heating and cooling with mini splits in the northeast

13
© buildingscience.com Heating and Cooling with Mini Splits in the Northeast Kohta Ueno September 24, 2014 2014 EEBA Mini Splits in Northeast 2 © buildingscience.com Background Supporting Zero Energy Ready Homes Transformations, Inc. currently building net-zero homes in Massachusetts Mini split heat pumps (MSHPs) part of builder’s strategy: tradeoffs Single point of heating/ cooling on each floor Researching how well does this work? How widely can it be applied? 2014 EEBA Mini Splits in Northeast 4 © buildingscience.com Full Report Available 140 page brick of a report Reports has details, presentation is overview Currently in final review If taking notes… relax EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014 Ueno © buildingscience.com 1 of 13

Upload: others

Post on 13-Nov-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Heating and Cooling with Mini Splits in the Northeast

© buildingscience.com

Heating and Cooling with Mini Splitsin the Northeast

Kohta Ueno

September 24, 2014

2014 EEBA Mini Splits in Northeast2

© buildingscience.com

Background

2014 EEBA Mini Splits in Northeast3

© buildingscience.com

Supporting Zero Energy Ready Homes Transformations, Inc.

currently building net-zero homes in Massachusetts

Mini split heat pumps (MSHPs) part of builder’s strategy: tradeoffs

Single point of heating/ cooling on each floor

Researching how well does this work? How widely can it be applied?

2014 EEBA Mini Splits in Northeast4

© buildingscience.com

Full Report Available 140 page brick of a report Reports has details,

presentation is overview Currently in final review If taking notes… relax

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 1 of 13

Page 2: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast5

© buildingscience.com

Transformations, Inc. Construction Triple glazed windows 1 ACH 50 typical Tankless DHW

High density spray foaminsulation

4” concrete slab

2” XPS rigid insulation

10” x 20” concretefooting

Compacted fill

High density spray foaminsulation

10” concrete�foundation wall

Dampproofing below grade

Free-drainingbackfill

Capillary break: damp-proofing, cementitiouscoating, or membrane-applied to top of footing

Filter fabric

Gravel (no fines)

Perforatedperimeter drain

Capillary break applied to�top of foundation wall

6 mil polyethylene

8” min.

(2) 2x6 P.T. sill

2x10 rim joist

2x4 P.T. studs @ 24” o.c.(optional)

2x4 studs @ 16” o.c.

Intumescent paint

1/2" gypsum board (optional)

ZIP System® roof sheathing

18" cellulose�insulation

Asphalt shingles

Fully-adhered membrane

Siding

1/2" gypsum board

ZIP System® wall sheathing

1/2” gypsum board

12” low density spray foamcavity insulation (R-47)

2x4 studs @ 16” o.c.

Low density spray foam atrim joist

Baffle

2014 EEBA Mini Splits in Northeast6

© buildingscience.com

Mini-Split Heat Pumps (MSHPs) Installations in Asia/Europe for 40+ years More expensive per ton BUT if ductless… Mitsubishi equipment: full heat capacity @ -5ºF Rated to -13ºF, still operating at -20ºF (H2i/HyperHeat)

Modulates to meet load Best performance @ part load (worst @ full load)

COPs in 2.5-3 range in cold winter conditions

0

1

2

3

4

5

0 10 20 30 40 50 60

Coefficient of P

erform

ance [‐]

Outdoor Temperature (F)

Maximum Capacity

Rated Capacity

2014 EEBA Mini Splits in Northeast7

© buildingscience.com

Builder’s MSHP Experience Low load houses: 10-18 kBtu/hour heating All production has MSHPs as single heat source

(one per floor, ~1800 sf houses typical) Savings from mechanicals into enclosure ~$15,000 enclosure upgrade cost (∆$) ~$5000 savings on simplified mechanicals (∆$)

Trouble-free operation—few equipment callbacks

2014 EEBA Mini Splits in Northeast8

© buildingscience.com

Monitoring Overview

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 2 of 13

Page 3: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast9

© buildingscience.com

Monitoring Timeline

Eight houses, two sites Mixed monitoring package—various sensors

(T/RH, doors, power) at different houses

0

500

1000

1500

HDD Ba

se 65 F

2014 EEBA Mini Splits in Northeast10

© buildingscience.com

Monitoring Package

Interior temperature/RH MSHP Electrical Use

Door Open/Closed StatusDoor Open/Closed Status

2014 EEBA Mini Splits in Northeast11

© buildingscience.com

Monitoring Package: 8 Houses, 2 Sites

Temperature/RH Sensor Door Closure Sensor

N

2014 EEBA Mini Splits in Northeast12

© buildingscience.com

Equipment Capacity

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 3 of 13

Page 4: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast13

© buildingscience.com

Did MSHPs Meet Setpoint? (Capacity) Heat pumps as a single source of heating in

Massachusetts (Zone 5A) (design T +2, -2ºF) NREL testing (2011)—matches equipment specs Monitored data: no sign of low equipment

capacity (i.e., long runtimes/high wattage and declining indoor temperature)—excess available

Included winter 2013-2014 (“Polar vortex”): 6730 HDD 65ºF vs. 6220 HDD 65ºF normal

When temperature was down, unit wasn’t running (or other issues)

2014 EEBA Mini Splits in Northeast14

© buildingscience.com

Hourly Power Use vs. Temperature

Spare Capacity @ Design

2014 EEBA Mini Splits in Northeast15

© buildingscience.com

Equipment Sizing Oversizing provides heating capacity at low Ts Oversizing not as big of a problem with MSHPs—

modulating.

