hrb 4 electrical 2012 8.5x10.875 - carson dunlop
TRANSCRIPT
Electrical
ELECTRICAL
The home RefeRence Book ©
eLecTRIcAL
146
Electricity has become an important element of every North American home. It provides lighting, heating and power for electric motors and electronics such as controls and computers. Our homes would not be nearly as comfortable or as convenient without electricity.
On the other hand, electricity is dangerous. It has to be installed and used properly to be safe. Electricity is tricky because it is invisible, it is complicated and it can kill.
InTRoduCTIon
1.0TheBasics
dESCRIPTIon Electricitycanprovideuswithheat,lightandpowerasinvisibleelectronsmoveinacircuitthrough wires and appliances. We can control whether it gives off mostly light or mostlyheatbyusinglightbulbsorelectricheaters.Electricitycanalsodriveelectricmotorswithfastchangingmagneticfields.
Wheredoeselectricitycomefrom?
Electricity is provided by utilities. It can be generated by moving water (e.g. Niagara Fallsgenerates hydroelectric power) burning fossil fuels like coal or from nuclear reactions, forexample.Aswelookformoreenvironmentallysensitivewaystogenerateelectricity,solar,windandgeothermalpowersourcesarebecomingmorecommon.Batteriesmaybeusedtostoreanddeliverpower.
Electricity is distributed through communities by a grid of overhead and/or undergroundwires. Electricity can be alternating current or direct current. Our discussion will focus onalternatingcurrent,sincethat’swhatwefindinhomes.
Let’sstartwithabriefdescriptionoffourcommonelectricalterms:V=Voltage,measuredinvolts.Thisrepresentstheelectricalforcethatisavailable.I=Current,measuredinamps(amperes).Thisrepresentstheamountofelectricityflowing.R=Resistance,measuredinohms.Thisisameasureoftheoppositiontoelectricalflow.P=Power,measured inwatts (1kilowatt is 1000watts).This representstherateatwhich
workisdone.
Thetablebelowshowstherelationshipbetweenthesefourterms.
Table1–ElectricalBasics
V=Voltage(volts) P=Power(watts) I=Current(amps) R=Resistance(ohms)
Formulas: V=IR P=VI
147
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
1.1Voltage
dESCRIPTIon Electricityflowsbecausethereisapressure(volts)beingappliedtoacircuit,suppliedfromthelocalutility.Utilitiesprovide240voltstohomes,intwo120-voltbundles.
1.2Current
dESCRIPTIon Theelectriccurrent inacircuit,measuredinamps(oramperes),istherateofflowofelectricitythat results when a light bulb,heater or appliance is turnedon. The amount of current is aresult of the amount of pres-sure (volts) and the resistanceto flow (ohms). The larger thepressure, the greater the flow.The larger the resistance, thesmallertheflow.
ConTRoLLIngThE Two dangerous things can goFLoW wrongwiththeflowofelectricity:
1. Too much flow results inoverheating and possiblyafire.Wecangettoomuchelectricityflowing iftoomanyappliancesareplugged intoonecircuit.Thereareotherwaystoomuchelectricitycanflow,butlet’sleaveitatthat.Ifeverything works properly, fuses and circuit breakers turn the electricity off when toomuchelectricityflows.
2. Electricitymayflowwhereitisnotsupposedto.Thisiswherepeoplegetelectricalshocks.Ithappenswhenyoudropthehairdryerorradiointothebathtub,youstickakeyintoanelectricaloutlet,oryoudriveanailintoaliveelectricalwire,forexample.Aflowoflessthanoneampcankillyou.
1.3Resistance
dESCRIPTIon Resistance,measuredinohms,preventselectricityfromflowing.Weuseresistancetocon-trolwhetherelectricityflows,andifso,howmuch.Thingsthatslowdownorresistelectricalflowarecalledresistorsor insulators.Thingsthatallowelectricitytofloweasilyarecalledconductors.
ConduCToRS Goodelectricalconductorshaverelativelylowresistance.Conductorsareusefulformovingelectricityfromoneplacetoanother.Mostmetalsincludingcopperandaluminumwiringaregoodconductors.Aluminumisnotquiteasgoodascopper,butislessexpensive.Waterisaverygoodconductor,whichiswhyit’sdangerous.Whenelectricitycontactswater,itoftenflowswhereitshouldn’t.Thehumanbodyisaprettygoodconductor,whichisunfortunateforus.
The home RefeRence Book ©
eLecTRIcAL
148
InSuLAToRShAVE Whenwedon’twantelectricitytoflow,weusethingswithlotsofresistance.ThesethingshIghRESISTAnCE arecalledinsulators.Air,glass,wood,rubberandmostplasticsaregoodinsulators.Homes
usecopperwire(aconductor)tomoveelectricityaround.Wewrapthewireinaplasticinsula-tor,sotheelectricitystayswithinthewire,makingitsafetotouch.
1.4Power
dESCRIPTIon Powerismeasuredinwattsorkilowatts(1000watts),andiscalculatedbymultiplyingthevoltage(volts)timesthecurrent(amps).Ahousewitha240-voltpowersupplyand100ampmain fuses has 24,000 watts. This is commonly referred to as 24 kilowatts (because onekilowattis1000watts).A1200-watthairdryerpluggedintoa120-voltcircuitwillresultina10-ampelectricalcurrentflow.
kILoWATT-houRS 1kilowatt(kW)is1000watts(W).Electricalconsumptioninyourhomeismeasuredinkilowatt-hours(kWh).Ifyouuse1000watts(1kilowatt)foronehour,youconsumeonekilowatt-hour(kWh).This ishowwebuyelectricity fromtheutility.Theelectricmeter recordskilowatt-hoursusedinthehouse.IfeachkWhcoststencentsandweuse500kWhinamonth,ourelectricalbillforthatmonthis$50.
nExTSTEPS Let’shaveaquicklookatwiresize,fusesandcircuitbreakersbeforewestarttolookatthehousesysteminmoredetail.
1.5WireSize(gauge)
dESCRIPTIon We use wires to move electricity around the house because wires are good conductors.The amount of current (amps) a wire can safely carry is determined largely by itsdiameter. A larger wire cancarry more current. Typicalhouseholdcircuitsaredesignedto carry 15 amps, and 14-gaugecopper wire will do this safely.Theillustrationshowscommonwiresizesandthetypicalsizeoffuse or breaker that is used toprotectthem.Aluminumisnotasgoodaconductorofelectric-ity, and a larger wire has to beusedtocarrythesameamountofelectricityascopper.It’sveryconfusing,becauselargerwireshave a smaller number gauge.Wethinkelectriciansdothistomakeithardforus.
149
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
1.6BreakersandFuses
dESCRIPTIon Whentoomuchelectricityflows,thingscanoverheatandwemighthaveafire.Fusesandcircuitbreakersturnofftheelectricitywhenthereistoomuchflow.Theyarethelifeguardsoftheelectricalsystem.Let’slookatanormalhouseholdcircuit.
A 14-gauge wire with 120-voltpressurecansafelycarryabout15 amps before things get toohot.Weputafuseorbreakeratthe beginning of the circuit toshutthecircuitoffifmorethan15 amps flow. A 1200-watt hairdryerwillcauseabout10ampstoflow. Ifwepluga1200-wattcurling iron into the same cir-cuit,another10ampswillflow.Nowwehave20ampsflowingandthewireisgoingtogettoohot. That’s when the circuitbreaker should trip or the fuseshould blow. Losing power is anuisance,butitpreventsafire.
oVERCuRREnT Thefancynameforcircuitbreakersandfusesisovercurrentprotectiondevices.BothfusesPRoTECTIon andbreakersperformthefunctionequallywell.Acircuitbreakercanbeturnedbackonlike
dEVICES aswitchaftertheoverloadsituationiscorrected.Afuse‘blows’andhastobereplaced.Mostmodernelectricalworkinhomesusescircuitbreakers.
nExTSTEPS Fortherestofthissection,we’lllookatelectricityinthehome.We’llstartwithhowelectricitygetsintothehouseandspendsometimeonthepanelbeforelookingatthewirecarryingelectricitythroughthehouse.We’llfinishwiththeswitches,lightfixtures,junctionboxesandelectricalreceptaclesattheendofthecircuit.
Somepeoplethinkofelectricityasatree.Thetrunkisthebundleofelectricitycomingintothehousefromtheutility.Thetrunkissplitintobranchesatthepanel.Youcanthinkofeachcircuitinthehomeasatreebranch.Eachcircuittypicallyhassomelights,switchesandrecep-tacles.Youcanthinkoftheseasthetwigsoneachbranch.
The home RefeRence Book ©
eLecTRIcAL
150
2.0ServiceEntrance
2.1ServicedropandLaterals:gettingElectricitytothehouse
dESCRIPTIon– Atypicalhousehas240-volts,broughtinthroughoverhead(servicedrop)orundergroundSERVICEdRoP wires (service laterals) fromtheutility.Thereare threewires.The liveblackandredwires
AndSERVICE eachbring120voltstothehome,andthewhitewireisneutral.ItdoesnotbringanyvoltageLATERALS tothehome,butcompletesthecircuit.
Thesewiresmaybecopperoraluminum.Thepotentialbetweentheblackandwhitewiresis120volts,betweentheredandwhiteis120volts,andbetweentheblackandredis240volts.(Incidentally,the“red”wireoftenhasblacksheathing,justtomakethingsconfusing).Thesizeoftheserviceentrancecabledetermineshowmuchelectricityisavailabletothehouse.
Theservicedropandservicelateralsaretypicallytheresponsibilityoftheutility.Everythingbeyond this point is the responsibility of the homeowner. Service drops connect to theservice entrance conductors, which are typically in conduit running down the outside ofthebuilding.
Undergroundservicewires(laterals)areinconduit,typicallyburiedtwotothreefeetdeep.Theconduitcomesuptotheelectricmeterontheoutsideofthebuilding.Fromtheelectricmeter,theconduitgoesintothebuilding.
Overheadservicedropsmaybeattachedtothesideofthebuilding,andcomedowntotheelectricmeterinaconduit(orcable),againalongtheoutsideofthebuilding.Onshorterbuild-ings,theysometimescomeinabovetherooflineandenteranelectricalmastthatsticksupabovetheroof.Thewiresgointothemast,whichformsaconduit,againrunningdowntheoutsideofthebuilding.
151
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
120-VoLTAnd Typicalhouseholdcircuitsare120-volt.Some120-voltcircuitsuseablackwireandwhitewire. 240-VoLT Theothersusearedwireandawhitewire.Largeappliancesthatneedlotsofelectricity,like CIRCuITS stoves,clothesdryers,waterheatersandairconditioners,use240-voltcircuits.Theyusea
blackwire,aredwireandawhitewire,typically.
SERVICESIzE Thesizeoftheelectricalservicetothehouse(100amps,200amps,etc.)isdeterminedbythesizeofthewirescomingtothehouse.We’lltalkmoreaboutthisshortly.
