Page 1: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Document n° 1350-1 ~ 14/11/2008

Fujitsu General (Euro) GmbH

Werftstrasse 20

40549 Düsseldorf

Germany

Heat pump air/watersplit 1 service

Installation and

operating manual

intended for professionals

To be saved

for future consultation

FR EN NL ITDE

Page 2: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

Complies with :

- Low tension Directive 73/23/CEE, under standard EN60335-1.

- Electromagnetic compatibility Diretive 89/336/CEE

- Directive 98/37/EC Machinery,

- Directive for pressurised equipment 97/23/EC,

- Directive for labelling energy consumption 2002/31/EC

This appliance also conforms to:- Regulation 842/2006 of the european parliament on certain fluorinated greenhouse gases

- The standards relating to the product and the testing methods used:

Air-conditioners, refrigeration units and heat pumps with compressor driven by electric motor for heating and

refrigeration EN 14511-1, 14511-2, 14511-3, and 14511-4

- To standard EN 12102: Air-conditioners, heat pumps and dehumidifiers with compressor driven by electric motor.

Measurement of airborne noise. Determination of acoustic power level.

Packing list

Heat pump Outdoor unit Hydraulic module

Designation Code Model Code Model Code

AOYA18LALL WSY 050 DA 023140

AOYA18LALL WSY 065 DA 023139

AOYA24LALL WSY 080 DA 023138

AOYA30LBTL WSY 095 DA 023137

AOYA45LATL WSY 128 DA 023136

AOY54LJBYL WSY 155 DA 023135

Optional equipment

• 2nd circuit hydraulic kit (UTW-KZSXA)- for connecting 2 heating circuits

• DWH kit (UTW-KDWXA)- for connecting a DHW tank (with built-in electricalbackups)

• Boiler connection kit (UTW-KBSXA)- for connecting a boiler to the heat pump

• Room thermostat T55 (UTW-C55XA)- For correcting the ambient temperature

• Remote control T75 (UTW-C75XA)- For correcting the ambient temperature andprogramming the heat pump.

• Cooling kit (UTW-KCLXA)

• Swimming pool kit (UTRPOK)

• High flow rate circulating pump kit ()For the installation of 1 circuit floor heating withmodel 128 and 155

• Cool ing ki t (UTW-KCHXA) compat ib le wi thcirculating pump (128 and 155)

Scope of application

This heat pump provides:

- Heating in winter,

- Control of two heating circuits*,

- Production of domestic hot water* (provided thatcombined with a DHW tank).

- Cooling in summer*.

- Ins ta l la t ion wi th bo i le r connect ion as asupplementary heating for the coldest days*.

* : These options require the use of additional kits(see § "Optional equipment").

Page 3: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 3

Heat pump, Splir 1 service

Contents

Description of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 4

Package . . . . . . . . . . . . . . . . . . P. 4

Definitions . . . . . . . . . . . . . . . . . P. 4

Specifications . . . . . . . . . . . . . . . P. 5

Heating power curve . . . . . . . . . . . P. 6

Description. . . . . . . . . . . . . . . . P. 11

Operating principle . . . . . . . . . . . P. 12

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 14

Regulation installation and maintenance

conditions . . . . . . . . . . . . . . . . P. 14

Unpacking and reservations . . . . . . P. 14

Receipt . . . . . . . . . . . . . . . . . . . . P. 14

Handling . . . . . . . . . . . . . . . . . . . P. 14

Accessories provided. . . . . . . . . . . . . P. 14

Installation position . . . . . . . . . . . P. 14

Installation of the external unit . . . . . P. 14

Installation precautions . . . . . . . . . . . P. 14

Outside unit positioning . . . . . . . . . . . P. 16

Condensate drain hose. . . . . . . . . . . . P. 16

Installing the hydraulic module . . . . . P. 17

Installation precautions . . . . . . . . . . . P. 17

Positioning the hydraulic module. . . . . . . P. 17

Refrigeration connections. . . . . . . . P. 18

Rules and precautions . . . . . . . . . . . . P. 18

Refrigeration connections . . . . . . . . . . P. 18

Creating the flarings . . . . . . . . . . . . . P. 18

Shaping the refrigeration pipes . . . . . . . P. 19

Connecting the flared connections . . . . . P. 19

Filling the installation with gas . . . . . P. 21

Creating a vacuum and filling the refrigeration

connections with gas . . . . . . . . . . . . . P. 21

Sealing test . . . . . . . . . . . . . . . . . . P. 21

Additional charge . . . . . . . . . . . . . . . P. 22

Connecting

the heating circuit hydraulically . . . . P. 23

General . . . . . . . . . . . . . . . . . . . . P. 23

Rinsing out the installation . . . . . . . . . . P. 23

Filling and purging the installation . . . . . . P. 23

Electrical connections . . . . . . . . . P. 24

Characteristic of the electrical supply . . . . P. 24

General remarks on electrical connections . P. 24

Overview of all the electrical connections . . P. 25

Cable section and protection rating . . . . . P. 25

Electrical connections on outside unit side . P. 26

Electrical connections on the hydraulic module

side . . . . . . . . . . . . . . . . . . . . . . P. 27

External sensor . . . . . . . . . . . . . P. 29

Room thermostat and/or remote control P. 29

Start-up . . . . . . . . . . . . . . . . . P. 30

Configuring the room thermostat . . . . P. 30

Configuring remote control . . . . . . . P. 30

Regulation system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 31

User interface and remote control T75

(Option) . . . . . . . . . . . . . . . . . P. 31

Room thermostat T55 (Option) . . . . . P. 32

Temperature control. . . . . . . . . . . P. 32

Manual adjustment . . . . . . . . . . . P. 32

Self-adaptation . . . . . . . . . . . . . P. 32

Parametering the setting . . . . . . . . P. 34

General . . . . . . . . . . . . . . . . . . . . P. 34

Setting parameters . . . . . . . . . . . . . . P. 34

List of function lines (settings, diagnosis, sta P. 34

Page 4: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

4 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

Configuring the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 46

Configuration 1, 2, 3 or 4:

heat pumps with electric back-ups . . P. 47

Hydraulic connections . . . . . . . . . . . P. 47

Electrical connections . . . . . . . . . . P. 47

Parametering the setting . . . . . . . . . P. 47

Special cases . . . . . . . . . . . . . . . P. 47

Electrical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 52

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 57

Faults displayed on hydraulic module . P. 57

Faults displayed on the external unit . P. 58

Information display . . . . . . . . . . . P. 59

Instructions for the user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 60

1 Description of the unit

1.1 Package

• 1 package: Outside unit

• 1 package: hydraul ic module and exter iortemperature sensor

1.2 Definitions

Split: The heat pump consists of two elements (anexternal unit for outside and a hydraulic module forinside the dwelling).

Air/water: The surrounding air is the energy source.This energy is transmitted to the water in the heatingcircuit by the heat pump.

Inverter: the fan and compressor speeds aremodulated according to the heating requirements.

This technology enables you to save on energy andoperate on a single-phase power supply, whateverthe heat pump's output, by avoiding heavy intensitieson start-up.

COP (coefficient of performance): this is therelationship between the energy transmitted to theheating circuit and electrical energy consumed.

Page 5: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

1.3 Specifications

Designation, Model . . . . . . . . . . . . . . . . . . . . . . . . 050 . . . . 065 . . . . 080 . . . . 095 . . . . 128 . . . . 155

Nominal heating performances (external temperature/ initial temperature)

Heat output

+7 °C / +35 °C - Floor heating system . . . . kW . . . . . . 5 . . . . . 6,5 . . . . . 8 . . . . . 10,3 . . . . 12,8 . . . . 15,5

-7 °C / +35 °C - Floor heating system . . . . kW. . . . . . 4,8 . . . . . 5,6 . . . . . 7 . . . . . 8,1 . . . . . 11. . . . . 13,8

+7 °C / +45 °C - Low temperature radiator . kW . . . . . 4,15 . . . . 5,4 . . . . . 6,2 . . . . . 8,3 . . . . . 9,7 . . . . 13,3

-7 °C / +45 °C - Low temperature radiator . . kW . . . . . 4,05 . . . . 5,1 . . . . . 5,9 . . . . . 7,3 . . . . . 8,3 . . . . . 11

Power absorbed

+7 °C / +35 °C - Floor heating system . . . . kW . . . . . 1,16 . . . . 1,63 . . . . 1,88 . . . . 2,57 . . . . 3,12 . . . . 3,88

-7 °C / +35 °C - Floor heating system . . . . kW . . . . . 1,75 . . . . 2,24 . . . . 2,54 . . . . 3,52 . . . . 3,79 . . . . 5,3

+7 °C / +45 °C - Low temperature radiator . . kW . . . . . 1,15 . . . . 1,61 . . . . 1,88 . . . . 2,51 . . . . 3,13 . . . . 4,09

-7 °C / +45 °C - Low temperature radiator . . kW . . . . . 1,72 . . . . 2,32 . . . . 2,62 . . . . 3,48 . . . . 4,61 . . . . 5,37

Nominal coefficient of performance (COP)

(+7 °C / + 35 °C) . . . . . . . . . . . . . . . . . . - . . . . . . 4,3 . . . . . 4 . . . . . 4,25 . . . . . 4 . . . . . 4,1 . . . . . 4

Electrical characteristics

Supply voltage (50 HZ) . . . . . . . . . . . . . . . V . . . . . 230 . . . . 230 . . . . 230 . . . . 230 . . . . 230 . . . . 230

Maximum start-up current of the appliance . . . . A . . . . . 10,5 . . . . 10,5 . . . . 12,9 . . . . 15,3 . . . . 22,6 . . . . 25,9

Nominal intensity . . . . . . . . . . . . . . . . . . A . . . . . . 8,3 . . . . . 8,3 . . . . 10,6 . . . . 11,7 . . . . 16,7 . . . . 20,6

Maximum current of the electrical back-ups . . . . A . . . . . . 13 . . . . . 13 . . . . . 13. . . . . 26,1 . . . . 26,1 . . . . 26,1

Power of the electrical back-ups . . . . . . . . . kW . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 6 . . . . . . 6 . . . . . . 6

Real power absorbed

- By the fan . . . . . . . . . . . . . . . . . . . W . . . . . . 54 . . . . . 54 . . . . . 65 . . . . . 103 . . . . 2x103 . . . 2x103

- By the circulation pump . . . . . . . . . . . . W . . . . . 113 . . . . 113 . . . . 113 . . . . 113 . . . . 151 . . . . 151

Maximum power absorption

- By the Outside unit . . . . . . . . . . . . . . W . . . . . 2600 . . . . 2600 . . . . 2930 . . . . 3500 . . . . 5150 . . . . 5900

Hydraulic circuit

Maximum operating pressure . . . . . . . . . . . bar . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 3

Hydraulic system flow rate

4°C<�t<8°C (nominal conditions)

- minimum . . . . . . . . . . . . . . . . . . . . . l/h . . . . . 540 . . . . 600 . . . . 860 . . . . 1000 . . . . 1380 . . . . 1670

- maximum . . . . . . . . . . . . . . . . . . . . . l/h . . . . . 1100 . . . . 1400 . . . . 1700 . . . . 2100 . . . . 2700 . . . . 3300

Various

Weight of Outside unit . . . . . . . . . . . . . . . kg . . . . . . 40 . . . . . 40 . . . . . 44 . . . . . 64 . . . . . 98 . . . . . 105

Noise level at 5 meters (Outside unit). . . . . . . dB . . . . . . 39 . . . . . 39 . . . . . 40 . . . . . 41 . . . . . 40 . . . . . 40

Weight of hydraulic module (empty/full of water) . kg. . . . 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5

Water capacity of the hydraulic module . . . . . . . l . . . . . . 25 . . . . . 25 . . . . . 25 . . . . . 25 . . . . . 25 . . . . . 25

Heating system operating limits

Exterior temp mini/maxi . . . . . . . . . . . . . . °C . . . . -15/+24 . . -15/+24 . . -15/+24 . . -15/+24 . . -15/+24 . . -15/+24

Initial max. heating water temperature

- Floor heating system . . . . . . . . . . . . . . °C . . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45

- Low temperature radiator . . . . . . . . . . . °C . . . . . . 52 . . . . . 52 . . . . . 52 . . . . . 52 . . . . . 52 . . . . . 52

Initial min. heating water temperature. . . . . . . °C . . . . . . 8 . . . . . . 8 . . . . . . 8 . . . . . . 8 . . . . . . 8 . . . . . . 8

Refrigeration circuit

Diameter of gas pipes . . . . . . . . . . . . . inches. . . . . . 1/2 . . . . . 1/2 . . . . . 5/8 . . . . . 5/8 . . . . . 5/8 . . . . . 5/8

Diameter of fluid pipes . . . . . . . . . . . . . inches . . . . . . ¼ . . . . . ¼ . . . . . ¼ . . . . . 3/8 . . . . . 3/8 . . . . . 3/8

Factory charge of refrigerant R410A . . . . . . . . g . . . . . 1250 . . . . 1250 . . . . 1700 . . . . 2100 . . . . 3350 . . . . 3400

Maximum operating pressure . . . . . . . . . . . bar . . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45

Minimum length of pipes . . . . . . . . . . . . . . m . . . . . . 5 . . . . . . 5 . . . . . . 5 . . . . . . 5 . . . . . . 5 . . . . . . 5

Maximum length of pipes* . . . . . . . . . . . . . m . . . . . . 15 . . . . . 15 . . . . . 15 . . . . . 20 . . . . . 20 . . . . . 20

Maximum length of pipes** . . . . . . . . . . . . . m . . . . . . 25 . . . . . 25 . . . . . 30 . . . . . 50 . . . . . 50 . . . . . 70

Maximum level difference**. . . . . . . . . . . . . m . . . . . . 15 . . . . . 15 . . . . . 20 . . . . . 30 . . . . . 30 . . . . . 30

* Factory charge of refrigerant R410A

Taking into account the possible additional load ofrefrigeration fluid R410A (see p. 22)

Installation and operating manual “1350-EN” 5

Heat pump, split 1 service

Page 6: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

6 Installation and operating manual “1350-EN”

Heat pump, split 1 service

1,00

2,00

3,00

4,00

5,00

6,00

7,00

-20 -15 -10 -5 0 5 10 15 20

5

External temperature (°C)

