log boiler 20 - 60 kw service manual 2… · 2019-07-15 en 0000000301 v.007 3.47.0 110, 218, 121p,...
TRANSCRIPT
2019-07-15EN0000000301V.0073.47.0110, 218, 121P, 219P93317-002
Log boiler20 - 60 kW
Service manual
ETA Heiztechnik
Gewerbepark 1
A-4716 Hofkirchen an der Trattnach
Tel: +43 (0) 7734 / 22 88 -0
Fax: +43 (0) 7734 / 22 88 -22
www.eta.co.at
General information
1 General information
Support for cleaning and maintenance
This document provides support for cleaning andmaintaining the product. The required steps are listedin detail here.
Take note of the date of the cleaning or maintenanceand any faults that may have occurred. This facilitatestroubleshooting for the expert (system operator,heating technician...).
For services (such as commissioning, mainte-nance, fault fixing) provided by ETA customer
service, the service reports are provided in digital form.For clarity, you should staple these reports to thisdocument or enclose them.
Commissioning data
Enter the manufacturing number of the product(printed on the type plate), the date of commissioningas well as the heating technician who commissionedthe system.
Copyright
All contents of this document are property of ETAHeiztechnik GmbH and are protected by copyright.Any reproduction, transfer to third parties or use forother purposes is prohibited without written permissionfrom the owner.
Subject to technical changes
We reserve the right to make technical modificationswithout notice. Printing and typesetting errors orchanges of any kind made in the interim are not causefor claims. Individual configurations depicted ordescribed here are only available optionally. In theevent of contradictions between individual documentsregarding delivery scope, the information in our currentprice list applies.
Explanation of symbols
Instructions and information
Layout of safety instructions
SIGNAL WORD!
Type and source of danger
Possible effects
• Measures for avoiding the danger
Types of safety instruction
CAUTION!
On non-compliance with this safety instruction, there isa risk of material damage.
WARNING!
On non-compliance with this safety instruction, there isa risk of physical injury.
DANGER!
On non-compliance with this safety instruction, there isa risk of major physical injury.
Commissioning data
Manufacturing number:
________________________________________
Commissioned on:
_________________________________________
Commissioned by (company):
_________________________________________
_________________________________________
_________________________________________
3
Maintenance notes Cleaning and maintenance
2 Cleaning and maintenance
2.1 Maintenance notes
Performing regular cleaning and maintenance
To ensure satisfactory functionality, cleaning andmaintenance must be performed at regular intervals.You will receive a timely reminder about this from theETAtouch control system.
Cleaning of the boiler must be carried out at leastonce a year, or when requested by the control
system. Maintenance is necessary at least every3 years, or when requested by the control system. Werecommend that you perform maintenance annually.You can also enter into a service agreement for yourheating system. Find out more from your heatingcontractor or customer service.
All tasks where the maintenance table reads"Customer" or "Customer or expert" in the column
"To be carried out by" can be carried out by any trainedadult. Instruction may be provided by the heatingtechnician or our customer service.Steps that are marked with "Expert" only can only becarried out by the heating technician or our customerservice.
Operation only by trained personnel
The product may be operated by trained adults only.Training may be provided by the heating technician orour customer service. Please read the associated doc-umentation carefully in order to avoid errors duringoperation and maintenance.
Persons who lack experience and knowledge as wellas children may not operate, clean, or maintain theproduct.
Display maintenance steps on the screen
With this boiler, the maintenance steps can also bedisplayed on the ETAtouch control system screen. Therequired activities will be explained to you step-by-stepand supplemented with detailed graphics. Eachmaintenance is saved and the details can be viewed atany time. So you can maintain a long-term overview ofthe maintenance carried out. Of course, themaintenance can also be carried out using the serviceguide, without the support of the ETAtouch controlsystem.
To access maintenance, switch to settings in the boilerfunction block ( [Settings] button) and then selectthe function [Maintenance].
