loadflow panel

84
P Workshop Notes © 1996-2010 ETAP/Operation Technology, Inc. Load Flow Analysis

Upload: dbogantesg9710

Post on 22-Dec-2015

11 views

Category:

Documents


0 download

DESCRIPTION

COMO HACER ESTUDIOS DE FLUJO DE POTENCIA EN ETAP. MANERA FACIL DE SIMULAR

TRANSCRIPT

Page 1: Loadflow Panel

ETAP Workshop Notes © 1996-2010 ETAP/Operation Technology, Inc.

Load Flow Analysis

Page 2: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 2

System ConceptsSystem Concepts

Page 3: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 3

jQP

IV

SS

IVS

LL

LN

*

13

*1

3

3

Lagging Power Factor Leading Power Factor

Inductive loads have lagging Power Factors. Capacitive loads have leading Power Factors.

Current and Voltage

Power in Balanced 3-Phase Systems

Page 4: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 4

Leading Power Factor

Lagging Power Factor

ETAP displays lagging Power Factors as positive and leading Power Factors as negative. The Power Factor is displayed in percent.

jQ P

Leading & Lagging Power Factors

P - jQ P + jQ

Page 5: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 5

B

2B

B

B

BB

MVA

)kV(Z

kV3

kVAI

B

actualpu

B

actualpu

Z

ZZ

I

II

B

actualpu

B

actualpu

S

SS

V

VV

B

2B

B

B

BB

S

VZ

V3

SI

ZI3V

VI3S If you have two bases:

Then you may calculate the other two by using the relationships enclosed in brackets. The different bases are:

•IB (Base Current)

•ZB (Base Impedance)

•VB (Base Voltage)

•SB (Base Power)

ETAP selects for LF:

•100 MVA for SB which is fixed for the entire system.

•The kV rating of reference point is used along with the transformer turn ratios are applied to determine the base voltage for different parts of the system.

3-Phase Per Unit System

Page 6: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 6

Example 1: The diagram shows a simple radial system. ETAP converts the branch impedance values to the correct base for Load Flow calculations. The LF reports show the branch impedance values in percent. The transformer turn ratio (N1/N2) is 3.31 and the X/R = 12.14

2B

1B kV

2N

1NkV

Transformer Turn Ratio: The transformer turn ratio is used by ETAP to determine the base voltage for different parts of the system. Different turn ratios are applied starting from the utility kV rating.

To determine base voltage use:

2

pu

pu

RX

1

RX

ZX

Transformer T7: The following equations are used to find the impedance of transformer T7 in 100 MVA base.

RX

xR pu

pu

1BkV

2BkV

Page 7: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 7

Impedance Z1: The base voltage is determined by using the transformer turn ratio. The base impedance for Z1 is determined using the base voltage at Bus5 and the MVA base.

06478.0)14.12(1

)14.12(065.0X

2pu

005336.014.12

06478.0R pu

The transformer impedance must be converted to 100 MVA base and therefore the following relation must be used, where “n” stands for new and “o” stands for old.

)3538.1j1115.0(5

100

5.13

8.13)06478.0j1033.5(

S

S

V

VZZ

23

oB

nB

2

nB

oBo

punpu

38.135j15.11Z100Z% pu

0695.431.3

5.13

2N1N

kVV utility

B

165608.0100

)0695.4(

MVA

VZ

22B

B

Page 8: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 8

8.603j38.60Z100Z% pu

)0382.6j6038.0(1656.0

)1j1.0(

Z

ZZ

B

actualpu

The per-unit value of the impedance may be determined as soon as the base impedance is known. The per-unit value is multiplied by one hundred to obtain the percent impedance. This value will be the value displayed on the LF report.

The LF report generated by ETAP displays the following percent impedance values in 100 MVA base

Page 9: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 9

Load Flow AnalysisLoad Flow Analysis

Page 10: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 10

1. Accelerated Gauss-Seidel Method

• Low Requirements on initial values, but slow in speed.

2. Newton-Raphson Method

• Fast in speed, but high requirement on initial values.

• First order derivative is used to speed up calculation.

3. Fast-Decoupled Method

• Two sets of iteration equations: real power – voltage angle, reactive power – voltage magnitude.

• Fast in speed, but low in solution precision.

• Better for radial systems and systems with long lines.

