LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-1
GAS TURBINEGeneral Electric LM6000 is the world’s most fuel-efficient simple-cycle
gas turbine. The LM6000 delivers world class reliability and economy in
simple-cycle, combined-cycle, and cogeneration applications. Proven
design provides long life for base load or peaking power. SPRINT
intercooling adds additional turbine power.
GENERATOR
Air-cooled generator with brushless excitation, rated 71,176 kVA @
0.85 PF, 13,800 volts, 60 Hz, 59° F (15° C) cooling air, suitable for Class 1,
Group D, Division 2 areas. Generator handles the full continuous power of
the gas turbine at any ambient temperature throughout the operating range.
Generator cooling air is filtered by the inlet air filter. Air cooling eliminates
the need for a cooling water loop and associated fans and pumps. Generator
is utility grade, 2-pole synchronous design with brushless excitation and
PMG (permanent magnet generator). Neutral and Lineside cubicles and
voltage regulator are included. (See Section 6 for details.)
DIRECT DRIVE GENERATOR
60-Hertz Generators are directly coupled to the gearbox with a dry,
flexible diaphragm coupling. No gearbox is required. The coupling
transmits full turbine torque to the generator at all operating conditions.
The following equipment and services are included in the basic scope of supply.
GE LM6000 Gas Turbine
Air-cooled Generator
Flexible Coupling Connects 60 Hz
LM6000 Turbine And Generator
BASIC SCOPE OF SUPPLY
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 2/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-2
ENCLOSURE
Acoustic enclosure for turbine and generator. The unit is protected by a
weatherproof acoustic enclosure with separate compartments for turbineand generator. Each compartment is ventilated with redundant fans.
Hazardous area AC lighting and fire and gas detection equipment are
provided in each compartment. A bridge crane in the turbine compartment
simplifies engine removal and maintenance. (See Section 8 for details.)
BASEPLATE
I-beam baseplate. LM6000 generator sets are mounted on two rugged
I-beam baseplates to simplify shipping and installation. The gas turbine is
mounted on one baseplate; the generator is mounted on the other. Tapered
pins between the baseplates simplify field alignment.
The baseplates are suitable for Uniform Building Code earthquake Zone 4
installations. Lifting spools are built into the baseplates.
INLET AIR SYSTEM
Pre-engineered for performance. GE Aero Energy Products filters all
combustion and ventilation air with a rugged, high-efficiency inlet air
system. We use pre-engineered filter options for job sites with special needs
such as dust, salt air, humidity or other local conditions. Optional cooling
coils improve turbine performance in hot weather, and protect the inlet
during icing conditions (with hot water circulation).
The filter house mounts above the turbine enclosure, supported by the
enclosure frame (or by optional legs). Downward airflow provides filtered
air for combustion and ventilation. This compact filter design is easily
installed in the field, and it eliminates customer-supplied ducting. The filter
system includes a stainless steel inlet silencer and a ladder and platform for
inspection and servicing the filter. (See Section 7 for details.)
Enclosure Protects Equipment And
Reduces Sound Emissions
Baseplates Are Fabricated With
Continuous, Full Penetration Welds
Inlet Air System Filters Both
Combustion And Ventilation Air
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 3/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-3
TURBINE EXHAUST SYSTEM
Axial exhaust for low loss. Straight-line exhaust system reduces pressure
drop and permits closer spacing of multiple units. Customer connects to
circular exhaust flange and furnishes remainder of exhaust system.
(GE Aero Energy Products offers an optional exhaust stack assembly for
simple-cycle units. See Section 9 for details.)
PIPING SYSTEM
Stainless steel throughout.
• 304 stainless steel – lube oil, fuel and water piping and fittings, lube oil
reservoirs, run-down tanks, water wash tanks, hydraulic systems, and
stainless steel trim on valves
• 321 stainless steel – steam piping and fittings
All piping is designed and fabricated to ANSI B31.1 Power Piping Code
requirements. Pipe spools are hydrostatically tested at 1.5 times maximum
working pressure. X-ray inspections are made on 100% of steam piping
welds and a random 10% of all other piping welds.
