HOME CONDITION REPORT This report is prepared for the exclusive use of the client by: GOSHEN INSPECTION SERVICE 325 Park St. Worden, IL 62097 618 459-3437 Inspection Date: 12/03/2007 Time: 09:00 AM Client Report Name: 2611626 Inspection Site: 602 East Mill Street Staunton, IL 62088 Client: Tammy Grondzki 1112 East Mill St. Staunton, IL 62088 GOSHEN INSPECTION SERVICE Thomas J Maloney IL License #450.0000113 ASHI #101306 Report prepared by Goshen Inspection Service 2611626 Final Report

Upload: others

Post on 23-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

  • HOME CONDITION REPORT

    This report is prepared for the exclusive use of the client by:

    GOSHEN INSPECTION SERVICE 325 Park St. Worden, IL 62097618 459-3437

    Inspection Date: 12/03/2007 Time: 09:00 AM

    Client Report Name: 2611626

    Inspection Site:

    602 East Mill Street Staunton, IL 62088

    Client:

    Tammy Grondzki 1112 East Mill St. Staunton, IL 62088

    GOSHEN INSPECTION SERVICE

    Thomas J Maloney IL License #450.0000113ASHI #101306

    Report prepared by Goshen Inspection Service2611626

    Final Report

  • SCOPE AND LIMITING CONDITIONThis Written report covers the highlights of the physical inspection, and of the discussions between you and our

    inspector. The client has been urged to be present, ask questions about the home and about the inspectionprocess. Full value from this inspection may be derived from: 1) The inspectors walk through or "show and tell"with you. 2) Your notes and discussion during the inspection. 3) Study of the written report. 4) Thesupplemental general information contained in the report. 5) Follow-up telephone consultation if needed.

    The report is intended only as a general guide to help the client make his/her own evaluation of the overallcondtion of the home, and is not intended to reflect the value of the premises, nor make any representation as tothe adviseability of purchase. The report expresses the personal opinions of the inspector, based on his visualimpressions of the conditions that existed at the time of inspection only. The inspection and report are notintended to be technically exhaustive, or to imply that every component was inspected, or that every possibledefect was discovered. No disassembly of equipment, opening of walls, moving of appliances or stored items isperformed. All components which by location are concealed or camouflaged are excluded from this report.

    Systems and conditions which are not within the "scope" of this inspection include, but are not limited to: 1)Building code or zoning ordinance violations. 2) Environmental hazards (mold, radon, lead, etc.) 3) PestInfestation. 4) Geological stability or ground condition of site. 5) Engineering, scientific or specialized techniciantests, readings, or evaluatiuons. 6) Structural integrity. 7) Fireplace draft. 8) Home warranties, systemwarranties and component warranties. Any general comments about the above systems or conditions areinformational only and do not represent an inspection.

    This report is not a warranty. This inspection service only warrants that its inspection services will be performedin accordance with the Scope and Standards of Practice of the American Society of Home Inspectors (ASHI). Thisis a limited non-transferable warranty and the only warranty given by this inspection company. This inspectioncompany makes and the client receives no other warranty, express or implied. All other warranties, includingwarranties of merchantibility and fitness for a particular purpose, are expressively excluded. Any opinionsexpressed regarding adequacy, capacity, or expected life of components are general estimates based oninformation about similar components and occasional wide variations are to be expected between such estimatesand actual experience.

    Goshen Inspection Service certifies that their inspector has no interest, present or contemplated, in thisproperty or its improvement and no involvement with tradespeople or benefits derived from any sales orimprovements. To the best of our knowledge and belief, all statements and information in this report are true andcorrect.

    Should any dispute, controversy, interpretation or claim, including claims for, but not limited to, breach ofcontract, any form of negligence, fraud or misrepresentation arising out of, from or related to, this contract orarising out of, from or related to this inspection or inspection report shall be submitted to final and bindingarbitration under the RULES AND PROCEDURES OF THE EXPEDITED ARBITRATION OF HOME INSPECTIONDISPUTES of Construction Arbitration Services, Inc. The decision of the arbitrator appointed thereunder shall befinal and binding judgement and the Award may be entered in any court of competant jurisdiction. Client agrees notto disturb or repair or have repaired anything which may constitute evidence relating to the complaint, except in the caseof an emergency. If any portion of this Agreement is found invalid or unenforceable by any court or arbitrator the remainingterms shall remain in force between the parties.

    Address of Subject Property: 602 East Mill Street

    Staunton, IL 62088 Client: Tammy Grondzki

    Inspection Date: 12/03/2007

    When credit has been extended to the client, the client agrees to pay for the stated fee for the services performed. This inspection is made exclusively for the client who purchased the report. This inspection is made with theexpress agreement of the client that he/she understands the conditions and limitations stated above.

