Level Control Unit
LevelControl Basic 2
Type Series Booklet
Type BS Type BC
Legal information/Copyright Type Series Booklet LevelControl Basic 2 KSB Aktiengesellschaft Frankenthal All rights reserved. Contents provided herein must neither be distributed, copied, reproduced, editedor processed for any other purpose, nor otherwise transmitted, published or made available to a thirdparty without KSB´s express written consent. Subject to technical modification without prior notice. © KSB Aktiengesellschaft Frankenthal 25.07.2011
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2
Type BS Type BC
General description
The control unit is a level-dependent pump control andmonitoring unit (with display) for either one or two pumps.
The following functions are available:
▪ Tank drainage
▪ Tank filling (using float switches or 4...20 mA sensor)
The ATEX variant of the control unit can be used for pumps inpotentially explosive atmospheres. The control unit is installedoutside the potentially explosive atmosphere.
Main applications
The control unit can be deployed in waste water engineeringand lifting/pumping stations for applications such as drainage,dewatering, water extraction, liquid transport and disposal.
The control unit can be used with the following pumps, forexample:
▪ Ama-Drainer
▪ Ama-Drainer N
▪ Ama-DrainerBox (LevelControl included in scope of supply)
▪ MK
▪ Ama-Porter
▪ Amarex N
▪ Amarex KRT
▪ CK pump stations (LevelControl included in scope ofsupply in some cases)
▪ miniCompacta/Compacta (LevelControl included in scopeof supply)
▪ Etaline
▪ Sewatec/-bloc
▪ Other pumps on request
Variants
Two variants are available:
▪ Basic Compact (plastic housing)
▪ Basic Control Cabinet (sheet steel housing)
Basic Compact
Pump control and monitoring unit in acompact housing, with display, for either 1or 2 pumps. The level is determined by atleast one float switch, an analog sensor 4 ..20 mA, an integrated pressure sensor(pneumatic) or - as special version - abubbler system up to 2 metres of water,for motors with DOL starting.
Basic Control Cabinet
Pump control and monitoring unit in asteel cabinet, with display, for either 1 or 2pumps. The level is determined by at leastone float switch, an analog sensor 4 .. 20mA or an integrated pressure sensor(pneumatic or bubbler control), for motorswith DOL or star-delta starting.
Designation
Example: BC 2 400 D F N O 100Designation
Code Description Other versionsBC Type BC LevelControl Basic - Compact
BS LevelControl Basic - Schaltschrank (control cabinet)2 Number of pumps 1 Single-pump unit
2 Dual-pump unit400 Voltage,
no. of wires230 230 V, 3 wires (L, N, P E)400 400 V, 4 or 5 wires (L1, L2, L3, (N), PE)
D Starting method D DOL startingS Star/delta
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 3
Code Description Other versionsW Soft startingX 3 wires (L, N, PE) capacitor motor 25 µFY 3 wires (L, N, PE) capacitor motor 40 µFZ Z = 3 wires (L, N, PE) capacitor motor 40 µF, start capacitor 66 µF
F Sensors F Float switch(es)P Pneumatic level measurement 3.5 mM Pneumatic level measurement 10.5 mL Bubbler control 2 mH Bubbler control 3 mU 4 .. 20 mA analog inputV Voltage input 0.5 .. 4.5 VD Digital switch
N ATEX N Without ATEX functionsE With ATEX functions
O Installation variants
O StandardA With rechargeable batteryM With motor protection switch (if not included in standard version)N With rechargeable battery and motor protection switch (if not included in
standard version)P With PTC relay (if not included in standard version; standard for 5.5kW and
above)Q With rechargeable battery and PTC relay (if not included in standard version)
100 Rated current 010 1.0 A016 1.6 A025 2.5 A040 4 A063 6.3 A100 10 A140 14 A180 18 A230 23 A250 25 A400 40 A630 63 A >63 A available on request
Technical specifications
Technical specifications
Characteristics BC BSRated operatingvoltage
3 ~ 400 V AC +10% -15%,1 ~ 230 V AC+10% -15%
Mains frequency 50 / 60 Hz ± 2 %Rated insulationvoltage
500 V AC
Rated current permotor
1 to 10 A max. 1 to 63 A max.
Rated power permotor
DOL starting: up to4 kW max.
DOL or star/deltastarting: 0.35 to 22kW
Enclosure IP 54Material Plastic:
polycarbonateRittal: sheet steel(colour RAL 7035,light grey)
Temperatureduring operation
-10 °C to 50 °C
Storagetemperature
-10 °C to 70 °C
The current is the leading variable: The control unit isselected on the basis of the rated current of the pump.Higher currents and power ratings are available on request.
Dimensions and weights
Dimensions and weights
Max. current [A]
Size HxWxD[mm] [kg]
Type BC10 400 x 278 x 135 3
Type BS110 400 x 300 x 155 1014 600 x 400 x 200 1418 600 x 400 x 200 1423 600 x 400 x 200 1425 600 x 400 x 200 1440 760 x 600 x 210 1863 760 x 600 x 210 18
Type BS210 400 x 300 x 155 1614 760 x 600 x 210 1918 760 x 600 x 210 1923 760 x 600 x 210 1925 760 x 600 x 210 1940 760 x 600 x 210 2463 760 x 600 x 210 26
Pump Control Systems
LevelControl Control Units
4 LevelControl Basic 2
Technical specifications for sensors
4 f loat /digital switches, 12 . . 25.2 V DC or 230V AC
▪ For ATEX with float switches:
– Single-pump station: 2 intrinsic safety barriers, typeStahl 9002/13-280-093-001
– Dual-pump station: 3 intrinsic safety barriers, typeStahl 9002/13-280-093-001
▪ For ATEX with digital switches (selection via EasySelect):
– Single-pump station: incl. 3 intrinsic safety barriers,type Stahl 9002/13-280-093-001
– Dual-pump station: incl. 4 intrinsic safety barriers,type Stahl 9002/13-280-093-001
4 . . 20 mA
▪ Two-wire and three-wire connection
▪ Input resistance ≤ 300 ohms
▪ ATEX-compliant versions in BS housing
▪ For ATEX-compliant version incl. 1 analog intrinsic safetybarrier, type Stahl 9002/13-280-110-001
Integrated pneumatic pressure sensor
▪ For open pressure bell or closed pressure bell
▪ Up to 3 metres of water (5 psi/345 mbar)
▪ Optional: Up to 10 metres of water (15 psi/1034 mbar)
Integrated pressure sensor with compressorfor bubbler control
▪ For open pressure bell
▪ Compressor up to 2 metres of water (3 metres of water onoption)
Motor protect ion sensors
▪ Max. 2 bimetal (thermal circuit breaker) for each pump, 24V, motor monitoring
▪ From 5.5 kW star/delta starting: PTC motor monitor foreach pump (optionally available for <5.5kW)
