Page 1: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

INNOVATION SAFETY EFFICIENCY

www.bluekit .euEFFICIENCY

REGULATED VENTILATIONFOR LIFT SHAFTS SIMPLE AND EFFICIENT BLUEKITVENTILATION FLAPS

Page 2: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

VERTICAL MOUNTINGin the shaft/on the facade

Abbreviations:- HV: Horizontal vertical- TF: Thermo Flap- LF: Louvre window- S: Sheet steel- A: Aluminum

The ventilation components constitute a key factor for ventilation regulation and optimization. They are crucial for the execution of an efficient energetic concept and contribute to the decrease of building operating costs. It is possible to combine our BlueKit® system with louvre windows or ventilation flaps which are in accordance with EN 12101-2, together or without protection accessories such as weather protection grilles or roof vents.

HORIZONTAL MOUNTINGin the shaft head/on the roof

Page 3: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

Contents

New building

Horizontal mounting

Ventilation flap JK-180 HV .............................................. 4

Ventilation flap JK-180 HV-dB ......................................... 6

Roof vent JK-180 HVC ..................................................... 8

Roof vent with blades JK-180 HVL ................................ 10

Insulated roof vent TF (Thermo Flap) ........................... 12

Vertical mounting

Ventilation flap with weather protection grille

JK-180 HV ALAS ........................................................... 14

Insulated louvre windows

S9-iVt-05 LF-MR ............................................................ 16

Tairmo-LF-MR ............................................................... 16

Modernisation

Horizontal and vertical mounting

Ventilation flap JK-190 .................................................. 18

Ventilation flap JK-190-dB ............................................ 20

Horizontal mounting

JK-190 ceiling-corner mounting (accessories) .............. 22

Page 4: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 20174

Ventilation flap

Technical specification

Type JK-180 HVLouvres Aluminium

Seals EPDM-rubberMaterial Profiled sheet steel, dimensionally stable

Thickness 1,5 mmType Spring return motor

Power supply 24 VAC/DCTorque 20 Nm

Functional safety 11.000 cycles (EN certification) Service life 60.000 emergency positions (manufacturer specifications)

Run-time Closing via motor ≤150 sec.Opening via spring return ≤20 sec.

Sound power level Closing via motor ≤40 dBOpening via spring return ≤62 dB

DescriptionSmoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent lift shaft opening. The flap is designed for a horizontal and integrated installation inside the opening. The flap’s spring return motor ensures its opening in case of power failure.

Supplementary products

Spring return motor

expanding, used for sealing between the ventilation flap and shaft wall (included in the mounting set)

Sealing tape

certified according to: EN 12101-2

The most efficient solution for new buildingssolution for new buildings

Characteristics• Flush installation• Easy connection to exterior ventilation shaft• Possible combination with roof vent• Easy installing, easy access to motor• Louvres made of aluminum profile, streamlined and torsion-resistant• Delivered and assembled with profiled mounting plate• Pre-assembled and pre-cabled motor• Motor cabling with RJ45 connector for easy connection to BlueKit® system• Motor with positive safety function in case of power failure

JK-180 HV New building

Page 5: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 5

MOUNTING FROM THE ROOF*

MOUNTING FROM THE SHAFT

Section B-B

Section B-B

Section A-A

Section A-A

Concrete ceiling

Concrete ceiling

Concrete ceiling

Concrete ceiling

Articles and dimensions - JK-180 HV

Designation acc. to flap opening (mm) BxH 360x360 530x530 700x700 860x860 1030x1030 1200x1200Net ventilation surface (m2) 0,10 0,23 0,41 0,62 0,90 1,22

Recommended opening dimensions (mm) B1xH1 590x450 760x620 930x790 1090x950 1260x1120 1430x1290Minimal opening dimensions (mm) B1xH1** 530x450 700x620 870x790 1030x950 1200x1120 1370x1290

Mounting plate dimensions (mm) B2xH2 740x600 910x770 1080x940 1240x1100 1410x1270 1580x1440Article number 01.723.00 01.726.00 01.725.00 01.727.00 01.728.00 01.729.00

Spring return motor dimensions

Ventilation flap

Other dimensions available upon request** When using the minimal opening, dimensions demounting of the flap is necessary for the maintenance or replacement of the motor.

