slow-front overvoltages

Upload: sorry2qaz

Post on 04-Apr-2018

232 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/29/2019 Slow-Front Overvoltages

    1/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 1 -

    Slow-Front Overvoltages

    Slow-front overvoltages have front durations of some tens to some thousandsof microseconds and tail durations in the same order of magnitude and areoscillatory by nature. They generally arise from:

    line energization and re-energization; faults and fault clearing; load rejections; switching of capacitive or inductive currents; distant lightning strikes to the conductor of overhead lines.

    Slow-front overvoltages have front durations of some tens to some thousandsof microseconds and tail durations in the same order of magnitude and areoscillatory by nature. They generally arise from:

    line energization and re-energization; faults and fault clearing; load rejections; switching of capacitive or inductive currents; distant lightning strikes to the conductor of overhead lines.

    The representative voltage stress is characterized by:

    a representative voltage shape 250/2500 s; a representative amplitude which can be either

    an assumed maximum overvoltage or a probability distribution of the overvoltage amplitudes.

    The representative voltage stress is characterized by:

    a representative voltage shape 250/2500 s; a representative amplitude which can be either

    an assumed maximum overvoltage or a probability distribution of the overvoltage amplitudes.

  • 7/29/2019 Slow-Front Overvoltages

    2/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 2 -

    d

    Slow-Front Overvoltages

    The representative amplitude is the amplitude ofthe overvoltage considered independently from its

    actual time to peak. However, in some systems in

    range II, overvoltages with very long fronts may

    occur and the representative amplitude may be

    derived by taking into account the influence of the

    front duration upon the dielectric strength of the

    insulation.

    The representative voltage shape is the standardswitching impulse: Tp = 250 s, T2 = 2500 s.

    s10 3020

    m

    0

    1

    3

    2

    4

    MV

    U

    1

    +

    2

    T = 250 s

    0

    s

    3

    d

    cr

    T = 850 scr

    T = 750 scr

    T = 650 scr

    T = 450 scr

    T = 250 scr

    see HVT II, Chapter 9:

    3: curve of minimum strength

  • 7/29/2019 Slow-Front Overvoltages

    3/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 3 -

    Slow-Front Overvoltages

    The probability distribution of the overvoltages without surge arrester operationis characterized by *)

    its 2 % values ue2, up2

    its deviations e, p

    its truncation values uet, upt.

    Although not perfectly valid, the probability distribution can be approximated by a

    Gaussian distribution between the 50 % value and the truncation value abovewhich no values are assumed to exist. see next slides

    Alternatively, a modified Weibull distribution may be used.

    (see: IEC 60071-2, Annex C, Annex D)

    *) Indices: e "phase-to-earth"p "phase-to-phase"

  • 7/29/2019 Slow-Front Overvoltages

    4/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 4 -

    Slow-Front Overvoltages

    f(u)

    P(u)

    u

    u

    Normal distribution (Gaussian distribution)Normal distribution (Gaussian distribution)

    2

    121( ) e

    2

    u

    f u

    =

    standard deviation expectation average mean value ofui

    ( ) ( ) du

    P u f u u

    =

    Probability density function of voltage occurrence:

    Cumulative distribution function of voltage occurrence:

  • 7/29/2019 Slow-Front Overvoltages

    5/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 5 -

    Slow-Front Overvoltages

    u f(u) P(u)

    u

    u

    u

    f(u)

    P(u)

    u

    u

    2%-value2%-value

    truncation valuetruncation value

  • 7/29/2019 Slow-Front Overvoltages

    6/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 6 -

    Slow-Front Overvoltages

    P(ue)

    ue / p.u.

    2%

    Example: normal distribution of phase-to-earth overvoltages, definitions acc. to IEC 60071-2(for phase-to-phase voltages accordingly)

    ue2ue2 uet = ue2 + euet = ue2 + e

    50%

    0.1%

    1

    All overvoltages are higher than 1 p.u.

    Overvoltages are characterized by their2% value ue2.

    The difference between the minimum value and the

    2% value is equivalent to 4 standard deviations:

    e 2 e1 4u = ( )e e 20.25 1u =

    ue50 = ue2 - 2eue50 = ue2 - 2e

    All relevant information can be derived from ue2.All relevant information can be derived from ue2.

    4e4e

  • 7/29/2019 Slow-Front Overvoltages

    7/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 7 -

    Slow-Front Overvoltages

    Example: normal distributions of SFO on overhead lines phase-to-earth

    Cumu

    lativedistribution/%

    ue2

    uet

    ue ue

  • 7/29/2019 Slow-Front Overvoltages

    8/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 8 -

    Slow-Front Overvoltages

    The assumed maximum value of the representative overvoltage stress is equal

    to the truncation value of the overvoltages or to the switching impulse protective level Upsof the surge arrester

    whichever is lower.

