Ref : 2670000_A 1 27/11/14 LINEAR OPERATOR CARD GETTING STARTED MANUAL ARIANE 3 ARIANE 3 ARIANE 3 ARIANE 3 brushless electric motor for modernisation kit Parc d’Activités Lyon Sud Ouest – 4 route du Dôme – 69630 CHAPONOST Tel : (0033) 04 78 86 81 00 / Fax : (0033) 04 78 86 81 08 Email : [email protected]

Upload: others

Post on 26-Jan-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • Ref : 2670000_A 1 27/11/14

    LINEAR OPERATOR CARD

    GETTING STARTED MANUAL

    ARIANE 3ARIANE 3ARIANE 3ARIANE 3 brushless electric motor for modernisation kit

    Parc d’Activités Lyon Sud Ouest – 4 route du Dôme – 69630 CHAPONOST Tel : (0033) 04 78 86 81 00 / Fax : (0033) 04 78 86 81 08

    Email : [email protected]

  • Ref : 2670000_A 2 27/11/14

    !! WARNINGS !!

    The ARIANE ARIANE ARIANE ARIANE card is default preset in the factory with the parameters :

    in03 ���� 2VOT Operator steel panels

    for a door with a Telescopic Opening, 2 standard panels, and a clear opening from 900 mm to 1300. After wiring according to the electrical schematic diagram attached to the manual’s back cover, switch on the card and configure it with respect to your control system according to the installed door type: Opening direction: change the SMOT parameter (page 16). (manual travel of the door with CMD3 (page 11). Configuring the standard parameters (page 7) For other changes, see Special Applications (page 8). Table of the parameter value ranges (page 19).

    Reminders:

    - Glazed doors (VITR parameter): (details, page 10) Standard EN81 – 1/2 articles 7.2.36 and 8.6.7.5 managed by the ARIANE card. This option prevents the catching of fingers when the door opens.

    - Master 2 mode (details, page 17) The door opens when someone moves through the cell beam and closes when the cell is no longer obstructed.

  • Ref : 2670000_A 3 27/11/14

    ARIANE 3ARIANE 3ARIANE 3ARIANE 3 USER GUIDE When the card is switched on, it executes the control system orders.

    To intervene on ARIANEARIANEARIANEARIANE, you can choose between three display modes, a parameter setting mode, and a manual commands mode:

    Scroll through the menu by successively pressing the key and make your choice by pressing

    the key (If you do not validate the display within three seconds, the display returns to the default value "Fr00"). Display modes :

    - "Fr00" → display of the motor frequency (Hz) - "0000" → display of the position (encoder points)

    - " _ _ " → display of the card’s Input/Output state

    OUVR FERM INSP

    INT NUD CELL RMF1

    RMF2CHOCFdCO FdCF

    A B

    Parameter setting mode : - PARA → Changing the parameters

    In the PARA mode, you can access all the door’s configuration parameters and the operating values.

    Scroll through the configuration parameters : successively press

    Scroll through the operating values : successively press

    To read the value, press

    To change the value, press or To save the new value, press

    To quit the mode, simultaneously press and

    .

    Manual commands mode : - CMD Commands CMD1 to CMD8

    In the CMD mode (for command), you can operate the door independently from the control system orders.

    Scroll through the command modes by successively pressing or To choose a command mode, press (flashing display)

    To quit the mode, press

  • Ref : 2670000_A 4 27/11/14

    CONTENTS

    User guide ............................................................................................................ Page 3

    Connecting the ARIANE 3 card .............................................................................. Page 5

    Special applications ........................................................................................................ Page 8

    � Inspection connection � Parameterizable relay outputs : RMF1, RMF2 � Connecting the cells safety light barrier � Special parameter settings : � Use with semi-automatic doors � Operator for glazed doors � Door equipped with CDL (cab door locking device) � Adaptation to traffic � Energy save

    Glossary .........................................................................................................................Page 11

    Parameter management by ARIANE ................................................................... Page 13 Parameters table ...........................................................................................................Page 15

    Setting parameters backup .........................................................................................Page 16

    Operating values ...........................................................................................................Page 18

    Value ranges table .............................................................................................. Page 19

    Note your setting values ...............................................................................................Page 20

    Maintenance : how to read and delete stored faults ................................................Page 21

    Using the display............................................................................................................Page 22

    Error codes list ..............................................................................................................Page 23

  • Ref : 2670000_A 5 27/11/14

    For the card to operate correctly, you have to mechanically adjust it to

    the door.