Fig. 2-1: Overview (example)
You can also access this overview by pressingthe maintenance switch. Also when the message
appears that maintenance of the boiler is required.
In the overview the different maintenance intervals arelisted in the upper area. This includes the maintenancealready carried out. With the button, informationabout the selected maintenance is displayed.Maintenance that you can carry out as an endcustomer is labelled with the symbol. All others arereserved for specialists and require authorisation.
Press the button to start the maintenance. Theindividual steps are displayed on the screen. You canswitch to the next or the previous screen respectivelywith the arrow keys on the left and right side of thescreen.
Fig. 2-2: Maintenance step (example)
4 www.eta.co.at
Cleaning and maintenance Maintenance notes
Follow the on-screen instructions and carry out allsteps carefully. Enter your name at the end ofmaintenance ( button) and save the maintenancewith the button.
Fig. 2-3: End of maintenance
To end maintenance prematurely, press the rightarrow key several times until you get to the end.
There you can end the maintenance with the button. Cancellation during a maintenance step is notpossible.
Explanation of the maintenance switch
The maintenance switch on the boiler is needed forperforming maintenance with the aid of the [Main-tenance] function in the ETAtouch control system. Thisdisplays the individual maintenance steps on the boilerscreen.
With this variant the heating mode is stopped, butthe boiler remains on at the mains switch. So that
all drives are disconnected, the safety chain of theboiler is disrupted with the maintenance switch. Thescreen will display a message when it is time to actuatethe maintenance switch.
Fig. 2-4: Maintenance switch
The maintenance switch is marked with the symbol and has two settings.
• "1" = regular operationThis is the standard position of the maintenanceswitch. The boiler can execute heating mode in thisposition.
• "0" = maintenance modeIn this position, all drives are disconnected toperform maintenance. The circuit boards,however, are still live.
Explanation of pictograms
Switch the boiler on/off with the mains switch.
Perform a visual check of the components.
Clean the components with a soft cloth, for example.
Remove deposits with a vacuum cleaner or an ash vacuum.
Remove deposits with the poker.
Remove deposits with the cleaning brush.
Replace the wear parts (e.g., seals) with new items.
Lubricate the components. The lubricant to use is listed in the respective step.
Mount the components (e.g., screws or nuts) by hand only, without tools.
Tighten the components (e.g., screws or nuts) with a tool.
Install the components with some force (e.g., the retaining tube or the Lambda probe).
Handle the components carefully, since they break very easily.
Measure or check dimensions or clearances on the components.
Mark the components so that the correct position can be found, for example, when mounting.
5
Maintenance notes Cleaning and maintenance
Clean panels
If necessary, clean the panels of the boiler and theETAtouch screen with a moist cloth.
Under no circumstances use aggressivesolvents, chemicals or scouring agents. They can
lead to stress cracks and damage.
Technical illustrations
The technical illustrations in this documentation showan SH30 log boiler with the actuators for the air valveson the left side.
The illustrations are representative for all compatibleETA log boilers.
Wear a protective mask to avoid injuries to the airways.
Seal the components. The sealant to use is listed in the respective step.
Use adhesive to affix the seals, for example.
Only blow out the components with your mouth.
Affix a seal. The required cross-section and sealing material are given at each step.
Tighten the screws or nuts alternately and evenly.
Do not use compressed air to clean the components.
Do not use cleaning brushes to clean the components.
Do not use an ash vacuum or vacuum cleaner.
Do not lubricate the components.
No water or moisture in this area.
No leaks in the components, e.g. screw connection or maintenance cover.
6 www.eta.co.at
Cleaning and maintenance Maintenance notes
7
Maintenance openings in the boiler Cleaning and maintenance
2.2 Maintenance openings in the
boiler
Maintenance openings and components
The illustrations show a wood chip boiler with30 kW output and the actuators for the air valves
on the left side. The illustrations are representative forall compatible log boilers.
