U P S Uninterruptible Power System Line Interactive (Network) UPS 400VA/ 500VA/ 600VA/ 800VA USERS MANUAL1 Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. The unit is intended for installation in a controlled environment. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing battery, replace with the same number and type. CAUTION: Do not dispose of battery or batteries in a fire, the battery may explode. CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. CAUTION: A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries: Remove watches, rings or other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of batteries. Disconnect charging source prior to connecting or disconnecting battery terminals.

Upload: buidang

Post on 12-Apr-2019

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IMPORTANT SAFETY INSTRUCTIONS SAVE THESE … · Important Safety Instructions ... Novell Netware, ... th e UPS in to signal s w hich ind iv idua l ope ra ting system recog nize s

U P S

Uninterruptible Power System

Line Interactive (Network) UPS

400VA/ 500VA/ 600VA/ 800VA

■USER‘S MANUAL■

1

Important Safety Instructions

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.

The unit is intended for installation in a controlled environment.

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

When replacing battery, replace with the same number and type.

CAUTION: Do not dispose of battery or batteries in a fire, the battery may explode.

CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

CAUTION: A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries:

Remove watches, rings or other metal objects.

Use tools with insulated handles.

Wear rubber gloves and boots.

Do not lay tools or metal parts on top of batteries.

Disconnect charging source prior to connecting or disconnecting battery terminals.

Page 2: IMPORTANT SAFETY INSTRUCTIONS SAVE THESE … · Important Safety Instructions ... Novell Netware, ... th e UPS in to signal s w hich ind iv idua l ope ra ting system recog nize s

2

Table of contents IMPORTANT SAFETY INSTRUCTIONS..................................................................1 INTRODUCTION................................................................................................2 1. PRESENTATION............................................................................................2 2. INSTALLATION .............................................................................................3 3. OPERATION.................................................................................................4 4. ALARM .......................................................................................................5 5. SOFTWARE AND INTERFACE PORT(OPTION)..................................................5 APPENDIX A TROUBLESHOOTING.....................................................................6 APPENDIX B SPECIFICATIONS ..........................................................................7

Introduction Please read and save this manual !

Thank you for selecting this uninterruptible power system (UPS). It provides you with a perfect protection for connected equipment. The manual is a guide to install and use the UPS. It includes important safety instructions for operation and correct installation of the UPS. If you should have any problems with the UPS, please refer to this manual before calling customer service.

1. Presentation The UPS is a line interactive uninterruptible power system (UPS). When utility input is normal, the UPS would provide surge protection and energy to charge the internal battery. If the utility input is abnormal, the UPS can supply AC power to the load immediately.

(1). Utilizes microprocessor based controls, it will minimizes the dependency on hardware. Beside this, it maximizes system flexibility and optimizes the assurance of reliability. (2). Automatic frequency selection to match with utility power. (3). Hi level battery charger to prolong battery’s life and fully charge the battery. (4). With actual overload protection both in line and battery mode. 1.1 Front and rear view 1. 1) Power Switch

1.2) RS-232 or USB Port (option) 1.3) Phone Jack (option) 1.4) AC Input 1.5) UPS Outlets 1.6) AC Fuse/ Breaker 1.7) Convenience Outlet

1 . 1

3

For models with RS-232 port as communication port

For models with USB port as communication port

For models with USB plus RS-232 port as communication port (option)

2. Installation 2.1 Inspection Inspect the UPS upon receipt. The packaging is recyclable; save it for reuse or dispose of it properly. 2.2 Utility Power The input power cord on the rear panel needs to plug into a socket on the wall. Please notice the voltage of utility power should match with the UPS. (For example, the UPS is 220V, the input utility power should be 220V as well.) 2.3 Connection The employed equipment’s power cords (such as computer) are plugged into the sockets on the rear panel.

