line current differential system - belmet · • line current differential with adaptive restraint...

8
217 Transmission Line Protection g Digital Energy Proven current differential protection ensures secure high-speed tripping Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P&C life cycle costs Increased sensitivity through dynamic charging current compensation and communication channel asymmetry compensation Adaptive restraint characteristic provides excellent security against measurement errors including CT saturation. Advanced fault and disturbance recording, including internal relay operating signals thus eliminating the need for external recording devices Phasor Measurement Unit - Synchronized phasor information according to IEEE C37.118 standard In-zone power transformer functionality enables savings on CTs and protection devices requirements Overhead lines and underground cables of different voltage levels Circuits with tapped transformer feeders Suitable for three terminal line configurations, with channel redundancy and direct transfer tripping (DTT) Wide area system monitoring and control and using integrated protection and synchrophasor measurement Applications requiring three-pole autoreclosing and independent synchrocheck supervision Real time monitoring of remote, local and differential per phase currents Oscillography - 64 samples/cycle, up to 64 records Event Recorder - 1024 time tagged events, with 0.5ms scan of digital inputs Data Logger - Up to 16 channels with user selectable sampling rate Synchronised measurement of voltage & current and sequence component phasors - 1 to 60 phasors/sec Monitoring and Metering Protection and Control Line current differential with adaptive restraint and In-zone transformer Stub bus protection Breaker failure Three pole Autoreclose Underfrequency protection Phase, ground, neutral and negative sequence time and instantaneous overcurrent Thermal overload, phase and neutral directional overcurrent and broken conductor Phase over/under voltage, negative sequence overvoltage Two independent Synchronism check elements Communications Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, C37.94 Multiple Protocols - IEC 61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-104 Direct I/O – secure, high-speed exchange of data between L30s for Direct Transfer Trip applications Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports FEATURES APPLICATIONS KEY BENEFITS EnerVista™ Software Graphical Logic Designer and Logic Monitor to simplify designing and testing procedures Document and software archiving toolset to ensure reference material and device utilities are up-to-date Robust communications with up to 8 HardFiber Bricks Seamless integration with existing L30 functions Redundant architecture for dependability and security IEC 61850 Process Bus Interface L30 Multilin™ LINE CURRENT DIFFERENTIAL SYSTEM Cost effective Current Differential System for high-speed Lines and Cables

Upload: vuongdung

Post on 13-Jul-2018

234 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

217

Tran

smis

sion

Lin

e Pr

otec

tion

g Digital Energy

• Provencurrentdifferentialprotectionensuressecurehigh-speedtripping

• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts

• Increasedsensitivitythroughdynamicchargingcurrentcompensationandcommunicationchannelasymmetrycompensation

• AdaptiverestraintcharacteristicprovidesexcellentsecurityagainstmeasurementerrorsincludingCTsaturation.

• Advancedfaultanddisturbancerecording,includinginternalrelayoperatingsignalsthuseliminatingtheneedforexternalrecordingdevices

• PhasorMeasurementUnit-SynchronizedphasorinformationaccordingtoIEEEC37.118standard

• In-zonepowertransformerfunctionalityenablessavingsonCTsandprotectiondevicesrequirements

• Overheadlinesandundergroundcablesofdifferentvoltagelevels

• Circuitswithtappedtransformerfeeders• Suitableforthreeterminallineconfigurations,withchannel

redundancyanddirecttransfertripping(DTT)

• Wideareasystemmonitoringandcontrolandusingintegratedprotectionandsynchrophasormeasurement

• Applicationsrequiringthree-poleautoreclosingandindependentsynchrochecksupervision

• Realtimemonitoringofremote,localanddifferentialperphasecurrents

• Oscillography-64samples/cycle,upto64records• EventRecorder-1024timetaggedevents,with0.5msscan

ofdigitalinputs• DataLogger-Upto16channelswithuserselectable

samplingrate• Synchronisedmeasurementofvoltage&currentand

sequencecomponentphasors-1to60phasors/sec

Monitoring and Metering

Protection and Control• LinecurrentdifferentialwithadaptiverestraintandIn-zone

transformer• Stubbusprotection• Breakerfailure• ThreepoleAutoreclose• Underfrequencyprotection• Phase,ground,neutralandnegativesequencetimeand

instantaneousovercurrent• Thermaloverload,phaseandneutraldirectionalovercurrent

andbrokenconductor• Phaseover/undervoltage,negativesequenceovervoltage• TwoindependentSynchronismcheckelements

Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,

RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,

ModbusTCP/IP,IEC60870-5-104• DirectI/O–secure,high-speedexchangeofdatabetween

L30sforDirectTransferTripapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber

opticportsand2copperports

FEATURES

APPLICATIONS

KEY BENEFITS

EnerVista™ Software• GraphicalLogicDesignerandLogicMonitortosimplify

designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensurereference

materialanddeviceutilitiesareup-to-date

• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingL30functions• Redundantarchitecturefordependabilityandsecurity

IEC 61850 Process Bus Interface

L30Multilin™

LINE CURRENT DIFFERENTIAL SYSTEM

CosteffectiveCurrentDifferentialSystemforhigh-speedLinesandCables

Page 2: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

218218

L30Line Differential SystemTr

ansm

issi

on L

ine

Prot

ectio

n

www.GEDigitalEnergy.com

Protection and ControlThe L30 is a cost effective line currentdifferential protection relay intended forsub-transmission and medium voltagelines and cables providing reliable andsecure operation even under the worstcase power system conditions. The L30providessecurehigh-speedfaultdetectionand clearance suitable for three-poletrippingapplications.PartoftheUniversalRelayfamily,theL30comeswithavarietyof versatile features truly integratingprotection, monitoring, metering,communicationandcontrol inoneeasy-to-usedevice.TheUniversalRelayfamilyoffersahighdegreeofmodularity in itsdesignandfunctionalityprovidingsuperiorperformance in protection and controlmeetingthetoughestrequirementsofthemarketplace.

Current Differential ProtectionTheL30currentdifferentialprotectionrelayusessuperiorandpatentedalgorithmstoaddress the challenges of bandwidth ,security,dependabilityand sensitivity incurrentdifferentialrelaying.Bandwidth requirements are effectivelyaddressedbymeansofapatentednewdata consolidation technique called“phaselets”.Thispermitsapplicationwithinacommunicationsbandwidthof64Kbps,andcandetect faultswithinahalfcyclepluschanneldelay.The L30 innovative dual slope adaptiverestraintcharacteristic,basedonestimates

ofmeasurementerrors,allowtherelaytobesecureonsevereexternalfaultswhilemaintainingsensitivityforinternalfaults.Theestimateoferrorsintheinputcurrentspermitsmoresensitivesettingsthanthoseusedinthetraditionalpercentdifferentialschemes. The Line Differential elementalso has 2nd harmonic inrush-currentinhibit for In-zone power transformerprotection.ThisfunctionalityenablestheL30 toprotect2or3-terminal lines thathave a power transformer in betweenends.

TheL30approachtoclocksynchronizationrel ies upon precise distr ibutedsynchronization. Clocks are phasesynchronized to each other andfrequency synchronized to the powersystem frequency.Each relaycomparesitsclocktothephaseoftheotherclocksandmakesappropriateadjustments.Thisallows forgreater transient ride-throughfor power system and communicationsdisturbances.

Enhancedadditionalsecurity isprovidedby a sensitive current disturbancedetector,whichcanbeusedtosupervisethecurrentdifferentialelement.

The L30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.