FUEL SYSTEM
Natural gas fuel system, complete, self-contained . Basic unit includes
natural gas fuel system with fuel metering valve and all necessary shutoff
valves, piping and instruments. Options include:
• Liquid fuel and dual fuel systems
• SPRINT® Power Enhancement System
• NOx Reduction Systems
- Water injection
- Steam injection
- Dry Low Emission (DLE)
(See Section 12 for details.)
Axial Exhaust Simplifies
Equipment Layout
304 Stainless Steel Pipe And Fittings
Woodward Fuel Gas Valve ProvidesPrecise Control
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 4/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-4
LUBE OIL SYSTEMS
Two systems - synthetic oil for the gas turbine, mineral oil for
the generator. Each lube oil system includes stainless steel
piping and reservoirs, stainless steel trimmed valves, duplex
filters and duplex plate and frame coolers.* The coolers, filters
and gas turbine lube oil reservoir are mounted on the auxiliary
module. The generator lube oil tank and filters are mounted on
the main unit.
*Shell and tube and fin-fan coolers are available for customers who prefer
these types (See Options O and P for details).
ELECTRO-HYDRAULIC
STARTING SYSTEM
Rotates turbine for starting and water washing.
Permits 10-minute start to full load**
Starting system includes:
• 200-hp electric motor (150 kW)
• Variable-displacement hydraulic pump
• Air/oil cooler
• Hydraulic reservoir, filters and controls
• Hydraulic starting motor on the turbine accessory gearbox
This system rotates the turbine for starting, water washing and
exhaust system purging. (See Section 10 for details.)
** HRSG Installations without a bypass will require longer loading cycles to warm
the HRSG.
Duplex Plate and Frame Lube Oil Coolers
200-hp Electric Motor Powers Hydraulic
Starting System
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 5/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-5
FIRE DETECTION SYSTEM
Fire and gas detection and extinguishing system.
Including:
• Sensors in turbine and generator enclosures:
- IR/optical flame detectors
- Gas detectors (on gas fuel packages)
- Temperature detectors (with rate-of-rise detection)
• Monitor in unit control panel
• Primary and secondary CO2 cylinders
• Piping and nozzles
• 24-volt fire and gas system battery and charger
(See Section 13 for details.)
DIGITAL CONTROL SYSTEM
Includes control panel and package-mounted sensors, valves and actuators. The GE Aero Energy Products system provides operating,sequencing and safety controls for the gas turbine and generator.The unit panel is suitable for indoor mounting in a nonhazardous, air-conditioned control room. System includes:
• Unit Control Panel, containing:- Digital/fuel controller
- PLC sequencer
- Vibration monitoring system
- Manual/Auto voltage regulator
- Protective relay system
- Industrial or desktop PC for HMI
(color monitor indicates alarms, shutdowns, status)
- Fire and gas system monitor
- Auto/Manual synchronization
- Auto/Manual generator loading
- Provisions for remote control with customer’s DCS
• Package-mounted sensors and valves
• 24-volt control battery system with dual 100% chargers
(See Section 14 for details.)
Fire and Gas Monitor in Unit Control Panel
Operator Controls Gas Turbine And
Generator From Unit Control Panel
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 6/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-6
WATER WASH
“On-line” and “crank wash” systems boost performance and availability.
Water wash system includes a stainless steel reservoir mounted on the
Auxiliary Module, a manifold of spray jets mounted in the turbine inlet
plenum and a pump to pressurize solution into the spray nozzles. An
electric heater for the water wash solution can be included as an option.
Customer supplies necessary chemicals and purified water to the auxiliary
module connection.
COMPONENT TESTING
LM6000 Factory Acceptance Testing
GE Aero Energy Products provides factory acceptance testing on the
LM6000 gas turbines, using GE state-of-the-art test cells.
Tests include:
• Mechanical integrity
• Output horsepower
• Heat rate
• Vibration
Generat or factory test. Each generator is factory-tested to stringent IEEE
or IEC requirements, including rotor overspeed (120%) test. Additional
factory tests are run on selected generators to verify resistances, reactances,
voltage, heat runs and open- and short-circuit characteristics.
Water Wash Removes Fouling and
Improves Gas Turbine Performance
LM6000 On Test
Generator On Test At Factory
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 7/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-7
Turbine and Generator Operate Under
Full Load During “STRING TEST” at
Jacintoport Assembly Plant.