Po

wer

(kW

)Floor heating system

Very low temperature radiator

Heat output

Power absorbed

1,00

2,00

3,00

4,00

5,00

6,00

7,00

8,00

9,00

10,00

-20 -15 -10 -5 0 5 10 15 20

6

External temperature (°C)

Po

wer

(kW

)

Heat output

Power absorbed

Floor heating system

Very low temperature radiator

1,00

3,00

5,00

7,00

9,00

11,00

13,00

-20 -15 -10 -5 0 5 10 15 20

8

External temperature (°C)

Po

wer

(kW

)

Heat output

Power absorbed

Floor heating system

Very low temperature radiator

1.4 Heating power curve Values according to standard EN 14511, for which it is necessary

to add the power absorbed by the heating circulation pump

Page 7: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 7

Heat pump, split 1 service

1,00

3,00

5,00

7,00

9,00

11,00

13,00

-20 -15 -10 -5 0 5 10 15 20

10

External temperature (°C)

Po

wer

(kW

)

Heat output

Power absorbed

Floor heating system

Very low temperature radiator

1,00

3,00

5,00

7,00

9,00

11,00

13,00

15,00

-20 -15 -10 -5 0 5 10 15 20

13

External temperature (°C)

Po

wer

(kW

)

Heat output

Power absorbed

Floor heating system

Very low temperature radiator

1,00

3,00

5,00

7,00

9,00

11,00

13,00

15,00

17,00

-20 -15 -10 -5 0 5 10 15 20

16

External temperature (°C)

Po

wer

(kW

)

Heat output

Power absorbed

Floor heating system

Very low temperature radiator

Page 8: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

8 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Figure 1 - Dimensions in mm

540

66790

10

347

300

189

177

578

320

121184

A

B

A

B

S8S5S6

1/4” 1/4”

1/2” 5/8”

Top view

Front view

Sight of lower part

Overflow hole (Ø 20)4 Holes Ø 10)

AIR

Side view

AIR

050

065080

� Outside unit,Model 050, 065, 080

77900

830

21

9

400

33031 12

196

147

170

99

3/8”

5/8”

370

650

AIR

Front view

Side view

Top view

AIR

Overflow hole (Ø 20) 4 Ø 10)Holes

Sight of lower part

� Outside unit,Model 095

Page 9: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 9

Heat pump, split 1 service

Figure 2 - Dimensions in mm

31 77900330 12

9

400

650

21

1290

147

170

196

370

99

3/8”

5/8”

Air

Overflow hole (Ø 20) 4 Ø 10)Holes

Top view

Front view

Sight of lower part

Side view

Air

Air

� Outside unit,Model 128, 155

480

88235

450

1034

1000

Front view Side view

Heating flowØ M 26x34

Heating returnØ M 26x34

Figure 3 - Dimensions in mm

� Hydraulic module

Page 10: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

10 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Fig. 4 - Hydraulic pressures and flow rates available

Fig. 5 - Ohmic values of the sensors

(Hydraulic module)

0,8 1 1,2 1,4 1,6

0

100

200

300

400

500

600

mbar 1 mbar = 10 mmCE = 100 Pa

1,8

m /h3

0,60,4

1

2

3

0

2500

5000

7500

10000

12500

15000

17500

20000

22500

25000

27500

30000

32500

0 10 20 30 40 50 60 70 80 90 100

°C

Ω

10 k 25°CΩ,

-50

1000

10000

43907

2490

338

-25 0 25 50 75 ° C

Ω

1 k 25°CΩ,

Outside sensor QAC34

Condensation sensorHeat pump return sensorHeat pump flow sensor

10000

1000

100

10

1

-20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130

ΩO

hm

icva

lue

(k)

- Evaporator outlet- Evaporator centre- Compressor casing

- Outside

- Compressor- Discharge

Temperature °C

Fig.6 - Ohmic values of the sensors (Outside unit)

Page 11: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

1.5 Description

Installation and operating manual “1350-EN” 11

Heat pump, split 1 service

Figure 7 - Outside unit components

� Model 050, 065, 080 � Model 128, 155

13

1 2

12 1110

9

8

7

6

543

13 1 2

12 1110

9

8

7

6

53

� Model 095

13

1 2

12 1110

9

8

7

6

543 Legend

1 - Low-noise, high-output coil

2 - Electric variable speed "inverter" motor

3 - "Inverter" control module

4 - Vacuum start (pump down) and control light

5 - Connection terminal blocks (power andinterconnection)

6 - Refrigerant accumulator bottle

7 - Cycle reversing valve

8 - Anti-corrosion treated bodywork

9 - Electronic expansion valve

10 - Noise and temperature insulated "inverter"compressor

11 - Refrigeration connection valves (flaredconnectors) with protective caps

12 - Holding tank with condensate drain hole

13 - High-performance exchange surfaceevaporator; anti-corrosion treated hydrophilicaluminium fins and grooved copper tubes.

Page 12: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

12 Installation and operating manual “1350-EN”

Heat pump, split 1 service

1

2

3

4

5

6 7 8

9

10

11

12

13 14

1516

Front view Side view

Identification plate

Figure 8 - Hydraulic module components

Legend

1 - Electric box

2 - Regulator / User interface

3 - Start/stop switch

4 - Heating circulation pump

5 - Initial heating

6 - Gas refrigeration connection

7 - Fluid refrigeration connection

8 - Heating return

9 - Drain valve

10 - Safety valve

11 - Safety thermostat ()

12 - Manometer

13 - Manual drainer

14 - Expansion vessel

15 - Condenser

16 - Electric back-ups

1.6 Operating principle

The heat pump transmits the energy contained in thesurrounding air into the dwelling to be heated.

The heat pump consists of four main elements, inwhich a refrigerant fluid (R410A) circulates.

- In the evaporator (rep. 13, fig 7, page 11): Theenergy is taken from the surrounding air and istransmitted to the refrigerant.

- Because it has a low boiling point, it changes fromthe liquid state to the vapour state, even in coldweather (down to -15 °C external temperature).

- In the compressor (rep. 10, fig 7, page 11): Thevaporised refrigerant brought to high pressure andtakes on more calories.

- In the condenser (rep. 15, fig 8, page 12): Theenergy in the refrigerant is transmitted to theheating circuit. The refrigerant returns to liquidstate.

- In the expansion valve (rep. 9, fig 7, page 11): Theliquefied refrigerant is brought back to low pressureand returns to its initial temperature and pressure.

The heat pump is equipped with a controller, whichcontrols the internal temperature based on theexternal temperature measurement and governed bythe temperature control.

The room thermostat (optional) provides a correctiveaction for the temperature control

The hydraulic module is equipped with an electricback-ups system, which is triggered to provideadditional heat during the coldest periods.

Regulation functions

- The heating circuit's initial temperature is controlledby the temperature control.

- The power of the Outside unit is modulatedaccording to initial heating temperature via the"inverter" compressor.

- Control of the electric back-up heating.

- The daily timer program enables you to define theperiods for comfortable or reduced ambienttemperature.

- Summer/winter mode switchover is automatic.

- Control of the supplementary boiler* (the electricback-ups are deactivated).

- The room thermostat* (optional) provides acorrective action for the temperature control

- Control of a second heating circuit*.

- Domestic hot water: Heating time programme,control of the operation of the DHW circulationpump.

- Control of swimming pool heating*.

Protection functions

- Anti-legionella cycle for domestic hot water.

* If the heat pump is equipped with optionalequipment and the associated kits.

Page 13: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Domestic hot water (DHW) operating principle

Two domestic hot water (DHW) temperatures can beparametered: comfort temperature (line 1610 to 60°C) and reduced temperature (line 1612 to 40 °C).

Setting for reduced temperature can be useful toprevent the DHW from switching on too often and fortoo long during the day.

The production of domestic hot water (DHW) istriggered when the temperature in the tank falls 7°C(setting from line 5024) below the set temperature.

The heat pump produces the domestic hot water,which is then supplemented, if required, by electricalbackup heating from the tank.

Depending on how the parameter (1620) is set,comfort temperature can be reached 24h/day or onlyat night or depending on the heat pump programme.

If the contract concluded with the energy providerincludes a subscription to day/night tariff, theelectrical backup is subordinate to the supplier'spower tariff and the comfort temperature may only bereached at night.

If no particular contract is concluded, the comforttemperature can be reached at any time, includingduring the day

The production of DHW takes priority over heating;nevertheless the production of DHW is controlled bycycles that control the times assigned to the heatingand the product ion of DHW in the event ofsimultaneous demand.

A DHW " boost" function is available on the front ofthe user interface (see ref. 1, fig. 39, p 31).

This DHW boost enables the DHW to be heated tothe comfort temperature at any time during the day.The boost function is cancelled automatically whenthe demand for hot water has been met.

If the heating installation is equipped with a DHWcirculation pump, the pump's operation during DHWcycles can be parametered.

Anti-legionella cycles can be programmed.

Installation and operating manual “1350-EN” 13

Heat pump, split 1 service

Ev

Dt

Cn

Cp

PAC

1 kW

COP 4

4 kW

20 °C

Electricalenergyconsumed

Energy from the air

Heat producedHeat produced

Figure 9 - Heat pump operating principle

PAC - Heat pump

Ev - Evaporator

Cp - Compressor

Cn - Condenser

Dt - Expansion valve

Page 14: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2 Installation

2.1 Regulation installation andmaintenance conditions

The appliance must be installed and the maintainedby an approved professional in accordance with theprevailing regulations and code of practice, inparticular:The legislation on the handling of refrigerants.

2.2 Unpacking and reservations

2.2.1 Receipt

Carefully check, in the carrier's presence, thegeneral appearance of the appliances and checkthat the Outside unit is not laid on its side or back.

In the case of any dispute, state any appropriatereservations to the carrier in writing within 48 hoursand send a copy of this letter to the After-Salesservice.

2.2.2 Handling

The external unit should not be laid on its side orback during transport.

Laying the unit down during transport is likely todamage the internal tubes and the compressorsuspensions.

Any damage caused by transportation of the unitlying down is not covered by the warranty.

If necessary the external unit may be tilted onlyduring manual handling (to go through a door or usea staircase).

This operation must be conducted very carefully andthe appliance must be immediately restored toupright position.

2.2.3 Accessories provided

Accessories provided with the external unit(figure 10).

Accessories provided with the hydraulic module(figure 11)

2.3 Installation position

The choice of the position for installation isparticularly important insofar as any later movementis a delicate operation requiring the intervention of aqualified person.

Choose the site of the external unit and the hydraulicmodule after discussion with the customer.

Observe the maximum and minimum distancesbetween the hydraulic module and the external unit(Figure 13); the guarantee of the performances andthe system's service life depend on this.

2.4 Installation of the external unit

2.4.1 Installation precautions

� The external unit must only be installedoutside (outdoors). If a shelter is required, itmust have broad openings on the 4 walls andobserve the installation clearances (fig. 12).

• Choose a site that is preferably sunny and shelteredfrom strong cold predominant winds (mistral,tramontana, etc…).

• The unit must be easily accessible for futureinstallation and maintenance work (fig. 12).

• Ensure that it is possible to make the connections tothe hydraulic module easily.

14 Installation and operating manual “1350-EN”

Heat pump, split 1 service

1 32 4

Figure 10 - Accessories provided

with the external unit

8

5 6 7

Figure 11 - Accessories provided

with the hydraulic module

1 Elbow For draining away thecondensates

2Plug (x 2)(Depend ingon the model)

3Flexiblei n s u l a t i o nplate

For filling the emptyspace at the input to theinterconnection cable

4Hex / Al lenkey

To open the valves

5 BracketTo secure thehydraulic model

6 Outside sensorTo moni to r theoutside temp

71/2" - 5/8" and/or1/4" - 3/8" adapter

To connect theflared connectionand the hydraulicmodel8

Nut (1/2" and/or)1/4"

Page 15: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 15

Heat pump, split 1 service

AIR

100 mm 100 mm

600 mm

100 à 300 mm

300 mm

300 mm

250 mmFor access

250 mmFor access

250 mmFor access

AIR

AIR

AIR

minimum600 mm

AIR

Figure 12 - Minimum installation clearances around external unit

(All models)

• The external unit is able to withstand bad weatherbut avoid installing in a position where it is likely tobe exposed to significant dirt or flowing water (undera defective gutter for example).

• Water may drain away from the external unit when itis operating. You can let this defrosted water run offover a gravel or sand bed or a concrete slab with adiamond point and a sinkhole in the ground. If theinstallation is in an area where the temperature canbe lower than 0°C for a long period, check that thepresence of ice does not present any danger. Adrainage pipe can also be connected to external unit(see § 2.4.3, page 16).

• Nothing should obstruct the air circulation throughthe evaporator and from the fan (fig. 12).

• Keep the external unit away from heat sources andinflammable products.

• Make sure the appliance not disturb the surroundingarea or users (noise level, draught generated, lowtemperature of the air being blown out, with the riskof freezing plants in its path).

The surface receiving the external unit must be ablegenerally to support its weight; provide a solid fixingand do not transmit any vibration to the dwelling.

Page 16: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Anti-vibratory blocks are available, please consultyour retailer (Atlantic).

2.4.2 Outside unit positioning

The external unit must be raised at least 50mmabove the ground. In snowy areas, this height mustbe increased (figure 14)

Fasten the external unit by means of screws andrubber tightening or toothed lock washers to avoidtheir coming loose.

2.4.3 Condensate drain hose

(see figure 14).

If the use of a discharge pipe is imperative:

Use the e lbow prov ided (C ) to connec t a16mm-diameter hose for draining away thecondensate.

Use the stopper or stoppers provided (B) to block theopening of the condensate tank.

Allow for the condensate to flow away under theforce of gravity (waste water, rain water, gravel bed).

� If the installation is made in an area where thetemperature can be lower than 0°C for a longperiod, provide the drain pipe with a traceresistance to avoid it icing up. The traceresistance must heat not only the pipe buta lso the bottom of the appl iance 'scondensate collection tank.

