INGENIERIA SISMO RESISTENTE Y DESASTRES NATURALES
TRABAJO DOMICILIARIO N°2: INGENIERIA SISMORESISTENTE SISTEMAS RESISTENTES A CARGAS LATERALES YANÁLISIS SÍMICO ESTÁTICO
INDICERESUMEN:...................................................................................................21) DESCRIPCION DE LA EDIFICACION........................................................3
NOMBRE DEL EDIFICIO:............................................................................3UBICACIÓN:..............................................................................................3PLANO DE UBICACIÓN:.............................................................................3DESCRIPCIÓN:..........................................................................................4
2) ESQUEMAS EN PLANTA:........................................................................53) ESQUEMAS EN ELEVACIÓN:..................................................................64) ELEMENTOS RESISTENTES A CARGAS VERTICALES Y A CARGAS LATERALES:
………………………………………………………………………………………….11SISTEMA ESTRUCTURAL DE MUROS CORTANTES (PLACAS):..................11LAS PLACAS SOPORTAN CARGAS VERTICALES Y LATERALES.................11
5) DENSIDAD DE LOS ELEMENTOS RESISTENTES EN EL PRIMER PISO:. . .126) METODO DE FUERZAS ESTATICAS EQUIVALENTES.............................127) ANALISIS ESTRUCTURAL TRIDIMENCIONAL (ETABS DEL EDIFICIO)......288) DIAGRAMA DE MOMENTO, FUERZAS CORTANTES, DE CADA EJE PORTANTE
………………………………………………………………………………………….295) DESPLAZAMIENTOS:............................................................................34
Sistemas resistentes a cargas laterales y Análisis símico estático 1
RESUMEN:
El presente trabajo consiste en realizar el análisis de una estructura de 8 pisos, para así conocer sus elementos estructurales, identificar los elementos resistentes a cargas verticales y laterales, calcular la densidad de muros, aplicar el método de fuerzas estáticas equivalentes para determinar las fuerzas sísmicas actuantes, además se modeló dicha estructura en ETABS, de esta manera podemos identificar los diagramas de momentos, diagramas de fuerzas cortantes y el desplazamiento de cada entrepiso.
Primero se procedió a identificar la estructura, se realizó el metrado de cargas, así hallamos el peso de la carga muerta, y por reglamento también determinamos la carga viva, con estos datos y con el uso de la Norma E030 – Diseño Sismo resistente se podrá hallar las fuerzas sísmicas actuantes, posteriormente se procedió hallar la densidad de muros, finalmente se modeló la estructura en el programa ETABS para determinar los diagramas de momentos, diagramas de fuerza cortante y el desplazamiento de cada entrepiso.
Sistemas resistentes a cargas laterales y Análisis símico estático 2
1) DESCRIPCION DE LA EDIFICACION
NOMBRE DEL EDIFICIO:
EDIFICIO MULTIFAMILIAR BORGOÑO
UBICACIÓN:
La Edificación de Vivienda Multifamiliar se encuentra ubicada en la Calle Gral. Borgoño Nº 394, Esq. con Calle Piura, Distrito de Miraflores, Provincia y Región Lima, proyectado para un área construida total de 1,690.55m².
PLANO DE UBICACIÓN:
Sistemas resistentes a cargas laterales y Análisis símico estático 3
Edificio Multifamiliar Borgoño:
Calle General Borgoño N°394
DESCRIPCIÓN:El propietario del edificio es CONSTRUCTORA GAEL S.A.C. El diseño estructural fue realizado por el Ingeniero Civil Jorge Avendaño A.
La Arquitectura del conjunto presenta un edificio de siete (07) pisos con servicio de 1 ascensor.
Hay 6 departamentos del tipo Flat distribuidos en los pisos 2º, 3º, 4º, 5º, 6º y 7º; y 3 departamentos del tipo dúplex en los pisos 2º, 5º y 7º; haciendo un total de 9 departamentos.
Descripción estructural:
El área del edificio es de m2.Todos los pisos tienen la misma altura y es de 2.65 m. Se han definido tres pisos típicos: el primero, cuarto y quinto tienen la misma configuración estructural; el segundo, tercero y sexto también tienen la misma configuración estructural y el séptimo constituye el tercer piso típico. El edificio está estructurado a base de pórticos y placas de concreto armado, siendo las placas las que soportan mayor cortante; ascensor y escaleras. La losa es Aligerada hecha a base de viguetas pretensadas.