CommonProblemswithServiceDropsandServiceLaterals
Whatcangowrongaswebringelectricitytothehouse?Therearethreecommonproblems–damage,improperlocation,andmoistureproblems.Wewillfocusontheoverheadwires,becausethere’snotmuchwecanseeofundergroundwiringcomingintothehouse.Remem-ber,problemswiththeservicedropareusuallytheresponsibilityoftheutility.
dAmAgEdWIRE Wirecanbedamagedbytreebranchesormaydeteriorateduetoweathering.Wheredamagesuchasfrayedinsulationisnoted,theutility(electriccompany)shouldbenotified.
CLEARAnCE Wiresthataretoolowcanbehitbyvehicles.Youdon’twantyourmovingtrucktakingoutyour electrical service before you move into the house. Overhead wires should be about12feetabovegroundlevel.Wedon’twantpeopleleaningoutwindowsorstandingondeckstobeabletotouchtheseoverheadwires.Wiresshouldbekeptatleastthreefeetawayfromwindows, and roughly ten feet above decks. Again, where clearance is not adequate, theutilityshouldbenotified.
WATER Waterontheoverheadwiresisnotaproblem.However,oncethewatergetsintotheconduitthatgoesintothehome,itisaproblem.
PooR Theservicedropwiresmaynotbewell-connectedtotheserviceentranceconductors.This ConnECTIonTo caninterferewiththehouseelectricalserviceandcreateadangeroussituation. SERVICE EnTRAnCE ConduCToRS
2.2ServiceEntranceConductors
dESCRIPTIon Theoverheadservicedropistypicallytheresponsibilityoftheutility.Thesewiresconnecttotheserviceentranceconductors,whicharetheresponsibilityofthehomeowner.Thishand-offpointfromtheutilitywirestothehomeownerwiresissometimescalledtheservicepoint.Theserviceentranceconductorsaretypicallyinametalorplasticconduitthatrunsdowntheoutsideofthehouse.Theconduitprotectsthewiresfrommechanicaldamageandmoisture.Somehomeshaveaserviceentrancecableratherthanaconduit.
dRIPLooP Adriplooppreventswaterenteringtheserviceconduit.Theservicewiresformaloopbelowtheservicehead,whichallowswatertodripoffthewire.Thatkeepsthewateroutoftheconduit.
The home RefeRence Book ©
eLecTRIcAL
152
ConnECTIonTo Remembertheservicedrophastobeatleast12feetabovetheground.Ontallbuildings,theBuILdIng serviceisconnectedtothesideofthebuilding.Theserviceentranceconductorsformadrip
loopandthenenteraconduitthatrunsdownthesideofthebuilding.Onshorterbuildings,thedrip loopattachestoaser-vicemast(conduit)thatextendsabove the roof and carries theservice entrance conductorsdown along the outside of thebuilding.
mETERS The service conduit carries theservice entrance conductorsthrough the electric meter sowe can pay for our electricity.Metersaretypicallyontheout-side of the home close to thefrontofthebuildingtofacilitatemeter reading by a utility rep-resentative. Modern systemsare eliminating the need for ahumanmeterreader.
InSIdEBuILdIng Onceinsidethebuilding,theconduitmustbekeptasshortaspossible,ideallygoingstraightintothebox.Thisavoidsexposingtheconduittomechanicaldamage.
CommonProblemswiththeServiceEntranceConductors
dRIPLooP Sometimesthedrip loop ismissingordoesnotcreatea lowspotforwatertorunoff themISSIng/ service entrance wires. This results in water getting into the conduit, which can run into
InEFFECTIVE theserviceboxorpanelinsidethehouse,causingrustandpoorelectricalconnections.
SERVICECAPnoT The service entrance conductors have to enter the conduit through a weather-tight cap.WATERPRooF Watercancauserustandpoorconnections.Wherethereisevidenceofwaterpenetration,
repairsshouldbemade.
mASTdAmAgEd/ Theservicemastabovetheroofhastobewellsecuredandfreefromrustorrot.WeaknessesTooShoRT/PooR hereshouldbecorrectedpromptlytomaintaintheintegrityoftheelectricalservicedropand
LoCATIon serviceconductors.Themastshouldbetallenough(atleastthreefeettypically)tokeepthewiresclearoftheroof,sotheywillnotinterferewithre-roofingormaintenanceactivities.Wealsotrytoavoidhavingoverheadwiresrunningacrossroofs.Wedon’twantsomeoneupontheroofcleaningtheguttersorrepairingaleaktotouchthesewires.
153
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
PooRFLAShIng Wherethemastpenetratestheroofsurface,theopeningshouldbeprotectedwithaflashing ATRooF thatpreventswatergettingintotheroofstructure.Wherethisisnoteffective,theremaybe
waterdamagetothebuilding.
dAmAgEd/ Theconduitshouldbeintactandwellsecuredtothebuilding.Rust,cracks,looseconnections PooRLySECuREd anddeformitiesintheconduitshouldbecorrected.
CoVEREdBy The service mast or conduit should not be covered by siding, so it will not be damaged SIdIng inadvertentlyandsoitcanbeinspectedeasily.
PooRSEALAT Theconduitshouldbesealedatthemeterandwhereitpassesthroughthewalltoprevent mETER/WALL waterpenetration.
2.3ServiceSize
dESCRIPTIon Theservicesizeisdeterminedbythesizeofthewirecomingfromthestreettothehome.It’softenhardtodeterminethewiresize,sinceitisinaconduit.Thesizeofthemainfusesorbreakersisagoodindicationofservicesize.
Asthepowerentersthehouse,itgoesintoaservicebox,whichhastwofusesortwocircuitbreakers(oronebigbreaker).Oneisfortheblackwireandoneisforthered.Nobreakerorfuseisusedontheneutralwire.Thesizeofthefusesorbreakersshouldmatchthewirecapacity.(100amps,200amps,etc.)SeeTable2belowforratingsofvariousserviceentrancewires.
Aserviceboxwithfusesmighthavetwo100-ampfuses.Thisindicatesa100-ampservice,not200amps.Youcan’taddthemtogether.Oneofthefusesprotectstheblackwireandtheotheroneprotectstheredwire.
Theratingstampedonthemeterboxorontheserviceboxisnotalwaysagoodindicatoroftheelectricalservicesize.
hoWmuCh Everyhousegets240volts.Theamountofelectricityavailableisdescribedbythenumberof ELECTRICITyIS ampsthesystemcansafelydeliver.100ampsisacommonelectricalserviceforanaverage Enough? home.Largerhousesorhouseswithbigelectricaldemandslikeelectricheatmighthave150
or200ampservices.Thelargestresidentialelectricalservicewetypicallyseeis400amps.Someolderhomeshave60-ampservices.Whilethismaybeserviceableforsomehomesandlifestyles,100ampsiscommonlyconsideredaminimum.
Table2–TypicalServiceEntranceSizes
minimumWireSize ServiceSize minimumWireSize uSA (amps) Canada
Copper Aluminum Copper Aluminum 4 2 100 3 2
2 1/0 125 2 2/0(1/0)
1/0 2/0 150 1/0 3/0
2/0 4/0 200 3/0 250MCM
Note:Variationsarepossible,dependingontypeofwire,temperaturerating,etc.
The home RefeRence Book ©
eLecTRIcAL
154
Table3 indicateswhattypicalelectricalappliancesneedtooperate.Thesizeoftheserviceneededforthehousedependsonthenumberofelectricalappliances.Someoftheappliancesthatcantaxanelectricalserviceincludeelectricheaters,saunas,andhottubs.Itisthesimul-taneoususeofappliancesthatcausesproblems,andthis isdependenton lifestyle.Largerfamiliesarelikelytousemoreelectricityatthesametime,andmayneedalargerelectricalservicethanasmallerfamilyinthesamehouse.
Table3–TypicalPowerandCurrentforhouseholdAppliances
Watts Amps
Stoveandoven 9600 40
Clothesdryer 5000 20
Centralairconditioner 5000 20
Electricwaterheater 3000 12.5
Kettle 1500 12.5
Toaster 1200 10
Microwaveoven 1500 12.5
Coffeemaker 1200 10
Dishwasher 1200 10
Iron 1500 12.5
Portableelectricheater 1500 12.5
Windowairconditioner 1200 10
Centralvacuum 1500 12.5
Hairdryer 1800 15
Portablevacuumcleaner 1400 12
Washingmachine 500 4.2
Furnacefan 250 2
Blender 360 3
Refrigerator 700 6
Television 120 1
DVDplayer 20 0.2
Stereo 120 1
Desktopcomputerwithmonitor 180 1.5
Laptopcomputer 60 0.5
60wattincandescentlight 60 0.5
14wattcompactfluorescentlight 14 0.1
1/4horsepowermotor 700 6
1/2horsepowermotor 1000 8
155
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
TheCommonProblemwithServiceSize
100ampservicesarecommonandtheminimumacceptableformosthomes.Howmuchelec-tricityyouneeddependsonthesizeofthehouse,andthenumberofelectricalappliances.
SERVICEToo Ahousewithanundersizedelectricalservice isnotasafetyconcern,but it isan inconve-SmALL nience.Anelectricalservicethatismarginallysizedmaysufferblowingofthemainfusesor
breaker.Thebreakerscansimplyberesetbythehomeowner,butfusesusuallyhavetobereplacedbytheutilityoranelectrician.Theentirehouse isoftenwithoutelectricitywhilewaitingforaservicecall.Thisisonereasonmoderninstallationsuseamainbreakerratherthanfuses.
Changing the service size typically means new wires from the street to the house, newconduit,anewmeterandusuallyanewservicebox.Replacingundergroundwiresismoreexpensivethanreplacingoverheadwires.
Most modern homes have acombination panel that incor-porates the service box (withthe main circuit breaker) witha panel housing the breakersthatgototheindividualcircuits.When a service in an existinghome is upgraded, a combina-tion panel is typically installed.A good installation includes apanel with room to add morecircuitsinthefuture.
2.4ServiceBox(ServiceEquipment)
dESCRIPTIon Theserviceboxincludesacircuitbreakerthatcanbeusedtoshutoffallthepowerinthehouse(newer),oraswitchwithahandlelocatedontheoutside,andtheservicefusesinside(older).Thisisyouremergencyshut-offforalltheelectricityinthehome.Theserviceboxmaystandalone,althoughinmodernhomes,acombinationpanel(servicepanel)iscommon.Thisincludesthebreakersfortheindividualbranchcircuits.
The home RefeRence Book ©
eLecTRIcAL
156
houSEPoWER Themainswitchorbreakerisnotshutoffduringahomeinspection,sinceitwouldshutdown LEFTon theentirehouse.Thiscandisruptclocks,timersandcomputers,forexample,andcanresultin
damagetosomemotorsandcompressors.
Homeinspectorsdon’tremovethecoverforthemainbreakers inacombinationpanelforsafetyreasons.
Not all homes have a single service box. Some have a number of different points whereelectricitycanbeturnedoff.Inmanyareas,uptosixdifferentdisconnectpointsareaccept-abletoturnoffalltheelectricityinthehouse.