    Report prepared by Goshen Inspection Service2611626

    Final Report

  • Summary of Deficiencies

    Address: 602 East Mill Street Report #2611626 Date: 12/03/2007

    PLEASE READ! Our inspection of the subject property has identified various items/components that, in theopinion of the inspector, represent one or more of the following: 1) An item or condition that is in need ofrepair/replacement. 2) Maintenance necessary to protect the property from damage by the elements. 3) An itemor condition that requires further evaluation by a qualified specialist. It is advisable to use experiencedtradespeople when contracting for work that may be beyond your capabilities. All comments made on this reportare repeated in the Final Checklist section of the report.

    EXTERIORExterior Structure Perimeter24. Visible Cracks: Cracks over 1/4 inch or larger at the left rear corner indicate excessive settling. Recommend furtherinvestigation by a qualified specialist.

    Exterior Structure41. Window Glass: There are one or more broken/cracked window panes noted. Replace as needed. Specific location was:One basement window.

    42. Storm/Screen Windows: One of the storm windows was missing in the living room. Storm windows should be installed for energysavings.

    Deck/Patio/Porch52. Steps/Handrails: Recommend installing a handrail at the steps for safety.

    53. Deck/Patio/Porch Railing: None at the front porch. Lack of banister/railing are a major cause of household accidents. All elevateddecks/patios should have sturdy protective banisters/railings. Consideration should be given to installing asafety railing.

    Utility Connections56. Electrical Service: Overhead. The insulator securing the service line to the house has pulled loose. Contact the serviceprovider for repair.

    ROOF/ATTICRoof Main87. Cover Material Condition: Parts of the roof cover are deteriorated and in poor condition. The roof cover is approaching the end of itseconomic life. Contact a licensed roofer for directed repair.

    91. Flashing: Tar sealant noted on/or the plumbing vent flashing. Tar sealant will require periodic maintenance

    Report prepared by Goshen Inspection Service2611626

    1 Final Report

  • (sealing).

    93. Valleys: One or more of the valleys are deteriorated. Repair/replace as needed.

    94. Ventilation: Gable Vents. The vents are blocked in the attic with plywood. Remove to provide ventilation to the attic.

    96. Downspouts: Two of the downspouts are incomplete or missing at the right rear. Replace the downspouts as needed.

    97. Drains/Splash blocks: There were no drains/splashblocks noted at the right rear. They are recommended to carry water awayfrom structure.

    Attic114. Inaccessible Areas: There was no access to the main attic. It could not be inspected. There should be access to all atticareas.

    MAJOR SYSTEMSGas Service119. Vents/Exhaust: Excessive condensation was noted at the furnace vent connectors. The pipe is probably oversized.Replace as needed.

    120. Gas Piping: There was no sediment trap on the gas line to the water heater. Recommend installation. The purpose ofa sediment trap is is to act as a trap to stop any moisture or sediment from entering a gas control valveand causing a seal to stick open allowing gas to enter the burner when the appliance is off. This couldcause a burst of accumulated gas when the appliance lights.

    121. Service Shut off Location(s): At the Stove. There were no gas shut offs noted at the furnace and water heater. Recommend installing.

    Electrical System152. Branch Circuits: Nonmetallic sheathed cable -copper. No junction box was installed at an outlet in the basement. Note heatdamaged insulation on one leg of a 240 volt circuit. There is also a broken outlet in the front bedroom.Extension cord wiring to the rear exterior light. Recommend hard wiring an outlet at the appliance.

    155. Breaker/Fuse Configuration: No factory linked handles on one pair of 240 volt fuses. Install factory linked handles.

    156. Wire Over Current Compatibility: There is some question as to the wire over current compatibility. This condition may present a hazard. Specific notation is made. #12 wire on 30 amp fuses. Recommend 20 amp.

    157. GFI Outlets: Current electrical code requires that GFIs be located in areas with the greatest risk of electric shock, at thekitchen counters, in bathrooms, at Hydromassage tub, in unfinished basements, in garages and anyoutside receptacle(s) and in the crawl space (if applicable). Consider installing for safety.

    Report prepared by Goshen Inspection Service2611626

    2 Final Report

  • 158. Grounding System in Place: A makeshift ground was noted at the furnace. The inspector has discovered one or more three prongfemale outlets that do not have the correct ground. Specific notation was made. All in the living room. Inthe bedrooms. In the bathroom. Grounding can be accomplished by: Installing a ground wire. Check forground wire at the receptacle and hook up. Installing a GFI (safety ground outlet) will provide safetywithout a ground wire. Choosing to return to a two prong ungrounded type receptacle also is an option.Also note a broken outlet in the front bedroom. Hot/Neutral reversed at the following receptacles. To theright of the kitchen sink. At the washer. Rewire as needed.

