  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    1/61

    ITS1000M (Mini-shelter)V100R003C02

    Product Description

    Issue 03

    Date 2013-06-19

    HUAWEI TECHNOLOGIES CO., LTD.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    2/61

    Issue 03 (2013-06-19)Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.i

    Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved.

    No part of this document may be reproduced or transmitted in any form or by any means without prior

    written consent of Huawei Technologies Co., Ltd.

    Trademarks and Permissions

    and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

    All other trademarks and trade names mentioned in this document are the property of their respective

    holders.

    Notice

    The purchased products, services and features are stipulated by the contract made between Huawei and

    the customer. All or part of the products, services and features described in this document may not be

    within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,

    information, and recommendations in this document are provided "AS IS" without warranties, guarantees orrepresentations of any kind, either express or implied.

    The information in this document is subject to change without notice. Every effort has been made in the

    preparation of this document to ensure accuracy of the contents, but all statements, information, and

    recommendations in this document do not constitute the warranty of any kind, express or implied.

    Huawei Technologies Co., Ltd.

    Address: Huawei Industrial Base

    Bantian, Longgang

    Shenzhen 518129

    People's Republic of China

    Website: http://www.huawei.com

    Email: [email protected]

    http://www.huawei.com/http://www.huawei.com/mailto:[email protected]:[email protected]:[email protected]://www.huawei.com/
  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    3/61

    ITS1000M (Mini-shelter)

    Product Description About This Document

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    ii

    About This Document

    PurposeThis document describes the Mini-shelter in terms of its positioning, benefits, architecture,

    application scenarios, typical configuration, and technical specifications.

    Intended Audience

    This document is intended for:

    Sales engineers

    System engineers

    Technical support personnel

    Symbol ConventionsThe symbols that may be found in this document are defined as follows.

    Symbol Description

    Alerts you to a high risk hazard that could, if not

    avoided, result in serious injury or death.

    Alerts you to a medium or low risk hazard that could, ifnot avoided, result in moderate or minor injury.

    Alerts you to a potentially hazardous situation thatcould, if not avoided, result in equipment damage, dataloss, performance deterioration, or unanticipated results.

    Provides a tip that may help you solve a problem or

    save time.

    Provides additional information to emphasize or

    supplement important points in the main text.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    4/61

    ITS1000M (Mini-shelter)

    Product Description About This Document

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    iii

    Change History

    Changes between document issues are cumulative. The latest document issue contains all the

    changes made in earlier issues.

    Issue 03 (20130619)

    This is the third official release.

    Modified the feature of the feeder window in section2.2.7 "Optional Components."

    Issue 02 (20121204)

    This is the second official release.

    Add ports description.

    Modify HTTP to HTTPS.

    Modify "monitored remotely" to "managed remotely".

    Delete "Telecom protocol".

    Issue 01 (20120730)

    This is the first official release.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    5/61

    ITS1000M (Mini-shelter)

    Product Description Contents

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    iv

    Contents

    About This Document .................................................................................................................... ii

    1 Overview ......................................................................................................................................... 1

    1.1 Positioning ....................................................................................................................................................... 1

    1.2 Benefits ............................................................................................................................................................ 1

    1.3 Network Diagrams ........................................................................................................................................... 3

    2 Architecture .................................................................................................................................... 6

    2.1 Overview ............................................................ .............................................................. ................................ 6

    2.1.1 System Architecture ....................................................... ............................................................... .......... 6

    2.2 Assembly Cabinet .......................................................... .............................................................. ..................... 8

    2.2.1 Cabinet Appearance ................................................................................................ ................................ 8

    2.2.2 Temperature Control Door .................................. ............................................................... ................... 11

    2.2.3 Rack ...................................................................................................................................................... 12

    2.2.4 Door Lock ............................................................................................................................................. 13

    2.2.5 Base ........................................................... .............................................................. .............................. 13

    2.2.6 Cabinet Lamp ................................................................. ............................................................... ........ 14

    2.2.7 Optional Components ........................................................................................................................... 15

    2.3 Temperature Control System .................................................................................................................. ........ 17

    2.3.1 Intelligent Heat Exchanger ........................................................ ............................................................ 17

    2.3.2 Heat Exchanger .............................................................. ............................................................... ........ 19

    2.3.3 Natural Ventilation Unit ................................................................................................................ ........ 21

    2.3.4 TEC ........................................................... .............................................................. .............................. 22

    2.3.5 AC Air Conditioner and DC Air Conditioner .......................................................... .............................. 24

    2.3.6 Heater ........................................................ .............................................................. .............................. 26

    2.3.7 Air Conditioner Controller ................................................................................................. ................... 28

    2.4 Monitoring System ........................................................ .............................................................. ................... 29

    2.5 Power Distribution System and Power System ...................................................................................... ........ 30

    2.5.1 ACDB ........................................................ .............................................................. .............................. 30

    2.5.2 DCDU ................................................................................................................................................... 31

    2.5.3 Power System........................................................................................................................................ 32

    2.5.4 Maintenance Socket (Optional)............................................................................................................. 38

    2.6 Cables ...................................................... ................................................................. ...................................... 38

    2.6.1 Power Cables ........................................................................................................................................ 39

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    6/61

    ITS1000M (Mini-shelter)

    Product Description Contents

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    v

    2.6.2 Ground Cables ...................................................................................................................................... 39

    2.6.3 Signal Cables ........................................................................................................................................ 40

    2.7 Ground System .............................................................. .............................................................. ................... 41

    3 Application Scenarios ................................................................................................................ 43

    4 Typical Configuration ................................................................................................................ 45

    5 Technical Specifications ............................................................................................................ 50

    5.1 Environmental Specifications......................................................................................................................... 50

    5.2 Engineering Specifications ..................................................................................................................... ........ 50

    5.3 Cable Layout Principle ............................................................ ............................................................... ........ 52

    6 Acronyms and Abbreviations ................................................................................................... 55

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    7/61

    ITS1000M (Mini-shelter)

    Product Description 1 Overview

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    1

    1 Overview1.1 Positioning

    The ITS1000M V100R003C02 (Mini-shelter for short) is a complete solution that provides anappropriate operating environment and security system for outdoor communications sites. TheMini-shelter is characterized by easy site determination, energy saving and emission reduction,quick deployment, and smooth evolution. The Mini-shelter integrates Huawei

    communications equipment, a power system, alternating current (AC) and direct current (DC)

    power distribution devices, storage batteries, and surge protection and grounding devices. Itcan also be used as a functional cabinet such as a power supply cabinet, a battery cabinet, and

    a transmission cabinet.

    The Mini-shelter is an outdoor shelter with strong housing capability. Any devices that meetthe space and power consumption requirements for the Mini-shelter can be installed,

    including devices from other vendors. The Mini-shelter provides comprehensive temperaturecontrol units (TCUs) such as the heat exchanger, intelligent DC/AC heat exchanger,

    thermoelectric cooler (TEC), IP55/IP34 natural ventilation unit, DC air conditioner, and ACair conditioner to meet temperature control requirements for different compartments. This

    helps operators to implement energy saving and emission reduction plans.

    The Mini-shelter provides cabinets with different heights, diverse temperature control modes,and intelligent monitoring, and meets multiple market requirements.

    The Mini-shelter can be integrated in factories or warehouses, shipped pre-assembled, and

    hoisted onsite. It can also be shipped in separate packages and assembled onsite, which isapplicable in areas like on rooftops and hilltops that are tough to access with vehicles and

    cranes.

    1.2 Benefits

    Table 1-1shows the benefits of the Mini-shelter.

    Table 1-1The benefits of the Mini-shelter

    Item Benefits Remarks

    Mini-shelter Easy site

    determination

    Has small dimensions with a compact structure.

    Each unit of the Mini-shelter occupies only 1 m2

    (10.76 ft2).

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    8/61

    ITS1000M (Mini-shelter)

    Product Description 1 Overview

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    2

    Item Benefits Remarks

    Applicable to various site scenarios, such as a

    rooftop site, street site, suburb site, or a site sharedby different operators' devices.

    Flexibleproductcombination,

    diverse

    requirementsupport

    Can house devices from multiple vendors.

    Supports side-by-side or back-to-back capacity

    expansion and smooth devices evolution.