16 Installation and operating manual “1350-EN”

Heat pump, split 1 service

PAC

Unité extérieure

PAC

Modulehydraulique

DLmini5 m

Figure 13 - Pipe diameters (in inches) and permissible lengths (in metres)

Gas and fluid conduits

Heat pump Gas FluidM i n i m u mlength (L)

* M a x i m u mlength (L)

**M a x i l e v e ldifference (D)

model 050

model 0651/2" ¼" 5 15 15

model 080 5/8" ¼" 5 15 20

model 095 5/8" 3/8" 5 15 30

model 128

model 1555/8" 3/8" 5 20 30

* : Without additional charge of R410A

** : Taking into account the possible additional load of refrigeration fluid R410A

(see § 2.7.3, page 22).

S

B

C

BH > 50 mm*

(Ø 12 mm)

(Ø 10 mm)

Depending on the model

Depending on the model

* In regions subject to frequent snow,(H) must be greater than the average snow layer.

4 holes

4 holes

Figure 14 - Positioning of the external unit,

draining away the condensate

Page 17: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.5 Installing the hydraulic module

2.5.1 Installation precautions

• The room in which the appliance operates mustcomply with the prevailing regulations.

• To facilitate maintenance and to allow access to thevarious components, we recommend that youprovide sufficient space all around the hydraulicmodule (figure 15).

• Be careful not to bring inflammable gas near to theheat pump during its installation, in particular whenit requires brazing

The appliances are not fireproof and should nottherefore be installed in a potentially explosiveatmosphere.

2.5.2 Positioning the hydraulic module

- 1, 2, 3 : Remove the front panel (2 screws A, figure 16)

- 4, 5 : Remove the sides (4 screws B, figure 17).

- Fix the support solidly (3 screws and plugs) to a flat,hard-wearing wall (not a light partition) ensuringthat it is correctly levelled.

- Hook the appliance onto its support.

- Refit the sides.

- Refit the front facing.

Installation and operating manual “1350-EN” 17

Heat pump, split 1 service

200 mm

1000 mm

150 mm

150 mm

Figure 15 - Minimum installation clearances

around the hydraulic module and distances to the

combustible partitions

1

3

2 A

Figure 16 - Removing the front facing

90 mm

(S)

505 mm

240 mm

150 mm

200 mm

305 mm

Figure 17 - Removing the sides and fixing the support (S)

B

B

(S)

5

5

4

Page 18: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.6 Refrigeration connections

� This appliance uses refrigerant R410A.

Comply with the legislation for handling refrigerationfluids.

2.6.1 Rules and precautions

• After every intervention on the refrigeration circuitand before final connection, take care to replace theplugs in order to avoid any pollution from therefrigeration circuit.

• Tools

Set of manometers with hoses exclusively reservedfor HFCs (Hydrofluorocarbons).

Vacuum pump specially for HFCs.

Provision on using tools that have been in contactwith HCFCs (R22 for example) or CFCs.

Use of a traditional vacuum pump is authorized if,and only if, it is fitted with a non-return valve on thesuction side.

The manufacturer declines any liability with regard tothe guarantee if the above instructions are notobserved.

• Flared connections

� Lubrication with mineral oil (for R12, R22) isforbidden.

- Only lubricate with polyolester refrigeration oil(POE). I f POE is not avai lable, f i t wi thoutlubrication.

• Braz ing on the refr igerat ion circui t ( i fnecessary)

- Silver brazing (40% minimum recommended).

- Brazing only under dry nitrogen internal flux.

• To eliminate any filings in the pipes, use dry nitrogento avoid introducing any humidity that mayadversely affect the appliances operation. Ingeneral, take every precaution to avoid humiditypenetrating into the appliance.

Proceed to insulate the gas and liquid pipes to avoidany condensation.

Use insulating sleeves resistant to temperaturesover 120°C. In addition if the humidity level in theareas where the refrigeration pipes pass risksexceeding 70%, protect the pipes with insulatingsleeves. Use a sleeve thicker than 15mm if thehumidity reaches 80%, and a sleeve thicker than20mm if the humid i ty exceeds 80%. I f therecommended thicknesses are not observed underthe conditions described above, condensation willform on the surface of the insulation material. Lastly,take care to use insulating sleeves whose thermalconductivity is 0.045 W/mK or less when thetemperature is 20°C. The insulation must beimpermeable to resist the passage of steam duringthe defrosting cycles (fibreglass wool is prohibited).

2.6.2 Refrigeration connections

The external unit must be connected to the hydraulicmodule wi th copper pipes and connect ions(refrigeration quality), insulated separately.

Comply with the pipe diameters and the permittedpipe lengths (figure 13).

The minimum length of the refr igerat ionconnections is 5m for correct operation.

The appliance will be excluded from guarantee if it isused with refrigeration connections less than 5mlong.

Manipulate the pipes and take them through wallswith protective plugs in place.

If the distance between the external unit and thehydraul ic module exceeds the length of themaximum conduits indicated in the table, anadditional charge of R410A must be loaded.

The quantity of R410A added must be adapted to thelength of the refrigeration circuit in order to the heatpump's per formance wi thout damaging thecompressor (figure 23).

2.6.3 Creating the flarings

- Cut the pipe to an appropriate length with apipe-cutter without deforming it.

- Carefully deburr it, holding the pipe towards thebottom to avoid introducing filings into the pipe.

- Remove the flared connection nut situated on thevalve to be connected and slip the pipe into the nut.

- Proceed to flare, letting the pipe overflow the flaringtool.

- After flaring, check the condition of the workingradius (L). This must not show any scratch or traceof any fracturing. Also check the dimension (B).

18 Installation and operating manual “1350-EN”

Heat pump, split 1 service

B

L

C

L B 0- 0,4 C

6,35 (1/4”)

15,88 (5/8”)

1,8 à 2

2,9 à 3,1

9,1

19,7

17

29

9,52 (3/8”) 2,5 à 2,7 13,2 22

12,7 (1/2”) 2,6 à 2,9 16,6 26

Ø HoseDimensions in mm

Flaring tool

Hose

Flarenut

Figure 18 - Flaring for flare connections

Page 19: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.6.4 Shaping the refrigeration pipes

The refrigeration pipes must be shaped only on abending machine or with a bending spring in order toavoid any risk of crushing or breaking them.

� Warning

• Remove the insulation material locally to bend thepipes.

• Do not bend the copper to any angle over 90°.

• Never bend pipes more than 3 times in the sameposition otherwise traces of fracturing may appear(from strain-hardening the metal).

2.6.5 Connecting the flared connections

� The small pipe must always be connectedbefore the large one.

� Take particular care positioning the tubeopposite its connector so as not to riskdamaging the threads. A carefully alignedconnector can be fitted easily by handwithout much force being required.

� The refrigeration circuit is very sensitive todust and humidity: check that the areaaround the connection is clean and drybefore removing the plugs protecting therefrigeration connectors.

Installation and operating manual “1350-EN” 19

Heat pump, split 1 service

Liquid valve

Flare nut

Liquid refrigeration connexionDiameter D2

“Gas” refrigeration connexionD1 Diameter

Gas valve

Flare nut

Flare nut

Flare nut

Adapter R2,dependingon the model

Adapter R1,dependingon the model

Outsideunit

Hydraulicmodule

Figure 19 - Connecting the flared connections

Outsideunit connections

Diameterof refr igerat ionconnections

Male-femaleadapter(reduction)

Hydraulic moduleconnections

Model 050

Model 065

Gas 1/2" (D1) 1/2" (R1) 1/2"-5/8" 5/8"

Fluid ¼" (D2) ¼" (R2) ¼"-3/8" 3/8"

Model 080Gas 5/8" (D1) 5/8" None 5/8"

Fluid ¼" (D2) ¼" (R2) ¼"-3/8" 3/8"

Model 095

Model 128

Model 155

Gas 5/8" (D1) 5/8" None 5/8"

Fluid 3/8" (D2) 3/8" None 3/8"

Page 20: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

- Depending on the case, connect an adapter(reducer) ¼''- 3/8'' or 1/2''- 5/8''. (see figure 19).

- Remove the plugs from the pipes and therefrigeration connections.

- Present the pipe to the flared connector and screwthe nut by hand while holding the connector with awrench until contact.

- Comply with the recommended tightening torques.

(see figure 21).

20 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Coat the flared surfacewith POE refrigeration oil

Do not use mineral oil.

Figure 20 - Prevention of gas leaks

Holding wrench

Torque wrench

Designation

Flare nut 6,35 mm (1/4”)

Flare nut 9,52 mm (3/8”)

Flare nut 12,7 mm (1/2”)

Flare nut 15,88 mm (5/8”)

Plug (A) 3/8”, 1/4”

Plug (A) 1/2”

Plug (B) 3/8”, 5/8”

Tightening torque

14 to 18 Nm

33 to 42 Nm

50 to 62 Nm

63 to 77 Nm

20 to 25 Nm

25 to 30 Nm

10 to 12 Nm

Plug (A) 5/8” 30 to 35 Nm

Plug (B) 1/2”, 1/4” 12,5 to 16 Nm

Figure 21 - Tightening torque

Page 21: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.7 Filling the installation with gas

� This operation is reserved for installersfamiliar with the legislation for handlingrefrigeration fluids.

� Creating a vacuum with a vacuum pump isessential.

� Never use equipment used beforehand withany refrigerant other than a HFC.

2.7.1 Creating a vacuum and filling the

refrigeration connections with gas

(see figure 22).

- Remove the protective plugs (B) from the charginghole (Schrader) in the gas valve (large diameter).

- Connect the blue hose (on the side with a valvepusher in good condi t ion) f rom the set ofmanometers (manifold).

- Connect the yellow hose to a vacuum pump andopen the blue valve on the set of manometers.

- Create a vacuum until the residual pressure in thecircuit falls below 0.01 bar.

- Let the pump continue to operate for another 15minutes after reaching the vacuum.

- Close the blue valve on the set of manometers andthen s top the vacuum pump w ithoutdisconnecting any of the hoses in place.

- Wait 10 minutes. If the pressure rises during this10-minute period, there is a leak in the circuit. Traceit and repair it: then start again.

When the pressure has remained stable for 10

minutes after the vacuum pump stops, the circuit is

considered to be gas-tight.

- Remove the access plugs (A) from the valvecontrols.

� If an additional charge is requires, add theadditional charge before filling the hydraulicmodule with gas. Please refer to the section("Additional charge", page 22).

- First of all fully open the small valve and then thelarge one using a hex key (counterclockwisedirection) without forcing excessively against thestop.

- Remove the blue hose rapidly.

- Ref i t the 2 plugs and t ighten them to therecommended tightening torque (see figure 21).

The external unit does not contain any additionalrefrigerant, enabling the installation to be purged.

Flushing is strictly forbidden.

2.7.2 Sealing test

Once the refrigeration circuit has been gassed asdescribed above, check that all the refrigerationconnectors are gas-tight:

6 connectors for models 050 and 065, 5 connectorsfor model 080 and 4 connectors for models 095, 128and 155.

The sealing test must be performed with anapproved gas detector.

If the flarings have been made correctly, there shouldbe no leaks.

If there is a leak, make the connection again.

Installation and operating manual “1350-EN” 21

Heat pump, split 1 service

Figure 22 - Extraction under vacuum and gassing

Lo Hi

Manometer kit(manifold)

Vacuum pump

Service hose

Lowpressure

Highpressure

Gas valveLarge diameter

Vacuum meter

Refrigeration connexion

Plug (A)

Hex / Allen key of 4 mm

3-way valve

Load orifice

Plug (B)Service hose (blue)fitted with valve push-button

Page 22: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.7.3 Additional charge

The charge in the external units corresponds to themaximum distances between the external unit andthe hydraulic module defined in Figure 13.

If the distances are greater, an additional charge ofR410A is required.

The additional charge depends on the distancebetween the external unit and the hydraulic modulefor each type of appliance (Fig. 23)

The additional charge of R410A must necessarily bemade by an approved refrigeration engineer.

• Example for a heat pump model 155

An external unit 32m away from the hydraulic modulewill require an additional charge of:

Additional charge = (32 - 20) x 40 = 480 g

The charge must be introduced after creating thevacuum and before the hydraulic module is filled withgas, as follows:

- Disconnect the vacuum pump (yellow hose) andconnect a bottle of R410A instead in the fluidextraction position.

- Open the bottle's valve.

- Bleed the yellow hose by loosening it slightly on themanifold side.

- Place the bottle on scales with a minimum accuracyof 10g. Note the weight.

- Carefully open the blue valve slightly and check thevalue shown on the scales.

- As soon as the value displayed has dropped by thevalue for the calculated additional charge, close thebottle and disconnect it.

- Then rapidly disconnect the hose connected to theappliance.

- Proceed to fill the hydraulic module with gas.

� Warning

• Only use R410A!

• Only use too ls su i tab le for R410A (set ofmanometers).

• Always charge in the fluid phase.

• Never exceed the length or the maximum differencein level.

22 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Model 050 - Model 065 20 g of R410A per additional meter

Length of the connections 15 m 20 m 25 m

Additional charge none 100 g 200 g

Model 080 20 g of R410A per additional meter

Length of the connections 15 m 20 m 25 m 30 m

Additional charge none 100 g 200 g 300 g

Model 095 40 g of R410A per additional meter

Length of the connections 15 m 20 m 30 m 40 m

Additional charge none 200 g 600 g 1000 g

Model 128 50 g of R410A per additional meter

Length of the connections 20 m 30 m 40 m

Additional charge none 500 g 1000 g

Model 155 40 g of R410A per additional meter

Length of the connections 20 m 30 m 40 m

Additional charge none 400 g 800 g

Figure 23 - Additional charge

R410A

Gas

Fluid

Figure 24 - Gas bottle R410A

Page 23: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.8 Connecting the heating circuithydraulically

2.8.1 General

The connection must comply with good tradepractice according to local building regulations.

The heating circulating pump is built into thehydraulic module.

Connect the central heating pipes to the hydraulicmodule, complying with the direction of circulation.

The diameter of the pipes between the hydraulicmodule and the heating collector must be at least 1inch (24x36mm).

Calculate the diameter of the pipes according to theflow rates and the lengths of the hydraulic systems.

Use union connectors to facilitate removing thehydraulic module.

Preferentially use connection hoses to avoidtransmitting noise and vibrations to the building.

Connect the drains from the drain valve and thesafety valve to the main sewer system.

Reminder : Sea l every th ing when f i t t ing inaccordance with prevailing trade practice forplumbing work:

- Use suitable seals (fibre seals, o-rings).

- Use Teflon tape or hemp.

- Use sealing paste (synthetic depending on thecase).

The use of glycol is not necessary.