    Connecting the Ariane 3 card

    The 230 V power supply must not come from the

    primary of a 110/230/400V transformer.

    If the voltage between neutral (N) and ground (T) is different from 0 volts, power the

    card with an isolation transformer (example : case of IT system connection).

    Check the connection of the motor cable shielding to the Ariane card box.

    Connection of the Hall effect sensor cable coming from the Brushless electric motor

  • Ref : 2670000_A 6 27/11/14

    The inputs (opening/closing orders, etc.) must be connected to dry contacts – do not

    apply the voltage from the control system input.

    Do not use the pins of old contactors to drive the card’s orders in case of renovation.

    Provide for automation operation relays.

    Inspection (input 28): (details, page 8)

    For the intervener’s safety, an inspection input on the cab roof allows directly checking

    the door

    Standard EN81 – 1/2 article 14.2.1.3 a

    The relays of the FCO, FCF and Choc outputs must convey control currents higher than

    10 mA.

    The RMF1 and RMF2 outputs are parameterizable (see special applications, page 8).

  • Ref : 2670000_A 7 27/11/14

    MANDATORY: THE CARD MUST BE CONFIGURED BEFORE IT IS USED FOR THE CONTROL SYSTEM. YOU MUST ONLY FILL IN THE FRAMED PARAMETRES

    Scroll through the menus by repeatedly pressing ,

    Choose ″PARA″ by pressing . Scroll through the parameters with the key

    To read the value, press

    To change the value, press

    To save the new value, press

    Display order of the parameters :

    → MSTF Maintain under closing voltage Default value NO

    → MSTO Maintain under opening voltage Default value YES

    → MODE Operating mode Default value Mait1

    → CHOC SHOCK CONTACT/CONTROL SYS. DIRECTION NO or NF

    → FdC LIMIT SWITCH / CONTROL SYS. DIRECTION NO or NF

    → SMOT Motor rotational direction to be set (check with CMD3)

    → VITR Glazing option to be set

    → CELL Automatic configuration during learning

    →TYPE Door type to be set

    → rMF2 MULTIFUNCTION RELAY 2 butE or VEnt, CAME, buZZ

    → rMF1 MULTIFUNCTION RELAY 1 buZZ or butE, Vent, CAME

    To exit the ″parameters″ menu, simultaneously press and

    Perform a ″learning″ operation over the entire travel range opposite the landing door with the CMD1 command.

    (if the intermediate stop is wired, perform a learning operation with CMD2 after CMD1 )

    THE DOOR IS READY TO WORK

  • Ref : 2670000_A 8 27/11/14

    SPECIAL APPLICATIONS

    INSPECTION CONNECTION

    For the intervener’s safety, an inspection input on the cab roof allows

    directly checking the door.

    Wiring : Connect a NO dry contact between the common (33) and the INSPECTION

    input (28) controlled by the inspection command.

    Operation : When the ″INSPECTION″ command is activated, ARIANE ARIANE ARIANE ARIANE no longer commands automatic control movements at the door, and the orders are no longer

    pulsed.

    The maintained order to open forces an opening at slow speed.

    The maintained order to close forces a closing at slow speed.

    Checkouts : To allow the checkout, when the ″inspection″ command is activated, the commands from the ARIANE ARIANE ARIANE ARIANE keyboard remain active and all the Manual Commands can be

    deliberately performed.

    PARAMETERIZABLE RELAY OUTPUTS (NO contacts)

    Two relay outputs, RMF1 and RMF2, can be equally assigned to four functions :

    A) Intermediate stop, B) Electromagnetic suction disc, C) Buzzer, or D) Electrocam.