CommonProblemswiththeServiceBox
undERSIzEdBox Theserviceboxratingmustbeatleastaslargeastheserviceentrancewires,andthefusesorbreakersinside.Forexample,ifahousehasa150-ampservice,aboxratedforonly100ampsisnotacceptable.
undERSIzEd The fuse or breaker rating shouldmatchthewires’ current rating (ampacity) toensureanBREAkERoRFuSE adequate supply of electricity to the home and to ensure proper protection for wires. If
improperlysized,themainfusesorbreakersshouldbereplaced.
mISmATChEd Thetwomainfusesintheserviceboxshouldbethesamesizetoproperlyprotectthewires FuSESIzES andensurethesupplyofelectricitytothehomeisadequate.Iftheyarenot,anelectrician
shouldbeengagedtocorrectthesituation.
PooR Poor connections may lead to overheating and should be corrected. In some cases it is ConnECTIonS/ necessarytoreplacetheserviceboxitself. EVIdEnCEoF oVERhEATIng
dAmAgEd/ If the main switch or breaker handle is inoperative or damaged, it should be replaced. PooRLySECuREd Similarly, if the box is rusted or damaged, it should at least be checked by an electrician.
The service box should be re-secured to the wall if it is loose, to prevent poor electricalconnections.
RuST Moistureintheboxleadstorust,whichdamagestheboxandcanresultinunsafeelectricalconditions.
PooRACCESS Theserviceboxshouldbeaccessibleandinadrylocation.Theserviceboxshouldberoughly oRLoCATIon fivefeetabovethefloorandhavethreefeetclearinfrontofthebox.Serviceboxesshouldnot
belocatedinclothesclosets,bathroomsorstairwells.
nExTSTEPS Beforewemoveontotalkaboutthepanelthatbreaksthetrunkofthetreeupintobranches,let’shavealookatasafetysystemcalledgrounding.
157
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
2.5Systemgrounding
dESCRIPTIon Thepurposeofgroundingistogiveelectricityasafeplacetogoifitgetsoutofcontrol.Whenpeopletouchliveelectricalthings,theygetanelectricalshock,andinsomecasestheydie.Groundinghelpspreventthat.
Untilroughly1960,groundingwasonlyfoundattheservicepanel.Sincethen, ithasbeenusedonallbranchcircuits,includinglightsandelectricaloutlets.Agroundwireisawirethatprovidesasafepathforstrayelectricity.
Generallyspeaking,thegroundingwiresareconnectedtometallicpartsofanelectricalsys-temthatarenotsupposedtocarryelectricity.Thesemetalcomponents(panels,switchboxes,light boxes, etc.), are close to electricity, and if something goes wrong, the metal cabinetcouldbecomelive.Apersontouchingthecabinetwouldgetashock.Connectingthegroundwiretothemetalcabinetensuresthatifsomeonetouchesthecabinet,heorshewillnotgetashock,evenifalivewireinsideistouchingthecabinet.
WhEREdoESThE The stray electricity quite literally goes to ground, where it dissipates harmlessly. In mostELECTRICITygo? houses, the electrical system is grounded to the metal water supply piping and/or one or
moreeight-footmetalrods(GroundingElectrodes)drivenintotheground.Thisallowsstrayelectricitytogetintotheground.Wheregroundingisthroughmetalsupplypiping,thegroundwire(GroundingElectrodeConductor–GEC)shouldbeconnectedtothesupplypipingnearitspointofentryintothehouse.Ifconnecteddownstreamofthewatermeterorawaterfilter,ajumperwireisprovidedacrossthemeterorfiltertomaintaintheconnectiontogroundevenifthedeviceisremoved.
oThER Othergroundingconfigurationsincludeawellcasing,alongcopperwireorbarencasedinthegRoundIng concretefooting,andametalplateorringburiedintheground.Noneoftheseisvisibleand
ELECTRodE theyarenotevaluatedduringahomeinspection. SySTEmS
The home RefeRence Book ©
eLecTRIcAL
158
CommonProblemswithGrounding
mISSIng The system ground is missing in some cases. It may have been omitted from the originalinstallation,orremovedduringelectricalorplumbingwork;ortheoriginalgroundmayhavebeen left behind when the service panel was relocated. Adding a new ground wire is notusuallydifficultorexpensive.
WIRETyPE/ Thegroundwiremaybetoosmallfortheservicesize,thewrongmaterial,ortheremaybe SPLICES splices.Connectionsingroundwiresaregenerallydiscouragedforfearofabadconnection.
InEFFECTIVE Thesystemgroundmaybeineffective.Iftheconnectionsarepoororthewiresdamaged,the gRoundIng qualityofgroundissuspect.Ifthereisaspliceinthegroundwire,apotentiallyweakconnec-
tionexists.Groundwiresaresometimesineffectivebecausetheyaresecuredtopipesthatarenolongerinservice.Thisiscommonongalvanizedsteelplumbingpipesthatareabandoned.Iftheplumberdidnotmovethegroundwireovertothenewpiping,thegroundingsystemwillbedefeated.Bythesametoken,connectingagroundwiretoplasticsupplypipingisnoteffective,sinceplasticisnotagoodelectricalconductor.Thegroundwire(GEC)mayalsobetoosmall.
Checkingthequalityofthegroundingsystemisbeyondthescopeofahomeinspection.
LACkoF Thegroundingsystemhastobecontinuous.Thegroundwirehastobebondedtootherwires BondIng thatrelyongrounding.Thegroundwire,theservicebox,andtheneutralwireshouldbeelectri-
callybondedtogetherattheservicebox,butoftenarenot.Thissituationshouldbecorrectedpromptly.Again,thecontinuityofthesystemisnotverifiedduringahomeinspection.
BondIngAnd Thesetermsaresimilar,confusingandoftenusedinterchangeably.Strictlyspeaking,aground gRoundIng wireconnectstoground.Bondingmeansconnectingthingselectricallysotheyhavethesame
electricalpotential.Thethingsmayhaveapotentialof120volts,zerovolts,oranythingelse,aslongasbotharethesame.Theideaiswedon’twantelectricityflowingbetweenthetwo.Whenwebondsomethingtoagroundwire,everythingiseffectivelygrounded.
BondIngPIPIng Metalpipesforwaterandgascanbecomeliveelectricallyifsomethinggoeswrong.Inmany SySTEmS areas,thehotwatercoldwaterandgaspipingarebondedtogetherandconnectedtothe
systemgroundtothehousetoreducetheriskofelectricalshockfrompiping.
gRoundWIRE ConnectingthegroundwiretotheplumbingsystemdownstreamofthewatermeterisnotdoWnSTREAmoF consideredeffectivebecausestrayelectricitymaynotbeabletogetpastthemetertoground, WATERmETER especially ifthemeter isremovedforrepair!Thiscanbeeasilycorrectedbyrelocatingthe groundwireupstreamofthemeter,orprovidingajumperwirearoundthemeter.
nExTSTEPS Nowwe’lllookatthemainpanelwhereelectricitygetsdistributedthroughoutthehouse.
159
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
3.0ServicePanel
3.1Panel(PanelboardinElectricalCodeTerms)
dESCRIPTIon Electricityiscarriedfromtheserviceboxtotheservicepanel.Modernsystemsuseacombina-tionpanelwheretheserviceboxandservicepanelareinonebox.Theblackandredwiresareeachconnectedtoaliveconnectionbar(calledabusbar–acurrent-carryingmetalbarwithseveralconnectionpoints)andthewhitewireisconnectedtotheneutralbusbar.Eachbranchcircuitisconnectedtooneofthetwobusbarsthroughafuseorcircuitbreakerthatprotectsthatcircuit.
TyPICAL The black or red branch circuit wire for an individual circuit is connected to its own smallhouSEhoLd breaker(orfuse).Thecurrentflowsthroughthebusbar,throughthebreakerorfuse,andinto
CIRCuIT theblackorredwireforthecircuit.Theelectricityflowsout,completesitscircuit,running(120-VoLT) throughwhateverfixturesorappliancesareinuseonthecircuit,andcomesbackthroughthe
white(neutral)wire.Thewhitecircuitwireisconnectedtotheneutralbar,whichisattachedtotheserviceentrancewhitewire.
Itdoesn’tmatterwhetherpoweristakenfromtheblackortheredbusbar.Theresultisthesame; a 120-volt branch circuit has been established. The typical 14-gauge copper wire isprotectedbya15-ampbreaker.
numBERoF Panels may have room for anyCIRCuITS where from four to 40 circuits.
240-volt circuits for large elec-tric appliances are establishedby combining a 120-volt blackcircuitanda120-voltredcircuit.
AuxILIARyPAnEL Whentheservicepanelisfilled,(SuBPAnEL) anauxiliarypanelcanbeadded.
Thisdoesnotbringmorepowerintothehouse;itsimplyallowsformorebranchcircuits.It’slikeadding more branches to thetreewithoutincreasingthesizeofthetrunk.
The home RefeRence Book ©
eLecTRIcAL
160
CommonProblemswithPanels
dAmAgEd/ Wherethepanelisdamagedmechanicallyorbywater, itshouldbereplaced.Waterinthe LooSE/RuST panel causes rust and possible connection problems. Poorly secured panels should be
re-securedtothewall.
oBSoLETEPAnEL Old ceramic fuse-holders, which may or may not be in a metal cabinet, are consideredobsoleteandunsafe.Theseshouldbereplaced.Thesepanels,whichmaybefoundonwallsorceilings,haveexposedterminalconnections,anditiseasytoaccidentallytouchalivewirewhilechangingafuse.
PAnELCoVER Coversshouldbeprovidedorreplacedasneeded.Loosecoversshouldbere-securedtoreduce mISSIngoR theriskofelectricshock.Powershouldbedisconnectedpriortoremovingthecover. dAmAgEd
unPRoTECTEd Thereshouldbenoopeningsinthepanelthatallowsomeonetoreachinandtouchalive PAnELoPEnIngS electricalcomponent.Thismayoccurwherethepanelhasroomformorecircuits,orwhere
afuseblockhasnofuse.Whereverthissituationexists, theopeningshouldbecoveredorthefuseblockfittedwithafuse.Installingablownfuseonasparecircuittofillanopeningisacceptable.
Unprotected panel openings may also occur at the sides of the panel, where circuit wirestypicallyleavethepanel.Anyopeningsinthesideofthepanelshouldbeblankedoff.
undERSIzEd Wherethepanelratingissmallerthantheservicesize,thepanelmustbereplacedwitha PAnEL largerone.
PooRPAnEL Panelsarenotallowedinclothesclosets,bathroomsorstairways,forexample. LoCATIon
PooRACCESSTo Thepanelshouldbeaccessiblewiththecenterofthepanelroughlyfivefeetabovethefloor. PAnEL Thethree-footareainfrontofthepanelshouldbekeptclearforserviceaccess.
