infrared thermal imaging inspe
TRANSCRIPT
-
8/18/2019 Infrared Thermal Imaging Inspe
1/129
Cairo at 24th
December 2015
To: Pepsico Egypt Company
Attn.: Eng. Ahmed Zain
Eng. Ahmed Youns
Infrared Thermal Imaging Inspection Report
Customer: Pepsico Egypt Company
Site: October Plant
Equipment: Electric System
Date: December 21, 2015
Reported by Sherif Mounir Ahmed
"Technical Support / Senior Service Engineer"
-
8/18/2019 Infrared Thermal Imaging Inspe
2/129
Page | II
Introduction
Infrared Thermographic image is an excellent condition monitoring tool to assist in
the reduction of maintenance costs on the electrical system and mechanical equipment and
detect developing problems. The technique allows for the monitoring of temperatures and
thermal patterns while the electrical system and mechanical equipment are online and
operating under full load. Unlike many other test methods, Infrared Thermal Imaging can beused on a wide variety of electric components and mechanical equipment. It has been
proven time after time to readily identify reliability and safety concerns, and to provide
excellent short-term. For example, early detection of a single fault in a large transformer can
easily save over one million dollars in maintenance costs.
What is infrared?
Infrared energy is part of the electromagnetic spectrum and behaves similarly to
visible light. It travels through space at the speed of light and can be reflected, refracted,
absorbed, and emitted. Has a wavelength longer than that of visible light. Infrared is usually
divided into 3 spectral regions: near, mid and far-infrared.
Where does infrared energy come from?
All objects emit thermal energy (heat) during normal operation as a function of their
temperature. This means all objects emit infrared radiation. Infrared energy is generated by
the vibration and rotation of atoms and molecules. The higher the temperature of an object,
the more the motion and hence the more infrared energy is emitted. This is the energy
detected by infrared cameras which detect thermal radiation only, not temperature. And the
most important factor that affects radiation emitted form a target is its emissivity. Emissivity
is the ability of a body to emit radiation. Each material has its own emissivity.
What is infrared thermography?All objects emit infrared radiation in the form of electromagnetic radiation in the
infrared spectrum which allows Infrared thermal imaging to evaluate their operating
condition. The hotter the object is, the more intense the infrared radiation emitted. This
radiation is, however, outside of the human eye range. Infrared thermography is used to
image and measure to detect this radiation. By detecting areas of abnormal temperature,
infrared thermography can diagnose problem areas and their severity.
• Infrared Thermography is the technique for producing an image of invisible infrared light
emitted by objects due to their thermal condition.
• An image produced by an infrared camera is called a thermogram or sometimes a
thermograph.• Thermography allows one to make non-contact measurements of an object’s temperature.
SKF cameras provide detailed photographs indicating each piece of operating component's
"heat signature". The amount of temperature rise over the normal operating temperature
provides a good indicator of the severity of a problem. This thermal profile, correctly
interpreted, can reveal a great deal regarding the operating condition of the equipment
being inspected. A probable cause and recommended action then can be suggested for each
finding.
-
8/18/2019 Infrared Thermal Imaging Inspe
3/129
Page | III
Why does infrared thermography work?
In mechanical and electrical applications, Infrared Thermal Imaging is more useful
for locating a problem area than for indicating the root cause of the overheating. The heat is
usually produced within a component that is not visible directly to the camera. That heat
must conduct up through the material and present itself as a pattern on the surface of the
object in order for the infrared camera to sense it.
Most component or processes are designed to eliminate thermal energy under normal
operation; simply identifying a thermal pattern does not mean a problem has been located.
Once a normal thermal signature is obtained and understood, any deviation from this
normal signature will then provide evidence of a suspect problem developing.
Why infrared thermography surveys are important?
Infrared Thermal Imaging is an electronic technique that quite literally allows us to
see thermal energy. Infrared thermographic imaging has been available for many years as a
troubleshooting tool. With this new capability plant maintenance personnel have recognized
Infrared Thermal Imaging as one of the most versatile and effective condition monitoringtools available today. Infrared Thermal Imaging enhances a company's ability to predict
equipment and component failure and plan corrective action before a costly shutdown,
component damage, or personal injury occurs.
How infrared thermography is performed?
Performed on operating equipment and machinery, an infrared survey is a
nondestructive test that does not interrupt normal business operations. Measurements are
made:
While the plant is operating.
Without contacting the target object.
With the equipment under full load.
From a safe distance from energized electrical component, rotating equipment or
equipment in hostile environments.
Points in the same target, and compare them.
Real time imaging allows us to do very fast scanning of stationary targets with immediate
results.
The real time character of infrared thermography lets us capture very fast moving target.
After the survey is completed, a report is prepared and can be delivered on-site in either
electronic format.
Electrical Inspection
One of the biggest problems in electrical systems is excessive temperatures. This
excessive heat from distribution and transmission systems for hot spots can be generated by
loose connections, damage, load imbalances and other failure mechanisms. Most electrical
system (such as transformers, Panel Boards, Control Panels, bus bars, transmission lines,
isolation disconnects, , relays, wiring ,Switchboards, Power Cabling, Cable Terminations,
Fuse Disconnects and holders) has allowable operating temperature limits that can be used
as guidelines.
-
8/18/2019 Infrared Thermal Imaging Inspe
4/129
Page | IV
Order and scope of work
As a partnership between Pepsico Company & Industrial Services Center- DATCO,
DATCO submit offer dated 07/09/2015 for Infrared Thermal Imaging Inspection on site.
Pepsico release a PO no. 4500505075 dated 24/11/2015.