    Wirings : RMF1 Contact, terminals 20-21 ; RMF2 Contact, terminals 22-23

    A) OPERATOR WITH INTERMEDIATE OPENING STOP

    The ARIANE card allows controlling, when it drives an Operator of a door with a lateral

    telescopic opening equipped with an intermediate retractable stop, a complete or partial

    opening of the door panels from the cab. With this function, which is designed to

    optimise the flow, you can use the same device either as a goods lift when the door

    panels are completely open, or as a passengers elevator, when the door panels are

    partially open.

    This stop must be wired to the parameterizable rMF1 or rMF2 output.

    B) OPERATOR EQUIPPED WITH AN ELECTROMAGNETIC SUCTION DISC

    This suction disc must be wired to the parameterizable rMF1 or rMF2 output.

    The ARIANE card drives the suction disc via the relay contact ; provide for a specific power

    supply if it is different from the card’s power supply (230Vac).

  • Ref : 2670000_A 9 27/11/14

    C) OPERATOR EQUIPPED WITH A BUZZER

    The buzzer must be wired to the parameterizable rMF1 or rMF2 output.

    The buzzer buzzes during resetting, after a mains power cut-off, nudging (forced slow

    closing), or during keyboard commands.

    D) OPERATOR EQUIPPED WITH AN ELECTROCAM

    The cam command can be wired to the parameterizable rMF1 or rMF2 output. It will be

    managed depending on the door type (semi-automatic or automatic) in accordance with

    the Standard NFP 82-212, article 4.2.14.a)

    CONNECTING THE CELLS SAFETY LIGHT BARRIER

    The cells safety light barrier can be connected to the ARIANE card and also powered by it if

    the barrier is supplied with 12v. The signal must be a Normally Closed (NF) type.

    - To adapt to the used control system’s operating mode, the cells barrier may be

    inhibited or not while the door is reset after a mains power cut-off.

    - If the card operates as the slave, the cell signal is simply fed back to the control

    system via the shock signal.

    - If the card operates as master 1, the cell signal completely opens the door and it is

    also transmitted to the control system via the shock signal.

    - If the card operates as master 2, the cell signal opens the door only when it is

    obstructed, and then will immediately close it afterwards. The cell signal is not

    transmitted to the control system via the shock signal except if the cell’s obstruction

    persists.

    Wirings : Power Supply, terminals 25-27 ; NF Signal, terminals 26-27

    SPECIAL PARAMETER SETTINGS :

    The ARIANE card adapts to the operators management with particularities thanks to

    adjustable parameters. For example, in the case of glazed doors, or the use of cab door

    locking device, or traffic adaptation.

    - OPERATORS USED IN FRONT OF SEMI-AUTOMATIC DOORS

    The cab is held open with a mechanical hook. In this case, set the MSTO parameter to

    NON (NO).

    If there are semi-automatic or automatic doors depending on the floors, the operator

    must have a hook to open and close the doors. Set the parameters as follows :

    MSTO : NON (NO)

    MSTF : NON (NO) or DEPL (MOVE)

  • Ref : 2670000_A 10 27/11/14

    - OPERATOR FOR GLAZED DOORS

    In accordance with articles 7.2.3.6 and 8.6.7.5 of the Standard NF EN 81-1/2, Ariane

    allows detecting the catching of a child’s finger during an opening and triggering a partial

    closing for glazed doors.

    The card must be configured in glazed door (VITR=OUI (YES)) and then the DURO

    parameter can be set to fit the desired sensitivity as well as the opening torque values

    U1-O and U2-O.

    - OPERATOR EQUIPPED WITH CDL (cab door locking device)

    For operators equipped with a Cab Door Locking (CDL) device, the skate travel in

    Opening (CSO) may have to be increased, where necessary, to allow a good unlocking of

    the CDL device in slow speed before the panels accelerate.

    - ADAPTATION TO TRAFFIC

    For the sake of energy saving and less wear on the equipment, the ARIANE card may be

    allowed to go to a reduced opening and closing speed if the calls are spaced very far

    apart. The call/call timeout is set with ″TA-O″ and the desired speed reduction with ″R-FP″.

    ENERGY SAVE

    - The display goes to standby (energy save) after 15 minutes have elapsed without a

    keyboard command (display of a moving point).

