IEC 61850 GOOSE IEC 61850 GOOSE MessageMessage

Configuration by DummyConfiguration by Dummy

Mohd Noorfazly NoranMohd Noorfazly Noran

Utility AutomationUtility Automation

TNB ResearchTNB Research

Page 2: IEC 61850 GOOSE Message_ver 3

What is IEC 61850 GOOSE Message? GOOSE is a peer-to-peer communication between IEDs in the

substation network The GOOSE message is repetitive transmission of the data

(tripping, analog value, interlocking, alarm, status etc.) The GOOSE message type can convey data attributes organized in

a dataset

Page 3: IEC 61850 GOOSE Message_ver 3

Why to use GOOSE?Why to use GOOSE?

Fast Fast system/network wide distribution of system/network wide distribution of input and output data valuesinput and output data values

Publisher and subscriber mechanism – Publisher and subscriber mechanism – less less complexitycomplexity

Multicast/broadcast services supports Multicast/broadcast services supports simultaneous delivery of data to multiple simultaneous delivery of data to multiple physical devices using same network – physical devices using same network – less less wiringwiring

Page 4: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Model and Mapping

IEC 61850 GOOSE Data Model

IEC 61850 GOOSE Communication Service

Mapping

Page 5: IEC 61850 GOOSE Message_ver 3

IED B SubscriberIEDB_SYSTEM

IED A Publisher

IEC 61850 GOOSE Message Information Model

IEDA_PROT

PDIF

IEDA_PROT/PDIF.Str.general[ST]

Dataset

LLN0

GoCB LLN0

general

Str

PDIS

general

Str

PTOC

stVal

Ind

GGIO

Str

general

IEDA_PROT/PDIS.Str.general[ST]

IEDA_PROT/PTOC.Str.general[ST]

IEDA_PROT/GGIO.Ind.stVal[ST]

Page 6: IEC 61850 GOOSE Message_ver 3
Page 7: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message IEC 61850 GOOSE Message Configuration (Publisher)Configuration (Publisher)

Dataset1

Data Attribute 1 [FC]Data Attribute 2 [FC]Data Attribute 3 [FC]

Data Attribute n [FC]

GOOSE Control Block

Communication Parameter

Data Attribute 4 [FC]

Constructed from multiple LNs Data Attribute which assigned with Functional

Constraint (FC)

The LNs with the Data

Attribute are grouped

together to create dataset

• GOOSE Control Block can be assigned for one dataset

• The parameter:• GoCB Name• GoID/AppID

• Subnet configuration process

• Subnet parameter:1. MAC Address2. APPID3. VLAN ID4. VLAN Priority

Page 8: IEC 61850 GOOSE Message_ver 3

Hierarchy of the IEC 61850 GOOSE Message Dataset

ExxFxx

LLN0

Logical Node

ExxFxx/LLN0.DSName

ExxFxx/PTOC.Op.stVal [ST]

ExxFxx/PDIS.Op.stVal[ST]

ExxFxx/GGIO.Ind.stVal [ST]

Dataset Member

Dataset

LNType

Logical Device

The Dataset allows the receiver to understand what data information being sent in a GOOSE

Page 9: IEC 61850 GOOSE Message_ver 3

Hierarchy of the IEC 61850 GOOSE Message Control Block

ExxFxx

LLN0

Logical Node

ExxFxx/LLN0.GoCBName1

Dataset

LNType

Logical Device

GOOSE Control Block

ExxFxx/LLN0.GoCBName2

ExxFxx/LLN0.DSName1

ExxFxx/LLN0.DSName1

ExxFxx/LLN0.GoCBNameN

ExxFxx/LLN0.DSName1

The GOOSE Control Block is unique to the system. A single Dataset can be used by multiple control blocks

Page 10: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Parameter Mapping

Component Name

Description Format Recommendation

DatSet Dataset name FCD/FCDA FCDA

GoID/AppID GOOSE Identifier Character The name shall represent the signal of the GOOSE message

GoCB GOOSE Control Block name Character

confV Configuration revision Number The number shall be updated by:10000 times if using configuration tool1 by online modification/configuration