Sistemas resistentes a cargas laterales y Análisis símico estático 4
Piso Departamento
2do 201202
3er 3014to 4015to 501
5026to 6017mo 701
702
2) ESQUEMAS EN PLANTA:
Sistemas resistentes a cargas laterales y Análisis símico estático 5
3) ESQUEMAS EN ELEVACIÓN:
EJE A-A
Sistemas resistentes a cargas laterales y Análisis símico estático 6
EJE C-C
EJE F-F
EJE K-KSistemas resistentes a cargas laterales y Análisis símico estático 7
EJE M-M
DIRECCION X
EJE 2-2Sistemas resistentes a cargas laterales y Análisis símico estático 8
EJE 4-4
EJE 5-5
Sistemas resistentes a cargas laterales y Análisis símico estático 9
EJE 10-10
EJE 13-13
Sistemas resistentes a cargas laterales y Análisis símico estático 10
4) ELEMENTOS RESISTENTES A CARGAS VERTICALES Y A CARGAS LATERALES:
SISTEMA ESTRUCTURAL DE MUROS CORTANTES (PLACAS):El sistema estructural está constituido por pórticos y placas en ambas direcciones, siendo las placas las de mayor configuración estructural; por ese motivo lo hace un sistema de “Muros cortantes”.
LAS PLACAS SOPORTAN CARGAS VERTICALES Y LATERALES
5) DENSIDAD DE LOS ELEMENTOS RESISTENTES EN EL PRIMER PISO:
D=∑ Acol+∑ Aplacas
Atechada%
Sistemas resistentes a cargas laterales y Análisis símico estático 11
∑ Acol=1.71m2
∑ Aplacas=6.08m 2
Atechada=224.21m 2
D=3.47 %
METODO DE FUERZAS ESTATICAS EQUIVALENTES
Datos del edificio:
Datos ClasificaciónUbicación Lima Zona3 , Z=0.4Suelo Grava S1=1 , Tp=0.4sUso Vivienda S/C 200Kg/cm2 Categoría C,U=1,%S/C=25%Rx Muros de corte R=6Ry Muros de corte R=6
Metrado de cargas del edificio:
PISO TIPICO 1 (Pisos 1, 4, 5)
Piso 1
Altura 2.65 m
P.E CONCRETO 2.4 T/M3
Peso
323.64
Columnas
B(m) H(m) A(m2) H(m)VOLUMEN(m3 CANTIDAD
VOL TOTAL(m3
PESO (T)
A. TOTAL (m2)
C1 A1 0.3 1.1 0.33 2.65 0.8745 3 2.6235 6.30 0.99C2 A2 0.3 0.8 0.24 2.65 0.636 1 0.636 1.53 0.24
C3 A4 0.3 1 0.3 1.325 0.3975 1 0.3975 0.95 0.3A5 0.3 0.8 0.24 1.325 0.318 1 0.318 0.76
C4 A6 0.3 0.8 0.24 2.65 0.636 1 0.636 1.53 0.2411.07 1.77
Losa Aligerada
Peso Propio Firth 335
kg/m2
Peso Propio Tipica 350
kg/m2
Anexo 1 Norma E.020
Sistemas resistentes a cargas laterales y Análisis símico estático 12
Peso Propio Concreto (e=0.25) 600
kg/m3
Area (m2)
Peso (T)
A1 11.16 3.91
A2 28.6210.02
A3 4.25 1.49
A4 22.31 7.81
A5 1.74 0.61
A6 6.32 2.21
A7 48.0516.10
A8 38.7013.55
A9 9.96 3.49
A10 9.95 5.9765.13
VigasP.E. concreto 2400 kg/m3
B(m) H(m) A(m2) L(m)VOLUMEN(m3)
PESO (T)
V-1 0.25 0.60 0.15 7.2 1.08 2.59V-2 0.25 0.60 0.15 4.5 0.675 1.62V-3 0.20 0.60 0.12 2.3 0.276 0.66V-4 0.25 0.60 0.15 4.15 0.6225 1.49V-5 0.25 0.60 0.15 7.2 1.08 2.59V-6 0.25 0.60 0.15 4.5 0.675 1.62V-7 0.25 0.60 0.15 7.2 1.08 2.59V-8 0.25 0.60 0.15 4.85 0.7275 1.75V-9 0.25 0.60 0.15 7.2 1.08 2.59V-10 0.25 0.60 0.15 7.2 1.08 2.59V-11 0.25 0.60 0.15 4.85 0.7275 1.75