    - Automatic door opening movements may be performed at reduced speed when traffic

    is light.

    For more information about the settings for these special applications, refer to the After-

    Sales Service (SAV) Manual.

    ENCODER FAILURE

    - In case the encoder fails, the door continues to operate in downgraded mode : slow

    speed and timed limit switches.

    SHOCK DETECTION DURING CLOSING

    - The door slows down at the spot where the shock occurred already during the second

    closing.

  • Ref : 2670000_A 11 27/11/14

    GLOSSARY

    THE VARIOUS COMMAND MODES

    With the command modes CMD1 / 3 / 5 / 7, you can test and set the parameters of your

    door.

    CMD1 Learning operation for the full travel range

    When this command is sent, the display indicates ″APPR″. The card triggers an opening cycle and then a closing cycle at the end of which the encoder’s absolute value is saved

    as the reference full travel range.

    If a learning operation was unsuccessful, the ″APPR″ or the ″Err6″ message (cf. page 23) will remain displayed at the end of the learning operation. You will

    have to redo it after the fault is eliminated (deleted).

    CMD3 Motor’s direct command

    In this mode, the motor is activated in the opening direction and in the closing

    direction .

    The motor stops as soon as the key is released. This command, among others, is

    intended to check the motor’s rotational direction. To quit this mode, press the key.

    CMD5 Openings and closings by ″″″″O″″″″ and ″″″″F″″″″

    Accessible only after the learning operation (CMD1) has been performed. When the

    key is pressed, it interrupts a closing cycle, if any, and starts an opening cycle. When

    the key is pressed, it interrupts an opening cycle, if any, and starts a closing cycle.

    To quit this mode, press the key.

    CMD7 Opening/closing cycles

    Accessible only after the learning operation (CMD1) has been performed. In this mode,

    the door continuously executes opening/closing cycles. Whenever one of the keys or

    is pressed, the door’s opening direction is reversed.

    To quit this mode, press the key.

  • Ref : 2670000_A 12 27/11/14

    The command modes CMD2/4/6/8 are specific to the settings of the

    doors with an intermediate opening (total or partial door opening on

    demand)

    CMD2 Learning operation of the intermediate travel range

    To start this command, the learning operation of the full travel range (CMD1) must

    have already been performed. Before starting the CMD2, the door must be in the closed

    position.

    The card triggers an opening cycle and then a closing cycle at the end of which the

    encoder’s absolute value is saved as the reference intermediate travel range.

    If a new learning operation of the full travel range is performed, the intermediate travel

    range has to be redone.

    CMD4 Motor’s direct command (intermediate opening)

    The CMD4 mode is exactly the same as the CMD3 mode, but for the intermediate travel

    range.

    CMD6 Intermediate openings and closings with and

    The CMD6 mode is exactly the same as the CMD5 mode, but the key starts an

    intermediate opening cycle. This mode is accessible only if the intermediate learning

    operation (CMD2) has been done.

    CMD8 Intermediate opening/closing cycles

    The CMD8 mode is exactly the same as the CMD7 mode, but the openings are made

    over the intermediate travel range. This mode is accessible only if the intermediate

    learning operation (CMD2) has been done.

  • Ref : 2670000_A 13 27/11/14

    PARAMETER MANAGEMENT BY ARIANE ARIANE ARIANE ARIANE

    The ARIANE card uses a list of parameters called ″″″″work″″″″ parameters

    This list consists of three parts :

    The configuration parameters : MSTO, MSTF, etc.

    The operating values : FP-O, FF-O, etc.

    The manufacturer’s parameters : Hidden

    All these values can be saved in the "save" list with the "SAVE" function

    These values can be reloaded in the work list with the "INIT" function

    The ARIANE 3 card memory stores 19 tables of operating values and manufacturer

    parameters for all the operator types.

    These values can be loaded in the "work" list with the functions in01 to in24

    Note : The "SAVE" function is only accessible in the "manufacturer" mode.