If you are using a glycol/water mix, provide for anannual check on the quantity of glycol.

In certain installations, the presence of differentmetals can cause corrosion problems; the formationof metal particles and sludge in the hydraulic circuitis then seen.

In this case, it is advisable to use a corrosion inhibitorin the proportions indicated by its manufacturer.

It is also necessary to ensure that the treated waterdoes not become aggressive.

2.8.2 Rinsing out the installation

Before connecting the hydraulic module to theinstallation, rinse out the heating system correctly toel iminate any part ic les that may affect theappliance's correct operation.

Do not use solvents or aromatic hydrocarbons(petrol, paraffin, etc.).

In the case of an old installation, provide a sufficientlylarge decanting pot with a drain on the return fromthe boiler and at the lowest point in the system inorder to collect and remove the impurities.

Add an alkaline product to the water and adispersant.

Rinse the installation several times before filling itdefinitively.

2.8.3 Filling and purging the installation

Check the pipe fixings, the tightness of theconnectors and the stability of the hydraulic module.

Check the direction in which the water is circulatingand that all the valves open.

Proceed to fill the installation.

Do not operate the circulating pump while filling.Open all the drain valves in the installation and thebleed valve for the hydraulic module to remove theair contained in the conduits.

Close the drain and bleed valves and add water untilthe pressure in the hydraulic circuit reaches 1.5 bar.

If the pressure is lower than 0,5 bar, the Heat Pumpstops and posts error 369.

Check that the hydraulic circuit has been purgedcorrectly.

Check that there are no leaks and that the circulatingpumps are not seized (if need be, release them).

After the "Start-up" stage (see p. 30), once themachine has started, purge the hydraulic moduleagain (2 litres of water).

Installation and operating manual “1350-EN” 23

Heat pump, Splir 1 service

Figure 25 - Release of the

circulation pump

IIS 5S 6S 8S 10

IIIS 13S 16

Figure 26 - Recommended

circulation speed (for radiator)

(P)

Figure 27 - (P) Hydraulic

module bleeder valve

II

050

065

080

095

III

128

155

Page 24: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.9 Electrical connections

Ensure that the general electrical power supply hasbeen cut off before starting any repair work.

2.9.1 Characteristic of the electrical supply

The electrical installation must be conducted inaccordance with the prevailing regulations.

The electrical connections must only be made whenall the other fitting operations have been completed(fixing, assembly, etc.).

� Warning

The contract concluded with the energy providermust be sufficient not only to cover the heat pump'spower but also the combined sum of all theappliances likely to be operating at the same time.

When the voltage is too low, check with your energyprovider the value subscribed to in your contract.

Never use a socket for the power supply.

The heat pump must be supplied with power byspecial protected leads from the electric panel via2-pole circuit breakers specially dedicated to theheat pump:

Curve D for the external unit, curve C for the electricheating and domestic water back-ups (see tables onpage 25).

The electrical installation must necessarily beequipped with a 30mA differential protection.

Use a flexible cable of H07 RN-F type.

This appliance is intended to operate under anominal voltage of 230V +/- 10%, 50 Hz.

2.9.2 General remarks on the electrical

connections

Tighten the screws on the terminal blocks perfectly.Unsufficient tightening can cause overheating,leading to breakdown or even a fire.

Use cable clamps to prevent the conductors frombeing disconnected accidentally.

Connection to Earth and Earth bonding continuityare essential.

• Connecting to screw terminals

Rigid wires (A, fig. 28).

Rigid wires are always preferable for f ixedinstallations, particularly in a building.

- Always select a wire that complies with theprevailing standards.

- Strip away around 25 mm from the end of the wire.

- With round end pliers, form a loop with a diametercorresponding to the tightening screws on theterminal.

- Tighten the terminal screw firmly onto the loopcreated.

Flexible wires (B, fig. 28)

H07RNF type flexible wire can be used with certainprecautions:

- Strip away around 10mm from the end of the wire.

- With tightening pliers, fit a round tag with a diametercorresponding to the terminal screw's diameter onthe end of the wire.

- Tighten the tag firmly onto the terminal with ascrewdriver.

- We strongly advise against using flexible wireswithout round tags.

- Always protect the cables when passing themthrough cable clamps with PVC protective conduit0.5 to 1mm thick.

• Connecting to regulation cards

- Remove the corresponding connector and makethe connection.

• Connecting to spring terminals (fig. 30)

Rigid wires

- Strip away around 10mm from the end of the wire.

- Slide the wire into the opening provided for thispurpose.

- Push the spring with a screwdriver so that the wireenters the cage.

- Remove the screwdriver and then check that thewire is jammed in the cage by pulling on it.

Flexible wires

- Use the ends and proceed as before.

24 Installation and operating manual “1350-EN”

Heat pump, split 1 service

25 mm10 mm

A : Rigid wires B : Flexible wires

LoopRound terminal tightened

Special screw andwasher

Terminalblock

Figure 28 - Outside unit terminal block

Figure 29 - Regulation connector

Figure 30 - Hydraulic module terminal block

Page 25: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 25

Heat pump, split 1 service

Interconnection between the external unitand the hydraulic modulePhase, Neutral, Earth, Communication busCable 4 x 1.5 mm²

General electrical supplyPhase, Neutral, EarthCable 3 x 1.5 to 4 mm² (depending on heat pump power)

Power supply to the electrical back-upsPhase, Neutral, EarthCable 3 x 2.5 to 6 mm²(depending on heat pump power)

Ambient temperature sensor(option)cable 2 x 0.5 mm²

T55

External sensorCable 2 x 0.75 mm²

Electric panel

Remote control T75 (option) :cable 3 x 0.5 mm²

Figure 31 - Overall layout of the electrical connections for a simple installation (1 heating circuit)

2.9.3 Overview of all the electrical connections

The wiring diagram for the hydraulic module is shown in detail on page 56.

2.9.4 Cable section and protection rating

The cable sections are given for information purposes only and do not exempt the installer from checking thatthese sections correspond to the requirements and comply with the prevailing standards.

• Power supply to external unit

Heat pump Electricity supply 230 V - 50 Hz

Model Power absorbed Cable connection(Phase, Neutral, Earth)

Curve D circuit breakersize (A)

050, 065 1860 W 3 x 1,5 mm² 16

080 2210 W 3 x 2,5 mm² 16

095 2680 W 3 x 2,5 mm² 20

128 3770 W 3 x 4 mm² 25

155 4700 W 3 x 4 mm² 32

Interconnection between the external unit and the hydraulic module. The hydraulic module is powered bythe external unit by means of a 4 x 1.5 mm² cable (Phase, Neutral, Earth, Communication bus).

• Power supply to the electrical back-ups

The hydraulic module contains two stages of electrical back-ups installed in a heat exchange cylinder.

Heat pump Electric back-ups Power supply to the electrical back-ups

Model Power Nominal intensityCable connection

(Phase, Neutral, Earth)

Curve C circuit breakersize (A)

050, 065, 080 2 x 1,5 kW 13 A 3 x 2,5 mm² 16

095, 128, 155 2 x 3 kW 26,1 A3 x 4 mm²

3 x 6 mm²32

Outside sensor, ambient air sensor, remote control

For the ambient air sensor, use a 2 x 0.5 mm² telephone type cable.

For the remote control, use a 3 x 0.5 mm² telephone type cable.

For the Outside sensor, use a 2 x 0.75 mm² cable.

Page 26: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.9.5 Electrical connections on the external

unit side

Access to the connection terminals

• Model 050, 065, 080

- Remove the cap (figure 32).

• Model 095, 128, 155

- Remove the front panel

- Remove the cap (figure 34).

Make the connections in accordance with thediagram(s) Fig. 33.

Use cable clamps to prevent the conductors frombeing disconnected accidentally.

Fill in the space where the cables enter the externalunit with the insulating plate (fig. 35).

26 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Remove the cap(1 screw)

Figure 32 - Access to external unit’s terminal block

(model 050, 065, 080)

General electricalsupply

Terminalblock

Interconnectionbetween the external unitand the hydraulic module

Figure 33 - Connections to external unit’s terminal

block

Remove the front panel(2 screws)

Remove the front panel(2 screws)

Removethe cap (1 screw)

Figure 34 - Access to external unit’s terminal block

(model 095, 128, 155)

Page 27: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

2.9.6 Electrical connections on the hydraulic

module side

Access to the connection terminals

- Remove the front panel (2 screws) (fig. 16, p. 17)

- Remove the cover of the electric box.

- Make the connections in accordance with thediagram(s) Fig. 37.

Do not place the sensor lines and the sector supplylines in parallel in order to avoid causing inadvertentinterference due to voltage points in the sectorsupply.

Ensure that all the electrical cables are housed in thespaces provided for this purpose inside the liftinghandles.

Installation and operating manual “1350-EN” 27

Heat pump, split 1 service

Release

Cable clamp

Cable clamp

Flexibleinsulation plate

Cables(supply andinterconnection)

Cables

Gas valve

Figure 35 - Finalisation of connection to external

unit

Transformer

Power card

Interface card

Heat pump regulator

Terminal blocks

Power relay

Cable grommet (Power)

Cable grommet (low voltage)

Safety thermostat

Figure 36 - Access to hydraulic model electric box and description

Page 28: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

• Interconnection between the external unit andthe hydraulic module

Comply with the correspondence between themarkings on the hydraulic module's terminals andthose on the external unit when connecting theinterconnection cables.

A connection error could cause the destruction ofone or other of the units.

• Electric back-ups

If the heat pump is not installed with a boilerconnection:

Connect the electrical supply for the back-ups(terminals 9, 10 and 11) to the electrical panel.

• Boiler connection

- Please refer to the instructions supplied with theboiler connection kit.

- Please refer to the instructions supplied with theboiler.

• Domectic hot water tank

If the installation is fitted with a DHW tank withelectrical back-up heating:

Please refer to the instructions supplied with theDWH kit.

Please refer to the instructions supplied with theDWH tank.

Second heating circuit

Please refer to the instructions supplied with thesecond circuit kit.

• Contract with the power provider

The heat pump's operation can be controlled to suitspecial contracts (e.g. off-peak, day/night).

In particular, domestic hot water (DHW) at Comforttemperature will be produced during the off-peakhours when electricity is cheaper.

- Connect the "Power Provider" contact to input EX5or EX4.

- Set the parameter (1620) to “Off-peak hours”.

• 230V on input EX5 = "Peak hours" informationactivated.

• Power limitation or EJP (peak day removal)

Power limitation is intended to reduce electricalconsumption when this is too high compared to thecontract with the power provider.

- Connect the power limiting device to input EX4(E6), the back-ups for the heat pump and the DHWstop in the event of over-consumption by thedwelling.

230 V on input EX4 (E6) = power limitation inprogress. (Operating line 2920)

28 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Rp ECS

1 2 3 4 5 6 7 8 9 10 11 12131415161718

Rp 1 Rp 2

L N

19

L NL N L N

NL

Interconnection between the outside unitand the hydraulic module

Electricity supply230 V

Red

Blue

Green / yellow

Brown

Outside unit Hydraulic module

DHW

Resistance of the back-up unit 1

Resistanceof the back-up unit 2

Boile

rro

om

therm

osta

tte

rmin

als

3w

ay

dis

trib

ution

valv

e(d

evia

tion

boile

r)O

peni

ngsi

gnal

(230

V)

Pow

er

supply

toth

eele

ctr

icalback-u

ps

Pow

er

supply

toth

eele

ctr

icalback-u

ps

Connexio

nto

the

DH

Wta

nk

resis

tance

HP andelectric back-ups

HP andboiler connection

Figure 37 - Connection to terminal block and power relays

Page 29: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

• Faults outside the heat pump

Any component of carryforward of information(thermostat, pressure switch, etc.) may signal anexternal problem and stop the heat pump.

E.g.: A safety thermostat on the heating floor will stopthe heat pump if the temperature in the floor is toohigh

- Connect the safety component to input EX6.

• 230 V on input EX6 = stoppage of heat pump (thesystem displays Error 369).

2.10 External sensor

The external sensor is required for the heat pump tooperate correctly.

Consult the fitting instructions on the sensor'spackaging.

Place the sensor on the coldest part, generally thenorthern or north-eastern side.

In any case, it must not be exposed to the morningsun.

It must be installed so as to be easily accessible butat least 2.5m from the floor.

It is essential that it avoid any sources of heat suchas flues, the upper parts of doors and windows,proximity to extraction vents, the underneath ofbalconies and under-eave areas which would isolatethe sensor from variations in the external airtemperature.

- Connect the external sensor to the M and B9terminals on the heat pump control board (fig. 38,p. 29).

2.11 Room thermostat and/or remotecontrol

The room thermostat (remote control) is optional.

Consult the fitting instructions on the sensor'spackaging.

The sensor must be installed in the living room areaon a very uncluttered wall, 1.5m above the floor.

Avoid direct sources of heat (chimney/f lue,te lev is ion , cook ing hobs) , d raughty areas(ventilation, door, etc.).

Air leaks in the seals in the constructions are oftentranslated into cold air blowing through the electricalconduits. Lag the electrical conduits if there is a colddraught on the back of the IR sensor.

Installation and operating manual “1350-EN” 29

Heat pump, split 1 service

2

1

MB9

CL-

CL+

3

2

CL-

CL+

EX6

EX5

EX4

5 6

2

1

1

CL-

CL+

G+

Outside sensor

Ambienttemperature

sensorcircuit 1

or

External fault(safety component)

Tariffs, peak times/off-peak times,day / night

Power sheddingor EJP (peak day removal)

External component contact*(faults, load shedder, power meter)

* If the control component does not provide a spare potential contact, the contact must be relayed to create equivalent wiring.In all cases, please refer to the instruction manuals for the external components (load limiting device, power meters) to create the wiring.

Remote control

Ambienttemperature sensor

circuit 2

Figure 38 - Connections to the heat pump regulator (accessories and options)

Page 30: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

• Installation equipped with two room thermostats

- Connect each of the sensors to one of the CL+ orCL- terminals on the heat pump control board(fig. 38, p. 29) using the connector supplied.

• Installation equipped with a room thermostat and aremote control

- Connect the sensor to one of the CL+ or CL-terminals on the heat pump control board (fig. 38,p. 29).

- Connect the remote control to the other CL+, CL-terminals and to G+.