CRoWdEd Panelsshouldnotbeoverfilledwithwire.Excesswireinthepanelcanleadtopoorconnec- WIRIngInThE tionsandoverheating.Thiscanhappenifinstallersdonottrimthewiretotherightlength PAnEL insidethepanel.
dAmAgEdoR Damagedwireshouldbereplaced.Abandonedwireinthepanelmayleadtoovercrowdingor ABAndonEd confusionaboutwhatisliveandwhatisnot.Itshouldberemoved.WIREInThEPAnEL
oVERhEATEd Evidenceofoverheatingincludingdiscolorationormeltedwireinsulationshouldbeinvesti- PAnELWIRIng gatedbyanelectricianimmediately.Itmaybetheresultofalooseconnection,mechanical
damage,moistureoroverloading.
PAnELWIRIng Mostwiringleavesthepanelthroughthesideofthebox.Wiringshouldbewellsecuredwhere PooRLySECuREd itleavesthepanel.Acableconnectorisusedtomakesurethewireisnotexposedtothesharp
edgesoftheholeinthebox,andtosecurethewiresothatifsomeonepullsonthewire,itwillnotloosentheconnectionsinsidethepanel.Wheretheseconnectorsaremissing,theyshouldbeprovided.
161
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
douBLEd-uP Peopleoftenaddcircuitsasahouseexpandsoraselectricalneedsgrow.Insomecases,circuits CIRCuITS inthepanelaredoubledbyaddingasecondwiretotheterminalscrewforonebreakerorfuse. douBLE-TAPS, Thisdouble-tappingordouble-luggingisnotpermittedandshouldbecorrected.Themost douBLE-LugS commonsolutionisaddinganauxiliarypanel.Replacingtheexistingpanelwithalargeroneis
acceptablebutmoreexpensive.Thismakessenseiftheexistingpanelisdamagedorveryold.
Somemanufacturershaveaspecialcircuitbreakerdesignedtoholdtwowires.Someauthori-tiesdonotacceptthesetypesofbreakers.Securingthreewiresunderoneterminalscrewisneveracceptable.
undERSIzEd Whereanauxiliarypanelisused,thewirefromtheservicepaneltotheauxiliaryshouldbe WIREFEEdIng protectedbybreakersorfusesinthemainpanel.Thewiresizeshouldbelargeenoughtocarry AuxILIARyPAnEL theloadfromtheauxiliarypanel.Iftheauxiliarypanelisratedat60amps,thewirefeedingit
shouldalsoberatedat60amps.Thiswouldbea6-gaugecopperwire.
InAPPRoPRIATE Thegroundwireandneutralwireshouldnotbebondedtogetherinanauxiliarypanel.This BondIngATThE mayturnthegroundingwireintoacurrent-carryingwireinadvertently,creatingadangerous AuxILIARyPAnEL situation.
SuSPECTPAnEL Someelectricalpanelshavebeenthesubjectofsomecontroversyandtherehavebeenrecalls.
3.2FusesandBreakers
dESCRIPTIon Fusesandbreakersperformthesamefunction.Theyarethebrainsoftheelectricalsystemandshutoffthecircuitwhentoomuchcurrentisflowing.Acircuitbreakercanbeturnedbackonaftertheoverloadsituationiscorrected.Afusehastobereplaced.
dAngERouS People sometimes get frustrated with fuses blowing. They do not understand that this is PRACTICES signalingaseriousproblem.Bypassingafuseisaverydangerouspractice.Itisfoolishtowrap
ablownfusewithfoilorputapennyinafuseblock.Thismaycauseafire.
oVER-FuSIng Onedisadvantageoffusesisthatitiseasytousethewrongsizefuse.Itisunfortunatethat15,20,25and30-ampfusesallfitintothesamefuseblock.Anoversizedfuseorbreakerwillnotshutoffthecircuitintimetopreventoverheating.Circuitbreakersaretypicallynotchangedbythehomeowner,andarelesslikelytobeincorrectlysized.
FuSEREjECToRS Fuserejectorwashersaresmallplasticringsthatareinsertedintothefuseblock.Therearedifferentrejectorsfor15,20,25and30ampfuses.Fuserejectorspreventthewrongfusefrombeingscrewedintothefuseblock.
TyPECFuSES Here’s another way to prevent over-fusing: Type C screw-in (plug) fuses are non-interchangeable.Thismeansthatthewrongsizefusewillnotfitintothefuseholder.
oThERTyPES Fusesratedat15,20,25and30ampsareglassscrew-intypefuses.Largerfusesarealways oFFuSES cartridgetypewithametalcollarateachend.Cartridgefusesarealsoavailableinsmaller
sizes.
TImEdELAy Whenelectricmotorsstartup,theydrawalotofelectriccurrentforaveryshorttime.Insome (TyPEd)FuSES casesthiscanleadtonuisancefuseblowing.Specialtimedelay(TypeD)fusesallowthisextra
electricityforaveryshorttime.Thisisokay,becausethingswillnotoverheatinasecondortwo.Circuitbreakershavethistimedelayfeaturebuiltin.
The home RefeRence Book ©
eLecTRIcAL
162
TyPEPFuSES TypePfuseshaveanaddedsafetyfeature.Thelowmeltingtemperatureofthisfusesensesheatbuild-uparoundthefuse,whichmaybecausedbyapoorconnectionbetweenthefuseitselfandthefuseholder.Poorconnectionscanoverheatandcausefireswithcurrentflowsthataretoosmalltoblowafuse.
WhIChCIRCuIT Mostcircuitbreakerstripbymovingtheswitchtothemiddleposition,otherssimplyswitchtoISoFF? theoffposition.Itisusuallyveryeasytoseewhichcircuitbreakerhastripped.Thecircuitis
re-activatedbysimply‘switching’thebreakeroffandonagain.Withfuses,itisnotalwayseasytoseewhichonehasblown.Onglassfuses,youcanusuallyseeifyoulookcloselythroughtheglass,butonacartridgetypefuseitisoftendifficulttoknow.
CommonProblemswithFusesandBreakers
oVER-FuSIng The most common flaw withfusepanelsisfusesthatarethewrong size for the wire. Thisunsafe condition should becorrected promptly to preventoverheating of the wire. Theillustrationbelowshowstheap-propriate size of fuse for givenwiresizes.
163
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
dAmAgEdoR Abrokenordamagedfuseholderorcircuitbreakermaynotoperateproperlyandshouldbe LooSE replaced.Poorlysecuredfuseholdersorcircuitbreakersmayresultinpoorconnectionsand
shouldbere-securedorreplaced.
douBLEd-uP Peopleoftenaddcircuitsasahouseexpandsoraselectricalneedsgrow.Insomecases,circuits CIRCuITS inthepanelaredoubledbyaddingasecondwiretotheterminalscrewforonebreakerorfuse. (douBLE-TAPS, Thisdouble-tappingordouble-luggingisnotpermittedandshouldbecorrected.Themost douBLE-LugS) commonsolutionisaddinganauxiliarypanel.Replacingtheexistingpanelwithalargerone (TExTREPEATEd is acceptable but more expensive. This makes sense if the existing panel is damaged or FoRCLARITy) veryold.
Somemanufacturershaveaspecialcircuitbreakerdesignedtoholdtwowires.Someauthori-tiesdonotacceptthesetypesofbreakers.Securingthreewiresunderoneterminalscrewisneveracceptable.
3.3240-VoltCircuitsandmulti-wire120-VoltCircuits
dESCRIPTIon Heavy duty appliances use 240-volts. These include electric ranges, ovens and cook tops,clothesdryers,electric furnacesandheaters,airconditionersandwaterheaters.Here, theblackwireandredwirearebothusedinthecircuit.Formostoftheseappliances,awhiteneutralwireisalsoused.
Multi-wire120-voltcircuitsusecableswiththeblack,redandwhiteconductor.Atsomepointinthecircuit,thesesplitintotwo120-voltcircuits.Thesecircuitscanbeusedtoreducetheamountofwirethathastoberunthroughoutthehouse.Thesearecommonfordishwashersandgarbagedisposals,forexample.Theymayalsobeusedatkitchenreceptacles.Thetophalfofthereceptaclecanbeononecircuitandthebottomhalfcanbeonanother.Thisallowsthetwo appliances to be plugged in to the same outlet without blowing a fuse or trippingthebreaker.Thesecircuitshavetwofusesorbreakers,justlike240-voltcircuits.
Twobreakers(orfuses)areneeded;onefortheblackwire,andonefortheredwire.Thesetwobreakers(orfuses)shouldbelinkedsothatifoneisswitchedoff(breaker)orpulledout(fuse),theothermustbeswitchedofforpulledoutwithit.Thisisasafetyfeaturetopreventelectricshocks.Ifonlyonepartofthecircuitwasturnedoff,therewouldstillbepowertotheotherpart.Itwouldnotbesafetoworkonthesystem.
The home RefeRence Book ©
eLecTRIcAL
164
Circuitbreakersshouldhavemechanicaltiesorlinkstomakesurebothareturnedoff.Therearealsospecialdoublecircuitbreakerswithasinglehandle.Withfuses,doublefuseholdersareusedthatmustbepulledouttogethertodisconnectthecircuit.
TheCommonProblemwithMulti-wireCircuits
mISSIngLInkS Themostcommonissuewith240-voltcircuitsandmulti-wire120-voltcircuitsistheabsenceFoRBREAkERSoR ofthedevicetomakesurebothcircuitsareturnedoff.Inmostcases,thisimportantsafety
mISSIng improvementisinexpensive. PuLLouTSFoR FuSES
nExTSTEPS Beforewemoveonand lookatthewiringthroughoutthehouse,wearegoingto lookatacoupleofotherdevicesthathelpcircuitbreakersandfusesmakehousessafer–groundfaultcircuitinterruptersandarcfaultcircuitinterrupters.Thenamesareconfusingbuttheconceptsaresimple.
165
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
3.4groundFaultCircuitInterrupters
dESCRIPTIon These safety devices have been around since about 1970. They improve the safety ofregularcircuitbreakersandfusesbyreducingelectricshockhazards.Insteadoflookingfortoomuchcurrentflowing,theylookforcurrentgoingwhereit’snotsupposedtogo.Theyshut the power off when aslittle as .005 amps are leaking.Under normal circumstances,the same amount of currentis flowing at any point in thecircuit. If there are five ampsflowing out through the blackwire,thereshouldbefiveampscomingbackthroughthewhitewire. If there is a difference,currentisescapingsomewhere,andthisisdangerous.TheGFCIshuts down the circuit when itmeasures different currents intheblackandwhitewires.
Modern electrical codes require ground fault protection where there is the potential forwatertocomeintocontactwithelectricity.Thisincludesreceptaclesforbathrooms,kitchencountertops, wet bars, laundry tubs, spas and hot tubs, whirlpool baths, swimming pools,unfinishedbasementsandoutdoorreceptacles.
ProtectionmaybeprovidedbyGFCIcircuitbreakersorreceptacles.GFCIcircuitbreakersatthepanelprotecttheentirecircuit.GFCIreceptaclesprotectonlythatoutlet,andthedownstreamoutletsonthatcircuit.Note:weusethetermsreceptacleandoutletinterchangeably,asmosthomeownersdo.