General Information
Description of survey
The inspection covered the components of the electrical system and the electric
insulation systems that were under load at the time of survey dated 21/12/2015. All
components of the electrical systems conform to coding system. The electric insulation
systems rated by NEMA, UL and IEC standards according to as insulation class or thermal
classification of each system.
Thermographer & Analyst Sherif Mounir Ahmed
Infrared thermographic camera E 50 IR camera
Firmware of the camera Version 2.23.14
Software Reporter Version 5.3.15320.1002
http://en.wikipedia.org/wiki/International_Electrotechnical_Commissionhttp://en.wikipedia.org/wiki/International_Electrotechnical_Commission
-
8/18/2019 Infrared Thermal Imaging Inspe
5/129
Page | V
Coding System
A code is assigned to each of the discovered faults. The purpose behind such procedure is to
classify the faults depending on the degree of seriousness of each fault. The more serious
the fault the more urgent it has to be corrected.
I- High Voltage
II- Medium & Low Voltage
Note: The codes are based on British Engineering Standards BS7671 - Regulation 523-01.
Code Fault Action DescriptionTemperatureIncrease (° C)
One Danger Immediate repair requiredFor components temp. exceeding 70°c and/ortemperature rise (compared to similar componentsunder similar load)
> 50
Two Critical Repair ASAPFor temp. rise (compared to similar componentsunder similar load)
30 - 50
Three Warning Schedule repairFor temp. rise (compared to similar componentsunder similar load)
20 - 30
Four AlertMonitor development andrepair as necessary
For temp. rise (compared to similar componentsunder similar load)
< 20
Code Fault Action DescriptionTemperature
Increase (° C)
One Danger Immediate repair requiredFor components temp. exceeding 70°c and/ortemperature rise (compared to similar componentsunder similar load)
> 30
Two Critical Repair ASAPFor temp. rise (compared to similar componentsunder similar load)
20 - 30
Three Warning Schedule repairFor temp. rise (compared to similar componentsunder similar load)
10 - 20
Four AlertMonitor development andrepair as necessary
For temp. rise (compared to similar componentsunder similar load)
5 - 10
-
8/18/2019 Infrared Thermal Imaging Inspe
6/129
Page | VI
Executive Summary of Inspection for Production Lines
Ser. Area Equipment (Unit) Image Code Fault Action
رغ
برك
وى
يكسوخ4 -MDB-
M
GR0363Normal No Fault No Action Required
GR0365
Processing VED- خط
4 GR0371 Normal No Fault No Action Required4M2-Heat Exchanger KHX -
خط
4 GR0373 Normal No Fault No Action Required
4M1-PCSO Packing - 4خط GR0375 Normal No Fault No Action Required
4M3-Starch Recovery -خط
4 GR0377 Normal No Fault No Action Required
4M6-Seasoning Loop 1 - 4خط GR0381 Normal No Fault No Action Required
4M6-Seasoning Loop 2 - 4خط GR0383 Normal No Fault No Action Required
(Fryer&Oven)- 6 GR0389 Normal No Fault No Action Requiredخط
0 (Corn Cleaning, LBCSS & HeatExchanger KHX)-
خط
6 GR0391 Normal No Fault No Action Required
1 2M1-Heat Exchanger - 5خط GR0395 Normal No Fault No Action Required
2 2M4-Fryer - 5 GR0397 Normal No Fault No Action Requiredخط
3 2M4-LBCSS - 5 GR0399 Normal No Fault No Action Requiredخط
4
يكسوخرا
اخدوسوكيت PC50
GR0409
Normal No Fault No Action Required5 GR0411
6 GR0413
7 GR0415
8حويكا-زور
جيع
GR0417 Normal No Fault No Action Required
9 GR0419 Four Alert Monitor development and repair as necessary
0 GR0423 Three Warning Schedule repair
1
Line 4
حوطايخا GR0425
Normal No Fault No Action Required2 GR0427
3 VDF Panel GR0429 Normal No Fault No Action Required
4
Fryer Panel
GR0431
Normal No Fault No Action Required5 GR0433
6 GR0435
7Line 5&6 Corn Panel
GR0437Normal No Fault No Action Required
8 GR0439
9
Line 6
LBCSS PanelGR0441
Normal No Fault No Action Required0 GR0443
1Shelter & Oven Panel
GR0455Normal No Fault No Action Required
2 GR0457
3Fryer & Seasoning
Panel
GR0461 Normal No Fault No Action Required
4 GR0463One Danger Immediate repair required
5 GR0465
6
Line 5
LBCSS PanelGR0445
Normal No Fault No Action Required7 GR0447
8
Shelter & Oven Panel
GR0449
Normal No Fault No Action Required9 GR0451
0 GR0453
1 Fryer & Seasoning Panel GR0459 Normal No Fault No Action Required
2
Line 7 Clextral Power Panel
GR0469
Normal No Fault No Action Required3 GR0471
-
8/18/2019 Infrared Thermal Imaging Inspe
7/129
Page | VII
Ser. Area Equipment (Unit) Image Code Fault Action
4 Line 7 Clextral Heater Panel GR0473 Normal No Fault No Action Required
5
Line 8
حوو GR0475 Normal No Fault No Action Required
6 Clextral Power Panel GR0477 Normal No Fault No Action Required7 GR0479
8Line 9
Nut Coating &
Roasting Panel
GR0481Normal No Fault No Action Required
9 GR0483
0 حويشيب1&2&3 GR0601 Normal No Fault No Action Required
1
Line 3
Fryer PanelGR0603
Four Alert Monitor development and repair as necessary2 GR0605
3 Potato Panel GR0607 Normal No Fault No Action Required
4 Seasoning Panel GR0609 Normal No Fault No Action Required
5
Line 2
Potato Panel GR0611 Normal No Fault No Action Required
6 Fryer Panel GR0613 Normal No Fault No Action Required7 Seasoning Panel GR0615 Normal No Fault No Action Required
8
Line 1
Potato Panel GR0617 Normal No Fault No Action Required
9 Fryer Panel GR0619 Normal No Fault No Action Required
0 Seasoning Panel GR0621 Normal No Fault No Action Required
-
8/18/2019 Infrared Thermal Imaging Inspe
8/129
Page | VIII
Executive Summary of Inspection of Utilities:
Ser. Area Equipment (Unit) Image Code Fault Action
Diesels
Room
Production Line 1 – T1 GR0485 Four Alert Monitor development and repair as necessary
Main Switch Line – T1 GR0487 Normal No Fault No Action Required
Power Factor Line 1 -
T1
GR0489 Normal No Fault No Action Required