    Temperature control doors for Mini-shelters withthe same height are the same in support dimensions

    and installation dimensions.

    Wide rang of

    application

    scenarios

    With modular design, the Mini-shelter provides basic

    functional compartments. The Mini-shelter can also be

    combined flexibly to meet different customerrequirements.

    Highintegration and

    low cost

    Features low capital expenditure (CAPEX),compared with equipment rooms and shelters.

    Requires fewer cables between devices, helping

    reduce engineering costs.

    Has strong housing capability and supports a high

    level of integration for multiple auxiliary devicesso that the site is neat and orderly.

    Quick

    deployment

    and increased

    Return onInvestment

    (ROI)

    Can be assembled in factories or warehouses and

    then shipped as pre-assembled or can also be

    shipped in separate packages and then assembled

    onsite. Assembling a Mini-shelter with three units

    (without installing devices and connecting cables)

    requires about 8 person-hours.

    Requires a much smaller engineering scale,compared with traditional equipment rooms and

    shelters.

    Cabinet Low heat

    exchange

    coefficient, freefrom solar

    irradiation andawning

    The wall of the Mini-shelter is made of 45 mm

    (1.77 in.) highly adiabatic sandwich panel, which

    has a minor heat bridge, reduces heat exchange,and saves energy. The adiabatic design enables the

    Mini-shelter to house various temperature controldevices and apply to more scenarios.

    It has been proved by tests that the Mini-sheltersuffers minor solar irradiation and does not need an

    awning. Shows as theTable 1-2.

    Carrier-classdesign and

    improvedreliability

    Components of the Mini-shelter use carrier-classdesign to ensure safety and reliability.

    Device safety is ensured and devices run reliably.

    Temperature

    control

    Independent

    temperature

    control and

    The equipment compartment and battery

    compartment use different temperature control

    devices, which saves energy and reduces the

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    9/61

    ITS1000M (Mini-shelter)

    Product Description 1 Overview

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    3

    Item Benefits Remarks

    energy saving operational expenditure (OPEX).

    The equipment compartment provides passivecooling (such as a heat exchanger and natural

    ventilation unit) and active cooling (such as anintelligent heat exchanger and two air conditioners

    working in redundancy mode) to meet variousapplication requirements.

    Independent temperature control (TEC, DC airconditioner, and AC air conditioner) for the battery

    compartment ensures that storage batteries operateat a temperature lower than 30C.

    Install andmaintain easily

    The temperature control system is integrated in theMini-shelter and mounted on the door, and less

    maintenance operations.

    Long lifespan The Mini-shelter can be used for 8-10 years, whichmeets the requirements of the telecom industry.

    Monitoring The (site monitoring unit) SMU reports alarms over RS485 ports ordry contacts.

    The SMU monitors environmental parameters, Boolean values, and

    analog parameters.

    Environmental

    friendlinessThe Mini-shelter complies with RoHS standards.

    Table 1-2The test result of solar irradiation

    Solution Solar IrradiationIntensity

    Temperature Rise SolarIrradiation

    Top Middle Bottom

    Mini-shelter > 1120 W/m2 4.5 K 2.7 K 1.2 K 27.86 K

    Metal sheet cabinet 1036 W/m2 12.1 K 7.1 K 3.2 K 397.9 K

    1.3 Network Diagrams

    Typical Mini-shelter Network Diagram

    Figure 1-1shows a typical network diagram of the Mini-shelter.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    10/61

    ITS1000M (Mini-shelter)

    Product Description 1 Overview

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    4

    Figure 1-1Typical network diagram of the Mini-shelter

    Typical Site Network Diagram

    Figure 1-2shows a typical site network diagram composed by site subsystems. The dashed

    line box is the Mini-shelter.

    The interfaces between the Mini-shelter and other systems are as follows:

    Integrated telecommunication shelter (ITS) foundation between the Mini-shelter and thecivil engineering part of the site

    Cable ladder between the Mini-shelter and the tower

    Power cables to the energy plant system and mains source

    Power cables and signal cables to external communications and transmission equipment

    Ground cable to the ground grid

    Installation ports between the Mini-shelter and internal devices in the Mini-shelter

    The shape and mode of the Mini-shelter vary according to system configurations and

    applications scenarios.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    11/61

    ITS1000M (Mini-shelter)

    Product Description 1 Overview

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    5

    Figure 1-2Site network diagram

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    12/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    6

    2 Architecture2.1 Overview

    Figure 2-1shows the Mini-shelter architecture.

    Figure 2-1Mini-shelter architecture

    2.1.1 System Architecture

    The Mini-shelter system is composed of an assembly cabinet and other components.

    The assembly cabinet consists of the temperature control door, rack, and cabinet. Temperature

    control doors are selected based on the device heat emission, range of operating temperatures,and ambient temperatures. Racks are selected based on the device installation mode. Cabinetsare selected based on the required installation space.

    Devices in the Mini-shelter include storage batteries, the power system, communicationsequipment, environment monitoring unit, and AC and DC distribution devices. The devices

    must be compatible with the temperature control door, rack, and cabinet.

    Table 2-1Mini-shelter system architecture

    System Architecture Component

    Assembly

    cabinet

    Temperature

    control door

    IP34 natural ventilation unit (two 120 mm axial fans)

    IP34 natural ventilation unit (two 175 mm centrifugal

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    13/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    7

    System Architecture Component

    fans)

    IP55 natural ventilation unit (two 175 mm centrifugalfans, mounted on a door)

    HX02

    HX02+IP34 natural ventilation unit

    HX02+TEC

    HX04

    HX05

    TEC

    AH1500

    AH1500D

    AH3000

    AH3000D

    AH1500+TEC

    PC500D

    PC500

    AH1500+PC500D

    AH1500D+PC500D

    HXC70S

    HXC70S+IP34 natural ventilation unit

    HXC70S+TEC

    Rack 19-inch rack

    Base transceiver station (BTS) rack

    Combination racks (19-inch rack + battery rack)

    Battery rack (with a one -layer, two-layer, and

    three-layer pallet)

    Cabinet One unit

    Two units

    Three units

    1+1 unit

    1+1+1 unit

    Devices

    Storage

    batteries

    2 V absorbed glass mat (AGM) or gel batteries

    12 V AGM

    Power system Subracks, power supply units (PSUs), SMU, alarm

    interface board, and alarm monitoring cables

    Environment

    monitoring unit

    Main monitoring devices, sensors, power cables, and

    sensor cables

    AC and DC

    distribution

    devices

    Alternating current distribution box (ACDB) including

    Class B surge protection device (SPD)

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    14/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    8

    System Architecture Component

    Direct current distribution unit (DCDU)

    Direct current distribution box (DCDB)

    Communications equipmentand

    transmissionequipment

    Indoor macro NodeB

    Distributed NodeB with built-in RRUs

    Distributed NodeB with external RRUs

    Data communication cabinet (CX600-X1, CX600-X2)

    Transmission cabinet housing the optical switch node(OSN), radio transmission node (RTN), and Metro

    Air conditionercontroller

    N/A

    2.2 Assembly CabinetThe assembly cabinet consists of the temperature control door, rack, cabinet, and other

    components. The assembly cabinet can be flexibly configured and assembled.

    2.2.1 Cabinet Appearance

    The cabinet has two basic configurations: configuration A and configuration B. They can beextended based on the device configuration.

    Figure 2-2shows the two physical configurations of the Mini-shelter.

    Configuration A is applicable to scenarios with devices or storage batteries. The devicesand storage batteries cannot be installed at the same time.

    If equipment is installed, the HX02, HXC70S, HX04, HX05, AH1500, IP34 natural

    ventilation unit (only if RRUs are installed) or IP55 natural ventilation unit, AH1500,and AH1500D, AH3000, or AH3000D can be used for temperature control.

    If storage batteries are installed, the IP34 natural-ventilation unit, TEC, and DC or

    AC air conditioner can be used for temperature control.

    Configuration B is applicable to scenarios where equipment is installed in the upper part

    and storage batteries are installed in the lower part. The HX02, HXC70S, IP55 natural

    ventilation unit, and AH1500 or AH1500D can be used for the upper part, and the IP34natural ventilation unit, TEC, and DC or AC air conditioner can be used for the lowerpart.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    15/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    9

    Figure 2-2Mini-shelter physical configurations

    By combining the two basic configurations, the Mini-shelter can form various solutions, asshown inFigure 2-3.

