    Basic Protective RelayingRemote-Local Backup

    ProtectionEd Khan

    April, 2013

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    2/19

    Backup Protection

    Back Up Protect ion are of three types:

    Remote

    Local

    Beaker Failure

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    3/19

    Backup ProtectionOverlapping Zon es of Protect ion

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    4/19

    Backup Protection

    Overlapp ing Zones

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    5/19

    Backup Protection

    Zones of Protect ion Prov ide Remote Backup

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    6/19

    Remote Backup ProtectionDRemote Backup is inherent when we overlap the zones.

    D The tr ipp ing o ccurs at stat ion or s tations other than the one

    that is respon sib le to provide pr imary protect ion

    D The speed is slow

    DA large part of sys tem has to b e tr ipped to iso late the faul tDSomet imes the remo te backup may n ot be sensi t ive enou gh

    B

    Zone 1

    Zone 2

    Zone 3

    X

    12

    3

    4

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

    5

    6

    Breaker 5 opens co rrect ly

    Breaker 3 fai ls to open

    Remote protect ion at

    Breakers 1 and 6 have to

    open and isolate the faul t .

    C

  • 7/28/2019 Local Remote Backup Line Protection

    7/19

    Remote Backup Protection

    21

    5

    6

    7

    8

    11

    12

    13 14

    3 4

    9 10

    15 16

    17

    18

    Supp ose breaker 8 fails to op en even though th e relaying may

    have worked fine. In that case we cou ld rely on remo te back

    at br eakers 14, 16 and 18.

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    8/19

    Backup Protection

    21

    5

    6

    7

    8

    11

    12

    13 14

    15 16

    3 4

    9 10

    17

    18

    We lose larger part of the sys tem using remote backup. Also ,

    t r ipp ing is not assured under all operating con di t ions due to

    Infeed effect, etc.

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    9/19

    Remote Backup Protection

    21

    5

    6

    7

    8

    11

    12

    13 14

    3 4

    9 10

    15 16

    17

    18

    Remote backup is inherent ly there due to overlapp ing of

    zones of pro tect ion.

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    10/19

    Remote Backup ProtectionSubstat iontopo logy

    affects tr ipp ing

    requirements.

    Less impact on

    system wi th

    Breaker and

    a Half

    arrangement

    13 14X

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    11/19

    Backup Protection

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

    With the advent of EHV and increased concern for sys tem

    rel iabi l ity a greater emph asis is being placed on local

    backu p/breaker failure. Remote backup st i l l remains as a

    secon d tier. Also , in som e instances, a faul t may have to be

    cleared by a com binat ion of local and remote backup

  • 7/28/2019 Local Remote Backup Line Protection

    12/19

    Local Backup Protection

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

    What does Lo cal Backup compr ise of :

    D Redund ant pr imary and secondary re lays

    D Primary and secon dary relays from dif ferent manu facturersD Different techno logies for pr imary and secondary relaying

    D Redundant CTs

    D Redundant battery sup pl ies

    D Dual breaker tr ip

    We do not u sual ly prov ide dual PTs

  • 7/28/2019 Local Remote Backup Line Protection

    13/19

    Local Backup Protection

    21

    5

    6

    7

    8

    11

    12

    13 14

    15 16

    3 4

    9 10

    17

    18

    Faul t between breakers 6 and 8 needs to cleared by these

    breakers. If pr imary relaying at any of th ese breakers fai ls,

    secon dary protect ion ( local backup ) at these breakers shou ld

    operate.

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    14/19

    Breaker Failure Protection

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

    Even w ith all the redundanc ies, the local backup

    is not complete ly adequate because of the

    fai lure of a breaker to open when called upon todo so .

    This is known as breaker fai lure.

    This is a type of local backup

  • 7/28/2019 Local Remote Backup Line Protection

    15/19

    Breaker Failure Protection

    What is Breaker Failure

    Breaker Fai ls to tr ip to clear a faul t due to :

    Trip Coi l is defect ive

    Contro l Wir ing Problem

    Gas pressure low

    Operat ing m echanism is jammed

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    16/19

    Breaker Failure Protection

    Breaker Fai lure Relaying Funct ional Log ic

    OR

    L1

    L2L3

    Fault detectors

    62

    Aux relay

    AND 62BF 86BF

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

    Timer

  • 7/28/2019 Local Remote Backup Line Protection

    17/19

    Breaker Failure Protection

    Protect ion

    Trip: 1Cy.

    Operat ing

    Time of CB : 2Cy.

    Drop out t ime

    Of current prot : 1 Cy.

    Margin : 5 Cy.

    Breaker fai l t imer t ime d elay : 8 Cy.

    Breaker fail protection start

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    18/19

    Breaker Failure Protection

    Operat ing

    Time of CB : 2Cy.

    Protect ion

    Trip: 1Cy.

    Drop out t imeOf current prot : 1 Cy.

    Margin : 5 Cy.

    Margin

    7 Cy.

    Operat ing

    Time of CB : 2 Cy.Breaker fai l

    Protect ion tr ip : 0.5 Cy

    Breaker fai l t imer t im e delay : 8 Cy.

    Breaker fail protect ion star t

    Remote Zone 2 Back up protect ion op erat ion t ime :say 20 Cy.

    Proprietary Mater ial-Do not reprodu ce witho ut permiss ion

  • 7/28/2019 Local Remote Backup Line Protection

    19/19

    Any Quest ions ?

    Thank You