Internal, Oil-immersed Secondary Circuit Breakers Transformers subjected to overloading or applied on lines without overload protection should be self-protected. Self-protected distribution transformers offer a complete, unified system of overload protection. The primary means of protecting the transformer is the circuit breaker, which is designed to give adequate protection from short circuits and severe overloads.

Upload: lyxuyen

Post on 02-May-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

Made in USA

Internal, Oil-immersed Secondary Circuit Breakers

Transformers subjected to overloading or applied on lines without overload protection should be self-protected. Self-protected distribution transformers offer a complete, unified system of overload protection. The primary means of protecting the transformer is the circuit breaker, which is designed to give adequate protection from short circuits and severe overloads.

Page 2: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

Options:

Signal Light - One of the features of the self-protected pole-type transformer is the signal light. When the transformer is thermally overloaded, the signal light will light, serving as visual evidence that an unusual overload has occurred on the transformer.

Emergency Overload - Through the use of the emergency overload lever, self-protected transformers are able to carry overloads in excess of those normally permitted by the circuit breakers. If a transformer circuit breaker has tripped and the bimetals are still at trip temperature, the use of the emergency overload lever may allow the operator to close the circuit breaker to restore service.

Tri Clamp Low Voltage Bushing

The ECI TriClamp Low Voltage Bushing is equipped with a 5/8-tt-UNC-2A threaded stud.

Page 3: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

C T Junction Box

The ERMCO Components, Inc., CT junction box provides a means to make external connections to current transformer leads when CT's are internally mounted within a power transformer.

Features:

• Designed for operation under oil • Lead attachment uses only standard tools • Has 21 connection terminals

Rugged cast aluminum housing eliminates the need for painting

Drip Guard

The Drip Guard for bayonet fuse assemblies prevents the dripping of transformer insulating fluids onto the rubber molded terminators or cables. Note the positive latching mechanism which prevents accidental removal.

Page 4: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

Dry-well Fuseholders for Current-limiting Fuses

The ECI dry-well fuseholder provides a method of placing dead-front type current-limiting fuses within the transformer. ERMCO Components' dry-well fuseholder design is suited to both single- and three-phase padmount applications. With the addition of the loadbreak function, the fuseholder provides an economical combination current-limiting fuse and loadbreak switch. The design provides the benefit of easy hotstick operability to a single fuse.

Loadbreak fuseholders for padmounted transformers are available at 8.3 and 15.2 kV (125 kV BIL). A special loadbreak design is available with parallel fuses for high current applications. Non-loadbreak fuseholders for padmounted transformer applications are available at 8.3, 15.2, and 21.1 kV (125 kV BIL), both standard and submersible construction. A 21.1 kV (150 kV BIL) rating is available in standard construction only.

Under Oil Arrester Disconnect Switch

The ECI arrester disconnect switch provides a means of performing electrical t ti f di t ib ti t f th t i d ith i t l d il

Page 5: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

testing of distribution transformers that are equipped with internal under oil lightning arresters.

The arrester disconnect switch must be open before dielectric testing of the transformer to prevent misleading results and possible arrester damage.

To open the switch, unscrew the pipe plug, pull the plug out to the stop to disconnect the arrester ground. Reverse the procedure to close the switch.

This switch is for testing the transformer. It is a de-energized switch only.

Bayonet Fuse Links

Two types of fuse elements are available; a FAULT SENSING fuse (catalog numbers 9F54MFC---) and a LOAD SENSING fuse (catalog numbers 9F54LFC---). The fault sensing fuse is current sensitive and will isolate the transformer from the system in case of a fault. The load sensing fuse is sensitive to both current and oil temperature and will protect against overloads as well as faults.

Catalog Number Reference

Number (1) Curve

Number (2) Ampere Rating

Fault Sensing Fuse Links

9F54MFC060 9F54MFC080 9F54MFC100 9F54MFC120 9F54MFC140 9F54MFC160 9F54MFC170

353C06 353C08 353C10 353C12 353C14 353C16 353C17

C06 C08 C10 C12 C14 C16 C17

10 15 25 40 65 100 140

Load Sensing Fuse Links

9F54LFC030 9F54LFC050 9F54LFC080 9F54LFC180 9F54LFC120

358C03 358C05 358C08 358C10 358C12

C03 C05 C08 C10 C12

3 8 15 25 50

1. ECI and Cooper bayonet fuse links are electrically and mechanically interchangeable.2. ECI and Cooper bayonet fuse link time-current curves are essentially indentical and have the same curve numbers.

