4050 Ver4.00-EN.fm/2 Schneider Electric Application example Note : auxiliary contact blocks and modules : see pages 24013/2 to 24013/11. For LC1 or LP1-D09 to D32 : clip-on mounting on 35 mm 6 rail AM1-DP. For LC1 or LP1-D40 to D95 : clip-on mounting on 35 or 75 mm 6 rail AM1-DL. Power terminals : LC1 or LP1-D09 to D95 protected against direct finger contact and ready-to-tighten terminals. Standard power ratings Taille Asso- Continuous Type of contactor required of motors 50/60 Hz Size ciated current (Basic reference. Single-phase 3-phase cable Complete with code indicating 1 Ø 3 Ø Type control circuit voltage) 115 V 230 V 200 V 230 V 460 V 575 V 75 °C-Cu 240 V 208 V 240 V 480 V 600 V HP HP HP HP HP HP A 0.5 1 2 2 5 7.5 00 AWG10 20 LC1, LP1-D09 1 2 3 3 7.5 10 0 AWG10 25 LC1, LP1-D12 1 3 5 5 10 15 0 AWG8 32 LC1, LP1-D18 2 3 5 7.5 15 20 1 AWG8 40 LC1, LP1-D25 2 5 7.5 10 20 30 1 AWG6 50 LC1, LP1-D32 3 5 10 10 30 30 2 AWG3 60 LC1, LP1-D40 7.5 7.5 15 15 40 40 2 AWG3 70 LC1, LP1-D50 7.5 10 20 20 50 50 2 AWG3 80 LC1, LP1-D65 7.5 15 20 25 60 60 2 AWG2 110 LC1, LP1-D80 7.5 15 20 25 60 60 2 AWG2 120 LC1-D95 For 15 HP-230 V motor Select a contactor type LC1-D50 or LP1-D50. Information : the contactor rating selected corresponds to size 2, the associated cable is type AWG3 75 °C-Cu. Sélection Contactors Contactors for the North American market conforming to standards UL and CSA, 20 to 120 A LC1-D0901pp pp LC1-D2510pp pp Selection guide : pages 24003/2 to 24007/3 Characteristics : pages 24008/2 to 24008/9 Dimensions, schemes : pages 24014/2 to 24014/7 LC1-D9511pp pp

Upload: francisco-mozart-b-meirelles

Post on 20-Nov-2015

4 views

Category:

Documents


2 download

TRANSCRIPT

  • 4050 Ver4.00-EN.fm/2 Schneider Electric

    Application example

    Note : auxiliary contact blocks and modules : see pages 24013/2 to 24013/11.For LC1 or LP1-D09 to D32 : clip-on mounting on 35 mm 6 rail AM1-DP.For LC1 or LP1-D40 to D95 : clip-on mounting on 35 or 75 mm 6 rail AM1-DL.Power terminals : LC1 or LP1-D09 to D95 protected against direct finger contact and ready-to-tighten terminals.

    Standard power ratings Taille Asso- Continuous Type of contactor requiredof motors 50/60 Hz Size ciated current (Basic reference.Single-phase 3-phase cable Complete with code indicating1 3 Type control circuit voltage)115 V 230 V 200 V 230 V 460 V 575 V 75 C-Cu

    240 V 208 V 240 V 480 V 600 VHP HP HP HP HP HP A

    0.5 1 2 2 5 7.5 00 AWG10 20 LC1, LP1-D09

    1 2 3 3 7.5 10 0 AWG10 25 LC1, LP1-D12

    1 3 5 5 10 15 0 AWG8 32 LC1, LP1-D18

    2 3 5 7.5 15 20 1 AWG8 40 LC1, LP1-D25

    2 5 7.5 10 20 30 1 AWG6 50 LC1, LP1-D32

    3 5 10 10 30 30 2 AWG3 60 LC1, LP1-D40

    7.5 7.5 15 15 40 40 2 AWG3 70 LC1, LP1-D50

    7.5 10 20 20 50 50 2 AWG3 80 LC1, LP1-D65

    7.5 15 20 25 60 60 2 AWG2 110 LC1, LP1-D80

    7.5 15 20 25 60 60 2 AWG2 120 LC1-D95

    For 15 HP-230 V motor Select a contactor type LC1-D50 or LP1-D50.Information : the contactor rating selected corresponds to size 2, the associated cable is type AWG3 75 C-Cu.

    Slection ContactorsContactors for the North American marketconforming to standards UL and CSA, 20 to 120 A

    LC1-D0901pppp

    LC1-D2510pppp

    Selection guide :pages 24003/2 to 24007/3

    Characteristics :pages 24008/2 to 24008/9

    Dimensions, schemes :pages 24014/2 to 24014/7

    LC1-D9511pppp

  • 24050 Ver4.00-EN.fm/Schneider Electric

    Application example

    (1) Auxiliary contact blocks and modules : see pages 25010/2 to 25010/7.Power terminals can be protected by the addition of shrouds, to be ordered separately. See page 25010/6.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).

    LC1-F185 and F225

    LC1-F265F780

    (3) For contactors LC1-F265 to F630 .(4) F7 for LC1-F630 and F780.(5) For contactors LC1-F185 to LC1-F330.(6) For contactors LC1-F265 to F630.

    Standard power ratings Taille Associated Continuous Type of contactor requiredof motors 50/60 Hz Size cable current (Basic reference.3-phase Type at 600 V max. Complete with code indicating3 75 C-Cu at control circuit voltage)200 V 230 V 460 V 575 V I continuous (1), (2)208 V 240 V 480 V 600 VHP HP HP HP A

    50 60 125 150 4 AWG 3/0 200 LC1-F185 pppp

    60 75 150 150 4 300 MCM 250 LC1-F225 pppp

    60 75 150 200 4 300 MCM 285 LC1-F265 pppp

    75 100 200 250 5 600 MCM 370 LC1-F330 pppp

    100 125 250 300 5 600 MCM 420 LC1-F400 pppp

    150 200 400 500 6 2 x 500 MCM 700 LC1-F500 pppp

    250 300 600 800 7 3 x 400 MCM 1000 LC1-F630 pppp

    400 900 8 3 x 600 MCM 1000 LC1-F800 pppp

    450 900 8 2 x 3 x 600 MCM 1350 LC1-F780 pppp

    For a 60 HP-230 V motor Select a contactor type LC1-F185.Information : the contactor rating selected corresponds to size 4, the associated cable is type AWG 3/0 75 C-Cu.

    Volts a 24 48 110 120 208 220 240 380 415 440

    50 Hz (coil LX1) B5 E5 F5 M5 U5 Q5 N5 60 Hz (coil LX1) E6 F6 G6 L6 M6 U6 Q6 R640400 Hz (coil LX9) E7 F7 G7 L7 M7 U7 Q7 N7 R7

    Volts a 48 110 120 208 220 240 380 415

    40400 Hz (coil LX1) E7 (3) F7 G7 (4) L7 M7 U7 Q7 N7

    Volts c 24 48 110 125 220 250 440LC1-F185F780 BD (5) ED (6) FD GD MD UD RD

    Contactors Contactors for the North American marketconforming to standards UL and CSA, 175 to 1000 A

    References

    Selection guide :pages 24003/2 to 24007/3

    Characteristics :pages 25007/2 to 25007/7

    Dimensions, schemes :pages 25011/2 to 25011/7

    LC1-F630