V-12 0.25 0.250.0625 4.85 0.303125 0.73
V-13 0.25 0.60 0.15 4.15 0.6225 1.49
Sistemas resistentes a cargas laterales y Análisis símico estático 13
V-14 0.25 0.30 0.075 4.85 0.36375 0.87V-15 0.25 0.30 0.075 4.15 0.31125 0.75
V-16 0.25 0.250.0625 1.6 0.1 0.24
V-17 0.25 0.250.0625 1.05 0.065625 0.16
V-18 0.50 0.25 0.125 7.25 0.90625 2.1826.09
Acabados 100 kg/m2
A. Bruta (m2)
A. Column (m2) A. Muros (m2)
A. Acab (m2) Peso (T)
228.9 1.77 23.77 203.36 20.34Tabiqueria 150 kg/m2
A. Acab (m2) Tabique (kg/m2) Peso (T)203.36 150 30.50
Placas
Area (m2) H (m)
Volumen (m3)
Peso (T)
P1 5.04 2.65 13.35229 32.05
P2 4.48 2.65 11.872 28.49
P3 14.25 2.65 37.773365 90.66
151.19Escalera 2400 kg/m3
Escalera N°1
Área Ancho VolumenPeso (kg) Peso (tn)
Tramo 1 0.61 1.20 0.731760.47 1.76
Tramo 2 0.37 1.20 0.441054.22 1.05
Tramo 3 0.54 1.20 0.651556.71 1.56
Escalera N°2Área Ancho Volumen Peso Peso (tn)
Sistemas resistentes a cargas laterales y Análisis símico estático 14
(kg)
Tramo 10.573325 1.2 0.68799
1651.176 1.651176
Tramo 2 0.3 1.2 0.36 864 0.864Tramo 3 0.52 1.2 0.624 1497.6 1.4976
Escalera N°3
Área Ancho VolumenPeso (kg) Peso (tn)
Tramo 11.148875 1.2 1.37865
3308.76 3.30876
11.69Sobrecarga
A. Acab (m2) %S/C Tabique (kg/m2) Peso (T)203.36 25% 150 7.63
PISO TIPICO 2 (Pisos 2, 3,6)Piso 5
Altura 2.65 m
P.E CONCRETO
2.4 T/M3
Peso
323.47
Columnas
B(m) H(m)A(m2)
H(m)
VOLUMEN(m3)
CANTIDAD
VOL TOTAL(m3)
PESO (T)
A. TOTAL (m2)
C1 A1 0.3 1.1 0.332.65 0.8745 3 2.6235
6.30 0.99
C2 A3 0.3 0.8 0.242.65 0.636 1 0.636
1.53 0.24
C3 A6 0.3 0.8 0.242.65 0.636 1 0.636
1.53 0.24
C4 A3 0.3 0.8 0.242.65 0.636 1 0.636
1.53 0.2410.88 1.71
Losa Aligerada
Peso Propio Firth 335
kg/m2
PesoPropio Tipica 350
kg/m2
Anexo 1 Norma E.020
PesoPropio Concreto
600 kg/m3
Sistemas resistentes a cargas laterales y Análisis símico estático 15
(e=0.25)
Area (m2)Peso (T)
A1 11.16 3.91
A2 28.6210.02
A3 4.25 1.49
A4 22.31 7.81
A5 1.74 0.61
A6 6.32 2.21
A7 48.0516.10
A8 38.7013.55
A9 9.96 3.49
A10 9.95 5.9765.13
VigasP.E. concreto 2400 kg/m3
B(m) H(m) A(m2) L(m)VOLUMEN(m3)
PESO (T)
V-1 0.25 0.60 0.15 7.2 1.08 2.59V-2 0.25 0.60 0.15 4.5 0.675 1.62V-3 0.20 0.60 0.12 2.3 0.276 0.66V-4 0.25 0.60 0.15 4.15 0.6225 1.49V-5 0.25 0.60 0.15 7.2 1.08 2.59V-6 0.25 0.60 0.15 4.5 0.675 1.62V-7 0.25 0.60 0.15 7.2 1.08 2.59V-8 0.25 0.60 0.15 4.85 0.7275 1.75V-9 0.25 0.60 0.15 7.2 1.08 2.59V-10 0.25 0.60 0.15 7.2 1.08 2.59V-11 0.25 0.60 0.15 4.85 0.7275 1.75
V-12 0.25 0.250.0625 4.85 0.303125 0.73
V-13 0.25 0.60 0.15 4.15 0.6225 1.49V-14 0.25 0.30 0.075 4.85 0.36375 0.87
Sistemas resistentes a cargas laterales y Análisis símico estático 16
V-15 0.25 0.30 0.075 4.15 0.31125 0.75
V-16 0.25 0.250.0625 1.6 0.1 0.24
V-17 0.25 0.250.0625 1.05 0.065625 0.16
V-18 0.50 0.25 0.125 7.25 0.90625 2.1826.09
Acabados 100 kg/m2
A. Bruta (m2)
