ingress protection bronzelite ingrade luminaires © copyright 2006 bronzeliterev. 1
TRANSCRIPT
INGRESS PROTECTION
Bronzelite Ingrade Luminaires© copyright 2006 Bronzelite Rev. 1
What is Ingress Protection?
The International Electrotechnical Commission or IEC provides Ingress Protection (IP) ratings that are used to determine the degree of protection provided by an electrical enclosure.
IP ratings define protection differently than an Underwriters Laboratories (UL) or Canadian UL (cUL) Wet Location Listing.
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
Why Ingress Protection?Since the IEC is an international standards organization, IP ratings have global application for lighting luminaire enclosures.
Global acceptance of IP rated luminaires ensures straightforward communication of enclosure ratings, facilitating specification on a worldwide scale.
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
What are IP ratings?IP ratings designate the degree of protection an enclosure provides against the ingress or intrusion of foreign objects.
IP ratings consist of the letters “IP” followed by two numbers.
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
What do the numbers represent?
IP6X
The first number designates protection against solid objects.
IPX8
The second number designates protection against water.
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
Professional testing
© copyright 2006 Bronzelite
INGRESS PROTECTION
Bronzelite tests per the IEC standard, ensuring reliable and quantifiable IP ratings.
For optimum results, we perform solid and water intrusion tests on our luminaires.
Rev. 1
Solid intrusion ratingsIP Rating Solid Object Size
IP1X > 50mm (1.97”) diameter
IP2X > 12.5mm (0.49”) diameter
IP3X > 2.5mm (0.098”) diameter
IP4X > 1.0mm (0.039”) diameter
IP5X dust-protected
IP6X dust-tight
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
Solid intrusion testing
© copyright 2006 Bronzelite
INGRESS PROTECTION
Solid intrusion testing is performed first. The luminaires are energized using the hottest wattage configuration and are operated to steady-state under normal operating temperatures.
They are de-energized and put in the dust chamber.
After the prescribed time, they are inspected for dust intrusion. The dust-tight IP6X rating means no dust has penetrated into the luminaires.
Rev. 1
Water intrusion ratingsIP Rating Type of Water
IPX1 vertical dripping
IPX2 dripping (up to 15o tilt)
IPX3 spraying (up to 60o angle)
IPX4 splashing from any direction
IPX5 jets from any direction
IPX6 powerful jets from any direction
IPX7 temporary immersion
IPX8 continuous immersion
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
Water intrusion dual IP ratings
Per the IEC standard, enclosures only rated IPX7 or IPX8 are restricted use and are unsuitable for exposure to jets of water.
Dual ratings are more versatile.
For example, IPX6/IPX8 designates an enclosure that protects against both powerful jets (such as from power washers or driving rain) AND against continuous immersion (such as when installations in low lying areas results in pooling of water on top of the luminare).
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
Water intrusion testing
© copyright 2006 Bronzelite
INGRESS PROTECTION
Water intrusion testing is performed after solid intrusion testing.
First, the luminaires are sprayed from all directions with a powerful water jet.
Rev. 1
Water intrusion testing
© copyright 2006 Bronzelite
INGRESS PROTECTION
After the prescribed time, the luminaire is inspected for water intrusion. The dual IPX6/X8 rating means no water has penetrated into the luminaire.
Then they are immersed with 1m (3.28ft) of headwater over top of them.
Rev. 1
Bronzelite ingrade IP Ratings
The following ingrade luminaires are
dual rated
IP66/IP68 to a depth of 1meter (3.28ft)
which means they are• dust-tight• sealed against powerful water jets AND• sealed against continuous immersion for a depth of up to 1m (3.28ft) of headwater
© copyright 2006 Bronzelite
INGRESS PROTECTION
Rev. 1
Bronzelite ingrade IP Ratings
© copyright 2006 Bronzelite
INGRESS PROTECTION
DB5000 Series
IP66/IP68 to 1m
(3.28ft)
Rev. 1
Bronzelite ingrade IP Ratings
© copyright 2006 Bronzelite
INGRESS PROTECTION
G8000 Series
G7000 Series
GM1000 Series
IP66/IP68 to 1m
(3.28ft)
Rev. 1
Bronzelite ingrade IP Ratings
© copyright 2006 Bronzelite
INGRESS PROTECTION
SG7000 Series
DG7000 Series
IP66/IP68 to 1m
(3.28ft)
Rev. 1
Bronzelite ingrade IP Ratings
© copyright 2006 Bronzelite
INGRESS PROTECTION
IP66/IP68 to 1m
(3.28ft)DB2000 Series
DB3000 Series
G5/G6 Series
Rev. 1
Bronzelite ingrade IP Ratings
© copyright 2006 Bronzelite
INGRESS PROTECTION
IP66/IP68 to 1m
(3.28ft)
G1/G3 Series
GM4000 Series
GM2000 Series
Rev. 1
INGRESS PROTECTION
© copyright 2006 Bronzelite
For more information regarding ingrade For more information regarding ingrade Ingress Protection and IP ratings, contact Ingress Protection and IP ratings, contact
your local Bronzelite Sales Representative.your local Bronzelite Sales Representative.
Rev. 1