    Figure 2-3Combined configurations for the Mini-shelter

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    16/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    10

    Cabinet Description

    The Mini-shelter has four types of unit cabinets. Capacity can be extended by combiningseveral unit cabinets.

    Dimensions of the cabinet shows asFigure 2-4.

    Figure 2-4Dimensions of the cabinet

    Table 2-2describes cabinets of the Mini-shelter.

    Table 2-2Mini-shelter cabinet description

    Cabinet Type Description

    1.5 m high

    cabinet

    The device space in the cabinet is 26 U.

    A maximum of one 2 V, 400 Ah battery string or 26 U 19-inch

    equipment can be installed in the cabinet. When the cabinet housesequipment, the communications equipment, environment monitoring

    unit, power system, DCDU, base band unit (BBU), and transmissionequipment can be configured.

    Available space dimensions (W x D x H) in the cabinet are 800 mm x800 mm x 1200 mm.

    Dimensions (W x D x H) of the unit cabinet (including the TCU) of

    the Mini-shelter are 905 mm x 1135 mm x 1490 mm.

    1.8 m high

    cabinet

    The device space in the cabinet is 33 U.

    A maximum of one 2 V, 500 Ah battery string or 33 U 19-inch

    equipment can be installed in the cabinet. When the cabinet housesequipment, the communications equipment, environment monitoring

    unit, power system, DCDU, base band unit (BBU), and transmissionequipment can be configured.

    Available space dimensions (W x D x H) in the cabinet are 800 mm x

    800 mm x 1500 mm.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    17/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    11

    Cabinet Type Description

    Dimensions (W x D x H) of the unit cabinet (including the TCU) of

    the Mini-shelter are 905 mm x 1135 mm x 1800 mm.

    2.1 m highcabinet

    The device space in the cabinet is 40 U. A maximum of one 2 V, 650 Ah battery string and four 12 V, 150 Ah

    battery strings or 40 U 19-inch equipment can be installed in the

    cabinet. The cabinet can house the communications equipment,environment monitoring unit, power system, DCDU, BBU, and

    transmission equipment.

    Available space dimensions (W x D x H) in the cabinet are 800 mm x

    800 mm x 1800 mm.

    Dimensions (W x D x H) of the unit cabinet (including the TCU) of

    the Mini-shelter are 905 mm x 1135 mm x 2100 mm.

    2.4 m high

    cabinet

    The device space in the cabinet is 47 U.

    The cabinet is used to house communications equipment from othervendors.

    Available space dimensions (W x D x H) in the cabinet are 800 mm x

    800 mm x 2100 mm.

    Dimensions (W x D x H) of the unit cabinet (including the TCU) ofthe Mini-shelter are 905 mm x 1135 mm x 2420 mm.

    2.2.2 Temperature Control Door

    Temperature control doors carry TCUs. In the Mini-shelter, temperature control doors carryheat exchangers, intelligent heat exchangers, and IP34/IP55 natural ventilation units forcooling equipment. They carry TEC, IP34 natural ventilation units, and DC/AC airconditioners for cooling storage batteries.

    Temperature control doors for Mini-shelters with the same height are the same in supportdimensions and installation dimensions. You can choose temperature control doors based on

    the heat emission, operating temperature range, and ambient temperature range of equipment.

    Figure 2-5shows temperature control doors.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    18/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    12

    Figure 2-5Temperature control doors

    2.2.3 Rack

    The racks include the battery rack and device rack (including a cable tray, and cable troughs

    installed on the two sides of the rack). Different racks are installed in different compartments

    to meet installation requirements.

    AGM batteries and gel batteries are installed on the battery rack. Communications device, the

    power system, indoor unit (IDU), ACDB, and DCDU are installed on the device rack.Figure2-6shows the racks.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    19/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    13

    Figure 2-6Racks

    2.2.4 Door Lock

    The Mini-shelter door uses a European standard DIN18152 lock. The door lock has thefollowing features:

    Fasteners are disassembled from cabinet interior, bolts are locked from the cabinet

    interior, and no bolt is exposed.

    The dedicated three-point antitheft lock prevents the door from being pried open from

    the side.

    The door has three protective locks. Lock cores can be replaced by customers. Thisresolves lock management problems for operators.

    Figure 2-7Door locks

    2.2.5 Base

    The steel base of the Mini-shelter has the following features:

    The base is 200 mm (7.87 in.) high and the wide base facilitates cable routing and other

    manual operations.

    There are multiple square and oval holes on the four circles of the base to make it easy touse a pallet truck or crane.

    The base is welded as a whole. Reinforcing ribs make the base compact, reliable, and

    hold heavy weights.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    20/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    14

    Figure 2-8Base

    2.2.6 Cabinet Lamp

    Each set of site is configured with a lamp. It is recommended that the lamp be installed and

    secured at the front left in the cabinet.Figure 2-9shows a lamp.

    Figure 2-9Lamp

    Table 2-3lists technical specifications of the lamp.

    Table 2-3Technical specifications of the lamp

    No. Item Specifications

    1 Rated voltage 48 V DC (10%)

    2 Operating current 1020 mA

    3 Power consumption 1 W

    4 Light source type Light emitting diode (LED)

    5 Luminance 500 cd/m2, at a distance of 500 mm away from the LED

    cover

    6 Dimensions (L x

    maximum shape

    diameter)

    280 mm x 54 mm

    7 Structure A colorless and transparent LED cover is used, the lamp

    is hand-held, and an embedded switch is available.

    8 Service life 1000 h

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    21/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    15

    2.2.7 Optional Components

    Antitheft Fence

    The antitheft fence provides antitheft measures for the cabinet. The antitheft fence has thefollowing features:

    The fence and cabinet are integrated to match perfectly by using harmonious colors.

    The fence has a small footprint and can be easily and quickly installed.

    The fence has multiple antitheft systems and functionality for installing an external lock.

    Figure 2-10Mini-shelter configured with an antitheft fence

    Awning

    The awning provides two tops when the awning is in normal status, to protect the Mini-shelter

    against sunshine, as shown inFigure 2-11.

    Figure 2-11Awning in normal status

    The awning protects maintenance personnel against rain when the awning is in open status, as

    shown inFigure 2-12.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    22/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    16

    Figure 2-12Awning in open status

    The awning is optional for one-cabinet, two-cabinet, and three-cabinet Mini-shelters. It has to

    be shipped with the Mini-shelter, because it cannot be installed onsite.

    Feeder Window

    The feeder window of the Mini-shelter has the following features:

    Maximum connector size that can be routed through the feeder window is 34 mm x 106

    mm.

    The feeder window is installed on the wall board close to communications equipmentand uses carrier-class anti-damage and waterproof design.

    The contact part between the feeder window and the Mini-shelter is sealed with

    waterproof tape, and the feeder window is secured from the Mini-shelter interior byusing bolts.

    Dedicated waterproof connectors can only be tightened or loosened from the

    Mini-shelter interior. The waterproofing performance does not change after thewaterproof connectors are tightened. The feeder window is secured with protective barsand cannot be tightened or loosened from the Mini-shelter exterior.

    The feeder window offers high anti-theft capability.

    Figure 2-13shows the feeder window.

    Figure 2-13Feeder window

    Base Cover Plate

    A base cover plate covers the cables at the cabinet bottom and avoids thefts. The number and

    type of base cover plates depend on site requirements.Figure 2-14shows the base cover plate.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    23/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    17

    Figure 2-14Base cover plate

    2.3 Temperature Control System

    The temperature control system helps provide a favorable cabinet environment required forlong-term equipment operating

    The TCUs include the intelligent heat exchanger, heat exchanger, natural ventilation unit,

    TEC, AC air conditioner, and DC air conditioner.

    This document figure is for reference only. The site cabinet prevails.

    The model of a TCU is specified on the nameplate.

    2.3.1 Intelligent Heat Exchanger

    Type and Appearance

    The Mini-shelter supports two types of intelligent heat exchangers: intelligent DC heatexchangers and intelligent AC heat exchangers. The intelligent DC heat exchangers:

    AH1500D and AH3000D. The intelligent AC heat exchangers: AH1500 and AH3000.Figure

    2-15shows a AH3000D.