    The assumed maximum value of the representative overvoltage stress is equal

    to the truncation value of the overvoltages or to the switching impulse protective level Upsof the surge arrester

    whichever is lower.

    see next slide

  • 7/29/2019 Slow-Front Overvoltages

    9/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 9 -

    Slow-Front Overvoltages

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    11001200

    10-4 10-2 10 2 10 41

    Peakvalueo

    fvoltage

    /kV

    Peak value of current / A

    residual voltage at switching impulse current 1 kA

    = switching impulse protection level = 680 kV

    Nominal discharge current In = 10 kA

    Switching impulse current = 1 kA

    residual voltage at In = lightning impulse protection level = 823 kV

    Standard switching impulse current values acc. to IEC60099-4; switching impulse protection level Ups =residual voltage at the highest current amplitude each

    Example forUs = 420 kV

    = 2 Ur= 2 336 kV = 475 kV

  • 7/29/2019 Slow-Front Overvoltages

    10/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 10 -

    Slow-Front Overvoltages

    0 1 2 3 4 5 6

    ue / p.u.

    Probability

    density

    Note:

    In case of overvoltage limitation by surge arresters increase of probability density at ups!

    ups

  • 7/29/2019 Slow-Front Overvoltages

    11/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 11 -

    Slow-Front Overvoltages

    Phase-peak method: from each switching operation the highest peak value ofthe overvoltage on each phase-to-earth or between each combination ofphases is included in the overvoltage probability distribution, i.e. each operationcontributes three peak values to the representative overvoltage probability

    distribution. This distribution then has to be assumed to be equal for each of thethree insulations involved in each part of insulation, phase-to-earth, phase-to-phase or longitudinal.

    Phase-peak method: from each switching operation the highest peak value ofthe overvoltage on each phase-to-earth or between each combination ofphases is included in the overvoltage probability distribution, i.e. each operationcontributes three peak values to the representative overvoltage probability

    distribution. This distribution then has to be assumed to be equal for each of thethree insulations involved in each part of insulation, phase-to-earth, phase-to-phase or longitudinal.

    Case-peak method: from each switching operation the highest peak value of theovervoltages of all three phases to earth or between all three phases isincluded in the overvoltage probability distribution, i.e. each operation

    contributes one value to the representative overvoltage distribution. Thisdistribution is then applicable to one insulation within each type.

    Case-peak method: from each switching operation the highest peak value of theovervoltages of all three phases to earth or between all three phases isincluded in the overvoltage probability distribution, i.e. each operation

    contributes one value to the representative overvoltage distribution. Thisdistribution is then applicable to one insulation within each type.

    IEC recommended practice

    Common practice in the US and Canada [HIL-99]

    (Both methods give only slightly different results; see IEC 60071-2, Annex D and [HIL-99])

  • 7/29/2019 Slow-Front Overvoltages

    12/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 12 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    A three-phase line energization or re-energization produces switchingovervoltages on all three phases of the line. Therefore, each switching operation

    produces three phase-to-earth and, correspondingly, three phase-to-phaseovervoltages.

    A three-phase line energization or re-energization produces switchingovervoltages on all three phases of the line. Therefore, each switching operation

    produces three phase-to-earth and, correspondingly, three phase-to-phaseovervoltages.

    TNA studies have to be performed with several switching operations at randomdistribution of the time instants.

  • 7/29/2019 Slow-Front Overvoltages

    13/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 13 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Range of 2% slow-front phase-to-earth overvoltages at the receiving end due to line energizationand re-energization (IEC 60071-2, Figure 1)

    Values just for estimation purposes; detailed studies required!Values just for estimation purposes; detailed studies required!

  • 7/29/2019 Slow-Front Overvoltages

    14/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 14 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Phase-to-phase overvoltagesIn the evaluation of the phase-to-phase overvoltages, an additional parameter needs tobe added. As the insulation is sensitive to the subdivision of a given phase-to-phaseovervoltage value into two phase-to-earth components, the selection of a specificinstant shall take into account the insulation characteristics.

    Time instant of phase-to-phase overvoltage peak: this instant gives the highest phase-to phase overvoltage value. It represents the highest stress for all insulation configurations,

    for which the dielectric strength between phases is not sensitive to the subdivisioninto components. Typical examples are the insulation between windings or short airclearances.

