liberal school district · liberal school district es & ms prototypes. 1.1 letter to the...

110
SCHEMATIC DESIGN SUBMITTAL JUNE 23, 2014 LIBERAL SCHOOL DISTRICT Elementary & Middle School Prototypes

Upload: duongkhanh

Post on 21-Sep-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

SCHEMATIC DESIGN SUBMITTALJUNE 23, 2014

LIBERAL SCHOOL DISTRICTElementary & Middle School Prototypes

June 23, 2014

Mr. Paul Larkin, Superintendent Liberal School District USD 480 P.O. Box 949 Liberal, KS 67905-0949

Re: Liberal Middle School and Elementary Prototype Projects Schematic Design Submittal

Dear Mr. Larkin:

DLR Group is pleased to submit the following schematic design phase package for the Liberal Middle School and Elementary Prototype projects. The schematic design phase presents an overview of the building design, the building spaces, and their relationships to the total building. Adjacencies are defined, and the preliminary floor plan is complete. The overall structural, mechanical, and electrical issues have been outlined and addressed in general terms. The site development plan shows all the roads, paved spaces, parking, drop-off areas and bus loops.

The project team is confident that the designs presented meets the District’s goals for the project, and will result in a facility that the District and its patrons can be pleased to call their own Schools.

At this point, the District can greatly affect the success of the project by reviewing the submitted schematic design package in detail and communicating your questions, comments, concerns, and revisions to the project team. DLR Group will address each comment to the District’s satisfaction.

We hope that the District is pleased with the design we have presented, and we look forward to developing it in further detail. Thank you for giving us the opportunity to work on such a rewarding project.

Sincerely,

DLR Group

Brad Kiehl, RA John Clement, RA Principal in the Firm Senior Associate in the Firm

SCHEMATIC DESIGNLiberal School District ES & MS Prototypes

1.1 LETTER TO THE DISTRICT

1.2 SITE CONCEPTS :: SITE PLANS

:: NARRATIVES INCLUDE: :: SITE GRADING AND DRAINAGE :: LANDSCAPE ARCHITECTURE :: ATHLETIC FIELDS AND TRACK :: CIVIL ENGINEERING

1.3 BUILDING CONCEPTS :: THE ES & MS ARCHITECTURE CONCEPTS

:: THE ELEMENTARY SCHOOL VISION :: ES FLOOR PLANS

:: THE MIDDLE SCHOOL VISION :: MS FLOOR PLANS

:: BUILDING RENDERINGS

1.4 STRUCTURAL SYSTEMS

1.5 MECHANICAL SYSTEMS

1.6 ELECTRICAL SYSTEMS

1.7 DLR BUDGET & PROGRAMMING :: PINE ES :: PINE MS :: WESTERN MS

1.8 JE DUNN ESTIMATE & PHASING

TABLE OF CONTENTS

4

GENERAL INFORMATION

1.2 SITE CONCEPTS

The proposed middle schools in this construction package will be located at the west and south sites. A new elementary school will also be located at the south site with the middle school to create a campus-type development for Liberal USD 480.

• Pine Street Site (South): Includes the new south middle school and related site amenities and a new elementary school with parking for about 100 cars and related outdoor play facilities.

• Western Site (West): Includes the new west middle school, parking for about 300 cars, track and fi eld, separate practice fi eld, and related site work.

SITE GRADING AND DRAINAGESite drainage will be directed overland to a combination of ditch sections and enclosed storm drain strategically located throughout the site site areas. Storm water detention is anticipated to be required and will be confi rmed with a storm water management study per city of Liberal public works requirements. Detention would be located within new or existing dry, shallow detention ponds. Refer to the civil engineering portion of the SD narrative.

Proposed building additions will have internal roof drains that will be connected to the existing storm drain system. A Storm Water Management Plan will be prepared during design development for this project. Proposed grading will work to balance cut and fi ll for both sites and erosion control measures will be in accordance with the city of Liberal and Kansas State Standards and Best Management Practices for erosion and sedimentation control.

LANDSCAPE ARCHITECTUREA. Proposed Landscape Plantings: New plantings and street trees will be provided as required by the City of Liberal. School entries will be planted with shade trees and ornamental trees with a few planting beds of shrubs and native grasses to create an inviting entry experience for school patrons and students. Planting beds will be mulched with durable hardwood mulch and edged with bed edging to reduce maintenance. A chemical weed barrier will be installed under and over the proposed shredded hardwood planting bed mulch material to prevent weed growth.

B. The open site areas used for storm water detention and other areas not used for playing fi elds will be seeded with native herbaceous prairie plants and native grasses. The intent is to re-create the natural beauty of the Kansas prairie and minimize the need for mowing, fertilization, and watering.

C. All lawn areas adjacent to the proposed building will be sodded with a drought tolerant, tall turf-type Fescue grass blend.

D. Irrigation: An automatic irrigation system will be provided for the natural turf play fi elds. Supplemental watering of turf and plantings outside of the irrigation zones

5

PINE STREET ES & MS SITE PLAN

will be manually watered with hoses attached to building hose bibs or quick connects located along the irrigation mainline. Areas of irrigation will be coordinated with the District during design development.

E. Elementary School Play Areas: Play areas include an 8,000 SF asphalt hard play with striping for games including: basketball, funnel ball, and possibly tetherball, four- square, hopscotch and other games. The soft play area will be roughly 80 x 80- feet with a 12-inch depth of cushioned engineered wood fi ber fi ll over a drainage layer and sub drain system. The soft play will be ADA accessible with a concrete edge containment curb. Soft play equipment including swings and climbers will be FFE by the District.

F. Middle School Play Areas: Play area includes an 8,000 SF asphalt hard play area with basketball and other court games suitable for middle school age kids. Play equipment including climbers and spinners will be FFE by the District.

G. Site Furnishings: Includes one architectural metal bench at each entry for each school.

SITE CONCEPTS

6

GENERAL INFORMATION CONTINUEDATHLETIC FIELDS AND TRACKA. Running Track: An eight-lane asphalt track with ½” polyurethane surface and structural spray system will be provided with striping meeting State High School Association requirements. Includes an inside perimeter track slot drain. Other track events including Long/Triple Jump, Pole Vault, Discus, and Shot Put will be located adjacent to the track. High Jump will be located inside the track “D” area.

1. New high jump areas at the north and south ends of the track; 2. One long/triple jump with two jump pits; 3. Pole vault landing pad and runway. 4. Install track timing and communication cables in communication boxes within the fi eld surfacing to accommodate track timing and photo fi nishes.

B. Natural Turf Football and Soccer Practice Fields: Construct the athletic fi eld with a well-drained soil mix and perimeter sub-drainage system. Install the following additional improvements:

1. A combination football/soccer goal system will be provided in the turf fi eld per NFHS standards. 2. Scoreboard and fl agpole outside of the track. 3. Football play clocks within the high jump concrete curb area. 4. Install communication boxes for potable water for the players, electric outlets, and track timing and communication system. 5. Install 6-feet height galvanized fencing in locations shown on the drawings around the track and fi eld for crowd control during games and to keep vehicles off of the fi eld areas.

C. Aluminum Grandstand: Construct a 500 seat aluminum grandstand on the home side.

CIVIL ENGINEERINGA. Pine Street Site 1. This site will need to be platted, overriding the previous platted subdivision in this area.

2. Utilities: • The existing lift station located at the north east area of the site (near Griffi th Avenue and Charles Street) will need to be upgraded, according to the City. This will fall under the School’s design and bidding services. Further investigation is needed to confi rm the need for upgrading.

• Sewer - Sewer lines will need to be relocated as well, since they were installed to serve as residential development that has yet to occur. The City will be providing the design and bidding for the sewer projects. Any easements will need to be vacated as part of the platting process.

1.2 SITE CONCEPTS

7

• Water - A water main will need to need relocated in a couple of areas, as they were also installed to serve a residential subdivision. The city will design and bid this relocation project.

• Power - Overhead power lines are currently crossing the proposed school site. These lines were also installed to serve a future subdivision. The lines need to be relocated. Coordination will need to be made with Southern Pioneer. Regardless, power is available to the site.

• We will need to check with AT&T, Zito (cable), and phone for service to the site. Fiber optic is not in the area.

• Gas - According to Black Hills Energy gas is available to the serve the site.

3. Griffi th Avenue will need to be extended to serve the east side of the proposed site and will be designed and constructed by the school district. Sidewalks will be required to be installed along the west side of the Griffi th extension.

WESTERN MS SITE PLANSITE CONCEPTS

8

GENERAL INFORMATION CONTINUED

1.2 SITE CONCEPTS

CIVIL ENGINEERING CONTINUED 4. Access is anticipated from the extended Griffi th Avenue, Hickory Street, and Walnut Street.

5. A pavement impact study will be required. The study will focus on the travel paths and the impact the traffi c will have on the current street structure. Some streets (Hickory, Walnut – last couple of eastern blocks, and Warren) only have a chip and seal structure. Bus traffi c will damage these streets after a short time and chip and seal is not intended to support a lot of standard vehicle traffi c.

6. Detention - The City has stated detention will be required for the proposed improvements. We understand the detention facility could be placed south of our site, as the developer to the south will modify the facility in the future when he develops the site. Although fi ll will most likely be placed in the fl oodplain for the control structure, more earth will likely be removed for the detention containment volume resulting in a net loss of earth in the fl oodplain. The City would fi le the necessary documents to FEMA for the permit. Detention could also be placed on- site for the school improvements only.

B. Western Site 1. The site will require platting, a drainage study, and a traffi c impact study.

2. Access is anticipated from Western Avenue.

3. The site has a blanket gas easement. The gas company will need to be contacted to vacate the blanket easement. Gas line should be able to be relocated to stay away from the school. The natural gas line runs along the western part of the site.

4. Coordination with FAA will be required prior to construction of the site to ensure building height and equipment height will remain below FAA’s height restrictions.

5. ONEOK has a high pressure pipeline clipping the S.E. corner of the site. We will need to have tight coordination with ONEOK to ensure we avoid confl ict with the proposed sanitary sewer service line and drainage design items (detention and storm systems).

6. Detention - Drainage runoff can be conveyed from the site to the “fi gure 8” detention facility south of the site (and increase the size of the detention facility – school district can use the fi ll) if the desire is to not have detention on-site. The City has an easement along the west side of Western Avenue which could be used to convey the storm runoff from the site to the detention facility, if the easement is wide enough. The runoff could be conveyed in an open ditch or through a storm system. Detention could be placed on the school site as well. Engineering Analysis to provide the most economical solution.

7. Traffi c – We understand a traffi c study is needed to evaluate the impact the proposed school traffi c will have on the existing traffi c on Western Avenue. The traffi c study will determine if any improvements are required to the geometrics of the roadway, or if traffi c signals are required.

9

8. Utilities – • Water - A 14-inch water main exits along the west side of Western Avenue. The City states the line should have enough pressure and fl ow to serve the site.

• Sewer – the City is designing and will be installing a new sanitary main to serve the proposed Western site. We understand this line will be installed deep enough to gravity fl ow the sewage from the new school.

• Power – Power line exist along the west side of Western Avenue and can serve the site

• Gas – According to Black Hills Energy gas is available to the serve the site.

DISCOVERY COURTYARDSAs a site plan feature to the ES Prototype, Discovery Courtyards are located adjacent to the Media Center and surrounded by building on three sides. This courtyard is a place for an outdoor learning classroom or simply a quiet place to read and enjoy the outdoors. These areas can be uniquely themed post-construction through the collaboration of the community & students.

SITE CONCEPTS

PINE ES SITE PLAN

10

DESIGN CHALLENGE:: Create student centered 21st century learning environments:: Establish parity and equity for all students and faculty:: Foster teacher/student relationships to promote self-learning and collaboration

GUIDING PRINCIPLES OF ES & MS DESIGNS

ES PROTOTYPE DESIGNThe design team has developed the proposed schematic design to meet the challenges and implement the guiding principles of design. The new elementary prototype will use the latest technology to reinforce the District’s emphasis on creating a 21st century school that serves the community, meets the needs of the students and provides a safe place for learning.

As established during the Visioning Meetings, the prototype design is organized around two grade level neighborhoods and delineation of community use spaces from classroom spaces. These ideas reinforce collaboration within classroom neighborhoods and promote community integration in the school. Classroom neighborhoods are organized around a fl exible Discovery area that provides additional educational space for students. These open, technology-fi lled Discovery areas take on a unique and identifi able character for each neighborhood. Natural daylight and views to an outdoor learning courtyard promote a positive learning environment.

The location of the commons, gymnasium, and media center allows for community use outside of school hours. Centered on the commons, the music room also serves as a stage for school or community performances. To further the fl exibility of the commons, an operable wall separates the gymnasium from the commons. This allows for a greater variety of uses for the students and community.

A safe and secure entry is established through the location of the administration. Visitors are directed through a reception area before gaining access to the school. A parent center adjacent to the administration provides a place for parents to interact and connect with the staff, administration, and each other. This unique space also facilitates parental involvement with the students.

THE ES & MS ARCHITECTURE CONCEPTS

1.3 BUILDING CONCEPTS

CURRICULUM NEEDS COLLEGE & CAREER PREPBETTER TEACHER-STUDENT RATIO GLOBAL LEARNING FLEXIBLE STUDENT CENTERED SAFE & SECURECOMMUNITY INTEGRATION COLLABORATION SPACES

THE ELEMENTARY SCHOOL VISION

11

UPPER LEVEL FLOOR PLAN

ELEMENTARY SCHOOLMAIN LEVEL FLOOR PLAN

CLASSROOM COMMONSFITNESSADMINISTRATIONSUPPORT

MEDIA CENTER

MUSICART

SPECIAL EDUCATION

ROOF

OPEN TO BELOW

BUILDING CONCEPTS

12

Three distinct spaces in the new elementary school are centrally located within the building plan. The media center, art, and music rooms all provide a unique learning environment. These spaces become a focal point in the design of the school through their location, building massing, and material treatment.

Strong, durable materials clad the exterior of the building. A blend of masonry, metal panel, and glazing in key locations defi ne the functions within and create an inviting and aesthetically pleasing school. Natural daylight and views are provided in all classrooms to enhance the learning environment.

COMMUNITY CHARACTERISTICSThe design team established key areas of the elementary school prototype that respond to each distinct school community. The Discovery Courtyard and the Community Courtyard take on a unique design related to the community in which the school resides. The exterior building materials also distinguish the individual school. Through the use of the color and pattern, a unique aesthetic defi nes each building.

Within the school, interior materials also establish a character that responds to the school’s community. Material pattern, color, and fi nish express a unique aesthetic for each individual elementary school. Through these elements, each prototype school takes on an individual character that responds to the community in which it resides.

The interior of the elementary schools will be a positive and creative environment that serves as a learning tool for students, the community and visitors. The interior will have a comfortable, fun and cool vibe through the use of innovative materials, textures and colors.

Each school will have established individual character that responds to the community in which it resides. This will occur through the placement of color and materials. Material fi nish selections will be durable and easy to maintain.

FLOOR FINISHESThe Main Corridor will have polished concrete. The Administration, Media Center and Music room will have carpet tile. The Commons Area will have resilient fl oor tile, while the Gymnasium will have resilient athletic sheet fl ooring. In the Kindergarten, First, Second, and Third Grade Classrooms, the fl oor fi nish will be carpet tile and resilient fl oor tile. The Fourth and Fifth Grade Classrooms will also have resilient fl oor tile. The Discovery Areas and Classroom Corridors will have a combination of carpet tile and resilient fl oor tile. In the Kitchen and rest rooms, the fl oor fi nish will be epoxy resin.