    Figure 2-15AH3000D

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    24/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    18

    Working Principles

    As a modular temperature control unit, the intelligent AC heat exchanger is installed in thecabinet and integrates two sets of heat dissipation systems: an air conditioner and a heatexchanger share a fan assembly and control board.Table 2-4shows the working principles of

    the intelligent heat exchanger.

    Table 2-4The working principles of the intelligent heat exchanger

    Ambient Temperature Operation Mode Remarks

    Temperature in cabinet -

    Ambient temperature

    Refrigeration starting point.

    If either the air conditioner or the

    heat exchanger is faulty, at leastone heat dissipation system is still

    running. This ensures that thetemperature inside the cabinet is

    within the proper range for acertain period.

    -15 C Temperature in

    cabinet - Ambient

    temperature < -2 C

    Both the heat

    exchanger and the air

    conditioner work.

    Temperature in cabinet -

    Ambient temperature

    -2 C

    The air conditioner

    starts working.

    Technical Specifications

    Table 2-5lists the technical specifications of the intelligent heat exchanger.

    Table 2-5Technical Specifications

    Item AH1500D AH3000D AH1500 AH3000

    Refrigeration

    capacityL35/L35

    1500 W 3000 W 1500 W 3000 W

    Maximum

    powerconsumption

    660 W 1270 W 640 W(AC)/200

    W(DC)

    860 W(AC)/200

    W(DC)

    Typical

    power

    consumption

    560 W 1050 W 490 W(AC)/160

    W(DC)

    660 W(AC)/190

    W(DC)

    Heat

    exchanging

    capacity

    80 W/K 120 W/K 75 W/K 120 W/K

    Input voltage -48 V DC 220 V AC/-48V DC (The input of dual

    live wire)

    Service life 10 years

    Work

    temperature

    -40C to +50C long-term operating. 50C to 55C short-term operating.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    25/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    19

    Item AH1500D AH3000D AH1500 AH3000

    Storage

    temperature-40C to +70C

    IP protectionlevel

    IP55

    Alarm

    reporting

    Generates alarms over dry contacts. If no alarm is generated, the dry

    contact is closed. If an alarm is generated, the dry contact is open.

    Altitude < 4000 m

    Failure rate < 1 %

    Noise < 65 dB(A)

    2.3.2 Heat Exchanger

    Type and Appearance

    The Mini-shelter supports four types of heat exchangers: HX02, HX04, HX05, and HXC70S.

    Figure 2-16shows a HX02.

    Figure 2-16HX02

    Working Principles

    A heat exchanger provides two separate air circulation systems, one indoors and the other

    outdoors. When the temperature in the cabinet is higher than the external temperature, the

    heat exchanger dissipates heat generated in the cabinet.Table 2-6shows the workingprinciples of the heat exchanger.

    Table 2-6The working principles of the heat exchanger

    Functions Working principles Remarks

    Convection

    heat transfer

    When the air is totally separated

    between the cabinet interior and the

    Generally, the heat exchanger

    ensures a temperature

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    26/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    20

    Functions Working principles Remarks

    cabinet exterior, the heat exchanger

    uses external cold air to cool the hot airin the cabinet, to lower the ambient

    temperature in the cabinet.

    difference of 10C between the

    internal and externalenvironment.

    Intelligent fanspeed control

    When the ambient temperature isrelatively high, the fan rotates at a high

    speed. When the ambient temperature

    is relatively low, the fan rotates at alow speed. This reduces power

    consumption.

    -

    Technical Specifications

    Table 2-7lists the technical specifications of the heat exchanger.

    Table 2-7Technical Specifications

    Item HX02 HX04 HX05 HXC70S

    Maximum

    power

    consumption

    68 W 190 W 380 W 80 W

    Typical powerconsumption

    50 W 130 W 260 W 56 W

    Heatexchanging

    capacity

    80 W/K 190 W/K 250 W/K 80 W/K

    Input voltage 38 V DC to58 V DC

    Service life 10 years

    Work

    temperature-40C to +45C short-term operating.

    Storage

    temperature-40C to +70C

    IP protection

    levelIP55

    Alarm reporting Generates alarms over dry contacts. If no alarm is generated, the dry

    contact is closed. If an alarm is generated, the dry contact is open.

    Altitude < 4000 m

    Failure rate < 1 %

    Humidity range 5%100% RH

    Noise < 65 dB(A)

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    27/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    21

    2.3.3 Natural Ventilation Unit

    The Mini-shelter supports three types of natural ventilation units: IP34 natural ventilation unit

    (two 120 mm axial fans), IP34 natural ventilation unit (two 175 centrifugal fan), and IP55

    (two 175 centrifugal fan). The former applies to the batter compartment and the latter appliesto the equipment compartment.

    Type and Appearance

    The Mini-shelter supports three types of natural ventilation units: IP34 natural ventilation unit

    (two 120 mm axial fans), IP34 natural ventilation unit (two 175 centrifugal fan), and IP55(two 175 centrifugal fan).Figure 2-17shows IP34 natural ventilation unit (two 120 mm axialfans), IP34 natural ventilation unit (two 175 centrifugal fan), and IP55 (two 175 centrifugal

    fan)

    Figure 2-17Natural ventilation unit

    Working Principles

    A natural ventilation unit draws cool air into the cabinet by using fans to cool the equipmentinside the battery compartment and equipment compartment, and therefore saves energy.

    Technical Specifications

    Table 2-8lists the technical specifications of the natural ventilation unit.

    Table 2-8Technical Specifications

    Item

    IP34 naturalventilation unit(two 120 mm axialfans)

    IP34 naturalventilation unit(two 175 centrifugalfan)

    IP55 naturalventilation unit(two 175centrifugal fan)

    Maximum power

    consumption48 W 68 W

    Typical power 33 W 50 W

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    28/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    22

    Item

    IP34 naturalventilation unit(two 120 mm axialfans)

    IP34 naturalventilation unit(two 175 centrifugalfan)

    IP55 naturalventilation unit(two 175centrifugal fan)

    consumption

    Heat exchanging

    capacity140 W/K 250 W/K

    Input voltage -48 V DC

    Service life 8 years

    Work

    temperature

    -10C to 33C battery compartment. -10C to 35C equipment

    compartment.

    Storage

    temperature

    -40C to +70C

    Alarm reporting Generates alarms over dry contacts. If no alarm is generated, the dry

    contact is closed. If an alarm is generated, the dry contact is open.

    Altitude < 4000 m

    Failure rate < 1 %

    Noise < 65 dB(A)

    2.3.4 TECA TEC is applicable to outdoor battery cabinets used for long-term power backup at a normalor low temperature.

    Type and Appearance

    Figure 2-18shows a TEC.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    29/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    23

    Figure 2-18TEC

    Working Principles

    A TEC provides two separate air circulation systems, one indoors and the other outdoors.

    Table 2-9shows the working principles of the TEC.

    Table 2-9The working principles of the TEC

    Function Working principles Remarks

    Cooling After the TEC applies a positive voltage to

    semiconductor refrigeration chips, theinternal circulation side becomes cold, and

    cold air is supplied to the cabinet throughthe cold-end heat sink. The externalcirculation side becomes hot, and heat is

    dissipated through the hot-end heat sink.

    Heat is transferred from the

    cold end to the hot end torealize refrigeration

    The controller controls thefans and semiconductor

    refrigeration chips,monitors the TEC04

    operation, and generates analarm when a fault occurs.

    Fans provided forced air in

    both cold end and the hotend, which speeds up heatdissipation from the heat

    sink.

    Heating After the TEC applies a negative voltage to

    semiconductor refrigeration chips, the

    internal circulation side becomes hot, and

    heat is supplied to the Mini-shelter throughthe cold-end heat sink. The externalcirculation side becomes cold, and heat is

    dissipated into the Mini-shelter through the

    hot-end heat sink.

    Technical Specifications

    Table 2-10lists the technical specifications of the TEC.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    30/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    24

    Table 2-10Technical Specifications

    Item Specifications

    Refrigeration capacity

    (Battery compartment)

    200 W

    Maximum powerconsumption (Cooling)

    330 W

    Typical powerconsumption(Cooling)

    300 W

    Cooling COP 0.61

    Heating capacity 570 W

    Heating power consumption 400 W

    Heating COP 1.43

    Input voltage -48 V DC

    Service life 10 years

    Work temperature -40C to +40C

    Storage temperature -40C to +70C

    IP protection level IP55, complying with IEC 60529

    Alarm reporting Generates alarms over dry contacts. If no alarm is

    generated, the dry contact is closed. If an alarm is

    generated, the dry contact is open.