* Depending on the installation position, the maintenance of the flap might have to occur on the roof. By way of precaution we point out that applicable accident prevention regulations must be observed.

ApplicationFor installation from the shaft, the RJ45 connection cable is placed on the shaft side and tightened through the cable joint in order to guarantee airtightness. The sealing tape is then attached on the edge of the mounting plate which faces the wall. Finally, the ventilation flap is placed in the opening and fixed through the drilling holes of the mounting plate with wall anchors.

JK-180 HV New building

Page 6: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 20176

DescriptionSmoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent lift shaft opening. The flap is designed for a horizontal and integrated installation inside the opening. The flap is equipped with a low-noise direct current motor.

Characteristics• Easy connection to exterior ventilation shaft• Possible combination with roof vent• Easy installation, easy access to motor• Louvres made of aluminum profile, streamlined and torsion-resistant• Delivered and assembled with profiled mounting plate• Pre-assembled and pre-cabled motor• Motor cabling with RJ45 connector for easy connection to BlueKit® system• Low-noise direct current motor

Low noise level

Direct current motor

Technical specification

Type JK-180 HV-dBLouvres Aluminium

Seals EPDM-rubberMaterial Profiled sheet steel, dimensionally stable

Thickness 1,5 mmType Direct current motor

Power supply 24 VDCTorque 10 Nm

Functional safety 11.000 cycles (EN certification) Run-time ca. 4 sec.

Sound power level ca. 25 dB

Ventilation flap

Supplementary products

expanding, used for sealing between the ventilation flap and shaft wall (included in the mounting set)

Sealing tape

certified according to: EN 12101-2

JK-180 HV-dB New building

Page 7: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 7

MOUNTING FROM THE ROOF*

MOUNTING FROM THE SHAFT

Section B-B

Section B-B

Section A-A

Section A-A

Concrete ceiling

Concrete ceiling

Concrete ceiling

Concrete ceiling

Articles and dimensions - JK-180 HV-dB

Designation acc. to flap opening (mm) BxH 360x360 530x530 700x700 860x860 1030x1030 1200x1200Net ventilation surface (m2) 0,10 0,23 0,41 0,62 0,90 1,22

Recommended opening dimensions (mm) B1xH1 590x450 760x620 930x790 1090x950 1260x1120 1430x1290Minimal opening dimensions (mm) B1xH1** 500x450 670x620 840x790 1000x950 1170x1120 1340x1290

Mounting plate dimensions (mm) B2xH2 740x600 910x770 1080x940 1240x1100 1410x1270 1580x1440Article number 01.723.99 01.726.99 01.725.99 01.727.99 01.728.99 01.729.99

Direct current motor dimensions

Ventilation flap

Other dimensions available upon request** When using the minimal opening, dimensions demounting of the flap is necessary for the maintenance or replacement of the motor.

* Depending on the installation position, the maintenance of the flap might have to occur on the roof. By way of precaution we point out that applicable accident prevention regulations must be observed.

ApplicationFor installation from the shaft, the RJ45 connection cable is placed on the shaft side and tightened through the cable joint in order to guarantee airtightness. The sealing tape is then attached on the edge of the mounting plate which faces the wall. Finally, the ventilation flap is placed in the opening and fixed through the drilling holes of the mounting plate with wall anchors.

JK-180 HV-dB New building

Page 8: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 20178

Technical specification

Type JK-180 HVC

Material Galvanized steel (ref. ...-S)Aluminium (ref. ...-A)

Base wall thickness Base structure - 1,2 mmFlange - 2 mm

Cover wall thickness Inner body - 2 mmExterior sheet - 1,2 mm

Finishing Base - spot weldingCover - riveting

DescriptionVentilation flap and roof vent hood for horizontal mounting on flat roofs. The hood is composed of a base and a removable cover. The base is adapted to the ventilation flap where both elements are connected. The hood guarantees absolute rain protection - even in opened position of the flap. The ventilation and smoke extraction are assured in case of high wind speeds regardless of the weather and wind direction.