A. Column (m2) A. Muros (m2)
A. Acab (m2) Peso (T)
228.9 1.71 23.77 203.42 20.34
Tabiqueria 150 kg/m2
A. Acab (m2)
Tabique (kg/m2) Peso (T)
203.42 150 30.51
Placas
Area (m2) H (m)
Volumen (m3) Peso (T)
P1 5.04 2.65 13.35229 32.05
P2 4.48 2.65 11.872 28.49
P3 14.25 2.6537.773365 90.66
151.19Escalera 2400 kg/m3
Escalera N°1
Area Ancho Volumen Peso (kg) Peso (tn)Tramo 1 0.61 1.20 0.73 1760.47 1.76Tramo 2 0.37 1.20 0.44 1054.22 1.05Tramo 3 0.54 1.20 0.65 1556.71 1.56
Sistemas resistentes a cargas laterales y Análisis símico estático 17
Escalera N°2Area Ancho Volumen Peso (kg) Peso (tn)
Tramo 1 0.573325 1.2 0.68799 1651.18 1.651176Tramo 2 0.3 1.2 0.36 864.00 0.864Tramo 3 0.52 1.2 0.624 1497.60 1.4976
Escalera N°3Area Ancho Volumen Peso (kg) Peso (tn)
Tramo 1 1.148875 1.2 1.37865 3308.76 3.3087611.69
Sobrecarga
A. Acab (m2) %S/C
Tabique (kg/m2) Peso (T)
203.42 25% 150 7.63
PISO TIPICO 3 (Piso 7)
Piso 6 Altura 2.65 mP.E CONCRETO 2.4 T/M3
Peso 259.75
Columnas
B(m) H(m)A(m2)
H(m)
VOLUMEN(m3)
CANTIDAD
VOL TOTAL(m3)
PESO (T)
A. Colu (m2)
C1 A1 0.3 1.1 0.33
1.325 0.43725 3 1.31175 3.15 0.99
C2 A3 0.3 0.8 0.24
1.325 0.318 1 0.318 0.76 0.24
C3 A6 0.3 0.8 0.24
1.325 0.318 1 0.318 0.76 0.24
C4 A3 0.3 0.8 0.24
1.325 0.318 1 0.318 0.76 0.24
C5 B1 0.25 0.4 0.1
1.325 0.1325 3 0.3975 0.95 0.3
C6 B2 0.25 0.25
0.0625
1.325
0.0828125 6 0.496875 1.19 0.375
C7 B3 0.25 0.6 0.15
1.325 0.19875 1 0.19875 0.48 0.15
C8 B4 0.25 0.5
0.125
1.325
0.165625 1 0.165625 0.40 0.125
5.44 2.66
Sistemas resistentes a cargas laterales y Análisis símico estático 18
Losa Aligerada
Peso Propio Firth 335
kg/m2
Peso Propio Tipica 350kg/m2
Anexo 1 Norma E.020
Peso Propio Concreto (e=0.25) 600
kg/m3
Area (m2)
Peso (T)
A1 10.86 3.80
A2 17.95 6.28
A3 2.34 0.82
A4 5.10 3.06
A5 6.00 3.60
A6 2.07 1.24
A7 2.18 0.76
A8 12.19 4.27
A9 14.07 8.44
A10 10.53 3.68
A11 1.74 0.61
A12 6.32 2.21
A13 18.50 6.20
A14 26.60 9.31
A15 4.68 2.81
A16 1.62 0.97
A17 1.45 0.87
A18 19.17 6.4265.36
VigasP.E. concreto 2400 kg/m3
B(m) H(m) A(m2) L(m) VOLUMEN PESO
Sistemas resistentes a cargas laterales y Análisis símico estático 19
(m3) (T)V-1 0.25 0.60 0.15 4.85 0.7275 1.75V-2 0.25 0.60 0.15 7.2 1.08 2.59V-3 0.20 0.60 0.12 4.5 0.54 1.30V-4 0.25 0.60 0.15 4.85 0.7275 1.75V-5 0.25 0.60 0.15 7.2 1.08 2.59V-6 0.25 0.60 0.15 4.5 0.675 1.62V-7 0.45 0.25 0.1125 4.85 0.545625 1.31V-8 0.25 0.60 0.15 4.85 0.7275 1.75V-9 0.25 0.25 0.0625 1.8 0.1125 0.27V-10 0.25 0.60 0.15 7.2 1.08 2.59V-11 0.25 0.25 0.0625 2.65 0.165625 0.40V-12 0.20 1.20 0.24 2 0.48 1.15V-13 0.25 0.60 0.15 4.15 0.6225 1.49V-14 0.30 0.25 0.075 2.5 0.1875 0.45V-15 0.30 0.25 0.075 1.45 0.10875 0.26V-16 0.20 1.60 0.32 1.05 0.336 0.81V-17 0.25 0.60 0.15 4.15 0.6225 1.49V-18 0.20 1.20 0.24 2.4 0.576 1.38V-19 0.15 1.20 0.18 2.4 0.432 1.04V-20 0.25 0.60 0.15 1.55 0.2325 0.56V-21 0.15 1.20 0.18 1 0.18 0.43V-22 0.60 0.25 0.15 7.25 1.0875 2.61V-23 0.50 0.25 0.125 7.25 0.90625 2.18V-24 0.50 0.25 0.125 4.6 0.575 1.38V-25 0.20 1.25 1.25 5.9 7.375 17.70V-26 0.25 0.60 0.15 5.05 0.7575 1.82V-27 0.25 1.00 0.25 1.95 0.4875 1.17V-28 0.25 1.00 0.25 2.2 0.55 1.32