GR0491 Four Alert Monitor development and repair as necessary
GR0495 Normal No Fault No Action Required
GR0497 Four Alert Monitor development and repair as necessary
Compressor 1 Panel –
T1
GR0499Normal No Fault No Action Required
GR0501
Power Factor Line 2 -
T1
GR0503 Normal No Fault No Action Required
0 GR0505 Three Warning Schedule repair
1 GR0507
Normal No Fault No Action Required2 GR0509
3 GR0511
4 Line New TC Panel -T1 GR0513 Normal No Fault No Action Required
5 Power Factor Line New TC - T1 GR0515 Normal No Fault No Action Required
6 حويركا - T1 GR0517 Normal No Fault No Action Required
7 Compressor 5,6&7 Panel – T1 GR0519 Normal No Fault No Action Required
8
Pump PC50 Panel - T1
GR0521
Normal No Fault No Action Required9 GR0523
0 GR0525
1حوطحرصاديدجا
- T1
GR0527Normal No Fault No Action Required
2 GR0529
3 Compressor 2 Panel –
T2
GR0531Normal No Fault No Action Required
4 GR0533
5Production Line 2 – T2
GR0535Normal No Fault No Action Required
6 GR0537
7Power Factor
طح
ادياصرف - T2
GR0539
Normal No Fault No Action Required8 GR0541
9 GR0543
0Power Factor Line Old
TC - T2
GR0545
Normal No Fault No Action Required1 GR0547
2 GR0549
3 Production Line 4 – T3 GR0551 Normal No Fault No Action Required
4 حوبطيرحا - T4 GR0553 Normal No Fault No Action Required
5حودخغاوضا - T4
GR0555Normal No Fault No Action Required
6 GR0557
7
Transfor
mers
Room
Transformer 1GR0565
Normal No Fault No Action Required8 GR0567
9
Transformer 2
GR0559
Normal No Fault No Action Required0 GR0561
1 GR0563
2Transformer 3
GR0569Normal No Fault No Action Required3 GR0571
-
8/18/2019 Infrared Thermal Imaging Inspe
9/129
Page | IX
Ser. Area Equipment (Unit) Image Code Fault Action
4 Transform
ers RoomTransformer 4
GR0575Normal No Fault No Action Required
5 GR0573
6 CompressorsRoom Compressor 4 GR0577 Normal No Fault No Action Required
7 Compres
sors EP
Room
Compressor 7 GR0581 Three Warning Schedule repair
8 Compressor 6 GR0583 Normal No Fault No Action Required
9 Compressor 5 GR0585 Normal No Fault No Action Required
-
8/18/2019 Infrared Thermal Imaging Inspe
10/129
Page | X
Executive Summary of Inspection of Clod Stores
For any further information, please do not hesitate to contact us.
Ser. Area Equipment (Unit) Image Code Fault Action
را
يسي را
وح سكي وى GR0587 Normal No Fault No Action Required
جث حو A GR0589 Normal No Fault No Action Required
حوجث B GR0591 Normal No Fault No Action Required
حوجث C + كسبت اطم GR0593 Normal No Fault No Action Required
حوجث C GR0595 Normal No Fault No Action Required
رغ
اشيل
حوجث C GR0597 Normal No Fault No Action Required
جث حو A GR0599 Normal No Fault No Action Required
-
8/18/2019 Infrared Thermal Imaging Inspe
11/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
1/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
Infrared Thermal ImagingInspection Report-ProductionLines
-
8/18/2019 Infrared Thermal Imaging Inspe
12/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
2/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:07:33 AM °C
Sp1
Sp2
30.0
22.7
IR_0363.jpg FLIR E50 49025354
Measurements °CSp1 28.7
Sp2 28.2
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note 4 -MDB-M
21/12/2015 10:07:33 AM
DC_0364.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
13/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
3/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:07:53 AM °C
Sp1
29.8
22.3
IR_0365.jpg FLIR E50 49025354
Measurements °CSp1 28.2
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note 4 -MDB-M
21/12/2015 10:07:53 AM
DC_0366.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
14/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
4/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:12:43 AM °C
Sp1
Sp2
Sp3
36.6
23.2
IR_0371.jpg FLIR E50 49025354
Measurements °CSp1 35.4
Sp2 36.7
Sp3 35.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteProcessing VED- 4خ
21/12/2015 10:12:43 AM
DC_0372.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in the abovementioned measurements table between the max. and the min. spots, which is anacceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
15/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
5/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:13:18 AM °C
Li1
Li2Li3
30.3
23.9
IR_0373.jpg FLIR E50 49025354
Measurements °CLi1 Max 27.9
Min 25.3
Average 26.7Li2 Max 29.3
Min 27.5
Average 28.1
Li3 Max 30.0
Min 27.2
Average 28.7
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note4M2-Heat Exchanger KHX - 4خ
21/12/2015 10:13:18 AM
DC_0374.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
16/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
6/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:14:02 AM °C
Li1
Li2 Li3
30.6
23.7
IR_0375.jpg FLIR E50 49025354
Measurements °CLi1 Max 28.7
Min 24.9
Average 27.1Li2 Max 28.5
Min 25.9
Average 27.3
Li3 Max 30.2
Min 27.8
Average 28.7
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note4M1-PCSO Packing - 4خ
21/12/2015 10:14:02 AM
DC_0376.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
17/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
7/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:15:25 AM °C
Li1
Li2
27.0
23.0
IR_0377.jpg FLIR E50 49025354
Measurements °CLi1 Max 25.8
Min 25.0
Average 25.4Li2 Max 28.2
Min 25.6
Average 26.1
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note4M3-Starch Recovery - 4خ
21/12/2015 10:15:25 AM
DC_0378.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
18/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
8/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:16:54 AM °C
Li1Li2
27.0
21.1
IR_0381.jpg FLIR E50 49025354
Measurements °CLi1 Max 24.5
Min 23.4
Average 24.0Li2 Max 25.1
