leaves the assessment of each recommendation up to Holcim to determine whether it is deemed
practicable, or otherwise.
LYNWOOD LIGHTING DESIGN REVIEW
FINAL DRAFT REPORT
L490brep001_D.docx Page 42 of 42 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 JULY 2015 ISSUE D ABN 14 064 354 776
8 THE LIGHTING QUESTION
The Question:
“If light bulb is shielded from above, is it possible that the light is visible from an elevated position? (i.e. above the eye
line of the shield)”.
Answer:
Direct or incident light emanating from a shielded light source would be prevented from being seen from an elevated
position by the shield, as described. If the light were not intercepted by any surface below the shield, that light would
be invisible and not be seen from the elevated position.
Light will travel in a straight line until it strikes a surface, where some may be absorbed and the remainder then
reflected or refracted, dependent upon the characteristics of the surface.
If there is an object below the light source where it is not directly shielded from view, the light will be reflected off the
surface of the object and that object may be seen from the elevated position. Such an object could be the ground, a
light pole, a building, a luminaire mounting bracket, a back light shield or even fine particles in the atmosphere, such
as dust or moisture.
All of these “objects” may be illuminated and may be seen from the elevated position, even when the light source is
shielded from view, as shown in the sketch below.