L30 Line Differential System

52

Monitoring CLOSE TRIP

Data From/To Remote End(via Dedicated Communications) MeteringFlexElement

TM TransducerInputs

50DD 87L50BF51_251P50_2

79

50P

27P

27X59N

59X

59P

25

51G50G

50N 51N 49 67N

67P

Functional Block Diagram

L30 - Protection, Metering, Monitoring and Control

DeviceNumber Function25 SynchronismCheck27P PhaseUndervoltage27X AuxiliaryUndervoltage49 ThermalOverload50BF BreakerFailure50DD CurrentDisturbanceDetector50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50_2 NegativeSequenceInstantaneousOvercurrent51G GroundTimeOvercurrent51N NeutralTimeOvercurrent51P PhaseTimeOvercurrent51_2 NegativeSequenceTimeOvercurrent52 ACCircuitBreaker59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage67N NeutralDirectional67P PhaseDirectional79 AutomaticRecloser87L SegregatedLineCurrentDifferential

ANSIDeviceNumbers&Functions

Page 3: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

219219

L30Line Differential System

Tran

smis

sion

Lin

e Pr

otec

tion

www.GEDigitalEnergy.com

Charging Current Compensation

For long lines and especially forundergroundcables,thechargingcurrentmaybelargeandresultinexcessivelyhighpickupsettings.TheL30candynamicallycompensate the charging current thusincreasingitssensitivitytothefaultcurrentonlongtransmissionlines.

Enhanced Monitoring Features

TheL30usesadvancederrordetectionandsupervising functions to secure the L30against maloperation due to erroneousdata.Highbiterrorratesareaddressedbymeans of computing a 32 bit CRC checksum,effectivelyaddressing theconcernsofmultiplebiterrorsduetohighchannelnoise.On multiplexed channels, channelasymmetrymaybeexpectedduetopathswitching spurious differential currents,which can endanger the security of thedifferential system. By using GPS timesynchronization, up to 10ms of channelasymmetrycanbecompensatedfor.ExtrasecurityhasbeenimplementedintheL30toensureproperoperationontheeventofIRIG-Bsignalfailure.Integrated channel monitoring providesreal-time diagnostic data on the healthof the L30. Communications channeldeterioration or failure will activate analarm,andcanbeusedtoenablebackupprotection. Channel propagation delayis monitored and adjusted according tovariationsincommunicationpaths.

Communication Topologies

Relays can communicate through directfiber,RS422,G.703,IEEEC37.94interfacesat64Kbps,withextensivechannelmonitoringanddiagnosticsareincluded.Inacurrentdifferential scheme, the L30s exchangedata via the communication link, actingeither asmaster collecting data,makingcalculations andmaking all relevant tripand restraint decisions, or as slave onlytransmittingcurrentdatatotheoneactingasmaster. For two terminal applications,use the redundant communicationscapabilityoftheL30foroptimalreliabilityof the current differential line protection.For this scheme, data is continuouslytransmitted over both channels, so if afailure occurs, the L30 will continue to

sentoverpilotcommunicationschannelsselectable through user configurablelogic.

Autoreclosing

The L30 provides multi-shot autoreclosingforthreepoleapplicationswithindependentlysettabledeadtimeforeachshot . Auto-reclose can be dynamicallyblockedbyuserprogrammablelogic.Fourdifferentauto-relcosemodesareavailableenablingtheuserstoselectthereclosingmodetosuitspecificapplications.

Synchronism Check

The L30 monitors voltage difference,phaseangledifferenceandslipfrequencyto ensureproper breaker closureasperuser requirements. The L30 providesadditionalenhancementsinsynchronizingby checking dead source conditionsfor synchronism bypass under theseconditions.

Breaker Failure

The L30 provides two fully independentbreakerfailureprotectionelements.

IEC 61850 Process BusThe IEC 61850 Process Bus module isdesignedtointerfacewiththeGEMultilinHardFiberSystem,allowingbi-directionalIEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existing

Typical two and application of L30. L30 supports a variety of media cards for signalling between L30’s including direct multimode or single mode fibre, RS422, G.703 and IEEE C37.94.

Typical Applications

providecurrentdifferentialprotection.Forthreeterminalapplications,advancedinter-relay communication featureseliminate the need for redundantcommunicationchannelsduetotheabilityoftheL30toautomaticallyswitchbetweenmaster and slave mode, maintaining adependablesystemevenwithafailureofoneofthecommunicationchannels.