Whileelectricalcodesrequirethesedevicesinnewwork,theydonotrequirethemonexist-inginstallations,althoughtheextraprotectionaffordedbythesedevicesisdesirable.CoderequirementsforGFCIshavechangedseveraltimessincetheywereintroducedin1970.
IdEnTIFICATIon Ground fault circuit interrupter breakers at the panel can be identified by the Test andReset buttons. Ground fault interrupter receptacles can also be identified by the TestandResetbuttons.
The home RefeRence Book ©
eLecTRIcAL
166
CommonProblemswithGroundFaultCircuitInterrupters
mIS-WIREd Inadditiontothenormalproblemsthatmaybetheresultofmis-wiredelectricalreceptacles,amis-wiredGFCIreceptaclemaynotshutoffthecircuitasexpected.Acommonproblemisthereversalofthe“line”and“load”connectionsonthebackorsidesoftheoutlet.NewerGFCIreceptacleswillnotresetifthewiringisdoneimproperly.Correctingthisproblemisquickandinexpensive.
mISSIng GFCIsmaynotbeprovidedinnewworkasrequiredbylocal jurisdictions.Replacingcon-ventional breakers with GFCI breakers is not difficult, although GFCI breakers are moreexpensive.
TESTFAuLTy/ GFCIshavea testbuttonthatsimulatesagroundfaultsituation.PressingthisbuttonwillInoPERATIVE causethebreakertotripifitisworkingproperly.Ifthetestbuttondoesnottripthebreaker,
the device may have to be replaced. Since this test turns off the power to everythingconnectedtothecircuit,manyhomeinspectorsdonotperformthistest.
TheremaybenopowertotheGFCI.Aspecialistshouldbeengagedtoinvestigate.
3.5ArcFaultCircuitInterrupters
dESCRIPTIon ArcFaultCircuitInterrupters(AFCIs)helpprotectagainstfiresbydetectingarcing.Arcingisanelectricalproblemthatoccurswhenelectricityjumpsfromoneconductoracrossaninsulatortoanotherconductor.Lightandheataregeneratedasthecurrentpassesthroughtheinsula-tor,whichmaybeairorasolidinsulatingmaterial.Arcfaultsarecommonwhereelectricalcordsaredamaged,orwhereoutletsarenotproperlyinstalled.
GFCIsaredesignedtopreventelectricalshock.AFCIsaredesignedtopreventfires.GFCIslookforelectricitythat isnotwhere it’ssupposedtobebymeasuringcurrentrunningthroughwires.AFCIslookforoverheatingbymonitoringthewaveformofthecircuitvoltage.
Arcfaultsaredangerousbecausethe heat generated may ignitenearby combustible material,startingafire.Arcfaultcurrentsare often too small to trip abreaker or blow a fuse. A GFCIwill not detect arc faults. AnAFCIbreakerprotectstheentirecircuit.
WhEREnEEdEd In houses built since roughly2001,AFCIshavebeenrequiredon circuits serving bedrooms.In some areas, codes have ex-tended this requirement tootherareasinthehouse,suchaslivingrooms,diningroomsandhallways.Theydonothavetobeaddedtoexistinginstallations.
167
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
CommonProblemswithArcFaultCircuitInterrupters
mISSIng AFCIsmaynotbeprovidedinnewhomesasrequiredbylocaljurisdictions.Replacingconven-tionalbreakerswithAFCIbreakersisnotdifficult,althoughAFCIbreakersaremoreexpensivethanconventionalbreakers.
FAuLTy AFCIshaveatestbuttontosimulateanarcingsituation.Pressingthisbuttonwillcausethebreakertotripifitisworkingproperly.Sincethisturnsoffthepowertoeverythingconnectedtothecircuit,manyhomeinspectorsdonotperformthistest.
4.0BranchCircuitWiring
4.1BranchCircuitWire:(distributionWiring)
dESCRIPTIon Thewirecarryingelectricityfromthepaneltothefixturesandappliancesistypicallycopper,althoughaluminumwascommonlyusedfromthemid-1960stothe late1970s.Eachpost-1960cableismadeupoftwoconductorsandonegroundwire.Pre-1960installationsdidnotincludeagroundwireineachbranchcircuit.(Notes:Datesareapproximate.Weusethetermswireandconductorinterchangeably.)
Theconductorsarewrappedwithcolor-codedplasticinsulation.Onolderwiring,theinsula-tionwasrubber.Thegroundwireisnotinsulated.Thisgroupofthreewiresistypicallywrappedinaplasticornylonsheathing.Oldersheathingswerepaper,clothandrubber.Flexiblemetalcableandrigidmetalconduitarealsousedassheathing.
BLACkAnd Oneconductorhasblackinsulationandistheliveorhotwire.Theotherconductorhaswhite WhITEWIRE insulation and is referred to as the neutral. Neither wire should be touched when there
ispowertothecircuit.Theblackandwhitewirescarrythecurrent.Thevoltageavailableis120volts,andthecurrentflowislessthan15amps.
gRoundWIRE Thegroundwireisnormallyidle.Ifthereisaproblem,thegroundactsasanescaperoutefor (EquIPmEnT theelectricity,inducingthecurrenttoflowthroughthiswiretotheground,ratherthaninto gRoundIng aperson,causinganelectricalshock.GroundeddistributionwiringwasintroducedtoresidentialConduCToR–ECg) electricsystemsinthelate1950s.
ThREE 240-voltcircuitsandmulti-wire120-voltcircuitshaveanadditionalliveorhotwire,aswehave ConduCToR discussed.Thiscablecontainsablack,red,andwhiteinsulatedwireaswellasanuninsulated CABLE groundwire.
WIREgAugE Thenormalwiresizeis14-gauge.Thisiscapableofcarrying15ampssafely.Afuseorcircuitbreakerratedat 15ampsshouldalwaysbeprovidedona 14-gaugecoppercircuit. Insomecases,20-ampcircuitsservekitchenorotheroutlets.Thecopperwiresizeforthesecircuitsshouldbe12-gauge.
The home RefeRence Book ©
eLecTRIcAL
168
dEdICATEd All240-voltappliancesgetdedicatedcircuits.Thisincludesthingslikestoves,waterheaters, CIRCuITS air conditioners, clothes dryers, hot tubs and saunas. Some 120-volt appliances also get a (IndIVIduAL dedicatedcircuit.Thisincludessuchthingsasthefurnaceorboiler,dishwasher,foodwasteBRAnChCIRCuITS) disposal,compactor,centralvacuumsystem,microwaveoven,refrigerator,freezer,washing
machine,whirlpoolbathtub,andelectricheaters.Splitreceptacles(outletswherethetopandbottomhalvesareonseparatecircuits)arealsousuallyondedicatedcircuits.Exteriorout-letsareoftenononededicatedcircuit.Ahomeinspectionwillnotidentifywhichcircuitsarededicated.Thesearedeterminedwhentheelectricalcircuitsarelabeled.
noTASAFETy Dedicated circuits are rare in older houses and it is very difficult to verify during a visual ConCERn inspection.Itisnotamajorexpensetorearrangethis,andtheissueisnotoneoflifesafety,
simplyamatterofconvenience.Withoutdedicatedcircuitsforeachoftheseappliances,thereisthepossibilityofnuisancefuseblowingorcircuitbreakertrippingwithseveralappliancesinusesimultaneously.
REFRIgERAToR Thereasonarefrigeratororfreezergetsadedicatedcircuitistopreventfoodspoilage.Ifitis AndFREEzER onacircuitwithotherappliances,thefuseorbreakermaybeblownasaresultofaprob-
lem with another appliance. The fuse or breaker may not be replaced immediately if thehomeownerdoesn’tknowthattherefrigeratororfreezerisalsoonthiscircuit.Asaresult,foodmaybespoiled.Again,homeinspectorswillnotpickthisup.
FuRnACEoR Theheatingsystemshouldbeonadedicatedcircuit.Iftheheatingsystemwastoshutdown BoILER duetoanoverloadfromanotherappliance,thehousewouldbewithoutheat.Thiscanresult
infreezingifthehomeisunoccupiedforsometime.
hEAVyCuRREnT Some appliances need dedicated circuits because of their heavy electrical draw. Putting dRAW additionaloutletsandlightsonthecircuitmayleadtoregularshut-downs.
CommonProblemswithBranchCircuitWiring
dAmAgEd Wirethatisdamagedorhasbeenoverheatedshouldbereplaced.Wirethatisnickedissmallerindiameteratthatspot.Thesmallerthewire,themoredifficultitisforelectricitytomovethrough. (The resistance is higher.) This can lead to localized overheating, and eventuallyafire.
oPEnSPLICES Connectionsshouldbemadeinsidepanelsorjunctionboxes.Exposedconnectionsarenotsafeandshouldbecorrected.
CABLE Wireshouldbeprotectedfromthemetaledgesofpanelsandboxeswithappropriatecable ConnECToRS connectors.Thisisusuallydonewithbushings,grommetsorcableclamps.Thesedevicesnot mISSIngoR onlyprotectthewirefromthesharpedges,buttheysecurethewire,sosomethingpullingon InEFFECTIVE the wire will not cause a loose connection. Missing or ineffective connectors should be
replaced.
169
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
LooSEoR Wiring which is poorly secured should be re-secured as necessary to protect it fromdAmAgEd mechanicaldamageandreducetheriskofelectricshock.Thewireshouldbesecuredwhereit
entersapanel,junctionboxorfixture.Thewireshouldbesecuredwithin12inchesofthebox,andeveryfourandahalffeettofivefeetthereafter.
If cable staples are used, onlyonewireshouldbesecuredun-der each staple. Staples shouldbe the appropriate size for thewire.Inappropriatestaplingcandamagethecable,riskingover-heatingorelectricshock.
ExPoSEdTo Wires should not be exposeddAmAgE to mechanical damage. Wires
shouldbe runthrough joists inunfinished basements, ratherthan on the underside, wheretheyaremorelikelytobedam-aged. Wires should be set wellback from any nailing surfacein stud walls, to avoid a nailbeingdrivenintothewires.Alternatively,steelplatesshouldbeusedtoprotectthewiresfromnailsorscrews.
Wireshouldnotberunalonginteriorsurfacesofwalls,floorsorceilingsinfinishedareas.
ExPoSEdInATTIC Ideally,thejoistsshouldbedrilledandthecablesshouldberunthroughthem.Althoughverycommon,itisconsideredpoorpracticetosecurethecabletothetopofthejoists.
don’TWALk Walking through an insulated attic where you can’t see what you are stepping on is veryThRough dangerousbecausewiringisoftenrunalongthetopoftheatticforjoistsortrusses.That’s
InSuLATEdATTICS whyhomeinspectorsdon’tdoit,andyoushouldn’teither.
dAmAgEd The wiring may be damaged by rodents. Mice and squirrels in the attic, for example, canInSuLATIon damagewiringinsulationandcreateafirehazard.This isoftendifficulttodetectwithout
pullingbacktheinsulation.Wherepestsareknowntohavebeeninahome,anelectricianshouldinspectthewiring.
unPRoTECTEd Wherewiringisrunonthesurfaceofwalls,baseboardsorotherinteriorfinishes,itshouldbeSuRFACEWIRIng protectedfrommechanicaldamagewitharigidcovering.