WALL FINISHESLobbies, Main circulation and Commons will have painted gypsum and painted concrete masonry units. Wall materials throughout classrooms neighborhoods will be high impact resistant wall board for durability. Decorative tack walls will be provided in key locations such as corridors, media center, and discovery areas. Painted wood fi ber board acoustical panels will be used in the gymnasium and

THE ES INTERIOR DESIGN VISION

THE ELEMENTARY SCHOOL VISION CONT.

1.3 BUILDING CONCEPTS

13

commons as needed to make the spaces acoustically comfortable. Rest rooms will have wainscot ceramic tile on wet/plumbing walls.

CEILING FINISHESThe ceilings will be 2’ x 2’ suspended acoustical panels with high NRC in Classrooms, Main Circulation corridor, the Media Center, Classroom corridors, Discovery Areas, Administration, and the Music classroom. Gypsum board soffi ts and bulkheads will be used in key locations throughout the building to defi ne a sense of entry and divide ceiling planes and heights. Some spaces will have exposed structure with fl oating acoustical clouds, such as the Corridors, Commons and Discovery areas. Some rooms may have exposed structure with no ceiling, such as the Art room, electrical and janitor closets, mechanical, and other rooms where ceilings are not required for the aesthetic or sound transmission purposes.

BUILDING CONCEPTS

THE MIDDLE SCHOOL VISION MS PROTOTYPE DESIGNDLR Group’s Liberal Middle School project team set out to design a new middle school for 6th through 8th grade students and staff. The building is organized to address a variety of issues and concerns, as well as building uses and teaching methods, that were identifi ed by the School District and DLR Group’s project team.

The circular Media Center sits at the core of the building, with a round-about corridor branching into radius hallways leading into academic wings and the public, community, and common spaces. Separate drives for bus and drop-off traffi c each have an entrance into the common areas of the building. Students arriving in the morning will enter one of the entrances and will go to the centrally-located commons area before classes begin. 6th graders will travel around one side of the roundabout corridor into their academic wing, while 7th and 8th graders travel the opposite side of the roundabout into their wing. Each academic wing houses Core Classrooms, Science Prep and Storage, a Teacher’s Planning Center, Resource Room, Computer Lab, a Small Conference Room, and two banks of restrooms. The academic wings are essentially self-contained, achieving separation of the 6th graders from the 7th-8th graders.

On the opposite side of the Media Center core are the building’s public, administrative, and elective spaces. Administration is located at the front entrance to the building to allow for proper supervision of the entrance, as well as convenient access from all areas of the building. The Commons area is also at the heart of the building and will serve as the eating area, a place for students to congregate before classes begin, and a gathering area for student or public activities. The Music Classroom rooms are located adjacent to Administration Suite. An 800-seat competition gym, support spaces, and a weight room are located at the north entrance. This allows for easy parking and after hours access for events and practices.

Elective classrooms, including FACS, Industrial Tech, Music, and Art are all centrally located off the Media Center roundabout corridor. This arrangement provides maximum program fl exibility and convenient access.

Special Education classrooms are located throughout the building. Inclusive program classrooms are near the building’s core, with additional classrooms for pullout and speech programs in each academic wing.

14

Staff support spaces are plentiful, and designed to meet the planning, preparation, and training needs of teachers and staff members. In addition to a Teacher’s Planning Center in each academic wing, staff will have a separate dining/lounge area adjacent to the Commons area and Cafeteria, and a Forum Room between the academic wings designed to accommodate large training sessions or meetings.

The new Liberal Middle School is designed to meet the growing functional needs of the District’s staff and students, while providing the fl exibility necessary to accommodate various teaching methods and a variety of student and staff activities.

EXTERIOR BUILDING MATERIALSThe exterior building materials will be modifi ed through the use of color and pattern of the materials listed below to distinguish a unique and aesthetic defi nition of each building for the individual schools.

The exterior building will be constructed of brick veneer on concrete load bearing masonry units, with two or three colors of brick incorporated in the design for accent. Precast concrete or cast stone will be used at windowsills and lintels for added accents to the façade. At the two main entrances and the Media Center clerestory, storefront or curtain wall system with metal panels above shall be incorporated to accent these key building elements.

The front entrances and commons area curtain wall systems shall have tinted glass to accent the building colors. Either storefront or aluminum windows will be strategically located in classrooms, the administration area, and other areas that require adequate natural lighting. The roof membrane will be a modifi ed bitumen roof system.

INTERIOR BUILDING MATERIALSThe interior building materials will be modifi ed through the use of color and pattern of the materials listed below to distinguish a unique and aesthetic defi nition of each building for the individual schools.

The majority of the building’s interior spaces will consist of concrete masonry walls. In the administration, media center and other areas with minimal threat of abuse, walls will largely be constructed of drywall over metal studs. Select interior public spaces will be accented with wood and, in some cases, exterior building wall materials.

The classroom wings, Media Center and administration will have carpeted fl oors. The Commons and central circulation corridor fl oors will be covered with an easily maintained vinyl product. The gymnasium will have a traditional cushioned maple plank fl ooring system. The restrooms and food service areas will be fl oored with quarry or porcelain tiles. Locker and shower rooms will have seamless epoxy resin fl ooring systems. Stained concrete will be used for the art, forum and science

THE MS INTERIOR DESIGN VISION

THE MIDDLE SCHOOL VISION CONT.

1.3 BUILDING CONCEPTS

15

BUILDING CONCEPTSMIDDLE SCHOOL FLOOR PLAN

CLASSROOM COMMONSFITNESSADMINISTRATIONSUPPORT

MEDIA CENTER

MUSICART

SPECIAL EDUCATION

classroom fl oors. There will be sealed concrete in the janitor’s closets, mechanical rooms, electrical rooms, and throughout building services areas.

The majority of the interior partitions will be painted. There will be wallcoverings applied in select administration areas. Classrooms and corridors will have tackable surfaces and markerboards.

Most ceilings will be a highly absorbent 2’ x 4’ acoustical tile. There will be exposed structure ceilings in the art classrooms, gymnasium, janitor’s closet, electrical rooms, and other areas where ceilings are not required for aesthetic or acoustical purposes. Restrooms and shower rooms will have epoxy painted drywall ceilings for moisture control. There will be a combination of painted drywall soffi ts and acoustical ceilings in the corridors and public areas such as the media center, commons and administration.

THE MS INTERIOR DESIGN VISION CONT.

16

ELEMENTARY SCHOOL RENDERINGSCOMMUNITY COURTYARD

1.3 BUILDING CONCEPTS

17

RENDERINGS

18

ELEMENTARY SCHOOL RENDERINGSMAIN ENTRY

1.3 BUILDING CONCEPTS

19

RENDERINGS

20

ELEMENTARY SCHOOL RENDERINGSCOMMONS

1.3 BUILDING CONCEPTS

21

RENDERINGS

22

MIDDLE SCHOOL RENDERINGSEXTERIOR PERSPECTIVES

1.3 BUILDING CONCEPTS

23

RENDERINGS

BUILT EXAMPLE

24

MIDDLE SCHOOL RENDERINGSEXTERIOR PERSPECTIVES

1.3 BUILDING CONCEPTS

25

RENDERINGS

BUILT EXAMPLE

26

MIDDLE SCHOOL RENDERINGSEXTERIOR PERSPECTIVES

1.3 BUILDING CONCEPTS

27

RENDERINGS

28

GENERAL OVERVIEWThe new Liberal Middle School Prototypes will be a one-story structure. The design will include an area of last resort (AOLR) for increased occupant protection during severe wind events, the structural design of which will be based on ICC 500-2008.

The new Liberal Elementary School Prototypes will consist of both one-story and two story components. The design will include an area of last resort (AOLR) for increased occupant protection during severe wind events, the structural design of which will be based on ICC 500-2008. STRUCTURAL SYSTEMS DESCRIPTIONA. Roof Systems: The roof framing systems at both schools will typically be a 1½” x 20 gage wide rib (Type B) painted metal roof deck supported by open-web steel joists and structural steel beams spanning between a combination of load bearing masonry walls and structural steel beams and columns. 3” x 22 gage Type N painted metal roof deck is anticipated to be used in the gymnasiums of both schools. Metal deck spans in the gymnasiums are anticipated to be 8’-0” to 10’-0”.

B. Floor Systems: At the Elementary Schools the typical elevated fl oor framing system will consist of a 3” thick reinforced concrete slab over 3” x 20 gage composite metal deck (6” total thickness) capable of spanning 8’-0” to 10’-0” between steel beams. Typical steel beams will be designed with headed studs to engage the slab in a composite manner to reduce steel costs. The typical fl oor framing will be supported by a combination of load bearing masonry walls and structural steel beams and columns. The fl oor framing over the area of last resort will either be a composite structural steel system as described above, with an additional 3” of concrete (9” total thickness), or a system consisting of precast hollowcore planks with a topping slab. The walls at the area of last resort will be either reinforced concrete or fully grouted masonry. Concrete walls at the perimeter of the area of last resort will be a minimum of 8” thick. Masonry walls at the perimeter of the area of last resort will likely need to be a minimum of 12” thick.

C. Foundation Systems: Foundations at both schools will consist of isolated and continuous shallow foundations that bear on suitable soil materials prepared as recommended by the project geotechnical engineer. All footings and foundations will be cast-in-place concrete and reinforced with ASTM A615 Grade 60 reinforcing steel. Perimeter trench footings will extend to frost depth as required by the building code and as recommended by the project geotechnical engineer. Slabs on grade will be a minimum of 4 inches thick and reinforced with welded wire reinforcement. Slabs on grade will be placed over a 15 mil vapor retarder placed on a minimum of 4 inches of granular drainage fi ll over the subgrade prepared as recommended by the project geotechnical engineer’s report.

D. Lateral systems: Resistance to wind and seismic lateral forces will be provided by ordinary reinforced masonry shear walls at the Middle Schools and by steel concentrically braced frames at the Elementary Schools.

1.4 STRUCTURAL SYSTEMS

29

STRUCTURAL DESIGN CRITERIAA. Roof Dead Loads 1. 3 psf joists 2. 2 psf metal deck 3. 10 psf insulation 4. 5 psf MEP 5. 5 psf fi nishes 25 psf Total Roof Dead Load

B. Roof Live Loads 1. 20 psf minimum 2. 25 psf for preliminary design 3. Roof top unit weights 4. No live load reductions

C. Floor Dead Loads (Typical) 1. 57 psf 3” concrete slab on 3” composite metal deck 2. 6 psf ½” extra concrete 3. 10 psf MEP 4. 7 psf fi nishes 80 psf Total Typical Floor Dead Load 5. 75 psf 6” concrete at Area of Last Resort 155 psf Total AOLR Floor Dead Load

D. Floor Live Loads 1. ASCE 7-05, Chapter 4 2. Classrooms 40 psf 3. Corridors 80 psf 4. First Floor Corridors 100 psf

E. Snow Loads 1. ASCE 7-05, Chapter 7 2. Ground snow load, Pg = 15 PSF 3. Occupancy Category: III (ASCE 7-05, Table 1-1) 4. Exposure Factor, Ce = 1.0 Terrain Category B, Partially Exposed (ASCE 7-05, Table 7-2) 5. Importance Factor, Is = 1.1 (ASCE 7-05, Table 7-4) 6. Thermal Factor, Ct = 1.0 (ASCE 7-05, Table 7-3) 7. Exposure Factor, Ce = 1.0 Partially Exposed (ASCE 7-05, Table 7-2) 8. Minimum roof snow load, Pm = 16.5 PSF

F. Wind Loads 1. ASCE 7-05, Chapter 6 2. Analytical Procedure (ASCE 7-05, Section 6.5) 3. Occupancy Category: III (ASCE 7-05, Table 1-1) 4. 90 mph Basic Wind Speed (3-sec gust) (ASCE 7-05, Figure 6-1) 5. Exposure Category B (ASCE 7-05, Section 6.5.6) 6. Enclosure Classifi cation: Enclosed 7. 250 mph Wind Speed at AOLR (ICC 500-08) 8. Exposure and Enclosure at AOLR per ICC 500-08

G. Seismic Loads 1. IBC 2009, Section 1613 and ASCE 7-05, Chapters 11 &12 2. Site Class: D (Default per IBC 1613.5.2) 3. Seismic Design Category: A 4. Ss = 0.116 (Per USGS ) 5. S1 = 0.041 (per USGS) 6. Fa = 1.6 (IBC 2012, Table 1613.5.3(1)) 7. Fv = 2.4 (IBC 2012, Table 1613.5.3(2)) 8. R = 5 for steel braced frames (ASCE 7-05, Table 12.2.1) 9. R = 2 for masonry shear walls (ASCE 7-05, Table 12.2.1) 10. Omega = 2½ masonry shear walls and steel braced frames (ASCE 7-05, Table 12.2.1) 11. Omega = 12. Cd = 3.5 for steel braced frames (ASCE 7-05, Table 12.2.1) 13. Cd = 1¾ for masonry shear walls (ASCE 7-05, Table 12.2.1) 14. Importance Factor, Ie = 1.25 (ASCE 7-05, Table 11.5-1)

SYSTEMS

30

MATERIALSA. Structural Steel 1. Wide fl ange shapes shall conform to ASTM A992 Grade 50 2. Channels shall conform to ASTM A36 3. Round Hollow Structural Sections (HSS) shall conform to ASTM A500 Grade B (Fy = 42 ksi, Fu = 58 ksi) 4. Square and Rectangular Hollow Structural Sections (HSS) shall conform to ASTM A500 Grade B (Fy = 46 ksi, Fu = 58 ksi) 5. Angles and structural plates shall conform to ASTM A36 6. High strength bolts shall conform to ASTM A325, Type 1 7. Threaded rods shall conform to ASTM A36 8. Anchor rods shall conform to ASTM F1554 Grade 55, weldable 9. Base plates shall conform to ASTM A36

B. Cast-In-Place Concrete 1. Reinforcing Steel: All reinforcing steel shall conform to ASTM A615, Grade 60 unless noted otherwise on the drawings 2. All concrete is normal weight concrete 3. Deformed bar anchors shall conform to ASTM A496. (Fy = 70 ksi) 4. Weldable Reinforcing steel shall conform to ASTM 706 5. Headed stud anchors shall conform to ASTM A108. (Fu = 60 ksi) 6. Spread (dug) footings f’c = 4500 psi, exposure category F2, C1 7. Shallow foundations f’c = 4500 psi, exposure category F2, C1 8. Foundation walls f’c = 4500 psi, exposure category F2, C1 9. Interior slab on Grade f’c = 3500 psi, exposure category F0, C0 10. Composite fl oor slabs f’c = 4000 psi, exposure category F0, C0

C. Structural Masonry 1. Reinforcing Steel: All reinforcing steel shall conform to ASTM A615, Grade 60 unless noted otherwise on the drawings 2. Masonry units shall be normal weight units 3. F’m = 1500 psi

GEOTECHNICAL RECOMMENDATIONSThe geotechnical reports for the two sites are pending.