    Altitude < 4000 m

    Failure rate < 1 %

    Humidity range 5%100% RH

    Positive polarity protection of

    DC power supplySupported

    Noise < 65 dB(A)

    2.3.5 AC Air Conditioner and DC Air Conditioner

    Type and Appearance

    The Mini-shelter supports two types of air conditioner: AC air conditioner and DC airconditioner. The DC air conditioner: PC500D. The AC air conditioner: PC500.Figure 2-19

    shows a PC500 and a PC500D.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    31/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    25

    Figure 2-19PC500 and PC500D

    Working Principles

    A air conditioner provides two separate air circulation systems, one indoors and the other

    outdoors.Table 2-11shows the working principles of the air conditioner.

    Table 2-11The working principles of the air conditioner

    AirConditioner

    Working Principles Remarks

    PC500 The refrigeration cycle is as follows:1. The compressor draws refrigerant from the

    evaporator and compress it to a hightemperature and pressure.

    2. The compressor drives the high-temperatureand high-pressure refrigerant into the

    condenser.

    3. The refrigerant in the condenser is cooled intohigh-pressure liquid.

    4. The high-pressure liquid refrigerant transformsinto low-pressure refrigerant after passing

    through throttles, and then enters the

    evaporator.5. The low-temperature and low-pressure

    refrigerant transforms into gas after beingheated in the evaporator.

    6. The compressor sucks the air refrigerant again.

    The condenser and

    evaporator are bothequipped with a

    cycle fan tostrengthen air

    convection and

    heat exchanging.

    The condenserperforms heat

    exchangingoutside the

    control cabinet.

    The evaporateperforms heatexchanginginside the

    control cabinet.

    PC500D

    Technical Specifications

    Table 2-12lists the technical specifications of the air conditioner.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    32/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    26

    Table 2-12Technical Specifications

    Item PC500D PC500

    Rated

    refrigerationcapacity L35/L35

    500 W

    Maximum power

    consumption240 W 300 W

    Typical powerconsumption

    200 W 250 W

    Input voltage -48 V DC 220 V AC and -48 V DC

    Service life 8 years

    Work temperature -40C to +55C -40C to +45C

    Storage

    temperature-40C to +70C

    IP protection level IP55

    Alarm reporting Generates alarms over dry contacts. If no alarm is generated, the dry

    contact is closed. If an alarm is generated, the dry contact is open.

    Altitude < 4000 m

    Failure rate < 1 %

    Humidity range 5%100% RH

    Noise < 65 dB(A)

    2.3.6 Heater

    Type and Appearance

    The Mini-shelter supports two types of Heater: HAU03A-01 and HAU02A-02.Figure 2-20

    shows a HAU03A-01 and a HAU02A-02.

    Figure 2-20HAU03A-01 and HAU02A-02

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    33/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    27

    Feature and Working Principles

    Table 2-13shows the features and working principles of the heater.

    Table 2-13Feature and Working PrinciplesItem HAU03A-01 HAU02A-02

    Consist The heater consists of a fan and a heating element.

    Features Front and rear ventilation channels are available in the heater.

    The surface temperature of the heating element is less than or equal to 140C

    when the heater is running.

    The temperature at the air exhaust vent is less than or equal to 70C.

    A fan is embedded in the heater. An external fan is configured for

    the heater.

    The air intake vent and air exhaust vent

    provide honeycomb holes.

    An 120 mm AC fan is used and a

    fan guard is configured outside the

    fan.

    Working

    Principles

    If the temperature at the air intake vent

    drops below 0C (tolerance 3C), the

    heater starts to work. If the temperatureexceeds 15C (tolerance 3C), the

    heater stops working.

    If the temperature at the air intake

    vent drops below 0C (tolerance

    3C), the heater starts to work. Ifthe temperature exceeds 15C

    (tolerance 3C), the heater stops

    working.

    The fan blows the generated heat to heat and balance temperature in thecabinet.

    Technical Specifications

    Table 2-14lists the technical specifications of the heater.

    Table 2-14Technical Specifications

    Item HAU03A-01 HAU02A-02

    Input voltage 220 V AC

    Frequency 45 Hz to 65 Hz

    Work temperature -40C to +65C

    Storage temperature -40C to +70C

    Alarm reporting Generates alarms over dry contacts. If

    no alarm is generated, the dry contact is

    closed. If an alarm is generated, the drycontact is open.

    -

    Humidity range 5%95% RH

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    34/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    28

    Item HAU03A-01 HAU02A-02

    Altitude -60 m to +1800 m

    Service life 10 years

    Heating capacity 500 W

    Noise < 45 dB(A) < 72 dB(A)

    2.3.7 Air Conditioner Controller

    The air conditioner controller switches between the primary and secondary air conditioners bycontrolling the refrigeration device based on the temperature requirements for equipment

    rooms. If the ambient temperature is greater than the maximum value, the air conditionercontroller allows both air conditioners to work. The air conditioner controller not only

    monitors the operating status of air conditioners in real time but also helps to extend the

    service life of the refrigeration device.

    Type and Appearance

    Air Conditioner Controller: ACM-1D.Figure 2-21shows an air conditioner controller.

    Figure 2-21ACM-1D

    Working Principles

    Table 2-15shows the working principles and functions of the air conditioner controller.

    Table 2-15Working Principles and Functions

    Item Description Remarks

    Working

    Principles

    The air conditioner controller ACM-1D is

    used to control the two air conditioners.

    1. After initial power-on, the primary airconditioner starts to work.

    2. After the temperature exceeds T1 3minutes later, the secondary air

    conditioner starts to work.

    3. If the temperature is lower than T1 bymore than 10C, the secondary airconditioner stops working.

    The default switch duration

    between the two airconditioners is seven days.

    The value range is 1 to 28

    days.

    T1 is the temperature forstarting the two air

    conditioners. The defaultvalue is 45C, and thevalue range is 40C to

    55C.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    35/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    29

    Item Description Remarks

    Functions Stores historical records.

    Records controller operations.

    Supports user permission management.

    Supports parameter settings.

    Reports alarms in real time.

    -

    Technical Specifications

    Table 2-16lists the technical specifications of the air conditioner controller.

    Table 2-16Technical Specifications

    Item Description

    Rated power input < 10 W

    Maximum carrying

    current50 A

    Work voltage -38.5 V DC to -60 V DC

    Work temperature -20C to +55C

    Storage temperature -40C to +70C

    Alarm reporting Generates alarms over dry contacts. If no alarm is generated, the drycontact is closed. If an alarm is generated, the dry contact is open.

    Altitude 2000 m (If the altitude is higher than 2000 m, the power is derated

    according to GB/T3859.2-93.)

    Humidity range 90% RH

    2.4 Monitoring System

    The monitoring system of Mini-shelter consists of ETP48200, sensor and cables. AndETP48200 consists of SMU02B, UIM02C, backplane and so on.

    Please seeDescription of SMU02Bfor details about SMU02B.

    Please seeDescription of UIM02Cfor details about UIM02C.

    Please seeMonitoring Systemfor details about monitoring system architecture.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    36/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    30

    2.5 Power Distribution System and Power System

    The power distribution system of the Mini-shelter provides AC power distribution and DC

    power distribution. The ETP48200-A6 or TP48200-B6 can be used as the power system.

    2.5.1 ACDB

    The ACDB is configured if multiple AC outputs are required.

    Type and Appearance

    The Mini-shelter supports four types of ACDB: ACDB-DS-063-N1, ACDB-DS-100-P1,

    ACDB-DT-100-P1, and ACDB-ST-063-P1.Figure 2-22shows ACDB.

    Figure 2-22ACDB

    Technical Specifications

    Table 2-17lists the technical specifications of the ACDB.

    Table 2-17Technical Specifications

    Item ACDB-DS-063-N1

    ACDB-DS-100-P1

    ACDB-DT-100-P1

    ACDB-ST-063-P1

    Rated input

    operatingvoltage

    Single-Phase (220 V) Three-Phase (220/380 V).