1 Door contact switch
2 Fuel chamber
3 Combustion chamber
4 Ash collection duct
5 Walls of ash collection duct
6 Cleaning lever for the turbulators in the heat ex-changer
7 Heat exchanger cover
8 www.eta.co.at
Cleaning and maintenance Maintenance openings in the boiler
1 Flue gas temperature sensor
2 Draught fan
3 Optional automatic heat exchanger cleaning
4 Actuator for primary air
5 Actuator for secondary air
6 Lambda probe
7 Turbulators in the heat exchanger
9
Maintenance table Cleaning and maintenance
2.3 Maintenance table
Cleaning of the boiler must be carried out at least once a year, or when requested by the control system.Maintenance is necessary at least every 3 years, or when requested by the control system. We recommend
that you perform maintenance annually.
TasksRegular
ly
Cleaning
annually
Maintenance
at least every 3 years
to be performed by
Check the pressure of the heating system X X X Customer
De-ash boiler
• Actuate cleaning lever
• Remove ash from the boiler
• Check walls of ash collection duct
X X X Customer
Check the safety devices
• Visual check of the safety valves
• Visual check of the thermal relief valve
X XCustomer or
specialist
Clean fuel chamber
• Remove ash behind suspended panels
• Clean primary air openings
• Clean secondary air openings
X XCustomer or
specialist
Chimney
• Clean the flue tube
• Flush the chimney's condensate drain
X XCustomer or
specialist
Clean the draught fan X XCustomer or
specialist
Clean the heat exchanger
• Remove ash from the heat exchanger compartment
• Check the heat exchanger tubes
• Check the seal on heat exchanger cover
X XCustomer or
specialist
Check boiler doors X XCustomer or
specialist
Optional automatic ignition
• Clean the ignition tubesX X
Customer or specialist
Clean the lambda probe X Specialist
Clean the temperature sensor X Specialist
Check air valve X Specialist
Check the optional automatic heat exchanger cleaner X Specialist
Optional automatic ignition
• Dismantle the ignition and cleaning the ignition tubesX Specialist
Calibrate the lambda probe X Specialist
Reset the maintenance counter X Specialist
Perform heating test X Specialist
10 www.eta.co.at
Cleaning and maintenance Regular maintenance
2.4 Regular maintenance
2.4.1 Preparation
End heating mode, perform ember burnout
During the last heating mode, press the [Emberburnout] button in the boiler overview (the button isthen displayed in yellow ). Ember retention is thendeactivated and the boiler performs a complete emberburnout (duration approx. 1 hour). The majority of thecharcoal burns in the fuel chamber.
Only start the maintenance when the boiler hascooled down sufficiently.
2.4.2 Check pressure of the heating system
Checking the heating system's water pressure
In buildings with up to three storeys, the optimumwater pressure in a cold heating system is between 1and 2 bar. For a warm heating system, the optimumwater pressure is between 1.5 and 2.5 bar.
Fig. 2-5: Pressure gauge
If the water pressure is too low, fill the coldheating system to approx. 2 bar. Do not fill to a
higher pressure, because water expands as thetemperature rises and the water pressure also rises inheating mode. The safety valve triggers at approx. 2.8bar.
If the water pressure drops several times a year,contact a heating professional. When refilling
water in the heating system, the same water as usedduring initial filling should be used whenever possible(e.g. treated water).
2.4.3 De-ash boiler
Actuate cleaning lever
Close the insulation door and clean the heatexchanger by repeated movement (10 x) of thecleaning lever on the side.
Fig. 2-6: Cleaning lever
This step is omitted if the optional automatic heatexchanger cleaner is mounted on the boiler.
De-ash boiler
The ash in the fuel chamber is needed asinsulation for ember retention. Therefore, leave a
layer of ash approximately 3 cm thick in the fuelchamber. Only rake the excess ash in the primarycombustion chamber. Some pieces of charcoal willdrop into the primary combustion chamber during thisprocess; these are best left there. The charcoal willburn during the next combustion cycle and the ash willprotect the bottom of the combustion chamber againstpremature wear.