    161. Open Splices/Open Junction Boxes: The inspection has discovered open splices. All splices should be in mounted junction boxes with coversand clamps on all wires. One or more in the back hall attic. One or more in the basement. There were oneor more junction boxes noted that are in need of covers. Recommend installing covers.One or more in thebasement.

    162. Double Tapping Noted: Double tapping was noted in the electrical panel. Specific notation is made., T one fuse. There is nospace available in the panel. Recommend installing a new sub panel or main panel.

    Plumbing System165. Structure Pipe Material: Copper. CPVC plastic/PVC plastic. Galvanized piping. There were copper to galvanized/steel connectionsnoted at one or more of the structure pipe connections. Install dielectric unions to prevent dissimilarmetals from contacting one another and the resulting corrosion.

    166. Waste Pipe Material: Cast iron. Lead. Galvanized piping. ABS plastic. PVC plastic. "Barnacles" on some of the cast iron drainpipes indicate deterioration of the pipes from the inside. The pipes should be replaced as directed by aplumber. One section of the cast iron pipe is cracked or split open. Replace. ABS to PVC noted at thefollowing: Tub drain. Recommend hubless connectors.

    172. Evidence of Leaks: Active leaking was noted at the following location: Drip at the rear hose bibb. At the open floor around thefloor drain in the basement.

    Water Heater182. Overflow Pipe: There was no overflow pipe/pressure relief pipe located on the water heater. A 3/4 inch copper/ orgalvanized pipe to extend to within 6 inches of the floor is recommended for safety.

    DOORSOther Exterior Doors197. Weather Strip: The weather strip is damaged or does not appear to fit the frame properly.

    200. Locks: The keyed deadbolt presents a hazard when the door is needed as an emergency exit. Install a deadboltwith an installed handle.

    INTERIORKitchen213. Stove/Oven: The stove worked properly, however no clamp is installed to prevent accidental tipping of the stove.

    Report prepared by Goshen Inspection Service2611626

    3 Final Report

  • Bedroom(s):229. Entry Door(s): The door to the front bedroom was not installed. No door was installed between the bedrooms. The door tothe rear bedroom does not close properly. This may indicate some movement of the wall.

    231. Walls: The plaster walls are damaged/deteriorated. Repair is indicated.

    BATHSFull Bath(s)250. Basin/Basin Fixtures: The fixture is cracked and leaks under the faucet.

    252. Under Sink Inspection: No shut offs were noted for the water. A leak as noted at the overflow drain channel. Repair as needed.

    255. Shower/Tub Enclosure: The bottom of the shower/tub enclosure has been water damaged.

    BASEMENT/FOUNDATIONUtility Basement276. Access Stairs: No handrail was installed at the lower part of the stairway. A safety railing should be installed from thebottom of the stairs to the top of stairs for safety.

    STRUCTUREDescription344. Smoke Detectors: Smoke detectors over 10 years old should be replaced. The design life of the detector is only 10 years. There were no carbon monoxide detectors noted in the structure. Recommend installation of COdetectors within 15' of each bedroom.

    Report prepared by Goshen Inspection Service2611626

    4 Final Report

  • Report IndexSITE ASSESSMENT 1

    EXTERIOR 2

    GARAGE 5

    ROOF/ATTIC 5

    MAJOR SYSTEMS 9

    DOORS 17

    INTERIOR 17

    BATHS 20

    BASEMENT/FOUNDATION 21

    STRUCTURE 23

  • Report prepared by Goshen Inspection Service2611626

    page 1 Final Report

    SITE ASSESSMENTThe foregoing is an opinion of the inspector of the general quality and condition of the structure at the time ofinspection. See Scope and Limiting Conditions at the front of the report.

    Site Assessment1. Street:

    Satisfactory.2. Curbs/Gutters No.3. Storm Drains: No.4. Sidewalks: Yes.5. AddressIdentification: Yes.6. Mailbox: Yes. A mailbox is present.7. Street Lights: Yes. Street lights are present.8. Fire hydrantNoted: Yes, a fire hydrant was noted in the proximity of the property.9. Driveway: The driveway is gravel and concrete.10. Walkways/Type: Concrete. The walkways are in satisfactory condition.11. Steps: None noted.12. Lawn: Satisfactory.13. Trees/Shrubs: The trees and shrubs are in satisfactory condition.14. InsectsNoted: Yes. Some insects were noted on the property. Specific notation was made.