Operation and Maintenance Manuals
Simplify Start-Up And Operation
COMPLETED UNIT TEST
Before shipment, GE Aero Energy Products runs a “full load
string test” on units with new design modifications and on
selected units from each production run. All other gas turbine
generator sets receive a rigorous, 400-point test of the completed
unit, including:
• Switch state (NO or NC), actuation, wiring, set point
• Temperature element output, wiring
• Transmitter range, output, wiring
• Solenoid operation
• Control valve torque motor, excitation, return signal
• Fire system continuity, device actuation
• System flushing verification
• Tubing line continuity and openness (not plugged)
DOCUMENTATION
Drawings:
GE Aero Energy Products provides all engineering drawings on-
line at a secure server (www.project-net.com). Each customer can
enter this database and view, print or annote his own project
drawings. ProjectNet provides the customer with immediate
access to the latest revisions of his drawings. ProjectNet speeds
job completion and saves weeks of time mailing drawings back
and forth.
Manuals:
GE Aero Energy Products provides:
• Installation manuals to assist in field re-assembly.
• Operation and maintenance manuals including:
- Operating concepts
- Troubleshooting
- Basic information on the gas turbine, generator and
auxiliary equipment.
Manuals are printed in English, with imperial and metric
measurement notation. (See Section 18 for details.)
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 8/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-8
TRAINING
Hands-on training for 10 customer’s operators and
supervisors. Experienced instructors, using specially developed
training materials, provide training in basic operating theory
and advanced concepts. Both classroom and hands-on training
are included.
Training includes Gas Turbine Familiarization at GE’s
Evandale, Ohio plant (3 days), plus System Design &
Operations at GE Aero Energy Products’ Jacintoport*, Texas
plant (5 days). Customer provides living and travel expenses
for his employees.
* Training at other locations is possible. Customer provides classroom,
projector, etc. Instructor’s travel and living expenses are billed at cost
plus a small handling charge.
GE Aero Energy Products Turbine
Operations Training at Jacintoport
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 9/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-9
OPTION A SYNCHRONOUS CONDENSER
Corrects system power factor. The LM6000 gener-
ator can be used as a synchronous condenser with
this option. GE Aero Energy Products furnishes a
synchronous clutch in an acoustic enclosure 8 6"
long. The clutch enclosure mounts between the
turbine and generator enclosures. (See section 6
for details.)
OPTION B WATER-COOLED GENERATOR
TEWAC system. GE Aero Energy Products fur-
nishes a totally enclosed water-to-air-cooled
(TEWAC) generator for customers who prefer
water-cooling. Customer must supply approxi-
mately 571 gpm (2161 lpm) of treated water at
85° F (29° C), or cooler, at 100 psig (690 kPa). If
water is to be recycled, customer must supply a
cooling loop to reject approximately
2 million BTU/hr (2110 MJ/hr).
(See Section 6 for details.)
OPTIONAL EQUIPMENT AND SERVICES
Generator With TEWAC Cooler
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 10/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-10
Standard Configuration Options C and D
(May be selected separately)
OPTION C LEFT-HAND PIPING CONNECTIONS
In the standard LM6000 configuration, the customer’s piping connections are on the right
side, as viewed from the exciter. As an option, the unit can be built with the piping connec-
tions on the left side. The turbine removal area is located on the side opposite the piping con-
nections.
OPTION D LEFT-HAND LINESIDE CUBICLE
In the standard LM6000 configuration the generator lineside cubicle is on the right hand side
as viewed from the exciter. The neutral cubicle is on the left. As an option, the unit can be
built with the lineside cubicle on the left-hand side and the neutral cubicle on the right side.
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 11/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-11
OPTION E LIQUID FUEL SYSTEM
Liquid fuel system replaces gaseous fuel system.
Typical liquid fuels include DF1, DF2, JP4 or kero-
sene. Customer must supply liquid fuel at 20–50 psig (138–345 kPa) and at least 20° F (11°C) above
the “wax point” temperature (normally > 35° F
(1.6° C)). Maximum fuel temperature is 150 °F
(65° C). Customer-supplied fuel must be clean, fil-
tered and meet required fuel specifications.
(See Section 12 for details.)
OPTION F DUAL FUEL SYSTEM
Primary and back up.