Fig. 2-7: Rake the excess ash and pieces of charcoal into the primary combustion chamber.
11
Regular maintenance Cleaning and maintenance
Check the openings for the primary air in thesuspension plates, and also the burn-through open-ings in the grate. These openings must be free; if not,clear them with the poker.
Fig. 2-8: Openings for primary air and burn-through openings
Pull most of the ash out of the primary combustionchamber into the ash box with the poker. Leave about1 cm of ash in the primary combustion chamber. Thisserves as insulation and protection.
Fig. 2-9: Removing ash from the combustion chamber
Pull the ash from the ash collection duct (under theprimary combustion chamber) into the ash box. Alsoclear the rear end of the ash collection duct, so there'sno ash in front of the lambda probe head.
Fig. 2-10: Removing ash from the ash collection duct
The draught fan runs during de-ashing. Pull the ashslowly and steadily out of the boiler so that not toomuch ash is stirred up and blown into the open airthrough the chimney.
If there are still embers in the ash, leave the ashin a closed, non-combustible container for at least
2 days. Only put the ash into the waste bin when youare sure that no more embers are present.
Do not push the ash box into the primarycombustion chamber. For the 40 - 60 kW boiler
this is possible, but the ash box is not designed for itand is destroyed by the high temperatures.
Checking the ash collection duct walls
Check the walls of the ash collection duct, they may bewhite to brown. If they are black with soot, either toomuch wood was burned at too low a heat consumption,the fire was not lit correctly at start-up or, in rare cases,the lambda probe gave incorrect measurement values.
Fig. 2-11: Checking the ash collection duct walls
12 www.eta.co.at
Cleaning and maintenance Cleaning (customer)
2.5 Cleaning (customer)
2.5.1 Preparation
Before this maintenance, perform all steps for thepreceding maintenance intervals
Before this maintenance, all steps for thepreceding maintenance intervals must be
performed.
End heating mode, perform ember burnout
During the last heating mode, press the [Emberburnout] button in the boiler overview (the button isthen displayed in yellow ). Ember retention is thendeactivated and the boiler performs a complete emberburnout (duration approx. 1 hour). The majority of thecharcoal burns in the fuel chamber.
Only start the maintenance when the boiler hascooled down sufficiently.
WARNING!
Switch off the electricity to the boiler via the mainsswitch
Switch off the electricity to the boiler via the mainsswitch. This prevents injuries caused by switchingthe boiler on inadvertently.
WARNING!
Burns caused by hot parts
Risk of burning on parts located behind theboiler housing, even after shutting the boilerdown.
Allow the boiler to cool down sufficientlybefore starting any activities.
2.5.2 Check safety devices
Check safety valves
Check all safety valves of the heating system bymeans of a visual inspection. The outlets of the safetyvalves must not drip.
Fig. 2-12: Safety valve
If the safety valve drips, open and rinse the safetyvalve with a 1/4 turn of the red cap (danger ofscalding). If the safety valve still cannot be sealedeffectively after being rinsed several times, it must becleaned or replaced by an installer (heating techni-cian).
A manual check of the safety valve is carried outwith a 1/4 turn of the red cap. This rinses the
safety valve. It is however very likely that the seal willbe damaged in the process and thus the outlet will drip.Therefore, only carry out the check on weekdays,never on weekends in the cold winter, because there isprobably no heating technician available if the seal isdefective.
13
Cleaning (customer) Cleaning and maintenance
Checking the thermal relief valve
Visually check the thermal relief valve. The outlet mustnot drip.
Fig. 2-13: Thermally actuated relief valve
If the relief valve drips, press the red button to rinse thevalve (danger of scalding). If the relief valve still cannotbe closed tightly after being rinsed several times, itmust be cleaned by an installer (heating technician) orreplaced.