  • Report prepared by Goshen Inspection Service2611626

    page 2 Final Report

    Off Site Assessment15. Trees/Shrubs: Satisfactory.16. Landscape: Satisfactory.17. AdjoiningPropertyCondition: Satisfactory.

    Fences and Gates18. Retainingwalls/Type: None noted.19. Fences: None noted.20. Gate(s): None noted.21. Locks/Latches: None noted.

    EXTERIORExterior Structure Perimeter

    22. FoundationType/Material: Concrete Block. 23. Vent Screens/

    Covers: N/A. 24. Visible

    Cracks:

    Cracks over 1/4 inch or larger at the left rear corner indicate excessive settling.Recommend further investigation by a qualified specialist.

    25. Evidence ofSettlement: Yes. There is evidence of settling at the left rear corner. 26. Site

    Drainage/Erosion: Satisfactory.

  • Report prepared by Goshen Inspection Service2611626

    page 3 Final Report

    27. Evidence ofInsects: No. No undesirable insects were noted. 28. Proper Earth

    to WoodClearance: Yes. Inspection around the perimeter of the structure does not show any

    contact of earth to wood. 29. Vegetation

    Clear fromStructure: Yes. There is no vegetation within two inches of structure.

    Exterior Structure 30. Exterior Wall

    Type: Vinyl siding over wood. 31. Siding

    Condition: Heat damage was noted to the vinyl siding next to the back door. One section ofsiding is loose at the top right wall.

    32. PaintedSurfaces: Peeling paint located at the following locations: At some trim. Recommend

    scraping. Prime and paint as needed to protect the wood from the elements. 33. Caulking

    Structure: Satisfactory. 34. Eaves/Soffit

    Area/Type: Aluminum. Satisfactory. 35. Fascia

    Boards/Type: Aluminum. Satisfactory. 36. Trim: Satisfactory. 37. Window

    Wells and/orwindow sills: The window sills are in satisfactory condition. 38. Predominant

    Window Type: Double Hung Wood. Satisfactory. 39. Window

    Latches/Locks: Two or more of the windows do not open. Appear to be painted shut. The sashcords are broken/missing on one window. Structures of this age often havebroken/missing sash cords.

    40. Glaze/CaulkWindows: Additional caulking/glazing needed on one or more windows to provide weather

    protection and to secure the glass in the window frame. 41. Window

    Glass: There are one or more broken/cracked window panes noted. Replace asneeded. Specific location was: One basement window.

    42. Storm/Screen Windows: One of the storm windows was missing in the living room. Storm windows

    should be installed for energy savings. 43. Security

    Lights: No. 44. Porch

    Pillars: N/A.

  • Report prepared by Goshen Inspection Service2611626

    page 4 Final Report

    Deck/Patio/Porch 48. Deck/Patio/

    Porch Type/Foundation: Not visible. 49. Deck/Patio/

    Porch SupportPosts/Type: Concrete block. Satisfactory. 50. Deck/Patio/

    Porch Decking: Satisfactory. 51. Deck/Patio/

    Porch Beams andJoists: N/A. 52. Steps/

    Handrails: Recommend installing a handrail at the steps for safety. 53. Deck/Patio/

    Porch Railing: None at the front porch. Lack of banister/railing are a major cause of householdaccidents. All elevated decks/patios should have sturdy protective banisters/railings. Consideration should be given to installing a safety railing.

    54. ElectricalService to Deck/Patio: No. 55. Deck/Patio

    Lights: Satisfactory. The lights appear to provide adequate lighting.

    Utility Connections 56. Electrical

    Service: Overhead. The insulator securing the service line to the house has pulled loose.Contact the service provider for repair.

    57. Gas Service: Natural. 58. Water

    Source: City. 59. Water Meter

    Location: Front yard. 60. Water

    shutoff: Front of the basement. 61. Cable TV

    Service: Overhead. 62. Sewer: City. 63. Sewer Line

    Clean-out: Rear of the basement. 64. Telephone

    Lines: Overhead. 65. Overhead

    Service Lines: Satisfactory.

  • Report prepared by Goshen Inspection Service2611626

    page 5 Final Report

    GARAGECondition/Type

    66. Type ofGarage: None.

    ROOF/ATTICRoof Main

    84. RoofSupport Type: 2x4 rafters at 24 inch centers at the rear entrance. Not determined on the main

    roof. 85. Roof Type: Intersecting Gable. 86. Roof Cover/

    Type: Asphalt Composition. 87. Cover

    MaterialCondition:

    Parts of the roof cover are deteriorated and in poor condition. The roof cover isapproaching the end of its economic life. Contact a licensed roofer for directedrepair.