Load Flow Calculation Methods

Page 11: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 11

kV

kVAFLA

kV

kVAFLA

EffPF

HP

EffPF

kWkVA

Rated

Rated

RatedRated

1

33

7457.0

Where PF and Efficiency are taken at 100 % loading conditions

kV

kVA1000I

)kV3(

kVA1000I

kVA

kWPF

)kVar()kW(kVA

1

3

22

Load Nameplate Data

Page 12: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 12

TYPE OF LOADS:TYPE OF LOAD PHASOR PHASE

ANGLE

POWER ABSORBED BY THE LOAD

P Q

V

I

R VI Ф = 0° P > 0 Q = 0

V

I

L

V

I

Ф Ф = +90° P = 0 Q > 0

V

IC

V

I

Ф Ф = - 90° P = 0 Q < 0

R

L

R L

I

V

V

ΦV

I 0°<Φ<+90° P > 0 Q > 0

Page 13: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 13

TYPE OF LOADS:TYPE OF LOAD PHASOR PHASE

ANGLE

POWER ABSORBED BY THE LOAD

P Q

-90°<Φ<0° P > 0 Q < 0

LI

V

-90°<=Φ<=+9

P = 0 Q = 0

R

C

RC

V

V

I

IVΦ

C

Ic IL

Tuned to

Resonance

IL = Ic

PL = Pc

Energy travels

Back & forth

Between C&L

Page 14: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 14

Constant Power Loads

• In Load Flow calculations induction, synchronous and lump loads are treated as constant power loads.

• The power output remains constant even if the input voltage changes (constant kVA).

• The lump load power output behaves like a constant power load for the specified % motor load.

Page 15: Loadflow Panel

• In Load Flow calculations Static Loads, Lump Loads (% static), Capacitors and Harmonic Filters and Motor Operated Valves are treated as Constant Impedance Loads.

• The Input Power increases proportionally to the square of the Input Voltage.

• In Load Flow Harmonic Filters may be used as capacitive loads for Power Factor Correction.

• MOVs are modeled as constant impedance loads because of their operating characteristics.

Constant Impedance Loads

© 1996-2008 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 15

Page 16: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 16

• The current remains constant even if the voltage changes.

• DC Constant current loads are used to test Battery discharge capacity.

• AC constant current loads may be used to test UPS systems performance.

• DC Constant Current Loads may be defined in ETAP by defining Load Duty Cycles used for Battery Sizing & Discharge purposes.

Constant Current Loads

Page 17: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 17

Constant Current Loads

Page 18: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 18

Load Type Summary

Page 19: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 19

Exponential Load

Polynomial Load

Comprehensive Load

Generic Loads

Page 20: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 20

Feedback Voltage •AVR: Automatic Voltage Regulation•Fixed: Fixed Excitation (no AVR action)

Generator Operation Modes

Page 21: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 21

Governor Operating Modes

• Isochronous: This governor setting allows the generator’s power output to be adjusted based on the system demand.

• Droop: This governor setting allows the generator to be Base Loaded, meaning that the MW output is fixed.

Page 22: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 22

Isochronous Mode

Page 23: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 23

Droop Mode

Page 24: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 24

Swing Mode•Governor is operating in Isochronous mode•Automatic Voltage Regulator

Voltage Control•Governor is operating in Droop Mode•Automatic Voltage Regulator

Mvar Control•Governor is operating in Droop Mode•Fixed Field Excitation (no AVR action)

PF Control•Governor is operating in Droop Mode•AVR Adjusts to Power Factor Setting

In ETAP Generators and Power Grids have four operating modes that are used in Load Flow calculations.

Page 25: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 25

Generator Capability Curve

Page 26: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 26

Generator Capability Curve

Page 27: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 27

Generator Capability Curve

Page 28: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 28

Field Winding Heating Limit

Armature Winding Heating Limit

Machine Rating (Power Factor Point)

Steady State Stability Curve

Maximum & Minimum Reactive Power

Page 29: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 29

Field Winding Heating Limit Machine Rating

(Power Factor Point)

Steady State Stability Curve

Generator Capability Curve

Page 30: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 30

Load Flow Loading Page

Generator/Power Grid Rating Page

10 Different Generation Categories for Every Generator or Power Grid in the System

Generation Categories

Page 31: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 31

X

V)*COS(

X

*VVQ

)(*SINX

*VVP

X

V)(*COS

X

*VVj)(*SIN

X

*VV

jQPI*VS

22

2121

2121

22

2121

2121

222

111

VV

VV

Power Flow

Page 32: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 32

Example: Two voltage sources designated as V1 and V2 are connected as shown. If V1= 100 /0° , V2 = 100 /30° and X = 0 +j5 determine the power flow in the system.