▪ Max. 1 moisture monitor for each Amarex N/KRT pump
Process inputs
▪ 1 external alarm input, 24 V
▪ 1 remote acknowledgement, 24 V
Process outputs
▪ 1 volt-free signalling output changeover contact (250 V, 1A, NO/NC contact)
▪ 1 signalling output (12.6 to 13.2 V, max. 200 mA), e.g. forconnecting a horn, alarm combination or alarm strobelight (12 V connection)
Rechargeable battery
Connection for rechargeable battery, for mains-independentpower supply of:
▪ Electronics
▪ Sensors
▪ Alarm equipment
Battery l i fe /charging t ime
Battery life:
▪ Approx. 10 hours when supplying the integrated piezobuzzer 85 dB(A), electronics, and sensors
▪ Approx. 4 hours when supplying external alarmequipment (e.g. horn, alarm combination, or alarm strobelight)
Charging time
▪ Approx. 11 hours (if battery is fully discharged)
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 5
LevelControl Basic 2 for Ama-Drainer
Documented device variants
Control units for s ingle-pump stat ion
Float switch incl. 4 .. 20 mA input
Pneumatic
Variant DFNO SFNO DPNO SPNO230 V: Up to 10 A BC1 230 DFNO 100 - BC1 230 DPNO 100 -400 V: 1.6 - 2.5 A BC1 400 DFNO 025 - BC1 400 DPNO 025 -400 V: 2.5 - 4.0 A BC1 400 DFNO 040 - BC1 400 DPNO 040 -400 V: 4.0 - 6.3 A BC1 400 DFNO 063 - BC1 400 DPNO 063 -400 V: 6.3 - 10 A BC1 400 DFNO 100 - BC1 400 DPNO 100 -400 V: 13 - 18 A - BS1 400 SFNO 180 - BS1 400 SPNO 180
Control units for dual-pump stat ion
Float switch incl. 4 .. 20 mA input
Pneumatic
Variant DFNO SFNO DPNO SPNO230 V: Up to 10 A BC2 230 DFNO 100 - BC2 230 DPNO 100 -400 V: 1.6 - 2.5 A BC2 400 DFNO 025 - BC2 400 DPNO 025 -400 V: 2.5 - 4.0 A BC2 400 DFNO 040 - BC2 400 DPNO 040 -400 V: 4.0 - 6.3 A BC2 400 DFNO 063 - BC2 400 DPNO 063 -400 V: 6.3 - 10 A BC2 400 DFNO 100 - BC2 400 DPNO 100 -400 V: 13 - 18 A - BS2 400 SFNO 180 - BS2 400 SPNO 180
Functional comparison
Single-pump station Dual-pump stationopt = optional Float switch
incl. 4 .. 20 mAPneumatic Float switch
incl. 4 .. 20 mAPneumatic
Variant DFNO SFNO DPNO SPNO DFNO SFNO DPNO SPNOFunctionsDraining x xFilling via float switch x - x -Stand-by pump: 1 pump redundant - - x xPump switchover after each start - - x xPump switchover in event of fault - - x xPeak load operation function - - x xRuntime limitation x xOFF via after-run time x xOFF via level x xOperation check run after idle period x xAlert history x xDisplay and operation7-segment display x xIndication of water level dig.1) x dig.1) x
For each pump: operation/fault/pumprunning
Multicolour LED Multicolour LED
General fault (traffic light) LED LEDHigh water LED LEDMains voltage x xOperating hours of each pump x x
1) Digital display of switching points
Pump Control Systems
LevelControl Control Units
6 LevelControl Basic 2
Single-pump station Dual-pump stationopt = optional Float switch
incl. 4 .. 20 mAPneumatic Float switch
incl. 4 .. 20 mAPneumatic
Variant DFNO SFNO DPNO SPNO DFNO SFNO DPNO SPNOStarts per pump x xRotary field direction detection (mains) x xPhase monitoring x xChange of switching levels - x - xHousing H [mm] x W [mm] x D [mm], IP 54Plastic 400 x 278 x 135 x - x - x - x -Sheet steel 600 x 400 x 200 - x - - - - - -Sheet steel 760 x 600 x 210 - - - - - x - xBuilt-in componentsMaster switch (lockable) opt x opt x opt x opt xManual-0-automatic switch for each pump x xDOL starting x - x - x - x -Star/delta starting - x - x - x - xMotor protectionFuse (in 230 V devices) x - x - x - x -Motor protection switch (in 400 V devices) x xMotor temperature warning input x xMotor temperature alert input x xPumpThermal circuit breaker/bimetal See note below See note belowInstallation optionsRechargeable battery for powering thedevice
opt opt
Control cabinet heating for type BS - opt - opt - opt - optAlarm equipment1 free alarm input x x1 digital input for high water alert x xVolt-free contact (changeover contact) x xPiezo buzzer 85 dB(A) x xHorn/alarm combination/alarm strobe light 12V DC
opt opt
Inputs/outputsInputs for float switches 4 - 4 -4 .. 20 mA analog input x - x -Pneumatic pressure sensor - x - xRemote acknowledgement x x12 V DC connection for horn, etc. x xSensor accessoriesFloat switch (NO contact) opt - opt -Redundant high water float - opt - optOpen pressure bell (open system) - opt - optClosed pressure bell (closed system) - opt - optF1 moisture sensor opt optToolsKSB ServiceTool for Windows XP opt opt
Note for 1~230 V AC:
▪ Ama-Drainer N 301/302/303, Ama-Drainer N 358, Ama-Drainer NE 4../5.. : bimetal switch in the motor
Bimetal switch is not connected to the control unit.
Note for 3~400 V AC:
▪ Ama-Drainer NE 4../5..,Ama-Drainer (B) 80 / (B)100: bimetal switch brought out. Bimetal switch is connected to the control unit via thepump cable.
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 7
Ama-Drainer with control unit type BC
1~230 V: Ama-Drainer N 301/302/303, Ama-Drainer N 358, Ama-Drainer NE 4../5.., Ama-Porter NE
18
19
20
21
22
23
22
24
25
26
27
15 16 17
J403
J201
J401 J601J604
1 2 3
4 5 6 7 8 9 10 11 12 13 14
2T1 4T2 6T3 14NO A2 2T1 4T2 6T3 14NO A2L3 L2 L1 N PE
bn bugn/y
e
PE PE 122
222
120
220
121
221
109
209
002001 012
013
016
017
014
015
010
011
030
031
050
051
040
041
018
019
021024 022
bn bugn/y
e
bn bu
bk bu
PE g
n/ye
bk bu
PE g
n/ye
+
-
bn bu
012
013
014
015
010
011
019
014
015
Analog IN+24V
(GND)
014
015
Analog IN+24V
PE g
n/ye
PE
gn/
ye
29
- +28
J203
Alarm
29
Circuit diagram: Ama-Drainer N 301/302/303, Ama-Drainer N 358, Ama-Drainer NE 4../5.., Ama-Porter NE
1 Contactor pump 1 2 Contactor pump 23 Mains connections
3~400V, 1~230V4 Moisture monitor
5 Thermal circuit breaker 6 Release7 Volt-free alarm contact 8 Float/digital switch9 High-water float 10 mini-Compacta/Compacta sensors11 Connection for alarm equipment 12 External alarm input13 Remote acknowledgement 14 Pneumatic15 Pump 1 16 Pump 217 Power supply 18 High-water float19 Float switches 20 Digital switch21 Analog sensor 4 ... 20 mA 22 Peak load ON23 Pump ON/OFF 24 Base load ON25 Pumps OFF 26 Signal transmitter 12 V DC27 Contact 28 Rechargeable battery connection29 230 V
bk (black)bu (blue)bn (brown)PE = gn/ye (green/yellow)
30 400VU1:bk (black)V1:bu (blue)W1:bn (brown)PE = gn/ye (green/yellow)
Pump Control Systems
LevelControl Control Units
8 LevelControl Basic 2
3~400 V: Ama-Drainer ND 4.. /5..