Overvoltage and undervoltage protection

Longlinesunderlightlyloadedconditionsor no-load may experience voltagesexceeding rated per unit voltage levelof the line. Use the phase overvoltageelementoftheL30toinitiatealocaltripaswellasaremotetripusingdirecttransfertrip.

Overcurrent Functions

TheL30provides thermaloverload, timeand instantaneousovercurrentelementsfor phase, neutral, ground, negativesequence,phaseandneutraldirectional.Any of them can run in parallel withprimarydifferentialprotectionorcanbeprogrammedtorunwhenthedifferentialelementisnotavailable.

Direct transfer trip (DTT)

UsethedirecttransfertripfeatureofL30to trip remote breaker. Both single poleand three pole direct transfer trips aresupported. Up to eight signals can be

Page 4: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

220220

L30Line Differential SystemTr

ansm

issi

on L

ine

Prot

ectio

n

www.GEDigitalEnergy.com

Universal Relay applications, includingprotection functions,FlexLogic,meteringandcommunications.

TheGEMultilinHardFiber Systemoffersthefollowingbenefits:

• CommunicatesusingopenstandardIEC61850messaging

• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations

• IntegrateswithexistingT60’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule

• DoesnotintroducenewCyberSecurityconcerns

VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.

Advanced AutomationTheL30incorporatesadvancedautomationfeatures including powerful FlexLogic™programmablelogic,communication,andSCADAcapabilitiesthatfarsurpasswhatisfoundintheaveragelinerelay.TheL30integratesseamlesslywithotherURrelaysforcompletesystemprotection.

FlexLogic™

FlexLogic™ is the powerful UR-platformprogramming logic engine thatprovidesthe ability of creating customizedprotectionandcontrol schemes therebyminimizing theneed,andtheassociatedcosts,ofauxiliarycomponentsandwiring.Using FlexLogic™, the L30 can beprogrammedtoproviderequiredtrippinglogicalongwithcustomschemelogicforlinebreakercontroland interlockinganddynamicsettinggroupchanges.

Scalable HardwareTheL30isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesignallowsforeasyconfigurationandfutureupgrades.

• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes

• Mechanicallylatchingoutputscanbeusedtodevelopsecureinterlockingapplicationsandreplaceelectromechanicallockoutrelays

Monitoring and MeteringTheL30includeshighaccuracymeteringand recording forallACsignals.Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. CurrentandvoltageparametersareavailableastotalRMSmagnitude,andasfundamentalfrequencymagnitudeandangle.

Fault and Disturbance Recording

The advanced disturbance and eventrecording features within the L30 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.Recordingfunctionsinclude:

• SequenceofEvent(SOE)-1024timestampedevents

• Oscillography,

-64digital&upto40Analogchannels

• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel

• FaultReports

-Powerfulsummaryreportofpre-faultandfaultvalues

The very high sampling rate and largeamount of storage space available fordata recording in the L30 can eliminatetheneed for installingcostlystandalonerecordingequipment.

Advanced Device Health Diagnostics

TheL30performscomprehensivedevicehealth diagnostic tests during startupand continuously at runtime to testits own major functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresentdevicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issueshelps improve systemuptime.

FlexLogicTM Designer

Flexlogic™ allows for customizing the L30 to operate and control the breakers and other auxiliary devices needed to fit most line protection schemes and applications.

Page 5: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

221221

L30Line Differential System

Tran

smis

sion

Lin

e Pr

otec

tion

www.GEDigitalEnergy.com

• Comprehensivedevicehealthdiagnosticperformedduringstartup

• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals

CommunicationsTheL30providesforsecureremotedataand engineering access,making it easyand flexible to use and integrate intonew and existing infrastructures. Fiberoptic Ethernet provides high-bandwidthcommunicationsallowingforlow-latencycontrolsandhigh-speed file transfersofrelayfaultandeventrecord information.Theavailable redundantEthernetoptionand the embedded managed Ethernetswitchprovidethemeansofcreatingfaulttolerant communicationarchitectures inaneasy,cost-effectivemanner.TheL30supportsthemostpopularindustrystandardprotocolsenablingeasy,directintegration into monitoring and SCADAsystems.