2.12 Start-up

- Close the installation's main circuit breaker.

On first commissioning (or in winter), in order to allowthe compressor to pre-heat, engage the installation'smain circuit breaker (power supply to the externalunit) some hours before starting up the tests.

- Engage the heat pump's ON/OFF button.

When the power is switched on and every time thatthe ON/OFF button is switched off and then switchedon again, the external unit will take approximately 4minutes to start up, even if the setting is requestingheating.

- Make all the specific adjustments to the setting(configuring the installation).

- Press the key

- Hold down the key for 3s and select the level of

access used with the aid of the knob .

- Confirm with the key

- Parameter the heat pump's setting

- Consult the settings' list (page 34).

On commissioning (or the case of error 10), theelectrical backup heaters are liable to start up even ifthe external temperature at the time is above theheaters’ trigger temperature.

The regulating system uses an average initialexternal temperature of 0°C and requires some timeto update this temperature.

To mitigate this situation, the sensor must beconnected correctly. Re-initialise parameter 8703(implementation level, consumer diagnostic menu).

2.13 Configuring the room thermostat

Room thermostat T55

To configure the room thermostat and connect it tothe appropriate heating zone:

- Hold down the presence key for more than 3seconds. The room thermostat displays RU and anumber flashes.

- Turn the wheel to choose the zone (1, 2).

� If the installation is fitted with 2 roomthermostats,- First connect one room thermostat andconfigure it in zone 2- Then connect the other room thermostatand configure it as default in zone 1.

- Hold down the presence key; the room thermostatdisplays P1 and a flashing number.1: Automatic recording: a correction of the settingwith the button is adopted without any particularconfirmation (timeout) or by pressing the regimekey.2: Recording with confirmation: a correction of thesetting with the button is not adopted until theregime key is pressed.

- Press the presence key again; the room thermostatdisplays P2 and a flashing number.0: OFF: all the operating elements are engaged.1: ON; the following operating elements are locked:

Switching over the heating circuit's operating mode

Adjusting the comfort setting

Changing the operating level

The room thermostat displays OFF for 3 secondswhen a locked button is pressed.

2.14 Configuring remote control

Remote control T75

During commissioning, after an initialisation periodof approx. 3 minutes, the user’s language must beset:

Press the key "OK"

Choose menu "Bedieneinheit"

Choose language (Sprache)

Select the language (english, français, nederlands,español, etc)

30 Installation and operating manual “1350-EN”

Heat pump, split 1 service

OK

OK

Page 31: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 31

Heat pump, split 1 service

Ref. Function - Definitions

1 Selection of the DHW operating regime(Domestic hot water)

- If the installation is fitted with a DHW tank.

- ON: Production of DHW according to the time program.

- Off: Preparing the domestic hot water for stopping with theanti-frost function active.

- Boost: Hold down the DHW key for 3 seconds. Immediate DHWoperation after use of the electrical back-ups until the DHWcomfort setting has been reached

2 Digital display - Operating control. Readout of the current temperature, of the

heating regime and of any faults .

- View the settings

3 Exit "ESC" - Quit the menu.

4 Navigation and setting - Selecting the menu.

- Setting parameters.

- Adjusting the ambient temperature setpoint.

5 Selecting the heating regime - Heating operating according to the heating programme(Summer/winter mode switchover is automatic).

- Constant comfort temperature.

- Constant reduced temperature.

- Stand-by regime with anti-frost protection (Provided thatthe heat pump's electrical power supply is not interrupted).

6 Information display - Various data (please see page 59).

- Reading error codes (please see page 57).

- Information concerning maintenance, special regime.

7 Confirm "OK" - Input into the selected menu.

- Confirmation of the parameter settings.

- Confirmation of the adjustment to the comfort temp. setting.

8 Selecting cooling mode - If the installation is fitted with the cooling kit:

- Cooling operating according to the heating programme(Summer/winter mode switchover is automatic).

9 RESET button(Hold down the "RESET" key for 3 seconds).

- Reinitialising the parameters and cancelling error messages.Do not use during normal operation.

3 Regulation system

3.1 User interface and remote control T75 (Option)

Figure 39

1

2

3

4

5

6

7

8

9

1

2

3

4

5

6

7

8

13

ON

Off

Page 32: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

3.2 Room thermostat T55 (Option)

3.3 Temperature control

The heat pump's operation is subject to thetemperature control.

The set temperature for the water in the heatingcircuit is adjusted according to the externaltemperature

The tempera ture cont ro l may be chosenautomatically by the machine (self-adaptation) or setmanually by the installer (Parameters 720, 721 and726).

If there are thermostatic valves on the installation,these must be fully open or adjusted for higher thanthe normal set temperature.

3.4 Manual adjustment

During installation, the temperature control must beparametered according to the heat emitters and thedwelling's insulation.

The temperature control' curves (Fig. 41) refer to anambient setting of 20°C.

The slope of the temperature control (parameter720) determines the impact of the variations in theexternal temperature on the in i t ia l heat ingtemperature variations.

The higher the slope, the more a slight reduction inthe external temperature causes a significantincrease in the initial water temperature in theheating circuit.

The off-set in the temperature control (parameter721) alters the initial temperature of all the curves,without altering the slope (Fig. 42).

The cor rec t ive ac t ions in the case of anyinconvenience are detailed in the table (Figure 43).

3.5 Self-adaptation

When this function is active (parameter 726), thetemperature control are automatically adjusted; it istherefore futile to alter the slope or the off-set in thetemperature control (parameters 720 and 721).

When this function is first activated, the end usermay experience some inconvenience for a few days.

This period of no more than a week is required by theregulator to determine the slope and off-set in thetemperature control.

We advise against changing the temperaturesettings during this period.

The following instructions must be observed for theself-adaptation system to operate correctly:

- A room thermostat must be connected.

- The inf luence of the ambient temperature"(parameter 750) must be set between 1 and 100%.

- Depending on the installation, the room thermostatmay have a greater or lesser influence on thetemperature control.

- The room in which the room thermostat is installedmust not contain any thermostatic valves. If this isthe case, the valves must be open fully.

32 Installation and operating manual “1350-EN”

Heat pump, split 1 service

°C

10

12

13

11

Figure 40 - Room thermostat T55 (option)

Ref. Function - Definitions

10 Selecting the heating regime - Heating operating according to the heating programme(Summer/winter mode switchover is automatic).

- Constant comfort temperature.

- Constant reduced temperature.

- Stand-by regime with anti-frost protection (Provided thatthe heat pump's electrical power supply is not interrupted).

11 Digital display - Operating control. Readout of the current temperature, of the

heating regime and of any faults .

12 Control knob - Adjusting the ambient temperature setpoint

13 Presence key - Comfort / Reduced switchover

Page 33: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 33

Heat pump, split 1 service

30

40

50

60

70

-20-15-10-505101520

20

0,25

0,5

0,75

1

1,25

External temperature (°C)

He

atin

gflo

wte

mp

era

ture

(°C

) Heating curve slope

Lowtemperatureradiator

Floorheatingsystem

Boiler connexion application

Heat pump application only

Figure 41 - Heating curve slope (line 720)

40

50

60

70

-20-15-10-5510

-4,5

+4,520

0,5

0

10

30

0

30

External temperature (°C)

Heating

flow

tem

pera

ture

(°C

)

Heatingcurve slope

Curve off-set

Figure 42 - Off-set of the heating curve (line 721)

Sensations... Corrective actions on the temperature control:

...in mild weather ...in cold weatherCurve slope

(line )720Curve off-set

(line )721

and

and

and

and

and

and

and

and

and

No correction No correction

No correction

No correction

No correction

No correction

OK

Cold

Cold

Cold

OK

OK

Hot

Hot

Hot

OK

Hot

OK

Cold

Hot

Cold

Hot

OK

Cold

Figure 43 - Corrective actions in the case of discomfort

Page 34: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

34 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

Line Function Setting rangeor display

Settingincrement

Basicsetting

Date and time

1 U Hours / minutes 00:00… 23:59 1

2 U Day / Month 01.01… 31.12 1

3 U Year 1900… 2099 1

5 S Start of Summer time (Day / Month) 01.01...31.12 1 25.03

6 S End of Winter time (Day / Month) 01.01...31.12 1 25.10

The change of hour will appear at 3:00 first Sunday after the regulated date

User interface

20 U Language English, ...

22 I Info Temporary | Permanent Temporary

26 S Operation locking On | Off Off

27 S Programming locking On | Off Off

28 S Direct setting Saving... ...automatic | ...withconfirmation

...withconfirmation

Hours / minutesDay / MonthYear

Hours 1...24 hMinutes 0...60 min

End user

123

Time and date

User interface

CC1 time programme

...

Press

for 3 seconds

OEMSpecialistStart-upEnd user

Hours / minutesDay / MonthYear

Start of Summer time

End of Winter time

01.01...31.12

123

4

5

Date and time

User interface

CC1 time programme

...

Brief

press

Basic

display

3.6 Parametering the setting

3.6.1 General

Only the parameters accessible to levels:

U End user

I Start-up

S SpecialistAre described in this document.

The access levels are specified in the secondcolumn of the table by means of the letters U, I and S.

The OEM parameters are not described and requirea manufacturer's access code.

3.6.2 Setting parameters

- Choose the desired level.

- Scroll the menu list.

- Choose the desired menu.

- Scroll the function lines.

- Choose the desired line.

- Adjust the parameter

- Check the setting by pressing OK

- To return the menu, press ESC

If no setting is made for 8 minutes, the screen returnsautomatically to the basic display.

3.6.3 List of function lines (settings, diagnosis, sta

Page 35: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 35

Heat pump, Splir 1 service

44 I Operation HC2 Jointly with HC1 |Independent

Jointly withHC1

This function enables you to choose whether you wish the room thermostat (as an option) to act on both zones or

just a single zone.

46 I Operation HCP Jointly with HC1 |Independent

Jointly withHC1

70 S Software version

Heating time programme, circuit 1

500 U Pre-selection (day / week)Mon-Sun Mon-Fri Sat-Sun Monday Tuesday…

Mon-Sun

501 U 1st phase On (start) 00 : 00… - -:- - 10 min 6 : 00

502 U 1st phase Off (end) 00 : 00… - -:- - 10 min 22 : 00

503 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- -

504 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

505 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- -

506 U 3rd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

516 U Standard values, Circuit 1 no, yes no

Yes + OK: The standard values memorised in the regulator replace and cancel the customised heating

programmes. Your customised settings are therefore lost.

Heating time programme, circuit 2

Only with the 2nd circuit option

520 U Pre-selection (day / week)Mon-Sun Mon-Fri Sat-Sun Monday Tuesday…

Mon-Sun

521 U 1st phase On (start) 00 : 00… - -:- - 10 min 6 : 00

522 U 1st phase Off (end) 00 : 00… - -:- - 10 min 22 : 00

523 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- -

524 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

525 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- -

526 U 3rd phase Off (end) 00 : 00… - -:- - 10 mn - -:- -

536 U Standard values, Circuit 2 no, yes no

Yes + OK: The standard values memorised in the regulator replace and cancel the customised heating

programmes. Your customised settings are therefore lost.

Time programme 4 / DHW

If the installation is fitted with a DHW tank. (Only with the DWH kit option)

560 U Pre-selection (day / week)Mon-Sun Mon-Fri Sat-Sun Monday Tuesday…

Mon-Sun

561 U 1st phase On (start) 00 : 00… - -:- - 10 min 00 : 00

562 U 1st phase Off (end) 00 : 00… - -:- - 10 min 05: 00

563 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- -

564 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

565 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- -

566 U 3rd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 36: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

36 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

576 U Standard values no, yes no

Time programme 5 / Cooling

If the installation is fitted with the cooling kit (Only with the cooling kit option)

600 U Pre-selection (day / week)Mon-Sun Mon-Fri Sat-Sun Monday Tuesday…

Mon-Sun

601 U 1st phase On (start) 00 : 00… - -:- - 10 min 6 : 00

602 U 1st phase Off (end) 00 : 00… - -:- - 10 min 22 : 00

603 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- -

604 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

605 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- -

606 U 3rd phase Off (end) 00 : 00… - -:- - 10 min - -:- -

616 U Standard values no, yes no

Yes + OK: The standard values memorised in the regulator replace and cancel the customised heating

programmes. Your customised settings are therefore lost.

Holidays, heating circuit 1

641 U Preselection Period 1 to 8 Period 1

642 U Date holidays start (Day / Month) 01.01… 31.12 1

643 U Date holidays end (Day / Month) 01.01… 31.12 1

648 U Heating schedule during the holidays Frost protection,Reduced

Frostprotection

Holidays, heating circuit 2

If the installation consists of 2 heating circuits (Only with the 2nd circuit option)

651 U Preselection Period 1 to 8 Period 1

652 U Date holidays start (Day / Month) 01.01… 31.12 1

653 U Date holidays end (Day / Month) 01.01… 31.12 1

658 U Heating schedule during the holidays Frost protection,Reduced

Frostprotection

Heating adjustment, circuit 1

710 U Comfort ambient temperature setpoint From reduced temperatureto 35°C

0,5 °C 20 °C

712 U Reduced ambient temperature setpoint from frost-free temp… tocomfort temperature

0,5 °C 18 °C

714 U Frost-free ambient temperature setpoint from 4°C…to reduced temperature

0,5 °C 8 °C

716 S Maximum comfort setpoint 20 °C… 35 °C 1 °C 28 °C

720 I Heating curve slope (See Figure 41) 0.1... 4 0,02 0.5

721 I Off-set of the heating curve (See Figure 42) -4.50 °C… 4.5 °C 0,5 °C 0 °C

726 S Auto-adaptation of the heating curve (see § 3.3.2) off, on on

730 I Summer/Winter heating limits 8 °C … 30 °C 0,5 °C 18 °C

When the average of the external temperatures over the past 24 hours reaches 18°C, the regulator switches off the

heating (as an economy measure).

During summer mode, the display shows "Eco". This function is only active in automatic mode.

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 37: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 37

Heat pump, Splir 1 service

732 S Limit of daily heating -10 °C … 10 °C 1 °C -3 °C

This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.

Increasing the value delays the switchover to summer regime.

Decreasing the value advances the switchover to summer regime.

This function is only active in automatic mode.