1.3

1.6

1.3 1.2

1.5 1.4

1.6

1.2

1.4 1.6

1.3 1.2

1.4

1.7

1.5

1.5

1.3

1.5

1.3 1.2

1.5 1.4

1.6

1.2

1.4 1.6

1.3

1.5

1.2

1.41.6

1.2 1.3

1.4 1.6

1.2

1.5

1.21.3

1.41.6

1.2

1.5

1.21.3

1.41.6

1.2

1.5

Page 3: IMPORTANT SAFETY INSTRUCTIONS SAVE THESE … · Important Safety Instructions ... Novell Netware, ... th e UPS in to signal s w hich ind iv idua l ope ra ting system recog nize s

4

3. Operation 3.1 Switch on with “Green Mode” Function under AC mode

When utility input is connected to the UPS, press “ON” button and keep pressing less than 3 sec to turn on the UPS. After that, connect the electrical cords of the equipments that will be used (such as desktop computer and CRT monitor) to the rear panel of UPS. In order to save the power, it will also automatically enable the “Green mode” - No Load (or Light load) shut-down function under backup mode (about 4 minutes later).

ATTENTION: At backup mode, UPS can be automatically turned off if none of the connected loads is operating. (Green mode; No Load shut down function) Once the utility power is normal again, the unit can be waked up by itself.

CAUTION: Never connect a laser printer or plotter to the UPS with other computer equipment. A laser printer or plotter periodically draws significantly more power than when its idle status, and may overload the UPS.

3.2 Switch on with “Disabled Green Mode” Function under AC mode When utility input is connected to the UPS, press “ON” button and keep pressing until the “Bi...Bi-Bi” beeps stopped to turn on the UPS. After that, connect the electrical cords of the equipments that will be used (such as Notebook computer and LCD monitor) to the rear panel of UPS. If the load is lighter than 15W, please also refer this function to avoid any inconvenience cause by “Green Mode” function.

3.3 DC Start with “Green Mode” Function If the power of UPS isn't supplied by utility but by the internal batteries to engage the UPS, press the power button and keep pressing less then 3 seconds.

3.4 DC Start with “Disabled Green Mode” Function If the power of UPS isn't supplied by utility but by the internal batteries to engage the UPS, press the power button and keep pressing until the sounds of “Bi Bi-Bi”.

3.5 Switch off Press the power switch and keep pressing more than 3 seconds to turn off the UPS.

3.6 Silence When UPS is under “BACKUP” mode, press power switch more than 1 second to silence the audible alarm. (The function is disable when UPS is under condition of “LOW BATTERY” or “OVERLOAD”) 3.7 Self test function Press power switch while utility power is connected, UPS will perform self-test procedure automatically.

5

4. Alarm 4.1 “BACKUP” (slow alarm) When the UPS is working under “BACKUP” mode, the UPS would emit audible alarm. The alarm stops when the UPS is return to “LINE” mode operation. ATTENTION: The alarm of “BACKUP” is going to beep every 2 seconds. (Slow-speed beep). ATTENTION: The UPS provides mute function for the warning. When the beeping sound occurs, press "ON" to stop it; and press "ON" again to regain the sound.

4.2 “LOW BATTERY” (rapid alarm) In the “BACKUP” mode, when the energy of battery becomes to lower level. (about 20%~30%) The UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to “LINE” mode operation.

ATTENTION: The alarm of the batteries caused by low voltage beeps every 0.5 second.

ATTENTION: The rapid alarm under “LOW BATTERY” condition cannot be muted.

4.3 “OVER LOAD” (continuous alarm) When the UPS is working under overload condition (the connected loads exceed the maximum rated capacity), the UPS will emit continuous alarm to warn an overload condition. In order to protect the unit and the loads, the UPS will be automatically turn off. Please disconnect nonessential devices from UPS to eliminate the overload alarm.