18
19
20
21
22
23
22
24
25
26
27
15 16 17
J403
J201
106J104J J604
1 2 3
4 5 6 7 8 9 10 11 12 13 14
012
013
016
017
014
015
010
011
030
031
050
051
040
041
018
019
+
-2T1 4T2 6T3 14NO A2 2T1 4T2 6T3 14NO A2
L3 L2 L1 N PE PE PE 122
222
120
220
121
221
109
209
002001 021024 022
2 3
L1
PE
gn/y
e
PE
gn/y
e
1 2 3 5gn
/ge
4
F6
F7
1 2 3 5gn
/ge
4
F6
F7
66
L2 L3 (N) PE
5 (4)
1 5 4
5 42 31
012
013
014
015
010
011
019
014
015
Analog IN+24V
(GND)
014
015
Analog IN+24V
- +28
J203
Alarm
30 30
Circuit diagram: Ama-Drainer ND 4.. /5..
1 Contactor pump 1 2 Contactor pump 23 Mains connections
3~400V, 1~230V4 Moisture monitor
5 Thermal circuit breaker 6 Release7 Volt-free alarm contact 8 Float/digital switch9 High-water float 10 mini-Compacta/Compacta sensors11 Connection for alarm equipment 12 External alarm input13 Remote acknowledgement 14 Pneumatic15 Pump 1 16 Pump 217 Power supply 18 High-water float19 Float switches 20 Digital switch21 Analog sensor 4 ... 20 mA 22 Peak load ON23 Pump ON/OFF 24 Base load ON25 Pumps OFF 26 Signal transmitter 12 V DC27 Contact 28 Rechargeable battery connection29 230 V
bk (black)bu (blue)bn (brown)PE = gn/ye (green/yellow)
30 400VU1:bk (black)V1:bu (blue)W1:bn (brown)PE = gn/ye (green/yellow)
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 9
3~400 V: Ama-Drainer B(80)
18
19
20
21
22
23
22
24
25
26
27
15 16 17
J403
J201
J401 J601J604
1 2 3
4 5 6 7 8 9 10 11 12 13 14
2T1 4T2 6T3 14NO A2 2T1 4T2 6T3 14NO A2L3 L2 L1 N PE PE PE 122
222
120
220
121
221
109
209
002001 012
013
016
017
014
015
010
011
030
031
050
051
040
041
018
019
021024 022
2 3
L1
PE
PE
+
-
1 2 3 5 PE4
F6
1 2 3 5 PE4
F6
66
L2 L3 (N) PE
5 (4)
1 5 4
5 42 31
012
013
014
015
010
011
019
014
015
Analog IN+24V
(GND)
014
015
Analog IN+24V
- +28
J203
Alarm
30 30
Circuit diagram: Ama-Drainer B(80)
1 Contactor pump 1 2 Contactor pump 23 Mains connections
3~400V, 1~230V4 Moisture monitor
5 Thermal circuit breaker 6 Release7 Volt-free alarm contact 8 Float/digital switch9 High-water float 10 mini-Compacta/Compacta sensors11 Connection for alarm equipment 12 External alarm input13 Remote acknowledgement 14 Pneumatic15 Pump 1 16 Pump 217 Power supply 18 High-water float19 Float switches 20 Digital switch21 Analog sensor 4 ... 20 mA 22 Peak load ON23 Pump ON/OFF 24 Base load ON25 Pumps OFF 26 Signal transmitter 12 V DC27 Contact 28 Rechargeable battery connection29 230 V
bk (black)bu (blue)bn (brown)PE = gn/ye (green/yellow)
30 400VU1:bk (black)V1:bu (blue)W1:bn (brown)PE = gn/ye (green/yellow)
Pump Control Systems
LevelControl Control Units
10 LevelControl Basic 2
LevelControl Basic 2 for Ama-Porter
Documented device variants
Control units for s ingle-pump stat ion
Float switch incl. 4 .. 20 mA input
Pneumatic Bubbler control
Variant DFNO DPNO DLNO in BS housing DLNO in BC housing230 V: Up to 10 A BC1 230 DFNO 100 BC1 230 DPNO 100 BS1 230 DLNO 100 BC1 230 DLNO 100400 V: 2.5 - 4.0 A BC1 400 DFNO 040 BC1 400 DPNO 040 BS1 400 DLNO 040 BC1 400 DLNO 040400 V: 4.0 - 6.3 A BC1 400 DFNO 063 BC1 400 DPNO 063 BS1 400 DLNO 063 BC1 400 DLNO 063
Control units for dual-pump stat ion
Float switch incl. 4 .. 20 mA input
Pneumatic Bubbler control
Variant DFNO DPNO DLNO in BS housing DLNO in BC housing230 V: Up to 10 A BC2 230 DFNO 100 BC2 230 DPNO 100 BS2 230 DLNO 100 BC2 230 DLNO 100400 V: 2.5 - 4.0 A BC2 400 DFNO 040 BC2 400 DPNO 040 BS2 400 DLNO 040 BC2 400 DLNO 040400 V: 4.0 - 6.3 A BC2 400 DFNO 063 BC2 400 DPNO 063 BS2 400 DLNO 063 BC2 400 DLNO 063
Functional comparison
opt = optional Single-pump station Dual-pump stationVariant DFNO DPNO DLNO
(BShousing)
DLNO (BC
housing)
DFNO DPNO DLNO(BS
housing)
DLNO(BC
housing)FunctionsDraining x xFilling via float switch x - - - x - - -Stand-by pump: 1 pump redundant - xPump switchover after each start - xPump switchover in event of fault - xPeak load operation function - xRuntime limitation x xOFF via after-run time x xOFF via level x xOperation check run after idle period x xDisplay and operation7-segment display x xIndication of water level dig.2) x x x dig.2) x x x
For each pump: operation/fault/pump running Multicolour LED Multicolour LEDGeneral fault (traffic light) LED LEDHigh water LED LEDMains voltage x xOperating hours of each pump x xStarts per pump x xRotary field direction detection (mains) x xPhase monitoring x xChange of switching levels - x x x - x x xHousing H [mm] x W [mm] x D [mm], IP 54Plastic 400 x 278 x 135 x x - x x x - xSheet steel 400 x 300 x 155 - - x - - - x -Built-in components
2) Digital display of switching points
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 11
opt = optional Single-pump station Dual-pump stationVariant DFNO DPNO DLNO
(BShousing)
DLNO (BC
housing)
DFNO DPNO DLNO(BS
housing)
DLNO(BC
housing)Master switch (lockable) opt opt x - opt opt x -Manual-0-automatic switch for each pump x xDOL starting x xMotor protectionFuse (in 230 V devices) x xMotor protection switch (in 400 V devices) x xMotor temperature warning input x xMotor temperature alert input x xPumpThermal circuit breaker/bimetal x xInstallation optionsRechargeable battery for powering the device opt optControl cabinet heating for type BS - - opt - - - x -Alarm equipment1 free alarm input x x1 digital input for high water alert x xVolt-free contact (changeover contact) x xPiezo buzzer 85 dB(A) x xHorn/alarm combination/alarm strobe light 12 VDC