55.15Acabados 100 kg/m2
A. Bruta (m2)
A. Column (m2)
A. Muros (m2)
A. Acab (m2)
Peso (T)
228.9 2.66 23.77 202.4720.25
Tabiqueria 150 kg/m2
A. Acab (m2) Tabique Peso (T)
Sistemas resistentes a cargas laterales y Análisis símico estático 20
(kg/m2)202.47 150 30.37
Placas
Area (m2) H (m)Volumen (m3) Peso (T)
P1 5.04 1.325 6.676145 16.02P2 4.48 1.325 5.936 14.25
P3 14.25 1.32518.8866825 45.33
75.60
Sobrecarga
A. Acab (m2) %S/CTabique (kg/m2) Peso (T)
202.47 25% 150 7.59
APLICACIÓN DEL MÉTODO:
Edificio de 7 pisos, hn = 18.55m.
Cada piso tiene: 2.65 m
Factor de amplificación sísmica C:C=2.5 x Tp
T
Determinación del periodo T: CTX =CTY =45
T=
hnCTX
=18 .5545
=0 .412 s
Artículo 17 (17.2)
CX=2 .5 x0 .3090 .4
=3 .23≤2 .5→C=2 .5
Artículo (7)
Cortante en la dirección X:
Sistemas resistentes a cargas laterales y Análisis símico estático 21
V X=ZUSC XRX
P =0,4 x1,0 x1 x2 .56
x 2190.96=365 .16
T=0 .412<0 .7 s Por lo tanto no se incluye la distribución de fuerza sísmica en altura. Articulo 17 (17.4)
PISO H Ht P Ht*P FT CORTE
7 2.65 18.55 259.754818.3655
877.340853
877.340853
8
6 2.65 15.9 324.885165.5801
682.914086
3 160.25494
5 2.65 13.25 323.474285.9345
168.794662
5229.04960
3
4 2.65 10.6 320.163393.6747
554.472766
3283.52236
9
3 2.65 7.95 317.50 2524.103740.515052
6324.03742
1
2 2.65 5.3 321.571704.3171
927.356443
6351.39386
5
1 2.65 2.65 323.64857.64680
913.766314
6 365.1601818.55 2190.96 22749.62
1
2
3
4
5
6
7
13.7663145922815
27.356443578407
40.5150525617468
54.4727663439955
68.7946624799448
82.9140862814882
77.3408537871362
FUERZAS SISMICAS
Sistemas resistentes a cargas laterales y Análisis símico estático 22
ANALISIS DE IRREGULARIDADES
Piso A Condicion 1 Condicion 21 25.5427 Regular Regular2 24.9727 Regular Regular3 25.72 Regular Regular4 25.48 Regular Regular5 25.48 Regular -6 25.48 Regular -7 26.43 Regular -
Sistemas resistentes a cargas laterales y Análisis símico estático 23
1
2
3
4
5
6
7
365.160179625
351.393865032719
324.037421454311
283.522368892565
229.049602548569
160.254940068624
77.3408537871362
FUERZA CORTANTE
Piso M(Tn) Condicion 1 Condicion 2 Por lo tanto1 323.64 Regular Regular regular2 321.22 Regular Regular regular3 317.43 Regular Regular regular4 320.16 Regular Regular regular5 323.47 Regular Regular regular6 324.88 Regular Regular regular7 259.75
Sistemas resistentes a cargas laterales y Análisis símico estático 24
En los planos de estructuras no se presentan desalineamiento vertical en ninguno de los muros ni placas.