Press the red button to manually check the reliefvalve. This rinses the relief valve. It is however
very likely that the seal will be damaged in the processand thus the outlet will drip. Therefore, only carry outthe check on weekdays, never on weekends in thecold winter, because there is probably no heatingtechnician available if the seal is defective.
2.5.3 Clean fuel chamber
Completely de-ash the boiler
Stoke all the ash and charcoal from the filling chamberthrough the burn-through openings into thecombustion chamber.
Fig. 2-14: Stoke the ash and pieces of charcoal into the combustion chamber
Pull all the ash and pieces of charcoal out of thecombustion chamber into the ash box with the poker.
Fig. 2-15: Removing ash from the combustion chamber
14 www.eta.co.at
Cleaning and maintenance Cleaning (customer)
Also pull the ash from the ash collection duct (underthe combustion chamber) with the poker into the ashbox.
Fig. 2-16: Removing ash from the ash collection duct
If there are still embers in the ash, leave the ashin a closed, non-combustible container for at least
2 days. Only put the ash into the waste bin when youare sure that no more embers are present.
Remove ash behind suspended panels
The suspended panels in the fuel chamber are hungfrom a bolt at the top. Lift the hanging plates slightly,detach them and remove them from of the fillingchamber.
Fig. 2-17: Suspended panels
After removing the front suspended panels, removethe guard plate between the filling chamber door andthe heating door so that it does not fall down later.
Fig. 2-18: Guard plate
Remove the ash deposits from the walls with the poker.You can leave the shiny soot on the walls. It is notnecessary to use chemical cleaning agents.
Fig. 2-19: Cleaning the walls
Cleaning the primary air openings
Clean the primary air opening with an ash vacuum.
Fig. 2-20: Primary air openings
15
Cleaning (customer) Cleaning and maintenance
Cleaning the secondary air openings
Take out both halves of the grate and remove the ashlying below.
Fig. 2-21: Grate
Remove the ash from both side openings for thesecondary air with an ash vacuum.
Fig. 2-22: Secondary air openings
Reinsert both grate halves. When inserting, makesure that the seal (above the secondary air
openings) is in the semicircular groove of the twogrates.
Fig. 2-23: Correct grate placement
Also ensure that the grate does not "wobble" and isfully inserted. Check the openings of the grates, theymust lie at the same height.
Fig. 2-24: Checking the grate position
Re-install the suspended panels and guard plate
Check the state of the suspended panels. If they aredistorted, knock them back into shape with a hammer.However, if holes (in addition to the existing holes) areburnt out of the suspended panels, they need to bereplaced.
Fig. 2-25: Suspended panel
16 www.eta.co.at
Cleaning and maintenance Cleaning (customer)
Re-attach the guard plate between the filling chamberdoor and ignition door.
Fig. 2-26: Guard plate
Re-attach the suspended panel to the bolts in the fillingchamber. First, mount the front suspended panel sothat the guard plate does not fall down.
Fig. 2-27: Suspended panels
2.5.4 Chimney
Clean flue tube
Sweep the flue duct from the flue outlet to the chimneyand remove the fly ash from the chimney with an ashvacuum cleaner.
Fig. 2-28: Flue duct
Only sweep the ash into the chimney and not intothe boiler. Otherwise, ash will collect in the
fan housing and can block the draught fan.
Rinse the chimney's condensate drain
Check the chimney's condensate drain to make sure itis free, as ash can block the outlet. To check, rinse theoutlet with some water.
Fig. 2-29: Condensate drain
17
Cleaning (customer) Cleaning and maintenance
2.5.5 Clean draught fan
Cleaning the draught fan
Unplug the draught fan's power supply. Loosen thewing screws and remove the draught fan.
Fig. 2-30: Draught fan
Remove the ash from the fan housing.
Fig. 2-31: Fan housing
Carefully clean the impeller with a soft brush (not awire brush) or compressed air to prevent imbalance.Replace the seal.