STRUCTURAL DESIGN CODES2009 International Building CodeICC 500-08 Standard for the Design and Construction of Storm SheltersASCE 7-05 Minimum Design Loads for Buildings and Other StructuresAISC 360-10 Specifi cation for Structural Steel BuildingsAISC Steel Construction Manual 14th EditionACI 318-08 Building Code Requirements for Structural Concrete (and Commentary)ACI 530-11/530.1-11 Building Code Requirements and Specifi cation for Masonry Structures (and Companion Commentaries)

1.4 STRUCTURAL SYSTEMS

31

GENERAL OVERVIEWThe HVAC and plumbing systems will be high performing, focusing on low operation and maintenance costs. Systems selection will focus on minimizing audible disruption from the HVAC and plumbing systems in the learning environment. Systems will be standardized to achieve effi ciencies in maintenance and operation.

APPLICABLE REFERENCE STANDARDSAll work, materials, and installations shall conform to appropriate codes, regulations, and enforcing agencies as listed below:

Americans with Disabilities Act, Accessibility Guidelines (ADAAG) American Refrigeration Institute (ARI) American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) American Society of Mechanical Engineers (ASME) Local and State Mechanical Code National Fire Protection Association (NFPA) Occupational Safety and Health Act (OSHA) Regulations of Local Utility Companies Sheet Metal and Air Conditioning Contractors National Association (SMACNA)

Design will conform to the following building codes:

2009 International Fire Code 2009 International Building Code 2009 International Mechanical Code 2009 International Plumbing Code 2009 International Fuel Gas Code 2009 International Energy Conservation Code

PLUMBING SYSTEM

A. Water Conservation: The vision for water conservation is to achieve 35% less water usage than a typical building according to the calculation procedure established by the USGBC.

B. Domestic Water System: 1. The domestic water service to the building will be sized based on the available water pressure at the site, the total required fl ow required by the fi xtures shown on the architectural plans, and to deliver a minimum pressure of 25 psi to the most remote fi xture.

2. The domestic water service to the building will be protected by a reduced pressure backfl ow preventer located inside the building in the main mechanical room.

3. Hot and cold water will be extended to all fi xtures where required.

1.5 MECHANICAL SYSTEMS SYSTEMS

32

1.5 MECHANICAL SYSTEMS

PLUMBING SYSTEM CONT. 4. Domestic water piping will be Type L copper piping with lead-free solder joints or mechanical coupling similar to pro-press.

5. The domestic water systems valves shall be bronze construction gate or ball valves. Valves will be installed to isolate individual fi xtures and groups of plumbing fi xtures.

6. Insulation: Cold and hot water will be insulated using fl exible elastomeric or mineral fi ber preformed pipe insulation. The insulation thickness will be specifi ed to be consistent with the energy code requirements.

7. Pipeline Supports: Domestic water pipeline supports will be specifi ed to be consistent with the requirements of the applicable plumbing code.

8. Identifi cation: Pipelines will have identifi cation tags and fl ow arrows. Pipeline identifi cation tags will be adhesive markers that are commercially available.

9. Water supplies to lavatories, sinks, and drinking fountains will have angle stops with loose key handles.

10. Hose bibs shall be provided in each large group restroom, and mechanical room. The hose bib will be surface mounted behind a lockable cover with access by a removable key.

C. Domestic Hot Water: 1. The domestic water heating system will comply with the requirements of the energy code.

2. Two domestic hot water systems will be located in the main mechanical room near the kitchen; one for the kitchen and one for the remainder of the building. Recirculation loops and pumps will be provided to ensure timely delivery of hot water to every fi xture.

3. The domestic hot water system for the kitchen will be distributed at 140 degrees F. Point of use mixing valves will be used to temper the hot water to hand washing sinks.

4. The domestic hot water system for the classroom wings will be distributed at 115 degrees F.

5. Hot water will be generated by 90%+ high effi ciency direct vent gas-fi red water heaters with integral storage tanks.

6. An electric hot water booster heater will be located at the dishwasher to raise the water temperature to a level suitable for the local health department.

33

SYSTEMSD. Plumbing Fixtures: 1. All plumbing fi xtures will be selected in accordance with the use of the facility and will meet all ADAAG, state, and local regulations.

2. Water closets will be of the water conserving type with consumption not to exceed 1.28 gallons per fl ush. Water closets will be fl oor mount, constructed from vitreous china. Water closets will have an elongated bowl, siphon jet action, and open-front seat. Flush valves will of the manually operated type.

3. Single lavatories will be wall mounted vitreous china with center-set faucets, open drain type waste outlet, fl exible supplies with angle stops, and adjustable 1¼-inch cast brass P-trap. Faucets will be of the manually operated type with water fl ows limited to 0.5 gallons per minute.

4. Urinals will be of the water conserving type with consumption not to exceed 0.125 gallons per fl ush. Urinals will be vitreous china, wall-hung blow out type with fl ush valve, wall hanger and backing plate. Flush valves will be of the manually operated type.

5. Drinking fountains will be refrigerated, wall-mounted via a backing plate, constructed from stainless steel, and conform to ADAAG standards

6. Sinks will be 18-gauge, type 302 or 304 stainless steel and will be outfi tted with faucet, supplies with stops, and cast brass P-trap. Faucet will be manual type with ADAAG-compliant handles. Faucets will be equipped with a 1.0 gpm fl ow restrictor for water conservation.

7. Showers will be prefabricated fi berglass type. Units will have a vandal resistant, single handle control valve. The head will be constructed from brass with chrome plating. Units will be low water consumption, pressure- balanced type. Reachable controls and hand shower option will be included for ADAAG installations.

8. Service sinks will be fl oor mounted, pre-molded stone type with sink edge guards, wall-mounted faucet with hose end, brace, and vacuum breaker. Water fl ow will be limited to 2.5 gallons per minute.

9. Handicapped- and ADAAG-accessible fi xtures and accessories will be provided where required.

34

1.5 MECHANICAL SYSTEMS

PLUMBING SYSTEM CONT.E. Sanitary Waste and Vent System: 1. Aboveground sanitary and vent piping will be cast iron, hub and spigot. Below ground piping will be PVC. Sanitary and vent pipelines will not be insulated. Below ground piping from the dishwasher shall be cast iron for a minimum of 15 feet.

2. Cleanouts will be installed at maximum 100 foot intervals, at changes in direction of more than 90 degrees, at the bottom of vertical risers, and where the sewer exits the building.

3. A grease interceptor with a capacity of 1000 gallons and meeting the requirements of the local authority will be provided for the kitchen area.

4. Clay traps will be provided in art room sinks. Traps will be accessible to clean out the fi xture traps.

5. Pipeline Supports: Sanitary waste and vent pipeline supports will be specifi ed to be consistent with the requirements of the applicable plumbing code.

6. Identifi cation: Pipelines will have identifi cation tags and fl ow arrows. Pipeline identifi cation tags will be stencil painted.

7. Floor drains will be installed in each restroom, mechanical rooms, janitor’s closets, and throughout the kitchen. All fl oor drains will have a trap seal protection. Floor drains in mechanical closets will have hinged covers for emptying of fl oor cleaning equipment.

8. Floor drains and/or fl oor sinks will be provided in mechanical equipment rooms, as required. In unfi nished areas, cast iron fl oor drain strainers will be provided.

F. Roof Drain/Storm Water System: 1. Primary roof drainage will be via gutters and downspouts 2. In the limited number of areas where roof drains are provided, the drains will be piped to below grade and will connect to the site storm drainage system. Overfl ow drainage will be piped to downspout nozzles terminating 12” above grade.

3. Storm water piping above grade will be cast iron with heavy-duty mechanical couplings. Storm water piping below grade will be PVC.

4. Insulation: Storm drain pipelines located indoors and above grade will be insulated to prevent condensation and reduce noise.

5. Pipeline Supports: Storm drain pipeline supports will be specifi ed to be consistent with the requirements of the applicable plumbing code.

35

SYSTEMS 6. Identifi cation: Pipelines will have identifi cation tags and fl ow arrows. Pipeline identifi cation tags will be stencil painted or with preformed pipe markers.

G. Natural Gas System: 1. Natural gas will be distributed on the roof at 2-psi and reduced to low pressure (less than 10” wc) at equipment and where entering the building.

2. Natural gas will be provided to equipment such as air handlers, water heaters, and kitchen equipment, and elsewhere as required.

3. Piping will be Schedule 40 carbon steel with threaded connections for sizes 1-1/2 inches and less. Piping will be specifi ed with welded fi ttings for sizes 2 inches and greater.

4. Gas pipelines will not be insulated.

5. Pipeline Supports: Gas pipeline supports will be specifi ed to be consistent with the requirements of the applicable fuel gas code.

6. Identifi cation: Pipeline identifi cation tags will be stencil painted or with preformed pipe markers.

FIRE PROTECTION SYSTEMA. The entire facility will be sprinkled according to NFPA 13 and any local requirements.

B. The main fi rewater service will enter the building in the main mechanical room near the kitchen. A double check backfl ow preventer and sprinkler riser assembly will be located at the main service entrance, internal to the building, in the main mechanical room. A fi re pump is not planned for this facility.

C. A wet type automatic wet pipe sprinkler system will be installed throughout the building. Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve.

D. A fi re department connection of the type required by the local jurisdiction will be provided on the exterior of the building. The fi re department connection shall be located at the nearest point of fi re department apparatus accessibility or at a location approved by the authority having jurisdiction.

E. Pipelines and materials will be specifi ed in accordance with the requirements of NFPA 13.

F. Sprinkler pipelines will be grooved end steel in compliance with the requirements of the NFPA 13.

G. Sprinkler pipelines will not be insulated.

36

1.5 MECHANICAL SYSTEMS

FIRE PROTECTION SYSTEM CONT.H. Pipeline Supports: Sprinkler pipeline supports will be specifi ed to be consistent with the requirements of the NFPA 13.

I. Identifi cation: Sprinkler systems will have labeling and pipe markers installed on equipment and piping according to requirements in NFPA 13.

HEATING, VENTILATING, & AIR CONDITIONING (HVAC)A. Energy Conservation: The vision for energy performance is to achieve an Energy Star rating greater than 70 percentile.

B. HVAC Systems: The fundamental basis for the classroom areas HVAC systems will be decoupling space temperature control from ventilation and humidity control. Dedicated outside air systems (commonly referred to as DOAS) will provide constant temperature, low humidity ventilation air.

C. Design Ambient Conditions:

Summer – ASHRAE 0.4%: 99.8° F db 69.4° F wbWinter - ASHRAE 99.6%: 7.4° F db

D. The following summarizes the design temperature set-point conditions within the facility:

E. Outdoor Air: Requirements per 2006 International Mechanical Code. As the ventilations systems are dedicated outdoor air (DOAS) units, the ventilation values are cumulative (equation 6-3 in ASHRAE 62.1-2007).

1. Classrooms: 10 cfm/person and 0.12 cfm/sf. 2. Art Classrooms: 10 cfm/person and 0.18 cfm/sf 3. Computer Labs: 10 cfm/person and 0.12 cfm/sf 4. Media Center: 10 cfm/person and 0.12 cfm/sf. 5. Music/Theater/Dance: 10 cfm/person and 0.06 cfm/sf 6. Multi-use/Assembly: 7.5 cfm/person and 0.06 cfm/sf 7. Cafeteria: 7.5 cfm/person and 0.18 cfm/sf 8. Conference Rooms: 5 cfm/person and 0.06 cfm/sf 9. Corridors: 0.06 cfm/sf 10. Storage Rooms: 0.12 cfm/sf

Description Summer (º F) Winter (º F)Administration 72 70Classrooms 72 70Media Center 72 70Kitchen 72 70Commons 72 70Auditorium/Stage 72 70Gymnasium 72 70Server/Data Rooms 68 68

37

SYSTEMS 11. Offi ces: 5 cfm/person and 0.06 cfm/sf 12. Reception: 5 cfm/person and 0.06 cfm/sf 13. Main Entry/Lobby: 5 cfm/person and 0.06 cfm/sf 14. Gym, stadium (play area): 0.30 cfm/sf 15. Health Club/Weight Room/Aerobics: 20 cfm/person and 0.06 cfm/sf

F. Exhaust Air: Requirements per 2006 International Mechanical Code 1. Art Classrooms: 0.70 cfm/sf 2. Kitchen: 0.70 cfm/sf 3. Janitor/Trash/Recycling: 1.0 cfm/sf 4. Copy, Printing (Work) Rooms: 1.0 cfm/sf 5. Heavy Use Bathrooms: 70 cfm per water closet or urinal 6. Single Bathrooms: 50 cfm per water closet or urinal 7. Locker/Dressing Rooms: 0.25 cfm/sf 8. Shower Rooms (per head): 50 cfm/hd (intermittent operation)

G. Miscellaneous Loads:

1. Offi ce Equipment: 200 W. 2. Data Closets: 3-Ton cooling units will be provided. 3. Computer Labs: 200 Watts per computer. 4. Classroom Equipment: 0.25 W/sf (Computers, TV, Printer etc.) 5. Kitchen Equipment: To be provided by the Kitchen Consultant 6. Lighting: ii. Offi ces: 1.1 W/sf iii. Conference/Meeting/Multipurpose: 1.3 W/sf iv. Classroom: 1.4 W/sf v. Corridor: 0.50 W/sf vi. Media Center: 1.2 W/sf vii. Kitchen: 1.2 W/sf viii. Gymnasium/Exercise Center: 1.4 W/sf

H. Classroom and Administrative Spaces 1. A dedicated split system heat pump with electric auxiliary heat will be provided for each classroom. The refrigerant for these systems will be R-410A to minimize the use of CFC for this project.

2. Systems manufactured by Carrier, Lennox, Trane, or York will be considered.

3. Ventilation for spaces with split systems will be via rooftop packaged dedicated outdoor air systems (DOAS). The DOAS units will provide neutral ventilation air (70° F, 55° F dew point) ducted directly to each space and exhaust air ducted from each space. Each DOAS unit will contain an economizer function and total energy recovery wheel to reduce energy consumption.

4. Control for each space will be via a digital control sensor, reporting information to the building management system (BMS).

5. Classroom and Administrative Spaces

38

1.5 MECHANICAL SYSTEMS

HEATING, VENTILATING, & AIR CONDITIONING (HVAC) CONT.I. Commons and Gymnasium 1. Heating and cooling will be provided by high effi ciency packaged, DX cooling, natural gas heating roof top units (RTUs).

2. Units will be controlled as single zone constant air volume systems providing varying temperature heating or cooling air with constant supply air quantities.

3. Overhead air distribution using fabric duct is planned.

4. Ventilation will be provided by the RTUs which will contain an economizer function and total energy recovery wheel to reduce energy consumption. The RTUs will also utilize CO2 control of ventilation to minimize the introduction of outside air when not required.

5. Control for each space will be via a stainless steel plate temperature sensor adjustable through the BMS only.

J. Kitchen: 1. Heating and cooling will be provided by a high effi ciency packaged, DX cooling, natural gas heating roof top unit (RTU).

2. The unit will be controlled as constant volume system providing constant airfl ow at varying supply air temperature.

3. Ventilation will be provided by the RTU which will contain an economizer function. The RTU will provide a constant volume of ventilation air.

4. Control will be an adjustable digital temperature sensor in the space tied into the BMS.

K. Server/Data Rooms:

1. Individual mini-split system cooling units will be provided including an indoor air-handling unit located in the room, direct expansion refrigeration, and a remote condensing unit. The remote condenser will be mounted on roof.

2. This equipment will be specifi cally designed for computer room

3. Airfl ow will be constant volume.

4. The refrigerant for these systems will be R-410A to minimize the use of CFC for this project.

5. Equipment specifi cation will include a requirement for low-ambient temperature operation.

39

SYSTEMS 6. Control will be via the controls provided by the mini-split manufacturer. The building management system will monitor space temperature and generate alarms at specifi ed temperatures. L. Electrical and Elevator Machine Rooms: 1. Where heat loads warrant the spaces will be provided with HVAC systems that include an unducted indoor air-handling unit located in the room, direct expansion refrigeration, and a remote condensing unit mounted on roof.