Characteristics• Ventilation flap JK-180 HV or JK-180 HV-dB (see specifications of JK-180 HV/JK-180 HV-dB)• Flat roof base with connection interface for the ventilation flap• Flexible mounting of the flap: flush-mounted from inside the shaft or inside of the base• Integration to thermal insulation• Weather protection• Condensate recovery gutter and outlet nozzle• Eased maintenance thanks to the good accessibility when removing the cover• Bird protection grille inside the hood• Types: spring return or low-noise direct current motor (ref. ...-dB...); roof vent hood made of galvanized steel (Ref. ...-S) or

aluminium (ref. ...-A)

certified according to: EN 12101-2

Optimal protectionunder all weather conditions

Base and cover available in numerous RAL colours

The mounting of the roof vent can easily be done by a roofer but shouldnot be part of the lift professional’s tasks. Depending on the installation position, the maintenance of the flap might have to occur on the roof. By way of precaution we point out that applicable accident prevention regulations must be observed.

Roof vent

JK-180 HVC New building

Page 9: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 9

* When using the minimal opening dimensions, demounting of the flap is necessary for the maintenance or replacement of the motor. See also JK-180 HV-dB for the minimal opening dimensions of JK-180 HVC-S-dB** other base heights available upon request

Section B-B Section A-A

Condensate outlet nozzle

Flat roof upper layer

Roof sealing

Thermal insulation

Concret ceiling

ApplicationFor installation from the roof, the flap is placed in the roof opening. The base is put on the mounting plate of the flap so that the drilling holes match and is then fixed on the ceiling with wall anchors. Finally, the weather cover is screwed on the base. Please refer to the BlueKit L-AIO installation guide for further installation details.

Articles and dimensions - JK-180 HVC

Designation acc. to flap opening (mm) BxH 360x360 530x530 700x700 860x860 1030x1030 1200x1200Net ventilation surface (m2) 0,10 0,23 0,41 0,62 0,90 1,22

Recommended opening dimensions (mm) B1xH1 590x450 760x620 930x790 1090x950 1260x1120 1430x1290Minimal opening dimensions (mm) B1xH1* 530x450 700x620 870x790 1030x950 1200x1120 1370x1290

Mounting plate dimensions (mm) B2xH2 740x600 910x770 1080x940 1240x1100 1410x1270 1580x1440Cover dimensions B3xH3 890x750 1060x920 1230x1090 1490x1350 1660x1520 1930x1790

Base height (mm) L1** 500 500 500 500 500 500Cover height (mm) L2 250 250 250 300 350 400

Overall height of the roof vent (mm) L3 750 750 750 750 750 750Article number JK-180 HVC-S 01.730.00 01.731.00 01.732.00 01.733.00 01.734.00 01.735.00

Article number JK-180 HVC-S-dB 01.730.99 01.731.99 01.732.99 01.733.99 01.734.99 01.735.99Article number JK-180 HVC-A 01.736.00 01.737.00 01.738.00 01.739.00 01.740.00 01.741.00

Article number JK-180 HVC-A-dB 01.736.99 01.737.99 01.738.99 01.739.99 01.740.99 01.741.99

Roof vent

JK-180 HVC New building

Page 10: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201710

DescriptionVentilation flap and roof vent hood with blade for horizontal mounting on flat roofs. The hood is composed of a base and a removable cover. The base is adapted to the ventilation flap where both elements are connected. The hood guarantees an absolute rain protection - even in opened position of the flap. The ventilation and smoke extraction are assured in case of high wind speeds regardless of the weather and wind direction.

Characteristics• Ventilation flap JK-180 HV or JK-180 HV-dB (see specifications of JK-180 HV/JK-180 HV-dB)• Flat roof base with connection interface for the ventilation flap• Flexible mounting of the flap: flush-mounted from inside the shaft or inside of the base• Integration to thermal insulation• Weather protection• Ideal for lack of space: the cover dimensions correspond to the base dimensions• Condensate recovery gutter and outlet nozzle• Eased maintenance thanks to the good accessibility when removing the cover• Bird protection grille inside the hood• Types: spring return or low-noise direct current motor (ref. ...-dB...); roof vent hood made of galvanized steel (Ref. ...-S) or

aluminium (ref. ...-A)

certified according to: EN 12101-2

Compact solution for optimal insulation

and protection

Base and cover available in numerous RAL colours

Technical specification

Type JK-180 HVL

Material Galvanized steel (ref. ...-S)Aluminium (ref. ...-A)

Base wall thickness Base structure - 1,2 mmFlange - 2 mm

Cover wall thickness Inner body - 2 mmExterior sheet - 1,2 mm

Finishing Base - spot weldingCover - riveting

Roof vent with blades

The mounting of the roof vent can easily be done by a roofer but shouldnot be part of the lift professional’s tasks. Depending on the installation position, the maintenance of the flap might have to occur on the roof. By way of precaution we point out that applicable accident prevention regulations must be observed.