Fig. 2-32: Cleaning the impeller, replacing the seal
Lubricate the screws with heat-resistant lubricant andre-attach the draught fan to the boiler. Tighten the wingscrews alternately and evenly. The plug connectionmust point to the right when viewed from behind theboiler. Plug the power supply back into the draught fan.
18 www.eta.co.at
Cleaning and maintenance Cleaning (customer)
2.5.6 Cleaning the heat exchanger
Removing the heat exchanger cover
Remove the cover next to the flue gas connection.
Fig. 2-33: Cover
Remove the insulation over the heat exchanger cover.
Fig. 2-34: Insulation
Loosen the knurled nuts of the heat exchanger coverby turning anti-clockwise. Then turn the ball knob by180°.
Fig. 2-35: Knurled nut and ball knob
Remove the heat exchanger cover.
Fig. 2-36: Heat exchanger cover
19
Cleaning (customer) Cleaning and maintenance
Cleaning the heat exchanger box
Remove the ash from the heat exchanger box with anash vacuum.
Fig. 2-37: Heat exchanger box
Checking the heat exchanger tubes
Check the heat exchanger tubes and the turbulatorsfor "tar deposits" (shiny soot).
Fig. 2-38: Turbulators
The turbulators must be removed as soon as thecleaning lever (or the automatic heat exchanger
cleaner) becomes difficult to move.
If the turbulators and their supporting brackets have tardeposits, the cause is often:
• leaks around the boiler doors
• boiler overheating
• incorrect ignition
• unsuitable fuel
Checking the seal on heat exchanger cover
Check if the seal on the heat exchanger cover is intactand replace if necessary.
Fig. 2-39: Heat exchanger cover
CAUTION!
Do not operate with damaged seals
Never operate the boiler with damaged seals.Otherwise, unwanted air is sucked in, disturbing thecombustion process and causing increased wear.
Always replace damaged seals immediately.
Closing the heat exchanger cover
Re-attach the heat exchanger cover. Turn the ballknob up to the stop to suspend the heat exchangercover. Then tighten the knurled nut by turningclockwise.
Fig. 2-40: Heat exchanger cover
20 www.eta.co.at
Cleaning and maintenance Cleaning (customer)
Replace the insulation on the heat exchanger cover.
Fig. 2-41: Insulation
Re-attach the cover.
Fig. 2-42: Cover
2.5.7 Check boiler doors
Checking the boiler door seals
Check the seals on the 3 boiler doors (filling chamberdoor, ignition door, combustion chamber door). To dothis, open the boiler doors and then close them again.When closing, make sure that the door can be closedfully and with force. The sealing edges of the doorframe must leave a clear indentation in the sealingcord of the boiler door.
Fig. 2-43: Check
Leaks can be detected by variations in the colourationof the sealing cord. If leaks are found, it is usuallysufficient to adjust the hinges and the closing rollermount. If the hinges cannot be adjusted any further,the sealing cord must be replaced.
Fig. 2-44: Seal between carbonization gas extraction duct and fuel chamber
Also check if the sealing cord is already "hard". Tocheck, press on the sealing cord with your finger
nail. If it can no longer be pressed, it is "hard" alreadyand must be replaced.
Especially check the seal between the carboniza-tion gas extraction duct and the filling chamber.
21
Cleaning (customer) Cleaning and maintenance
To adjust, open the respective door, lift it out of thehinges and remove the door.
1 Closing roller holder
2 Hinge
Loosen the flange nuts (top and bottom) on the hingeand the closing roller holder, and evenly reduce thegap (only slightly) to the boiler with the setting screws(Phillips screws).
Fig. 2-45: Reduceing the gap
Retighten the flange nuts. Suspend the door andcheck whether it now closes fully. If not, repeat theprocess.
Fig. 2-46: Check
Always adjust the hinges and the closing roll-er mount so that the seal is evenly compressed.