I

var536535.10X|I|

268j1000)68.2j10)(50j6.86(IV

268j1000)68.2j10(100IV

68.2j10I

5j

)50j6.86(0j100

X

VVI

22

*2

*1

21

Page 33: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 33

2

1

0

1

Real Power FlowReactive Power Flow

Power Flow1

2

V E( )

Xsin

V E( )

Xcos

V2

X

0

The following graph shows the power flow from Machine M2. This machine behaves as a generator supplying real power and absorbing reactive power from machine M1.

S

Page 34: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 34

ETAP displays bus voltage values in two ways

•kV value

•Percent of Nominal Bus kV

%83.97100%

5.13

min

alNo

Calculated

Calculated

kV

kVV

kV 8.13min alNokV

%85.96100%

03.4

min

alNo

Calculated

Calculated

kV

kVV

kV 16.4min alNokV

For Bus4:

For Bus5:

Bus Voltage

Page 35: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 35

Page 36: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 36

Lump Load Negative Loading

Page 37: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 37

Exercise Time

• Open LF-Example-A1

• Follow instructions in LF-Example-A1.PDF

Page 38: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 38

Load Flow Adjustments• Transformer Impedance

– Adjust transformer impedance based on possible length variation tolerance

• Reactor Impedance– Adjust reactor impedance based on specified tolerance

• Overload Heater– Adjust Overload Heater resistance based on specified tolerance

• Transmission Line Length– Adjust Transmission Line Impedance based on possible length

variation tolerance

• Cable Length– Adjust Cable Impedance based on possible length variation tolerance

Page 39: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 39

Adjustments applied

•Individual

•Global

Temperature Correction

• Cable Resistance

• Transmission LineResistance

Load Flow Study Case Adjustment Page

Page 40: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 40

Allowable Voltage DropNEC and ANSI C84.1

Page 41: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 41

Load Flow Alerts

Page 42: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 42

Bus Alerts Monitor Continuous Amps

Cable Monitor Continuous Amps

Reactor Monitor Continuous Amps

Line Monitor Line Ampacity

Transformer Monitor Maximum MVA Output

UPS/Panel Monitor Panel Continuous Amps

Generator Monitor Generator Rated MW

Equipment Overload Alerts

Page 43: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 43

Protective Devices Monitored parameters % Condition reported

Low Voltage Circuit Breaker Continuous rated Current OverLoad

High Voltage Circuit Breaker Continuous rated Current OverLoad

Fuses Rated Current OverLoad

Contactors Continuous rated Current OverLoad

SPDT / SPST switches Continuous rated Current OverLoad

Protective Device Alerts

Page 44: Loadflow Panel

If the Auto Display feature is active, the Alert View Window will appear as soon as the Load Flow calculation has finished.

© 1996-2009 Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 44

Page 45: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 45

Exercise Time

• Open LF-Example-B1

• Follow instructions in LF-Example-B1.PDF

Page 46: Loadflow Panel

Load Flow Example B1 Part 1

© 1996-2009 Operation Technology, Inc. - Workshop Notes: Load Flow AnalysisSlide 46

Page 47: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 47

Load Flow Example B1 Part 2

Page 48: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 48

Voltage Control

• Under/Over Voltage Conditions must be fixed for proper equipment operation and insulation ratings be met.