    Single-Phase (220 V)

    Input 2-pole 63 A

    circuit breaker(supporting

    twomechanicallyinterlocked

    inputs)

    Two 2-pole 100

    A circuit breakers(supporting two

    mechanicallyinterlockedinputs)

    Two 4-pole 100

    A circuit breakers(supporting two

    mechanicallyinterlockedinputs)

    One 3-pole 63 A

    circuit breaker(single-Phase 220

    V)

    Output One 40 A

    terminal

    connector

    One 1-pole 63 A

    circuit breaker,

    two 1-pole 32 A

    One 3-pole 63 A

    circuit breaker,

    two 1-pole 32 A

    One 3-pole 50 A

    circuit breaker,

    one 1-pole 20 A

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    37/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    31

    Item ACDB-DS-063-N1

    ACDB-DS-100-P1

    ACDB-DT-100-P1

    ACDB-ST-063-P1

    (L/N), two

    2-pole 32 A

    circuitbreakers, andoneall-purpose

    maintenancesocket

    (withoutcircuit breaker

    protection)

    circuit breakers,

    two 1-pole 10 A

    circuit breakers,and oneall-purposemaintenance

    socket

    circuit breakers,

    two 1-pole 10 A

    circuit breakers,and oneall-purposemaintenance

    socket

    circuit breakers,

    and two 1-pole 16

    A circuitbreakers.

    Surge

    protection

    properties

    Not required Level-B surge

    protection

    (maximumdischarge current:60 kA)

    Level-B surge protection (maximum

    discharge current: 100 kA)

    IP

    protectionlevel

    IP20

    Rated inputfrequency

    50/60 Hz

    Work

    temperature-33C to +55C

    Installation 19-inch subrack

    2.5.2 DCDU

    When the Mini-shelter is applied in the DBS3900, a DCDU-03B is used to distribute DCpower. When there is more than one route, a DCDU-03C and a DCDB-SZ-100-P1 are used todistribute DC power.

    Type and Appearance

    The Mini-shelter supports three types of DCDU: DCDU-03B, DCDU-03C, andDCDB-SZ-100-P1.Figure 2-23shows DCDU.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    38/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    32

    Figure 2-23DCDU

    Technical Specifications

    Table 2-18lists the technical specifications of the DCDU.

    Table 2-18technical specifications

    Item DCDU-03B DCDU-03C DCDB-SZ-100-P1

    Function The DCDU-03B

    provides nine48

    V DC outputs to

    power DC devices.

    The DCDU-03C provides

    nine48 V DC outputs to

    power DC devices.

    The DCDB-SZ-100-P1

    provides nine48 V DC

    outputs.

    Surge

    protectionproperties

    Differential mode (8/20 s): 10 kA. Common mode (8/20 s): 15 kA

    IP

    protectionlevel

    IP20

    Input

    current100 A

    Output

    circuit

    breaker

    Six 20 A circuit

    breakers and three

    12 A circuit

    breakers

    Seven 12 A circuit

    breakers and two 6 A

    circuit breakers

    Six 25 A circuit breakers

    and three 16 A circuit

    breakers

    Installation 19-inch subrack

    2.5.3 Power System

    The ETP48200-A6 or ETP48200-B6 can be used as the power system.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    39/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    33

    Configuration and Appearance

    The ETP48200-A6 & ETP48200-B6 consists of rectifiers, monitoring unit, and powerdistribution unit (PDU).

    Figure 2-24shows a ETP48200-A6.Figure 2-25shows a ETP48200-B6.

    Figure 2-24ETP48200-A6

    Figure 2-25ETP48200-B6

    Features Comprehensive management on itself and storage batteries.

    The monitoring module is of network design and provides one FE port, oneRS485/RS232 port.

    Supports simple network management protocol (SNMP), control area network (CAN),

    and Hypertext Transfer Protocol Secure (HTTPS) and can communicate with NetEco orthird-party element management systems (EMSs). They can also be managed remotely

    and work in unattended mode.

    Support the remote software upgrade.

    Displays information on the liquid crystal display (LCD) and provides buttons for ease

    of operation.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    40/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    34

    Allows you to query component information recorded on electronic labels over a webuser interface (WebUI).

    Support multiple display languages, such as English, Chinese, German, Spanish, and

    Portuguese.

    Rectifiers and the monitoring unit are hot-swappable. The power factor of rectifiers is high to 0.99.

    Technical Specifications

    Table 2-19lists the technical specifications of the Power System.

    Table 2-19Technical Specifications

    Item ETP48200A6 ETP48200B6

    Main AC input Three-phase or Single-phase Dual-live wire or Single-phase

    AC input circuit

    breaker63 A/3P*1 100 A/2P*1

    DC output circuit

    breaker

    LLVD: 100 A*2

    BLVD:63 A*1,32 A*1,16 A*3

    LLVD:100 A*2,20 A*1

    BLVD:63 A*1; 32 A*1; 16

    A*3

    AC output circuit

    breaker16 A/1P*2,20 A/1P*1 16 A/2P*1

    Input Voltage 85 V AC to 300 V AC 90/180 V AC to 145/290 VAC(Two-Phase 110 V). 85 V

    AC to 300 V AC(Single-Phase220 V)

    DC surge

    protectionDifferential mode (8/20 s) 10 kA. Common mode (8/20 s) 20 kA

    AC surge

    protectionLevel-B surge protection

    Rated discharge capacity In: 30 kA (8/20 s)

    Maximum discharge capacity Imax: 60 kA (8/20 s)

    Battery circuit

    breaker125 A*2

    Description of SMU02B

    The SMU02B monitors operating parameters of the ETP48200-A6 and ETP48200-B6 in realtime, analyzes the operating status, and generates alarms when necessary.

    Figure 2-26shows the SMU02B panel.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    41/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    35

    Figure 2-26Panel

    1. Running status indicator 2. Minor alarm indicator 3. Major alarm indicator

    4. Liquid crystal display (LCD) 5. Locking latch 6. Four buttons

    7. USB (Reserved) 8. RS485/RS232 9. FE

    Table 2-20shows the description of communications port on the SMU02B.

    Table 2-20The description of the communications port

    CommunicationsPorts

    CommunicationsParameter

    ProtocolCompliance

    Remarks

    FE 10 M/100 M

    Auto-adaptation

    TCP/IP, HTTPS,

    and SNMPN/A

    RS485/RS232 Baud rate: 9,600bit/s or 19,200 bit/s

    Huawei protocols The RS485 andRS232 ports are

    mutually exclusive.

    NOTE

    All ports in this manual are protected by a security mechanism.

    Description of UIM02C

    UIM02C supports 8 dry contact output ports, 6 Boolean value input ports and 7 sensor ports.

    Figure 2-27shows the UIM02C panel.

    Figure 2-27Panel

    Table 2-21shows the description of ports on the UIM02C.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    42/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    36

    Table 2-21Ports

    Port Type Silkscreen Description

    Sensor

    ports

    TEM_HUM Temperature and humidity sensor

    WATER Water sensor

    TEMP1 Temperature sensor 1 (used for adjusting the fan speed)

    TEMP2 Temperature sensor 2 (used for adjusting the fan speed)

    GATE Door status sensor

    SMOKE Smoke sensor

    BTEMP Battery temperature sensor

    Boolean

    value inputports

    DIN1 Boolean value input 1

    DIN2 Boolean value input 2

    DIN3 Boolean value input 3

    DIN4 Boolean value input 4

    DIN5 Boolean value input 5 (Heater alarm)

    DIN6 Boolean value input 6 (Temperature control system alarm)

    Dry contactoutput

    ports

    ALM1 AC power failure alarm

    Default mode (Close: alarm; Open: normal) can bemodified as required.

    ALM2 DC undervoltage alarm or DC overvoltage alarm

    Default mode (Close: alarm; Open: normal) can bemodified as required.

    ALM3 rectifier faults alarm

    Default mode (Close: alarm; Open: normal) can bemodified as required.

    ALM4 SPD failure alarm

    ALM5 Fuse blown alarm or circuit breaker tripping alarm

    Default mode (Close: alarm; Open: normal) can bemodified as required.

    ALM6 Battery temperature alarms, environment temperature alarm

    Default mode (Close: alarm; Open: normal) can bemodified as required.

