BAB 1. KONSEP DASAR
1.1 Daya Listrik pada Rangkaian 1
Fasa
1.2 Rangkaian Tiga Fasa
1.3 Daya Listrik pada Rangkaian 3
Fasa
![Page 3: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/3.jpg)
BAB 1. 1
Daya Listrik pada Rangkaian 1 Fasa
Real (Active) and Reactive Power
Real (Active) and Reactive Loads
Power Triangle
Real (Active) and Reactive Power Flow
![Page 4: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/4.jpg)
Sine Wave Basics (Review) RMS – a method for computing the effective value of a time-varying e-m
wave, equivalent to the energy under the area of the voltage waveform.
![Page 5: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/5.jpg)
Real, Reactive and Apparent
Power in AC Circuits in DC circuits: P=VI but…= in AC circuits: average
power supplied to the load will be affected by the phase angle between the voltage and the current.
If load is inductive the phase angle (also called impedance angle) is positive; (i.e, phase angle of current will lag the phase angle of the voltage) and the load will consume both real and positive reactive power
If the load is capacitive the impedance angle will be negative (the phase angle of the current will lead the phase angle of the voltage) and the load will consume real power and supply reactive power.
![Page 6: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/6.jpg)
Resistive and Reactive Loads
![Page 7: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/7.jpg)
Impedance Angle, Current Angle
& Power
Inductive loads positive impedance angle current angle lags voltage angle
Capacitive loads negative impedance angle current angle leads voltage angle
Both types of loads consume real power
One (inductive) consumes reactive as well while the other (capacitive) supplies reactive power
![Page 8: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/8.jpg)
Tegangan, Arus dan Daya
First term is average or Real power (P)
Second term is power transferred back and forth
between source and load (Reactive power Q)
![Page 9: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/9.jpg)
More equations
Real term averages to P = VI cos (+)
Reactive term Q = VI sin (+ for inductive load,
- for capacitive load)
Reactive power is the power that is first stored and then released
in the magnetic field of an inductor or in the electric field of a capacitor
Apparent Power (S) is just = VI
![Page 10: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/10.jpg)
Tegangan, Arus dan Daya sbg Fungsi Waktu
![Page 11: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/11.jpg)
Tegangan, Arus (sefasa) dan Daya sbg Fungsi
Waktu
![Page 12: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/12.jpg)
Tegangan, Arus (lag 90°) dan Daya sbg Fungsi
Waktu
![Page 13: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/13.jpg)
Loads with Constant Impedance
V = IZ
Substituting…
P = I2Z cos
Q = I2Z sin
S= I2Z
Since… Z = R + jX = Z cos + jZ sin
P = I2R and Q = I2X
![Page 14: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/14.jpg)
Review V, I, Z
If load is inductive then the Phase Angle
(Impedance Angle Z) is positive, If phase
angle is positive, the phase angle of the current
flowing through the load will lag the voltage
phase angle across the load by the impedance
angle Z.
![Page 15: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/15.jpg)
Complex Power
S = P + jQ
S = VI cos + j VI sin
S = VI (cos + j sin)
S = VI ej
S = VI
I = I- dan V = V0o)
S = VI* Since S=√(P2 + Q2)
Rangk. Induktif
I-
V0°
S
PCos
![Page 16: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/16.jpg)
Complex Power and Key
Relationship of Phase Angle to V&I
S = P + jQ
S = VI* (complex conjugate operator)
If V = V30o and I = I15o
THEN….. COMPLEX POWER SUPPLIED TO
LOAD = S = (V30o)(I-15o) = VI (30o-15o )
= VI cos(15o ) + jVI sin(15o )
NOTE: Since Phase Angle = v - i
S = VI cos() + jVI sin() = P + jQ
![Page 17: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/17.jpg)
The Power Triangle
![Page 18: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/18.jpg)
Aliran Daya Aktif
0VV
BILA SEPHASE DENGAN , BERARTI
DAYA LISTRIK DIBANGKITKAN (SUMBER
ADALAH GENERATOR) DAN MENGALIR MENUJU
SISTEM (ARUS KELUAR DARI TERMINAL
POSITIP)
P = Re (VI*) MEMPUNYAI TANDA POSITIP.
II
cosI
V
I
cosI V
![Page 19: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/19.jpg)
Aliran Daya Aktif II
BILA MEMPUNYAI BEDA PHASE 180°
TERHADAP , BERARTI DAYA LISTRIK DISERAP
(SUMBER ADALAH MOTOR), DAN ARUS MENUJU
TERMINAL POSITIP DARI SUMBER.
P = Re (VI*) MEMPUNYAI TANDA NEGATIP.
0VV
cosIV
I
cosI
V
![Page 20: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/20.jpg)
Aliran Daya Reaktif
0VV
DAYA REAKTIF SEBESAR I2 XL (DENGAN
TANDA POSITIP) DIBERIKAN PADA INDUKTANSI
ATAU INDUKTANSI MENYERAP DAYA REAKTIF.
ARUS TERBELAKANG (LAGGING) 90°
TERHADAP
Q = Im (VI*) MEMPUNYAI TANDA POSITIF
90II
V
I90
LX
VI
![Page 21: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/21.jpg)
Aliran Daya Reaktif
II
DAYA REAKTIF SEBESAR I2 XC (DENGAN TANDA
NEGATIF) DIBERIKAN PADA KAPASITOR ATAU
SUMBER MENERIMA DAYA REAKTIF DARI
KAPASITOR.
ARUS MENDAHULUI (LEADING) 90° TERHADAP
Q = Im (VI*) MEMPUNYAI TANDA NEGATIF.