• IEC61850

• DNP3.0

• IEC60870-5-104

• ModbusRTU,ModbusTCP/IP

Interoperability with Embedded IEC 61850

TheL30with integrated IEC61850canbeused to lower costs associated with lineprotection, control and automation. GEMultilin’s leadership in IEC 61850 comesfrom thousands of installed devices andfollowsonMultilin’sextensivedevelopmentexperiencewithUCA2.0.

• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging

• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVista™ViewpointEngineer

• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVista™ViewpointMonitoring

Multi-Language

TheL30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista™ setup software, andproductmanual. Easily switch between Englishandanadditional languageon the localdisplayswithoutuploadingnewfirmware.

EnerVistaTM SoftwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifieseveryaspectofusing the L30 relay. TheEnerVista™ suite provides all the toolsto monitor the status of the protectedasset , maintain the relay, and integrateinformation measured by the L30 intoDCS or SCADA monitoring systems.ConvenientCOMTRADEandSequenceof

Record the operation of the internal L30 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during line faults and disturbances.

Power System TroubleshootingTheL30containsmanytoolsandreportsthatsimplifyandreducetheamountoftimerequiredfortroubleshootingpowersystemevents.

Analyze line faults using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.

Page 6: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

222222

L30Line Differential SystemTr

ansm

issi

on L

ine

Prot

ectio

n

www.GEDigitalEnergy.com

EventsviewersareanintegralpartoftheUR Setup software included with everyURrelay,tocarryoutpostmortemeventanalysis to ensure proper protectionsystemoperation.

EnerVista™ Launchpad

EnerVista™ Launchpad is a powerfulsoftware package that provides userswith all of the setup and support toolsneeded for configuringandmaintainingGEMultilinproducts.Thesetupsoftwarewithin Launchpad allows configuringdevices in real-time by communicatingusing serial, Ethernet , or modemconnections,orofflinebycreatingsettingfilestobesenttodevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and availablewhen needed.Documentsmadeavailableinclude:

• Manuals

• ApplicationNotes

• GuideformSpecifications

• Brochures

• WiringDiagrams

• FAQ’s

• ServiceBulletins

Viewpoint Monitoring

Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:

• Plug-&-PlayDeviceMonitoring

• SystemSingle-LineMonitoring&Control

• AnnunciatorAlarmScreens

• TrendingReports

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

Viewpoint Engineer

ViewpointEngineerisasetofpowerfultoolsthatwillallowtheconfigurationandtestingofURrelaysatasystemlevelinaneasy-to-usegraphicaldrag-and-dropenvironment.ViewpointEngineerprovidesthefollowingconfigurationandcommissioningutilities:

• GraphicalLogicDesigner

• GraphicalSystemDesigner

• GraphicalLogicMonitor

• GraphicalSystemMonitor

Viewpoint Maintenance

ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:

• SettingsSecurityAuditReport

• DeviceHealthReport

• SingleClickFaultDataRetrieval

EnerVista™ Integrator

EnerVista™ Integrator is a toolkit thatallowsseamlessintegrationofGEMultilindevices into new or existing automationsystems.IncludedinEnerVista™Integratoris:

• OPC/DDEServer

• GEMultilinDrivers

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

User InterfaceTheL30 frontpanelprovidesextensive localHMIcapabilities. The localdisplay isused formonitoring, statusmessaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.

LEDIndicators

Multi-LanguageDisplay• English• Russian• French• Chinese

UserProgrammablePushbuttons

Page 7: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

223223

L30Line Differential System

Tran

smis

sion

Lin

e Pr

otec

tion

www.GEDigitalEnergy.com

Typical Wiring

L30

A B C

52

1

Powersupply

9

CPU

7

COM

8

CT/VT

6Inputs/outputs

*

6Inputs/outputs

*

6Inputs/outputs

*

6

Inputs/outputs

6Inputs/outputs

*

JU MX LW KV BHT DN GS FPR

RS-232

DB-9

(front)