    Time instant of phase-to-phase overvoltage peak: this instant gives the highest phase-to phase overvoltage value. It represents the highest stress for all insulation configurations,for which the dielectric strength between phases is not sensitive to the subdivisioninto components. Typical examples are the insulation between windings or short airclearances.

    Two particular time instants are of importance (see also next two slides):

    Phase-to-phase overvoltage at the instant of the phase-to-earth overvoltage peak:although this instant gives lower overvoltage values than the instant of the phase-to-phase overvoltage peak, it may be more severe for insulation configurations for which thedielectric strength between phases is influenced by the subdivision into components.Typical examples are large air clearances for which the instant of the positive phase-to-earth peak is most severe, or gas-insulated substations (three-phase enclosed)

    for which the negative peak is most severe.

    Phase-to-phase overvoltage at the instant of the phase-to-earth overvoltage peak:although this instant gives lower overvoltage values than the instant of the phase-to-phase overvoltage peak, it may be more severe for insulation configurations for which thedielectric strength between phases is influenced by the subdivision into components.Typical examples are large air clearances for which the instant of the positive phase-to-earth peak is most severe, or gas-insulated substations (three-phase enclosed)for which the negative peak is most severe.

  • 7/29/2019 Slow-Front Overvoltages

    15/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 15 -

    Time instants of max. UpTime instants of max. Up

    Slow-Front Overvoltages Line Energization and Re-Energization

  • 7/29/2019 Slow-Front Overvoltages

    16/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 16 -

    Dielectric Breakdown of Gases

    Breakdown voltage of positive tip is always lower

    than that of a negative tip (derived for air):

    Ud, positive < Ud, negativeUd, positive < Ud, negative

    memory hook: "positive is negative"

    At alternating voltage stress the breakdown of a strongly inhomogeneousasymmetrical electrode configuration in air generally occurs in the positive half cycle

    At alternating voltage stress the breakdown of a strongly inhomogeneousasymmetrical electrode configuration in air generally occurs in the positive half cycle

    Recall from HVT II:

    Extension of this rule: this is valid only for air insulation!In SF

    6under high pressure (GIS): just the other way round

    At alternating voltage stress the breakdown of a strongly inhomogeneous

    asymmetrical electrode configuration in SF6 under high pressure generallyoccurs in the negative half cycle

    At alternating voltage stress the breakdown of a strongly inhomogeneous

    asymmetrical electrode configuration in SF6 under high pressure generallyoccurs in the negative half cycle

  • 7/29/2019 Slow-Front Overvoltages

    17/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 17 -

    Time instants of max. UeTime instants of max. Ue

    Slow-Front Overvoltages Line Energization and Re-Energization

  • 7/29/2019 Slow-Front Overvoltages

    18/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 18 -

    The 2% phase-to-phase overvoltage can approximately be determined from thephase-to-earth overvoltage:

    three-phase re-energization

    three-phase energization

    Slow-Front Overvoltages Line Energization and Re-Energization

  • 7/29/2019 Slow-Front Overvoltages

    19/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 19 -

    factor2.83factor2.83

    factor2.5factor2.5

    factor2.0

    factor2.0

    Standard insulation levels for range II(IEC 60071-1, Table 3):

    The smaller the factor Ue/Um, thehigher the factor Up/Ue

    Slow-Front Overvoltages Line Energization and Re-Energization

    Comparison with the slide before:

    Um = 300 kV 1 p.u. = 245 kV 850 kV = 3.47 p.u.

    Up2/Ue2 = 1.45

    Um = 300 kV 1 p.u. = 245 kV 850 kV = 3.47 p.u.

    Up2/Ue2 = 1.45

    Um = 420 kV 1 p.u. = 343 kV 1050 kV = 3.06 p.u.

    Up2/Ue2 = 1.5

    Um = 420 kV 1 p.u. = 343 kV 1050 kV = 3.06 p.u. U

    p2/U

    e2= 1.5

    Um = 765 kV 1 p.u. = 625 kV 1550 kV = 2.48 p.u. Up2/Ue2 = 1.6

    Um = 765 kV 1 p.u. = 625 kV 1550 kV = 2.48 p.u. Up2/Ue2 = 1.6

  • 7/29/2019 Slow-Front Overvoltages

    20/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 20 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Possible causes of line switching overvoltages (continued next slide)

  • 7/29/2019 Slow-Front Overvoltages

    21/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 21 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Possible causes of line switching overvoltages

  • 7/29/2019 Slow-Front Overvoltages

    22/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 22 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Sending end

    Sending end

    Receiving end

    Receiving end

    Energizing at voltage peakin phase R (tR = 0)