opt opt
Inputs/outputsInputs for float switches 4 - - - 4 - - -4 .. 20mA analog input x - - - x - - -Pneumatic pressure sensor - x - - - x - -Bubbler control with compressor - - x x - - x xRemote acknowledgement x x12 V DC connection for horn etc. x xSensor accessoriesFloat switch (NO contact) opt - - - opt - - -Redundant high water float - opt opt opt - opt opt optOpen pressure bell (open system) - opt opt opt - opt opt optClosed pressure bell (closed system) - opt - - - opt - -F1 moisture sensor opt optToolsKSB ServiceTool for Windows XP opt opt
Pump Control Systems
LevelControl Control Units
12 LevelControl Basic 2
Ama-Porter with control unit type BC
Ama-Porter NE
18
19
20
21
22
23
22
24
25
26
27
15 16 17
J403
J201
J401 J601J604
1 2 3
4 5 6 7 8 9 10 11 12 13 14
2T1 4T2 6T3 14NO A2 2T1 4T2 6T3 14NO A2L3 L2 L1 N PE
bn bugn/y
e
PE PE 122
222
120
220
121
221
109
209
002001 012
013
016
017
014
015
010
011
030
031
050
051
040
041
018
019
021024 022
bn bugn/y
e
bn bu
bk bu
PE g
n/ye
bk bu
PE g
n/ye
+
-
bn bu
012
013
014
015
010
011
019
014
015
Analog IN+24V
(GND)
014
015
Analog IN+24V
PE g
n/ye
PE
gn/
ye
29
- +28
J203
Alarm
29
Circuit diagram: Ama-Porter NE
1 Contactor pump 1 16 Pump 22 Contactor pump 2 17 Power supply3 Mains connections 18 High-water float4 Moisture monitor 19 Float switches5 Thermal circuit breaker 20 Digital level switch6 Release 21 Analog sensor 4 ... 20 mA7 Volt-free alarm contact 22 Peak load ON8 Float/digital level switch 23 Pump ON/OFF9 High-water float 24 Base load ON10 mini-Compacta/Compacta sensors 25 Pump OFF11 Connection for alarm equipment 26 Signal transmitter 12 V12 External alarm input 27 Contact13 Remote acknowledgement 28 Rechargeable battery connection14 Pneumatic 29 230 V
bk (black)bu (blue)bn (brown)PE = gn/ye (green/yellow)
15 Pump 1
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 13
Ama-Porter ND 400V
18
19
20
21
22
23
22
24
25
26
27
15 16 17
J403
J201
J401 J601J604
1 2 3
4 5 6 7 8 9 10 11 12 13 14
2T1 4T2 6T3 14NO A2 2T1 4T2 6T3 14NO A2L3 L2 L1 N PE PE PE 122
222
120
220
121
221
109
209
002001 012
013
016
017
014
015
010
011
030
031
050
051
040
041
018
019
021024 022
bu bn
L1
+
-
U1
V1 W1
PE
PE
44
L2 L3 (N) PE
5 (4)
bk PE
gn/
ye
U1
V1
W1
bu bnbk
012
013
014
015
010
011
019
014
015
Analog IN+24V
(GND)
014
015
Analog IN+24V
PE
gn/
ye
30
- +28
J203
Alarm
30
Circuit diagram: Ama-Porter ND
1 Contactor pump 1 16 Pump 22 Contactor pump 2 17 Power supply3 Mains connections 18 High-water float4 Moisture monitor 19 Float switches5 Thermal circuit breaker 20 Digital level switch6 Release 21 Analog sensor 4 ... 20 mA7 Volt-free alarm contact 22 Peak load ON8 Float/digital level switch 23 Pump ON/OFF9 High-water float 24 Base load ON10 mini-Compacta/Compacta sensors 25 Pump OFF11 Connection for alarm equipment 26 Signal transmitter 12 V12 External alarm input 27 Contact13 Remote acknowledgement 28 Rechargeable battery connection14 Pneumatic 30 400 V
U1: bk (black)V1: bu (blue)W1: bn (brown)PE: gn/ye (green/yellow)
15 Pump 1
Pump Control Systems
LevelControl Control Units
14 LevelControl Basic 2
LevelControl Basic 2 for Amarex N
Non-ATEX versions
Documented device variants
Control units for s ingle-pump stat ion (without ATEX)
Float switch incl. 4 .. 20 mA input
Pneumatic Bubbler control
Variant DFNO DPNO DLNO in BS housing DLNO in BC housing400 V: 2.5 - 4.0 A BC1 400 DFNO 040 BC1 400 DPNO 040 BS1 400 DLNO 040 BC1 400 DLNO 040400 V: 4.0 - 6.3 A BC1 400 DFNO 063 BC1 400 DPNO 063 BS1 400 DLNO 063 BC1 400 DLNO 063400 V: 6.0 - 10 A BC1 400 DFNO 100 BC1 400 DPNO 100 BS1 400 DLNO 100 BC1 400 DLNO 100
Control units for dual-pump stat ion (without ATEX)
Float switch incl. 4 .. 20 mA input
Pneumatic Bubbler control
Variant DFNO DPNO DLNO in BS housing DLNO in BC housing400 V: 2.5 - 4.0 A BC2 400 DFNO 040 BC2 400 DPNO 040 BS2 400 DLNO 040 BC2 400 DLNO 040400 V: 4.0 - 6.3 A BC2 400 DFNO 063 BC2 400 DPNO 063 BS2 400 DLNO 063 BC2 400 DLNO 063400 V: 6.0 - 10 A BC2 400 DFNO 100 BC2 400 DPNO 100 BS2 400 DLNO 100 BC2 400 DLNO 100
Functional comparison
opt = optional Single-pump station Dual-pump stationVariant DFNO DPNO DLNO
(BShousing)
DLNO(BC
housing)
DFNO DPNO DLNO(BS
housing)
DLNO(BC
housing)Functions Draining x xFilling via float switch x - - - x - - -Stand-by pump: 1 pump redundant - xPump switchover after each start - xPump switchover in event of fault - xPeak load operation function - xRuntime limitation x xOFF via after-run time x xOFF via level x xOperation check run after idle period x xAlert history x xDisplay and operation7-segment display x xIndication of water level dig.3) x x x dig.3) x x x
Operation/fault/pump running Multicolour LED Multicolour LEDGeneral fault (traffic light) LED LEDHigh water LED LEDMains voltage x xOperating hours of each pump x xStarts per pump x xRotary field direction detection (mains) x xPhase monitoring x xChange of switching levels - x x x - x x x
3) Digital display of switching points
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 15
opt = optional Single-pump station Dual-pump stationVariant DFNO DPNO DLNO
(BShousing)
DLNO(BC
housing)
DFNO DPNO DLNO(BS
housing)
DLNO(BC
