instructions: panel enclosures - layout, frame - abutting...
TRANSCRIPT
Pane
l Enc
losu
res -
Lay
out,
Fram
e - A
butt
ing,
VFD
with
AC.
dwg
SHEET NO.
DS-32.4DATE: 9/01/2016
OVERHEAD
RIGHT SIDE
LEFT SIDE
FRONT
TOP VIEW
FRONT VIEW
BOTTOM VIEW
BACK VIEW
BACK
END VIEW
REC1
REC2
PUMP 1
PANEL
ENC2
PUMP 2
PANEL
ENC2
PUMP 2
PANEL
PUMP 1
PANEL
POWER
PANEL
ENC1
(SEE
NOTE 2)
CONTROL
PANEL
ENC1
POWER
PANEL
ENC1
CONTROL
PANEL
ENC1
PUMP 1
PANEL
ENC2
PUMP 2
PANEL
ENC2
XF1
POWER
PANEL
CONTROL
PANEL
UTILITY
POWER
EMERGENCY
POWER
18"
42"
24"
24" 24"
53"
36" 36"
84"
MOTOR
POWER
AND
CONTROL
51"
72"
36"
30"
24"
18"
66"
36" 36"
24"
54"
2"
42"
19" 19"
23" 23"
2" 2"
37"
2"
2"
12"
18"
24"
24" 24"
72"
36"
24"
18"
48"
24"
XF1
XF1
HVAC1
HVAC2
HVAC1
HVAC2
MOUNT AIR CONDITIONER AS FAR
FORWARD AS POSSIBLE TO ALLOW
FOR MAXIMUM AIRFLOW (TYP.)
1"C (MIN) CARFLEX LIQUIDTIGHT
FLEXIBLE NONMETALLIC CONDUIT
FOR PRIMARY AND SECONDARY
TRANSFORMER CONDUCTORS
SINGLE HORIZONTAL 3" ANGLE,
3 PLC'S TO SUPPORT INTERNAL
CABLES AND CONDUIT. WELD
BETWEEN OTHER (3) SUPPORTS
PERFORATED METAL, SS
STAGGERED
1
4
" HOLES @
5
16
" CENTERS
DIRECTMETALS.COM
FRONT OF BASE WILL HAVE REMOVABLE PANELS
AT EACH OPENING AS SHOWN, ATTACH SCREENS
TO BACK SIDE OF REMOVABLE PANELS.
*SEE RACK DETAILS BELOW
FOR ADDITIONAL INFORMATION
AND DIMENSIONS
SPOT WELD AS NEEDED
DRILL (16)
5
8
" DIA. HOLES AS
SHOWN, CENTERED ON ANGLE
ENTIRE BASE MADE FROM
3" STAINLESS STEEL ANGLE, WELDED
2" X 2" S.S. ANGLE
FOR VERTICAL MEMBERS
2" WIDE FLAT S.S.
FOR HORIZONTAL
MEMBERS
HVAC1
HVAC2
HVAC2HVAC1
GEN REC
(SEE NOTE 2)
PANEL NOTES
1. SEE SHEET DS-34 FOR LEGENDS AND TAGS.
2. GENERATOR RECEPTACLE AND POWER PANEL TO
BE ON THE DRIVEWAY-SIDE OF THE ENCLOSURES.
FRAMEWORK NOTES
1. TOP AND BOTTOM OF BASE TO BE LEFT OPEN.
2. DRILL TOP OF BASE TO ATTACH ENCLOSURES AS
REQUIRED.
3. DRILL BOTTOM OF BASE TO ATTACH TO SLAB AS
REQUIRED.
BASE FRAMEWORK LAYOUT
ABUTTING EXTERIOR PANEL
AND CONDUIT LAYOUTS
RACK DETAILS
FRONT & SIDE VIEWS
XF1XF1
XF1XF1
50"
MOTOR
POWER
AND
CONTROL
LEVEL TRANSDUCER,
PRESSURE TRANSDUCER,
FLOW METER, & ANTENNA COAX
BACKUP
FLOATS
*SEE RACK DETAILS
BELOW FOR ADDITIONAL
INFORMATION AND
DIMENSIONS
LS2 LS3
LS1 LS4
(480V ONLY)
480V
ONLY
Instructions:Select this sheet for abuttingpanel layouts with VFD startertype.
SEE NOTE #10 ON SHEET DS-0.1
Instructions:Include Transformer and Rack for
480V systems only, and remove for208V/240V systems.