5. Software and Interface Port (Option) 5.1 Power Monitoring Software The UPSMON series software (or the other power monitoring software) is applied standard RS-232 or USB interface to perform monitoring functions. It certainly provides graceful shutdown of computer in the event of power failure. Moreover, it simultaneously monitors the UPS and displays all the diagnostic symptoms on the monitor such as voltage, frequency and battery level and so on. For UPS with RS-232 communication port, the software is compatible with Windows 95/ NT4.0/ 98/ ME/ 2000 / XP/ 2003 Server, Novell Netware, Linux, and others. For UPS with USB communication port, the software is compatible with Windows 98SE/ ME/ 2000/ XP/ 2003 Server. Call your dealer for more information about the solutions of others operating system.

Page 4: IMPORTANT SAFETY INSTRUCTIONS SAVE THESE … · Important Safety Instructions ... Novell Netware, ... th e UPS in to signal s w hich ind iv idua l ope ra ting system recog nize s

6

stiK ecafretnI 2.5 .gnirotinom SPU edivorp taht smetsys noitarepo rof elbaliava si stik ecafretni fo seires A

ecafretni laiceps eht sedulcni tik ecafretni hcaE morf slangis sutats trevnoc ot deriuqer elbac gnitarepo laudividni hcihw slangis otni SPU eht ta elbac ecafretni ehT .sezingocer metsys

ta ,TROP ETOMER ot detcennoc eb tsum edis SPU trop seires rehtie eb nac edis retupmoc itcurtsni noitallatsni rehto ehT .trop BSU ro ot refer esaelp serutaef lufrewop dna sno

.elif EM.DAER

trop ecafretni retupmoc fo scitsiretcarahc ehT 3.5 :scitsiretcarahc gniwollof eht sah trop ecafretni retupmoc ehT

SPU eht fo kcab eht no trop noitacinummoc ehT sihT .retupmoc tsoh ot detcennoc eb yamsutats eht rotinom ot retupmoc eht swolla trop eht fo noitarepo eht lortnoc dna SPU eht fo

yllamron snoitcnuf rojam stI .sesac emos ni SPU :gniwollof eht fo lla ro emos edulcni .sliaf rewop nehw egassem gninraw a pu-pop oT

erofeb selif denepo pu kcab oT .nwodtuhs metsys gnitarepo .SPU eht ffo nrut oT

c laiceps a htiw deppiuqe era sretupmoc emoS .trop noitacinummoc eht htiw knil ot rotcennon eb yam droc ni-gulp laiceps ,noitidda nI SPU laiceps deen yam sretupmoc emoS .dedee

of relaed ruoy tcatnoC .erawtfos gnirotinom .stiK ecafretni suoirav eht no sliated eht r

:NOITNETTA ledom rof elbaliava tsuj noitcnuf trop ecafretni dna erawtfos NOMSPUc 232-SR dradnats ehT .xiffa ”P“ htiw eman trop noitacinummoc no dneped( BSU ro elba

eht rof trop MOC retupmoc dna TROP ETOMER SPU neewteb detcennoc eb nac )SPU no.erawtfos seires NOMSPU

gnitoohselbuorT A xidneppA

EKAT OT NOITCA ESUAC ELBISSOP MELBORP ro dehsup ton hctiws rewoP

trohs oot emit-hsup 1 naht erom hctiws rewop eht sserP

dnoces

sruoh 42 tsael ta SPU eht egrahceR V01 naht ssel egatlov yrettaB

ecivres rof llaC eruliaf BCP

no nrut ton nac SPU thgil ton DEL

yrettab ta W03 naht ssel daoLedom

nwodtuhs daol oN“ ,noitidnoc lamroN )2.3 eeS( evitca si ”noitcnuf

droc rewop eht ni gulP esol droc rewoP esuf CA eht ecalpeR tuo nrub esuf CA

wol oot ,hgih oot egatlov eniL tuo kcalb ro

noitidnoc lamroN yrettab ta syawla SPU

edom

ecivres rof llaC eruliaf BCP sruoh 6 tsael ta SPU eht egrahceR degrahc ylluf ton si yrettaB

trohs oot emit pu kcaB ecivres rof llac ,BCP ecalpeR eruliaf BCP

suounitnoc rezzuBgnipeeb

sdaol emos evomeR daolrevO

7

snoitacificepS B xidneppA PA/A008 PA/A006PA/A005PA004A004ledoM

AV008 AV006 AV005 AV004 AV004 yticapaC tupni enil ta %52-/+ ,V042 ,V032 ,V022 / V021 ,V511,V011 egatloVtupnI