Min 23.6
Average 24.3
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note4M6-Seasoning Loop 1 - 4خ
21/12/2015 10:16:54 AM
DC_0382.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
19/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
9/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:17:59 AM °C
Li1Li2
26.3
21.1
IR_0383.jpg FLIR E50 49025354
Measurements °CLi1 Max 24.2
Min 22.7
Average 23.6Li2 Max 24.7
Min 22.5
Average 23.8
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note4M6-Seasoning Loop 2 - 4خ
21/12/2015 10:17:59 AM
DC_0384.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
20/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
10/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:20:33 AM °C
Li1Li2
Li3Li4
35.2
21.7
IR_0389.jpg FLIR E50 49025354
Measurements °CLi1 Max 33.9
Min 26.9
Average 32.0Li2 Max 37.6
Min 24.4
Average 31.6
Li3 Max 31.6
Min 28.4
Average 30.9
Li4 Max 32.4
Min 27.9
Average 30.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note2M2&2M3 (Fryer&Oven)- 6خ
21/12/2015 10:20:33 AM
DC_0390.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
21/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
11/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:21:35 AM °C
Li1Li2
Li3Li4
Li5Li6
28.2
19.5
IR_0391.jpg FLIR E50 49025354
Measurements °CLi1 Max 26.8
Min 24.1
Average 25.4Li2 Max 25.7
Min 23.1
Average 24.5
Li3 Max 23.4
Min 22.3
Average 22.9
Li4 Max 24.0
Min 22.1
Average 22.7
Li5 Max 23.0
Min 21.3
Average 22.3
Li6 Max 22.7
Min 21.1
Average 22.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note2M5,2M6&2M7(CornClining,LBCSS&Heat Exchanger KHX)-
6خ
21/12/2015 10:21:35 AM
DC_0392.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
22/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
12/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:24:09 AM °C
Li1Li2
26.4
21.0
IR_0395.jpg FLIR E50 49025354
Measurements °CLi1 Max 25.4
Min 23.0
Average 24.7Li2 Max 24.7
Min 23.2
Average 24.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note2M1-Heat Exchanger - 5خ
21/12/2015 10:24:09 AM
DC_0396.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
23/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
13/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:24:37 AM °C
Sp1
Li1
29.6
20.9
IR_0397.jpg FLIR E50 49025354
Measurements °CSp1 23.9
Li1 Max 29.5
Min 24.3 Average 25.5
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note2M2-Fryer - 5خ
21/12/2015 10:24:37 AM
DC_0398.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
24/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
14/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:25:10 AM °C
Li1
26.4
19.6
IR_0399.jpg FLIR E50 49025354
Measurements °CLi1 Max 25.1
Min 21.8
Average 23.3
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note2M4-LBCSS - 5خ
21/12/2015 10:25:10 AM
DC_0400.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
25/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
15/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:44:50 AM °C
Li1
Li2
25.0
20.8
IR_0409.jpg FLIR E50 49025354
Measurements °CLi1 Max 24.3
Min 21.9
Average 23.2Li2 Max 25.4
Min 21.7
Average 23.2
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note PC50
21/12/2015 10:44:50 AM
DC_0410.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
26/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
16/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:45:14 AM °C
Li1
24.5
19.3
IR_0411.jpg FLIR E50 49025354
Measurements °CLi1 Max 24.3
Min 21.3
Average 22.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note PC50
21/12/2015 10:45:14 AM
DC_0412.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
27/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
17/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:45:59 AM °C
Li1
25.4
20.9
IR_0413.jpg FLIR E50 49025354
Measurements °CLi1 Max 25.8
Min 21.9
Average 23.1
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note PC50
21/12/2015 10:45:59 AM
DC_0414.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
28/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
18/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:46:34 AM °C
Li1
26.1
21.1
IR_0415.jpg FLIR E50 49025354
Measurements °CLi1 Max 25.6
Min 22.3
Average 24.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note PC50
21/12/2015 10:46:34 AM
DC_0416.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
29/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
19/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:50:17 AM °C
Sp1 Sp2 Sp3
Li1
29.5
24.0
IR_0417.jpg FLIR E50 49025354
Measurements °CSp1 28.8
Sp2 26.2
Sp3 25.7Li1 Max 27.9
Min 25.6
Average 26.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note-ل
21/12/2015 10:50:17 AM
DC_0418.jpg
Text annotations
Description of analysis & observation Normal conditions are observed as the temp. diff. on the left phase is more loadedthan right phase, otherwise temp. diff. for each component/phase is an acceptable.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
30/129
-
8/18/2019 Infrared Thermal Imaging Inspe
31/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
21/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:52:38 AM °C
Sp1Sp2 Sp3
Sp4Sp5 Sp6
44.7
22.6
IR_0423.jpg FLIR E50 49025354
Measurements °CSp1 46.3
Sp2 28.7
Sp3 29.3Sp4 39.6
Sp5 31.2
Sp6 31.3
Dt2 Sp4 - Sp5 8.3
Dt1 Sp1 - Sp2 17.7
ParametersEmissivity 0.95
Refl. temp. 20 °C
21/12/2015 10:52:38 AM
DC_0424.jpgxt annotations
scription of analysis & observation Raised temperature are observed on spot (1), the temp. diff. is within the range 10 - 20° C asshown in the above mentioned measurements table between the max. and the min. spots.