*FCDA: Functional Constraint Data Attribute

*FCD: Functional Constraint Data

Page 11: IEC 61850 GOOSE Message_ver 3

FCDA and FCD FCDA:

a single data attribute, a sub data object or sub data attribute of a data object having a specific functional constraint (FC) value

Object reference:E01F11LP1/GGIO.Ind.stVal [ST]

FCD: The reference to an ordered collection of data

attributes of a data object having the same functional constraint (FC) value

Example:E01F34LC/MMXU.A [MX]

Page 12: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Parameter Mapping Data set:

a group of data attributes with specific functional constrain

Each of data attributes is called Member of the dataset

It can be:1. Configurable

2. Dynamic

3. Fix

A dataset can be assigned to multiple GoCB

Page 13: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Addressing Parameter

Parameter Name Description Format Recommendation

MAC Address Destination Media Access Control Address

01-0C-CD-01-XX-XX16

XX-XX: From 00-0016 to 01-FF16

The last two bytes should have the same value with the APPID and VLAN ID

APPID Application Identifier 000016 to FFFF16 Should have same value with the last two bytes of MAC Address

VLAN-ID VLAN Identifier 00016 to FFF16 Should have same value with the last two bytes of MAC Address

VLAN-PRIORITY VLAN User Priority 0 to 7 Default value: 4

Page 14: IEC 61850 GOOSE Message_ver 3

IEC 61850-8-1 Destination Mac Address

Page 15: IEC 61850 GOOSE Message_ver 3

GOOSE Parameters – APPIDGOOSE Parameters – APPID

GOOSE Type 1 Reserved Value Range : 0x0000 to 0x3FFF

GOOSE Type 1A (Trip) Reserved Value Range : 0x8000 to 0xBFFF

Page 16: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Retransmission

Page 17: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Application

Page 18: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Application for Breaker Failure Initiation

Breaker Failure Initiation by Main Protection-using

hardwire connection

Conventional Breaker Failure Protection Scheme

Page 19: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Application for Breaker Failure Initiation

Binary Input from the Main Protection signal- 4 copper wires

Conventional Breaker Failure Protection Scheme

Page 20: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Application for Breaker Failure Initiation

Main1-87L50BFMain protection R,Y

and B Operating signal

Main protection 3 phase operating signal

Page 21: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message Application for Breaker Failure Initiation

F11LP1PDIF F50RBRF

F11LP1Prot.87L1PDIF1.Str.phsA [ST] (Red)F11LP1Prot.87L1PDIF1.Str.phsB [ST] (Yellow)F11LP1Prot.87L1PDIF1.Str.phsC [ST] (Blue)F11LP1Prot.87L1PDIF1.Str.general[ST] (3-phase)

GOOSE 1

Page 22: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message MappingF11LP1

Logical Device: Protection

87L1PDIF1

Str

phsA [ST]

Logical Device: System

87L1LLN0

phsB [ST]

phsC [ST]

general [ST]

Datset1

87L1PDIF1.Str.phsA [ST]

87L1PDIF1.Str.phsB [ST]

87L1PDIF1.Str.phsC [ST]

87L1PDIF1.Str.general [ST]

GoCB1

Datset1

Op

Communication

GSE:

• LD Instant: F11LP1System• GoCB: GoCB1

Address:

• VLAN-ID: 00016 to FFF16

• VLAN Priority: 0-8 (Default: 4)

• MAC Address: 01-0C-CD-01-01-AA

• APPID: 01AA16

T Max (TimeAllowedToLive):T Min:

phsA [ST]

phsB [ST]

phsC [ST]

general [ST]

Appid: CurrentDiffStartConfRev: 1GoCB Name: GoCB1

Page 23: IEC 61850 GOOSE Message_ver 3

IEC 61850 GOOSE Message-Conclusion

GOOSE messages are one of the key differentiators of IEC 61850

Client –Server communications are not suitable for protection applications

Peer-to-Peer communications can meet the protection performance requirements

Successful implementation of GOOSE based protection systems requires not only good understanding of the basics, but also planning and motivation