Complete fuel systems for two different fuels, including piping, valves and
controls. Fuels can be:
• Natural gas with liquid fuel
• Two gaseous fuels
• Two liquid fuels
Manual or automatic transfer to backup fuel.
(See Section 12 for details.)
OPTION G WATER INJECTION
METERING SYSTEM
NO x control with gaseous or liquid fuels. Water
injection is used for NOx reduction on gaseous fuel,
liquid fuel and dual fuel systems. Optional water
injection system includes:
• Inlet strainer
• Valves and piping
• Controls
• Boost pump skid (simplex or duplex)
Water injection can reduce NOx emissions to
42 ppm for liquid fuel and 25 ppm for natural gas
fuel. (See Section 12 for details.)
Liquid Fuel Replaces Gaseous Fuel
Fuel System Can Transfer
Automatically To Backup Fuel
Water Is Injected Into Combustor to
Reduce Nox Emissions
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 12/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-12
OPTION H STEAM INJECTION
METERING MODULE
Reduces NO x Emissions with gaseous fuel . Steam injection is used for NOx reduction with gas-
eous fuel. Optional steam injection system includes:
• Baseplate module for mounting above auxiliary
module
• Steam valves and piping
• Controls
Customer supplies purified steam at 475–670 psig
(3275–4620 kPa) and 650° F (343° C) nominal.
Consult GE Aero Energy Products for details.(See Section 12 for details.)
OPTION I DRY, LOW EMISSIONS (DLE)
Controls NO x without water or steam injection.
We install special manifolds, nozzles and metering
to control flame temperature and reduce emissions
of NOx, CO and unburned hydrocarbons. This
DLE system reduces emissions over the entire
power range, not just at high power settings.(See Section 12 for details.)
OPTION J SPRINT POWER BOOST SYSTEM
SPRINT is a spray intercooling system that:
• Reduces combustion air temperature
• Boosts turbine output power• Increases exhaust energy by injecting fine water
droplets into the inlet and interstage air stream.
(See Section 5 for details.)
Module Controls Steam Injection For
NOx Reduction.
LM6000 With DLE Manifold.
SPRINTcools inlet air stream to
increase turbine output power.
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 13/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-13
OPTION K EVAPORATIVE COOLING
Lowers inlet temperature for added power.
Recommended when high dry bulb temperatures are
common, with low/medium ambient humidity.
K.1 Non-Recirculating Design
The base evaporative cooler system is a non-
recirculating type, fully piped and wired. Customer
must supply 56 gpm (212 lpm) of filtered, potable
water at 15 psig (103 kPag) into the flange connec-
tion at the GE Aero Energy Products filter house,
and must dispose of drain water from a flanged drain
connection on the filter house.
K.2 Recirculating Design
Similar to the non-recirculating design, except
designed for recirculation of evaporative cooling
water from a sump in the bottom of the inlet air fil-
ter. This option includes recirculation pump, conduc-
tivity probe, blowdown and make-up valves, piping
and wiring. Customer must supply filtered, potable
water to a flanged connection on the filter house and
must dispose of waste water from the blowdown
valve. Flow rates will vary based on blowdown.
K.3 Spray Mist Design
This design mists water directly into incoming air
stream. System includes medium pressure water
delivery skid, weather station, spray array, SOVs,
and coalescers. Weather station reads ambient condi-
tions and the integrated controls command SOVs
open or closed to modulate flow. VFD motor main-
tains constant system pressure throughout operating
range of pump and motor.
Evaporative Cooling Lowers Inlet Air
Temperature to Boost Power
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 14/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-14
OPTION L INLET AIR ANTI-ICE COIL
Cold weather protection. GE Aero Energy Products
recommends an anti-ice system for safe operating
during icing conditions (See Section 7 for details).With this option, GE Aero Energy Products installs a
heat exchanger coil as the first element in the inlet
air system. Customer circulates a heated water-gly-
col mixture through the coil to heat the inlet air
15° F (8.3° C). Other anti-ice systems are available.
Check with GE Aero Energy Products for details.
OPTION M INLET AIR CHILLER COIL
Optimize Turbine Output in Hot Weather. Toincrease the output of the LM6000 during hot
weather, GE Aero Energy Products offers the follow-
ing optional cooling equipment:
• High-performance cooling coils installed in inlet
air system.
