Installation Instructions SensaGuard™ 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation Instructions Installation must be in accordance with the following steps and stated specifications and should be carried out by suitable competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted. Adherence to the recommended maintenance instructions forms part of the warranty. This device is intended to be part of the safety related control system of a machine. Before installation, a risk assessment should be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications below for certification information and ratings. Technical Specifications ENGLISH: This instruction sheet is available in multiple languages at www.rockwellautomation.com/literature. Select publication language and type "SensaGuard" in the search field. GERMAN: Dieses Instruktionsblatt kann in mehreren Sprachen unter www.rockwellautomation.com/literature gelesen werden. Bitte Ihre Sprache anwählen und "SensaGuard" im Suchfeld eintippen. FRENCH: Ces instructions sont disponibles dans différentes langues à l'adresse suivante www.rockwellautomation.com/literature. Sélectionner la langue puis taper “SensaGuard” dans le champ de recherche. ITALIAN: La presente scheda d'istruzione è disponibile in varie lingue sul sito www.rockwellautomation.com/literature. Selezionare la lingua desiderata e digitare "SensaGuard" nel campo di ricerca. SPANISH: Puede encontrar esta hoja de instrucciones en varios idiomas en www.rockwellautomation.com/literature. Seleccione el idioma de publicación y escriba "SensaGuard" en el campo de búsqueda. PORTUGUESE: Esta folha de instruções está disponível em várias línguas em www.rockwellautomation.com/literature. Seleccione a língua de publicação e entre com "SensaGuard" no espaço de busca. POLISH: Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: www.rockwellautomation.com/literature Wybierz jezyk publikacji i wpisz w polu poszukiwania "SensaGuard". The presence of spare actuators compromise the integrity of the safety systems. Personal injury or death, property damage or economic loss can result. Appropriate management controls, working procedures and alternative protective measures should be introduced to control their use and availability. Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result. The sensor MUST be connected to a Class 2 SELV 24V DC, +10%/-15% power supply. Safety Classification Type 4 Interlocking Device per ISO 14119 (Low Coding) PLe, Cat 4 per ISO 13849-1 SIL CL3 per IEC 62061 and IEC 61508 Standards ISO 14119, IEC 60947-5-3, IEC 61508, IEC 62061, ISO 13849-1, UL508, CSA 22.2 No.14 Certifications TÜV, CE Marked for all applicable directives, cULus Functional Safety Data PFH D : 1.12 - 10 -9 ATTENTION WARNING Operating Characteristics Outputs (guard door closed, actuator in place) Environmental Sensing Distance 18 mm Actuator 30 mm Actuator Assured Make 15 mm 25 mm Assured OFF 25 mm 35 mm Typical Misalignment (±7 mm in both axes) Repeat Accuracy 10% of sensing range Max. output current (all outputs) 200 mA Input Current 50 mA (no load supply current) Operational Current, Min. 1 mA DC Off-state Current <0.5 mA DC Max. no. of switches, connected in series Unlimited. See Unit Response Time section on page 4. Operating Voltage 24V DC +10%/-15% Class 2 SELV power supply Frequency of operating cycle 1 Hz Response Time (Off) 54 ms first switch, 18 ms for each additional switch Case Material Polycarbonate Actuator Material Polycarbonate Outputs Description Status Safety 2 x PNP, 0.2 A max. ON (+24V DC) Auxiliary 1 x PNP, 0.2 A max. OFF (0V DC) Operating Temperature [C (F)] -10…+55 ° (14…131 °) Operating Humidity 5…95% relative Washdown Rating NEMA 3, 4X, 12, 13, IP69k Shock & Vibration IEC 68-2-27 30 g, 11 ms/IEC 68-2-6 10…55 Hz Radio Frequency IEC 61000-4-3 IEC 61000-4-6

Upload: vohanh

Post on 05-Nov-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

Installation InstructionsSensaGuard™ 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26*

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.

Installation InstructionsInstallation must be in accordance with the following steps and stated specifications and should be carried out by suitable competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted. Adherence to the recommended maintenance instructions forms part of the warranty.

This device is intended to be part of the safety related control system of a machine. Before installation, a risk assessment should be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications below for certification information and ratings.

Technical Specifications

ENGLISH: This instruction sheet is available in multiple languages at www.rockwellautomation.com/literature. Select publication language and type "SensaGuard" in the search field.

GERMAN: Dieses Instruktionsblatt kann in mehreren Sprachen unter www.rockwellautomation.com/literature gelesen werden. Bitte Ihre Sprache anwählen und "SensaGuard" im Suchfeld eintippen.