housing)Housing H [mm] x W [mm] x D [mm], IP 54Plastic 400 x 278 x 135 x x - x x x - xSheet steel 400 x 300 x 155 - - x - - - x -Built-in componentsMaster switch (lockable) opt opt x - opt opt x -Manual-0-automatic switch for each pump x xDOL starting x xMotor protectionMotor protection switch x xMotor temperature warning input x xMotor temperature alert input x xPumpThermal circuit breaker/bimetal x xMoisture monitor: motor leakage x xInstallation optionsRechargeable battery for powering thedevice
opt opt
Control cabinet heating for type BS - - opt - - - opt -Alarm equipment1 free alarm input x x1 digital input for high water alert x xVolt-free contact (changeover contact) x xPiezo buzzer 85 dB(A) x xHorn/alarm combination/alarm strobe light12 V DC
opt opt
Inputs/outputsInputs for float switches 4 - - - 4 - - -4 .. 20 mA analog input x - - - x - - -Pneumatic pressure sensor - x - - - x - -Bubbler control with compressor - - x x - - x xRemote acknowledgement x x12 V DC connection for horn etc. x xSensor accessoriesFloat switch (NO contact) opt - - - opt - - -Redundant high water float - opt opt opt - opt opt optOpen pressure bell (open system) - opt opt opt - opt opt optClosed pressure bell (closed system) - opt - - - opt - -F1 moisture sensor opt optToolsKSB ServiceTool for Windows XP opt opt
ATEX versions
The control units are not explosion-proof, which meansthat they must not be operated in potentially explosiveatmospheres.
Analog intrinsic safety barriers are required in ATEXversions for 4 .. 20 m (see "Installation options"). Selection viaEasySelect.
Documented device variants
Control unit for single-pump station (ATEX version)
Float switch Pneumatic Bubbler controlVariant DFEO DPEO DLEO in BS housing DLEO in BC housing400 V: 2.5 - 4.0 A BS1 400 DFEO 040 BC1 400 DPEO 040 BS1 400 DLEO 040 BC1 400 DLEO 040400 V: 4.0 - 6.3 A BS1 400 DFEO 063 BC1 400 DPEO 063 BS1 400 DLEO 063 BC1 400 DLEO 063400 V: 6.0 - 10 A BS1 400 DFEO 100 BC1 400 DPEO 100 BS1 400 DLEO 100 BC1 400 DLEO 100
Pump Control Systems
LevelControl Control Units
16 LevelControl Basic 2
Control units for dual-pump station (ATEX version)
Float switch Pneumatic Bubbler controlVariant DFEO DPEO DLEO in BS housing DLEO in BC housing400 V: 2.5 - 4.0 A BS2 400 DFEO 040 BC2 400 DPEO 040 BS2 400 DLEO 040 BC2 400 DLEO 040400 V: 4.0 - 6.3 A BS2 400 DFEO 063 BC2 400 DPEO 063 BS2 400 DLEO 063 BC2 400 DLEO 063400 V: 6.0 - 10 A BS2 400 DFEO 100 BC2 400 DPEO 100 BS2 400 DLEO 100 BC2 400 DLEO 100
Functional comparison
opt = optional Single-pump station Dual-pump stationVariant DFEO DPEO DLEO
(BShousing)
DLEO (BC
housing)
DFEO DPEO DLEO (BS
housing)
DLEO(BC
housing)FunctionsDraining x xFilling via float switch x - - - x - - -Stand-by pump: 1 pump redundant - xPump switchover after each start - xPump switchover in event of fault - xATEX mode x xPeak load operation function - xRuntime limitation x xOFF via after-run time x xOFF via level x xOperation check run after idle period x xAlert history x xDisplay and operation7-segment display x xIndication of water level dig.4) x x x dig.4) x x x
Operation/fault/pump running Multicolour LED Multicolour LEDGeneral fault (traffic light) LED LEDHigh water LED LEDMains voltage x xOperating hours of each pump x xStarts per pump x xRotary field direction detection(mains)
x x
Phase monitoring x xChange of switching levels - x x x - x x x
opt = optional Single-pump station Dual-pump stationVariant DFEO DPEO DLEO
(BShousing)
DLEO (BC
housing)
DFEO DPEO DLEO(BS
housing)
DLEO(BC
housing)Housing H [mm] x W [mm] x D [mm], IP 54Plastic 400 x 278 x 135 - x - x - x - xSheet steel 400 x 300 x 155 - - x - - - x -Sheet steel 600 x 400 x 200 x - - - x - - -Built-in componentsMaster switch (lockable) x opt x - x opt x -Manual-0-automatic switch for each pump x xDOL starting x xMotor protectionMotor protection switch per pump x xMotor temperature warning input x xMotor temperature alert input x xPump
4) Digital display of switching points
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 17
opt = optional Single-pump station Dual-pump stationVariant DFEO DPEO DLEO
(BShousing)
DLEO (BC
housing)
DFEO DPEO DLEO(BS
housing)
DLEO(BC
housing)Thermal circuit breaker/bimetal x xMoisture monitor: motor leakage x xInstallation optionsRechargeable battery for powering thedevice
opt opt
Control cabinet heating for type BS opt - opt - opt - opt -Alarm equipment1 free alarm input - non-ATEX x x
1 digital input for high water alert 5) x - x x x - x x
Volt-free contact (changeover contact) x xPiezo buzzer 85 dB(A) x xHorn/alarm combination/alarm strobe light 12V DC
opt opt
Inputs/outputsInputs for float switches 2 - - - 3 - - -Intrinsic safety barrier for float 2 - - - 3 - - -Pneumatic pressure sensor - x - - - x - -Bubbler control with compressor - - x x - - x xRemote acknowledgement x x12 V DC connection for horn etc. x xSensorsFloat switch (NO contact) opt - - - opt - - -Open pressure bell (open system) - opt opt opt - opt opt optClosed pressure bell (closed system) - opt - - - opt - -ToolsKSB ServiceTool for Windows XP opt opt
5) Additional intrinsic safety barrier required for high water float (see "Installation options")
Pump Control Systems
LevelControl Control Units
18 LevelControl Basic 2
Amarex N with control unit type BC
Amarex N
2T1 4T2 6T3 14NO A2 2T1 4T2 6T3 14NO A2
J403
L3 L2 L1 N PE PE PE
J201
122
222
120
220