    88. How ManyCovers: One cover?

  • Report prepared by Goshen Inspection Service2611626

    page 6 Final Report

    89. Moss/Debrison Roof:

    Moss/Mildew noted on the roof. Tree should be trimmed away from roof andtree branches can cause damage to the roof cover. Debris noted on roof.Debris should be kept clear of roof as it may cause roof to age prematurely.

    90. ExteriorChimneyCondition: Satisfactory. 91. Flashing: Tar sealant noted on/or the plumbing vent flashing. Tar sealant will require

    periodic maintenance (sealing). 92. Ridges: Satisfactory. 93. Valleys:

    One or more of the valleys are deteriorated. Repair/replace as needed.

  • Report prepared by Goshen Inspection Service2611626

    page 7 Final Report

    94. Ventilation:

    Gable Vents. The vents are blocked in the attic with plywood. Remove toprovide ventilation to the attic.

    95. Gutters: Aluminum. The section of the gutter at the left of the rear entryway is loose.Resecure as needed. The gutters need to be cleaned to prevent restricted flow.

    96.Downspouts: Two of the downspouts are incomplete or missing at the right rear. Replace the

    downspouts as needed. 97. Drains/

    Splash blocks: There were no drains/splashblocks noted at the right rear. They arerecommended to carry water away from structure.

    98. Roof Inspectfrom Underside: The inspector was unable to view the underside of the roof structure. 99. Exposed

    Rafters/Sheathing/Type: 1 inch board. Not visible. 100. Light Thru: Not determined.101. Indicationsof Leaking: Not determined.102. Soft/SpringySpots: No.103. Skylight: None.104. Roof CoverAge Appears ToBe: 18-20 years. 105. Average LifeExpectancy of aRoof Cover ofThis Type: Fiberglass or Asphalt or Composition: 18-20 years with proper care and

    maintenance.106. RoofEvaluated By: Walk Surface.

  • Report prepared by Goshen Inspection Service2611626

    page 8 Final Report

    Attic107. Attic Type: There is no access to the main attic.108. WholeHouse Fan: N/A.109. Insulation: Not determined.110. AccessLocation: None. Scuttle hole in the back hall. 111. Side-WallInsulation: Not Determined.112. Ventilation:

    See item #94. Stains from moisture condensing in the attic and some fungalgrowth indicate that there is not adequate ventilation of the attic. Installadditional vents to remove the moisture from the structure. Additional energysavings, moisture control in the attic, and extended roof life could be achievedby additional ventilation. Half of the ventilation should be installed low on theroof to provide a draw of air and half the ventilation should be installed high onthe roof to provide an exhaust for the air.

    113. Duct work/Piping: Not visible.114. InaccessibleAreas: There was no access to the main attic. It could not be inspected. There should

    be access to all attic areas.115. AtticEvaluated By: Inaccessible.

  • Report prepared by Goshen Inspection Service2611626

    page 9 Final Report

    MAJOR SYSTEMSGas Service

    116. SystemsPresent: Stove. Furnace. Water heater.117. MeterLocation: Right side of house.118. Gas OdorsDetected: There were no gas odors detected using a combustible gas detector.119. Vents/Exhaust:

    Excessive condensation was noted at the furnace vent connectors. The pipe isprobably oversized. Replace as needed.

    120. Gas Piping: There was no sediment trap on the gas line to the water heater. Recommendinstallation. The purpose of a sediment trap is is to act as a trap to stop anymoisture or sediment from entering a gas control valve and causing a seal tostick open allowing gas to enter the burner when the appliance is off. Thiscould cause a burst of accumulated gas when the appliance lights.

  • Report prepared by Goshen Inspection Service2611626

    page 10 Final Report

    121. Service Shutoff Location(s): At the Stove. There were no gas shut offs noted at the furnace and water

    heater. Recommend installing.

    Heating System122. SystemType/Information: Gas fired forced air. Trane TUD 060C924K4 Serial # 4313 1BT1G

    Manufactured 7-2004 60,000 BTU.123. Location ofFurnace: Basement.124. ThermostatLocation: Living room.125. On/OffCheck: The system was tested and appears to operate properly.126. OperationNoise: Satisfactory. 127. Filter Size: 16x25x1.128. FilterCondition: The filter needs to be changed/cleaned.129. ElectronicFilter System: No.130. Vents/Returns/Piping: Satisfactory.131. Ducts: Satisfactory.132. Non-heatedLiving Areas: None noted.133. ReturnTemperature atAir Handler: 58°.134. AirTemperature afterpassing throughheat exchanger: 113°.135. Temperaturedifferential: 55°.