JK-180 HVL New building

Page 11: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 11

Condensate outlet nozzle

Flat roof upper layer

Roof sealing

Thermal insulation

Concrete ceiling

Section B-B Section A-A

Articles and dimensions - JK-180 HVL

Designation acc. to flap opening (mm) BxH 360x360 530x530 700x700 860x860 1030x1030 1200x1200Net ventilation surface (m2) 0,10 0,23 0,41 0,62 0,90 1,22

Recommended opening dimensions (mm) B1xH1 590x450 760x620 930x790 1090x950 1260x1120 1430x1290Minimal opening dimensions (mm) B1xH1* 530x450 700x620 870x790 1030x950 1200x1120 1370x1290

Mounting plate dimensions (mm) B2xH2 740x600 910x770 1080x940 1240x1100 1410x1270 1580x1440Cover dimensions B3xH3 890x750 1060x920 1230x1090 1490x1350 1660x1520 1930x1790

Base height (mm) L1** 500 500 500 500 500 500Cover height (mm) L2 250 250 250 300 350 400

Overall height of the roof vent (mm) L3 750 750 750 750 750 750Article number JK-180 HVL-S 01.742.00 01.743.00 01.744.00 01.745.00 01.746.00 01.747.00

Article number JK-180 HVL-S-dB 01.742.99 01.743.99 01.744.99 01.745.99 01.746.99 01.747.99Article number JK-180 HVL-A 01.748.00 01.749.00 01.750.00 01.751.00 01.752.00 01.753.00

Article number JK-180 HVL-A-dB 01.748.99 01.749.99 01.750.99 01.751.99 01.752.99 01.753.00

Roof vent with blades

* When using the minimal opening, dimensions demounting of the flap is necessary for the maintenance or replacement of the motor. See also JK-180 HV-dB for the minimal opening dimensions of JK-180 HVL-S-dB** other base heights available upon request

ApplicationFor installation from the roof, the flap is placed in the roof opening. The base is put on the mounting plate of the flap so that the drilling holes match and is then fixed on the ceiling with wall anchors. Finally, the weather cover is screwed on the base. Please refer to the BlueKit L-AIO installation guide for further installation details.

JK-180 HVL New building

Page 12: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201712

Technical specification

Type TF

Louvre window 1,5 mm aluminium sheet on both sides25 mm PU foam insulation inside

Base 2,5 mm GRP layer on both sides, Foam insulation inside - Overall thickness 60 mm

Cover 0,8 mm galvanized steel sheetType Direct current motor

Power supply 24 VDCTorque 10 Nm

Functional safety 11.000 cycles Run-time ca. 4 sec.

Sound power level ca. 25 dB

DescriptionThermally insulated smoke and heat exhaust ventilation (SHEV) hood for horizontal mounting on flat roofs (max. slope up to 5%). For ventilation and smoke exhaust purposes the hood is equipped with an 24V electric motor. Ready-to-install solution composed of a base in fiberglass, an integrated motor-driven louvre window with thermally separated aluminium profiles and a cover.

Characteristics• Integration to thermal insulation• Weather protection• Ready-to-install solution • Fall-through-resistant• Ventilation and smoke extraction through ventilation opening on 4 sides assured regardless of wind direction• The insulated base in fiberglass (GRP) prevents from condensate formation• Eased maintenance thanks to the good accessibility when removing the cover• Insect protection grille inside the cover• Excellent heat transfer coefficient: 0,41 - 0,55 W/m2k• Ideal for lack of space: the cover dimensions correspond to the base dimensions

certified according to: EN 12101-2

The all-in-one solutionwith insulation

Insect protection grille

Insulated roof vent

TF (Thermo Flap) New building

Page 13: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 13

Section B-B Section A-A

Flat roof upper layer

Roof sealing

Thermal Insulation

Concrete ceiling

450x450mm - 1 blade

600x600mm - 2 blades

800x800mm - 3 blades

Articles and dimensions - TF

Designation acc. to opening dimensions (mm) BxH 450x450 600x600 800x800Net ventilation surface (m2) 0,10 0,20 0,39