121
221
109
209
002001
J401
012
013
016
017
014
015
010
011
030
031
050
051
040
041
018
019
J601
021024
J604
022
2 3
L1
PE
PE
+
-
1 2 3 2122
88
L2 L3 (N) PE
5 (4)
1
2 31
012
013
014
015
010
011
019
014
015
Analog IN+24V
(GND)
014
015
Analog IN+24V
20
2122 202122 20
PE
99
9 1 2 3 2122 20 PE9
1 2 3
4 5 6 7 8 9 10 11 12 13 14
15 16 17
18
19
20
21
22
23
22
24
25
26
27
- +28
J203
Alarm
30 30
Circuit diagram: Amarex N1 Contactor pump 1 15 Pump 12 Contactor pump 2 16 Pump 23 Mains connections 17 Power supply4 Moisture monitor 18 High-water float5 Thermal circuit breaker 19 Float switches6 Release 20 Digital level switch7 Volt-free alarm contact 21 Analog sensor 4 ... 20 mA8 Float/digital level switch 22 Peak load ON9 High-water float 23 Pump ON/OFF10 mini-Compacta/Compacta sensors 24 Base load ON11 Connection for alarm equipment 25 Pump OFF12 External alarm input 26 Signal transmitter 12 V13 Remote acknowledgement 27 Contact14 Pneumatic 28 Rechargeable battery connection
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 19
LevelControl Basic 2 for Amarex KRT
Documented device variants
Control units for s ingle-pump stat ion
Float switch incl. 4 .. 20mA input
Float switch Pneumatic Bubbler control
Variant xFNO xFEO xPEO xLEO ATEX ATEX ATEX400 V: 6.3 - 10 A BS1 400 DFNO 100 BS1 400 DFEO 100 BS1 400 DPEO 100 BS1 400 DLEO 100400 V: 9 - 14 A BS1 400 SFNO 140 BS1 400 SFEO 140 BS1 400 SPEO 140 BS1 400 SLEO 140400 V: 13 - 18 A BS1 400 SFNO 180 BS1 400 SFEO 180 BS1 400 SPEO 180 BS1 400 SLEO 180400 V: 17 - 23 A BS1 400 SFNO 230 BS1 400 SFEO 230 BS1 400 SPEO 230 BS1 400 SLEO 230400 V: 20 - 25 A BS1 400 SFNO 250 BS1 400 SFEO 250 BS1 400 SPEO 250 BS1 400 SLEO 250400 V: 25 - 40 A BS1 400 SFNO 400 BS1 400 SFEO 400 BS1 400 SPEO 400 BS1 400 SLEO 400400 V: 40 - 63 A BS1 400 SFNO 630 BS1 400 SFEO 630 BS1 400 SPEO 630 BS1 400 SLEO 630
Control units for dual-pump stat ion
Float switch incl. 4 .. 20mA input
Float switch Pneumatic Bubbler control
Variant xFNO xFEO xPEO xLEO ATEX ATEX ATEX400 V: 6.3 - 10 A BS2 400 DFNO 100 BS2 400 DFEO 100 BS2 400 DPEO 100 BS2 400 DLEO 100400 V: 9 - 14 A BS2 400 SFNO 140 BS2 400 SFEO 140 BS2 400 SPEO 140 BS2 400 SLEO 140400 V: 13 - 18 A BS2 400 SFNO 180 BS2 400 SFEO 180 BS2 400 SPEO 180 BS2 400 SLEO 180400 V: 17 - 23 A BS2 400 SFNO 230 BS2 400 SFEO 230 BS2 400 SPEO 230 BS2 400 SLEO 230400 V: 20 - 25 A BS2 400 SFNO 250 BS2 400 SFEO 250 BS2 400 SPEO 250 BS2 400 SLEO 250400 V: 25 - 40 A BS2 400 SFNO 400 BS2 400 SFEO 400 BS2 400 SPEO 400 BS2 400 SLEO 400400 V: 40 - 63 A BS2 400 SFNO 630 BS2 400 SFEO 630 BS2 400 SPEO 630 BS2 400 SLEO 630
Functional comparison
opt = optional Single-pump station Dual-pump stationVariant xFNO xFEO xPEO xLEO xFNO xFEO xPEO xLEOFunctionsDraining x xStand-by pump: 1 pump redundant - xPump switchover after each start - xPump switchover in event of fault - xATEX mode - x x x - x x xPeak load operation function - xRuntime limitation x xOFF via after-run time x xOFF via level x xOperation check run after idle period x xAlert history x xDisplay and operation7-segment display x xIndication of water level dig.6) x dig.6) x
Operation/fault/pump running Multicolour LED Multicolour LEDGeneral fault (traffic light) LED LEDHigh water LED LED
6) Digital display of switching points
Pump Control Systems
LevelControl Control Units
20 LevelControl Basic 2
opt = optional Single-pump station Dual-pump stationVariant xFNO xFEO xPEO xLEO xFNO xFEO xPEO xLEOMains voltage x xOperating hours of each pump x xStarts per pump x xDisplay and operationRotary field direction detection (mains) x xPhase monitoring x xChange of switching levels - x - xHousing H [mm] x W [mm] x D [mm], IP 54Sheet steel 400 x 300 x 155 Up to 10 A Up to 10 ASheet steel 600 x 400 x 200 14 to 25 A / up to 10 A (float, ATEX-
compliant)Up to 10 A (float, ATEX-compliant)
Sheet steel 760 x 600 x 210 40 to 63 A 14 A to 63 ABuilt-in componentsMaster switch (lockable) x xManual-0-automatic switch for each pump x xDOL starting <=10 A <=10 AStar/delta starting >10 A >10 AMotor protectionMotor protection switch per pump x xMotor temperature warning input x xMotor temperature alert input x xPumpThermal circuit breaker/bimetal x xPTC for each pump x xMoisture monitor: motor leakage x xInstallation optionsRechargeable battery for powering thedevice
opt opt
Additional intrinsic safety barrier - opt opt opt - opt opt optControl cabinet heating opt optAlarm equipment1 free alarm input x x1 digital input for high water alert 1 - x opt opt - x opt optVolt-free contact (changeover contact) x xPiezo buzzer 85 dB(A) x xHorn/alarm combination/alarm strobe light12 V DC
opt opt
Inputs/outputsInputs for float switches 4 2 - - 4 3 - -Intrinsic safety barrier for float - 2 - - - 3 - -4 .. 20 mA analog input x opt7) - - x opt7) - -
Pneumatic pressure sensor - - x - - - x -Bubbler control with compressor - - - x - - - xRemote acknowledgement x x12 V DC connection for horn, etc. x xSensorsFloat switch (NO contact) opt - opt -
Redundant high water float8) - opt - opt
Open pressure bell (open system) - opt - optClosed pressure bell (closed system) - - opt - - - opt -ToolsKSB ServiceTool for Windows XP opt opt
7) Analog intrinsic safety barriers are required in ATEX versions for 4 .. 20 m (see "Installation options"). Selection viaEasySelect.
