insulating steel stud back-up & masonry veneer
TRANSCRIPT
Insulating Steel Stud Insulating Steel Stud BackBack--Up Up
for Masonry Veneerfor Masonry VeneerHerbert Slone
Registered ArchitectTechnical Manager, Commercial Insulation
1.5 Hour, HSW
Copyright Materials
This presentation is protected by US and InternationalCopyright laws. Reproduction, distribution, display and use
of the presentation without written permission of OwensCorning is prohibited.
©Owens Corning 2007
Learning Objectives
For steel stud/foam sheathing/brick veneer,
1. Understand thermal performance.
2. Understand vapor migration and simple evaluation methods to estimate potential moisture build-up.
3. Understand bracing and brick tie methods.
4. Understand code/fire design considerations.
1 “ci” = Insulating Sheathing
What is the benefit?¤ Minimizes thermal
bridging¤ Minimizes transverse
flow
1
Total R-ValueCalculation Method
w/ Gypsheathing
Series 14.75
7.75
7.45
Correction FactorModified Zone Method
w/ “ci”sheathing
18.10
11.10
11.90
Effective “R” for Steel Stud Walls w/ “ci”
INTERIOR AIR FILM
1/2” GYPSUM BOARD
STEEL STUD R-13 BATT INSULATION
R-3.8 FOAM INSULATION
AIR SPACE
MASONRY
EXTERIOR AIR FILM
3.5” stl stud @ 16”o.c., R13 Batt + R3.8 continuous insulation
Wall Plan Section
Warm Interior
An insulating sheathing, “ci”, reduces heat loss by minimizing lateral heat energy transfer through the large sheathing surfaces of the wall.
1 Thermal Performance: Summary
2 “ci” must be water resistant…….
the Brick Industry Association recommends the use of “inherently moisture resistant”sheathing such asclosed cellextruded polystyrene.
Due to expected exposure to moisture……
2“ci” joint treatment……..
must be water resistant.
Batt Insulation
Sealant under brackets
T&G Joint w/Tape or SealantXPS Sheathing
Brick TieBrick VeneerVapor RetarderGypsum Board
Foundation Wall
Steel Stud
2 Static Dewpoint, “Glaser Method”
Where Actualfalls below Dew Point, condensation is suspected under that set of static conditions.
2 Change to low perm facer on FG…Winter Conditions: Exterior, 0OF, 50% RH; Interior, 72OF, 30% RH
1” XPS Sheathing0.02 (low) perm Faced FG
No Dew Point in FG or XPS. VERY GOOD
Per Modified Zone Method RT= 12.2
0
10
20
30
40
50
60
70
80
90
100
Tem
pera
ture
(F)
Foil
Face
d FG
Bat
t R11
Inte
rior A
ir Fi
lm
1/2"
Gyp
sum
1/2"
Gyp
sum
1" A
ir Sp
ace
4" B
rick
Ven
eer
Exte
rior
Air
Film
Actual Temp. Dew Point Temp
2 Summer/Southern, Internal VR
Gyp Exterior Sheathing0.5 perm Foil Faced FG
Dew Point at retarder,UNDESIRABLE.
Summer Conditions: Exterior, 95OF, 95% RH; Interior, 72OF, 50% RH
3 Carefully Consider Bracing of Studs
In theory, all components act together………brick veneer, sheathing, studs, act as a composite assembly, resisting out-of-plane loads by each taking a portion of the load relative to it’s stiffness, span length, and the ability of the brick ties to transfer load between brick and framing.
3In reality, they don’t………over time, the brick and sheathing are continually flexed. Brick cracks, sheathing to stud connections deteriorate around fastener heads, sheathing wetting may occur. Composite action is lost.
Wind Load
Carefully Consider Bracing of Studs
3Deflection Bracing
for all Sheathing TypesAssume that the entire out-of-plane load must be resisted by the steel stud and bracing.
3 Brick Ties for XPS Insulating Sheathing
Anchors and ties:
•Connect directly to steel studframing.
•Don’t rely on the compressive strength of the sheathingsurface to maintain a stable base for the tie.
3 Penetrating Brick Tie Types
These types penetrate the sheathing layer, making a solid connection to transfer wind loads directly to the steel stud framing.
3 Unacceptable Brick Tie Types
Some minimize steel through the insulating layer to minimize thermal bridging, however, efficient load transfer must be the critical priority.
Steel Stud/Brick Veneer Fire Resistance
System fire resistance ratings must be established.
• Exterior Wall Rating (Time, ASTM E119)• Non-Combustible Wall w/ Combustible
Components (Pass/Fail, NFPA 285)• Perimeter Joint (Time, ANSI/UL 2079)
4
Exterior Wall Fire Resistance Rating4ASTM E119 Fire Resistance Furnace
Underwriters Laboratories, Northbrook, IL
Exterior FaceExterior Face Interior FaceInterior Face
Foam & fiber glassFoam & fiber glassgone after 3 hourgone after 3 hourexposureexposure
Exterior Wall Fire Resistance Rating4V434; 1 hour interior.1 hour exterior.Steel stud.Load bearing.
Foam sheathing (directly over stud).
Fiber glass or mineral wool in cavity.
Brick veneer.
4 NFPA 285: Multi-Story Test
Stud CavityFiber Glass
Type IV XPSSheathing
Test Window Opening
Mineral Wool Fire Safing
4 NFPA 285: Window Head
MW Fire Safing
4 NFPA 285: Fire Exposure
4 NFPA 285: Test Result, PASSNo flame propagation. Limited melt back.
4 ANSI/UL 2079 Perimeter Joint
Unrated Rated
Sill Detail
PerimeterJoint:assumes nonatural firestop.
Head Detail
4 Rated Joint Schematic
Mineral woolcovered with spray sealant
Gypsum insideand out.