750 I Influence of the ambient temperature 1%... 100% 1% 20%

If the installation is fitted with a room thermostat:

This function enables you to choose the ambient temperature's influence on the setting.

If no value is entered, the setting is made based on the temperature control.

If the parameter is set at 100%, the setting is only based on the ambient temperature.

790 S Maximum optimisation on switch-on 0 … 360 min 10 min 120 min

791 Maximum optimisation on switch-off 0 … 360 min 10 120 min

800 S Start of increase in reduced functioning mode - 30 … 10 °C 1 °C ---

801 S End of increase in reduced functioning mode - 30 … 10 °C 1 °C -5 °C

830 S Mixer valve boost 0...50 °C 1 °C 0

832 S Type of servomotor 2-pos, 3-pos 2-pos

833 S Switching differential 2-pos 0 … 20 °C 0,5 °C 2 °C

834 S Servomotor travel time 30 … 873 s 1 s 240 s

850 I Floor controlled drying (fig. 44) off

– off: Early interruption of the current programme, programme inactive– Operational heating– Heating ready for occupation– Operational heating + ready heating– Ready heating + operational heating– Manual

Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after

25 days.

851 I Manual floor drying setpoint(if line 850 = manual)

0 °C… 95°C 1 °C 25 °C

This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The

concrete slab-drying programme stops automatically after running for 25 days.

856 I Current drying day 0 ... 32

857 I Terminated drying days 0 ... 32

50

45

40

35

30

2050

25

55

1 15 7

X

10 18

25

15

1

Day

Operationalheating

Heating

flow

tem

pera

ture

°C

Heating ready for occupation

Operational heating + Heating ready for occupation

Figure 44 - Diagram of the concrete slab drying programmes

� Please comply with thestandards and instructionsof the manufacturer of thebui ld ing! A goodperformance of th isfunction is only possiblewi th an insta l la t ioncorrect ly implemented(hydraulic, electricity andadjustments)! This functioncan be stopped byanticipation when settingthe adjustment on “Stop”.

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 38: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

38 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

900 S Change of regime None, Protection mode,Reduced, Comfort,Automatic

1 Protectionmode

Operating mode at end of concrete slab drying period

Cooling circuit 1

901 U Regime off, Automatic off

902 U Comfort ambient temperature setpoint 17...40 °C 0,5 °C 24 °C

907 U Release 24h/day, Time programmeHC, Time programme 5 /Refresh

24h/day

908 I Flow temp setp at OT 25°C 6...35 °C 0,5 °C 20 °C

909 I Flow temp setp at OT 35°C 6...35 °C 0,5 °C 16 °C

912 I Cooling limit at OT - - -, 8...35 °C 0,5 °C 24 °C

913 S Lock time at end of heating - - -, 8...100 1 h 24

918 S Summer comp start at OT 20...50 °C 1 °C 26 °C

919 S Summer comp end at OT 20...50 °C 1 °C 40 °C

920 S Summer comp setp increase - - -, 1...10 °C 1 °C 4 °C

923 S Flow temp setp min OT 25°C 6...35 °C 0,5 °C 18 °C

924 S Flow temp setp min OT 35°C 6...35 °C 0,5 °C 18 °C

928 I Influence of the ambient temperature - - -, 1...100 % 1 % 80 %

If the installation is fitted with an room sensor:

This function enables you to choose the ambient temperature's influence on the setting.

If no value is entered, the setting is made based on the temperature control.

If the parameter is set at 100%, the setting is only based on the ambient temperature.

932 S Room temp limitation - - -, 0,5...4 0,5 °C 0,5 °C

938 S Mixing valve decrease 0...20 °C 1 °C 0 °C

939 S Type of servomotor 2-pos, 3-pos 3-pos

940 S Switching differential 2-pos 0...20 °C 0,5 °C 2,5 °C

941 S Servomotor travel time 30...873 s 1 s 240 s

945 S Mixing valve in heating mode Control, Open Control

946 S Lock time dewpoint limiter - - -, 10...600 min 10 min 60 min

947 S Flow temp setp incr hygro - - -, 1...20 °C 1 °C 10 °C

948 S Flow setp incr start at r.h. 0...100 % 1 % 60 %

950 S Flow temp diff dewpoint ---, 0...5 °C 1 °C 2 °C

963 S With prim contr/system pump No, Yes No*

*Basic setting : 1 circuit = No ; 2 circuits = Yes

969 S Change of regime None, off, Automatic off

Heating adjustment, Circuit 2

If the installation consists of 2 heating circuits (Only with the 2nd circuit option)

1010 U Comfort ambient temperature setpoint From reduced temperatureto 35°C

0,5 °C 20 °C

1012 U Reduced ambient temperature setpoint from frost-free temp… tocomfort temperature

0,5 °C 18 °C

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 39: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 39

Heat pump, Splir 1 service

1014 U Frost-free ambient temperature setpoint from 4°C… to reducedtemperature

0,5 °C 8 °C

1016 S Maximum comfort setpoint 20…35 °C 1 °C 28 °C

1020 I Heating curve slope 0.1... 4 0,02 0.5

1021 I Off-set of the heating curve -4.50 °C… 4.5 °C 0,5 °C 0 °C

1026 S Adaptation of the heating curve (see § 3.3.2) off, ON off

1030 I Summer/Winter heating limits 8 °C … 30 °C 0,5 °C 18 °C

When the average of the external temperatures over the past 24 hours reaches 18°C, the regulator switches off the

heating (as an economy measure).

During summer mode, the display shows "Eco".

This function is only active in automatic mode.

1032 S Limit of daily heating -10 °C … 10 °C 1 °C -3 °C

This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.

Increasing the value delays the switchover to summer regime.

Decreasing the value advances the switchover to summer regime.

This function is only active in automatic mode.

1050 I Influence of the ambient temperature 1%... 100% 1% 20%

If the installation is fitted with a room thermostat:

This function enables you to choose the ambient temperature's influence on the setting.

If no value is entered, the setting is made based on the temperature control.

If the parameter is set at 100%, the setting is only based on the ambient temperature.

1090 S Maximum optimisation on switch-on 0 … 360 min 10 min 120 min

1091 S Maximum optimisation on switch-off 0 … 360 min 10 min 120 min

1100 S Start of increase in reduced functioning mode - 30 … 10 °C, --- °C 1 °C ---

1101 S End of increase in reduced functioning mode - 30 … 10 °C, --- °C 1 °C - 5 °C

1130 S Mixer valve increase 0 … 50 °C 1 °C 0 °C

1132 S Type of servomotor 2-pos, 3-pos 3-pos

1133 S Switching differential 2-pos 0 … 20 °C 0,5 °C 2 °C

1134 S Servomotor travel time 30 … 873 s 1 s 240 s

1150 I Floor controlled drying (fig. 44) off

– off: Early interruption of the current programme, programme inactive– Operational heating– Heating ready for occupation– Operational heating + ready heating– Ready heating + operational heating– Manual

Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after

25 days.

1151 I Manual floor drying setpoint(if line 850 = manual)

0 °C… 95°C 1 °C 25 °C

This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The

concrete slab-drying programme stops automatically after running for 25 days.

1156 I Current drying day 0 ... 32

1157 I Terminated drying days 0 ... 32

1161 S Excess heat evacuation off, Heating regime,Permanent

Permanent

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 40: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

40 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

1200 S Change of regime None, Protection mode,Reduced, Comfort,Automatic

1 Protectionmode

Operating mode at end of concrete slab drying period

DHW setting (domestic hot water) (Only with the DWH kit option)

1610 U Comfort setting Reduced setting (line 1612)… to65 °C

1 60 °C

The backup electrical system is required to reach this level.

1612 U Reduced setting 8 °C,,,toComfort setting (line 1610)

1 40 °C

1620 I Release of DHW load 24h/dayHeating circuit timeprogrammeProgramme 4/DHWOff-peak tariff (Off-peak)Programme 4/DHW andOff-peak

Programme4/DHW

24h/day: The temperature of the DHW is constantly maintained at the DHW comfort setting.

Heating circuit time programme: The DHW is produced according to the programming for the ambient

temperature (with 1 hour in advance when switched on).

Programme 4/DHW: The DHW programme is separate form the heating circuit programme.

Off-peak tariff*: The electrical backup heating is only authorised to operate during the off-peak period.

Programme 4/DHW and Off-peak*:

The electrical backup heating is authorised to operate during the comfort period or off peak.

* - Connect the "Power Provider" contact to input EX5 or EX4.. (See Figure 38, page 29). In the case of a day /night

contract, the electric back-ups for the DHW tank are subject to the power supplier's tariffs. Switching on the electric

back-up for the DHW tank is only authorised during off-peak hours.

1640 I Anti-legionella function off,Periodic (depending on theline setting 1641)Set day of the week(depending on the linesetting 1642)

off

1641 I Intervals for the anti-legionella cycles 1 to 7 1 day 7

1642 I Weekday anti-legionella cycle run Monday, Tuesday,... Saturday

1644 I Hour of anti-legionella cycle run --:--, 00 :00… 23 :50 --:--

If no value is entered, no anti-legionella cycle has been run.

1645 I Anti-legionella setting 55 °C… 95 °C 65 °C

1646 I Duration of anti-legionella cycle --:--, 10 min… 360 min 30

1647 I Circulating pump anti-legionella cycle ON, off ON

1660 I Release of circulating pump Programme 3/HCP,Release of DHW,Programme 4/DHW

Release ofDHW

Swimming pool (Only with swimming pool kit option)

2056 U Generator heating setting 8...35 22

Heat pump

2884 I Release el flow below OTElectrical release - start-up with outside temperature

-30...30 °C 2 °C

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 41: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 41

Heat pump, Splir 1 service

2920 S With electrical utility lock (EX4) Locked, Released Released

Released : HP = ON _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON

Locked : HP = off _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON

Additional generator (Boiler connection)

3700 S Release under external temperature --- , -50 … 50 °C 0,5 °C 2 °C

3705 I Time delay on stopping 0 … 120 min 1 min 20

Domestic hot water (DHW) (Only with the DWH kit option)

5020 S Overheight initial setting 0 … 30°C 1 °C 5 °C

5024 S Differential 0 … 20°C 1 °C 7 °C

5030 S Limitation on load duration 10 … 600 min 10 min 90 min

5060 S Electrical resistance regime Replacement, Summer,Always, Cooling regime

Replacement

5061 S Release of electrical resistance 24h/day, Release of DHW,Programme 4/DHW

Release ofDHW

Installation configuration

5700 I Pre-setting 1,2,3...12 1 1

This control enables you to choose one of the 8 pre-selected installation configurations. The hydraulic layouts for

the various configurations are detailed in the section: "Installation Configurations".

– Pre-setting 1 : 1 heating circuit– Pre-setting 2 : 1 heating circuit and DHW tank.– Pre-setting 3 : 2 heating circuits.– Pre-setting 4 : 2 heating circuits and DHW tank.– Pre-setting 5 : Boiler connection and 1 heating circuit.– Pre-setting 6 : Boiler connection and 2 heating circuits– Pre-setting 7 : Boiler connection, 1 heating circuit and DHW tank.– Pre-setting 8 : Boiler connection, 2 heating circuits and DHW tank.– Pre-setting 9 to 12 : Do not use for heat pump model "S". Reserved only for heat pump model "Duo"

5711 S Cooling circuit 1 Off, System with 4 tubes,System with 2 tubes

Off

5870 S Combined DHW tank no, yes No

6046 I Function input H21 - Operating mode change HCs + DHW2 - Operating mode change HCs3 - Operating mode change HC14 - Operating mode change HC26 - Error/alarm message9 - Dew point monitoring16 - Swimming pool release

1 … 16 1 9

6047 I Contact type H2NC - Normally-closed, NO - Normally-opened

NC, NO NO

6100 S External temperature sensor correction -3 … 3 °C 0,1 °C 0 °C

6120 S Installation frost-free mode ON, Off ON

6205 S Re-initialise parameters No, yes No

6220 S oftware version (RVS) 0...99 0

Error

6711 U Heat pump Reset No, yes No

6740 S Temperature alarm initiation CC1 ---, 10… 240 min 10 min ---

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 42: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

42 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

6741 S Temperature alarm initiation CC2 ---, 10… 240 min 10 min ---

6745 S DHW load alarm ---, 1… 48 h 1 h ---

6746 S Temperature alarm initiation Cold 1 ---, 10… 240 min 10 min ---

6800 S History 1 Time, Date, Error code

6802 S History 2 Time, Date, Error code

6804 S History 3 Time, Date, Error code

6806 S History 4 Time, Date, Error code

6808 S History 5 Time, Date, Error code

6810 S History 6 Time, Date, Error code

6812 S History 7 Time, Date, Error code

6814 S History 8 Time, Date, Error code

6816 S History 9 Time, Date, Error code

6818 S History 10 Time, Date, Error code

Maintenance / special regime

7070 I Interval time for maintenance HP --- , 1… 240 1 Month ---

7071 I Operating time HP since last maintenance.Reset ? (no, yes)

0… 240 1 Month 0

7072 I Maximum number of starting of the compressor 1,authorized per hour of operation.

--- , 0,1 … 12 0,1 ---

7073 I Average number of starts of the compressor per hour ofoperation, since the 6 last weeks.Reset ? (no, yes)

0 … 12 0

7076 I Maximum discrepancy condens / week --- , 1… 250 1 ---

7077 I Current maximum discrepancy condens / weekReset ? (no, yes)

0… 250

7078 I Minimum discrepancy condens / week --- , 1… 250 1 ---

7079 I Current minimum discrepancy condens / weekReset ? (no, yes)

0… 250 0

7090 I DHW tank period --- , 1… 240 1 Month ---

7091 I DHW tank since maintenanceReset ? (no, yes)

0… 240 0

7092 I Heat pump DHW min load temperature 5… 80 °C 1 5 °C

7141 U Emergency regime Off, ON Off

Off: The heat pump does not use the backup electrical heating system or the boiler connection when a fault occurs (error

370)

ON: The heat pump uses the backup electrical system or the boiler connection when a fault occurs (error 370).

In the "ON" position, the energy costs can be onerous if the error is not eliminated.

7142 S Emergency service operating type Manual, Automatic Manual

Manual: Emergency mode is not active when a fault occurs. (Emergency mode = OFF)

Automatic: Emergency mode is active when a fault occurs. (Emergency mode = ON)

In automatic position, the energy cost can be onerous if the error is not detected and eliminated.