8) Additional intrinsic safety barrier for redundant high water float in variants for pneumatic and bubbler control
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 21
Examples
Type: BC2 230 DFNO 100
1~230 V AC, DOL starting up to 10 A, float switch, 4 .. 20 mA,digital level switch for:
▪ Ama-Drainer N 301/302/303
▪ Ama-Drainer N 358
▪ Ama-Drainer NE 4.. /5.. ~230 V AC
▪ Ama-Porter NE ~230 V AC
45
32
1
11
10
6
7
89
12
1 Control panel 7 Digital inputs, 4 .. 20 mA, 12 V for horn, etc.2 Master switch (optional) 8 Volt-free contact3 Connection for pump 1 9 Mains supply4 Connection for pump 2 10 Contactors5 Manual-0-automatic switch 11 Motor protection switch (pumps)6 Control board 12 Rechargeable battery (optional)
Type: BC2 400 DFNO 010-100
3~400 V AC, DOL starting 1.6 -10 A, float switch, 4 .. 20 mA,digital level switch for:
▪ Ama-Drainer NE 4.. /5.. ~400 V AC
▪ Rotex
▪ Ama-Porter ND ~400 V AC
▪ Amarex N - non-ATEX
2
31
9
8
4
5
67
10
1 Control panel 6 Volt-free contact2 Master switch (optional) 7 Mains supply3 Manual-0-automatic switch 8 Contactors (pump connection)4 Control board 9 Motor protection switch (pumps)5 Digital inputs, 4 .. 20 mA, 12 V for horn, etc. 10 Rechargeable battery (optional)
Type: BC2 400 DFNO 010-100 / BC2 400 DPNO 010-100
3~400 V AC, DOL starting up to 10 A, pneumatic
▪ Ama-Porter ND - 400 V AC
▪ Amarex N - non-ATEX and ATEX version
▪ CK pump station
Pump Control Systems
LevelControl Control Units
22 LevelControl Basic 2
2
31
11
10
54
6
7
89
12
1 Control panel 7 Connection (open/closed pressure bell)2 Master switch (optional) 8 Volt-free contact3 Manual-0-automatic switch 9 Mains supply4 Control board 10 Contactors (pump connection)5 Internal pressure sensor 11 Motor protection switch (pumps)6 Pneumatic,12 V for horn, etc. 12 Rechargeable battery (optional)
Type: BS2 400 DLNO 010-100 / BS2 400 DLEO 010-100
3~400 V AC, DOL starting up to 10 A, bubbler control
▪ Ama-Porter ND ~ 400 V AC
▪ Amarex N - non-ATEX and ATEX version
▪ CK pump station
1
2
3
91011
65
7
8
413
12
1 Master switch 7 12 V for horn, etc.2 Control panel 8 Contactors (pump connection)3 Manual-0-automatic switch 9 Mains supply4 Control transformer 10 Compressor5 Rechargeable battery (optional) 11 Connection for open pressure bell6 Control electronics 12 Motor protection switch (control circuit) 13 Motor protection switch (pumps)
Type: BS2 400 DFEO 010-100
3~400 V AC, DOL starting 1.0 -10 A, float switch, digital levelswitch, ATEX version
▪ Amarex N/KRT - ATEX version
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 23
1
2
3
910
13
4
65
7
8
12
11
1 Master switch 7 Digital inputs, 4 .. 20 mA, 12 V for horn, etc.2 Control panel 8 Contactors (pump connection)3 Manual-0-automatic switch 9 Mains supply4 Control transformer 10 Connection (float switch, digital level switch) via
intrinsic safety barriers5 Rechargeable battery (optional) 11 Motor protection switch (control circuit)6 Control electronics 12 Motor protection switch (pumps) 13 Intrinsic safety barrier
Pump Control Systems
LevelControl Control Units
24 LevelControl Basic 2
Overview of Outdoor Cabinets
Enclosure IP44, protection against splashing water.Ventilation ducts prevent condensation.The ventilation ducts are designed as a labyrinth to preventthe ingress of foreign bodies and are poke proof.
To prevent condensation inside the housing, grout thefoundation up to the height of the cable fixing rail afterinstallation.
BC1... 010/016/025/040/063/100
BC2...010/016/025/040/063/100
BS1...010/016/025/040/063/100/140/180/230/250
BS2...010/016/025/040/063/100
BS1... 400/630
BS2... 140/180/230/250/400/630
BC1... 010/016/025/040/063/100
BC2... 010/016/025/040/063/100
Plastic housing, IP54
400 x 278 x 135 mm
Sheet steel housing, IP54
400 x 300 x 155 mm
600 x 400 x 200 mm
Sheet steel housing, IP54
760 x 600 x 210 mm
Plastic housing, IP54
400 x 278 x 135 mm
Item O 10 Item O 11 Item O 12 Item O 14Outdoor cabinet type 142, IP44 Outdoor cabinet type 0/845,
IP44Outdoor cabinet type 1/1005,IP44
Wall-mounted cabinet KS
Can be buried Can be buried Can be buried Wall-mounted
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 25
Installation Options
LevelControl Basic 2 installation options (processed via KSB EasySelect)9)
Item Description Mat. No. [kg]O 1 Master switch for LevelControl Basic 2, installed for type BC... 01143084 0,2O 2 Control cabinet heating, installed for type BS... 19074269 0,3O 7 Intrinsic safety barrier for additional float in potentially explosive
atmospheresFor example, high water float for pneumatic or bubbler control inpotentially explosive atmospheresOnly in conjunction with type BS...: Stahl 9002/13-280-093-001
01085568 0,2
O 9 Intrinsic safety barrier for 4...20 mA in potentially explosive atmospheresOnly in conjunction with type BS...: Stahl 9002/13-280-110-001
01110746 0,1
O 10 Outdoor cabinet type 142 with integrated base for control unit BC 19071911 15O 11 Outdoor cabinet type 0/845 for control units BS1 (up to 25 A) and BS2 (up
to 10 A)Prepared for control unitControl unit housings: 400 x 300 x 155 mm and 600 x 400 x 200 mmDimensions H x W x D [mm]: 1745 x 585 x 315Dimensions of upper section H x W x D [mm]: external 845 x 585 x 315Dimensions of base H x W x D [mm]: external 900 x 585 x 315IP 44, glass fibre reinforced polyester, colour: RAL 7035, DIN 43 629,locking device: profile half cylinder, can be buried, incl. metal frame forsetting in concrete
19071440 40
O 12Outdoor cabinet type 1/1005 for control units BS1 (40 A and above) andBS2 (14 A and above)Dimensions of control unit housing H x W x D [mm]: 760 x 600 x 210Prepared for control unitDimensions of upper section H x W x D [mm]: external 1005 x 780 x 315Dimensions of base H x W x D [mm]: external 900 x 780 x 315IP 44, glass fibre reinforced polyester, colour: RAL 7035, locking device:profile half cylinder, can be buried, incl. metal frame for setting inconcrete
19071960 57
O 14 Plastic wall-mounted cabinet for type BCAdditional housing for LevelControl Basic 2 type BC single-pump and dual-pump station up to 10 AEnclosure: IP66Wall mountingLock: double-bit keyColour: RAL 7035Dimensions (H mm x W mm x D mm): external 600 x 400 x 200Material: Impact-resistant, glass fibre reinforced, unsaturated polyester,self-extinguishing to ASTM D635 and UL 94 VO, temperature-resistantbetween -30 ℃ and + 80 ℃Safety cylinder (see accessories)
01146647 11,5
O 15 Outdoor housing for type BS with housingDimensions (H x W x D): 1200 x 800 x 300 mmComplete with base and rain canopyPrepared for control unitUsed as control cabinet extension (to accommodate installation options)Material: V2A, brushed, RA240Dimensions: 1400 x 900 x 500 mmIP44, colour: bright metal, locking device: profile half cylinder, buriablebase
01351206 123,5
9) Installation options must be processed via KSB EasySelect, otherwise they will be supplied with the unit but not fitted.