• Methods of Improving Voltage Conditions:

– Transformer Replacement

– Capacitor Addition

– Transformer Tap Adjustment

Page 49: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 49

Under-Voltage Example

• Create Under Voltage Condition

– Change Syn2 Quantity to 6. (Info Page, Quantity Field)

– Run LF

– Bus8 Turns Magenta (Under Voltage Condition)

• Method 1 - Change Xfmr

– Change T4 from 3 MVA to 8 MVA, will notice slight improvement on the Bus8 kV

– Too Expensive and time consuming

• Method 2 - Shunt Capacitor

– Add Shunt Capacitor to Bus8

– 300 kvar 3 Banks

– Voltage is improved

• Method 3 - Change Tap

– Place LTC on Primary of T6

– Select Bus8 for Control Bus

– Select Update LTC in the Study Case

– Run LF

– Bus Voltage Comes within specified limits

Page 50: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 50

Advanced LF TopicsAdvanced LF Topics

Voltage Control

Mvar Control

Load Flow Convergence

Load Flow vs. Optimal Power Flow

Page 51: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 51

Mvar Control

• Vars from Utility

– Add Switch to CAP1

– Open Switch

– Run LF

• Method 1 – Generator

– Change Generator from Voltage Control to Mvar Control

– Set Mvar Design Setting to 5 Mvars

• Method 2 – Add Capacitor

– Close Switch

– Run Load Flow

– Var Contribution from the Utility reduces

• Method 3 – Xfmr MVA

– Change T1 Mva to 40 MVA

– Will notice decrease in the contribution from the Utility

Page 52: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 52

Advanced LF TopicsAdvanced LF Topics

Voltage Control

Mvar Control

Load Flow Convergence

Load Flow vs. Optimal Power Flow

Page 53: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 53

Load Flow Convergence

• Negative Impedance

• Zero or Very Small Impedance

• Widely Different Branch Impedance Values

• Long Radial System Configurations

• Bad Bus Voltage Initial Values

Page 54: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 54

Exercise Time

• Open LF-Example-A2

• Follow instructions in LF-Example-A2.PDF

Page 55: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 55

Advanced LF TopicsAdvanced LF Topics

Voltage Control

Mvar Control

Load Flow Convergence

Load Flow vs. Optimal Power Flow

Page 56: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 56

Review of Load Flow Solution

• Given generation, loading and control settings (Mwgen, Vgen, LTC, Capacitor Bank, …)

• Solve bus voltages and branch flows

• Check over/under voltage, device overloading conditions

• Reset controls and run Load Flow again

• Iterative process

Page 57: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 57

Optimal Power Flow Approach

• Given control setting ranges

• Specify bus voltage and branch loading constraints

• Select optimization objectives (Min. P Losses, Min. Q Losses, …)

• Solve bus voltages, branch flows and control settings

• Direct solution

Page 58: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 58

Control Variables

• Load Tap Changer (LTC) Settings• Generator AVR Settings• Generator MW Generation• Series or Shunt VAR Compensator Settings• Phase Shift Transformer Tap Positions• Switched Capacitor Settings• Load Shedding• DC Line Flow• …

Page 59: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 59

Objective Functions

• Minimize Real Power Losses

- To minimize real power losses in the system

• Minimize Reactive Power Losses

- To minimize reactive power losses in the system

• Minimize Swing Bus Power

- To minimize real power generation at the swing bus(s)

Page 60: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 60

Objective Functions

• Minimize Shunt var Devices

- To minimize var generation from available shunt var control devices

• Minimize Fuel Cost

- To minimize total generation fuel cost

• Minimize Series Compensation

- To minimize var generation from available series var control devices

Page 61: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 61

Objective Functions

• Minimize Load Shedding

- To minimize load to be shed from the available bus load shed schedule

• Minimize Control Movement

- To minimize total number of controls

• Minimize Control Adjustment

- To minimize overall adjustment from all controls

Page 62: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 62

Objective Functions

• Maximize Voltage Security Index

Where,

AllBuses

i

n

i

avgii

dV

VV2

,IndexSecurity Voltage

2min,max,

,ii

avgi

VVV

2min,max, ii

i

VVdV

Page 63: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 63

• Maximize Line Flow Security Index

Where, is the line rating

• Flat Voltage Profile- Voltage Magnitude difference between all

buses is minimum

Objective Functions

sAllBranche

i

n

i

i

S

S2

IndexSecurity Flow Line

iSd

Page 64: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 64

Other Constraints

• Bus Voltage Constraints

• Branch Flow Constraints

• Interface Flow Constraints

• …

Page 65: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 65

Exercise Time

• Open LF-Example-A3

• Follow instructions in LF-Example-A3.PDF

Page 66: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 66

Comparison of LF and OPF

Page 67: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 67

Panel SystemsPanel Systems

Page 68: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 68

Panel Boards• They are a collection of branch circuits

feeding system loads

• Panel System is used for representing power and lighting panels in electrical systems