ion / Severity Schedule repair required for the Sp (1). / Potential severity
de / Fault Three / Warning
ential impact upon severity Occur short circuiting/turn-to-turn faults/burning component.
nditions Found/Deviation Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/overheating is of concern.
ysical inspection/Electrical testing/Remedy The source of the raised temperature shall be investigated and eliminated by cleaning/tighten theconnection/check the load/inspection the internal component/change the component, if possible.
-
8/18/2019 Infrared Thermal Imaging Inspe
32/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
22/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:56:32 AM °C
Li1
Li2
32.1
25.6
IR_0425.jpg FLIR E50 49025354
Measurements °CLi1 Max 27.5
Min 26.7
Average 27.1Li2 Max 27.5
Min 26.4
Average 26.8
ParametersEmissivity 0.95
Refl. temp. 20 °C
Noteل
21/12/2015 10:56:32 AM
DC_0426.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
33/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
23/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:57:37 AM °C
Li1
Li2
Li3
35.0
23.9
IR_0427.jpg FLIR E50 49025354
Measurements °CLi1 Max 29.6
Min 28.2
Average 28.9Li2 Max 28.6
Min 28.2
Average 28.4
Li3 Max 28.6
Min 28.0
Average 28.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
Noteل
21/12/2015 10:57:37 AM
DC_0428.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
34/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
24/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 10:58:47 AM °C
Li1
55.0
27.4
IR_0429.jpg FLIR E50 49025354
Measurements °CLi1 Max 47.9
Min 40.7
Average 44.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteVDF Panel
21/12/2015 10:58:47 AM
DC_0430.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
35/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
25/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:00:08 AM °C
Li1
Li2
43.5
34.9
IR_0431.jpg FLIR E50 49025354
Measurements °CLi1 Max 38.2
Min 37.3
Average 38.0Li2 Max 39.4
Min 36.9
Average 38.1
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 11:00:08 AM
DC_0432.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
36/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
26/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:00:41 AM °C
Li1 Li2
Li3
43.2
34.8
IR_0433.jpg FLIR E50 49025354
Measurements °CLi1 Max 40.8
Min 40.4
Average 40.6Li2 Max 40.2
Min 38.6
Average 39.5
Li3 Max 43.3
Min 40.6
Average 41.7
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 11:00:41 AM
DC_0434.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
37/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
27/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:02:27 AM °C
Li1
42.5
33.1
IR_0435.jpg FLIR E50 49025354
Measurements °CLi1 Max 41.7
Min 37.7
Average 40.3
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 11:02:27 AM
DC_0436.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
38/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
28/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:04:15 AM °C
Li1
Li2
37.4
23.0
IR_0437.jpg FLIR E50 49025354
Measurements °CLi1 Max 31.9
Min 29.5
Average 30.3Li2 Max 31.4
Min 29.9
Average 30.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteCorn Panel
21/12/2015 11:04:15 AM
DC_0438.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in the abovementioned measurements table between the max. and the min. spots, which is anacceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
39/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
29/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:04:45 AM °C
Li1
41.7
26.3
IR_0439.jpg FLIR E50 49025354
Measurements °CLi1 Max 35.1
Min 33.3
Average 34.2
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteCorn Panel
21/12/2015 11:04:45 AM
DC_0440.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
40/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
30/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:06:45 AM °C
Li1
48.9
36.9
IR_0441.jpg FLIR E50 49025354
Measurements °CLi1 Max 38.1
Min 37.5
Average 37.9
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteLBCSS Panel
21/12/2015 11:06:45 AM
DC_0442.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
41/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
31/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:07:12 AM °C
Li1
40.3
36.2
IR_0443.jpg FLIR E50 49025354
Measurements °CLi1 Max 39.0
Min 38.2
Average 38.5
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteLBCSS Panel
21/12/2015 11:07:12 AM
DC_0444.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
42/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
32/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:15:14 AM °C
Li1
Li2
46.3
35.1
IR_0455.jpg FLIR E50 49025354
Measurements °CLi1 Max 41.4
Min 39.6
Average 40.0Li2 Max 42.0
Min 38.7
Average 40.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteShelter & Oven Panel
21/12/2015 11:15:14 AM
DC_0456.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
43/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
33/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:15:31 AM °C
Li1
Li2
65.2
39.2
IR_0457.jpg FLIR E50 49025354
Measurements °CLi1 Max 48.7
Min 39.8
Average 44.3Li2 Max 50.0
Min 39.5
Average 44.3
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteShelter & Oven Panel
21/12/2015 11:15:31 AM
DC_0458.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
44/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
34/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:17:53 AM °C
Li1
Li2
54.3
28.9
IR_0461.jpg FLIR E50 49025354
Measurements °CLi1 Max 41.7
Min 35.9
Average 40.1Li2 Max 55.1
Min 35.2
Average 41.5
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer & Seasoning Panel
21/12/2015 11:17:53 AM
DC_0462.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
45/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
35/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:20:16 AM °C
Li1
Li2
79.2
35.2
IR_0463.jpg FLIR E50 49025354
Measurements °CLi1 Max 77.4
Min 42.3
Average 53.0Li2 Max 84.6
Min 57.3
Average 77.6
Dt1 Li1.Max - Ref. temp. 7.4
Dt2 Li2.Max - Ref. temp. 14.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer & Seasoning Panel
21/12/2015 11:20:16 AM
DC_0464.jpgxt annotations
scription of analysis & observation Elevated temperature are observed on line (1&2). The temp. exceeding reference temperature70°C. The temp. diff. between the spot and the reference temperature is shown in the abovementioned measurements table.