    Energizing 2 ms after voltagepeak in phase R

    tR = 1 ms, ts = 5 ms, tt = 3 ms tR = 0 ms, ts = 2 ms, tt = 2 ms

    Synchronousswitching

    Non-synchronousswitching

    (by pre-strikingof the contacts)

    ueT =

    1.35

    ueR =1.60

    ueR =

    1.35

    ueR =1.70

    ueS =

    1.40

    ueT=

    1.95

    ueT =

    1.35

    ueT =

    1.85

    ue = 1.35ue = 1.35

    +15%

    ue = 1.70ue = 1.70

    ue = 1.40ue = 1.40

    ue = 1.95ue = 1.95

    +26%

    +39%

    Example: 420-kV line, length 340 km,

    resonant frequency (100200) Hz [DOR-81]

  • 7/29/2019 Slow-Front Overvoltages

    23/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 23 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Measures against line switching overvoltages (continued next slide)

  • 7/29/2019 Slow-Front Overvoltages

    24/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 24 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Measures against line switching overvoltages (continued next slide)

  • 7/29/2019 Slow-Front Overvoltages

    25/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 25 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Measures against line switching overvoltages

  • 7/29/2019 Slow-Front Overvoltages

    26/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 26 -

    Slow-Front Overvoltages Line Energization and Re-Energization

    Measures against line switching overvoltages

    IEC 60071-2: "It should be noted that whenarresters are installed at the ends of longtransmission lines for the purpose of limiting slow-front overvoltages, the overvoltages in the middleof the line may be substantially higher than atthe line ends."

    IEC 60071-2: "It should be noted that whenarresters are installed at the ends of longtransmission lines for the purpose of limiting slow-

    front overvoltages, the overvoltages in the middleof the line may be substantially higher than atthe line ends."

    For this reason AEP (American Electric Power)installed one set of 800-kV transmission linearresters in the middle of the line.

    ABB

  • 7/29/2019 Slow-Front Overvoltages

    27/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 27 -

    Slow-Front Overvoltages Earth Faults

    Highest slow-front overvoltages due to earth faults in isolated neutral systems!Example:

    [DOR-81]

    ue = 2.7 p.u.ue = 2.7 p.u.

  • 7/29/2019 Slow-Front Overvoltages

    28/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 28 -

    Slow-Front Overvoltages Switching Cap. or Ind. Currents

    Restrike of the circuit breakerRestrike of the circuit breaker

    ue = 2.1 p.u.ue = 2.1 p.u.

    Begin of opening of the circuit breakerBegin of opening of the circuit breaker

    Measure against: use ofrestrike-free breakersMeasure against: use ofrestrike-free breakers

  • 7/29/2019 Slow-Front Overvoltages

    29/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 29 -

    Slow-Front Overvoltages Limitation by Arresters

    MO arresters limit switching overvoltages (current peak values 500 A 2 kA)to about:

    Ups (peak value) 2Ur (r.m.s. value) (see slide 9: Ur= 336 kV; Ups = 680 kV)

    Conclusions:

    MO arresters do limit slow-front overvoltages due to line energization and re-

    energization and switching of inductive and capacitive currents. MO arresters usually cannot limit slow-front overvoltages caused by earth

    faults and fault clearing (exception: isolated neutral systems, series

    compensated lines), as their amplitudes are too low.

    Separation effects (protective distance) have not to be taken into account(overvoltages too slow)

    But: exception for long transmission lines voltages in middle and/or end ofline can take considerably higher values than arrester's protection level!

    Separation effects (protective distance) have not to be taken into account(overvoltages too slow)

    But: exception for long transmission lines voltages in middle and/or end ofline can take considerably higher values than arrester's protection level!

    Ur (r.m.s. value) 1 p.u. Ups 2 p.u.

  • 7/29/2019 Slow-Front Overvoltages

    30/30

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 3 - 30 -

    Slow-Front Overvoltages Limitation by Arresters

    Representative voltages in case of MO surge arresters:

    Phase-to-earth: Ure = UpsPhase-to-earth: Ure = Ups

    Phase-to-phase: the lower value of Urp = 2 Ups Urp = Upt (truncation value determined acc. to IEC 60071-2, Annex D)

    Phase-to-phase: the lower value of Urp = 2 Ups Urp = Upt (truncation value determined acc. to IEC 60071-2, Annex D)

    If arresters limit phase-to-earth voltages to less than 70% of their unaffectedUe2-values, the resulting phase-to-phase voltages will be Up 2 Ups of thearrester.

    If arresters limit phase-to-earth voltages to less than 70% of their unaffectedUe2-values, the resulting phase-to-phase voltages will be Up 2 Ups of thearrester.