    ALM7 Door status alarm

    ALM8 Heater or temperature control system alarm

    Communic

    ation PortCOM RS485

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    43/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    37

    Monitoring System

    The BBU detects Boolean values and reports dry contact alarms to the M2000 over the portsused for detecting Boolean values. The monitoring system architecture to the M2000 is shownasFigure 2-28.

    Figure 2-28The monitoring system architecture to the M2000

    The power output alarms are reported to the third-party monitoring host over dry contacts or

    to a third-party EMS over an RS485 port by the intelligent equipment communicationprotocol. The monitoring system architecture to a third-party EMS is shown asFigure 2-29.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    44/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    38

    Figure 2-29The monitoring system architecture to a third-party EMS

    2.5.4 Maintenance Socket (Optional)

    The maintenance socket with a 20 A all-purpose socket supplies AC power to installation and

    maintenance tools and devices.

    Figure 2-30shows a maintenance socket.

    Figure 2-30Maintenance socket

    2.6 CablesCables in the Mini-shelter include power cables, ground cables, and signal cables.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    45/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    39

    2.6.1 Power Cables

    Power cables used in the Mini-shelter include AC power cables and DC power cables.Table

    2-22lists power cables of the Mini-shelter

    Table 2-22Power Cables

    Power Cables Cable Types Remarks

    AC power cables Power cable to the heater The cable is connected to the heater

    by using the transfer busbar.

    DC power cables Power cables to devices inthe cabinet

    Blue cables and black cables.

    Power cables to storage

    batteriesRed cables and black cables.

    2.6.2 Ground Cables

    A ground cable is yellow and green and has OT terminals at both ends.Figure 2-31shows theground cables.

    Figure 2-31Ground cables

    Table 2-23lists ground cables of the Mini-shelter.

    Table 2-23Ground cables

    No. Ground cables Remarks

    1 Ground cable between the rack and the indoor

    ground bar.

    No measures are required

    on site.

    2 Ground cable between devices and the rack.

    3 Ground cable between devices and the indoorground bar.

    4 Ground cable between devices and the outdoorground bar or ground grid.

    5 Equipotential ground cable between the cabinet and

    the temperature control door.

    6 Equipotential ground cable between units in the

    cabinet.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    46/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    40

    No. Ground cables Remarks

    7 Ground cable to the BBU. No measures are required

    on site.8 Ground cable to the monitoring device.

    9 Ground cable to the AC-to-DC power system.

    10 Ground cable to the battery rack.

    11 Equipotential ground cable between the ground barin the compartment and the outdoor ground bar.

    12 Ground cable between the indoor ground bar and theground grid.

    13 Ground cable to the positive DC output busbar

    (RTN) of the AC-to-DC power system.

    If this cable has been

    connected in the powersystem, no onsiteprocessing is required

    14 The cables include the shielded DC power cable for

    powering the RRU, shielded power cable to thenavigation light, intermediate frequency cable, andfeeder.

    The shield layers and

    jackets of cables must beconnected to the outdoorground bar by using ground

    clips before the cables are

    routed into thecompartment.

    2.6.3 Signal CablesTable 2-24lists signal cables of the Mini-shelter.

    Table 2-24Signal Cables

    No. Signal Cables Remarks

    1 Communicationscables

    Temperature controlsystem communications

    cables

    The cables are installed beforedelivery.

    Power system

    communications cablesOptional

    2 Sensor cables Temperature-humidity

    sensor cableDelivered with sensors (optional).

    Battery temperature

    sensor cable

    The cables are installed before

    delivery.

    Door status sensor cable Delivered with the cabinet.

    Water sensor cable The cables are installed before

    delivery.

    Smoke sensor cable Delivered with sensors (optional).

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    47/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    41

    No. Signal Cables Remarks

    3 Dry contact

    alarm cables

    Temperature control

    system dry contact alarmcables

    The cables are installed before

    delivery.

    Power system dry contactalarm cables

    Optional

    ACDB or DCDU dry

    contact alarm cablesN/A

    Other equipment dry

    contact alarm cablesN/A

    2.7 Ground SystemThe Mini-shelter is grounded by using indoor and outdoor ground bars.

    Figure 2-32shows the ground bar.

    Figure 2-32Ground Bar

    Table 2-25lists features of the ground bar.

    Table 2-25Features

    Item Outdoor Ground Bar Indoor Ground Bar

    FeaturesCan be installed on the base or rear

    wall of the Mini-shelter or the

    concrete floor.

    More indoor ground bars can be

    added as required.

    Is configured with 12 M8 bolts and

    one M10 bolt.

    Is configured with seven M6 bolts

    and one M8 bolt.

    Uses interlacing holes and self-clinching nuts for ease of onsite cable

    connection and operations.

    The ground bar is flexible and easy to install.

    Function The Mini-shelter is configured withthe outdoor ground bar for grounding

    outdoor cables and cables to the tower

    The Mini-shelter is configured withthe indoor ground bar used for

    grounding devices in the cabinet.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    48/61

    ITS1000M (Mini-shelter)

    Product Description 2 Architecture

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    42

    Item Outdoor Ground Bar Indoor Ground Bar

    before these cables are routed into the

    Mini-shelter. These cables include thepower cable to the RRU, power cable

    to the navigation light, intermediatefrequency cable, and feeder.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    49/61

    ITS1000M (Mini-shelter)

    Product Description 3 Application Scenarios

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    43

    3 Application ScenariosTargeted at various customer requirements, the Mini-shelter provides different configurations

    for different site environments. The Mini-shelter provides outdoor operating environmentsand security system for communications sites, to meet site setup requirements in urban areas,

    suburbs, and rural areas.

    Table 3-1lists the feature of the application scenarios.Figure 3-2shows application scenarios.

    Table 3-1The feature of the application scenarios

    ApplicationScenarios

    Features

    Urban rooftop

    scenario

    Small size, light weight, easy transportation, fast setup, and superior

    covertness

    Low rental, good environment adaptability, and raised ROI speed

    Neat site, easy management, and smooth expansion

    Curbsidescenario

    Small footprint and low rental

    Concealed exterior

    Fast deployment and good environment adaptability

    Rural groundscenario

    Large coverage radius for wide coverage

    Long-term power backup required due to poor mains conditions

    Allowed site setup in mountains and delivery in components for poortransportation

    2G-3G

    co-siting

    scenario

    Small footprint and flexible installation modes

    Strong housing capability and independent space for the co-siting ofdifferent operators

    Easy setup and fast installation. The transportation, installation,

    commissioning of the Mini-shelter can be completed in one day.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    50/61

    ITS1000M (Mini-shelter)

    Product Description 3 Application Scenarios

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    44

    Figure 3-2Application Scenarios

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    51/61

    ITS1000M (Mini-shelter)

    Product Description 4 Typical Configuration

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    45

    4 Typical ConfigurationThis section describes the typical configuration of the Mini-shelter by using the 2.1 m high

    cabinet as an example.

    Overview

    Figure 4-1shows the application scenario diagram of the Mini-shelter.

    Figure 4-1Application scenario diagram of the Mini-shelter

    Functional Cabinet Power cabinet

    Table 4-1Typical configuration of the power cabinet

    PowerSystem Type

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    ETP48200 200 ATwo 12 V,150 Ah

    battery

    strings

    Power

    compartment:

    HX02 andHXC70S

    Battery

    Power

    compartment:

    7001500 W

    Battery

    compartment:

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    52/61

    ITS1000M (Mini-shelter)

    Product Description 4 Typical Configuration

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    46

    PowerSystem Type

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    compartment: TEC

    and natural

    ventilation unit.

    190500 W

    Outdoor battery cabinet

    Table 4-2Typical configuration of the battery cabinet

    BatteryType

    BatteryCapacity

    HeatDissipation

    Application Scenario

    2 V

    AGM

    batteries

    300650 Ah TEC, natural

    ventilation

    unit, DC airconditioner,

    and AC airconditioner

    When the ambient temperature is below

    33C, the battery cabinet uses the natural

    ventilation unit for temperature control.

    When the ambient temperature is between33C and 40C, the battery cabinet uses theTEC for temperature control.

    When the ambient temperature is between

    40C and 55C, the battery cabinet uses theDC air conditioner for temperature control.

