Introduction to FlashWrite 3.1
Thank you very much purchasing FlashWrite 3.1 (calls "this product" later). This document guides this
product.
Feature of this product
This product have following feature.
As Communication Interface Unit
Monitoring communication data between outdoor unit and indoor unit
Monitoring communication data between indoor unit and remote controller
Monitoring communication data between outdoor unit and outdoor unit (W-Multi)
Monitoring operational data directly from GHP outdoor unit
Monitoring operational data directly from Commercial VirusWasher (aka. VW)
Writing microcontroller's firmware, using with Windows based Flash-Writer software
As Flash-Writer
Downloading microcontroller's firmware onto this product (needs PC)
Writing downloaded microcontroller's firmware, solely with this product (without PC)
Package Contents
This product contains following objects. Inspect if there were no missing components before using this
product.
FlashWriter 3.1 unit itself
Cables (there is 5 cables)
Installer CD-ROM (contains this document file)
Note: The equipped cables are for connecting between this product and air-controller(s). There is no USB
cable equipped. Please purchase commercial USB standard cable.
Details and pictures of contents
FlashWriter 3.1 itself
1 de 15
Cable 1 for Flashing PAC outdoor unit : 4P White ↔ 4P White
Cable 2 for Flashing PAC outdoor unit : 6P White ↔ 6P White
2 de 15
Cable for Flashing GHP outdoor unit : 7P White ↔ 7P White
Cable for Flashing VW unit : 4P White ↔ 2P Blue + 6P Yellow
3 de 15
Cable for Monitoring PAC/GHP communication data : 4P White ↔ Stripped Wire
This cable is for monitoring data purpose only: It is *NOT* required for Flashing microcontrollers.
4 de 15
Extend this cable with crimp contact and clips, if nessessary.
Environment
PCs with USB 1.1/2.0/3.0 port, using following OS
Windows 2000SP4, XP Home/Professional SP2/SP3
Windows Vista / SP1 / SP2 (every Edition)
Windows 7 / SP1 (every Edition)
Notices
Windows 95, 98, Me are NOT supported (Microsoft declared they are outdated)
works for all CPU/Memory
Works both 32bit/64bit OS. (Application program is provided both 32bit/64bit mode.)
Installing Hardware/Driver
This product is fully Plug-and-Play compatible. This product uses standard HID driver provided by
Microsoft, no extra installation is required.
Softwares
This product contain only one software: i.e, download microcontroller's firmware onto this product
(ifloader).
Monitoring softwares are provided separatedly. PC-Based Flash-Writer softwares are provided
separatedly.
Installing ifloader software
If you have installed ifupdate software, first uninstall ifupdate, and then install ifloader. Both ifupdate and
ifloader provide same feature.
Administrator's privilidges are required for installing software. Logon with Administrator or user account
who have enough privilidges. In case for Vista or later, get ready for password for UAC with
Administrator privilidges.
for 32bit OS
Double click ifloader_32bit\setup.exe and install ifloader 32bit. Visual C++ 2010 Runtime Distributable
may be also installed automatically. (In some cases the japanese character is displayed incorrectly: you
can safely ignore it.)
for 64bit OS
Double click ifloader_64bit\setup.exe and install ifloader 64bit. Visual C++ 2010 Runtime Distributable
5 de 15
may be also installed automatically. (In some cases the japanese character is displayed incorrectly: you
can safely ignore it.)
Otherwise, you can install 32bit version (refer for 32bit OS) : all feature is same.
common notice
In case for Vista or later, UAC warns there's no digial-signature for installer. Please continue. If UAC
wants administrator password, type it.
And then follow the instruction.
Connectors
Left side
7P White Socket : for connecting directly to GHP outdoor unit
USB STD B Socket : for connecting to PC/HUB
Right side
6 de 15
4P White Socket
for connecting to PAC outdoor unit
for connecting to commercial VW unit
for connecting to serial line between PAC/GHP outdoor unit and indoor units
Use only central 2pins, to connect serial line (make it open edge 2P)
2P White Socket
for connecting to serial line between indoor unit to remote controller
for connecting to serial line between PAC W-Multi outdoor unit and outdoor unit
6P White Socket
for connecting to ROM/debug line of PAC outdoor unit
How to use as Interface Unit
This product will work as communiceation interface unit, if there is USB connection.
connect this product to PC's USB port (or external USB HUB)
connect this product to the communication line
This document omits details for communication interface. Refer guidance/manuals of monitoring
software.
How to use as Flash-Writer Unit
This product will work as Flash-Writer unit, if no USB connection. We intend to use as following:
7 de 15
Downloading microcontroller's firmware which is provided by e-mail, or web.
This operation is done at the office desk, with PC (and USB connection).
Writing outdoor unit's microcontroller firmware, with connecting cable provided together.
This operation is done at the customer's place, without PC (and no USB connection).
Otherwise, you can write outdoor unit's microcontroller firmware with PC Flash-Writer sofware. (This
product is used only as communication interface, not flash-writer) This case, you must carry PC and this
product to the place near outdoor units (and find the power outlet). You must get PC's Flash-Writer
software, provided separatedly.
Restriction of stand-alone Flash-Writer
There are some restrictions for stand-alone flash-writer of this product:
There must be 1 on 1 connection between the target unit and this product's.
This product can not operate if there are plural units (e.g, indoor units or system controllers).
This product can hold only one microcontroller's firmware.
Especially, GHP H/J1 type outdoor unit contains TWO microcontroller's in one PCB: this product
can write only one (not both) microcontroller's firmware. You need PC's software or two Flash-
Writer3, for writing both microcontroller in the GHP H/J1 type outdoor unit.