UR COMPUTER

1

TXD RXD

RXD TXD

SGND SGND

1 832

207645

22

CONNECTOR

PERSONALCOMPUTER

CONNECTOR

2 23 34 45 56 67 78 89 9

DC

TOREMOTE

L30

OPTIONAL

TC

TC

N

2

1H1a

H2b

H1cH1b

H2c

H2a

H4a

H4c

H3bH3a

H4b

H3c

SURGE

H6a

H8a

H5b

H7b

H8b

H5a

H7a

H6c

H8c

H5c

H7c

H1

H2

H3

H4

I

V

I

V

I

V

I

V

6G

U8a

U7b

U7a

U8c

U7c U1b

U2b

U3b

U4b

U5b

U6b

U1a

U2a

U3a

U4a

U5a

U6a

U1c

U2c

U3c

U4c

U5c

U6c

SURGEU8b

U1

U5

U2

U6

U3

U4

6H I

V

I

V

I

V

I

V

I

V

I

V

N7a

N1a

N2b

N7c

N1c

N7b

N1b

N8cN8b

N2c

N8a

N2a

N4a

N5b

N4c

N6b

N3bN3a

N6a

N4b

N5c

N5a

N3c

N6c

6K N1

N5

N2

N6

N3

N7

N4

N8

CRITICALFAILURE

OUTPUT

CONTROLPOWER

HILO

1

FILTERSURGE

B3a

B1b

B8a

B6b

B8b

B6a

B3b

B1aB2b

B5b

Tx1 Rx1

Tx2 Rx2

INTE

R-RE

LAY

CO

MM

S.W

7A

FIBER

FIBER

6C

S1

S5

S2

S6

S3

S7

S4

S8

S7a

S1a

S2b

S7c

S1c

S7b

S1b

S8cS8b

S2c

S8a

S2a

S4a

S5b

S4c

S6b

S3bS3a

S6a

S4b

S5c

S5a

S3c

S6c

L6a

L8a

L5b

L7b

L5a

L7a

L6c

L8c

L5c

L7c

SURGE

L1a

L8b

L4c

L2c

L3aL3c

L1c

L3b

L1b

L4a

L2a

6D

minimum

PROVIDED

8L

F1c

F4a

F3c

F2c

F4c

F1a

F4b

F1b

F2a

F3a

F2b

F3b

IA IB IC IGIA5

IA1

IB5

IC5

IG5

IB1

IC1

IG1

F8c

F8a

F5a

F5c

F7c

F6a

F7a

F6c

VX

VA VB

VC VX

VA VB

VC

Multilin

com

10BaseFL

10BaseFL

10BaseT

D1aD2a

D4bD3a

D4a IRIG-BInput

IRIG-BOutput

COM1

RS485

ALTERNATE

NORMAL

Tx2Rx2

Tx1Rx1

BNC

BNC

FibreOptic

*

RemoteDevice

Shielded

Co-axial

Co-axial

com

10BaseFL

10BaseFL

10BaseT

D1aD2a

D4bD3a

D4a IRIG-BInput

IRIG-BOutput

COM1

RS485

ALTERNATE

NORMAL

Tx2Rx2

Tx1Rx1

BNC

BNC

FibreOptic

*

RemoteDevice

Shielded

Co-axial

Co-axial

L30-H00-HCL-F8L-H6G-L6D-N6K-S6C-U6H-W7A

Page 8: LINE CURRENT DIFFERENTIAL SYSTEM - BELMET · • Line current differential with adaptive restraint and In-zone ... used in the traditional percent differential ... calculations and

224224

L30Line Differential SystemTr

ansm

issi

on L

ine

Prot

ectio

n

www.GEDigitalEnergy.com

L30 - * 00 -H * * -F ** -H ** -L ** -N ** -S ** -U ** -W/X ** For Full Sized Horizontal MountBaseUnit L30 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable)

G RS485+Multi-modeST10BaseFH RS485+Mutli-modeSTRedundant10BaseFJ RS485+Multi-modeST100BaseFXK RS485+Multi-modeSTRedundant100BaseFXN RS485+10/100BaseTS RS485and6-portmanagedEthernetSwitch