2. Airfl ow will be constant volume.

3. The refrigerant for these systems will be R-410A to minimize the use of CFC for this project.

4. Equipment specifi cation will include a requirement for low-ambient temperature operation.

5. Control will be via the controls provided by the mini-split manufacturer. The building management system will monitor space temperature and generate alarms at specifi ed temperatures.

M. Service type areas; i.e. mechanical rooms, etc., will be heated with cabinet or horizontal electric unit heaters with integral thermostats for local control of the equipment. No cooling is planned for these areas.

N. Vestibules and building entry locations will be provided with a supplemental heating source. This heating source will be electric unit heaters with integral thermostats for local control of the equipment.

O. Commissioning: Commissioning is not planned for this project.

P. Ductwork: 1. Supply and return ductwork (except kitchen hood exhaust, and dishwasher exhaust) will be galvanized sheet metal, and will have all joints sealed with fi re retardant duct sealer. Supply air ductwork will be constructed to a 2-inch static pressure design standard. Exhaust, return, and outside air ductwork will be constructed to a 2-inch static pressure design standard.

a. Supply and outside air ductwork will be insulated for sound and moisture control. Return and exhaust ductwork will be insulated in critical areas for sound control. The insulation shall be external wrapped, fi berglass type with a reinforced jacketing.

b. Exterior ductwork will be specifi ed with rigid insulation covered by a weatherproof protective jacketing.

40

1.5 MECHANICAL SYSTEMS

HEATING, VENTILATING, & AIR CONDITIONING (HVAC) CONT. 2. Pipelines: a. Refrigerant pipelines will be constructed and sized per the manufacturer’s recommendations, typically copper piping and tubing. Pipelines will be insulated with ¾-inch fi berglass insulation. Exterior piping will have aluminum jacketing and interior piping will have kraft jacketing.

b. Identifi cation: Pipelines and valves will have identifi cation tags and fl ow arrows. Pipeline identifi cation tags will be adhesive markers that are commercially available. Valve tags will be brass pieces with stamped numbers/letters affi xed using a chain.

3. Building Management System: a. System Description: The building management system (BMS) will have digitally based components, a graphical interface, and be accessible via the World Wide Web.

b. The following is a summary of the anticipated control points associated with the equipment scheduled for this project:

1) Global Points

Outdoor Dry BulbOutdoor Wet BulbOutdoor Relative HumidityOutdoor EnthalpySchedulesSetpoints 2) Split System Heat Pump Units Zone TemperatureZone Cooling SetpointZone Heating SetpointOccupied/Unoccupied ModeUnit Operation Mode (Heating/Cooling)Unit AlarmError CodeUnit Enable/Disable/StatusFan Speed

3) Packaged HVAC Units

Zone TemperatureZone Cooling SetpointZone Heating SetpointReturn Air TemperatureReturn Air HumidityReturn Air CO2 PPMReturn Air Smoke Detector StatusHeat Wheel Exhaust Bypass PositionHeat Wheel Enable/Disable/ModulationExhaust Fan Enable/Disable/Modulation Exhaust Damper PositionOutside Air Damper PositionHeat Wheel Outside Air Bypass PositionReturn Air Damper PositionMixed Air TemperatureAir Filter StatusRefrigeration Enable/Disable/ModulationHot Gas Reheat Enable/Disable/ModulationHeating Enable/Disable/ModulationSupply Air Fan Enable/Disable/StatusSupply Air TemperatureSupply Air Humidity

41

SYSTEMS4) Packaged DOAS Units

Supply Air Temperature SetpointSupply Air Humidity SetpointReturn Air TemperatureReturn Air HumidityReturn Air Smoke Detector StatusHeat Wheel Exhaust Bypass PositionHeat Wheel Enable/Disable/ModulationExhaust Fan Enable/Disable/Modulation Exhaust Damper PositionOutside Air Damper PositionHeat Wheel Outside Air Bypass PositionIntermediate Supply Air TemperatureAir Filter StatusRefrigeration Enable/Disable/ModulationHot Gas Reheat Enable/Disable/ModulationHeating Enable/Disable/ModulationSupply Air Fan Enable/Disable/StatusSupply Air TemperatureSupply Air Humidity

5) Server Room Units:

(Internal operation of unit shall be performed via local controls)Room temperatureHigh space temperature alarm

6) Water: Instantaneous, Peak, and Total Consumption 7) Gas: Instantaneous, Peak, and Total Consumption 8) Electrical: Instantaneous, Peak, and Total Consumption

9) Fire Alarm and Sprinkler System: System status/alarm Trouble Water fl ow

10)Kitchen(s): Cooler temperature alarm Freezer temperature alarm

11)Small Restrooms Exhaust Fans (Less than Two Water Closets): No BMS interface Local control

4. The BMS will include a graphical interface with dedicated screens for the following equipment: RTUs, DOAS, VRF units, and overall building parameters (temperature, relative humidity, static pressure).

5. The BMS will be specifi ed with an unoccupied building setback cycle that will include an optimized start, warm-up/cool-down sequence, and sequenced equipment startup to minimize peak power demand.

6. The BMS will include trending software designed to monitor the control points for a specifi ed period of time.

Q. HVAC Test and Balance:Air Balance: Balancing will be accomplished by a fi rm independent of the mechanical contractor with a minimum of three years of experience on similar projects.

42

1.5 MECHANICAL SYSTEMSPreliminary Specification Sections

The following list summarizes the specification sections that are anticipated to be prepared for this project:

SECTION 210500 COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 211313 WET-PIPE SPRINKLER SYSTEMS SECTION 220500 COMMON WORK RESULTS FOR PLUMBING SECTION 220519 METERS AND GAGES FOR PLUMBING PIPING SECTION 220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT SECTION 220719 PLUMBING PIPING INSULATION SECTION 221116 DOMESTIC WATER PIPING SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES SECTION 221123 DOMESTIC WATER PUMPS SECTION 221125 FACILITY NATURAL GAS PIPING SECTION 221316 SANITARY WASTE AND VENT PIPING SECTION 221319 SANITARY WASTE PIPING SPECIALTIES SECTION 221323 SANITARY WASTE INTERCEPTORS SECTION 221413 STORM DRAINAGE PIPING SECTION 221423 STORM DRAINAGE PIPING SPECIALTIES SECTION 223400 FUEL-FIRED DOMESTIC WATER HEATERS SECTION 221429 SUMP PUMPS SECTION 223100 WATER SOFTENERS SECTION 224000 PLUMBING FIXTURES SECTION 230500 COMMON WORK RESULTS FOR HVAC SECTION 230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC SYSTEMS SECTION 230713 DUCT INSULATION SECTION 230719 HVAC PIPING INSULATION SECTION 230900 INSTRUMENTATION AND CONTROL FOR HVAC SECTION 232300 REFRIGERANT PIPING SECTION 233113 METAL DUCTS SECTION 233116 NONMETAL DUCTS SECTION 233300 AIR DUCT ACCESSORIES SECTION 233423 HVAC POWER VENTILATORS SECTION 233713 DIFFUSERS, REGISTERS, AND GRILLES SECTION 233813 COMMERCIAL-KITCHEN HOODS

43

SYSTEMSSECTION 237413 PACKAGED, OUTDOOR, CENTRAL-STATION AIR HANDLING

UNITS SECTION 237423 PACKAGED, DIRECT-FIRED, OUTDOOR, HEATING-ONLY

MAKUP-AIR UNITS SECTION 238126 SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238239 UNIT HEATERS SECTION 238323 RADIANT HEATING ELECTRIC PANELS

44

1.5 MECHANICAL SYSTEMSMechanical Systems for Middle School Prototypes

I. Applicable Reference Standards

All work, materials, and installations shall conform to appropriate codes, regulations, and enforcing agencies as listed below:

Americans with Disabilities Act, Accessibility Guidelines (ADAAG) American Refrigeration Institute (ARI) American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) American Society of Mechanical Engineers (ASME) Local and State Mechanical Code National Fire Protection Association (NFPA) Occupational Safety and Health Act (OSHA) Regulations of Local Utility Companies Sheet Metal and Air Conditioning Contractors National Association (SMACNA)

Design will conform to the following building codes:

2009 International Fire Code 2009 International Building Code 2009 International Mechanical Code 2009 International Plumbing Code 2009 International Fuel Gas Code 2009 International Energy Conservation Code

II. Plumbing Systems

A. Water Conservation: The vision for water conservation is to achieve 35% less water usage than a typical building according to the calculation procedure established by the USGBC.

B. Domestic Water System:

45

SYSTEMS1. The domestic water service to the building will be sized based on

the available water pressure at the site, the total required flow required by the fixtures shown on the architectural plans, and to deliver a minimum pressure of 25 psi to the most remote fixture.

2. The domestic water service to the building will be protected by a reduced pressure backflow preventer located inside the building in the main mechanical room.

3. Hot and cold water will be extended to all fixtures where required. 4. Domestic water piping will be Type L copper piping with lead-free

solder joints or mechanical coupling similar to pro-press. 5. The domestic water systems valves shall be bronze construction

gate or ball valves. Valves will be installed to isolate individual fixtures and groups of plumbing fixtures.

6. Insulation: Cold and hot water will be insulated using flexible elastomeric or mineral fiber preformed pipe insulation. The insulation thickness will be specified to be consistent with the energy code requirements.

7. Pipeline Supports: Domestic water pipeline supports will be specified to be consistent with the requirements of the applicable plumbing code.

8. Identification: Pipelines will have identification tags and flow arrows. Pipeline identification tags will be adhesive markers that are commercially available.

9. Water supplies to lavatories, sinks, and drinking fountains will have angle stops with loose key handles.

10. Hose bibs shall be provided in each large group restroom, and mechanical room. The hose bib will be surface mounted behind a lockable cover with access by a removable key.

C. Domestic Hot Water:

1. The domestic water heating system will comply with the requirements of the energy code.

2. Electric domestic hot water systems will be located in each building wing to serve the classrooms and administrative areas. Heaters will be located in the janitor’s closet. Recirculation loops and pumps will be provided to ensure timely delivery of hot water to every fixture.

3. Gas domestic hot water systems will be provided for the kitchen and locker room areas. The kitchen water heater will be located in the mechanical room near the kitchen with hot water distributed at 140 degrees F. Point of use mixing valves will be used to temper the hot water to hand washing sinks. The water heater for the locker room areas will be located in the janitor’s closet near the locker

46

1.5 MECHANICAL SYSTEMS4. The domestic hot water system for the classroom wings and locker

rooms will be distributed at 115 degrees F. 5. Gas heaters will be generate hot water by 90%+ high efficiency

direct vent gas-fired water heaters with integral storage tanks.

D. Plumbing Fixtures:

1. All plumbing fixtures will be selected in accordance with the use of the facility and will meet all ADAAG, state, and local regulations.

2. Water closets will be of the water conserving type with consumption not to exceed 1.28 gallons per flush. Water closets will be floor mount, constructed from vitreous china. Water closets will have an elongated bowl, siphon jet action, and open-front seat. Flush valves will of the manually operated type.

3. Single lavatories will be wall mounted vitreous china with center-set faucets, open drain type waste outlet, flexible supplies with angle stops, and adjustable 1¼-inch cast brass P-trap. Faucets will be of the manually operated type with water flows limited to 0.5 gallons per minute.

4. Urinals will be of the water conserving type with consumption not to exceed 0.125 gallons per flush. Urinals will be vitreous china, wall-hung blow out type with flush valve, wall hanger and backing plate. Flush valves will be of the manually operated type.

5. Drinking fountains will be refrigerated, wall-mounted via a backing plate, constructed from stainless steel, and conform to ADAAG standards

6. Sinks will be 18-gauge, type 302 or 304 stainless steel and will be outfitted with faucet, supplies with stops, and cast brass P-trap. Faucet will be manual type with ADAAG-compliant handles. Faucets will be equipped with a 1.0 gpm flow restrictor for water conservation.

7. Showers will be prefabricated fiberglass type. Units will have a vandal resistant, single handle control valve. The head will be constructed from brass with chrome plating. Units will be low water consumption, pressure-balanced type. Reachable controls and hand shower option will be included for ADAAG installations.

8. Service sinks will be floor mounted, pre-molded stone type with sink edge guards, wall-mounted faucet with hose end, brace, and vacuum breaker. Water flow will be limited to 2.5 gallons per minute.

9. Handicapped- and ADAAG-accessible fixtures and accessories will be provided where required.

47

SYSTEMSE. Sanitary Waste and Vent System:

1. Aboveground sanitary and vent piping will be cast iron, hub and spigot. Below ground piping will be PVC. Sanitary and vent pipelines will not be insulated. Below ground piping from the dishwasher shall be cast iron for a minimum of 15 feet.

2. Cleanouts will be installed at maximum 100 foot intervals, at changes in direction of more than 90 degrees, at the bottom of vertical risers, and where the sewer exits the building.

3. A grease interceptor with a capacity of 1000 gallons and meeting the requirements of the local authority will be provided for the kitchen area.

4. Clay traps will be provided in art room sinks. Traps will be accessible to clean out the fixture traps.

5. Pipeline Supports: Sanitary waste and vent pipeline supports will be specified to be consistent with the requirements of the applicable plumbing code.

6. Identification: Pipelines will have identification tags and flow arrows. Pipeline identification tags will be stencil painted.

7. Floor drains will be installed in each restroom, mechanical rooms, janitor’s closets, and throughout the kitchen. All floor drains will have a trap seal protection. Floor drains in mechanical closets will have hinged covers for emptying of floor cleaning equipment.

8. Floor drains and/or floor sinks will be provided in mechanical equipment rooms, as required. In unfinished areas, cast iron floor drain strainers will be provided.

F. Roof Drain/Storm Water System:

1. Roof drainage will be via internal roof drains with the drains piped to below grade and connecting to the site storm drainage system. Overflow drainage will be piped to downspout nozzles terminating 12” above grade.

2. Storm water piping above grade will be cast iron with heavy-duty mechanical couplings. Storm water piping below grade will be PVC.

3. Insulation: Storm drain pipelines located indoors and above grade will be insulated to prevent condensation and reduce noise.

4. Pipeline Supports: Storm drain pipeline supports will be specified to be consistent with the requirements of the applicable plumbing code.

5. Identification: Pipelines will have identification tags and flow arrows. Pipeline identification tags will be stencil painted or with preformed pipe markers.

48

1.5 MECHANICAL SYSTEMSG. Natural Gas System:

1. Natural gas will be distributed on the roof at 2-psi and reduced to low pressure (less than 10” wc) at equipment and where entering the building.

2. Natural gas will be provided to equipment such as air handlers, water heaters, and kitchen equipment, to science labs and elsewhere as required.

3. Piping will be Schedule 40 carbon steel with threaded connections for sizes 1-1/2 inches and less. Piping will be specified with welded fittings for sizes 2 inches and greater.

4. Gas pipelines will not be insulated. 5. Pipeline Supports: Gas pipeline supports will be specified to be

consistent with the requirements of the applicable fuel gas code. 6. Identification: Pipeline identification tags will be stencil painted or

with preformed pipe markers.

II. Fire Protection System

A. The entire facility will be sprinkled according to NFPA 13 and any local requirements.

B. The main firewater service will enter the building in the main mechanical room near the kitchen. A double check backflow preventer and sprinkler riser assembly will be located at the main service entrance, internal to the building, in the main mechanical room. A fire pump is not planned for this facility.