FRENCH: Ces instructions sont disponibles dans différentes langues à l'adresse suivante www.rockwellautomation.com/literature. Sélectionner la langue puis taper “SensaGuard” dans le champ de recherche.

ITALIAN: La presente scheda d'istruzione è disponibile in varie lingue sul sito www.rockwellautomation.com/literature. Selezionare la lingua desiderata e digitare "SensaGuard" nel campo di ricerca.

SPANISH: Puede encontrar esta hoja de instrucciones en varios idiomas en www.rockwellautomation.com/literature. Seleccione el idioma de publicación y escriba "SensaGuard" en el campo de búsqueda.

PORTUGUESE: Esta folha de instruções está disponível em várias línguas em www.rockwellautomation.com/literature. Seleccione a língua de publicação e entre com "SensaGuard" no espaço de busca.

POLISH: Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: www.rockwellautomation.com/literature Wybierz jezyk publikacji i wpisz w polu poszukiwania "SensaGuard".

The presence of spare actuators compromise the integrity of the safety systems. Personal injury or death, property damage or economic loss can result. Appropriate management controls, working procedures and alternative protective measures should be introduced to control their use and availability.

Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result. The sensor MUST be connected to a Class 2 SELV 24V DC, +10%/-15% power supply.

Safety ClassificationType 4 Interlocking Device per ISO 14119 (Low Coding)PLe, Cat 4 per ISO 13849-1SIL CL3 per IEC 62061 and IEC 61508

StandardsISO 14119, IEC 60947-5-3, IEC 61508, IEC 62061, ISO 13849-1, UL508, CSA 22.2 No.14

Certifications TÜV, CE Marked for all applicable directives, cULus

Functional Safety Data PFHD: 1.12 - 10-9

ATTENTION

WARNING

Operating Characteristics

Outputs(guard door closed, actuator in place)

Environmental

Sensing Distance 18 mm Actuator 30 mm Actuator

Assured Make 15 mm 25 mm

Assured OFF 25 mm 35 mm

Typical Misalignment (±7 mm in both axes)

Repeat Accuracy 10% of sensing range

Max. output current (all outputs) 200 mA

Input Current 50 mA (no load supply current)

Operational Current, Min. 1 mA DC

Off-state Current <0.5 mA DC

Max. no. of switches, connected in seriesUnlimited. See Unit Response Time section on page 4.

Operating Voltage24V DC +10%/-15%Class 2 SELV power supply

Frequency of operating cycle 1 Hz

Response Time (Off)54 ms first switch,18 ms for each additional switch

Case Material Polycarbonate

Actuator Material Polycarbonate

Outputs Description Status

Safety 2 x PNP, 0.2 A max. ON (+24V DC)

Auxiliary 1 x PNP, 0.2 A max. OFF (0V DC)

Operating Temperature [C (F)] -10…+55 ° (14…131 °)

Operating Humidity 5…95% relative

Washdown Rating NEMA 3, 4X, 12, 13, IP69k

Shock & VibrationIEC 68-2-27 30 g, 11 ms/IEC 68-2-610…55 Hz

Radio FrequencyIEC 61000-4-3IEC 61000-4-6

Page 2: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

Protection

Dimensions [mm (in.)]

Mode of Operation

Status indicators:

• “Power/Fault” LED illuminates green: Door/guard closed, safety outputs active.

• “Power/Fault” LED illuminates red: Door/guard open, safety outputs off.

• “Power/Fault” LED flashes red: Unit failure. See Diagnostic section on page 3.

• “Power/Fault” LED flashes green: Safety inputs off.

Short-circuit Incorporated

Current Limitation Incorporated

Overload Incorporated

False Pulse Incorporated

Transient Noise Incorporated

Reverse Polarity Incorporated

Overvoltage Incorporated

Thermal Shutdown/Restart Incorporated

Electrical Life 10 x 106

30 mm Actuator

48.92[1.926]

19.81[0.78]

22.22[0.875]

48.92[1.926]

19.81[0.78]

22.22[0.875]

30.40[1.197]

16.84[0.663]

3.17[0.125]

4.57[0.18]

2 places

Dia.

Sensor18 mm Actuator

67.06[2.640]2.03

[.080]

M18X1

36.47[1.436]

13.72[0.54] 15.87

[0.625]

36.47[1.436]

13.72[0.54]

15.87[0.625]

4.57[0.180] DIA

19.81[0.78]

3.17[0.125]

15.42[0.607]

2 PLACES

2

Mounting InformationUse non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over torque the mounting hardware.

Position the switch and actuator so they are aligned with each other.