7150 I External temperature simulation --- , -50 … 50 °C 0,5 ---

7181 I Contact's telephone 1 0 … 255

7183 I Contact's telephone 2 0 … 255

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 43: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 43

Heat pump, Splir 1 service

Inputs / outputs test

7700 I Relay test No test

This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check

that the relays are working and that the cabling is correct. Check that each appliance in the installation is operating

correctly.

– No test _ Everything is on STOP _ Relay output QX23, QX22, QX21 module 1 _ Relay output QX1 toQX6 _ Relay output QX23, QX21, QX22 module 2 _ Relay output QX7

The display shows the “Key” symbol. Pressing the Info button displays “Error 368”

Warning: The component being tested is receiving electrical power throughout the test.

7710 I Output (Ux) test --- , 0 … 100 % 1 ---

7711 I Voltage (Ux) value 0 … 10 Volt 0

7720 I Digital outputs test 0 = No test1 = Everything is on STOP2 = Digital output DO13 = Digital output DO

No test

7721 I Digital output DO1 Cooling regime,Heating regime

Heatingregime

7722 I Digital output DO2 Off, ON ON

7730 I External temperature (B9) -50 … 50 °C 0

7820 I Sensor temperature BX1 -28 … 350 °C 0

7823 I Sensor temperature BX4 -28 … 350 °C 0

7824 I Sensor temperature BX5 -28 … 350 °C 0

7830 I Sensor temperature BX21 module 1 -28 … 350 °C 0

7831 I Sensor temperature BX22 module 1 -28 … 350 °C 0

7832 I Sensor temperature BX21 module 2 -28 … 350 °C 0

7833 I Sensor temperature BX22 module 2 -28 … 350 °C 0

7841 I Contact status H1 Open, Closed Open

7846 I Contact status H2 Open, Closed Open

7855 I Contact status H3 Open, Closed Open

7914 I Input EX4 0, 230 V 0

7915 I Input EX5 0, 230 V 0

7916 I Input EX6 0, 230 V 0

Etat

8000 I State heating circuit 1 0

8001 I State heating circuit 2 0

8003 I State DHW 0

8004 I State cooling circuit 1 0

8006 I State heat pump 0

8011 I State swimming pool 0

8022 I State supplementary source 0

8050 I History 1 Time, Date, State code

8052 I History 2 Time, Date, State code

8054 I History 3 Time, Date, State code

8056 I History 4 Time, Date, State code

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 44: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

44 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

8058 I History 5 Time, Date, State code

8060 I History 6 Time, Date, State code

8062 I History 7 Time, Date, State code

8064 I History 8 Time, Date, State code

8066 I History 9 Time, Date, State code

8068 I History 10 Time, Date, State code

Generator diagnosis

8402 I Electrical resistance flow 1 Off, ON Off

8403 I Electrical resistance flow 2 Off, ON Off

8406 I Condenser pump Off, ON Off

8410 U Heat pump return temperature 0 … 140 °C

Setpoint (flow) HP 0 … 140 °C

8412 U Heat pump flow temperature 0 … 140 °C

Setpoint (flow) HP 0 … 140 °C

8413 U Compressor modulation 0 … 100%

8425 I Condenser temperature difference -50 … 140 °C

8440 I Min forced stop, compressor 1 0 … 255 min

8454 S Locking time Heat PumpReset ? (no, yes)

0 … 2730 h

8455 S Heat pump stops counterReset ? (no, yes)

0 … 65535

8456 S Hours run electrical flowReset ? (no, yes)

0 … 2730 h

8457 S Start counter electrical flowReset ? (no, yes)

0 … 65535

Diagnostics consumers

8700 U External temperature -50 .. 50 °C

8701 U Minimum external temperatureReset ? (no, yes)

-50 .. 50 °C

8702 U Maximum external temperatureReset ? (no, yes)

-50 .. 50 °C

8703 I Attenuated external temperatureReset ? (no, yes)

-50 .. 50 °C

This is the average of the external temperature over a 24-hour period. This value is used for automatic Summer /

Winter switchover (line 730)

8704 I Mixed external temperature -50 .. 50 °C

The mixed external temperature is a combination of the current external temperature and the average external

temperature calculated by the regulator. This value is used for calculating the initial temperature.

8720 I Ambient relative humidity 0 … 100 %

8721 U Room temperature 0 .. 50 °C

8722 I Dew point 1 0 … 50 °C

8730 I Circulation pump, circuit 1 Off, ON Off

8731 I Mixer valve HC1 open Off, ON Off

8732 I Mixer valve HC1 closed Off, ON Off

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 45: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 45

Heat pump, Splir 1 service

8740 U Room temperature 1 0 … 50 °C 20 °C

Ambient temperature setting 1 4 … 35 °C 20

8743 U Flow temperature 1 0 … 140 °C 50

Flow temperature setpoint 1 0 … 140 °C 50

8756 U Cooling flow temperature 1 0 … 140 °C 0

Cooling flow temperature setpoint 1 0 … 140 °C 0

8760 I Circulation pump, circuit 2 Off, ON Off

8761 I Mixer valve HC2 open Off, ON Off

8762 I Mixer valve HC2 closed Off, ON Off

8770 U Room temperature 2 0 … 50 °C 20

Ambient temperature setpoint 2 4 … 35 °C 20

8773 U Flow temperature 2 0 … 140 °C 50

Flow temperature setpoint 2 0 … 140 °C 50

8820 I DHW pump Off, ON Off

8821 I DHW electrical resistance Off, ON Off

8830 U DHW (domestic hot water) temperature 0 … 140 °C

DHW temperature setpoint 5 … 80 °C 50

8840 S DHW pump operating timesReset ? (no, yes)

0 … 2730 h

8841 S DHW pump start-ups counter 0 … 2730 h

8842 S DHW electric operating times 0 … 2730 h

8843 DHW electric start-ups counter 0 … 65535

8900 U Swimming pool temperature 0 … 140 °C

Swimming pool temperature setpoint 0 … 80 °C 24

8950 I Common flow temperature 0 … 140 °C

I Common flow temperature setpoint 0 … 140 °C 0

8957 I Common flow setpoint, refrigeration 0 … 140 °C

9031 I Relay output QX1 Off, ON Off

9032 I Relay output QX2 Off, ON Off

9033 I Relay output QX3 Off, ON Off

9034 I Relay output QX4 Off, ON Off

9035 I Relay output QX5 Off, ON Off

9036 I Relay output QX6 Off, ON Off

9037 I Relay output QX7 Off, ON Off

9050 I Relay output QX21 module 1 Off, ON Off

9051 I Relay output QX22 module 1 Off, ON Off

9052 I Relay output QX23 module 1 Off, ON Off

9053 S Relay output QX21 module 2 Off, ON Off

9054 I Relay output QX22 module 2 Off, ON Off

9055 I Relay output QX23 module 2 Off, ON Off

Line Function Setting rangeor display

Settingincrement

Basicsetting

Page 46: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

46 Installation and operating manual “1350-EN”

Heat pump, Splir 1 service

4 Configuring the installation

� Optional DHW kit

DHW tank control (with electrical back-up) requiresthe use of the DWH kit.

Warning: The tank must be fitted with an electricback-up, particularly for anti-legionella cycles.

Please refer to section (Operating principle, page 13)

� Optional 2nd circuit kit

The control of 2 heating circuits requires theinstallation of the 2nd circuit.

I f the ins ta l la t ion cons is ts of rad ia tors (orfan-convectors) and a heated floor, zone 2 willcorrespond to the radiator (or fan-convectors) zoneand zone 1 to the heated floor zone.

� Optional boiler connection kit

The connection of an oil or gas boiler to the heatpump requires the instal lat ion of the boi lerconnection kit.

When a boiler is connected to the heat pump, theheat pump's electric back-ups must not beconnected. It is the boiler that provides theheating back-up on the coldest days.

The boiler is controlled by the heat pump.

Please refer to the instructions supplied with theboiler connection kit.

� Swimming pool kit option

Please refer to the instructions supplied with theswimming pool kit.

Configuration(Parameter 5700)

Type of installation Page

Pre-setting 1 1 heating circuit 48

Pre-setting 2 1 heating circuit and DHW tank 49

Pre-setting 3 2 heating circuits 50

Pre-setting 4 2 heating circuits and DHW tank 51

Pre-setting 5 Boiler connection and 1 heating circuitPlease refer to the

instructions suppliedwith the boilerconnection kit.

Pre-setting 6 Boiler connection and 2 heating circuits

Pre-setting 7 Boiler connection, 1 heating circuit and DHW tank

Pre-setting 8 Boiler connection, 2 heating circuits and DHW tank

Pre-setting 9

Do not use for heat pump model (S). Reserved only for heat pump model (Duo)Pre-setting 10

Pre-setting 11

Pre-setting 12

� Please consult us regarding any other installation configuration.

Page 47: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 47

Heat pump, Splir 1 service

4.1 Configuration 1, 2, 3 or 4:heat pumps with electric back-ups

DHW tank control (with electrical back-up) requiresthe use of the DWH kit.

The control of 2 heating circuits requires theinstallation of the 2nd circuit.

4.1.1 Hydraulic connections

� In the case of a mixed DHW tank

Install the directional valve on the heating circuit (oncircuit 2 if it exists).

� In the case of 2 heating circuits

With the 2nd circuit kit, the hydraulic module'scirculation pump (CC1) must be moved and installedin a box of the 2nd circuit kit (CC1).

4.1.2 Electrical connections

• 1 - Power supply to external unitPlease refer to section (Electrical connections onthe external unit side page 26).

• 2 - Interconnection between the external unit andthe hydraulic module (See fig. 37, p. 28).

• 3 - Power supply to the electrical back-ups:

- Connect the electrical supply for the back-ups(terminals 9, 10 and 11) to the electrical panel. (seefig. 37, p. 28).

• 4 - Outside sensor (see fig. 37, p. 28).

• 5 - Air thermostat and/or remote control (Option,See fig. 38, p. 29).

• 6 - Contract with the power provider:

- Connect the "Power Provider" contact to input EX5or EX4. (see fig. 38, p. 29)

� In the case of a mixed DHW tank

Please refer to the instructions supplied with theDWH kit (Ref. 073950).

• 7 - Connect the directional valve to connector QX4,(See fig. 38, p. 29).

• 8 - Connect the domestic water sensor to terminalBX1 on the heat pump’s control panel (see fig. 38,p. 29).

• 9 - Connect the back-up resistance to terminal 19(Earth) and relay RP DHW to terminals 2 (L) and 4(N). (see fig. 37, p. 28)

• 10 - Connect the electrical power supply for thedomestic water back-up (terminals 17, 18 and 19) tothe electric panel. (see fig. 37, p. 28)

� In the case of 2 heating circuits

Please refer to the instructions supplied with thesecond circuit kit.

11 - Circulation pump

12 - Circulation pump

13 - Mixer valve

14 - Initial sensor

() - Interconnection between RVS and AVS

� In the case of a heated floor

Heated floor thermal safety fuse

• 20 - Connect the safety component to input EX6.

230 V on input EX6 = stoppage of heat pump (thesystem displays Error 369).

4.1.3 Parametering the setting

• Adjust the configuration: 1, 2, 3 or 4, Line 5700.

• Adjust the DHW programme (Line 1610 to 1661)

• 1 heating circuitAdjust the heating curve slope.Line 720

• 2 heating circuitsAdjust the heating curve slope.Line 720 (Circuit 1)Line 1020 (Circuit 2)

4.1.4 Special cases

Please consult us regarding any other installationconfiguration

� Parameter 5700

Configuration 1 : 1 heating circuit (See Figure page 48)

Configuration 2 : 1 heating circuit and DHW tank. (See Figure page 49)

Configuration 3 : 2 heating circuits (See Figure page 50)

Configuration 4 : 2 heating circuits and DHW tank. (See Figure page 51)

Page 48: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

48 Installation and operating manual “1350-EN”

Heat pump, split 1 service

CC

SA

SE

R

SP

CC

SA

SE

R

SP

1

2

3

6 5

4

20

Legend

CC - Heating circulation pump

R - Radiators (or fan convectors)

SA - Room thermostat (option)

SE - Outside sensor

SP - Heated floor thermal safety fuse

Configuration 1 :1 heating circuit.

� See detailed instructionson Page 47

Overview of all the electrical connections

Overall hydraulic layout

Page 49: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 49

Heat pump, split 1 service

M

CC

VD

SA

Kit 073950

SSaSE

AE

RR

SP

CAR

M

CC

VD

SA

Kit 073950

SSaSE

AE

RR

SP

1

2

3

4

5

7

8

9

10

6

20

Legend

CAR - Non-return valve

AE - Electric back-up

CC - Heating circulation pump

R - Radiators (or fan convectors)

SA - Room thermostat (option)

SE - Outside sensor

SP - Heated floor thermal safety fuse

SSa - DWH sensor

VD - Distribution valve

Configuration 2 :1 heating circuit and DHW tank.

Overview of all the electrical connections

Overall hydraulic layout

� See detailed instructionson Page 47

Page 50: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

50 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Configuration 3 :2 heating circuits

Circuit 2

Circuit 1

CC2

M

VM1

CC1

SA2

SA1

Kit073952

SDp1

SE

R

SPCAR

CAR

Circuit 2

Circuit 1

CC2

M

VM1

CC1

SA2

SA1

Kit073952

SDp1

SE

R

SP

1

2

3

4

5

11

1213

14

56

AVS 20

Legend

CAR - Non-return valve

CC1 - Heating circulation pump, Circuit 1 (Remote heat

pump circulation pump)

CC2 - Heating circulation pump, Circuit 2

R - Radiators (or fan convectors)

SA1 - Room thermostat, Circuit 1 (option)

SA2 - Room thermostat, Circuit 2 (option)

SE - Outside sensor

SDp1 - Flow sensor, Circuit 1

SP - Heated floor thermal safety fuse

VM1 - Mixer valve, Circuit 1

Overview of all the electrical connections

Overall hydraulic layout

� See detailed instructionson Page 47

Page 51: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 51

Heat pump, split 1 service

Circuit 2

Circuit 1

M

CC2

VD

M

VM1

CC1

SA2

SA1

Kit073952

SDp1

Kit073950

SSaSE

AE

R

SP

R

CAR

CAR

Circuit 2

Circuit 1

M

CC2

VD

M

VM1

CC1

SA2

SA1

Kit073952

SDp1

Kit073950

SSaSE

AE

R

SP

R

1

2

3

4

5

7

8

9

10

6

11

1213

14

5

AVS 20

Legend

AE - Electric back-up

CAR - Non-return valve

CC1 - Heating circulation pump, Circuit 1 (Remote heat

pump circulation pump)

CC2 - Heating circulation pump, Circuit 2

R - Radiators (or fan convectors)

SA1 - Room thermostat, Circuit 1 (option)

SA2 - Room thermostat, Circuit 2 (option)

SE - Outside sensor

SDp1 - Flow sensor, Circuit 1

SSa - DWH sensor

SP - Heated floor thermal safety fuse

VD - Distribution valve

VM1 - Mixer valve, Circuit

Configuration 42 heating circuits and DHW tank.