The home RefeRence Book ©
eLecTRIcAL
170
TooCLoSETo Wiringshouldbekeptat leastone inchawayfromheatingductsandhotwaterpipingtoduCTSAndPIPIng avoidoverheatingthewire.Insulationcanbeusedtoseparatethesematerials.
undERSIzEdWIRE Wirethatistoosmallfortheapplianceitserves,orfortherestofthecircuitwiring,shouldbereplacedtoreducetheriskofoverheating.
ExTEnSIon Extension cords should not be used as permanent wiring, and should never be stapled to CoRdSuSEdAS walls,floorsortrim.Cordsshouldnotrunundercarpetsorgothroughdoorwaysorwindows. PERmAnEnT Thesepracticesarefirehazards. WIRIng
ABAndonEd Wiresthatarenotinuseshouldberemovedorthewireendsshouldbeterminatedinjunction WIRIng boxestopreventconfusionandelectricalshocks.
ImPRoPER Exteriorwiringshouldbesuitableforoutdooruse.TherearedifferenttypesofexteriorwireExTERIoRWIRIng forabovegradeandbelowgrounduse.Exteriorwiringshouldbeprotectedfrommechanical
damageandspecialexteriorjunctionboxesarerequired.
Smaller electrical wires (14-gauge, 12-gauge and 10-gauge) are made up of a single solidconductor.Largerwires(8-gaugeandlarger)aremadeupofanumberofstrandsofsmallerconductors.Thesestrandedwiresaremuchstrongerintensionthansolidconductors.Solidconductors(10-gaugeandsmaller)cannotberunasoverheadunsupportedwiringbecausethemetalmayfatigue.Solidconductoroverheadwiringshouldbereplaced.
oVERLoAdEd Whileitisdifficulttotellfromavisualinspection,thenumberoflightsandoutlets(receptacles) CIRCuITS onanygivenbranchcircuitshouldbesuchthatthecircuitwillnotdrawmorethanthecircuit
rating(typically15amps)undernormalcircumstances.Atamaximum,12lightsand/oroutletsshouldbeconnectedtoeachcircuit.Thepracticallimitation,however,isifoneoftheoutletsisusedforahairdryer,whichmaydrawcloseto15amps,itiswisetoconnectthecircuitonlytootheroutletswhichwillbeusedforvery low-drawingappliancessuchasclocks,radios,televisions,computersor lights.Mostcircuitsserveacombinationofelectricalreceptaclesandlights.
TERmInoLogy Electricity is confusing, there’s no getting around it. Here’s an example of what electrical douBLE-TALk puristscallthings:Blackandredwiresareliveandarecalled‘ungrounded’conductors.White
wires are neutral and are called ‘grounded’ conductors. Ground wires are the emergencysystemandarecalled‘grounding’conductors.That’sjustcruel.
171
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
4.2knob-and-TubeWiring
dESCRIPTIon Knob-and-tubewiringwasusedinhomesuntilapproximately1950.Whiledifferentthanthewiringthatisusednow,itisnotnecessarilyinferior.Thiswiregetsitsnamefromtheceramicknobsthatsecureitandtheceramictubesthatprotectthewireasitpassesthroughwood-framingmemberssuchasfloorjoists.
SEPARATEBLACk The black and white wires inAndWhITE knob-and-tube systems are
run separately, in two distinctcables. In modern cables, theblack wire, white wire andground wire are all wrappedup in a single cable. It was feltoriginally,thathavingtheblackwire and white wire separatewassafer,sincetherewasverylittle chance of the black andwhite wires ever touching, cre-atingashortcircuit.Thishasnotprovedtobeabigproblemwithmoderncables.
nojunCTIon Anotherdifferencebetweenknob-and-tubewiringandmoderncableisthatwithknob-and-BoxES tubewiring,electricaljunctionboxeswerenotusedtoconnectwires.Inmodernconstruc-
tion,wiresmustbeconnectedinsideaclosedbox.Knob-and-tubeconnectionsweremadebytwistingthewiringtogether,solderingthewires,andwrappingtheconnectioninrubber,theninelectricaltape.Whilenolongeracommonpractice,ifproperlydoneandnotdisturbed,theseconnectionswillserveindefinitely.
nogRoundWIRE Another difference between knob-and-tube wiring and modern cable is the absence of agroundwire.Asmentionedearlier,knob-and-tubewiringwasusedupuntil1950.Fromthe1950s to roughly 1960, two-conductor cable was popular, although no ground wire wasincluded.Sinceroughly1960,groundwireshavebeenincorporatedintothetwo-conductorcable,andelectricalreceptaclesincludedathirdslot(forthegroundingpin)thereafter.
WIREInSuLATIon Anotherdistinctionbetweenknob-and-tubewiringandsomemoderncablesisintheinsula-tion.Theknob-and-tubewiringusedrubberinsulationandclothsheathingaroundthewiring.Inmoderncables,eachwirehasplasticinsulationtypically,andtheentirecableiswrappedwithanotherlayerofplastic.Overtheyears,thesesheathingmaterialshaveincludedcloth,paper,rubber,metalandplastic.
BRITTLE Breakdownoftheinsulationonknob-and-tubewiringisoftenthereasonitisreplaced.ThisisInSuLATIon frequentlytheresultofoverheatingormechanicalabuse.
REPLACEmEnT Whileknob-and-tubewiringmustberecognizedasold,itisnotnecessarytoreplaceitasamatterofcourse.Itshouldbeinspectedandevaluatedonanindividualbasis.
The home RefeRence Book ©
eLecTRIcAL
172
CommonProblemswithKnob-and-TubeWiring
PooR Problemswithknob-and-tubewirealmostalwaysresultfromamateurishconnectionsmadeConnECTIonS after original installation. Since original connections were made without junction boxes,
manyhomeownersfelttheytoocouldmakeconnectionstoknob-and-tubewiringwithoutjunctionboxes.Thisisanunsafepractice,particularlysincethechanceofmakingaspliceasgoodastheoriginalconnectionisveryremote. Inanycase,thisviolatesmodernelectricalrules.
dAmAgE Since knob-and-tube wiring isinvariably old, it has been sub-ject to more home handymen,more mechanical abuse (suchas items stored on top of thewire in the basement or attic),and is more likely to have suf-fered wear and tear. Pinchedwiringanddamaged insulationisaproblem,particularlyinun-finished basements, where thewiringisexposed.
BRITTLE Another problem is brittleknob-and-tube wire insulation,whichmayoccurifthewirehasoverheatedinthepastasaresultofover-fusing,apoorconnectionordamagedcable.Oftenthewirebecomesbrittleinhighheatareas,suchaspanelsandjunctionboxes.Inexposedareas,whereinspectioniseasy,thereisusuallygoodaircirculationandlittleheatbuild-up.Thewiresareleastlikelytobebrittleintheseareas.
Brittlewireinsulationmaybeaproblemwherethewireisburiedinatticinsulation.Thisiscommoninatticswhereinsulationhasbeenupgraded.
CIRCuITS Since older electrical systems had few circuits by today’s standards, the chances of eachExTEndEd knob-and-tubecircuithavingbeenextendedovertheyearsareverygood.Whilethisisnot
necessarilyaproblem,theadditional loadsandthepossibilitiesofpoorconnectionsmakean argument for replacing older knob-and-tube wiring. This is often cost-effective duringremodeling.
TWoFuSE Inallmodernsystems,thereisonlyonecircuitbreakerorfuseatthebeginningofeachcircuit.CIRCuITS(FuSEd Thereisaverygoodreasonforthis.Whenwewanttoworkonacircuit,wehavetoturnit
nEuTRALS) off.Usingthefuseorcircuitbreakerisacommonwaytodothat.Ifthefuseorbreakerisattheendofthecircuit,turningitoffwillleavetheentirecircuitliveuntilwegettothebreaker.Thatmakesitverydangeroustoworkonthesystem.
Anotherproblemspecifictoknob-and-tubewiringisthepresenceoftwofusesonasinglecircuit.Boththeblackandwhitewireshavefusesonsomeveryoldpanels.Thismeansthereisafuseatthebeginningandattheendofthecircuit.Ifthefuseontheneutralwireblows,
173
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
thefixturesandappliancesonthiscircuitwillnotwork.Itisnotsafe,however,toworkonthecircuit!Powerisstillavailablethroughthecircuit,rightuptotheblownfuse.Apersoncouldgetashockinthiscase.Bytheway,onefuseoneachcircuitisperfectlyadequate.
Wecanreplacetheseoldpanelstosolvetheproblem,withouthavingtoreplacetheknob-and-tubewiringthroughoutthehouse.
InSuRAnCE Somecompanieswillonlyprovideinsuranceafteraninspectionandapprovaloftheknob-and- dIFFICuLTIES tubewiringbythelocalauthorities.Manycompanieswillnotofferinsuranceatallonhouses
withknob-and-tubewiring.
REPLACEWhEn Itismuchlessexpensivetoreplacewiringinahomewhenremodelingahome.Walls,ceilings REmodELIng andfloorsareopenedupandaccessible.Manyhomeswithknob-and-tubewiringhavethe
wiringreplacedasindividualroomsareremodeled.It’sverycommontofindpre-1950shomeswithacombinationofknob-and-tubeandmodernwiring.
4.3AluminumWire
dESCRIPTIon Aluminumwiringwascommonlyusedfromthemid-1960suntilabout1978.Itwasintroducedbecauseitwaslessexpensivethancopper.Itwasrecognizedfromthestartthataluminumwiring is not quite as good a conductor of electricity as is copper. As a result, 12-gaugealuminumwasusedinplaceof14-gaugecopperfora15amphouseholdcircuit.Otherwiresizeswerealsosuitablyincreased.Thiswasfine.
ThERmAL Someotherpropertiesofaluminum,however,werenotrecognizedanddidcauseproblems. ExPAnSIon Firstly, aluminum has a higher co-efficient of thermal expansion than copper. This means
thatwhenthewireheatsup(asallwiredoeswhenelectricityflows)thealuminumtendstoexpandmorethancopper.Thisleadstothewiretryingtomoveoutfromundertheterminalscrewsatconnections.Thisphenomenoniscalled“creep”andcanleadtopoorconnectionsandsubsequentoverheating.
SoFT Secondly,aluminumissofterthancopper,andelectriciansusedtoworkingwithcopperwouldoftennickaluminumwiringinadvertently.Nickingthewire,ofcourse,reducesitsdiameter,anditsabilitytocarryelectricity.Localizedhotspotscandevelopwherethewirehasbeennicked.Further,ifthewireisbentafterithasbeennicked,itwilloftenbreak.