ion / Severity Immediate repair required for the Li(1&2). / Severity is high. This is strongly recommended as aresult of this suffered temp. will lead to fault immediately.
de / Fault One / Danger
ential impact upon severity Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.
nditions Found/Deviation Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/overheating is of concern.
ysical inspection/Electrical testing/Remedy The source of the raised temperature shall be investigated and eliminated by cleaning/tighten theconnection/check the load/inspection the internal component/change the component, if possible.
-
8/18/2019 Infrared Thermal Imaging Inspe
46/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
36/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:20:46 AM °C
73.6
36.9
IR_0465.jpg FLIR E50 49025354
Measurements °CLi1 Max 74.5
Min 57.6
Average 64.9Dt1 Li1.Max - Ref. temp. 4.5
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer & Seasoning Panel
21/12/2015 11:20:46 AM
DC_0466.jpgxt annotations
scription of analysis & observation Elevated temperature are observed on line (1). The temp. exceeding reference temperature 70°C. The temp. diff. between the spot and the reference temperature is shown in the abovementioned measurements table.
tion / Severity Immediate repair required for the Li (1). / Severity is high. This is strongly recommended as aresult of this suffered temp. will lead to fault immediately.
de / Fault One / Danger
tential impact upon severity Occur arcing/short circuiting/turn-to-turn faults/burning component/fire.
nditions Found/Deviation Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/overheating is of concern.
ysical inspection/Electrical testing/Remedy The source of the raised temperature shall be investigated and eliminated by cleaning/tighten theconnection/check the load/inspection the internal component/change the component, if possible.
-
8/18/2019 Infrared Thermal Imaging Inspe
47/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
37/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:08:26 AM °C
46.9
33.3
IR_0445.jpg FLIR E50 49025354
Measurements °CLi1 Max 35.4
Min 33.5
Average 34.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteLBCSS Panel
21/12/2015 11:08:26 AM
DC_0446.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
48/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
38/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:08:55 AM °C
Li1
Li2
Li3
44.3
30.1
IR_0447.jpg FLIR E50 49025354
Measurements °CLi1 Max 31.8
Min 31.3
Average 31.5Li2 Max 33.7
Min 32.9
Average 33.4
Li3 Max 37.5
Min 34.4
Average 36.1
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteLBCSS Panel
21/12/2015 11:08:55 AM
DC_0448.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
49/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
39/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:13:04 AM °C
Li1
Li2
46.7
35.2
IR_0449.jpg FLIR E50 49025354
Measurements °CLi1 Max 47.3
Min 43.0
Average 45.6Li2 Max 47.1
Min 41.6
Average 44.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteShelter & Oven Panel
21/12/2015 11:13:04 AM
DC_0450.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
50/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
40/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:13:52 AM °C
Li1
Li2
Li3
48.8
37.2
IR_0451.jpg FLIR E50 49025354
Measurements °CLi1 Max 48.5
Min 46.1
Average 47.3Li2 Max 49.8
Min 43.9
Average 47.4
Li3 Max 48.1
Min 46.2
Average 47.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteShelter & Oven Panel
21/12/2015 11:13:52 AM
DC_0452.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
51/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
41/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:14:08 AM °C
Li1
Li2
51.6
34.0
IR_0453.jpg FLIR E50 49025354
Measurements °CLi1 Max 51.5
Min 46.6
Average 49.1Li2 Max 49.2
Min 41.5
Average 43.5
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteShelter & Oven Panel
21/12/2015 11:14:08 AM
DC_0454.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
52/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
42/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:17:08 AM °C
Li1
44.2
31.2
IR_0459.jpg FLIR E50 49025354
Measurements °CLi1 Max 35.5
Min 34.7
Average 35.2
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer & Seasoning Panel
21/12/2015 11:17:08 AM
DC_0460.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
53/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
43/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:33:08 AM °C
Sp1
Sp2
Sp3
Li1
Li2
Li3
41.8
26.1
IR_0469.jpg FLIR E50 49025354
Measurements °CSp1 34.2
Sp2 36.9
Sp3 32.8Li1 Max 41.5
Min 31.9
Average 37.4
Li2 Max 41.7
Min 34.3
Average 38.7
Li3 Max 34.7
Min 32.7
Average 33.8
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteClextral Power Panel
21/12/2015 11:33:08 AM
DC_0470.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
54/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
44/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:35:01 AM °C
Li1
Li2
Li4
Li5
67.3
28.4
IR_0471.jpg FLIR E50 49025354
Measurements °CLi1 Max 43.4
Min 38.5
Average 41.7Li2 Max 48.0
Min 42.3
Average 46.1
Li3 Max 41.6