Mount the switch and actuator to removable guard, door, or gate. Keep the switch and actuator within the sensing range below.

This switch is not meant to be fully embedded in metal. Use the stainless steel version (440N-Z21S17* or 440N-Z21U17*) for embedding.

Nut Torque Specification

Plastic Barrel Switch: 2.26 N•m (20 in•lb)Plastic Actuators: 2.26 N•m (20 in•lb)

Minimum Distance Between Sensors

Misalignment Curve

18 mm Unit with 18 mm Target

There must be a minimum spacing of 4 mm (0.157 in.) if actuator and sensor face approaches laterally. This will prevent false triggering due to the side lobe areas.

18 mm Actuator

75 mm

Sensor1

Sensor2

30 mm Actuator

100 mm

Sensor1

Sensor2

Lateral Misalignment Tolerance—mm (in)

Face

to Fa

ce D

istan

ce—

mm

-15(-0.59)

-10(-0.39)

-5(-0.19)

0 5(0.19)

10(0.39)

15(0.59)

0

5

10

15

20

25

-25(-0.98)

-20(-0.787)

20(0.787)

25(0.98)

Side Lobe Side Lobe

Assured SensingDistance

OFF OFF

ON

Assured SensingDistance

OFF

IMPORTANT

Page 3: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

18 mm Unit with 30 mm Target

Wiring Diagram

8-Pin Unit

Recommended mating cable, 2 m (6.5 ft)—889D-F8AB-2. Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

There must be a minimum spacing of 7 mm (0.275 in.) if actuator and sensor face approaches laterally. This will prevent false triggering due to the side lobe areas.

Pin Number Wire Color Signal

1 White Aux. Outputs

2 Brown +24V

3 Green NA

4 Yellow OSSD 2, +24V Input

5 Grey OSSD 1

6 Pink OSSD 2

7 Blue 0V

8 Red OSSD 1, +24V Input

0

5

10

15

20

25

30

35

-30(-1.18)

-20(-0.787)

-10(-0.39)

0 10(0.39)

20(0.787)

30(1.18)

Face

to Fa

ce D

istan

ce—

mm

Side Lobe Side Lobe

Assured SensingDistanceOFF OFF

ON

Lateral Misalignment Tolerance—mm (in)

Assured SensingDistance

OFF

IMPORTANT

47

68

1

5

23

Brown

White

Blue

Pink

Grey

Green

Red

Yellow

3

5-Pin Unit

Recommended cordset, 2m (6.5 ft) - 889D-F5AC-2. Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

Note: If the user does not require the auxiliary signal, a 4-pin cordset (889D-F4AC-2) can be used.

Recommended patchcord for use with ArmorBlock® Guard Safety I/O, 2 m (6.5 ft) - 889D-F4ACDM-2. Replace the 2 with 0M3 (0.3 m), 1 (1 m), 5 (5 m), or 10 (10 m) for standard cable lengths.

Note: Do not use a 5-pin patchcord with the ArmorBlock.

Diagnostic

Unit Indicators (per IEC 60073)

Pin Number Signal

1 +24V

2 OSSD 1

3 0V

4 OSSD 2

5 Aux.

Device Output

LED

State Status Troubleshooting

Off Not Powered NA

Red Not Safe, OSSD not active NA

Green Safe, OSSD active NA

Green Flash

Power up test or OSSD inputs not valid

Check 24V DC or OSSD inputs (yellow and red wire)

Red Flash

1 Hz Flash Recoverable Fault 4 Hz Flash Non-recoverable Fault

Recoverable fault —check OSSD outputs are not shorted to GND, 24V DC or each other.

Cycle power.

Refer to Technical Specifications (page 1) for certification information and ratings.

15

2

4

3

IMPORTANT

Page 4: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

TroubleshootingSeries Circuit

Unit Response Time (does not include safety control system response time)

Refer to Technical Specifications (page 1) for certification information and ratings.

Refer to Technical Specifications (page 1) for certification information and ratings.

Yel

Red

Brow

n

Gray

Pink

Blue

24VDCPowerSupply

1606-XL120D

Switch 1

+24

RTN

Switch 2

White

Whit

e

Yel

Red

Brow

n

Gray

Pink

Blue

Actuator 1 Actuator 2

Switch 3

Whit

e

Yel

Red

Brow

n

Gray

Pink

Blue

Actuator 3

Switch 4

Whit

e

Yel

Red

Brow

n

Gray

Pink

Blue

Actuator 4

Switch 5

Whit

e

Yel

Red

Brow

n

Gray

Pink

Blue

Actuator 5

+24 V+24 V

+24 V+24 V

+0 V+0 V

+0 V+0 V

+0 V+0 V

Actuator 2 is in sensing range.Switch 2 is functioning properlyOSSDs are energize to 24 VGreen LED is ON.