• Offered in conjunction with a mechanical chiller
skid, complete, ready for on-skid installation with
pumps, motors and controls for water/glycol circu-
lation 3300 gpm (12,493 lpm) supplied by the bal-
ance-of-plant group. (See Section 7 for details.)
OPTION N PULSE FILTER
GE Aero Energy Products uses a pre-engineered,
self-cleaning filter option for job sites with special
needs such as dust, pulp and paper fiber and snow.
Self-cleaning filter elements are provided for com-
bustion and ventilation air paths. The pulse filter
option can be supplied with optional cooling coils to
improve turbine performance in hot weather by cir-
culating chilled water, and protect the inlet during
icing conditions by circulating hot water.
The filter house mounts above the turbine enclosure
and is supported with legs. Downward airflow pro-
vides filtered air for combustion and ventilation.
This compact filter design is easily installed in the
field, and it eliminates customer-supplied ducting.
The filter system includes a stainless steel inlet
silencer and a ladder and platform for inspection and
servicing of the filter.
Pulse Filter
Inlet Air Is Cooled To
Boost Power.
Anti-Ice System Provides Protection
During Icing Conditions
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 15/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-15
OPTION O FIN-FAN COOLER
Fin-Fan Cooler replaces standard plate and framecool-
ers for customers who prefer air cooling of lube oil. Fin-
fan cooler includes dual stainless steel coils (one forsynthetic oil; one for mineral oil) and two electric
motor-driven fans (one running and one backup).
OPTION P SHELL AND TUBE COOLERS
Customers who prefer shell and tube oil coolers can
select them as an option to replace our standard plate
and frame coolers.
OPTION Q WINTERIZATION
Cold weather protection. For equipment operating out-
doors in cold climates, -20° to 40° F (-29 to 4.4° C),
GE Aero Energy Products recommends a winterization
option. This option will include the following modifi-
cations:
• Inlet air anti-icing (See Option L for details).
• Heat tracing and insulation of applicable unit-
mounted piping.
• Enclosing and heating exposed instruments andequipment, as specified by GE Aero Energy Prod-
ucts.
For ambient temperatures below -20° F (-29° C), the
above modifications plus additional special provi-
sions will be required. Consult GE Aero Energy
Products for details.
GE Aero Energy Products
Turbines In Severe Cold Weather
Milne Point, Alaska
Optional Shell & Tube Lube Oil
Coolers
Typical GE Aero Energy Products Dua
Fin-Fan oil Cooler
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 16/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-16
OPTION R BLACK START SYSTEM
Emergency starting power. Includes a 600 kW* die-
sel generator set, with unit-mounted-battery starting
system, to start the turbine when normal AC power
is not available. The diesel generator provides
480 VAC power (380 V for 50 Hz) to the ventilation
fans, accessories and hydraulic start module. (See
Section 16 for details). A control cubicle for the
black start generator is provided.
* Typical rating. Larger generators are available, if
required, for balance-of-plant loads.
OPTION S MODULAR CONTROL ROOM
Convenient, pre-wired control center. GE Aero
Energy Products can furnish modular control rooms
to house the control panel, MCC and other electrical
equipment normally required for the gas turbine-
generator system. Control building includes air con-
ditioning, heating and insulation. (See Section 16 for
details.)
OPTION T SWITCHGEAR
Metal-clad breaker assembly. GE Aero Energy
Products can include the generator circuit
breaker and related switchgear in our
equipment scope. Switchgear conforms
to our standard design and specifications.
(See Section 16 for details.)
Switchgear Includes Circuit Breaker
and Potential Transformers
Modular Control Room HousesTurbine Control Panel and MCC
Diesel Black Start Generator with
Optional Enclosure
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 17/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-17
OPTION U UNIT MOTOR
CONTROL CENTER
Dependable motor control . Free-standing lineup of motor controls for motors in GE Aero Energy Prod-
ucts equipment.* The MCC is suitable for indoor
installation in optional modular control room or
other nonhazardous area. (See Section 16 for
details.) Customer supplies feeder breaker to ener-
gize the MCC and interconnecting wiring to motors
on main enclosure.
* Balance-of-Plant equipment can be added to the MCC as
a special option.