    To enter the manufacturer mode :

    1. Switch off the card and wait for the relays to ″break″ 2. Press and hold the keys "+" and "Valid" 3. While still holding the keys, switch on the card again

    When "FP-O" is displayed, release the keys. You are in the "manufacturer" mode

    Access to the "SAVE" and "INIT" commands via the ″Pini″ configuration parameter

  • Ref : 2670000_A 14 27/11/14

    Pini

    Choice parameter for values pre-saved in the Ariane card depending on door type and

    door dimension.

    The following list allows to choose the value table corresponding to the door

    driven

    IN 01 IN 02 IN 03 IN 04 IN 05 IN 06

    IN 07 IN 08 IN 09 IN 10 IN 11 IN 12

    IN 13 IN 14 IN 15 IN 16 IN 17 IN 18

    Door type : 2VOL / 3VOL

    CO till 850 CO 900 to 1200 CO and CH very large

    STEEL GLASS STEEL GLASS STEEL GLASS

    GLASS

    GLASS

    Door type : 4VOC / 6VOC

    CO till 850 CO 900 to 1200 CO and CH very large

    STEEL GLASS STEEL GLASS STEEL

    STEEL GLASS STEEL GLASS STEEL

    Door type : 2VOC

    CO till 850 CO 900 to 1200 CO and CH very large

    In order to store your choice of parameters, quit the parameter setting by

    simultaneously pressing and .

  • Ref : 2670000_A 15 27/11/14

    PARAMETERS TABLE

    Specific to Ariane 3 CANOPEN PrtE Not used Specific to Ariane 3 CANOPEN baud Not used Motor type Motr ASyn / bruS Last 10 faults Err Fault no. 0 to 9 + EFF Cycle counter CYCL n X 1000 cycles Default parameter setting Pini QUIT/init/ini1/ini2,,,

    Multifunction relay output rmF1 butE/buZZ/CAME/VEnt (stop/buzz/cam/wind)

    Multifunction relay output rmF2 butE/buZZ/CAME/VEnt (stop/buzz/cam/wind)

    Door type TYPE MOBI / FI / BATT (mobile/ fixed /semi-automatic)

    Cab cell CELL OUI / NON / LIMI (YES / NO / LIMI)

    Glazing option VITR OUI / NON (YES / NO)

    Motor rotational direction SMOT DIR / INV (DIR / REV)

    Closing FDC direction FDC NO / NF (NO / NC)

    Shock contact direction CHOC NO / NF (NO / NC)

    Operating mode MODE MAIT 1 / MAIT2 / ESCL (MASTER1/MASTER2/SLAVE)

    Maintain under opening voltage MSTO OUI / NON (YES / NO)

    Maintain under closing voltage MSTF OUI / NON / DEPL (YES / NO / MOVE)

    THE ABOVE PARAMETERS VALUES

    CYCL

    Indicates the number of cycles in thousands since the start-up.

    This number cannot be reset to 0.

    Motr Motor type : asynchronous or brushless

    Select the brushless electric motor type with the

    Modernisation kit

    Pini to be filled after having chosen the motor type

    Allows loading the saved or preprogrammed set values.

    INIT allows restoring the last saved parameter setting.

    In01, In02, In03 etc. … allows loading the factory parameters table corresponding to

    the various door types (SAV)

    SAVE allows saving the current setting.

  • Ref : 2670000_A 16 27/11/14

    SAVE PROCEDURE

    Switch off ARIANE and wait 15 seconds

    Press and hold and then ; switch on ARIANE while still pressing the buttons

    Release the buttons after the version U3.-- (or U2.--) is displayed

    The card displays FP-O

    To display Pini, press and then

    To display SAVE, press

    To quit the parameters, simultaneously press and .

    TYPE Door type selection :

    BATT : Operator installed in front of a swinging door

    FI : Operator with fixed blade

    MOBI : Operator with mobile skate

    Warning ! If the door type is changed, a new learning operation

    (CMD1) must be done.

    CELL Cell input control option : OUI, NON, LIMI (YES, NO, LIMI)

    The cell must be a Normally Closed (NF) type and be connected to

    ARIANE

    The cell is automatically ″viewed″ during the learning operation and filled in. The CELL parameter allows eliminating it, where necessary.

    With the LIMI option, the cell is inhibited while the door is reset after a mains

    power cut-off (230Vac).