C. A wet type automatic wet pipe sprinkler system will be installed throughout the building. Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve.

D. A fire department connection of the type required by the local jurisdiction will be provided on the exterior of the building. The fire department connection shall be located at the nearest point of fire department apparatus accessibility or at a location approved by the authority having jurisdiction

E. Pipelines and materials will be specified in accordance with the requirements of NFPA 13.

49

SYSTEMSF. Sprinkler pipelines will be grooved end steel in compliance with the

requirements of the NFPA 13.

G. Sprinkler pipelines will not be insulated.

H. Pipeline Supports: Sprinkler pipeline supports will be specified to be consistent with the requirements of the NFPA 13.

I. Identification: Sprinkler systems will have labeling and pipe markers installed on equipment and piping according to requirements in NFPA 13.

III. Heating, Ventilating and Air Conditioning (HVAC):

A. Energy Conservation: The vision for energy performance is to achieve an Energy Star rating greater than 70 percentile.

B. Design Ambient Conditions:

Summer – ASHRAE 0.4%: 99.8° F db 69.4° F wb Winter - ASHRAE 99.6%: 7.4° F db

C. The following summarizes the design temperature set-point conditions within this facility:

Description Summer (º F) Winter (º F)

Administration 72 70

Classrooms 72 70

Media Center 72 70

Kitchen 72 70

Commons 72 70

Auditorium/Stage 72 70

Gymnasium 72 70

Server/Data Rooms 68 68

D. The following summarizes each area within the facility and more specifics on the type of HVAC system planned for the area.

50

1.5 MECHANICAL SYSTEMS1. Classroom Wings:

a. One rooftop mounted HVAC unit will serve each wing of the classroom portion of the facility. The HVAC unit will be rooftop mounted, packaged, unitary unit with direct expansion refrigeration, gas-fired heat, and an airside economizer.

b. Airflow will be variable volume with speed control for the supply, return, and exhaust fans. The equipment selection and sequence of operation will be selected so the supply air delivered from the HVAC unit in the cooling season is at or below 55 F allowing for dehumidification in the area served.

c. Each classroom will be equipped with a temperature sensor to control the operation of an air terminal device. Air terminal devices will be used to vary the airflow and temperature to each area served. The air terminal devices will have either electric or hot water reheat.

2. Administration:

a. One rooftop mounted HVAC unit will serve the administration portion of the facility. The HVAC unit will be rooftop mounted, packaged, unitary unit with direct expansion refrigeration, gas-fired heat, and an airside economizer.

b. Airflow will be variable volume with speed control for the supply, return, and exhaust fans. The equipment selection and sequence of operation will be selected so the supply air delivered from the HVAC unit in the cooling season is below 55 F allowing for dehumidification in the area served.

c. The administration area will be divided into zones, as necessary, based on exposure and occupancy. Each zone will be equipped with a temperature sensor to control the operation of an air terminal device. Air terminal devices will be used to vary the airflow and temperature to each area served. The air terminal devices will have either electric or hot water reheat.

3. Media Center: The HVAC system will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, hot-gas reheat, and an airside economizer. The airflow will be variable volume.

51

SYSTEMSa. One rooftop mounted HVAC unit will serve the music/band

portion of the facility. The HVAC unit will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, and an airside economizer.

b. Airflow will be variable volume with speed control for the supply, return, and exhaust fans. The equipment selection and sequence of operation will be selected so the supply air delivered from the HVAC unit in the cooling season is below 55 F allowing for dehumidification in the area served.

c. Each zone will be equipped with a temperature sensor to control the operation of an air terminal device. Air terminal devices will be used to vary the airflow and temperature to each area served. The air terminal devices will have either electric or hot water reheat.

4. Gymnasium: The HVAC system will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, energy recovery, hot-gas reheat, and an airside economizer. The air handling system will include multiple units (2-50% for example) to allow better load control and redundancy. The airflow will be constant volume. The hot-gas reheat will be used to control humidity in this area. The HVAC unit will be equipped with a CO2 monitor for active adjustment of the ventilation air introduced into the facility.

5. Weight Room: The HVAC system will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, hot-gas reheat, and an airside economizer. The airflow will be constant volume. The hot-gas reheat will be used to control humidity in this area during the cooling season.

6. Locker Rooms: The HVAC system will be rooftop mounted, packaged, energy recovery unit with direct expansion refrigeration, gas-fired heat, hot-gas reheat, and an airside economizer. The airflow will be 100% outside air, constant volume, with no return air recirculated back to the space. The hot-gas reheat will be used to control humidity in this area during the cooling season. An enthalpy wheel heat exchanger will be utilized for heat recovery.

7. Music/Band, Industrial Arts:

a. One rooftop mounted HVAC unit will serve the music/band portion of the facility. The HVAC unit will be rooftop

52

1.5 MECHANICAL SYSTEMSrefrigeration, gas-fired heat, and an airside economizer.

b. Airflow will be variable volume with speed control for the supply, return, and exhaust fans. The equipment selection and sequence of operation will be selected so the supply air delivered from the HVAC unit in the cooling season is below 55 F allowing for dehumidification in the area served.

c. Each classroom will be equipped with a temperature sensor to control the operation of an air terminal device. Air terminal devices will be used to vary the airflow and temperature to each area served. The air terminal devices will have either electric or hot water reheat.

d. The HVAC unit will be equipped with a CO2 monitor for active adjustment of the ventilation air introduced into the facility. Each HVAC unit will also be equipped with a humidity sensor to monitor the relative humidity in the area.

8. Kitchen:

a. The kitchen hood(s) will be equipped with an exhaust fan(s) and makeup air unit(s). The exhaust fan(s) and makeup air unit(s) be constant volume. The makeup air unit will be specified with a gas-fired heater intended to temper the outside air to 60 F. Air conditioning is not planned for the makeup air system.

b. The HVAC system will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, and an airside economizer. The airflow will be constant volume. The intent of this unit is to provide minimal air-conditioning for the kitchen and supplement the heating provided by the make-up air unit associated with the kitchen hood.

9. Commons: The HVAC system will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, hot-gas reheat, and an airside economizer. The airflow will be constant volume. The hot-gas reheat will be used to control humidity in this area. The HVAC unit will be equipped with a CO2

monitor for active adjustment of the ventilation air introduced into the facility.

10. Computer Lab: The HVAC system will be a packaged, unitary system with direct expansion refrigeration, gas-fired heat, and an airside economizer. Airflow will be variable volume with speed

53

SYSTEMScontrol for the supply, return, and exhaust fans. The fan speed will be referenced to the temperature sensor in the space. The equipment selection and sequence of operation will be selected so the supply air delivered from the HVAC unit in the cooling season is below 55 F allowing for dehumidification in the area served. Equipment specification will include a requirement for low-ambient temperature operation.

11. Server/Data Rooms: The HVAC system will include an indoor air-handling unit located in the room, direct expansion refrigeration, and a remote condensing unit. The remote condenser will be mounted on roof. This equipment will be specifically designed for computer room applications, capable of satisfying temperature and humidity requirements. Airflow will be constant volume. Equipment specification will include a requirement for low-ambient temperature operation.

12. Family Arts and Consumer Science: The HVAC system will be rooftop mounted, packaged, unitary system with direct expansion refrigeration, gas-fired heat, hot-gas reheat, and an airside economizer. The airflow will be constant volume. The hot-gas reheat will be used to control humidity in this area during the cooling season. The HVAC unit will be equipped with a CO2

monitor for active adjustment of the ventilation air introduced into the facility.

13. Entries and service type areas; i.e., vestibules, mechanical rooms, etc., will be heated with cabinet or horizontal unit heaters with remote thermostats for local control of the equipment. No air conditioning is planned for these areas.

E. Heating Water Plant (option):

1. Hot water for VAV box reheat will be generated by (2) 1,000 Mbh condensing boilers to meet 120% of the building reheat capacity. Hot water will be distributed by a primary-secondary piping system to the VAV boxes. Piping will be steel with mechanical joints, or polypropylene with heat fusion joints. Polypropylene piping in ceiling plenums will require wrapping with fireproof insulation.

F. Ductwork:

1. All supply and return ductwork (except kitchen hood exhaust, fume hood exhaust, and dishwasher exhaust) will be galvanized sheet

54

1.5 MECHANICAL SYSTEMSSupply air ductwork upstream of air terminal units will be constructed to a 4” static pressure design standard. Supply air ductwork downstream of air terminal units will be constructed 2” static pressure design standard. Exhaust, return, and outside air ductwork will be constructed to a 2” static pressure design standard.

2. Kitchen exhaust duct will be constructed from carbon steel to a 2” static pressure design standard.

3. Dishwasher exhaust duct will be constructed from stainless steel to a 2” static pressure design standard.

4. Fume hood exhaust duct will be constructed from stainless steel to a 2” static pressure design standard.

5. Supply and outside ductwork will be insulated for sound and moisture control. Return and exhaust ductwork will be insulated in critical areas for sound control. The insulation shall be external wrapped, fiberglass type with a reinforced jacketing. Acoustic board will be specified in noise abatement areas. The insulation thickness will be specified to be consistent with the requirements of the Model Energy Code.

6. Exterior ductwork will be specified with rigid insulation covered by weatherproof protective jacketing.

G. Miscellaneous Pipelines:

1. Condensate drains will be constructed from Schedule 40 PVC. Condensate drains will not be insulated, unless specific conditions justify.

2. Refrigerant pipelines will be constructed and sized per the manufacturer’s recommendations, typically copper piping and tubing. Suction pipelines will be insulated with ¾” fiberglass insulation. Exterior piping will have aluminum jacketing and interior piping will have PVC jacketing.

3. Identification: Pipelines and valves will have identification tags and flow arrows. Pipeline identification tags will be adhesive markers that are commercially available. Valve tags will be brass pieces with stamped numbers/letters affixed using a chain.

55

SYSTEMSH. Exhaust Requirements:

1. Kitchen: The appliance hood will be an island canopy type designed with the minimum required exhaust volume for effective smoke and fume removal.

2. Dishwasher: A separate exhaust fan will be ducted to both ends of the dishwasher.

3. Science Room(s): The Science Room with fume hoods will be served by an exhaust fan for fume removal.

4. Art Room(s): The Kiln Room will be served by an exhaust fan for fume and heat removal. A roof-mounted exhaust fan will also provide general fume exhaust for the whole room.

5. General exhaust will be provided for custodial closets, toilet rooms, and other areas, as required.

I. Building Management System:

1. System Description: The building management system (BMS) will have digitally based components, a graphical interface, and accessible via the World Wide Web. The following is a summary of the anticipated control points associated with the equipment scheduled for this project:

a. Roof Top Units: Outside air temperature Mixed air damper Mixed air temperature Return air temperature Air filter pressure drop Refrigeration enable/disable Heating enable/disable Supply air fan enable/disable Supply air fan speed Supply air fan current Return air fan enable/disable Return air fan speed Return air fan current Supply air temperature Supply air duct static pressure

56

1.5 MECHANICAL SYSTEMSb. Air Terminal Units:

Primary air flow Primary air damper position Electric heat enable/disable Electric heat stages (up to 3 points) Room temperature Room relative humidity (each classroom wing, Administration, Computer Lab, Media Center, Gymnasium, Commons)

c. Fan-Powered Terminal Units: Primary airflow Primary air damper position Fan enable/disable Electric heat enable/disable Electric heat stages (up to 3 points) Room temperature

d. Server Room Units: Unit enable/disable Room temperature Room humidity

e. Kitchen/Make-up Air: Make up air unit fan status Kitchen hood fan status

f. Outside Weather Station: Outside air temperature Outside relative humidity

g. Domestic Water: Incoming water pressure Flow meter – totalizing

h. Electrical: Main power voltage – Phase A Main power voltage – Phase B Main power voltage – Phase C Main power amperage – Phase A Main power amperage – Phase B Main power amperage – Phase C Main power factor

57

SYSTEMSi. Fire Alarm and Sprinkler System:

System status/alarm Trouble Water flow

j. Security System: System status/alarm Trouble

k. Main Restrooms: Exhaust fan enable/disable

l. Small Restrooms (less than two water closets): No BMS interface Local control

m. Domestic Hot Water: No BMS interface Local control of water heaters and recirculation pumps

n. Cabinet Unit Heaters: Unit enable/disable Local control of temperature

2. The BMS will include a graphical interface with dedicated screens for the following equipment: RTUs, terminal units, and overall building parameters (temperature, relative humidity, static pressure).

3. The BMS will be specified with a unoccupied building set-back cycle that will including an optimized start, warm-up/cool-down sequence, and sequenced equipment startup to minimize peak power demand.

4. The BMS will include trending software designed to monitor the control points of a specified period of time.

J. HVAC Test and Balance:

1. Air and Water Balance: Balancing will be accomplished by a firm with a minimum of three years of experience on similar projects.

II. Specification Sections

58

1.5 MECHANICAL SYSTEMSA. The following list summarizes the specification sections that are

anticipated to be prepared for this project:

SECTION 210500 COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 211000 WATER-BASED FIRE-SUPPRESSION SYSTEMS

SECTION 220500 COMMON WORK RESULTS FOR PLUMBING SECTION 220519 METERS AND GAGES FOR PLUMBING PIPING SECTION 220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT SECTION 220700 PLUMBING INSULATION SECTION 221116 DOMESTIC WATER PIPING SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES SECTION 221123 DOMESTIC WATER PUMPS SECTION 221316 SANITARY WASTE AND VENT PIPING SECTION 221319 SANITARY WASTE PIPING SPECIALTIES SECTION 221323 SANITARY WASTE INTERCEPTORS SECTION 221413 STORM DRAINAGE PIPING SECTION 221423 STORM DRAINAGE PIPING SPECIALTIES SECTION 221429 SUMP PUMPS SECTION 223400 FUEL-FIRED DOMESTIC WATER HEATERS SECTION 224000 PLUMBING FIXTURES SECTION 224500 EMERGENCY PLUMBING FIXTURES SECTION 224700 DRINKING FOUNTAINS AND WATER COOLERS

SECTION 230500 COMMON WORK RESULTS FOR HVAC SECTION 230519 METERS AND GAGES FOR HVAC PIPING SECTION 230523 GENERAL-DUTY VALVES FOR HVAC PIPING SECTION 230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC SYSTEMS SECTION 230700 HVAC INSULATION SECTION 230900 INSTRUMENTATION AND CONTROL FOR HVAC SECTION 231123 NATURAL-GAS PIPING SECTION 232113 HYDRONIC PIPING SECTION 232123 HYDRONIC PUMPS SECTION 232300 REFRIGERANT PIPING SECTION 232500 HVAC WATER TREATMENT SECTION 233113 METAL DUCTS SECTION 233116 NONMETAL DUCTS SECTION 233300 AIR DUCT ACCESSORIES SECTION 233423 HVAC POWER VENTILATORS SECTION 233600 AIR TERMINAL UNITS SECTION 233713 DIFFUSERS, REGISTERS, AND GRILLES SECTION 233723 HVAC GRAVITY VENTILATORS SECTION 233813 COMMERCIAL-KITCHEN HOODS

59

SYSTEMSSECTION 235216 CONDENSING BOILERS SECTION 237413 PACKAGED, OUTDOOR, CENTRAL-STATION AIR HANDLING UNITS SECTION 237435 ROOF-TOP EQUIPMENT SCREENS SECTION 237439 PACKAGED, OUTDOOR, DIRECT FIRED HEATING MAKEUP SECTION 238123 COMPUTER-ROOM AIR-CONDITIONERS SECTION 238239 UNIT HEATERS

60

1.6 ELECTRICAL SYSTEMS

I. Codes and Standards

A. The following codes are applicable to this project:

1. National Electrical Code (NEC) – 20082. International Building Code (IBC) – 20093. International Energy Conservation Code (IECC) - 20094. International Mechanical Code (IBC) - 2009

B. Publications from the following standards organizations will be used as design guidelines for the project:

1. National Fire Protection Association (NFPA)2. Illuminating Engineering Society of North America (IES) 3. Building Industry Consulting Services International (BICSI) 4. Americans with Disabilities Act (ADA) 5. National Electrical Manufacturer’s Association (NEMA) 6. Electrical Industries Alliance (EIA) 7. Telecommunications Industry Association (TIA)

C. The project will be designed to conform to the Americans with Disabilities Act and Architectural Guidelines (ADAAG).

II. Electrical Service

III. A padmount utility transformer will provide a 277/480-volt, 3-phase, 4-wire electrical service for each school. A main switchboard will distribute power within each building. Services will be underground if underground services are agreeable to the local utility.