InSuLATIng Lastly,theoxideofaluminumthatformsonthewireisaverypoorelectricalconductor.All oxIdE metalsrustoroxidize.Thegreenishcopperoxidethatformsoncopperwiringisnoproblem
becauseitisagoodelectricalconductor.Theoxidethatformsonaluminumcanleadtohigherresistanceandhighertemperatures.
Cu-AL&Co/ALR Asaresultofthesedifficulties,specialcomponents,designatedCU-ALorAL-CU,wereintro-duced.Thesecomponentscanbeusedwitheithercopperoraluminumwiring.Theseincludedwireconnectors(wirenuts),electricalreceptacles,circuitbreakers,stoveblocks,etc.Inmostcases, these improvements were satisfactory. However, electrical receptacles and lightswitchescontinued to be a problem.The subsequently designed receptacles andswitchesweredesignatedCO/ALR.ThisdesignationmeansCopper/AluminumRevised.
The home RefeRence Book ©
eLecTRIcAL
174
Onealternativetousingspecialcomponents is to join the alu-minumwirestoshort“pig-tails”ofcopperwire justbeforetheyconnect to outlets, distributionpanelterminals,andsoon.Theconnectionbetweenthealumi-num and copper wire is madewith a connector known to beappropriate. There are connec-tors specifically approved forthispurpose.
SPECIALSySTEmS Thereweresomespecialsystemsdevelopedtoconnectcopperandaluminumwire.Manyarenolongeravailableandinstallationsaretypicallyevaluatedindividuallybyanelectrician.
ACCEPTABLE Aslongasproperconnectorsareused,andtheconnectionsaremadewithoutdamagingthewire,aluminumwiringisconsideredsafe.Itispermittedforusebyelectricalcodes,althoughit isnotcommonlyused inhomesdueto theadversepublicity it receivedduring itsearlyproblemyears.Itisstillusedcommonlybyutilitiesinstreetwiringandforserviceentrancecables.Insomeareas,aluminumisstillcommonlyusedfor240voltapplianceslikerangesandairconditioners.
CommonProblemswithAluminumWiring
PAnEL/BREAkERS/ Wherespecialdevicesorconnectorshavenotbeenprovidedforaluminum,theyshouldbeRECEPTACLES/ added.Itisoftendifficulttoknowwhetherthesmalltwist-onconnectorsareappropriate.
ConnECToRS– Thesafestthing is toreplacethemwiththoseknowntobeappropriate.Forexample, thenoTPRoPERLy smalltwist-onconnectorsaresosmallthattheyarenotmarkedCU-AL.Theyarenowcolor-
RATEd coded,butonolderones it isdifficulttoknowwhetherornottheyareappropriate.Sincetheyonlycostafewcentseach,itmakessensetoreplacethemwiththoseknowntobethecorrect type. Some experts do not consider twist-on connectors to be appropriate for usewithaluminumwire.
InSPECTIonBy Theexaminationofeveryelectricalconnectioninthehomeisnotpartofahomeinspection.SPECIALIST Theprovisionofspecialaluminumcompatibleconnectorsisnotanexpensiveundertaking.
RECommEndEd Werecommendthatthespecialistcheckallthedevicesinthehomeofaluminumwiringandmakeimprovementsasneeded.
oVERhEATIng Aluminum wires that show evidence of overheating should be further investigated by aspecialist.Theremayormaynotbeasignificantproblem.
AnTI-oxIdAnT Connectionsonlargegaugealuminumwiresaretypicallycoatedwithaspecialgreasetopre-mISSIng ventcorrosion.Wherethisismissing,aluminumoxidemaybuildupandthewiresmayoverheat.
nExTSTEPS We’vetalkedabouteverythingrightuptoandincludinghowwegetelectricitythroughthehouse.Nowwe’llhavealookattheendpointswhereitgetsused.
175
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
5.0outlets,Lights,SwitchesAndjunctionBoxes
5.1outlets(Receptacles)
dESCRIPTIon Electricaloutletsareusedtopluginportablelights,appliances,heaters,etc.Mostoutletsareduplex,meaningthatwecanplugintwoappliances.Theyareusuallylocatedinwalls,butcanalsobeinstalledinceilingsandfloorsinspecialcases.Anadequatenumberofconvenientreceptacles is a distinct advantage for today’s lifestyles. Situations that require extensioncordsareinherentlydangerous.
ThERuLESkEEP Therulesaroundelectricaloutletschangeregularly.Mostexistinghouseswillnotcomply ChAngIng with the most current code requirements. While improvements are possible, this is not
consideredadefect.
PoLARIzEd Until 1960mostreceptacleswereungrounded.Theyhadonlytwoslots inthem,onecon-nectedtoablackwireandoneconnectedtoawhite.Outletstypicallyhavethetwoslotsindifferentsizes,(polarizedreceptacles)sothatapolarizedappliancecouldonlybeinstalledintheproperorientation.Thesmallerslotisdesignedfortheblackwire(hotorlivewire)andthelargerslotisconnectedtothewhite(neutralwire).
LIghTSoCkET Polarityisimportantonsomeappliances.Insomecases,polarityisimportantforsafety.In PoLARITy othersitisimportantforproperoperationoftheappliance.
Alampisagoodexampleofanappliancethathasapolarizedplugforsafetyreasons.Therearetwoelectricalcomponentsofthelightsocketthatmaybeliveelectrically.Thethreadedcollararoundthesocketisonehalfoftheconnection,andthebrassbuttonatthebottomofthesocketistheotherconnection.Apersonismuchmorelikelytotouchthethreadedcollarthatcomesuptothetopofthesocketwhenreplacingalightbulb,soitissafertomakethatthewhite(neutral)connection.Theblack(live)connectionatthebottomofthesocketislesslikelytobetouched.
Somehomeentertainmentsystemsrequirepolarizedconnectionstooperateproperly.
BLACkToBRASS Manymodernoutletshaveabrasscoloredscrewononesidetowhichthelive(usuallyblack)wireisconnected.Thewhite(neutral)wireisconnectedtothesilvercoloredscrewontheopposite side, and the ground wire is connected to the ground screw (usually green) neartheendoftheoutlet.
The home RefeRence Book ©
eLecTRIcAL
176
PuSh-In, Somemodernoutletsdonothavescrewsonthesidestoholdwiresinplace,buthaveholesin BAyonEToR theback, intowhichthewiresarefitted.Thesearecalledbayonet,daggerorpush-intype dAggER connectors,becauseofthewaythewireisinserted.Theseoutletswereparticularlytrouble-
somewhenusedwithaluminumwire.
TAmPER Tamper-resistantreceptaclesaredesignedtopreventchildrenfrominsertingthingslikepaper RESISTAnT clipsorkeysintothereceptacle.Aninternalmechanismwillblocksuchattemptsunlessboth
prongsofaplugareinsertedintotheoutletatthesametime.
gRoundEd The grounding of electrical outlets, which became popular after 1960, affords additional ouTLETS protection.Thegroundwireisathirdwirethatnormallyconductsnoelectricity.Itisanescape
routeforstrayelectricity, incasesomethinggoeswrongwiththeapplianceor receptacle.Whenanappliancemalfunctions,acordisdamaged,aconnectioncomeslooseorarecep-tacle is faulty,apersontouchinga liveelectricalcomponentmaygetashock.Thegroundwireprovidesasafepathfortheelectricity,soitdoesnotflowthroughapersontouchingthesystem.
Groundedreceptaclesareonlyusefulforapplianceswithgroundedplugs.Thereareveryfewhomeapplianceswithgroundedplugs.Theseincluderefrigerators,washingmachines,micro-waves,waterbedheaters,somecomputers,somesmallkitchenappliancesandsomepowertools,forexample.Groundedplugsalsocontrolpolarity,sinceapplianceplugscanonlybeputintooutletsoneway.
gFCISASAn A ground fault circuit interrupter (GFCI) on an ungrounded circuit will improve the safety ALTERnATIVE ofthesystem.Manyelectricalauthoritieswillnowacceptgroundfaultcircuitinterruptersas
analternativetogroundinginexistinghomes.GFCIscanbeinstalledatthepanelorasGFCIreceptacles.SomeauthoritiesmaynotacceptGFCIreceptacles.Formoreinformationabouthowgroundfaultcircuitinterrupterswork,see3.4inthischapter.
20-AmP 20-ampreceptaclesareprotectedbya20-ampbreakerandthewiresizefor20-ampcircuits RECEPTACLES is12-gauge,ratherthan14-gauge.20-ampreceptaclesareeasytoidentifybecausethelarger FoRkITChEnS (neutral)slotsareT-shaped.Thesereceptaclesarealsocommoninlaundryareasandbath-
roomswherehigh-currentsmallappliancesarecommon–kettles,toasters,hairdryers,etc.Receptaclesratedat15ampsmaybefoundon20-ampbranchcircuits.
177
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
CommonProblemswithOutlets(Receptacles)
ungRoundEd Where only two-prong appliances are used, this does not pose a hazard. However, wherethree-prongplugs(groundedappliances)areused,theoutletshouldbegrounded.Aspecialgroundwirecanbeadded,butthisisexpensiveandrarelydone.Thegroundfaultcircuitinter-rupterprovidesimprovedsafety,butitisnotquiteareplacementforgrounding.
PooRLoCATIon Outletsshouldnotbeinstalledhorizontallyinfloorsorcountertopsunlesstheyareaspecialtype suitable for this application. Moisture can create an electrical hazard. For the samereason,outletsshouldnotbelocatedoncountertopsurfaces,facingup.
Outletsshouldnotbeclosetoasourceofwaterunlessprotectedbyagroundfaultcircuitinterrupter.Theyshouldnotbedirectlyabovekitchensinksorbathroombasins,forexample,where appliance wires may touch water. Outlets should not be above electric baseboardheatersorclosetootherheatsources,whereappliancewiresmaytouchhotsurfaces.
REVERSEd Modern outlets have a large slot (neutral) and small slot (hot). If the wires are connectedPoLARITy improperly,thisisreferredtoasreversedpolarity.AreversedpolarityoutletcancompromiseouTLETS the safety of an electric appliance. A grounded appliance may have its grounding made
ineffectivebyreversedpolarity.
The home RefeRence Book ©
eLecTRIcAL
178
Withreversedpolarityoutlets,itispossibleforsomeapplianc-estohavetheirhousingbecomelive in the event of a malfunc-tion.Itisalsopossibleforsomeelectricalequipmenttooperateimproperlywithreversedpolar-ity. This may include a homecomputer, a stereo system,etc. Corrective action simplyinvolves connecting the wiresto the correct terminals on theoutlet (black wire to the brassterminal and white wire to thesilverterminal).
numBERoF Thereshouldbereceptacleswhereverpeoplearelikelytoplugthingsin.Innewconstruction,ouTLETS thereshouldbeanoutletwithinsixfeethorizontallyofanypointalongthewall(infinished
livingspaces).Translated,thismeansthereshouldbeanoutletevery12feetalongthewall.Innewkitchens,thereshouldbeanoutletwithintwofeetorthreefeetofanypointalongthecounter.