Air Conditioners supported by this product
This product supports only following air conditioners:
PAC outdoor units
some U type outdoor units (which uses Flash Microcontroller: 3WAY/Water units only)
all outdoor units A/B type (or later ones)
GHP outdoor units
all outdoor units H type (or later ones)
PAC/GHP indoor units
EQ type
NOTE: GHP G type outdoor units are NOT SUPPORTED (connection cable is not compatible)
How to download microcontroller's firmware onto this product
Microcontroller's firmware file is usually provided with suffix .mot .hex .fwi .
associating application to suffix
You can associate ifloader application to suffix .mot .hex .fwi, when:
Installing ifloader application (automatically opens ifloader)
Manually invoking ifloader application (from start button)
Right click to microcontroller's firmware file, selecting "Open With..." and check "Always use...",
open with ifloader.
You can open automatically microcontroller's firmware file with ifloader, once associated.
not associating application to suffix
8 de 15
Drag & Drop microcontroller's firmware file to the ifloader application/shortcut icon.
Notice
This product can only download flash microcontroller's firmware. (No upload feature. No generic
mass-storage feature.)
This product displays checksum/firmware version/firmware ID onto the LCD screen, if and only
successful download completion. If no information is shown when ifloader application completes : This
means that download is not successful. Please try again.
If no information is shown after retry,
The microcontroller of the target firmware file is not supported by this product. Please update
firmware of this product (contact with your dealer).
Flash memory of this product is reached its life limit. Please purchase new one.
Connecting to Outdoor unit
Power supply of outdoor unit is nessessary to flash outdoor units. This product can get power from
outdoor unit, extra power supply cable is not nessessary.
Connecting to PAC outdoor unit
Actual connecting scheme is different for each outdoor unit. Refer your TARGET-PRODUCT service
manual in advance.
Connecting with 6P-6P cable
9 de 15
Writer cable 6P is to be connected to the 6P socket on the PCB. 6P socket is named 'ROM' or 'DEBUG' or
'FLASH', etc., may be different in some cases. 6P socket color may be BLACK or RED or WHITE, etc.,
may be different in some cases.
10 de 15
For using this connection, you need not remove cables from OC/EMG socket.
Connecting with 4P-4P cable
11 de 15
DO NOT PLACE THIS PRODUCT DIRECTLY ON THE PCBS!
12 de 15
Be sure "Terminate" pin on the PCB is "SHORT". If "OPEN", temporarily change the short-pin onto
"SHORT".
With the equipped 4P-4P cable, connect this product and ROM socket on the outdoor unit's PCB. Both
socket/plug is white 4P (JST XA 4P). If the outdoor unit is already connected to the indoor units or
controllers, remove the cable on OC (2P BLUE) or EMG (2P BROWN) plug on the outdoor unit's PCB.
Otherwise Error Happens!
connecting with 7P-7P cable
It is same procedure to Connecting to GHP outdoor unit.
Connecting to GHP outdoor unit
With the equipped 7P-7P cable, connect this product and ROM socket on the outdoor unit's PCB. Both
socket/plug is white 7P (JST XH 7P).
DO NOT PLACE THIS PRODUCT DIRECTLY ON THE PCBS!
Connecting to Commercial VW unit
13 de 15
With the equipped 4P - 6P+2P cable, connect this product and OC/T10 socket on the VW PCB.
DO NOT PLACE THIS PRODUCT DIRECTLY ON THE PCBS!
Flash
Power on the outdoor unit, if not.1.
Check the ID/Version/CheckSum on the LCD display. If OK, press button approx. 1sec.2.
Buzzer rings and flash starts. LCD displays the state of progress.3.
Buzzer rings at end of flash.4.
If failure, check connection and/or downloaded microcontroller's firmware ID/Version, then retry.5.
After Flashing
Remove this product from the outdoor units.
Revert all socket/plugs/short-pins same to the beginning, if you changed.
Troubleshooting for flash error
Flashing error may happen in some reasons: if error happened, DO NOT POWER OFF THE UNITS
(Target/FlashWriter 3.1). First check the connections described above, and then retry.
LCD displays "Not Found" or "ID Mismatch"
Connection is not 1-on-1 (forgot removing wires on OC/EMG socket)
14 de 15
Microcontroller software is not match to the target
One or more Connection socket/plug are wrong (This may happen both side of this product
and target unit)
Communication wire is NOT terminated
LCD displays "Error! Erase"
Connection is not 1-on-1 (forgot removing wires on OC/EMG socket)
The target has non flash-microcontroller (mask/OTP microcontroller)
Exceeded flash-microcontroller's erase/write life limit
LCD displays "Error! Write" or "Error! CheckSum"
Connection is not 1-on-1 (forgot removing wires on OC/EMG socket)
Exceeded flash-microcontroller's erase/write life limit
Specifications
PC Interface : USB SPEC2.0 Full-Speed (USB3.0 compliant)
PC Cable : USB standard cable (STD A-STD B)
USB transfer : Human-Interface-Device (HID1.10) based Interrupt transfer
Power Source : Self-Powered (connecting to outdoor unit) or Bus-Powered (connected to USB)
Power Consumption : Max 200mA (in Bus-Powered)
Surprise Removal Compliant
History of this document
Document 1.04 2012.Mar.10
rewrite for FlashWriter 3.1
Document 1.03 2011.Aug.21
Add Desciption of Windows 7, add notes for connecting with ACC-CR-FL3
Document 1.02 2007.Jul.27
Add Desciption of Windows Vista
Document 1.01 2007.Apr.12
Add pictures/VW, add notes ifupdate spec change
Document 1.00 2006.Dec.31
-- First Version --
15 de 15