    VITR Glazed door option : OUI, NON (YES, NO) allows preventing the catching of

    fingers when the door is opened.

    SMOT Software reversal of the motor rotational direction : DIR (DIR) or INV

    (REV)

    FDC Relays operating direction FdC-O/FdC-F :

    NO (NO), NF (NC)

  • Ref : 2670000_A 17 27/11/14

    CHOC OBSTACLE relay’s operating direction : NO (NO), NF (NC)

    MODE Choice of behaviour in case of blocking during closing

    ESCL : Slave mode : the door is not reopened, but the Obstacle relay is

    actuated. The timeout of the control system for the ″operating direction reversal″ movement must be set to 0. MA-1: Master 1 mode : the door is completely re-opened with timeout in

    case of blocking or a cell detection with actuation of the Obstacle relay.

    MA-2: Master 2 mode : the door is reopened as long as the cell signal is

    active in case of a cell detection. Otherwise, the door is immediately

    reclosed. The Obstacle relay is actuated in case of a shock or if the door is completely

    reopened by the cell.

    MSTO Maintain under open voltage OUI, NON (YES, NO). Generally, ″yes″ is for auto doors and ″no″ for swinging doors

    In case a mechanical hook is present to hold the door in the open

    position, choose NON (NO)

    MSTF Maintain under closed voltage OUI (YES), NON (NO) or DEPL (MOVE) DEPL = movement : The motor is maintained under power if the closing

    input is activated. Generally, ″yes″ is for auto doors and ″no″ for swinging doors

    In case a mechanical hook is present to hold the door in the closed

    position, choose NON (NO)

    TA-O Timeout before transition to energy save mode (timeout setting range : 5 to 90 minutes).

    R-FP Frequency reduction ratio 0 to 50% of the ″cruise″ (or normal level-off)

    speeds in energy save mode.

    (r-FP = 0 does not activate the energy save mode)

  • Ref : 2670000_A 18 27/11/14

    u-Fr Braking torque : allows to keep up with door’s inertia.

    u-Fr has a strong impact on the other parameters.

    (to be moderately modified).

    OPERATING VALUES

    The speeds are expressed according to the frequency sent to the motor - therefore in

    Hz. They correspond to the various door opening or closing phases ; they are called by

    their abbreviation : for example, FP-O = Cruise Opening Frequency.

    The ramps of acceleration or deceleration correspond to the time it takes to go,

    respectively, from 0 to 50 Hz or from 50 to 0 Hz expressed in seconds.

    The travel ranges are expressed in encoder points, which correspond roughly to a few

    millimeters.

    The door hardnesses are expressed in % of speed drop off triggering a reopening. The

    higher the %, the harder the door.

    The torques are directly dependent on the voltage sent to the motor. Therefore, they are

    expressed in Volts.

    The minimum voltage values are defined for a 2 Hz frequency and the maximum voltage

    values for a 50 Hz frequency.

    The voltage sent to the motor during the operation is calculated between these two

    extreme values according to the frequency.

    There are three separate parameter settings : opening, closing and skate.

  • Ref : 2670000_A 19 27/11/14

    VALUE RANGES TABLE

    ENTRY POINT IN THE PARAMETERS LIST Cruise opening speed FP-O 2 to 50 Hz End of opening speed FF-O 2 to 50 Hz Skate opening speed FS-O 2 to 50 Hz Movement opening speed FM-O 2 to 50 Hz Cruise closing speed FP-F 2 to 50 Hz End of closing speed FF-F 2 to 50 Hz Skate closing speed FS-F 2 to 50 Hz Movement closing speed FM-F 2 to 50 Hz Opening acceleration time RA-O 1 to 3 sec Opening deceleration time RD-O 1 to 3 sec Closing acceleration time RA-F 1 to 3 sec Closing deceleration time RD-F 1 to 3 sec Slow closing travel CLF 1 to 250 points Slow opening travel CLO 1 to 250 points Braking torque U-FR 10 to 250 Opening hardness DURO 5 to 128% Closing hardness DURF 5 to 128% U/F : Min. opening torque U1-O 20 to 70 Volts U/F : Max. opening torque U2-O 70 to 180 Volts U/F : Min. closing torque U1-F 20 to 70 Volts U/F : Max. closing torque U2-F 70 to 180 Volts U/F : Min. Skate torque U1-S 30 to 70 Volts U/F : Max. Skate torque U2-S 80 to 180 Volts Skate opening travel CS-O 1 to 250 points Skate closing travel CS-F 1 to 250 points Timeout (tps) before entry in energy save mode