Min 37.5
Average 40.1
Li4 Max 47.1
Min 38.7
Average 43.8
Li5 Max 45.9
Min 43.9
Average 44.8
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteClextral Power Panel
21/12/2015 11:35:01 AM
DC_0472.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
55/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
45/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:36:25 AM °C
Li1
Li2
34.4
30.3
IR_0473.jpg FLIR E50 49025354
Measurements °CLi1 Max 32.9
Min 31.7
Average 32.1Li2 Max 33.8
Min 32.0
Average 32.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteClextral Heater Panel
21/12/2015 11:36:25 AM
DC_0474.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
56/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
46/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:39:24 AM °C
Sp1 Sp2
Sp3
40.5
25.6
IR_0475.jpg FLIR E50 49025354
Measurements °CSp1 31.5
Sp2 32.1
Sp3 31.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteClextral Power Panel
21/12/2015 11:39:24 AM
DC_0476.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
57/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
47/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:40:54 AM °C
Li1
42.1
29.5
IR_0477.jpg FLIR E50 49025354
Measurements °CLi1 Max 35.4
Min 32.7
Average 34.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteClextral Power Panel
21/12/2015 11:40:54 AM
DC_0478.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
58/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
48/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:41:59 AM °C
Li1
43.5
31.1
IR_0479.jpg FLIR E50 49025354
Measurements °CLi1 Max 43.1
Min 39.4
Average 41.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteClextral Power Panel
21/12/2015 11:41:59 AM
DC_0480.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
59/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
49/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:44:49 AM °C
Li1
30.4
22.4
IR_0481.jpg FLIR E50 49025354
Measurements °CLi1 Max 24.9
Min 24.1
Average 24.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteNut Coating & Roasting Panel
21/12/2015 11:44:49 AM
DC_0482.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
60/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
50/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 11:45:22 AM °C
Li1
Li2
41.8
25.0
IR_0483.jpg FLIR E50 49025354
Measurements °CLi1 Max 26.3
Min 25.9
Average 26.1Li2 Max 26.9
Min 25.6
Average 26.1
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteNut Coating & Roasting Panel
21/12/2015 11:45:22 AM
DC_0484.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
61/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
51/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 02:43:07 PM °C
Li1
30.4
16.2
IR_0601.jpg FLIR E50 49025354
Measurements °CLi1 Max 23.5
Min 21.6
Average 22.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
Note1&2&3ل
21/12/2015 02:43:07 PM
DC_0602.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
62/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
52/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 02:52:28 PM °C
Sp1 Sp2 Sp3
51.5
31.1
IR_0603.jpg FLIR E50 49025354
Measurements °CSp1 45.6
Sp2 51.8
Sp3 45.1Dt1 Sp2 - Sp3 6.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 02:52:28 PM
DC_0604.jpgext annotations
escription of analysis & observation Raised temperature are observed on spot (2), the temp. diff. is within the range 5 - 10° C asshown in the above mentioned measurements table between the max. and the min. spots.
ction / Severity Monitor development and repair as necessary required for the Sp (2). / low severity
ode / Fault Four / Alert
otential impact upon severity Occur short circuiting/turn-to-turn faults.
onditions Found/Deviation Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/overheating is of concern.
hysical inspection/Electrical testing/Remedy The source of the raised temperature shall be investigated and eliminated by cleaning/tighten theconnection/check the load/inspection the internal component, if possible.
-
8/18/2019 Infrared Thermal Imaging Inspe
63/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
53/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 02:52:55 PM °C
Sp1 Sp2 Sp3
Sp4 Sp5 Sp6
54.0
30.0
IR_0605.jpg FLIR E50 49025354
Measurements °CSp1 49.4
Sp2 55.0
Sp3 51.2Sp4 45.8
Sp5 49.8
Sp6 47.4
Dt2 Sp5 - Sp4 4.1
Dt1 Sp2 - Sp1 5.6
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 02:52:55 PM
DC_0606.jpgxt annotations
escription of analysis & observation Raised temperature are observed on spot (2), the temp. diff. is within the range 5 - 10° C asshown in the above mentioned measurements table between the max. and the min. spots.
tion / Severity Monitor development and repair as necessary required for the Sp (2). / low severity
de / Fault Four / Alert
tential impact upon severity Occur short circuiting/turn-to-turn faults.
nditions Found/Deviation Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/overheating is of concern.
ysical inspection/Electrical testing/Remedy The source of the raised temperature shall be investigated and eliminated by cleaning/tighten theconnection/check the load/inspection the internal component, if possible.