IV. Metering

A. A customer-owned meter will be provided integral to the main switchboard. Meter will be interfaced with the building management system (BMS) to allow the owner to monitor overall power usage.

V. Cables and Conductors

A. All conductors will be copper; aluminum conductors will not be used.

ELEMENTARY SCHOOLS

61

SYSTEMSB. Cables with Type XHHW-2 insulation will be provided for services entrances

conductors and feeder conductors to panelboards

C. Cables with Type THHN-THWN insulation will be used for other feeders and all branch circuit conductors.

VI. Grounding and Bonding

A. Grounding of the service entrance equipment will be performed in accordance with NEC and will include all optional forms of supplemental electrodes.

B. Telecommunications system grounding will be provided according to BICSI guidelines. Grounding will include a main telecommunications grounding busbar (MTGB) in the main telecommunications room (building distributor, BD).

C. A grounding electrode will be provided for each exterior pole supporting lighting fixtures.

VII. Hangers and Supports

A. Hangers and supports will be constructed of steel in all areas.

VIII. Raceways and Boxes

A. The following types of raceways as defined by NEC are proposed:

1. Electrical Metallic Tubing (EMT) 2. Intermediate Metallic Tubing (IMC) 3. Rigid Metallic (Steel) Conduit (RMC) 4. Rigid Nonmetallic Conduit (RNC) 5. Flexible Metallic Conduit (FMC) 6. Liquid-Tight Flexible Metallic Conduit (LFMC)

B. Application of raceway and box products in exterior locations will be as follows:

1. Exposed Raceway: IMC or RMC 2. Concealed Raceway, Aboveground: IMC or RMC 3. Underground Conduit: RNC 4. Connections to Vibrating Equipment: LFMC 5. Boxes, Above Ground: NEMA Type 3R or Type 4

62

1.6 ELECTRICAL SYSTEMS

C. Application of raceway and box products in interior locations will be as follows:

1. Exposed, Not Subject to Physical Damage, Dry Locations: EMT 2. Exposed, Subject to Physical Damage: RMC 3. Damp or Wet Locations: RMC 4. Concealed: EMT or MC cable where allowed below. 5. Connections to Vibrating Equipment, Dry Locations: FMC 6. Connections to Vibrating Equipment, Wet Locations: LFMC 7. Connections between lighting fixtures within a room: Contractor will

have the option to use factory assembled pre-connectorized flexible wiring system.

8. Boxes, Dry Locations: NEMA 250, Type 1 9. Boxes, Damp and Wet Locations: NEMA 250, Type 4 stainless steel 10. MC cable will be allowed between devices boxes within metal stud

wall and for branch circuit wiring above accessible ceilings. MC cable will not be allowed for homeruns to panelboards.

IX. Cable Trays

A. Cable trays will be provided above accessible ceilings in corridors in areas of concentrated low voltage cabling for use as a pathway for low voltage cabling from workstations to telecommunications rooms.

B. Cable tray will be wire basket type constructed of zinc-plated steel.

X. Lighting Control

A. All spaces will have an automatic means, either occupancy sensor, vacancy sensor, or relay panel type control, to ensure lights are turned off. In addition each space will have a manual means to control lights.

B. The following types of occupancy sensors are proposed:

1. Passive Infrared Switch-Box Occupancy Sensors: Device mounted in a standard switch box. These devices will be used in small rooms where sensors have a direct line of sight to the occupants with major motion.

2. Dual-Technology Switch-Box Occupancy Sensors: Device mounted in a standard switch box. These devices will be used in small rooms with extended periods of minor motion (offices).

63

SYSTEMS3. Ceiling Mounted Occupancy Sensors: Low voltage sensor with

remote relay pack for control of loads in larger spaces.

a. Ultrasonic Type: Devices of this type will be used in rooms with walking-type movements, such as restrooms

b. Dual Technology Type - Passive Infrared and Ultrasonic: Devices of this type will be used in rooms with fine motor skill movements, such as desk and office workspace activities

C. Control for individual interior spaces will be as follows, with manual switches in all areas utilizing occupancy sensors:

1. Classrooms: Vacancy sensor via control system described above. 2. Gymnasium: Dual level low voltage switches / relay panel control. 3. Media Center: Low voltage switches / relay panel control. 4. Offices: Occupancy sensors. 5. Conference Rooms: Occupancy sensors. 6. Teacher’s Planning Center: Occupancy sensors. 7. Workrooms: Occupancy sensors. 8. Kitchen: Low voltage switches / relay panel control. 9. Restrooms: Occupancy sensors. 10. Storage Rooms: Occupancy sensors. 11. Utility Rooms: Occupancy sensors except for spaces where, due to

room configuration and type of equipment, occupancy sensors may not be ideally suited.

12. Corridors: Combination of occupancy sensing and relay panel control.

13. Commons: Low voltage switches / relay panel control. Daylight harvesting will be considered for area immediately adjacent to exterior windows in the commons.

14. Entry vestibules. Relay panel control. Photocell input to the relay panel shall be programmed to keep fixture off when adequate ambient light is available.

D. Daylight zone control. Manual override control of daylight zones will be provided in spaces as required by code. This includes all classrooms.

E. Control for exterior spaces will be as follows:

1. Parking: Relay panel control with input from the building management system (BMS).

a. AM: On at a preset time and off at dawn b. PM: On at dusk and off at a time set by Owner.

64

1.6 ELECTRICAL SYSTEMS

2. Building Exterior: Relay panel control. Dusk to dawn operation.

XI. Transformers

A. Transformers will be required to derive 120-volt and 208-volt power for receptacles and other loads.

B. Transformers will be three-phase, unless a large single-phase load makes a single-phase transformer necessary

C. Transformers will carry the NEMA TP1 rating for energy efficiency.

XII. Switchboards

A. Switchboards will consist of multiple sections, rear aligned requiring access from the front only. Switchboards shall contain breakers for mains and branch devices.

B. The service entrance switchboard will contain digital metering that will be monitored by the building management system (BMS).

C. The service entrance switchboard will contain integral factory-installed Surge Suppression Device (SPD).

XIII. Panelboards

A. Panelboards will be provided throughout the building to serve mechanical, lighting, and receptacle branch circuits. Typically, panelboards will be located in dedicated electrical rooms.

B. With the possible exception of fractional motor loads, mechanical equipment will not be served from the same panelboards serving lighting or receptacle loads.

C. Panelboards will have bolt-on type branch breakers. Plug-in type breakers will not be permitted.

D. Panelboards will be fully rated for the calculated available fault current. Series rated devices will not be permitted.

E. SPD’s will be provided on branch circuit panelboards serving electronic loads. This will include most, if not all, 120/208volt panelboards.

XIV. Motor Controllers

65

SYSTEMSA. NEMA ICS 2, Class A, full voltage, non-reversing across-the-line motor

controllers will be provided under Division 26 where simple start-stop motor operation is required. Such motor controllers will contain a NEMA rating based on horsepower of the load, and adjustable overload relays for motor running overload protection with NEMA ICS 2, Class 20 tripping characteristics to protect motor against voltage and current unbalance and single phasing.

B. Variable frequency drives (VFD’s) will be provided with the associated motor under Division 23 where variable speed control is required.

XV. Wiring Devices

A. Wiring devices will be specification grade, tamper-resistant.

B. Standard receptacles will have a NEMA 5-20R configuration rated for 20 amps.

C. Standard toggle switches will be rated for 120/277 volts and 20 amps.

D. Wiring device faceplates will be Type 302 stainless steel.

XVI. Fuses

A. Fuses will be NEMA FU 1, non-renewable cartridge type.

B. Fuses greater than 600 amps will be Class L time delay. All other fuses will be Class J time delay.

XVII. Lightning Protection

A. Lightning protection for the building will not be provided.

XVIII. Generator

A. An emergency standby generator will not be provided.

XIX. Interior Lighting

A. Light Levels: Designed average maintained lighting levels are as follows:

1. Classrooms: 45 foot-candles (fc) 2. Gymnasium: 50 foot-candles 3. Media Center: 50 foot-candles 4. Offices: 45 foot-candles

66

1.6 ELECTRICAL SYSTEMS

5. Conference Rooms: 45 foot-candles 6. Teacher’s Planning Center: 45 foot-candles 7. Workrooms: 45 foot-candles 8. Kitchen & Serving: 50 foot-candles 9. Commons: 40-footcandles 10. Restrooms: 20 foot-candles 11. Storage Rooms: 20 foot-candles 12. Utility Rooms: 20 foot-candles 13. Corridors and Stairwells: 20 foot-candles

B. Fixture Types:

1. Classrooms: Lensed 2x4 troffers 2. Gymnasium: Fluorescent high bays with T5HO fluorescent lamps 3. Media Center: Pendant direct/ indirect fluorescent 4. Offices: Lensed 2x4 troffers 5. Conference Rooms: Lensed 2x4 troffers 6. Teacher’s Planning Center Lensed 2x4 troffers 7. Workrooms: Lensed 2x4 troffers 8. Kitchen: Lensed 2x4 troffers 9. Restrooms: Linear fluorescent fixtures. 10. Storage Rooms: Lensed 2x4 troffers in rooms with finished ceiling and

industrial troffers in rooms with no ceiling. 11. Utility Rooms: Industrial troffers 12. Commons: Fluorescent high bays with T5HO fluorescent lamps 13. Corridors: Lensed 2x4 troffers

C. Lamps and Ballasts: Fluorescent lighting will consist of low mercury T8/3500K lamps with electronic ballasts.

D. Exit Lighting: Exit light fixtures for egress lighting will be provided to meet applicable codes and will use LEDs as a light source.

E. Emergency Lighting: Emergency egress lighting will be provided as required by code. Secondary power source for emergency lighting will be via batteries. Inverters will be provided to provide emergency egress lighting in large spaces such as the gymnasium and the commons. Integral emergency fluorescent power supplies (battery ballasts) will be provided for all other areas.

XX. Exterior Lighting

A. Light Levels: Designed average maintained lighting levels are as follows:

67

SYSTEMS1. Surface Parking Lots and Bus Drop, Uncovered: 1 foot-candle (fc) 2. Entry Drives: 0.5 foot-candle

B. Lamps and Ballasts: LED’s shall be used for all exterior lighting.

C. Fixtures shall be full cut-off type.

D. Pole Heights: 25 foot poles will be utilized.

XXI. Theatrical Lighting

A. A small theatrical lighting system will be provided for the stage.

XXII. Communication Systems

A. Telecommunications rooms

1. Rooms dedicated for communications systems equipment will be provided throughout the building. Typical branch telecommunications rooms (horizontal distributors, HD) will be sized to contain two floor mounted full height racks with access to three sides of racks. A larger main telecommunications room will be provided to allow enter of outside plant services and equipment for telephone, intercom, and security systems.

B. Pathways

1. Pathways will be provided to allow relocations, additions, and changes to occur in the future.

2. Cable tray furnished under Division 26 will be used as the major pathway for telecommunications cabling. Sleeves through walls and floors will also be furnished under Division 26. Where openings are required through rated walls for large quantities of cables, a fire-rated pathway containing an intumescent material will be used to allow the pathway to remain open.

C. Telecommunications Cabling – Horizontal

1. Horizontal data cabling will be unshielded twisted pair (UTP) copper cable, category 6. Horizontal data cabling will be terminated on RJ45 8-position jacks at the workstation and on rack mounted patch panels at the designated telecommunications room (TR). Color coding of cabling and jacks is TBD.

68

1.6 ELECTRICAL SYSTEMS

2. Horizontal voice cabling will match horizontal data cabling. Horizontal voice cabling will be terminated on RJ45 8-position jacks at the workstation and on rack mounted patch panels in the designated telecommunications room (TR). Color coding of cabling and jacks is TBD.

3. Scope of horizontal video cabling is TBD.

4. Wall plates at workstation outlets will be stainless steel with ID tags under clear plastic windows.

5. Stations cords will be provided by the Owner.

6. The quantity of telecomm outlets in a typical classroom is TBD.

7. The quantity of telecomm outlets in a typical office is TBD.

D. Telecommunications Cabling – Backbone

1. Backbone data cabling will consist of laser optimized 50micron multimode fiber, unless directed otherwise by the Owner. Fiber termination type (SC, ST, LC, other) is TBD.

E. Master Antenna Television Systems

1. Master Antenna Television System equipment is not in the contract.

2. See telecommunications cabling (above) for scope of cabling to be included in the contract.

F. Sound Reinforcement Systems

1. A stand-alone sound reinforcement system for spaces such as the gymnasium and commons is included in the contract.

G. Classroom Audio-Visual Systems

1. Each classroom will have a projector. Most, but not all, classrooms will have an electronic whiteboard. Rough-in (boxes and conduit) will be provided in the contract. Cabling and installation of classroom A-V systems is by Owner.

H. Intercom System

1. A microprocessor based intercom system will be provided.

69

SYSTEMS2. Classroom will be provided with a wall mounted call-in station and a

ceiling mounted speaker for hands-free two-way communication.

3. The paging speakers will be on supervised circuits so that speakers can function as part of a Fire Alarm / Emergency Communications System for paging, fire alarm, and severe weather.

I. Telephone System

1. Telephone system equipment, including the telephone switch and handsets, will be provided by the Owner.

J. Clock System

1. Clocks will be provided in each classroom, the cafeteria, and the gymnasium. Secondary clocks will be analog.

XXIII. Safety and Security Systems

A. Intrusion Detection Systems

1. Intrusion detection consisting of exterior door monitoring will be included as part of the access control system.

B. Video Surveillance Systems

1. A video surveillance system is included in the contract. System may be bid as part of larger district-wide security package.

2. Cameras shall be IP based.

3. Interior cameras shall obtain power via Power over Ethernet (PoE) switches. Switches furnished by Owner.

4. Cameras shall be provided for coverage of building entries and corridors.

C. Access Control Systems

1. Access control will be provided. Access control will be limited to the building exterior doors and the main security vestibule. Select exterior doors will be electrified and provided with card readers.

2. System may be bid as part of a larger district-wide security package.

70

1.6 ELECTRICAL SYSTEMS

3. Power will be provided for power supplies requiring a 120-volt power source.

D. Fire Alarm and Emergency Communication

1. The building will be provided with a fire detection and alarm system. The system shall be designed to meet local building codes, NFPA, ADA and other applicable local codes.

