lamtec flame monitoring

16
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG LAMTEC LAMTEC Flame Monitoring Flame Monitoring Flame monitoring device F152 1 Flame scanner FFS07 (Ex) Flame scanner FFS08

Upload: others

Post on 09-Dec-2021

6 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

LAMTECLAMTEC

Flame MonitoringFlame Monitoring

Flame monitoring device F152

1

Flame scanner FFS07 (Ex) Flame scanner FFS08

Page 2: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

LAMTEC Flame monitoring

Standards and Directives (under approval):

• DIN EN 298:2012

• DIN EN 230:2005

• DIN EN 60730-2-5:2011

• DIN EN 50156:2005, section 10.5

• DIN EN 746-2:2011 (Safety requirements for industrial thermoprocessing equipment)

• 97/23/EG (Pressure equipment directive)

• 2009/142/EG (Gas equipment directive)

• 2006/95/EG (Low voltage directive)

• 2004/108/EG (EMV-directive)

• DIN EN 61508:2011 Ed.2 Teil 2 (Requirements SIL 2)

• DIN EN 60730-1:2012

• DIN EN 60079-0:2012, -15:2011 (Explosive protection)

2

Page 3: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Characteristics

› Plug-in module for DIN rail mounting

› Two- electronic channel system with self-monitoring for fail safe operation and supervision

› Suppression of strange light sources such as lamps, power frequency radiation sources or direct light, such as solar radiation

› Digital flame frequency evaluation in the range 10 to 200 Hz

› Status display by LED's

› Measuring output for intensity 0-20 mA

› UV and IR flame detectors of series FFS07 ... and FFS08...

3

Page 4: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Areas of application / Selection criteria

Selection criteria for flame scanners

Sensor type Spectral range Application / fuel

FFS07 / 08 UV-1 260 ... 400 nm Oil, Gas

FFS07 / 08 UV-4 215 ... 360 nm Oil, Gas, (Specialty gases such as refinery and blast furnace gases)

FFS07 / 08 IR-1 1000 ... 2500 nm Oil, gas, firing with strong flue gas recirculation,

yellow colored waste gases without UV- radiation

4

Areas of application• Monitoring of burner flames without complicate selection tasks

• Single and multi-fuel burners in heating stations and process industry

Page 5: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Indicators / Dimensions - F152

5

LED YE –Flammenintensität 100%

LED RT – Flame OFF

LED GN – Flame ON

LED YE – Flame intensity

LED YE – Flame intensity 100%

Page 6: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Dimensions Flame Scanner FFS07

6

Flame scanner FFS07

Flame scanner FFS07 Ex

Page 7: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Dimensions Flame Scanner FFS08

7

Flame scanner FFS08

Page 8: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Sensitivity adjustments for scanner FFS07

8

X 3 X 5 X 6 X 4 X 2 X1

S1

S2

X9 X10

OFF ON OFF ON

M10

C13

V14

R25

V13

V11

V12

V15

S1S2

100%

75%

50%

25%21

ON

21

ON

21

ON

21

ON

21

ON

21

ON

21

ON

21

ON

Sensitivity

Factory adjustment for UV

Factory adjustment for IR

The adjustment is made to the switches S1 and S2, accessible after opening of the sensor housing

Measurable sensor signals:

• IR-scanner >10mV AC

• UV-scanner >25mV AC

Page 9: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Sensitivity adjustments for scanner FFS08

9

S1S2

21

ON

21

ON

21

ON

21

ON

21

ON

21

ON

21

ON

21

ON

S1

S2

On

On

RA20 RA21

RB20

RB21

1

2

1

2

X1 X6 X3

min.

Sensitivity

min.

max.

The adjustment is made to the switches S1 and S2, accessible after opening of the sensor housing.

NOTICE!

The FFS08 UV scanners don’t have this sensitivity adjustment. The optimization is

carried out only with the optimum focus to the flame. For optimization is to be used

the measurable voltage output signal at a measuring instrument.

Measurable sensor signals:

• IR-scanner >10mV AC

• UV-scanner >25mV AC

Factory adjustment for IR50%

Page 10: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Wiring Diagram

10

F152

FFS07 / 08

X15/2

X15/1 PK

X16/1 BK

X16/2 GN

X16/3 BU

X16/4 RD

X15/4 WH

X15/3 YE

- X14/3

X11/4

X11/2, 3

X11/1

+ X14/4

flame signal

status signal

0..20mA

N X12/2

L X12/4

power

X141 4

X151 4

X161 4

X11 4 1

X12 4 1

F152

Page 11: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Ordering information for flame monitoring device F152

11

Type Product Order-no.

F152 Flame monitoring device 659G0501

Page 12: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Ordering informations for flame scanner FFS07 (IR)

12

Type Spectral range Choice

FFS07 IR-1IR-spectral range 1.000 – 2.500 nm

3m cable without plug659D21-10 0 3 0

3m cable with plug 659D21-10 0 3 Ste

FFS07 IR-1 Ex 3m cable without plug 659D22-10 0 3 0

Holding devices acc. to product overview, publication DLT7660-12-bDE-002

Connection-/extension cable, length 3 m 1) 659 R 3112

Connection-/extension cable, length 5 m 1) 659 R 3115

Connection-/extension cable, length 10 m 1) 659 R 31141) Only for scanner variants FFS07 and FFS08 with plug

Page 13: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Ordering informations for flame scanner FFS07 (UV)

13

Type Spectral range Choice

FFS07 UV-1UV-spectral range 260 – 400 nm

3m cable without plug659D21-01 0 3 0

3m cable with plug 659D21-01 0 3 Ste

FFS07 UV-1 Ex 3m cable without plug 659D22-01 0 3 0

FFS07 UV-4UV-spectral range 215 – 360 nm

3m cable with plug659D21-04 0 3 0

3m cable with plug 659D21-04 0 3 Ste

FFS07 UV-4 Ex 3m cable without plug 659D22-04 0 3 0

Holding devices acc. to product overview, publication DLT7660-12-bDE-002

Connection-/extension cable, length 3 m 1) 659 R 3112

Connection-/extension cable, length 5 m 1) 659 R 3115

Connection-/extension cable, length 10 m 1) 659 R 31141) Only for scanner variants FFS07 and FFS08 with plug

Page 14: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Ordering informations for flame scanner FFS08

14

659D31-04 0 2 0UV-spectral range 215 – 360 nm

2m cable without plugFFS08 UV-4

659D31-04 0 2 Ste2m cable with plug

659D31-01 0 2 0UV-spectral range 260 – 400 nm

2m cable without plugFFS08 UV-1

659D31-01 0 2 Ste2m cable with plug

Type Spectral range Choice

FFS08 IR-1IR-spectral range 1.000 – 2.500 nm

2m cable without plug659D31-10 0 2 0

2m cable with plug 659D31-10 0 2 Ste

Holding devices acc. to product overview, publication DLT7660-12-bDE-002

Connection-/extension cable, length 3 m 1) 659 R 3112

Connection-/extension cable, length 5 m 1) 659 R 3115

Connection-/extension cable, length 10 m 1) 659 R 3114

1) Only for scanner variants FFS07 and FFS08 with plug

Page 15: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Thank you for your attention

Questions?

15

Page 16: LAMTEC Flame Monitoring

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

Contact:

Bernd Hampel

Tel./Phone: +49 (0) 34298 / 4875-14

Fax: +49 (0) 34298 / 4875-99

E-Mail: [email protected]

16