Overview of all the electrical connections

Overall hydraulic layout

� See detailed instructionson Page 47

Page 52: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

52 Installation and operating manual “1350-EN”

Heat pump, split 1 service

5 Electrical wiring diagrams

Gre

en

123456

123456

123456

123456

123

123

123

123

12

12

12

12

1234

1234

1212

123

123

CN71

CN73

CN72

CN70

W4

W2

W1

W3

W11

W10

CN40

CN801

W7W8W9

CN30 4WV

PMV

F M

S (S)

C (T)

R (R)

C M

2( N )

1 3 L N

15A 250V

3.15A250V

Black

Red

White

Yellow

Blue

Red

White

Black

Red

Brown

Blue

Orange

Yellow

White

Black

Black

Black

Black

Black

Black

Black

White

White

Red

Brown

Brown

Brown

Brown

Black

Black

White

Red

Yello

w

Yello

w

Bla

ck

Bla

ck

Bla

ck

Red

White

Black

4-way valve

Ventilator

Electronic

expansion

valve

Compressor

Reactance

Evaporator

outlet

Discharge

Compressor

Outside

Fuse

250V 5A

Terminal

block

Interconnection

between the outside unit

and the hydraulic module

Electricity supply

Fuse 250V 20A

Regulation board

Fuse

Fuse

Tem

pera

tuurv

oele

rs

Evaporator

centre

Figure 45 - Electrical wiring of Outside unit Model 050, 065, 080

Page 53: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 53

Heat pump, split 1 service

1098765432110987654321

21

1098765432110987654321

654321

654321

43214321

43214321

321

321

21

2121

76543

21

21

21

654321

7654321

654321

321

321

21

21

21

21

21

21

21

21

21

21

CN700

CN801

CN500

CN110CN1

CN400CN200

CN11

CN60

CN61

CN62

CN64

CN90

CN40CN42

CN303 CN301W306

W307

W302

W301

W17

W16

TM102TM101

W303W

W304V W305

U

W8

W7

W13

W12

L2 L1+

P

N1

N2

L0

TM600TM601

W4

RC

S

CN100

1 2

W29W28W25W26

W21 W20W9 W17

W3

W18W2W1

W19

1 2 3 L N

F M

PMV

4WV

C M

Klemmenstrook

ACTPM

I P M PCB

RedRed

BrownBrown

BlueBlue

BlackBlack

BrownBrown

Black

Black

WhiteYellowOrangeBlueBrownRed

Red

Red

Black

GreenBlackWhiteWhite

Black

Purple

White

Yellow Yellow

Blue Blue

Black

Red

Brown

Orange

Black Black

White White

Red Red

Orange

Orange

Bla

ck

Whi

te

Bro

wn

Red

Bro

wn

Red

Ora

nge

Yel

low

Gre

enB

lue

Pur

ple

Gre

yB

lack

Whi

te

Bro

wn

Red

Ora

nge

Yel

low

Bla

ck

Bla

ck

Whi

te

Gre

y

Whi

teW

hiteWhi

te

Whi

te

Terminal block

Fuse 250V 25A

HP pressure switch

Coil

Posistor

Compressor

Terminal block

Capacitor PCB

Power card

Regulation board

Evaporator centre

Discharge

Compressor

Outside

Tem

pera

ture

sensors

4-way valve

Electronic

expansion valve

Electricity supply

Interconnection

between the outside unit

and the hydraulic module

BrownYellowWhiteBlack Ventilator

Figure 46 - Electrical wiring of Outside unit Model 095

Page 54: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

54 Installation and operating manual “1350-EN”

Heat pump, split 1 service

R(R)

S(S)

C(T)

Temperature sensors

Discharge Compressor

Outside

Compressor

Terminal block

Coil

Red

White

Black

White

Red

Black

Module

filtre

actif

BrownRed

Orange

Yellow

Yellow

Blue

Posistor

Orange

Orange

Red

Black

White

Black

White

Brown

Bla

ck

Fu

se

25

A

Wh

ite

Bla

ck

Gre

en

Terminal block

Re

d

Wh

ite

Electrical cabling

Bla

ck

Re

d

Wh

ite

Bla

ck

Bro

wn

HP pressure switch

4-way valve

Electronic

expansion

valve

Fuse

Fuse

Ventilator 1

Ventilator 2

Red

Red

Black

Black

Red

WhiteYellow

Brown

Red

Brown

BlueOrange

YellowWhite

Black

Red

WhiteYellow

Brown

Black

Black

Black Black

Brown Brown

Blue

Filter

Evaporator outlet

Evaporator centre Compressor casing

Interconnection

between the outside unit

and the hydraulic module

Regulation board

Fu

se

10

A

Figure 47 - Electrical wiring of Outside unit Model 128

Page 55: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

Installation and operating manual “1350-EN” 55

Heat pump, split 1 service

Temperature sensors

Dis

charg

e

Evapora

tor

Com

pre

ssor

Outs

ide

Compressor

Regulation board

Terminal block

Coil

Posistor

Terminal block

Electricity

supply

HP pressure switch

4-way valve

Electronic

expansion

valve

Fuse

Ventilator 1

Ventilator 2

Bla

ck

Bro

wn

Bro

wn

Blu

e

Bla

ck

Active

filter

unit

White

Brown

Filter EMI

Filter EMIConnector

Yellow

Blue

OrangeRed

Red

Brown

Yellow

Diode bridgeRelay

Red

White

Red

White

Bla

ck

Gre

y

Gre

y

Bla

ck

Red

Filter EMI FilterFilter EMI

Red

Red

Black

Yellow

Brown

White

Orange

Blue

Black

Red

Black

Yellow

Brown

White

Black

Yellow

Brown

White

Red

White

Black

White

Bla

ck

White

Bla

ck

Gre

en

White

Bla

ck

Bla

ck

Red

Bro

wn

Com

pre

ssor

casin

g

Interconnection

between the outside unit

and the hydraulic module

Filter EMI

White

Violet

Terminal block

BlackBlack

Ora

nge

Ora

nge

Filter EMI

Fuse

10

A

Red

Figure 48 - Electrical wiring of Outside unit Model 155

Page 56: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

56 Installation and operating manual “1350-EN”

Heat pump, split 1 service

CN9

CN1

CN2

CN4

CN5

CN14

CN15

CN7

CN8

CN103

CN106

CN114

CN105

CN113CN116

CN104

MBX5MBX4MDO2MDO1

QX7QX6QX5

QX3

N

N

L

UrefUX

H3MH1

A1 A2

B1 B2

A1 A2

B1 B2

2a 2b

1a 1b

1 2 3 4 5 6 7 8 9 10 11 121314151617 1819

RpECS Rp1 Rp2

X50ouX30

Condensationsensor

Return sensor

Flow sensor

Heating circulation pump

Resistance 2of the back-up unit

Resistance 1of the back-up unit

Safety thermostat

Start/stopswitch

Timed fuse3,15 A - 250V

Figure 49 - Electrical wiring, Hydraulic module (Except installer's connections)

Connection to terminal block andpower relays (see figure 37, page 28)

Connections to the heat pumpregula tor (accessor ies andoptions) (see figure 38, page 29)

Page 57: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

6 Troubleshooting

Depending on whether the fault comes from theexternal unit or the hydraulic module, the fault maybe indicated by the digital display or the diode on theinterface cards.

6.1 Faults displayed on the hydraulicmodule

Faults or breakdowns on the hydraulic mode areindicated by the display on the user interface.

The display shows the "Bell" symbol .

Press the Info key for more details on the originof the fault.

When the error has been resolved, the faults arere-initialised at zero automatically.

Installation and operating manual “1350-EN” 57

Heat pump, split 1 service

Hydraulic module : Fault visible on the digital display

Error number Error description Error locationHeat pump operationdespite the error

- No connectionFai lure to comply wi th roomthermostat's polarity

No

10 Outside sensor B9 Yes with OT = 0 °C

33 Heat pump initial temperature sensor error B21 Yes

44 Heat pump return temperature sensor error B71 Yes (Model S)

50 DHW temperature sensor B3 Yes

60 Ambient temperature sensor 1 Yes

65 Ambient temperature sensor 2 Yes

105 Maintenance message Yes

121 Flow temperature for (HC1) not reached Yes

122 Flow temperature for (HC2) not reached Yes

127 Anti-legionella temperature not reached Yes

369 External fault (safety component) No

370 Outside unit connection error See below and fig. 58 and 59 No

Hydraulic module : Flashing of the diode visible on the interface card

Diode display Erroneous element

1 Flash Transmission error, "hydraulic module - external unit"

2 Flashes Abnormal discharge temperature or defective discharge sensor

3 Flashes Defective exchanger sensor

4 Flashes Defective external temperature sensor

5 FlashesAbnormal compressor temperature or defective compressortemperature sensor

6 Flashes HP pressure switch cut off

7 Flashes Abnormal current quality

8 Flashes Current quality detection circuit defective

9 Flashes Active filter error

10 Flashes Compressor is not operating

11 Flashes External fan error

12 Flashes Compressor casing resistance fault

13 Flashes Active filter cut off for over-intensity

CN9

CN1

CN2

CN4

CN5

CN14

CN15

CN7

CN8

Page 58: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

58 Installation and operating manual “1350-EN”

Heat pump, split 1 service

Outside unit, Reference AOYA18LACL (Model 050 and 065) and Reference AOYA24LACL (Model 080)

Diode display Erroneous element

0,1 seconds lit and 0,1 seconds unlit Defective temperature sensor (see hydraulic module)

0,5 seconds lit and 0,5 seconds unlit Abnormal intensity detector error

2 seconds lit and 2 seconds unlit Electric current circuit breaker error

5 seconds lit and 5 seconds unlit Defective fan motor

0,1 seconds lit and 2 seconds unlit Position of the compressor’s rotor not detected

5 seconds lit and 0,1 seconds unlit Abnormal PAM circuit voltage

1 seconds lit and 0,1 seconds unlit Timer cut off

2 seconds lit and 5 seconds unlit Abnormal compressor temperature

5 seconds lit and 2 seconds unlit Active filter error

Permanently lit Abnormal discharge temperature

Outside unit, Reference AOY30LNAWL (Model 095)

Diode display Erroneous element

0,1 seconds lit and 0,1 seconds unlit Defective temperature sensor (see hydraulic module)

0,5 seconds lit and 0,5 seconds unlit Defective IPM card

2 seconds lit and 2 seconds unlit Communication serial bus error (red wire)

5 seconds lit and 5 seconds unlit Defective fan motor

0,1 seconds lit and 2 seconds unlit Position of the compressor’s rotor not detected

5 seconds lit and 0,1 seconds unlit Defective ACTPM card

Permanently lit Abnormal discharge temperature

6.2 Faults displayed on the external unit

To access the electronic board, you must remove the front (right-hand) facing from the external unit.

Faults are coded by diode flashes.

Page 59: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

6.3 Information display

Various data can be displayed by pressing the infobutton.

Depending on the type of unit, configuration andoperating state, some of the info lines listed belowmay not appear.

- Possible error messages from the error code list(See table, page 57).

- Possible service messages from the maintenancecode list.

- Possible special mode messages.

- Various data (See below).

Designation Line

Floor drying current setpoint -

Current drying day -

Terminated drying days -

Room temperature 8721

State heat pump 8006

State supplementary source 8022

State DHW 8003

State swimming pool 8011

State heating circuit 1 8000

State cooling circuit 1 8001

State heating circuit 2 8004

External temperature 8700

Room setpoint 1 8740

Flow temperature 18743

Flow temperature setpoint1

Room setpoint 2 8771

Flow temperature 28773

Flow temperature setpoint 2

DHW (domestic hot water) temperature 8830

Heat pump return temperature8410

Setpoint (flow) HP

Heat pump flow temperature8412

Setpoint (flow) HP

Swimming pool temperature8900

Swimming pool temperature setpoint

Installation and operating manual “1350-EN” 59

Heat pump, split 1 service

Outside unit, Reference AOYA45LATL (Model 128) and Reference AOY54LJBYL (Model 155)

Diode display Erroneous element

1 Flash Transmission error, "hydraulic module - external unit"

2 Flashes Defective “discharge” temperature sensor

3 Flashes Defective “evaporator” temperature sensor

4 Flashes Defective “external” temperature sensor

5 Flashes (Model 128) Defective “evaporator centre” temperature sensor

6 Flashes (Model 128) Abnormal discharge temperature

7 Flashes Defective compressor temperature sensor

8 Flashes Defective “compressor casing” temperature sensor

9 Flashes Defective HP pressure switch

10 Flashes (Model S 13) Abnormal compressor temperature

12 Flashes Defective IPM card

13 Flashes Position of the compressor’s rotor not detected

14 Flashes Compressor is not operating

15 Flashes Defective upper fan motor

16 Flashes Defective lower fan motor

5 seconds lit and 1 seconds unlit Switched to safety mode

1 seconds lit and 1 seconds unlit (Model 128) Switched to vacuum

Permanently lit No error

Page 60: Installation and operating manual - Klima-Therm · Installation and operating manual intended for professionals ... •Room thermostat T55 ... combined with a DHW tank)

7 Instructions for the user

Explain to the user how his installation operates, inparticular the functions of the room thermostat andthe programmes accessible to him from the userinterface.

Emphasise that a heated floor has significant inertiaand that therefore any adjustments must be madeprogressively

Also explain to the user how to check the filling of theheating circuit

60 Installation and operating manual “1350-EN”

Heat pump, split 1 service