OPTION V REMOTE WORK STATION
GE Aero Energy Products offers a remote work station
consisting of a desktop Pentium® computer and HMI,
keyboard and mouse. This station is linked to the main
control and mimics the HMI located in the turbine con-
trol panel in monitoring and control features.
OPTION W EXHAUST ASSEMBLY
(SIMPLE CYCLE)
GE Aero Energy Products offers an optional
exhaust silencer assembly for simple cycle installa-
tions. The assembly includes an exhaust expansion
joint, a 90-dB(A) silencer with internally-insulated,
409 stainless-steel lining, and an exhaust stack.
Options include EPA and CEMS sampling ports and
platforms.
Typical GE Aero Energy Products
Exhaust Assembly
Remote Work Station
Motor Control Center Controls Motors
in GE Aero Energy Products
Equipment
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 18/19
LM6000 Gas Turbine-Generator Se
LM6000-60 HZ PSM 4/2002 4-18
OPTION X GENERATOR STEP-UP TRANS-
FORMER
High efficiency transformers. GE Aero EnergyProducts provides robust, high efficiency step up
transformers, designed and tested to IEEE standards.
Transformer high voltage levels, tap changers and
safety features are built to match customer’s site
requirement. (Please consult GE Aero Energy Prod-
ucts for details).
OPTION Y DC ENCLOSURE LIGHTING
GE Aero Energy Products can furnish DC emer- gency lighting in the turbine and generator enclo-
sures as an option. DC lights turn on if AC power
fails.
OPTION Z NI-CAD BATTERIES
GE Aero Energy Products will furnish nickel-cad-
mium batteries as an option to replace our standard
lead-calcium batteries.
OPTION AAWATER TREATMENT SYSTEM
GE can supply a water treatment system configured
to provide the required water quantity and quality to
meet the operational requirements of the LM6000.
The design incorporates features to enhance perfor-
mance reliability, and incorporates advanced electro-
deionization technology to deliver high purity water
without the need for hazardous chemicals. It is pro-
vided completely assembled, installed and wired in a
separate stand-alone enclosure. Field assembly is
virtually eliminated and connection requirements at
the job site are minimal, so that field labor costs are
low. High purity water is required in the turbine
operation as a pretreatment to optimize efficiency,
specifically in the areas on NOx suppression,
“SPRINT®” (Spray intercooling).
Generator Step-Up Transformer
DC Enclosure Light
Nickel-Cadmium Batteries
Water Treatment System
SCOPE OF SUPPLY
7/16/2019 LM6000 Scope of Supply Doc for Ref Only Thought to Be Opart of 2001 or 2002 Gray Book
http://slidepdf.com/reader/full/lm6000-scope-of-supply-doc-for-ref-only-thought-to-be-opart-of-2001-or-2002-563386401da0d 19/19
LM6000 Gas Turbine-Generator Se
OPTION OPERATIONS AND
BB MAINTENANCE
GE Aeroderivative and Package Services
(GE A&PS) provides LTSAs, maintenance agree-ments, extended warranties, and lease engine services.
GE Contractual Services operates and maintains the
gas turbine, generator HRSG, and related balance-of-
plant equipment.
OPTION ON-SITE MECHANICAL
CC REASSEMBLY
Expert on-site assembly. GE Aero Energy Products
personnel will reassemble the standard gas turbinegenerator set and air filter module. The work pro-
vided by GE Aero Energy Products and customer
requirements are shown below. Consult GE Aero
Energy Products for complete details.
GE Aero Energy Products personnel will provide
supervision and labor to perform the following work:
• Reinstall generator and related items, if removed
for shipping
• Install coupling and verify alignment• Install roof ventilation module
• Install standard inlet air filter module
• Mount lineside and neutral cubicles
• Mount CO2 extinguishant module
Customer will provide:
• Authorization for GE Aero Energy Products’
employees to perform the work described above
• Dedicated crane and cherry picker, with operators• Unloading, uncrating rigging and staging of all
equipment
• Placement, leveling and grouting of all equipment
• Electrical and mechanical interconnect piping,
wiring, conduit and cables (including fabrication,
installation and termination labor for these items)
GE Aeroderivative and Package
Services Provides Experienced
Supervisors and Technicians