Pump Control Systems
LevelControl Control Units
26 LevelControl Basic 2
Item Description Mat. No. [kg] Signalling module for LevelControl Basic 2
Individual fault signalling and IO extension module for LevelControl Basic2
▪ Six volt-free signalling relays (max. 30VDC, 1A) for signalling
– High water
– Fault pump 1
– Fault pump 2
– Plus three other user-definable individual (fault) messages, e.g.for "Pump 1 operational", "Pump 2 operational", "Externalfault", "Sensor fault", etc.
– Analog output 0/4..20mA
– Additional pressure sensor for redundant pneumaticmeasurement or redundant bubbler system (as retrofit kit,complete with necessary tubing and installation materials),depending on version.
– Mod Bus interface for hook-up to the process control system
– Can be used with Firmware 1.2 or higher
O 200 Signalling module for LevelControl Basic 2, type BC 19075182 0,2O 201 Signalling module for type BC
With pressure sensor 3 mlc for redundant pneumatic level measurement orredundant bubbler system
19075183 1,1
O 202 Signalling module for type BCWith pressure sensor 10 mlc for redundant pneumatic level measurement
19075184 1,4
O 203 Signalling module for LevelControl Basic 2, type BS 19075185 1,1O 204 Signalling module for type BS...
With pressure sensor 3 mlc for redundant pneumatic level measurement orredundant bubbler system
19075186 0,8
O 205 Signalling module for type BS...With pressure sensor 10 mlc for redundant pneumatic level measurement
19075187 0,8
Current measurement for LevelControl Basic 2 for measuring pumpcurrent
Connection via signalling module only (see O 200 to O 205)
Effective current, effective power and power factor displayed per pump
Operating current measured directly up to 10A; higher pump currentsmeasured indirectly via primary transformer in the control cabinet
The current measuring module cannot be retrofitted but must be includedat the factory.
One current measuring module per pump is required for dual-pumpapplications.
O 210 Pump current measuring moduleMeasuring range: 0.5 - 10 A (15 A)
19075188 0,15
O 211 Pump current measuring moduleMeasuring range: 10 - 20 A (30 A)
19075189 0,15
O 212 Pump current measuring moduleMeasuring range: 20 - 40 A (60 A)
19075190 0,15
O 213 Pump current measuring moduleMeasuring range: 40 - 75 A (110 A)
19075191 0,15
Accessories
Item Description Mat. No. [kg]E 60 Float switch with free cable end (NO contact)
Switch housing made of polypropylene (max. fluid temperature 70 °C),circuit closed in upper float position, connection cable (H 07 RN-F3G1)
3 m 11037742 0,55 m 11037743 0,810 m 11037744 1,315 m 11037745 1,820 m 11037746 2,425 m 11037747 2,930 m 11037748 3,4
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 27
Item Description Mat. No. [kg]E 61 Float switch with free cable end, oil resistant (NO contact)
Circuit closed in upper float position (PUR 3 x 1)5 m 11037753 0,810 m 11037754 1,220 m 11037755 2
E 63 Float switch with free cable end (NO contact)With declaration of compliance with explosion protection standardsCircuit closed in upper float position
5 m 01148226 0,710 m 01148247 120 m 01148248 2
E 64 Moisture sensor F 13 mAs contactor for alarm switchgear AS 0, AS 2 or AS 4, or LevelControl,max. 40 °C, not suitable for steam and condensate, with 3-metreconnection cable. Possible applications for alarm transmission:- High-water alert by suspending the moisture sensor in a (pump) sumpabove the pump start-up level.- Water alarm signal at a water level of only 1 mm (!), by placing thecontactor on the floor of rooms subject to a flooding risk, e.g. thecellar or next to the washing machine in the kitchen orbathroom.Dimensions: (H mm x W mm x D mm) 52 x 21 x 20
3 m 19072366 0,2
E 65 Open pressure bell set - pneumatic and bubblercontrolwith polyamide tube 8 x 1
Tube length 10 m 19071721 1,2Tube length 20 m 19071837 2Tube length 50 m 19074200 2,5
E 66 Closed pressure bell set - pneumaticwith polyamide tube 8 x 3
Tube length 10 m 19071722 3,5
Tube length > 10 m
On request
E 70 Horn, 12 V DC, 105 dB(A), 1.2 W54For indoor and outdoor installation, to be mounted in a positionwhere it is protected from direct rain, enclosure IP 54
01086547
0,1
E 71 Alarm combination, 12 V DVIP 65
01139930 0,1
E 72 Alarm strobe light, 12 V DC 01056355 0,3E 73 PC service tool
Windows XP, RS 232 interface 47121210 0,2
E 90 Rechargeable battery retrofit kit forLevelControl Basic 2, for powering theelectronics, the float switches or internalpressure sensor and the alarm equipment(buzzer, horn, alarm combination), for single-pump and dual-pump stations
For type BC,consisting of 2rechargeablebatteries 6 V, 1,3 Ahand charging unit
19074194 0,8
E 91 For type BS,consisting of 1rechargeable battery12 V, 1.2 Ah andcharging unit
19074199 1
E 95 Plastic handle with safety cylinder insert for KSwall-mounted cabinetImportant: Please order 2 off for KS cabinet!
01087727 0,1
E 100 LevelControl Basic 2 Operating manual inGerman
01148254
Operating manual inEnglish
01148255
Operating manual inFrench
01148256
Operating manual inDutch
01148337
Operating manual inSpanish
01148338
Operating manual inSwedish
01148339
Operating manual inFinnish
01148340
Operating manual inPolish
01148341
Operating manual inItalian
01148342
Operating manual inCzech
01148343
Pump Control Systems
LevelControl Control Units
28 LevelControl Basic 2
Item Description Mat. No. [kg]Operating manual inRussian
01149725
Operating manual inHungarian
01148344
Operating manual inTurkish
01235989
Operating manual inBulgarian
01350442
Operating manual inSlovakian
01350443
The operating manuals can be downloaded free of charge from the KSB web site (www.ksb.com).Incl. parameter label. For ordering additional copies only! The operating manual and the parameter label are enclosed with thedevice.
Pump Control Systems
LevelControl Control Units
LevelControl Basic 2 29