Base dimensions (mm) B1xH1 810x810 960x960 1160x1160Cover dimensions (mm) B2xH2 595x630 745x780 950x985

Base height (mm) L1 500 500 500Cover height (mm) L2 332 332 385

Overall height (mm) L3 789 789 842U-Value (W/m2K) 0,41 0,46 0,55

Number of blades 1 2 3Weight (kg) 39 54 69

Article number TF 01.960.00 01.961.00 01.962.00

ApplicationThe low weight allows a simple handling and positioning on the roof. No special substructure or mounting is required: the hood is preassembled and is fixed directly above the opening with stainless steel screws.

The mounting of the roof vent can easily be done by a roofer but should not be part of the lift professional’s tasks. Depending on the installation position, the maintenance of the flap might have to occur on the roof. By way of precaution we point out that applicable accident prevention regulations must be observed.

Insulated roof vent

TF (Thermo Flap) New building

Page 14: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201714

DescriptionVentilation flap and weather protection grille allowing a flush-mounted closure of the permanent lift shaft opening. The flap is designed for a vertical and integrated installation inside the facade opening. The weather and bird protection grille can be installed from the shaft and provides the necessary weather protection on the outside wall.

Characteristics• Integrated flush-mounting of the ventilation flap (see specifications of JK-180 HV)• Integration to thermal insulation• Weather protection grille ALAS with fixed rain-repellent blades preventing the ingress of rain• A supplementary grid protects against intrusion of birds• Easy installation from the shaft or the machine room• Mounting feet for easy attaching inside the opening• Types: spring return or low-noise direct current motor (ref. ...-dB...)

certified according to: EN 12101-2

Vertical ventilation and protection, quite simply!

Technical specification

Type JK-180 HV-ALASLouvres Galvanized steel

Bird protection grid Galvanized steelFrame Galvanized steel

Note The position of the smoke exhaust opening has to be planified in such a way that the smoke exhaust is not affected by the wind!

Ventilation flap with weather protection grille

JK-180 HV-ALAS New building

Page 15: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 15

Insi

de

Out

side

Insi

de

Out

side

Inside view Outside view

Section Alternativesection

Mounting plate B2xH2

Opening dimensions B1xH1Flap Frame

Flap opening BxH

Articles and dimensions - JK-180 HV-ALAS

Designation acc. to flap opening(mm) BxH 360x360 530x530 700x700 860x860 1030x1030 1200x1200Net ventilation surface (m2) 0,10 0,23 0,38 0,56 0,77 1,03

Opening dimensions (mm) B1xH1 590x450 760x620 930x790 1090x950 1260x1120 1430x1290Mounting plate dimensions (mm) B2xH2 740x600 910x770 1080x940 1240x1100 1410x1270 1580x1440

Article number JK-180 HV-ALAS 01.818.00 01.819.00 01.820.00 01.821.00 01.822.00 01.823.00Article number JK-180 HV-ALAS-dB 01.818.99 01.819.99 01.820.99 01.821.99 01.822.99 01.823.99

Mounting feet dimensions

Weather protection grille depth (mm): 78Ventilation flap depth (mm): 180

Minimum wall thickness (mm): 260

Other dimensions available upon request

ApplicationThe weather protection grille is secured against falling with a safety line and placed diagonally through the opening to the outside. While pulling the grille against the outer wall, it is attached to the inside of the opening with the mounting feet. Finally, the ventilation flap incl. the sealing tape is placed in the opening and fixed to the inner wall through the drilling holes of the mounting plate.

Ventilation flap with weather protection grille

JK-180 HV-ALAS New building

Page 16: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201716

DescriptionLouvre window and mounting frame allowing a flush-mounted closure of the permanent lift shaft opening. The window is designed for a vertical and integrated installation inside the facade opening and guarantees optimal insulation thanks to excellent heat transfer coefficients.