22 www.eta.co.at
Cleaning and maintenance Cleaning (customer)
2.5.8 Optional automatic ignition
Cleaning the ignition tubes
Clean the ignition tube by suction and carefully removeany deposits.
Fig. 2-47: Ignition tubes
2.5.9 Establish operational readiness
Switch on the boiler with the mains switch
Restore the power supply for the boiler and switch onthe boiler at the mains switch.
23
Maintenance (expert) Cleaning and maintenance
2.6 Maintenance (expert)
2.6.1 Preparation
Before this maintenance, perform all steps for thepreceding maintenance intervals
Before this maintenance, all steps for thepreceding maintenance intervals must be
performed.
WARNING!
The following activities may only be performed byqualified specialist personnel.
If you carry out these activities without the correspond-ing specialist training, and above all without therequired experience, safe operation is no longerguaranteed. The resulting defects and consequentialdamage are excluded from the guarantee andwarranty.
Equally an incorrect performance of these activitiescan lead to serious injuries.
End heating mode, perform ember burnout
During the last heating mode, press the [Emberburnout] button in the boiler overview (the button isthen displayed in yellow ). Ember retention is thendeactivated and the boiler performs a complete emberburnout (duration approx. 1 hour). The majority of thecharcoal burns in the fuel chamber.
Only start the maintenance when the boiler hascooled down sufficiently.
WARNING!
Switch off the electricity to the boiler via the mainsswitch
Switch off the electricity to the boiler via the mainsswitch. This prevents injuries caused by switchingthe boiler on inadvertently.
WARNING!
Burns caused by hot parts
Risk of burning on parts located behind theboiler housing, even after shutting the boilerdown.
Allow the boiler to cool down sufficientlybefore starting any activities.
2.6.2 Clean lambda probe
Cleaning the lambda probe
Unscrew the retaining tube of the lambda sensor witha pipe wrench.
Fig. 2-48: Retaining tube
Remove the lambda probe and the sealing washer outof the boiler.
Fig. 2-49: Lambda probe and sealing washer
24 www.eta.co.at
Cleaning and maintenance Maintenance (expert)
Let the lambda probe cool down and clean it with anash vacuum. Particularly vacuum out the openings inthe head of the lambda probe.
Fig. 2-50: Head of lambda probe
Clean the sealing seat for the lambda sensor in theboiler. It must be absolutely clean. Check this with aflashlight and vacuum out the coupling with an ashvacuum.
Fig. 2-51: Vacuuming out the opening
Check the sealing washer to seal the flange of thelambda sensor and the seat in the boiler for damageand replace if necessary.
Fig. 2-52: Sealing washer
Screw the lambda probe with the retaining tube backinto the boiler.
Fig. 2-53: Installing the lambda probe
Retighten the retaining tube with a pipe wrench (with20 kg at 20 cm lever length).
Fig. 2-54: Tightening the retaining tube
Excessive wear on the combustion chamber isoften due to a leaky installation of the lambda
probe. Leak air penetrates the boiler and the controlsystem reduces the air intake too much and the tem-peratures in the combustion chamber reach impermis-sible levels.
25
Maintenance (expert) Cleaning and maintenance
2.6.3 Clean temperature sensor
Cleaning the flue gas temperature sensor
Loosen the screws and pull out the flue gastemperature sensor. Clean it with a soft cloth. Thenreplace the temperature sensor. Only hand-tighten thescrews so as not to damage the temperature sensor.
Fig. 2-55: Flue gas temperature sensor
2.6.4 Check air valve
Checking the air valve of the log boiler
Remove the rubber caps and check for dirt or depositson the air valves.
Fig. 2-56: Rubber caps
Actuate both actuators manually and check that theymove smoothly. For manual actuation, push theunlocking device (black button) and turn the drive 90°with a ring spanner.
Fig. 2-57: Actuators
Lubricate the air valves only with dry lubricant(e.g. PTFE spray) if they are difficult to move.