Olderhomeswillnottypicallyhaveasmanyoutletsasmodernlifestylesdemand.Commonsensesaysthereshouldbeoutletswhereveryouneedthem. Ifyouhave lotsofextensioncords,youneedmoreoutlets.
BAThRoomS Outlets should be within threefeet of basins, but not directlyabove the basin. In modernconstruction,bathroomoutletsshouldbeprotectedbyGFCIs.
LooSE/ As outlets wear, they may notdAmAgEd/ hold plugs securely in place.
WoRn/ Electricaloutletsthatare looseoVERhEATEd or damaged should be re-
paired or replaced. Similarly,coverplatesshouldbereplacedwhen damaged. Where thereis evidence of overheating, aspecialistshouldbeengagedtoinvestigate.
WEAThER-TIghT Specialweather-tightoutletsarerequiredoutdoorsorwherewatermaycontacttheoutlet. ouTLETSnEEdEd
179
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
CoVERPLATE Damagedormissingcoverplatesshouldbereplaced. mISSIng/ dAmAgEd
Won’TWoRk Ifanoutletisinoperative,itispossiblethat: 1. Theoutletitselfisdefective. 2.Thewiresinsidetheboxattheoutletarenotproperlyconnected.(Intermittentproblems
usuallymeanalooseconnection.) 3.Thereisaprobleminthewirebetweenthepanelandtheoutlet(perhapsatanotherbox
upstream). 4. Thereisablownfuseortrippedbreakerinthepanel. 5. Thereisapoorconnectionordamagedwireinthepanel. 6. Thepowerhasbeenturnedoff.
5.2Lights(LuminairesinElectricalCodeTerms)
dESCRIPTIon Installedlightingmaytaketheformoftraditionalceiling-mountedfixtures,recessedlight-ing,combinationlightsandfans,oranynumberorarchitecturaloptions.Thereareseveraltypesoflightingfixturesincludingincandescent,fluorescent,LED(lightemittingdiode)andhalogen.
CommonProblemswithLightFixtures
dAmAgEd/ Damaged light fixtures may present a fire or shock hazard and should be replaced. LightPooRLySECuREd/ fixturesshouldbewell securedto junctionboxes.Theyshouldneverbesupportedby the oVERhEATIng wiring.Lightfixturesshouldbearrangedsothattheyarenotsusceptibletooverheating.Some
fixturesrequireclearancefromcombustiblestopreventoverheating,andsomecanonlybeinstalledincertainorientations.
mISSIng Whenlightfixturesareremoved,sometimesopenjunctionboxesareleftwithlivewiresinthem.Thisisnotsafeandtheboxshouldbecovered.
Lightsshouldbeprovidedforallexteriorentrancedoors,sopeoplecanentersafelyatnight.
Won’TWoRk Inoperativelightsmaybetheresultof–
1.Aburnedoutbulb. 2.Afaultylightfixture. 3.Apoorconnectioninthebox. 4.Aflawinthewiringleadingtothebox. 5.Aproblemwiththeswitchcontrollingthelight. 6.Aproblemwiththewirebetweenthepanelandtheswitch. 7.Ablownfuseortrippedbreaker. 8.Apoorconnectionwithinthepanel.
Iftheproblemisnotsimplyaburnedoutbulborablownfuse,youmayneedanelectriciantoresolvethedifficulty.
The home RefeRence Book ©
eLecTRIcAL
180
FLICkERIng Flickeringlightsmayindicatedangerousconditionsincludingpoorconnections.TheseshouldLIghTS beinvestigatedpromptlybyanelectrician.
PoTLIghTS Unless they are specially de-(RECESSEdLIghT signed for the application,
FIxTuRES) recessed light fixtures shouldShouLdBE notbe installed inareaswhere
ChECkEd insulation will blanket thefixture, impeding normal heatdissipation. This may lead tooverheating and is a commonproblem on the upper floorof the house. Special fixturestypically have a designationthat includes the letters IC (In-sulation Contact or InsulatedCeiling). These are often notvisibletothehomeinspector.Wherepotlightsareusedinaninsulatedcavity,anelectricianshouldbeengagedtoverifythesafetyofthesystem.
dAmPAREAS Lightsused inareaswhereexposuretowatermayoccur,shouldbeofaspecial type.ThisnEEdSPECIAL includeslightsinshowerstalls,saunasandoutdoorlightfixtures.Again,thehomeinspector
FIxTuRES maynotbeabletodeterminewhetherthelightsareappropriatefortheapplication.
STAIRLIghTIng Light for stairwells, except for unfinished basements, should be switched at the top andShouLdBE bottom.Thiseliminatestheneedtowalkupordownpoorlylitstairs.
ConTRoLLEd FRomThEToP AndBoTTom
hEATLAmP Heat lamps at ceiling levelPRoBLEmS should be located beyond the
swingofanydoors. Ifadoor ispartially open below a heatlamp,atowelorarticleofcloth-ing flung over the top of thedoor can be ignited, causingafire.
181
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
gRoundIng Lightingfixtures,outlets,switchesandjunctionboxesshouldbegrounded.Remember,wemISSIng saidgroundingwasimportanttocarrystrayelectricitytoasafeplace,sowedon’tgetanelec-
tricshock.Homeinspectorsdon’tdeterminewhetherlightfixturesareproperlygrounded.
oBSoLETE Veryold-styleporcelainlightfixtures,usedwithoutelectricalboxes,arenotsafeandshouldbereplaced.Liveelectricalconnectionsareexposedonthesefixtures.
ExPoSEdTo Lightfixturesinclosetsareaconvenientfeature,butthelightsmustbekeptclearofareasmEChAnICAL wheretheymaybedamaged,orwherestoragemaybedirectlyagainstthelightbulb.Lights
dAmAgE shouldnotbeinstalledaboveorbesideshelvingunitsinclosets,forexample.Lightsonthewall above the closet door are usually safe. Incandescent bulbs should be fully enclosed,ideally.
5.3Switches
dESCRIPTIon Switchesmaycontrollights,receptacles,exhaustfansorotherinstalledequipment,suchasfurnacesandboilers.Ideally,lightswitchesshouldbeplacedinareaswheretheycanbeeasilyreachedwhenenteringaroom,orapproachingasetofstairs.
ThREE-WAy Three-way switches are requiredSWITChES inordertocontrollightingfrom
both the top and bottom ofmost stairways. Despite theirname, there are two switchesthat control one set of lights.Theyarealsocommonateitherendsofhallways.
CommonProblemswithSwitches
dAmAgEd/ Damagedorlooseswitchesorcoverplatesshouldberepairedorreplaced.TheoldpushbuttonLooSE/oBSoLETE switches (with two circular buttons which push into the switch and pop out) are gener-
allyconsideredunsafeandshouldbereplaced.ReproductionswitchesofthistypearenowapprovedandavailableinNorthAmericaforthearchitecturalpurist.
ImPRoPER Any switch that works only intermittently or that causes the lights to flicker should beoPERATIon replacedpromptly.
The home RefeRence Book ©
eLecTRIcAL
182
PooRLoCATIon Traditionally, switches were located about five feet above the floor. Where access for thedisabledisimportant,switchesaretypicallyaboutfourfeetabovethefloor.
Switchesinbathroomsshouldbeasfaraspossiblefrombasins,bathtubsandshowers,ideallyfivefeetormore.
ImPRoPER Stairwelllightingshouldbeswitchedbothtopandbottom. STAIRWELL LIghTIng
SWITChoRCoVER Damagedormissingswitchesorcoverplatesshouldbereplaced. PLATEmISSIng/ dAmAgEd
Won’TWoRk Aninoperativeswitchmaybe:1.Aproblemwithintheswitchmechanism.2.Aproblemwiththeconnectionsofthewireintheboxattheswitch.3.A flaw in the wire between the panel and the switch (including boxes upstream of the
switch).4.Aproblemdownstreaminthecircuitfromtheswitchthatmakesitseemliketheswitchis
faulty.5.Ablownfuseortrippedbreakerinthepanel.6.Adamagedorpoorlyconnectedwireatthepanel.7.Aburnedoutlightbulb.
Anelectricianshouldbecontactedtolocateandcorrecttheproblem.
5.4junctionBoxes
dESCRIPTIon Junction boxes are used to contain and support switches, outlets and lights. They can bemetalorplastic,andcome ina largevarietyofshapesandsizes. Junctionboxesmayalsosimplycontainwireconnections.Junctionboxesnotonlyprotecttheconnectionitself,butsecurethewirescomingintotheboxandholdtheminplace.Allmodernconnectionsshouldbemadeinsideajunctionbox.
CommonProblemswithJunctionBoxes
mISSIng Whereelectricalconnectionsaremadewithnojunctionboxes,thedangerofelectricalshockandfireisincreased.Withtheexceptionoftheearlyknob-and-tubewiring,allconnectionsshouldbeinjunctionboxes.
LooSE Junctionboxesshouldbeproperlysecuredtoframingmembers,andwiresshouldbesecuredto the box, otherwise there is potential for strain on the wires, which may result in looseconnections.
183
eLecTRIcAL
The home RefeRence Book ©
ELECTRICAL
SPECIAL Specialwater-resistantjunctionboxesarerequiredonbuildingexteriors.Thisappliestoother ouTdooR damplocationsaswell. BoxESnEEdEd
CRoWdEd Everyjunctionboxisratedforacertainnumberofwiresofacertainsize.Whereboxesareovercrowded,thereisadangerofoverheatingandpinchingwires.
noTACCESSIBLE All electrical junction boxes should be accessible for servicing. This means they cannot becoveredbyplaster,drywallorpaneling,forexample.
CoVERPLATE All junction boxes should be provided with cover plates to prevent people touching live mISSIngoR electricalconnections. dAmAgEd
5.5Appliances
Some appliances have special electrical situations or needs. A few of those are discussedhere.
CEILIngFAnS Thebladesofceilingfansshouldbeatleastsevenfeetabovefloorlevelsothatpeopledonotgetinjured.Thefanbladesthemselvesshouldbe12inchesbelowtheceiling.Heavyfansshouldbesupportedindependentlyoftheelectricalbox.
AIR Theoutdoorcomponentofanairconditioningsystemshouldhaveanelectricdisconnectina CondITIonERS weathertightbox.Thismakes it safe forservicementomakesure thepower isoffbefore
workingontheequipment.
gARBAgE The cord for a garbage disposal should be no shorter than 18 inches and no longer than dISPoSALS 36inches.Itshouldhaveadriploopandinmanyareasmustbearmoredcable.
dIShWAShERS Thecordforadishwashershouldbebetweenthreefeetandfourfeetlong.
FuRnACESAnd Thereshouldbeadisconnectswitchwithinsightoftheheatingunit. BoILERS
WhIRLPooL Theseshouldbeprotectedbyagroundfaultcircuitinterrupter.Thepumpmotorshouldbe BAThTuBS accessible. hydRomASSAgE TuBoR CIRCuLATIng BAThTuB
The home RefeRence Book ©
eLecTRIcAL
184