Characteristics• Integrated flush-mounting • Integration to thermal insulation• Excellent thermal performance: low heat transfer coefficient (Ug-/Up-/Uw-value)• Air permeability, water tightness and heat protection• Sandwich panels (S9-iVt-05 LF-MR) or glass blade frame with triple glazing (Tairmo-LF-MR)• Anti breakage• Attractive architectural design in the facade

Note The position of the smoke exhaust opening has to be planified in such a way that the smoke exhaust is not affected by the wind!

Combine ventilation, energetic efficiency and modern design

Technical specification

Type S9-iVt-05 LF-MR / Tairmo-LF-MRLouvres Thermally separated aluminium profilesMaterial Sandwich panels / triple glazing

Type Direct current motorPower supply 24 VDC

Torque 0,3 Nm ... 4,5 NmFunctional safety 11.000 cycles (EN certification)

Run-time ca. 4 sec.Sound power level ca. 25 dB

Tairmo-LF-MR

S9-iVt-05 LF-MR

Insulated louvre windows

S9-iVt-05 LF-MR and Tairmo-LF-MR New building

Supplementary products

expanding, used for sealing between the louvre window and shaft wall (included in the mounting set)

Sealing tape

certified according to: EN 12101-2

Page 17: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 17

Outside view

Section

Insi

de Out

side

Articles and dimensions

Type S9-iVt-05 LF-MR Tairmo-LF-MRDesignation according to the

element dimensions BxH 420x420 630x390 570x570 775x775 800x350 590x505 740x505 815x815

Net ventilation surface (m2) 0,10 0,15 0,20 0,39 0,11 0,15 0,20 0,40Opening dimensions (mm) B1xH1 450x450 660x420 600x600 805x805 830x380 660x535 770x535 845x845

Uw-value (W/m2K) 2,5 2,3 2,3 2,1 1,9 1,8 1,7 1,6Number of blades 1 1 2 3 1 1 1 2

Article number 01.950.00 01.951.00 01.952.00 01.953.00 01.956.00 01.957.00 01.958.00 01.959.00

Other dimensions available upon request

Outside view

Section

Insi

de Out

side

Mounting frame: 50 x 150 x 5mm (50 x 50 x 5 mm or 50 x 100 x 5 mm dimensions available upon request)

ApplicationThe sealing tape is first placed on the wall sided edge of the mounting frame. The element is then aligned in the opening parallel to the opening edges, secured and fixed to the wall via wall anchors.

Insulated louvre windows

S9-iVt-05 LF-MR and Tairmo-LF-MR New building

Page 18: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201718

Technical specification

Type JK-190Louvres Aluminium

Seals EPDM-rubberMaterial Profiled sheet steel, dimensionally stable

Thickness 1,5 mmType Spring return motor

Power supply 24 VAC/DCTorque 20 Nm

Functional safety 11.000 cycles (EN certification) Service life 60.000 emergency positions (manufacturer specifications)

Run-time Closing via motor ≤150 sec.Opening via spring return ≤20 sec.

Sound power level Closing via motor ≤40 dBOpening via spring return ≤62 dB

DescriptionSmoke and heat exhaust ventilation (SHEV) device allowing a surface-mounted closure of the permanent lift shaft opening in existing buildings. The flap is fitted for horizontal or vertical non-integrated installation. The flap’s spring return motor ensures its opening in case of power failure.

Spring return motor

The flexible solution for modernisations

Characteristics• Non-integrated solution – surface mounting• Does not decrease the ventilation surface• The additional 10 mm depth of the frame allows a wider ventilation surface (free movement of the blades

and airflow increase between the blades)• Can be adapted to all openings• Easy ventilation flap installation and motor maintenance• Louvres made of aluminum profile, streamlined and torsion-resistant• Pre-assembled and pre-cabled motor• Motor cabling with RJ45 connector for easy connection to BlueKit® system• Solution for the ventilation flap mounting in a corner with additional mounting angles (accessories)• Motor with positive safety function in case of power failure

Ventilation flap

certified according to: EN 12101-2

Supplementary products

expanding, used for sealing between the ventilation flap and shaft wall (included in the mounting set)

Sealing tape

JK-190 Modernisation

Page 19: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 19

Section B-B Section A-A

Concrete ceiling Concrete ceiling

JK-190 Modernisation

ApplicationThe ventilation flap is used in front of the opening to mark the drilling points. After having drilled, the sealing tape is attached on the frame. The flap is then fixed to the wall through the drilling holes of the frame with wall anchors.