)gnisnes otua( %01 -/+ zH06 ro 05 ycneuqerF pukcaB( egatloV

)edom ,V032 ,V022 / V021 ,V511 ,V011 ,V001 ta evaw enis detalumiS

%5 -/+ V042 ycneuqerF

)edoM pukcaB( zH1 -/+ zH06 ro 05

egatloV otuA)RVA( noitalugeR

tupni evoba %51 egatlov tuptuo esaercni yllacitamotua RVA tuptuo esaerced RVA .lanimon fo %52-ot %9- fi egatlov

lanimon fo %52+ ot %9+fi egatlov tupni woleb %31 egatlov

tuptuO

)lacipyT( sdnocesillim 4emiT refsnarT 460Joules (2X0 V) / 265Joules (1X0 V) 8/20usnoitcetorP ekipS

of rekaerb tiucric ro esuF tupnI tinU ic trohs & daolrevo r noitcetorp tiucrdaolrevOnoitcetorP

lanimon fo %011 sdeecxe daolrevo fi ffo rewop citamotua SPU s3 ta %031 dna s06 ta

elbaC T-esaB 01troP SEY/lanoitpO SEYlanoitpO

noitcetorPgniretliF dna

mmi ffo tuc tuptuo SPU tiucriC trohS noitcetorp esuf tupni ro yletaide

epyT sraey 6-3 htiw seirettab dica dael eerf-ecnanetniam ,delaeS emitefil lacipyt

egrahceR lacipyT emiT )yticapac lluf fo %09 ot( sruoh 6

noitcetorp egrahcsid otuA noitcetorP yrettaB

CP( emiT pu kcaB DCL ”51 htiw

)rotinom≒ nim 51 ≒ nim 02 ≒ nim 02 ≒ nim 02 ≒ nim 52

gK thgieW teN )sbl( )3.21(6.5)2.9(2.4 /)2.31(0.6

)9.31(3.6 /)7.31(2.6 )3.41(5.6

/)9.31(3.6 )7.41(7.6

thgieW gnippihS )sbl( gK )2.31(0.6)1.01(6.4 /)3.41(5.6

)0.51(8.6 /)8.41(7.6 )4.51(0.7

/)0.51(8.6 )9.51(2.7

)mm( noisnemiD H x D x W

x 062 x 79 x ”8.3( 531)”3.5 x ”2.01

)”3.5 x ”5.21 x ”8.3( 531 x 023 x 79

telni rewop 023 CEI telnI tupnI

lacisyhP

CEI ,)V0x1( R51-5AMEN selcatpeceR )V0x2( relpuoc ecnailppa elamef 023 )zH74.0 tuoba( dnuos gnipeeb wolSpU-kcaB yrettaB )zH428.1 tuoba( dnuos gnipeeb dipaR woL yrettaBmralA

dnuos gnipeeb ylsuounitnoC daolrevO SEY/ON SEY ON BSU/232-SR ecafretnI

tneibmA noitarepO

,gnisnednoc-non ytidimuh %59-0 ,noitavele .xam sretem 005,304-0 ℃

)ecafrus morf retem 1(ABd04<esioN elbiduAtnemnorivnE

.xam sretem 000,51noitidnoC egarotS

Page 5: IMPORTANT SAFETY INSTRUCTIONS SAVE THESE … · Important Safety Instructions ... Novell Netware, ... th e UPS in to signal s w hich ind iv idua l ope ra ting system recog nize s