Click to drop once on OLVDouble-Click to drop multiple panels

Page 69: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 69

A panel branch circuit load can be modeled as an internal or external load

Advantages:1. Easier Data Entry2. Concise System Representation

Representation

Page 70: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 70

Pin 0 is the top pin of the panel ETAP allows up to 24 external load connections

Pin Assignment

Page 71: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 71

Assumptions

• Vrated (internal load) = Vrated (Panel Voltage)

• Note that if a 1-Phase load is connected to a 3-Phase panel circuit, the rated voltage of the panel circuit is (1/√3) times the rated panel voltage

• The voltage of L1 or L2 phase in a 1-Phase 3-Wire panel is (1/2) times the rated voltage of the panel

• There are no losses in the feeders connecting a load to the panel

• Static loads are calculated based on their rated voltage

Page 72: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 72

Line-Line Connections

Load Connected Between Two Phases of a3-Phase System

A

B

C

Load

IBCIC = -IBC

A

B

C

LoadB

IB = IBC

Angle by which load current IBC lags the load voltage = θ Therefore, for load connected between phases B and C: SBC = VBC.IBC

PBC = VBC.IBC.cos θ

QBC = VBC.IBC.sin θ

For load connected to phase B SB = VB.IBPB = VB.IB.cos (θ - 30)QB = VB.IB.sin (θ - 30) And, for load connected to phase C SC = VC.ICPC = VC.IC.cos (θ + 30)QC = VC.IC.sin (θ + 30)

Page 73: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 73

3-Phase 4-Wire Panel3-Phase 3-Wire Panel1-Phase 3-Wire Panel1-Phase 2-Wire Panel

NEC SelectionA, B, C from top to bottom or left to right from the front of the panel

Phase B shall be the highest voltage (LG) on a 3-phase, 4-wire delta connected system (midpoint grounded)

Info Page

Page 74: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 74

Intelligent kV CalculationIf a 1-Phase panel is connected to a 3-Phase bus having a nominal voltage equal to 0.48 kV, the default rated kV of the panel is set to (0.48/1.732 =) 0.277 kV

For IEC, Enclosure Type is Ingress Protection (IPxy), where IP00 means no protection or shielding on the panel

Select ANSI or IEC Breakers or Fuses from Main Device Library

Rating Page

Page 75: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 75

Schedule Page

  Circuit Numbers with Column Layout

Circuit Numbers with

Standard Layout

Page 76: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 76

Description TabFirst 14 load items in the list are based on NEC 1999Last 10 load types in the Panel Code Factor Table are user-definedLoad Type is used to determine the Code Factors used in calculating the total panel loadExternal loads are classified as motor load or static load according to the element typeFor External links the load status is determined from the connected load’s demand factor status

Page 77: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 77

Rating Tab

Enter per phase VA, W, or Amperes for this load.

For example, if total Watts for a 3-phase load are 1200, enter W as 400 (=1200/3)

Page 78: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 78

Loading Tab

For internal loads, enter the % loading for the selected loading category

For both internal and external loads, Amp values are calculated based on terminal bus nominal kV

Page 79: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 79

Protective Device Tab

Library Quick Pick - LV Circuit Breaker (Molded Case, with Thermal Magnetic Trip Device) or

Library Quick Pick – Fuse will appear depending on the Type of protective device selected.

Page 80: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 80

Feeder Tab

Page 81: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 81

Action Buttons

Copy the content of the selected row to clipboard. Circuit number, Phase, Pole, Load Name, Link and State are not copied.

Paste the entire content (of the copied row) in the selected row. This will work when the Link Type is other than space or unusable, and only for fields which are not blocked.

Blank out the contents of the entire selected row.

Page 82: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 82

Summary Page

Continuous Load – Per Phase and Total

Non-Continuous Load – Per Phase and Total

Connected Load – Per Phase and Total (Continuous + Non-Continuous Load)

Code Demand – Per Phase and Total

Page 83: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 83

Output Report

Page 84: Loadflow Panel

© 1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Load Flow Analysis Slide 84

Panel Code Factors

Code demand load depends on Panel Code Factors

The first fourteen have fixed formats per NEC 1999

Code demand load calculation for internal loads are done for each types of load separately and then summed up