Sistemas resistentes a cargas laterales y Análisis símico estático 25
DT 10.2D1 3.7
Condición irregular
ANALISIS DEL METODO CON IRREGULARIDAD
VARIABLES DATOSZ3 = 0.4S = 1U = 1C = 2.5R = 6CT = 60Tp = 0.4H = 18.55T = 0.30916667P = 2190.55V = 486.78824
PISO H Ht P Ht*P FT CORTE7 2.65 18.55 259.75 4818.36558 103.112427 103.1124276 2.65 15.9 324.88 5165.58016 110.542776 213.6552025 2.65 13.25 323.47 4285.93451 91.7184677 305.373674 2.65 10.6 320.16 3393.67475 72.6242193 377.9978893 2.65 7.95 317.43 2523.55515 54.0037676 432.0016572 2.65 5.3 321.22 1702.48869 36.433047 468.4347041 2.65 2.65 323.64 857.646809 18.3535355 486.78824
18.55 2190.55 22747.25
Sistemas resistentes a cargas laterales y Análisis símico estático 26
1
2
3
4
5
6
7
18.3535354935939
36.4330470175425
54.0037675889591
72.6242193454826
91.7184676502606
103.112426755301
110.54277564886
FUERZAS SISMICAS
1
2
3
4
5
6
7
486.7882395
468.434704006406
432.001656988864
377.997889399905
305.373670054422
213.655202404161
103.112426755301
FUERZA CORTANTE
Sistemas resistentes a cargas laterales y Análisis símico estático 27
6) ANALISIS ESTRUCTURAL TRIDIMENCIONAL (ETABS DEL EDIFICIO)
MODELACIÓN EN ETABS
Sistemas resistentes a cargas laterales y Análisis símico estático 28
7) DIAGRAMA DE MOMENTO, FUERZAS CORTANTES, DE CADA EJE PORTANTE
PLANTA DEL PRIMER PISO PRINCIPALES EJES RESISTENTES
CORTANTE RECIBIDO POR CADA ELEMENTO
DIRECCION X
Sistemas resistentes a cargas laterales y Análisis símico estático 29
EJE 2-2
EJE 4-4
EJE 5-5
Sistemas resistentes a cargas laterales y Análisis símico estático 30
EJE 10-10
EJE 13-13
Sistemas resistentes a cargas laterales y Análisis símico estático 31
DIRECCION Y
EJE A-A
EJE C-C
Sistemas resistentes a cargas laterales y Análisis símico estático 32
EJE F-F
Sistemas resistentes a cargas laterales y Análisis símico estático 33
5) DESPLAZAMIENTOS:
Sismo en Dirección X-X Sismo en Dirección Y-YPISO Δ(máx mm) Δ(Relativo) PISO Δ(máx mm) Δ(Relativo)
7 24.7 0.00136 7 43.6 0.002346 21.1 0.00151 6 37.4 0.002645 17.1 0.00162 5 30.4 0.002874 12.8 0.00162 4 22.8 0.002983 8.5 0.00151 3 14.9 0.002832 4.5 0.00121 2 7.4 0.002111 1.3 0.00049 1 1.8 0.00068
0 0
Tabla N° 8
LIMITES PARA DESPLAZAMIENTO LATERAL DE ENTREPISO
Estos límites no son aplicables a naves industriales
Material Predominante ( i / hei )
Concreto Armado 0,007
Acero 0,010
Albañilería 0,005
Madera 0,010
De acuerdo a la norma E-030 DE DISEÑO SISMORRESISTENTE LOS DESPLAZAMIENTOS ESTAN DENTRO DE LO PERMITIDO POR LA NORMA.
Sistemas resistentes a cargas laterales y Análisis símico estático 34
Sistemas resistentes a cargas laterales y Análisis símico estático 35