    12 V

    AGM

    batteries

    300600 Ah

    2 V deep

    cyclebatteries

    (DCBs)

    300650 Ah

    Transmission cabinet

    Table 4-3Typical configuration of the transmission cabinet

    Installation SupportedTransmissionDevice Type

    HeatDissipation

    HeatDissipationCapability

    Remarks

    19-inch rackinstallation or

    ETSI rack

    installation

    OSN1500

    OSN3500

    RTN950

    RTN910

    HX02 700 W When the ambient

    temperature is below40C and the

    maximum operating

    temperature of thedevice can reach

    50C, it isrecommended that

    the heat exchanger

    be used.

    HX04 2000 W

    AH1500 and

    AH1500D1500 W When the cabinet is

    used in ahigh-temperature

    area or the

    maximum operatingtemperature of thedevice is below

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    53/61

    ITS1000M (Mini-shelter)

    Product Description 4 Typical Configuration

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    47

    Installation SupportedTransmissionDevice Type

    HeatDissipation

    HeatDissipationCapability

    Remarks

    45C, it is

    recommended thatthe intelligent heatexchanger be used.

    Site Cabinet Indoor HUAWEI BTS3900 (short-term power backup)

    Table 4-4Configuration of the indoor HUAWEI BTS3900 (short-term power backup)

    PowerSystem Type

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    ETP48200 200 A Two 12 V,

    150 Ah

    battery

    strings

    Communications

    equipmentcompartment:

    HX04, HX05,AH3000D, andAH3000

    Power

    compartment:HX02, HXC70S,

    and AH1500 Battery

    compartment:

    TEC, naturalventilation unit,DC air

    conditioner, and

    AC air conditioner

    Communications

    equipmentcompartment:

    20003000 W

    Power

    compartment:

    7001500 W

    Battery

    compartment:190500 W

    Indoor HUAWEI BTS3900 (long-term power backup)

    Table 4-5Configuration of the indoor HUAWEI BTS3900 (long-term power backup)

    PowerSystem Type

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    ETP48200 200 A Four 12 V,

    150 Ahbattery

    strings or

    one 2 V,650 Ahbattery

    string

    Communications

    equipmentcompartment:

    HX04, HX05,

    AH3000D, andAH3000

    Power

    compartment:

    Communications

    equipment

    compartment:

    20003000 W

    Powercompartment:

    7001500 W

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    54/61

    ITS1000M (Mini-shelter)

    Product Description 4 Typical Configuration

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    48

    PowerSystem Type

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    HX02, HXC70S,

    AH1500D, and

    AH1500

    Batterycompartment:TEC, natural

    ventilation unit,

    AC airconditioner, and

    DC air conditioner

    Battery

    compartment:

    190500 W

    Distributed tower-mounted RRU

    Table 4-6Configuration of the distributed tower-mounted RRU

    PowerSystem Type

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    ETP48200 200 A

    Two 12 V,

    150 Ah

    batterystrings

    Equipment

    compartment:

    HX02, HXC70Sand AH1500

    Batterycompartment:

    TEC, naturalventilation unit,

    AC airconditioner, and

    DC airconditioner

    Equipmentcompartment:

    7001500 W

    Battery

    compartment:

    190500 W

    Distributed built-in RRU

    Table 4-7Configuration of the distributed built-in RRU

    Power SystemType

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    ETP48200 200 A

    Four 12 V,

    150 Ahbattery

    strings or

    one 2 V,650 Ahbattery

    string

    Communications

    equipmentcompartment:HX04, HX05,AH3000D, and

    AH3000

    Power

    compartment:HX02, HXC70S,

    and AH1500

    Communications

    equipmentcompartment:

    20003000 W

    Power

    compartment:7001500 W

    Battery

    compartment:

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    55/61

    ITS1000M (Mini-shelter)

    Product Description 4 Typical Configuration

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    49

    Power SystemType

    PowerCapacity

    BatteryCapacity

    Heat Dissipation Heat DissipationCapability

    Battery

    compartment:

    TEC, naturalventilation unit,and DC airconditioner

    190500 W

    The previous typical configurations can be flexibly selected based on site requirements.

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    56/61

    ITS1000M (Mini-shelter)

    Product Description 5 Technical Specifications

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    50

    5 Technical Specifications5.1 Environmental Specifications

    Table 5-1lists the operating temperature of the Mini-shelter.

    Table 5-1Operating temperature of the Mini-shelter

    Item Description

    Storage

    temperature-50C to +70C

    Altitude < 4000 m (When the altitude is above 2000 m, the maximum operating

    temperature decreases by 1C for each additional 300 m.)

    Windresistance

    50 m/s

    Solar radiation 1120 W/m2

    Dust pollution No requirement

    5.2 Engineering Specifications

    This section describes engineering specifications such as the external and internal dimensionsof the Mini-shelter in different configurations.

    Table 5-2lists the engineering specifications.

    Table 5-2Engineering specifications

    Configuration External Dimensions (H x Wx D)

    Internal Dimensions (H x W xD)

    Two units (2.1 m

    high cabinet)

    2110 mm x 1755 mm x 1085

    mm1800 mm x 1650 mm x 800 mm

    Three units (2.1 m 2110 mm x 2610 mm x 1085 1800 mm x 2500 mm x 800 mm

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    57/61

    ITS1000M (Mini-shelter)

    Product Description 5 Technical Specifications

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    51

    Configuration External Dimensions (H x Wx D)

    Internal Dimensions (H x W xD)

    high cabinet) mm

    Table 5-3lists the cabinet structural specifications.

    Table 5-3Cabinet structural specifications

    Item Specifications Remarks

    Noise control Noise judging criteria:

    Test the noise at a position 1.5 maway from the front of the cabinet

    and 1 m away from the ground. The

    noise value is less than 65 dB (A).

    See the Outdoor Temperature

    Control Unit TestingSpecifications(Huawei technical

    specifications) and GR 487 (anindustry standard).

    IP protection The equipment compartment isprotected to IP55 (to IP34 inRRU scenarios).

    The TEC battery compartment is

    protected to IP55.

    The natural-ventilation battery

    compartment is protected toIP34.

    The HX02 plusnatural-ventilation compartment

    is protected to IP34.

    The DC/AC air conditioner

    compartment is protected to

    IP55.

    N/A

    The cabinet uses sealing design.

    This prevents insects and micefrom entering the cabinet.

    The cabinet uses antitheft design.No fastener is exposed.

    Structure safety The flame spread rating meets

    requirements for the classificationon burning behavior for buildingmaterials in GB 8624-2006. The

    sealing rubber strip and

    heat-insulation material meet therequirements of UL94 HF-1.

    The cabinet structure consists of

    sheet-metal top, extrudedaluminum profile column,sheet-metal door, sandwich panel,

    and steel base. All materials

    except the sandwich panel areincombustible. The sandwich

    panel is made of PU or EPS. Thesandwich panel is not exposedafter being installed. The

    sandwich panel meets the flamespread rating requirement.

    Packing and Both onsite assembling and overall

    hoisting after partial integration are

    The packing and transportation

    meet storage and transportation

  • 5/20/2018 ITS1000M (Mini-shelter) V100R003C02 Product Description 03

    58/61

    ITS1000M (Mini-shelter)

    Product Description 5 Technical Specifications

    Issue 03 (2013-06-19) Huawei Proprietary and Confidential

    Copyright Huawei Technologies Co., Ltd.

    52

    Item Specifications Remarks

    transportation supported, collective packing and

    transportation for multiple parts aresupported, and overall packing and

    transportation after partialintegration are supported.

    requirements in GB 4798.

    Atmospheric

    pressure70-106 kPa N/A

    Anti-corrosion

    performance

    No corrosion occurs on exposed

    components after a 240-hour salt

    spray test.

    Test method: IEC60068-2-52

    Service life 10 years N/A

    5.3 Cable Layout PrincipleThe AC power cable to the mains is routed into the power distribution equipment

    compartment from the bottom of the cabinet to connect to the AC power distribution device.

    Communications cables such as the intermediate frequency cable and feeder are routed intothe equipment compartment from the upper part of the compartment side panel. Then the

    communications cables are routed along columns of the rack to connect to devices. Cables ineach compartment are routed along the rack. Cables are routed between compartments by

    using cable holes reserved on the wall board.Figure 5-1shows the cable layout of the

    Mini-shelter.