Page 6: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

Isolation Link

The ECI Isolation Link is used in a series with bayonet type expulsion fuses to provide extra protection during re-fusing operations. They are coordinated to operate at currents that exceed the one-shot rating of the expulsion fuse used in pad or vault type transformers. The isolation link will melt during transformer failure so the opened primary circuit of a failed transformer cannot be re-energized by the line crew.

Low Voltage Distribution Arrester

The LVDA Light Duty Distribution Class surge arrester is designed and tested in accordance with ANSI/IEEE C62.11 requirements. The LVDA is designed for protection at the distribution transformer 120/240 VAC secondary bushings. Various IEEE and industry studies have determined that impulse voltages from lightning and other sources can enter the transformer secondary and cause extensive damage. Such surges are typically beyond the energy handling capability of Secondary Class Surge Arresters.

Page 7: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

Low Voltage Breaker Operating Detail

The new Operating Detail with integral light eliminates the need for a second hole in the transformer tank wall to accommodate the overload indicating light.

Tap Changer Switch

The ERMCO Components, Inc. externally operated single phase, under oil tap changer switch for distribution transformers.

The tap changer switch cap is removed and reversed to make the cap an operating wrench. The cap-wrench is equipped with a key, preventing removal until the switching operation is complete.

An indicating arm kit with locking plate and screw is available if conversion from the cap-wrench is desirable.

Features:

• Designed for operation under oil L d tt h t l t d d t l

Page 8: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

• Lead attachment uses only standard tools • Connection configurations:

o Axial tab type terminals with holes for 1/4" dia. bolts (100 ampere rating)

o Radial, #12-#10 crimp terminals (100 ampere rating).

Ratings:

• Maximum continuous current: 100 Amps • Impulse 150 kV

High Voltage Bushing Well

The ERMCO Components, Inc. SURE MAKE separable connector high voltage bushing well is designed for the termination of primary leads in oil filled devices such as padmounted transformers. The bushing well mating interface conforms to the ANSI/IEEE Std. 386 for Separable Insulated Connectors and will accept switch modules (bushing well inserts) complying with the Standard.

Design Features:

• Insulated body is molded of a polyester formulation designed for excellent electrical and mechanical properties.

• The ground shield coating is oil resistant. • The removable stud version is tin plated for corrosion resistance and

ease of removal. o Use a 5/35" Allen wrench to replace stud, and torque to 100

inch lbs.

Ratings:

• Maximum Continuous Line to Ground Voltage 15.2 kV RMS • Continuous Current 200 AMP RMS • Basic Impulse Level 125 kV Crest

Page 9: Internal, Oil-immersed Secondary Circuit Breakersthaivirawat.com/Documents/Products/Pdf/ECI.pdf · Internal, Oil-immersed Secondary Circuit Breakers ... a FAULT SENSING fuse ... Oil-immersed

200 AMP, 35 kV Class 3Ø Rated Integrated Bushing

The ERMCO Components, Inc. SURE MAKE separable connector 200 amp, 35 kV Class Three Ø Rated Loadbreak Integrated Bushing meets all requirements of ANSI/IEEE Std. 386 - Separable Insulated Connector Systems, and combines the advantages of reliable one-piece design with the operating features required for underground distribution switching. The bushing is designed for padmounted transformers, switchgear and other apparatus filled with transformer oil.

Design Features:

• Insulating body is molded of an epoxy formulation designed for excellent electrical and mechanical properties.

• The ground shield coating is oil resistant. The coating covers from the elbow cuff mating surface and extends 0.50 inch beyond the sealing gasket through the tank wall.

Ratings:

• Maximum Continuous Voltage 35 kV RMS • Maximum Continuous Line to Ground Voltage 21.1 kV RMS • Maximum Continuous Line to Line Voltage 36.6 kV RMS • Continuous Current 200 AMP RMS • Switching 10 Operations at 200 amp RMS at 36.6 kV • Fault Closure 10,000 amp RMS Symmetrical at 36.6 kV after 10

switching operations for 0.17 seconds • Basic Impulse Level 150 kV Crest