2. Signaling line circuits shall be wired per NFPA class B / style 4.

3. Notification appliance circuits shall be wired per NFPA class B / style Y.

4. Emergency communications supervised speaker system shall be provided throughout the building. The speaker system will be used for intercom system paging, class change notification, fire alarm, and severe weather notification.

5. The system shall contain automatic and manual alarm initiation. Automatic alarm initiation will be limited to areas requiring this function as mandated by code. Smoke detection shall provide coverage of corridors, storage, and utility spaces.

6. Manual alarm initiation will be provided at each building exit, in the food service area, and other locations as required by code.

7. Alarm annunciation including audible and visual annunciation will be provided throughout the building. Audible alarms shall be via tones and prerecorded messages played on emergency communication speakers.

8. Plenum rated cabling not in conduit will be allowed where installed above accessible finished ceilings.

XXIV. Specifications

A. The following sections are expected to be used for this project:

SECTION 260500 COMMON WORK RESULTS FOR ELECTRICAL SECTION 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES SECTION 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

71

SYSTEMSSECTION 260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 260923 LIGHTING CONTROL DEVICES SECTION 260943 LIGHTING CONTROL SYSTEMS SECTION 262220 LOW-VOLTAGE TRANSFORMERS SECTION 262413 SWITCHBOARDS SECTION 262416 PANELBOARDS SECTION 262726 WIRING DEVICES SECTION 262813 FUSES SECTION 262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262913 ENCLOSED CONTROLLERS SECTION 263323 CENTRAL BATTERY EQUIPMENT SECTION 265100 INTERIOR LIGHTING SECTION 265561 THEATRICAL LIGHTING SECTION 265600 EXTERIOR LIGHTING

SECTION 270500 COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 271100 COMMUNICATIONS EQUIPMENT ROOM FITTINGS SECTION 271300 COMMUNICATIONS BACKBONE CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING SECTION 275123 EDUCATIONAL INTERCOMMUNICATIONS AND

PROGRAM SYSTEMS SECTION 275313 CLOCK SYSTEMS

SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY SECTION 281300 ACCESS CONTROL SECTION 282300 VIDEO SURVELLIENCE SECTION 283100 FIRE ALARM AND EMERGENCY COMMUNICATION

72

1.6 ELECTRICAL SYSTEMS

I. Codes and Standards

A. The following codes are applicable to this project:

1. National Electrical Code (NEC) – 20082. International Building Code (IBC) – 20093. International Energy Conservation Code (IECC) - 20094. International Mechanical Code (IBC) - 2009

B. Publications from the following standards organizations will be used as design guidelines for the project:

1. National Fire Protection Association (NFPA)2. Illuminating Engineering Society of North America (IES) 3. Building Industry Consulting Services International (BICSI) 4. Americans with Disabilities Act (ADA) 5. National Electrical Manufacturer’s Association (NEMA) 6. Electrical Industries Alliance (EIA) 7. Telecommunications Industry Association (TIA)

C. The project will be designed to conform to the Americans with Disabilities Act and Architectural Guidelines (ADAAG).

II. Electrical Service

III. A padmount utility transformer will provide a 277/480-volt, 3-phase, 4-wire electrical service for each school. A main switchboard will distribute power within each building. Services will be underground if underground services are agreeable to the local utility.

IV. Metering

A. A customer-owned meter will be provided integral to the main switchboard. Meter will be interfaced with the building management system (BMS) to allow the owner to monitor overall power usage.

V. Cables and Conductors

A. All conductors will be copper; aluminum conductors will not be used.

MIDDLE SCHOOLS

73

SYSTEMSB. Cables with Type XHHW-2 insulation will be provided for services entrances

conductors and feeder conductors to panelboards

C. Cables with Type THHN-THWN insulation will be used for other feeders and all branch circuit conductors.

VI. Grounding and Bonding

A. Grounding of the service entrance equipment will be performed in accordance with NEC and will include all optional forms of supplemental electrodes.

B. Telecommunications system grounding will be provided according to BICSI guidelines. Grounding will include a main telecommunications grounding busbar (MTGB) in the main telecommunications room (building distributor, BD).

C. A grounding electrode will be provided for each exterior pole supporting lighting fixtures.

VII. Hangers and Supports

A. Hangers and supports will be constructed of steel in all areas.

VIII. Raceways and Boxes

A. The following types of raceways as defined by NEC are proposed:

1. Electrical Metallic Tubing (EMT) 2. Intermediate Metallic Tubing (IMC) 3. Rigid Metallic (Steel) Conduit (RMC) 4. Rigid Nonmetallic Conduit (RNC) 5. Flexible Metallic Conduit (FMC) 6. Liquid-Tight Flexible Metallic Conduit (LFMC)

B. Application of raceway and box products in exterior locations will be as follows:

1. Exposed Raceway: IMC or RMC 2. Concealed Raceway, Aboveground: IMC or RMC 3. Underground Conduit: RNC 4. Connections to Vibrating Equipment: LFMC 5. Boxes, Above Ground: NEMA Type 3R or Type 4

74

1.6 ELECTRICAL SYSTEMS

C. Application of raceway and box products in interior locations will be as follows:

1. Exposed, Not Subject to Physical Damage, Dry Locations: EMT 2. Exposed, Subject to Physical Damage: RMC 3. Damp or Wet Locations: RMC 4. Concealed: EMT or MC cable where allowed below. 5. Connections to Vibrating Equipment, Dry Locations: FMC 6. Connections to Vibrating Equipment, Wet Locations: LFMC 7. Connections between lighting fixtures within a room: Contractor will

have the option to use factory assembled pre-connectorized flexible wiring system.

8. Boxes, Dry Locations: NEMA 250, Type 1 9. Boxes, Damp and Wet Locations: NEMA 250, Type 4 stainless steel 10. MC cable will be allowed between devices boxes within metal stud

wall and for branch circuit wiring above accessible ceilings. MC cable will not be allowed for homeruns to panelboards.

IX. Cable Trays

A. Cable trays will be provided above accessible ceilings in corridors in areas of concentrated low voltage cabling for use as a pathway for low voltage cabling from workstations to telecommunications rooms.

B. Cable tray will be wire basket type constructed of zinc-plated steel.

X. Lighting Control

A. All spaces will have an automatic means, either occupancy sensor, vacancy sensor, or relay panel type control, to ensure lights are turned off. In addition each space will have a manual means to control lights.

B. The following types of occupancy sensors are proposed:

1. Passive Infrared Switch-Box Occupancy Sensors: Device mounted in a standard switch box. These devices will be used in small rooms where sensors have a direct line of sight to the occupants with major motion.

2. Dual-Technology Switch-Box Occupancy Sensors: Device mounted in a standard switch box. These devices will be used in small rooms with extended periods of minor motion (offices).

75

SYSTEMS3. Ceiling Mounted Occupancy Sensors: Low voltage sensor with

remote relay pack for control of loads in larger spaces.

a. Ultrasonic Type: Devices of this type will be used in rooms with walking-type movements, such as restrooms

b. Dual Technology Type - Passive Infrared and Ultrasonic: Devices of this type will be used in rooms with fine motor skill movements, such as desk and office workspace activities

C. Control for individual interior spaces will be as follows, with manual switches in all areas utilizing occupancy sensors:

1. Classrooms: Vacancy sensor via control system described above. 2. Gymnasium: Dual level low voltage switches / relay panel control. 3. Media Center: Low voltage switches / relay panel control. 4. Offices: Occupancy sensors. 5. Conference Rooms: Occupancy sensors. 6. Teacher’s Planning Center: Occupancy sensors. 7. Workrooms: Occupancy sensors. 8. Kitchen: Low voltage switches / relay panel control. 9. Restrooms: Occupancy sensors. 10. Storage Rooms: Occupancy sensors. 11. Utility Rooms: Occupancy sensors except for spaces where, due to

room configuration and type of equipment, occupancy sensors may not be ideally suited.

12. Corridors: Combination of occupancy sensing and relay panel control.

13. Commons: Low voltage switches / relay panel control. Daylight harvesting will be considered for area immediately adjacent to exterior windows in the commons.

14. Entry vestibules. Relay panel control. Photocell input to the relay panel shall be programmed to keep fixture off when adequate ambient light is available.

D. Daylight zone control. Manual override control of daylight zones will be provided in spaces as required by code. This includes all classrooms.

E. Control for exterior spaces will be as follows:

1. Parking: Relay panel control with input from the building management system (BMS).

a. AM: On at a preset time and off at dawn b. PM: On at dusk and off at a time set by Owner.

76

1.6 ELECTRICAL SYSTEMS

2. Building Exterior: Relay panel control. Dusk to dawn operation.

XI. Transformers

A. Transformers will be required to derive 120-volt and 208-volt power for receptacles and other loads.

B. Transformers will be three-phase, unless a large single-phase load makes a single-phase transformer necessary

C. Transformers will carry the NEMA TP1 rating for energy efficiency.

XII. Switchboards

A. Switchboards will consist of multiple sections, rear aligned requiring access from the front only. Switchboards shall contain breakers for mains and branch devices.

B. The service entrance switchboard will contain digital metering that will be monitored by the building management system (BMS).

C. The service entrance switchboard will contain integral factory-installed Surge Suppression Device (SPD).

XIII. Panelboards

A. Panelboards will be provided throughout the building to serve mechanical, lighting, and receptacle branch circuits. Typically, panelboards will be located in dedicated electrical rooms. Panelboards serving kitchen loads will be located (recessed) in the kitchen walls, if wall space is available.

B. With the possible exception of fractional motor loads, mechanical equipment will not be served from the same panelboards serving lighting or receptacle loads.

C. Panelboards will have bolt-on type branch breakers. Plug-in type breakers will not be permitted.

D. Panelboards will be fully rated for the calculated available fault current. Series rated devices will not be permitted.

E. SPD’s will be provided on branch circuit panelboards serving electronic loads. This will include most, if not all, 120/208volt panelboards.

XIV. Motor Controllers

77

SYSTEMSA. NEMA ICS 2, Class A, full voltage, non-reversing across-the-line motor

controllers will be provided under Division 26 where simple start-stop motor operation is required. Such motor controllers will contain a NEMA rating based on horsepower of the load, and adjustable overload relays for motor running overload protection with NEMA ICS 2, Class 20 tripping characteristics to protect motor against voltage and current unbalance and single phasing.

B. Variable frequency drives (VFD’s) will be provided with the associated motor under Division 23 where variable speed control is required.

XV. Wiring Devices

A. Wiring devices will be specification grade.

B. Standard receptacles will have a NEMA 5-20R configuration rated for 20 amps.

C. Standard toggle switches will be rated for 120/277 volts and 20 amps.

D. Wiring device faceplates will be Type 302 stainless steel.

XVI. Fuses

A. Fuses will be NEMA FU 1, non-renewable cartridge type.

B. Fuses greater than 600 amps will be Class L time delay. All other fuses will be Class J time delay.

XVII. Lightning Protection

A. Lightning protection for the building will not be provided.

XVIII. Generator

A. An emergency standby generator will not be provided.

XIX. Interior Lighting

A. Light Levels: Designed average maintained lighting levels are as follows:

1. Classrooms: 45 foot-candles (fc) 2. Gymnasium: 50 foot-candles 3. Media Center: 50 foot-candles 4. Offices: 45 foot-candles

78

1.6 ELECTRICAL SYSTEMS

5. Conference Rooms: 45 foot-candles 6. Teacher’s Planning Center: 45 foot-candles 7. Workrooms: 45 foot-candles 8. Kitchen & Serving: 50 foot-candles 9. Commons: 40-footcandles 10. Restrooms: 20 foot-candles 11. Storage Rooms: 20 foot-candles 12. Utility Rooms: 20 foot-candles 13. Corridors and Stairwells: 20 foot-candles

B. Fixture Types:

1. Classrooms: Lensed 2x4 troffers 2. Gymnasium: Fluorescent high bays with T5HO fluorescent lamps 3. Media Center: Pendant direct/ indirect fluorescent 4. Offices: Lensed 2x4 troffers 5. Conference Rooms: Lensed 2x4 troffers 6. Teacher’s Planning Center Lensed 2x4 troffers 7. Workrooms: Lensed 2x4 troffers 8. Kitchen: Lensed 2x4 troffers 9. Restrooms: Linear fluorescent fixtures. 10. Storage Rooms: Lensed 2x4 troffers in rooms with finished ceiling and

industrial troffers in rooms with no ceiling. 11. Utility Rooms: Industrial troffers 12. Commons: Fluorescent high bays with T5HO fluorescent lamps 13. Corridors: Lensed 2x4 troffers

C. Lamps and Ballasts: Fluorescent lighting will consist of low mercury T8/3500K lamps with electronic ballasts.

D. Exit Lighting: Exit light fixtures for egress lighting will be provided to meet applicable codes and will use LEDs as a light source.

E. Emergency Lighting: Emergency egress lighting will be provided as required by code. Secondary power source for emergency lighting will be via batteries. Inverters will be provided to provide emergency egress lighting in large spaces such as the gymnasium and the commons. Integral emergency fluorescent power supplies (battery ballasts) will be provided for all other areas.

XX. Exterior Lighting

A. Light Levels: Designed average maintained lighting levels are as follows:

79

SYSTEMS1. Surface Parking Lots and Bus Drop, Uncovered: 1 foot-candle (fc) 2. Entry Drives: 0.5 foot-candle

B. Lamps and Ballasts: LED’s shall be used for all exterior lighting.

C. Fixtures shall be full cut-off type.

D. Pole Heights: 25 foot poles will be utilized.

XXI. Theatrical Lighting

A. Theatrical lighting is not included in the project.

XXII. Communication Systems

A. Telecommunications rooms

1. Rooms dedicated for communications systems equipment will be provided throughout the building. Typical branch telecommunications rooms (horizontal distributors, HD) will be sized to contain two floor mounted full height racks with access to three sides of racks. A larger main telecommunications room will be provided to allow enter of outside plant services and equipment for telephone, intercom, and security systems.

B. Pathways

1. Pathways will be provided to allow relocations, additions, and changes to occur in the future.

2. Cable tray furnished under Division 26 will be used as the major pathway for telecommunications cabling. Sleeves through walls and floors will also be furnished under Division 26. Where openings are required through rated walls for large quantities of cables, a fire-rated pathway containing an intumescent material will be used to allow the pathway to remain open.

C. Telecommunications Cabling – Horizontal

1. Horizontal data cabling will be unshielded twisted pair (UTP) copper cable, category 6. Horizontal data cabling will be terminated on RJ45 8-position jacks at the workstation and on rack mounted patch panels at the designated telecommunications room (TR). Color coding of cabling and jacks is TBD.

80

1.6 ELECTRICAL SYSTEMS

2. Horizontal voice cabling will match horizontal data cabling. Horizontal voice cabling will be terminated on RJ45 8-position jacks at the workstation and on rack mounted patch panels in the designated telecommunications room (TR). Color coding of cabling and jacks is TBD.

3. Scope of horizontal video cabling is TBD.

4. Wall plates at workstation outlets will be stainless steel with ID tags under clear plastic windows.

5. Stations cords will be provided by the Owner.

6. The quantity of telecomm outlets in a typical classroom is TBD.

7. The quantity of telecomm outlets in a typical office is TBD.

D. Telecommunications Cabling – Backbone

1. Backbone data cabling will consist of laser optimized 50micron multimode fiber, unless directed otherwise by the Owner. Fiber termination type (SC, ST, LC, other) is TBD.