Software 00 NoSoftwareOptions03 IEC6185006 PhasorMeasurementUnit(PMU)07 IEC61850+PhasorMeasurementUnit(PMU)18 3PAutorecloseandSynchrocheck19 3PAutoreclose,Synchrocheck,IEC61850andPhaseMeasurementUnit(PMU)

Mount/Coating H Horizontal(19"rack)-StandardA Horizontal(19"rack)-HarshEnvironmentCoatingV Vertical(3/4size)-StandardB Vertical(3/4size)-HarshEnvironmentCoating

UserInterface C English

NOTE:Theseselectionsareonlyforhorizontalunits

P Englishwithadditional4smalland12largeprogrammablepushbuttonsA ChineseB Chinesewithadditional4smalland12largeprogrammablepushbuttonsD FrenchG Frenchwithadditional4smalland12largeprogrammablepushbuttonsR RussianS Russianwithadditional4smalland12largeprogrammablepushbuttonsK EnhancedEnglishFrontPanelL EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttonsM EnhancedFrenchFrontPanelN EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttonsQ EnhancedRussianFrontPanelT EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttonsU EnhancedChineseFrontPanelV EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons

PowerSupply H 125/250VAC/DC*SeeBelow H RH 125/250VAC/DCwithredundant125/250VAC/DC

L 24-48V(DConly)L RL 24-48V(DConly)withredundant24-48V(DConly)

CT/VTDSP 8F Standard4CT/4VT8H Standard8CT8L Standard4CT/4VTwithenhanceddiagnostics8N Standard8CTwithenhanceddiagnostics

IEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX NoModule

4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs67 67 67 67 67 8Form-A(NoMonitoring)Outputs6C 6C 6C 6C 6C 8Form-COutputs6D 6D 6D 6D 6D 16DigitalInputs6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs6F 6F 6F 6F 6F 8FastForm-COutputs6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputs

TransducerI/O 5A 5A 5A 5A 5A 4dcmAInputs,4dcmAOutputsSelectamaximumof3 5C 5C 5C 5C 5C 8RTDInputs

5D 5D 5D 5D 5D 4RTDInputs,4dcmAOutputs5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs5F 5F 5F 5F 5F 8dcmAInputs

Inter-RelayCommunications 7A 7A 820nm,multi-mode,LED,1Channelselectamaximumof1 7B 7B 1300nm,multi-mode,LED,1Channel

7H 7H 820nm,multi-mode,LED,2Channels7I 7I 1300nm,multi-mode,LED,2Channels7R 7R G.703,1Channel7S 7S G.703,2Channels7T 7T RS422,1Channel7W 7W RS422,2Channels72 72 1550nm,single-mode,LASER,1Channel73 73 1550nm,single-mode,LASER,2Channels76 76 IEEEC37.94,820nm,multimode,LED,1Channel77 77 IEEEC37.94,820nm,multimode,LED,2Channel2A 2A C37.94SM,1300nmSinglemode,ELED,1ChannelSinglemode2B 2B C37.94SM,1300nmSinglemode,ELED,2ChannelSinglemode

EthernetSwitchoptionwillexcludetheRedundantPowerSupplyoption

2S HighPowerSupply6-portmanagedEthernetSwitch2T LowPowerSupply6-portmanagedEthernetSwitch

Ordering Note: ToviewthelatestoptionsavailablefortheL30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.

• URApplicationsILearningCD TRCD-URA1-C-S-1

• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1

• ViewpointEngineer VPE-1

• ViewpointMaintenance VPM-1

• ViewpointMonitoringIEC61850 VP-1-61850

Accessories for the L30 • ViewGuideformspecifications

• Downloadtheinstructionmanual

• Reviewapplicationsnotesandsupportdocuments

• BuyaL30online

• ViewtheURFamilybrochure

Visit www.GEMultilin.com/L30 to:

Ordering

110503-v5

*Redundantpowersupplyonlyavailableinhorizontalunit .Ifredundantchosen,mustbesametypeMaximum2perchassis