26 www.eta.co.at
Cleaning and maintenance Maintenance (expert)
2.6.5 Check the optional automatic heat exchanger cleaner
Checking the automatic heat exchanger cleaner
Remove the cover above the heat exchanger cleaner.
Fig. 2-58: Cover
Check the gap between the sensor and the connectingrod. The gap should be about 1 - 2 mm.
Fig. 2-59: Gap
Fig. 2-60: Connecting rod
CAUTION!
Do not lubricate the connecting rod
Never lubricate the bearing of theconnecting rod with oil, grease or otherlubricants. Dirt may stick to the lubricant,resulting in encrustation and stiffness.
Re-install the cover.
Fig. 2-61: Cover
27
Maintenance (expert) Cleaning and maintenance
2.6.6 Optional automatic ignition
Dismantling the ignition and cleaning the ignitiontubes
Loosen the screws and carefully remove the ignitions.Make sure that the included springs do not get lost.
Fig. 2-62: Springs
The ceramic igniter is very fragile. Make sure thatit is not damaged.
Fig. 2-63: Ceramic igniter
Check the ignition tubes for deposits and removethem, e.g. with a screwdriver.
Fig. 2-64: Cleaning the ignition tubes
Re-attach the ignitions with the screws and theretaining plate.
Only hand-tighten the screws, so that the ignitionis held by the springs. Do not overtighten the
screws, otherwise the ignition may be damaged.
Fig. 2-65: Only hand tighten the screws
28 www.eta.co.at
Cleaning and maintenance Maintenance (expert)
2.6.7 Calibrate lambda probe
Calibrating the lambda probe
The boiler's built-in lambda probe checks theresidual oxygen content of the flue gas and uses
it to control the combustion. To ensure reliability, thecontrol system autonomously performs an automaticcalibration after every 500 hours of operation. Thisalways occurs after an ember burnout and only at nightbetween the hours of 23:00 and 04:00. This calibrationcan also be initiated manually by opening the primaryand secondary air valves and purging the boiler withfresh air using the draught fan.
If you wish to perform a manual lambda probe calibra-tion, the control system provides the [Addl. calibration]function. This function can be selected with the[Service] access level and can be found under:
Switch on this function and the additional calibrationwill now start. If the boiler has not been started up forover 48 hours, this calibration takes only 30 minutes. Ifthe boiler was in operation until recently, the calibrationcan take up to 3 hours. If the boiler is started up duringcalibration, calibration will be aborted and restart9 days later.
After another 100 hours of operation, the controlsystem automatically performs another calibra-
tion.
2.6.8 Establish operational readiness
Reset maintenance counter
When maintenance is complete, reset the counter.With the [Service] access level, it will be visible in theboiler text menu under:
Perform heating test
To perform the heating test, put the log boiler intoemissions measurement mode. To do this, carry outthe following steps.
Place logs in the fuel chamber, ignite them, and wait15 minutes. In the log boiler overview, press the [Mea-surement] button to open the emissionsmeasurement settings window.
Fig. 2-66: Settings window for emission measurement
Press the [Start now] button so the boiler will startimmediately. The control system ensures thatsufficient heat is channelled to the buffer, the heatingcircuits, and the hot water tank.
After around 10 minutes, a residual oxygen value of4.5% to 7% should be reached. The current residualoxygen content is displayed in the boiler's text menuunder:
If the value does not drop below 12% residualoxygen content, the boiler is receiving leak air.
The reason (leaky boiler doors, heat exchanger cover,lambda probe installation, etc.) must be identified andcorrected.
If possible, perform a flue gas measurementduring the heating test.
Inputs
Residual O2
Calibration
Addl. calibration
Counters
Full load hours since maint.
Reset counter?
Boiler
Residual O2
29
Maintenance (expert) Cleaning and maintenance
After the heating test, switch the boiler back to normalmode. To do this, press the [Deactivate measurement]
button in the settings window.
30 www.eta.co.at
www.eta.co.at
www.eta.co.at/downloads
DOWNLOAD