E. Master Antenna Television Systems

1. Master Antenna Television System equipment is not in the contract.

2. See telecommunications cabling (above) for scope of cabling to be included in the contract.

F. Sound Reinforcement Systems

1. A stand-alone sound reinforcement system for spaces such as the gymnasium and commons is included in the contract.

G. Classroom Audio-Visual Systems

1. Each classroom will have a projector. Most, but not all, classrooms will have an electronic whiteboard. Rough-in (boxes and conduit) will be provided in the contract. Cabling and installation of classroom A-V systems is by Owner.

H. Intercom System

1. A microprocessor based intercom system will be provided.

81

SYSTEMS2. Classroom will be provided with a wall mounted call-in station and a

ceiling mounted speaker for hands-free two-way communication.

3. The paging speakers will be on supervised circuits so that speakers can function as part of a Fire Alarm / Emergency Communications System for paging, fire alarm, and severe weather.

I. Telephone System

1. Telephone system equipment, including the telephone switch and handsets, will be provided by the Owner.

J. Clock System

1. Clocks will be provided in each classroom, the cafeteria, and the gymnasium. Secondary clocks will be digital.

XXIII. Safety and Security Systems

A. Intrusion Detection Systems

1. Intrusion detection consisting of exterior door monitoring will be included as part of the access control system.

B. Video Surveillance Systems

1. A video surveillance system is included in the contract. System may be bid as part of larger district-wide security package.

2. Cameras shall be IP based.

3. Interior cameras shall obtain power via Power over Ethernet (PoE) switches. Switches furnished by Owner.

4. Cameras shall be provided for coverage of building entries and corridors.

C. Access Control Systems

1. Access control will be provided. Access control will be limited to the building exterior doors and the main security vestibule. Select exterior doors will be electrified and provided with card readers.

2. System may be bid as part of a larger district-wide security package.

82

1.6 ELECTRICAL SYSTEMS

3. Power will be provided for power supplies requiring a 120-volt power source.

D. Fire Alarm and Emergency Communication

1. The building will be provided with a fire detection and alarm system. The system shall be designed to meet local building codes, NFPA, ADA and other applicable local codes.

2. Signaling line circuits shall be wired per NFPA class B / style 4.

3. Notification appliance circuits shall be wired per NFPA class B / style Y.

4. Emergency communications supervised speaker system shall be provided throughout the building. The speaker system will be used for intercom system paging, class change notification, fire alarm, and severe weather notification.

5. The system shall contain automatic and manual alarm initiation. Automatic alarm initiation will be limited to areas requiring this function as mandated by code. Smoke detection shall provide coverage of corridors, storage, and utility spaces.

6. Manual alarm initiation will be provided at each building exit, in the food service area, and other locations as required by code.

7. Alarm annunciation including audible and visual annunciation will be provided throughout the building. Audible alarms shall be via tones and prerecorded messages played on emergency communication speakers.

8. Plenum rated cabling not in conduit will be allowed where installed above accessible finished ceilings.

XXIV. Specifications

A. The following sections are expected to be used for this project:

SECTION 260500 COMMON WORK RESULTS FOR ELECTRICAL SECTION 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES SECTION 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

83

SYSTEMSSECTION 260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 260923 LIGHTING CONTROL DEVICES SECTION 260943 LIGHTING CONTROL SYSTEMS SECTION 262220 LOW-VOLTAGE TRANSFORMERS SECTION 262413 SWITCHBOARDS SECTION 262416 PANELBOARDS SECTION 262726 WIRING DEVICES SECTION 262813 FUSES SECTION 262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262913 ENCLOSED CONTROLLERS SECTION 263323 CENTRAL BATTERY EQUIPMENT SECTION 265100 INTERIOR LIGHTING SECTION 265600 EXTERIOR LIGHTING

SECTION 270500 COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 271100 COMMUNICATIONS EQUIPMENT ROOM FITTINGS SECTION 271300 COMMUNICATIONS BACKBONE CABLING SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING SECTION 275123 EDUCATIONAL INTERCOMMUNICATIONS AND

PROGRAM SYSTEMS SECTION 275313 CLOCK SYSTEMS

SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY SECTION 281300 ACCESS CONTROL SECTION 282300 VIDEO SURVELLIENCE SECTION 283100 FIRE ALARM AND EMERGENCY COMMUNICATION

8484

1.7 DLR BUDGET & PROGRAMMING

FCI

Modernization $170.00 psfExisting Space Unit Quantity Total Cost CommentsExisting School 30468 1 30,468 $0.00 REPLACE

1 0 $0.008 0 $0.001 0 $0.00

Total 0 $0.00A/E Fees 8% $0.00Soft Costs: 18% $0.00Total Renovation Project Cost $0.00

New Construction $220.00 psfNew Program Space Unit Quantity Total Cost Comments

Kindergarten 1000 5 5,000 $1,100,000.00Classrooms (1-3) 850 12 10,200 $2,244,000.00Classrooms (4-5) 850 8 6,800 $1,496,000.00Kindergarten - RR 50 5 250 $55,000.00Media Center 1855 1 1,855 $408,100.00Computer Lab 900 1 900 $198,000.00Fine Arts Instruction 1200 1 1,200 $264,000.00Fine Arts Storage 100 1 100 $22,000.00Discovery Area 425 3 1,275 $280,500.00Phys Ed Area 5300 1 5,300 $1,166,000.00Special Education 2375 1 2,375 $522,500.00Administration 760 1 760 $167,200.00Student Dining 3975 1 3,975 $874,500.00Food Service 1857 1 1,857 $408,540.00Building Services 12620 1 12,620 $2,776,400.00Support Space 5319 1 5,319 $1,170,180.0010% Construction 59,786 0.1 5,979 $1,315,292.00

Total 65,765 $14,468,212.00

PreK Classrooms 1000 0 0 $0.00PreK - RR 50 0 0 $0.00Additional SF 59786 0.1 5,979 $1,315,292.00

Total New Construction 71,743 $15,783,504.00

NEW Elementary K-5 New

PINE ELEMENTARY SCHOOL

85

PROGRAMMINGTotal Construction Cost $15,783,504.00Architectural / Engineering Fees (base contract) 6.0% $947,010.24Architectural / Engineering Fees 5.5% $868,092.72Specialty Consultants (Kitchen / Theater / Acoustics) 0.3% $47,350.51Bond Management (1.0%) 0.0% $0.00A/E Reimbursables (printing/shipping/travel) 0.5% $78,917.52Site Acquisition 2.0% $315,670.08Off- Site Development 0.5% $78,917.52Street Improvements 0.5% $78,917.52Surveys / Geotechnical Engineering 0.5% $78,917.52Plan Review Fees (% of construction value) 0.1% $15,783.50Construction Materials Testing 0.5% $78,917.52Telephone and Technology 1.3% $205,185.55Furniture Fixtures and Equipment (FF&E) 7.7% $1,215,329.81Owner Direct Costs (Moving/Operational/Attorney) 0.3% $47,350.51Project Design Contigency 2.8% $441,938.11Project Construction Contigency 5.0% $789,175.20Soft Cost Contingency (1.2% of soft costs) 0.0% $0.00

Soft Costs Subtotal: 27.5% $4,340,463.60Total New Project Cost $20,123,967.60

TOTAL PROJECT SQUARE FEET: 71,743TOTAL PROJECT COST (Modernization / New): $20,123,967.60Inflationary Estimation at 4% / yr 0 20,123,968 $0.00

$20,123,967.60

PINE ELEMENTARY

8686

1.7 DLR BUDGET & PROGRAMMING

New Construction $225.00 psfNew Program Space Unit Quantity Total Cost Comments

Grade 6 Classrooms 850 8 6,800 $1,530,000.00Grade 7-8 Classrooms 850 15 12,750 $2,868,750.00Science Cls/Lab chem 1440 1 1,440 $324,000.00Science Cls/Lab Bio 1300 1 1,300 $0.00Science Prep 300 1 300 $0.00Chem Stor 150 1 150 $0.00Multi Use Room 1500 0 $0.00Instruct Multi-Purpose 850 1 850 $0.00Project Lab / Cls 1100 0 $0.00Computer Lab 900 1 900 $202,500.00Reading Rm / Circultn 2640 1 2,640 $594,000.00Art Room 1200 1 1,200 $270,000.00Art Material Storage 100 1 100 $22,500.00Instrumental Room 1400 1 1,400 $315,000.00Music Storage 100 1 100 $22,500.00Vocal Room 1200 1 1,200 $270,000.00Vocal Storage 150 0 $0.00Phys Ed Area 9900 1 9,900 $2,227,500.00Student Locker Room 850 0 $0.00Student Restoom/Shwr 350 0 $0.00Workforce Dev 1300 1 1,300 $292,500.00Special Education 2375 1 2,375 $534,375.00Administration 760 1 760 $171,000.00Auditorium 15000 0 $0.00Stage Area (incl wings) 6000 0 $0.00Student Dining 4950 1 4,950 $1,113,750.00Food Service 2312 1 2,312 $520,200.00Building Services 15700 1 15,700 $3,532,500.00Support Space 9478 1 9,478 $2,132,550.0010% Construction 77,905 0.1 7,791 $1,752,862.50

Total 85,696 $19,281,487.50

0 $0.000 $0.00

Additional SF 77905 0.15 11,686 $2,629,293.75

Total New 97,381 $21,910,781.25

PINE MIDDLE SCHOOLFCI

660 Capacity

Modernization $90.00 psfExisting Space Unit Quantity Total Cost CommentsExisting School 0 0 0 $0.00

New MS Pine Street

87

PROGRAMMINGTotal Improvement $21,910,781.25Architectural / Engineering Fees (base contract) 6.0% $1,314,646.88Architectural / Engineering Fees 5.5% $1,205,092.97Specialty Consultants (Kitchen / Theater / Acous 0.3% $65,732.34Bond Management (1.0%) 0.0% $0.00A/E Reimbursables (printing/shipping/travel) 0.5% $109,553.91Site Acquisition 2.0% $438,215.63Off- Site Development 0.5% $109,553.91Street Improvements 0.5% $109,553.91Surveys / Geotechnical Engineering 0.8% $175,286.25Plan Review Fees (% of construction value) 0.1% $21,910.78Construction Materials Testing 0.5% $109,553.91Telephone and Technology 1.3% $284,840.16Furniture Fixtures and Equipment (FF&E) 7.7% $1,687,130.16Owner Direct Costs (Moving/Operational/Attorne 0.3% $65,732.34Project Design Contigency 3.0% $657,323.44Project Construction Contigency 5.0% $1,095,539.06Soft Cost Contingency (.5% of soft costs) 0.5% $109,553.91

Soft Costs Subtotal: 28.5% $6,244,572.66Total New Project Cost $28,155,353.91

TOTAL PROJECT SQUARE FEET: 97,381TOTAL PROJECT COST $28,155,353.91Inflationary Estimation at 4% / yr 0.07 21,910,781 $1,533,754.69

$29,689,108.59

PINE MIDDLE SCHOOL

8888

1.7 DLR BUDGET & PROGRAMMING

New Construction $225.00 psfNew Program Space Unit Quantity Total Cost Comments

Grade 6 Classrooms 850 8 6,800 $1,530,000.00Grade 7-8 Classrooms 850 15 12,750 $2,868,750.00Science Cls/Lab chem 1440 1 1,440 $324,000.00Science Cls/Lab Bio 1300 1 1,300 $0.00Science Prep 300 1 300 $0.00Chem Stor 150 1 150 $0.00Multi Use Room 1500 0 $0.00Instruct Multi-Purpose 850 1 850 $0.00Project Lab / Cls 1100 0 $0.00Computer Lab 900 1 900 $202,500.00Reading Rm / Circultn 2640 1 2,640 $594,000.00Art Room 1200 1 1,200 $270,000.00Art Material Storage 100 1 100 $22,500.00Instrumental Room 1400 1 1,400 $315,000.00Music Storage 100 1 100 $22,500.00Vocal Room 1200 1 1,200 $270,000.00Vocal Storage 150 0 $0.00Phys Ed Area 9900 1 9,900 $2,227,500.00Student Locker Room 850 0 $0.00Student Restoom/Shwr 350 0 $0.00Workforce Dev 1300 1 1,300 $292,500.00Special Education 2375 1 2,375 $534,375.00Administration 760 1 760 $171,000.00Auditorium 15000 0 $0.00Stage Area (incl wings) 6000 0 $0.00Student Dining 4950 1 4,950 $1,113,750.00Food Service 2312 1 2,312 $520,200.00Building Services 15700 1 15,700 $3,532,500.00Support Space 9478 1 9,478 $2,132,550.0010% Construction 77,905 0.1 7,791 $1,752,862.50

Total 85,696 $19,281,487.50

0 $0.000 $0.00

Additional SF 77905 0.15 11,686 $2,629,293.75

Total New 97,381 $21,910,781.25

WESTERN MIDDLE SCHOOLFCI

660 Capacity

Modernization $90.00 psfExisting Space Unit Quantity Total Cost CommentsExisting School 0 0 0 $0.00

New MS Western

89

PROGRAMMINGTotal Improvement $21,910,781.25Architectural / Engineering Fees (base contract) 6.0% $1,314,646.88Architectural / Engineering Fees 5.0% $1,095,539.06Specialty Consultants (Kitchen / Theater / Acous 0.3% $65,732.34Bond Management (1.0%) 0.0% $0.00A/E Reimbursables (printing/shipping/travel) 0.5% $109,553.91Site Acquisition 2.0% $438,215.63Off- Site Development 0.5% $109,553.91Street Improvements 0.5% $109,553.91Surveys / Geotechnical Engineering 0.8% $175,286.25Plan Review Fees (% of construction value) 0.1% $21,910.78Construction Materials Testing 0.5% $109,553.91Telephone and Technology 1.3% $284,840.16Furniture Fixtures and Equipment (FF&E) 7.7% $1,687,130.16Owner Direct Costs (Moving/Operational/Attorne 0.3% $65,732.34Project Design Contigency 3.0% $657,323.44Project Construction Contigency 5.0% $1,095,539.06Soft Cost Contingency (.5% of soft costs) 1.0% $219,107.81

Soft Costs Subtotal: 28.5% $6,244,572.66Total New Project Cost $28,155,353.91

TOTAL PROJECT SQUARE FEET: 97,381TOTAL PROJECT COST $28,155,353.91Inflationary Estimation at 4% / yr 0.07 21,910,781 $1,533,754.69

$29,689,108.59

WESTERN MIDDLE

9090

ESTI

MAT

ING

91

1.8 JE DUNN ESTIMATES & PHASING

PROJECT COSTS

92

1.8 JE DUNN ESTIMATES & PHASING

ELEMENTARY SCHOOLS

93

ESTIMATING

94

1.8 JE DUNN ESTIMATES & PHASING

ELEMENTARY SCHOOLS

95

ESTIMATING

96

1.8 JE DUNN ESTIMATES & PHASING

ELEMENTARY SCHOOLS

97

ESTIMATING

98

1.8 JE DUNN ESTIMATES & PHASING

ELEMENTARY SCHOOLS

99

ESTIMATING

100

1.8 JE DUNN ESTIMATES & PHASING

MIDDLE SCHOOLS

101

ESTIMATING

102

1.8 JE DUNN ESTIMATES & PHASING

MIDDLE SCHOOLS

103

ESTIMATING

104

1.8 JE DUNN ESTIMATES & PHASING

MIDDLE SCHOOLS

105

ESTIMATING

106

PHA

SIN

G

listen.DESIGN.deliver