    TA-O 5 to 90 minutes

    Frequency reduction ratio in energy save mode

    R-FP 0 to 50%

  • Ref : 2670000_A 20 27/11/14

    RECORD YOUR SETTING VALUES

    (Cross out inappropriate indications)

    MSTF Maintain under closing voltage OUI / NON / DEPL

    MSTO Maintain under opening voltage OUI / NON / DEPL

    MODE Operating mode ESCL/ Mait1 / Mait2

    → CHOC SHOCK CONTACT / CONTROL SYS. DIRECTION NO / NF

    → FdC LIMIT SWITCH CONTACT/CONTROL SYS. DIRECTION NO or NF

    → SMOT Motor rotational direction DIR / INV

    → VITR Glazing option OUI / NON

    → CELL If cell connected to ARIANEARIANEARIANEARIANE OUI / NON /LIMI

    →TYPE Type of door MOBI / FI / Batt

    FP-O Cruise opening speed FF-O vitesse v End of opening speed FS-O Skate opening speed FM-O Movement opening speed FP-F Cruise closing speed FF-F End of closing speed FS-F Skate closing speed FM-F Movement closing speed RA-O Opening acceleration time

    ouverture

    RD-O Opening deceleration time ouverture

    RA-F Closing acceleration time RD-F Closing deceleration time CLF Slow closing travel CLO Slow opening travel U-FR Braking torque DURO Opening hardness DURF Closing hardness U1-O U/F : min. opening torque U2-O U/F : max. opening torque U1-F U/F : min. closing torque U2-F U/F : max. closing torque U1-S U/F : min. Skate torque U2-S U/F : max. Skate torque CS-O Skate opening travel CS-F Skate closing travel

    tA-O Call/call timeout rFP Cruise reduction frequency

  • Ref : 2670000_A 21 27/11/14

    ARIANE - MAINTENANCE

    How to read the 10 stored faults :

    Scroll the menus in steps with , and then choose ″PARA″ by pressing . Go in steps with up to Err : validate

    The screen displays the last saved fault.

    Display example : 01 = 8

    latest saved fault error 8

    Press => display: 02 = (previous fault)

    Press => until display of :10 = (oldest saved fault)

    (When you press , the fault stack contents can be displayed in the reverse

    direction.)

    How to delete the stored fault stack :

    Scroll the menus in steps with , and then choose ″PARA″ by pressing .

    Press until EFFA is displayed and then validate

    The fault stack is deleted :

    Return to the display : 01 = 0 (no fault)

  • Ref : 2670000_A 22 27/11/14

    Using the display

    to view the input/output state :

    (bar strokes mode)

    Enter the display mode (--) by repeatedly pressing the key.

    In this mode, very useful in the troubleshooting phase, you can display the card’s

    Input/Output state.

    (lit leds � active Inputs / Outputs) Door Door opening closing command command Inspection Encoder channels A and B input input input Intermediate opening command input

    OUVR FERM INSP

    INT NUD CELL RMF1

    RMF2CHOCFdCO FdCF

    A B

    Multifunction

    Opening Cell relay outputs Limit input switch Shock output output Closing limit Forced switch slow closing output (nudging) command input

  • Ref : 2670000_A 23 27/11/14

    Err : Error codes list

    Err1 Memory fault

    Err2 Power card mute

    Err3 High temperature

    Err4 Overcurrent detected

    Err5 Overload detected

    Err6 Encoder or drive fault (driveshaft, belt).

    Err7 Mains overvoltage fault (above 270V)

    Err8 Mains undervoltage fault (below 155V)

    Err9 Logic card and power card incompatible

    Err10 Hall effect sensor fault

    EFF Deletion of the last 10 saved errors