Spring return motor dimensions

Ventilation flap

* Most-used standard dimensions in grey

JK-190*

Net ventilation surface (m2) Ventilation flap opening

(mm) H/B 360 530 700 860 1030 1200

360 0,1 0,15 0,2 0,25 0,3 0,35530 0,16 0,23 0,3 0,37 0,45 0,52700 0,21 0,31 0,41 0,5 0,6 0,7860 0,26 0,38 0,51 0,62 0,75 0,87

1030 0,31 0,46 0,61 0,75 0,9 1,041200 0,37 0,54 0,71 0,87 1,05 1,22

Page 20: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201720

DescriptionSmoke and heat exhaust ventilation (SHEV) device allowing a surface-mounted closure of the permanent lift shaft opening in existing buildings. The flap is fitted for horizontal or vertical non-integrated installation. The flap is equipped with a low-noise direct current motor.

certified according to: EN 12101-2

Characteristics• Non-integrated solution – surface mounting• Does not decrease the ventilation surface• The additional 10 mm depth of the frame allows a wider ventilation surface (free movement of the blades

and airflow increase between the blades)• Can be adapted to all openings• Easy ventilation flap installation and motor maintenance• Louvres made of aluminum profile, streamlined and torsion-resistant• Pre-assembled and pre-cabled motor• Motor cabling with RJ45 connector for easy connection to BlueKit® system• Solution for the ventilation flap mounting in a corner with additional mounting angles (accessories)• Low-noise direct current motor

Direct current motor

Technical specification

Type JK-190-dBLouvres Aluminium

Seals EPDM-rubberMaterial Profiled sheet steel, dimensionally stable

Thickness 1,5 mmType Direct current motor

Power supply 24 VDCTorque 10 Nm

Functional safety 11.000 cycles (EN certification) Run-time ca. 4 sec.

Sound power level ca. 25 dB

Low noise level solution for mordernisations

Ventilation flap

Supplementary products

expanding, used for sealing between the ventilation flap and shaft wall (included in the mounting set)

Sealing tape

JK-190-dB Modernisation

Page 21: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 21

Section B-B Section A-A

Concrete ceiling Concrete ceiling

ApplicationThe ventilation flap is used in front of the opening to mark the drilling points. After having drilled, the sealing tape is attached on the frame. The flap is then fixed to the wall through the drilling holes of the frame with wall anchors.

* Most-used standard dimensions in grey

JK-190-dB*

Net ventilation surface (m2) Ventilation flap opening

(mm) H/B 360 530 700 860 1030 1200

360 0,1 0,15 0,2 0,25 0,3 0,35530 0,16 0,23 0,3 0,37 0,45 0,52700 0,21 0,31 0,41 0,5 0,6 0,7860 0,26 0,38 0,51 0,62 0,75 0,87

1030 0,31 0,46 0,61 0,75 0,9 1,041200 0,37 0,54 0,71 0,87 1,05 1,22

Direct current motor dimensions

Ventilation flap

JK-190-dB Modernisation

Page 22: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

BlueKit ventilation flaps - September 201722

DescriptionMounting angles - Accessories for horizontal mounting of JK-190 and JK-190-dB

Characteristics• Ventilation flap JK-190 with mounting angles• Solution for the ventilation flap mounting in a corner of the shaft ceiling when space for fixing is not sufficient• Flexible mounting according to the access to the ventilation opening

2

1

2

Application• Fixing of angle corner (1) to the ventilation flap together with the supplied nuts• Positioning of the ventilation flap including mounting angle (1) in front of the opening and screw mounting

in the shaft slab• Positioning of mounting angle (2) on the ventilation flap and screw mounting in the shaft wall

Accessories

JK-190 - ceiling/corner Modernisation

Page 23: INNOVATION SAFETY EFFICIENCY...6 BlueKit ventilation flaps - September 2017 Description Smoke and heat exhaust ventilation (SHEV) device allowing a flush-mounted closure of the permanent

September 2017 - BlueKit ventilation flaps 23

JK-190 - ceiling/corner Modernisation

Drawings and dimensions with mounting angles

1

1

2 2

2

Ceiling corner view

Section B-B Section A-A

Accessories