    Electrical System146. Panel/SubPanelLocation(s): Basement.147. Location ofServiceDisconnect: The main and range fuses must both be pulled to disconnect all power. 148. Service Size(amps): 100 amp service.149. Voltage: 120/240 volt.150. OverCurrent Devices: Overload protection is provided by fuses.

  • Report prepared by Goshen Inspection Service2611626

    page 11 Final Report

    151. Service toPanel: #3 copper.152. BranchCircuits:

    Nonmetallic sheathed cable -copper. No junction box was installed at an outletin the basement. Note heat damaged insulation on one leg of a 240 volt circuit.There is also a broken outlet in the front bedroom. Extension cord wiring to therear exterior light. Recommend hard wiring an outlet at the appliance.

    153. PanelCover: Satisfactory.154. Panel CoverRemoved: The panel cover was removed.155. Breaker/FuseConfiguration: No factory linked handles on one pair of 240 volt fuses. Install factory linked

    handles. 156. Wire OverCurrentCompatibility: There is some question as to the wire over current compatibility. This condition

    may present a hazard. Specific notation is made. #12 wire on 30 amp fuses.Recommend 20 amp.

  • Report prepared by Goshen Inspection Service2611626

    page 12 Final Report

    157. GFI Outlets: Current electrical code requires that GFIs be located in areas with the greatestrisk of electric shock, at the kitchen counters, in bathrooms, at Hydromassagetub, in unfinished basements, in garages and any outside receptacle(s) and inthe crawl space (if applicable). Consider installing for safety.

    158. GroundingSystem in Place:

    A makeshift ground was noted at the furnace. The inspector has discovered oneor more three prong female outlets that do not have the correct ground.Specific notation was made. All in the living room. In the bedrooms. In thebathroom. Grounding can be accomplished by: Installing a ground wire. Checkfor ground wire at the receptacle and hook up. Installing a GFI (safety groundoutlet) will provide safety without a ground wire. Choosing to return to a twoprong ungrounded type receptacle also is an option. Also note a broken outlet inthe front bedroom. Hot/Neutral reversed at the following receptacles. To theright of the kitchen sink. At the washer. Rewire as needed.

    159. TiredReceptacles: None noted.160. MysterySwitches NotedAt: In the kitchen and back hall.

  • Report prepared by Goshen Inspection Service2611626

    page 13 Final Report

    161. OpenSplices/OpenJunction Boxes:

    The inspection has discovered open splices. All splices should be in mountedjunction boxes with covers and clamps on all wires. One or more in the backhall attic. One or more in the basement. There were one or more junction boxesnoted that are in need of covers. Recommend installing covers.One or more inthe basement.

    162. DoubleTapping Noted: Double tapping was noted in the electrical panel. Specific notation is made., T

    one fuse. There is no space available in the panel. Recommend installing anew sub panel or main panel.

    163. ServiceGround Verified: The service ground is provided by bonding the service conduit to the driven

    ground rod.

    Plumbing System164. Service Sizeto Structure: Three quarters of an inch.

  • Report prepared by Goshen Inspection Service2611626

    page 14 Final Report

    165. StructurePipe Material:

    Copper. CPVC plastic/PVC plastic. Galvanized piping. There were copper togalvanized/steel connections noted at one or more of the structure pipeconnections. Install dielectric unions to prevent dissimilar metals fromcontacting one another and the resulting corrosion.

  • Report prepared by Goshen Inspection Service2611626

    page 15 Final Report

    166. Waste PipeMaterial:

    Cast iron. Lead. Galvanized piping. ABS plastic. PVC plastic. "Barnacles" onsome of the cast iron drain pipes indicate deterioration of the pipes from theinside. The pipes should be replaced as directed by a plumber. One section ofthe cast iron pipe is cracked or split open. Replace. ABS to PVC noted at thefollowing: Tub drain. Recommend hubless connectors.

    167. PipeRumble: No.168. SurgeBangs: No.169. MineralDeposits: None noted.170.Encrustations: None noted.171, Hot WaterPipe Insulation: None noted.

  • Report prepared by Goshen Inspection Service2611626

    page 16 Final Report

    172. Evidence ofLeaks:

    Active leaking was noted at the following location: Drip at the rear hose bibb. Atthe open floor around the floor drain in the basement.

    173. Interior/Exterior WaterFlow: Satisfactory.174. PressureReading: 60 psi.175. Soft WaterSystem: None noted.176. FilterSystem: None noted.