0VV V
I90
I V
![Page 22: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/22.jpg)
Contoh soal 1
V = 1200o V
Z = 20-30o
Calculate current I, Power Factor (is it leading or
lagging), real, reactive, apparent and complex
power supplied to the load
![Page 23: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/23.jpg)
BAB 1.2
Rangkaian Tiga Fasa (3-)
What are they?
Benefits of 3- Systems
Wye (Y) and delta () connections
One line diagram (of a balanced 3 phase
system)
![Page 24: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/24.jpg)
What does Three-Phase mean?
A 3- circuit is a 3- AC-generation system
serving a 3- AC load
3 - 1- AC generators with equal voltage but
phase angle differing from the others by 120o
![Page 25: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/25.jpg)
![Page 26: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/26.jpg)
Balanced 3 phase systems
SISTEM TEGANGAN TIGA FASA YANG
SEIMBANG TERDIRI DARI TEGANGAN SATU
FASA YANG MEMPUNYAI MAGNITUDE DAN
FREKWENSI YANG SAMA TETAPI ANTARA
SATU DENGAN LAINNYA MEMPUNYAI BEDA
FASA SEBESAR 120°.
![Page 27: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/27.jpg)
Tegangan & Arus 3 Fasa
Balanced
Same amplitude
120° phase diff.
Phase shift
ia lags ua angle j
Phase sequence
abc
![Page 28: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/28.jpg)
Fasor Tegangan/Arus
Urutan Fasa abc
Seimbang: Ia+ Ib+ Ic=0
No return current
Losses reduced
No return conductor
a
b
c
![Page 29: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/29.jpg)
Benefits of 3- circuits
GENERATION SIDE:
More power out
Constant power out (vs. pulsating sinusoidal)
………
LOAD SIDE:
Induction Motors (no starters required)
![Page 30: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/30.jpg)
Common Neutral
A 3- circuit can have the negative ends of the
3- generators connected to the negative ends
of the 3- AC loads and one common neutral
wire can complete the system
If the three loads are equal (or balanced) what
will the return current be in the common neutral?
![Page 31: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/31.jpg)
If loads are equal….
the return current can be calculated to be…
ZERO!
Neutral is actually unnecessary in a balanced
three-phase system (but is provided since
circumstances may change)
![Page 32: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/32.jpg)
Wye (Y) and delta () connection
![Page 33: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/33.jpg)
Delta ()
![Page 34: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/34.jpg)
Hubungan Y
n : TITIK NETRAL
Vab=Vbc=Vca = VL : TEGANGAN ANTAR
FASA
Van=Vbn=Vcn = Vp : TEGANGAN FASA
![Page 35: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/35.jpg)
Hubungan Arus dan Tegangan
Bila IL adalah Arus Saluran dan Ip adalah Arus
Fasa, maka berlaku :
IL = Ip
VL = √3 Vp
Dimana VL, Vp, IL , Ip adalah harga efektif dari
tegangan dan arus
![Page 36: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/36.jpg)
Diagram Fasor (Hub. Y)
Sumber = Beban
Vab
30o
opcn 120VV
opan 0VV
o
pbn VV 120
![Page 37: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/37.jpg)
Hubungan ∆
TITIK NETRAL tidak ada
Iab=Ibc=Ica = Ip : ARUS FASA
Ia=Ib=Ic = IL : ARUS SALURAN
![Page 38: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/38.jpg)
Hubungan Arus dan Tegangan
Bila VL adalah Tegangan Antar Fasa dan Vp
adalah Tegangan Fasa, maka berlaku :
VL = Vp
IL = √3 Ip
Dimana VL, Vp, IL , Ip adalah harga efektif
dari tegangan dan arus
![Page 39: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/39.jpg)
Diagram Fasor (Hub. ∆)
o
pbc II 120
o
pca II 120
Sumber ≠ Beban
o
pab II 0
bI
o30
o
pbc II 120
o
pca II 120
o
pab II 0
aI
o30
![Page 40: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/40.jpg)
One-Line Diagram (of a BALANCED 3 PHASE SYSTEM)
since all phases are the same (except for phase
angle) and loads are typically balanced only one
of the phases is usually shown on an electrical
diagram… it is called a one-line diagram
Typically include all major components of the
system (generators, transformers, transmission
lines, loads, other [regulators, swithes])
![Page 41: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/41.jpg)
Daya pada Rangkaian 3 Fasa
=uiR
=uiL
![Page 42: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/42.jpg)
Daya 3 Fasa
![Page 43: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/43.jpg)
Daya 3 Fasa
ptotal(t)= pa(t)+ pb(t)+ pc(t)
Daya 3 fasa = Jumlah Daya tiap-tiap Fasa
ptotal(t)=constant
If voltages and currents balanced
cosj need not be zero
Constant ptotal(t) => constant torque
![Page 44: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/44.jpg)
ppp
ppp
SinIVQ
CosIVP
j
j
j
j
3
3
3
3
LpL
p IIV
V ; 3
3 ; L
pLp
IIVV
Untuk Sistem 3 fasa seimbang
φp adalah sudut antara
Arus Fasa (Lagging) dan
Tegangan Fasa
Hubungan Y
Hubungan ∆
![Page 45: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/45.jpg)
Rumus Daya 3 Fasa
pLL
pLL
SinIVQ
CosIVP
j
j
j
j
3
3
3
3
LLIV
QPS
3
22
Watt
Var
VA
![Page 46: Konsep Dasar.pdf](https://reader033.vdocuments.site/reader033/viewer/2022050805/55cf999c550346d0339e457b/html5/thumbnails/46.jpg)
TUGAS
PELAJARI CONTOH SOAL (HAND OUT)