Actuator 3 is in sensing range.Switch 3 has fault.See Table Above—Red LED is flashing

Actuator 1 is in sensing range.Switch 1 is functioning properlyOSSDs are energize to 24 VGreen LED is ON.

Actuator 4 is in sensing range.Switch 4 is functioning properly.Series inputs are 0 V.OSSDs are de-energized to 0V .Green LED is Flashing to indicateSeries inputs are not 24V.

Actuator 5 is in sensing range.Switch 5 is functioning properl y .Series inputs are 0V.OSSDs are de-energized to 0V.Green LED is Flashing to indicateSeries inputs are not 24V.

OSSD’s are OFFRecoverable fault

IMPORTANT

YelRed

WhiteGrayPink

Blue

24V DCPowerSupply

1606

Sens

or 1

+24

RT

Sens

or 2

Brown Brown Gray

PinkWhite

YelRedBl

ue

Sens

or 3

Brown Yel

RedWhiteGrayPink

Blue

A1

S21

S11 41332313S12S52

42342414A2S34S22

MSR127TP

Actu

ator

1

Actu

ator

2

Actu

ator

3

Initial Conditions:All actuators are in sensing distance.

Actuator 1 is moved out ofsensing range.

Sensor 2 drops the 24 volts (red and yellow) from Sensor 1 OSSD outputs.Green LED flashes.

Sensor 3 drops the 24 volts (red and yellow) from Sensor 2 OSSD outputs.Green LED flashes.

0 ms 54 ms 72 ms 90 ms

Actuator 1 is out of sensing range.Actuator 2 and 3 are in sensing range.

Actuator 1 is moved into sensing range.Sensor 1 OSSD outputs are energized.

Sensor 2 OSSD inputs (red and yellow) transition to 24V DC from Sensor 1 OSSD outputs.Sensor 2 OSSD outputs are energized

Sensor 3 OSSD inputs (red and yellow) transition to 24V DC from Sensor 2 OSSD outputs.Sensor 3 OSSD outputs are energized.

0 ms 360 ms 378 ms 396 ms

OFF

ON

IMPORTANT

4

Page 5: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

Application Wiring Examples

Refer to Technical Specifications (page 1) for certification information and ratings.

K1

+24V DC

MSR127RP with 1 sensor, monitored manual reset, driving 100S or 700S safety controllers.

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

MSR127RP

Reset

GND

BlueG

rayPink

YellowRed

Brown

SensaGuardUnit 1

K2

+24V DC

GND

MSR127RP with 3 sensors in series, monitored manual reset, driving 100S or 700S safety controllers

BlueG

rayPinkYellowRed

Brown

SensaGuardUnit 1

SensaGuardUnit 2

SensaGuardUnit 3

K1

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

MSR127RP

Reset

K2BlueG

rayPinkYellowRed

Brown

BlueG

rayPink

YellowRedBrow

n

MSR127RP with 3 sensors and 1 440L light curtain in series, monitored manual reset, driving 100S or 700S safety relays.Note: Light curtain must be last (farthest from MSR127).

GND

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

MSR127RP

Reset

K1 K2

+24V DC

BlueG

rayPinkYellowRedBrow

n

SensaGuardUnit 1

SensaGuardUnit 2

SensaGuardUnit 3 GuardShield

BlueG

rayPinkYellowRedBrow

n

BlueG

rayPinkYellowRedBrow

n

BlueG

rayPink

Brown

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

MSR127TP

GND

MSR127RP with 1 sensor, automatic reset, driving 100S or 700S safety controllers

+24V DC

SensaGuardUnit 1

K1 K2

BlueG

rayPinkYellowRedBrow

n

MSR127TP with 3 sensors in series, automatic reset, driving 100S or 700S relays.

MSR127TP

+24V DC

GND

Blue

Gray

Pink

YellowRed

Brown

SensaGuardUnit 1

K1

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

K2

Blue

Gray

Pink

YellowRed

Brown

Blue

Gray

Pink

YellowRed

Brown

SensaGuardUnit 3

SensaGuardUnit 2

MSR127TP with 3 sensors and 1 440L light curtain in series, automatic reset, driving 100S or 700S safety contactors.Note: Light curtain must be last (farthest from MSR127)

MSR127TP

GND

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

K1 K2

+24V DC

Blue

Gray

Pink

YellowRed

Brown

Blue

Gray

Pink

YellowRed

Brown

Blue

Gray

Pink

YellowRed

Brown

Blue

Gray

Pink

Brown

GuardShieldSensaGuardUnit 1

SensaGuardUnit 3

SensaGuardUnit 2

IMPORTANT

5

Page 6: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

Application Wiring Examples

Refer to Technical Specifications (page 1) for certification information and ratings.

