inverter grounding and overvoltages - ieee power and ... · pdf fileinverter grounding and...

Download Inverter grounding and overvoltages - IEEE Power and ... · PDF fileInverter grounding and overvoltages Michael Ropp, Ph.D., P.E. Northern Plains Power Technologies 1

If you can't read please download the document

Upload: phungkhanh

Post on 06-Feb-2018

235 views

Category:

Documents


4 download

TRANSCRIPT

  • Inverter grounding and overvoltages

    Michael Ropp, Ph.D., P.E.

    Northern Plains Power Technologies

    1

  • Scope

    This presentation will focus on inverter-based DG

    Includes all DC and variable-frequency primary sources

    Solar

    Type IV wind (and Type III in certain cases)

    Battery storage systems

    Looking mostly at transient overvoltage

    2

  • Inverter overvoltage mechanisms

    Ground fault overvoltage (GFO)

    Inverter controls saturation is wrapped up in this one

    Load rejection overvoltage (LRO)

    3

  • Need for detailed modeling

    Specifics of inverter controls and physics are key to understanding transient behavior

    Cant model inverters as constant current sources

    Averaged models must include detailed controls and model the effective gain of the power stage; otherwise GFO and LRO are overpredicted

    4

  • Key point to remember

    5

  • Ground Fault Overvoltage (GFO)

    6

    Pre-fault During an SLG fault

    Vcenter Vn 0

  • GFO and inverterswhy not just require effective grounding?

    Normal procedure is to try to ensure X0/X1 < 3 and R0/X1 < 1 (IEEE 142-2007) using a grounding transformer.

    But for inverters, R1 and X1 are software-defined and not constant, and theres usually a zero-sequence open circuit. IEEE 1547.8 (going to ballot now!) suggests a solution

    Many grounding transformers may impact utility fault detection and coordination.

    Ground potential rise at the PV plant must be considered (be sure to use the right fault currentIEEE 367 clause 4.4).

    7

  • Fundamental mechanisms of GFO

    Assume a Yg-Yg GSU transformer.

    Rotating machines support GFO because they act like voltage sources behind impedance.

    Inverters act as current sources. They do not enforce phase-phase voltage, and thus do not cause GFO.

    The load impedance (usually neglected from the sequence networks) plays a critical role.

    Load completes negative and zero sequences

    Generation-load ratio is critical, as is Yg to delta load ratio

    8

  • Conclusions: inverters and GFO

    Effective grounding of inverters for GFO reasons is probably not necessary.

    Important caveats:

    If the GSU transformer has a delta on the MV (feeder) side, GFO is possible because of the transformer, regardless of DG type.

    If the inverter controls saturate, it may no longer act as a current source, and then it can support GFO.

    9

  • GFO simulation results

    10

  • GFO and islanding detection

    It would be best to separate islanding detection and fault detection

    Islanding detection primarily designed to detect island formation when local generation and loads are very closely matched; has 2 sec to do so

    No generation-load matching during a fault; many other conditions to detect, and needs to act faster

    Inverters could easily have the smarts to do fault detection, especially with Yg-Yg GSU transformers

    11

  • Load Rejection Overvoltage (LRO)

    12

    Isource

  • Load rejection overvoltage

    Load rejection overvoltage can happen with inverters

    However, levels of LRO for inverter-based DG are frequently overpredicted

    NOT linear in generation:load ratio

    Effective gain of inverter power stage drops as AC voltage rises

    Cannot neglect power-limited nature of DG

    Often very short-lived

    13

  • Example LRO case: 1 PV, partial G

    14

    50% irradiance

  • Example LRO case: 2 PVs + WT, full power

    15

    100% irradiance

  • LRO mitigation Because of required speed of response, LRO should

    be mitigated in the inverter

    DTT isnt fast enough

    External meters usually arent fast enough

    Software solutions exist

    Key factors:

    Fast measurements

    Stop gating; dont open a breaker

    No delay in tripping

    Alternative: restrict DG penetration levels

    16

  • LRO testing and certification

    Because LRO is a potential issue but solutions already exist, should incorporate LRO testing into UL-1741 or something similar

    Efforts already under way to do this. Example: the Industry Task Force on Effective Grounding (ITFEG) has been working on such a test for several months.

    17

  • Conclusions GFO likely is not a problem with inverter-

    based DG, but until this is proven many utilities are requiring effective grounding, which brings its own set of challenges

    LRO can be an issue with inverters, but inverter-based solutions exist; testing and certification will be key

    18