    Water Heater177. Location/Type: Basement. Gas water heater. Bradford White MI30T6LN10 Serial #

    SC1310464 32,000 BTU.178. Size Main/Auxiliary: 30 gallon.179. Evidence ofLeaks: None noted.180. Evidence ofEncrustations: None noted.181. SafetyValve: The water heater is equipped with a safety valve.182. OverflowPipe: There was no overflow pipe/pressure relief pipe located on the water heater. A

    3/4 inch copper/ or galvanized pipe to extend to within 6 inches of the floor isrecommended for safety.

    183. InsulationBlanket: None noted.

  • Report prepared by Goshen Inspection Service2611626

    page 17 Final Report

    184. Installation: The installation of the water heating system appears to be satisfactory.

    DOORSMain Entry Door

    185. Main EntryDoor Type: Steel.186. CorrectApplication: Yes. The main entry door appears to be of proper construction and application.187. Door Fit: Satisfactory.188. WeatherStrip: Some light was noted through the weather stripping on the door. Replace as

    needed.189. FinishCondition: Satisfactory.190. Locks: Satisfactory.191. Storm/Screen Door: N/A.192. Door Chime: None.193. Lighting: The lighting at the entrance does not operate properly. Bulb?

    Other Exterior Doors194. Location/Type: Back hall to the back yard - Steel and glass.195. CorrectApplication: Yes. The secondary structure entry doors appear to be of proper construction

    and application.196. Door Fit: Satisfactory.197. WeatherStrip: The weather strip is damaged or does not appear to fit the frame properly.198. FinishCondition: Satisfactory.199. Storm/Screen Door: None.200. Locks: The keyed deadbolt presents a hazard when the door is needed as an

    emergency exit. Install a deadbolt with an installed handle. 201. SlidingGlass/Safety: It appears that the door glass is properly identified as safety plate or is properly

    provided with safety film and is in good condition.

    INTERIORKitchen

    202. Location: Right rear. 203. Windows: Satisfactory.204. Lighting: Satisfactory. The lighting in the kitchen appears to be adequate.

  • Report prepared by Goshen Inspection Service2611626

    page 18 Final Report

    205. Floor CoverCondition: Satisfactory. The floor covering in the kitchen area appears to be providing

    adequate protection.206. Walls: Satisfactory.207. Ceiling: Satisfactory.208. Under SinkInspection: Satisfactory. No shut offs were noted for the water.209. Faucets/Spouts Leak: No.210. DrainsClear:

    The drain appears to be unvented and poorly plumbed. There is functionaldrainage.

    211. Water forRefrigerator: No. A water line would have to be installed to provide water for refrigerator.212. Stove/OvenType: Gas.213. Stove/Oven: The stove worked properly, however no clamp is installed to prevent accidental

    tipping of the stove.

  • Report prepared by Goshen Inspection Service2611626

    page 19 Final Report

    214. Built-InMicrowave: None present.215. CounterTops Condition: Satisfactory.216. WoodworkFinishes: Satisfactory.217. CabinetsCondition: Satisfactory.218. DishwasherOperation: N/A.219. GarbageDisposalOperation: N/A.

    Laundry Area220. Washer/Dryer Hook-up: Yes. There are washer and dryer hookups.221. Gas Service: No.222. DryerElectrical Service240v: Yes.223. Floor/WallsCondition: Satisfactory.224. LaundryBasin/BasinFixtures: None present.225. Lighting: Satisfactory.226. DryerVentilationSystem: Satisfactory.227. DrainFunctional: Floor drain- The washer drains to a floor drain.

    Bedroom(s):228. Location: Left front. Left rear. 229. EntryDoor(s): The door to the front bedroom was not installed. No door was installed between

    the bedrooms. The door to the rear bedroom does not close properly. This mayindicate some movement of the wall.

    230. Flooring: Some worn flooring was noted. 231. Walls: The plaster walls are damaged/deteriorated. Repair is indicated.232. Ceiling: Satisfactory. Minor cracks noted in the ceiling.233. Closets/Closet Doors: Satisfactory.234. Lighting: The lighting in the bedrooms appears to be adequate.

  • Report prepared by Goshen Inspection Service2611626

    page 20 Final Report

    235. Windows: Satisfactory.

    Other Rooms:236. Location/Type: Right front -living room. 237. EntryDoor(s): Satisfactory. 238. Flooring: Some worn flooring was noted. 239. Walls: Minor cracks noted in the walls.240. Ceiling: Satisfactory.241. Closet(s): Satisfactory.242. InteriorStairways: N/A.243. Lighting: Satisfactory. The lighting in the other rooms appears to be adequate.244. Windows: Satisfactory.