-
8/18/2019 Infrared Thermal Imaging Inspe
64/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
54/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 02:56:20 PM °C
Sp1 Sp2Sp3
Sp4 Sp5 Sp6
44.7
28.9
IR_0607.jpg FLIR E50 49025354
Measurements °CSp1 40.9
Sp2 38.6
Sp3 36.9Sp4 38.8
Sp5 38.3
Sp6 37.3
Dt1 Sp1 - Sp3 4.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
NotePotato Panel
21/12/2015 02:56:20 PM
DC_0608.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
65/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
55/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 02:58:58 PM °C
Li1
Li2
54.6
28.5
IR_0609.jpg FLIR E50 49025354
Measurements °CLi1 Max 29.8
Min 29.1
Average 29.4Li2 Max 29.6
Min 29.0
Average 29.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteSeasoning Panel
21/12/2015 02:58:58 PM
DC_0610.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
66/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
56/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 03:00:55 PM °C
Li1
Li2
47.7
33.3
IR_0611.jpg FLIR E50 49025354
Measurements °CLi1 Max 41.8
Min 39.5
Average 40.6Li2 Max 40.1
Min 37.3
Average 38.4
ParametersEmissivity 0.95
Refl. temp. 20 °C
NotePotato Panel
21/12/2015 03:00:55 PM
DC_0612.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
67/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
57/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 03:02:29 PM °C
Sp1
Li1
Li2
38.4
26.6
IR_0613.jpg FLIR E50 49025354
Measurements °CSp1 32.4
Li1 Max 35.3
Min 33.5 Average 34.4
Li2 Max 39.5
Min 32.6
Average 34.0
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 03:02:29 PM
DC_0614.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
68/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
58/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 03:03:48 PM °C
Li1
39.9
31.2
IR_0615.jpg FLIR E50 49025354
Measurements °CLi1 Max 34.8
Min 34.0
Average 34.5
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteSeasoning Panel
21/12/2015 03:03:48 PM
DC_0616.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
69/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
59/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 03:06:52 PM °C
Sp1Sp2 Sp3
34.9
22.7
IR_0617.jpg FLIR E50 49025354
Measurements °CSp1 35.3
Sp2 34.1
Sp3 34.3
ParametersEmissivity 0.95
Refl. temp. 20 °C
NotePotato Panel
21/12/2015 03:06:52 PM
DC_0618.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
70/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
60/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 03:07:30 PM °C
Sp1 Sp2 Sp3
42.9
29.0
IR_0619.jpg FLIR E50 49025354
Measurements °CSp1 41.8
Sp2 39.1
Sp3 42.2
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteFryer Panel
21/12/2015 03:07:30 PM
DC_0620.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, which isan acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
71/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
61/61 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 03:08:40 PM °C
Li1
Li2
60.2
27.9
IR_0621.jpg FLIR E50 49025354
Measurements °CLi1 Max 34.8
Min 33.9
Average 34.5Li2 Max 33.9
Min 32.5
Average 33.3
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteSeasoning Panel
21/12/2015 03:08:40 PM
DC_0622.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
72/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
1/50 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
Infrared Thermal ImagingInspection Report-Utilities
-
8/18/2019 Infrared Thermal Imaging Inspe
73/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
2/50 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 12:51:28 PM °Cp
Li1 Li2
39.1
23.5
IR_0485.jpg FLIR E50 49025354
Measurements °CSp1 39.1
Sp2 35.6
Sp3 34.8Sp4 39.3
Sp5 34.5
Sp6 33.5
Li1 Max 31.5
Min 25.1
Average 29.0
Li2 Max 30.7
Min 24.3
Average 27.3
Dt1 Sp1 - Sp3 4.4
Dt2 Sp4 - Sp6 5.8
ParametersEmissivity 0.95
Refl. temp. 20 °C
NoteProduction Line 1 – T1
21/12/2015 12:51:28 PM
DC_0486.jpgxt annotations
scription of analysis & observation Raised temperature are observed on spot (4), the temp. diff. is within the range 5 - 10° C asshown in the above mentioned measurements table between the max. and the min. spots.
ion / Severity Monitor development and repair as necessary required for the Sp (4). / low severity
de / Fault Four / Alert
ential impact upon severity Occur short circuiting/turn-to-turn faults.
nditions Found/Deviation Loose connections/poor contacts/rust/unbalanced loads/deteriorated internal contact/overloading/overheating is of concern.
ysical inspection/Electrical testing/Remedy The source of the raised temperature shall be investigated and eliminated by cleaning/tighten the
connection/check the load/inspection the internal component, if possible.
-
8/18/2019 Infrared Thermal Imaging Inspe
74/129
-
8/18/2019 Infrared Thermal Imaging Inspe
75/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
4/50 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 12:53:52 PM °C
Li2
Li3
Li4
Li5
Li6
Li7
Li8
36.6
22.0
IR_0489.jpg FLIR E50 49025354
Measurements °CLi1 Max 26.5
Min 24.7
Average 25.5Li2 Max 28.6
Min 27.0
Average 27.9
Li3 Max 26.1
Min 24.6
Average 25.3
Li4 Max 27.1
Min 25.9
Average 26.4
Li5 Max 31.5
Min 28.3
Average 29.9
Li6 Max 26.8
Min 25.3
Average 25.9
Li7 Max 33.1
Min 30.2
Average 32.1
Li8 Max 32.1
Min 29.1
Average 30.8
ParametersEmissivity 0.95
Refl. temp. 20 °C
NotePower Factor Line 1- T1
21/12/2015 12:53:52 PM
DC_0490.jpg
Text annotations
Description of analysis & observation Normal conditions are observed, the temp. diff. is less than 5°C as shown in theabove mentioned measurements table between the max. and the min. spots, whichis an acceptable diff.
Action / Severity No Action required / No severity
Code / Fault Normal condition / No fault
-
8/18/2019 Infrared Thermal Imaging Inspe
76/129
-
8/18/2019 Infrared Thermal Imaging Inspe
77/129
Industrial Services Center - Datco78 Al Moultka Al Araby st., Sheraton, 11361 Cairo - EgyptWeb Site: http://www.datcoegypt.com
6/50 Infrared Thermal Imaging Inspection ReportReport Author: Sherif Mounir AhmedMobile: +2 012 - 85 711 000Email: [email protected]
21/12/2015 12:56:33 PM °C
Sp1Sp2
Sp3
Li2
Li3
Li4
31.2
22.1
IR_0495.jpg FLIR E50 49025354
Measurements °CSp1 31.2
Sp2 30.0
Sp3 28.3Li1 Max 28.4
Min 25.6
Average 27.2
Li2 Max 27.5
Min 25.7
Average 26.5
Li3 Max 29.6
Min 25.8
Average 27.6
Li4 Max 25.8
Min 24.6
Average 25.2
ParametersEmissivi