MSR200 series with 3 sensors and 1 440L light curtain, automatic reset, driving 100S or 700S safety contactors.Note: Light curtain can be attached to any input

GuardShield

+24V DC

GND

440R-H23177

Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

440R-H23179

K1

S32S20S12

S62S50S42

S32

S32

440R-H23180

MSR221P MSR211P MSR230P

K2K1

K2 K3

K4

SensaGuard

Blue

Brown

GrayPink

Blue

Brown

Yellow

Red

GrayPink

SensaGuard SensaGuard

GrayPink GrayPink

Blue

Brown

Yellow

Red

Blue

Brown

Yellow

Red

MSR200 series with 3 sensors and 1 440L light curtain, manual reset, driving 100S or 700S safety contactors.Note: Light curtain can be attached to any input.

Reset

GuardShield

+24V DC

GND

440R-H23177

Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

440R-H23179

K1

S32S20S12

S62S50S42

S32

S32

440R-H23180

MSR221P MSR211P MSR230P

K2K1

K2 K3

K4

SensaGuard

Blue

Brown

GrayPink

Blue

Brown

Yellow

Red

GrayPink

SensaGuard SensaGuard

GrayPink GrayPink

Blue

Brown

Yellow

Red

Blue

Brown

Yellow

Red

MSR200 series with 4 sensors, automatic reset, driving 100S or 700S safety contactors.

Yellow

Red

+24V DC

GND

440R-H23177

Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

440R-H23179

K1

S32S20S12

S62S50S42

S32

S32

440R-H23180

MSR221P MSR211P MSR230P

K2K1

K2 K3

K4

SensaGuardSensaGuard

Blue

Brown

GrayPink

Blue

Brown

Yellow

Red

GrayPink

SensaGuard SensaGuard

GrayPink GrayPink

Blue

Brown

Yellow

Red

Blue

Brown

Yellow

Red

MSR200 series with 4 sensors, manual reset, driving 100S or 700S safety contactors.

Reset

+24V DC

GND

440R-H23177

Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

440R-H23179

K1

S32S20S12

S62S50S42

S32

S32

440R-H23180

MSR221P MSR211P MSR230P

K2K1

K2 K3

K4

SensaGuardSensaGuard

Blue

Brown

GrayPink

Blue

Brown

Yellow

Red

Yellow

Red

GrayPink

SensaGuard SensaGuard

GrayPink GrayPink

Blue

Brown

Yellow

Red

Blue

Brown

Yellow

Red

IMPORTANT

6

Page 7: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

List of Recommended Safety Control InterfacesGSR DI, GSR DIS, GSR SI, CR30, MSR126, MSR127, MSR131, MSR138, MSR211, MSR221, MSR121, MSR320, SmartGuard™,1791DS/ES CompactBlock™ Guard Safety I/O, 1732DS/ES ArmorBlock Guard Safety I/O. Relay must have OSSD (light curtain) inputs.

Maintenance

Monthly

Check the correct operation of the switching circuit. Also check for signs of abuse or tampering. Inspect the switch casing for damage.

RepairIf there is any malfunction or damage, no attempts at repair should be made. The unit should be replaced before machine operation is allowed.

Declaration of ConformityThis is to declare that the products shown in this document conform with the Essential Health and Safety Requirements (EHSRs) of the European Machinery Directive. These products also conform to EN 60947-5-3, EN ISO 14119, and have Third Party Approval.

For a comprehensive certificate please visit: www.ab.com/safety.

Check the machine is isolated and stopped whenever the interlocked guard door is open.

IMPORTANT: Afterinstallation and commissioning, the actuator, switch and switch lid fixing screws should be coated with tamper evident varnish or similar compound.

7

Page 8: IMPORTANT: SAVE THESE INSTRUCTIONS FOR … Instructions SensaGuard 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation

o

Rockwell Automation maintains current product environmental information on its website athttp//www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/pr

Allen-Bradley, ArmorBlock, CompactBlock, Rockwell Software, SensaGuard, and SmartGuard are tradema

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 440N-IN010C-EN-P — September 2014 — 10000979Supersedes Publication 440N-IN010B-EN-P — August 2014

duct-environmental-compliance.page

rks of Rockwell Automation, Inc.

549 Ver 00 PN-243703Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.