    BATHSFull Bath(s)

    245. Location(s): First floor hall.246. Entry Door: Satisfactory.247. Ceiling/Walls: Satisfactory.248. Floor CoverCondition: Satisfactory.249. MildewNoted: No.250. Basin/BasinFixtures: The fixture is cracked and leaks under the faucet.251. Basin Drain: Functional.252. Under SinkInspection: No shut offs were noted for the water. A leak as noted at the overflow drain

    channel. Repair as needed. 253. Shower/TubFixtures: The spout diverter does not divert the full flow to the shower head.254. Shower/TubDrain: Functional.255. Shower/TubEnclosure: The bottom of the shower/tub enclosure has been water damaged.256. WaterResistant WallCover: Satisfactory.257. Caulking -Water ExposedAreas: Satisfactory. The caulking in the bathroom appears to be providing adequate

    protection. Water leaking through non-sealed areas can cause structuraldamage. Caulking should be maintained to continue protection.

  • Report prepared by Goshen Inspection Service2611626

    page 21 Final Report

    258. SafetyHazard fromGlass: No. There is no safety hazard from glass. The inspector noted a safety seal or

    there was no glass to be a hazard.259. Toiletfixtures: Satisfactory.260. Ventilation: Satisfactory. Proper ventilation can be satisfied with either a window or

    ventilation fan/system.261. Heat: Yes.262. Lighting: Satisfactory. The lighting in the bath appears to be adequate.

    BASEMENT/FOUNDATIONUtility Basement

    275. AccessLocation: Steps off of the kitchen. 276. AccessStairs:

    No handrail was installed at the lower part of the stairway. A safety railingshould be installed from the bottom of the stairs to the top of stairs for safety.

    277. Lighting: Satisfactory.278. Living Area: No.279. Moisture: Minor seepage was evident. Some water penetration is normal for this type and

    age of structure.280. Ventilation/Insulation: Satisfactory.281. Odor: No.282. Evidence ofInsects and/orpests: No. A visual inspection of the basement has revealed no undesirable insects.283. Utilities: Furnace. Water Heater. Electrical Panel.

  • Report prepared by Goshen Inspection Service2611626

    page 22 Final Report

    284. Floors/Walls: Satisfactory. The floor/walls of the basement are adequately providing their

    desired function.285. Cracks over1/4 Inch:

    Yes. Cracks in excess of 1/4 inch were evident at the left rear of the basement.This may indicate excessive settling. We recommend further investigation by aqualified specialist.

    286. ExposedDucts/Piping: Yes. There is exposed ductwork/piping that was examined. 287. Beams: Satisfactory.288. BearingWalls: N/A.289. Joists/Trusses: Satisfactory.290. Piers/Posts: N/A.291. SumpPump: No.

    Raised Foundation314. AccessLocation: Front of the basement.315. AccessSize: Satisfactory.316. Clearance: Satisfactory.317. InaccessibleAreas: None. All areas were accessible.318. Debris/Trash: No.319. Moisture: Satisfactory.320. VaporBarrier: None.

  • Report prepared by Goshen Inspection Service2611626

    page 23 Final Report

    321. InsulationNoted: None noted.322. Ventilation: None.323. Evidence ofInsects and/orpests: There is evidence of previous rodent or small animal infestation.324. DeterioratedWood: No.325. Proper Earthto WoodClearance: Yes. Inspection of the crawl space areas shows proper earth to wood

    clearance.326. WoodMembers: Satisfactory.327. ExposedDuctwork/Piping: Satisfactory.328. Evidence ofCracks - StemWalls: See #285.329. Separationover 1/4 Inch: Yes. Cracks over 1/4 inch or larger may indicate excessive expansion or

    settling. We recommend further investigation by a qualified specialist.330. Sill PlateAnchors: N/A.331. ConcreteColumns: N/A.332. Beams: Satisfactory.333. BearingWalls: N/A.334. Joists/Trusses: Satisfactory.335. Piers/Posts: No piers/posts were present. 336. SumpPump: No.

    STRUCTUREDescription

    337. StructureFaces: North.338. Date Built: Unknown.339. Bedrooms: Two.340. Bathrooms: One.341. OtherRooms: One.342. RemodelEvident: No.

  • Report prepared by Goshen Inspection Service2611626

    page 24 Final Report

    343. RepairsNoted: No.344. SmokeDetectors: Smoke detectors over 10 years old should be replaced. The design life of the

    detector is only 10 years. There were no carbon monoxide detectors noted inthe structure. Recommend installation of CO detectors within 15' of eachbedroom.

    345. Storage: Vacant.346. Alarm/Security System: No.347. SuspectAsbestos Noted: No.348. Lead BasedPaint Suspected: Yes. Due to age of structure only. 359. WeatherConditions: Partly cloudy 38°.