Location Lot A.G.

Square Feet

Heating Design Load kBtu/hr

Installed Equipment Capacity kBtu/hr

Oversizing Factor

Devens 3 1728 16.8 25.0 149% Devens 4 1728 16.3 25.0 153% Devens 7 1952 18.2 37.5† 206% Devens 8 1524 13.0 25.0 192%

Easthampton 13 1728 12.1 22.0 182% Easthampton 17 1239 11.0 11.0 [22.0]‡ 100% [200%] Easthampton 23 1132 10.0 11.0 [22.0]‡ 110% [220%] Easthampton 30 2266 18.1 22.0 [33.7]* 121% [186%]

Original installed capacity [Retrofitted Equipment Capacity]

2014 EEBA Mini Splits in Northeast16

© buildingscience.com

Operating Patterns

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 4 of 13

Page 5: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast17

© buildingscience.com

0

500

1000

1500

2000

2500

‐20

‐10

0

10

20

30

40

50

60

70

80

11/2/12 11/22/12 12/12/12 1/1/13 1/21/13 2/10/13 3/2/13 3/22/13 4/11/13 5/1/13

Hourly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) TNorth BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

Temperature & Power Use Plot

Varying wattage draw-modulation First vs. second floor; comparison to max 2000 W

2014 EEBA Mini Splits in Northeast18

© buildingscience.com

0

500

1000

1500

2000

2500

‐20

‐10

0

10

20

30

40

50

60

70

80

11/2/12 11/22/12 12/12/12 1/1/13 1/21/13 2/10/13 3/2/13 3/22/13 4/11/13 5/1/13

Hourly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) TNorth BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

Temperature & Power Use Plot

Varying wattage draw-modulation First vs. second floor; comparison to max 2000 W

0

500

1000

1500

2000

2500

‐20

‐10

0

10

20

30

40

50

60

70

80

11/2/12 11/22/12 12/12/12 1/1/13 1/21/13 2/10/13 3/2/13 3/22/13 4/11/13 5/1/13

Hourly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) TNorth BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

2014 EEBA Mini Splits in Northeast19

© buildingscience.com

0

500

1000

1500

2000

2500

‐20

‐10

0

10

20

30

40

50

60

70

80

11/2/12 11/22/12 12/12/12 1/1/13 1/21/13 2/10/13 3/2/13 3/22/13 4/11/13 5/1/13

Hourly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) TNorth BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

Temperature & Power Use Plot

Varying wattage draw-modulation First vs. second floor; comparison to max 2000 W

0

500

1000

1500

2000

2500

‐20

‐10

0

10

20

30

40

50

60

70

80

11/2/12 11/22/12 12/12/12 1/1/13 1/21/13 2/10/13 3/2/13 3/22/13 4/11/13 5/1/13

Hourly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) TNorth BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

0

500

1000

1500

2000

2500

‐20

‐10

0

10

20

30

40

50

60

70

80

11/2/12 11/22/12 12/12/12 1/1/13 1/21/13 2/10/13 3/2/13 3/22/13 4/11/13 5/1/13

Hourly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) TNorth BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

2014 EEBA Mini Splits in Northeast20

© buildingscience.com

Temperature & Power Use Plot-Cooling

Second floor doing most of cooling Started running first floor unit—more even Ts?

0

200

400

600

800

1000

1200

1400

1600

1800

2000

0

10

20

30

40

50

60

70

80

90

100

5/1/13 5/21/13 6/10/13 6/30/13 7/20/13 8/9/13 8/29/13

Hou

rly Electrical Use (W

h)

Tempe

rature (F)

Exterior T First Floor T Second Hall T Front BR T Mid BR T Master BR T 1st Floor Wh 2nd Floor Wh

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 5 of 13

Page 6: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast21

© buildingscience.com

Monthly Energy Use

First winter—basement uninsulated First floor vs. second floor unit

0

200

400

600

800

1000

1200

Dec

Jan

Feb

Mar Apr

May Jun Jul

Aug

Sep

Oct

Nov Dec

Jan

Feb

Mar Apr

May Jun Jul

Aug

Sep

Oct

Nov Dec

Jan

Feb

Mar

2011 2012 2013 2014

kWh/mon

th

Sum of 2nd Floor kWh

Sum of 1st Floor kWh

Values

2014 EEBA Mini Splits in Northeast22

© buildingscience.com

Simplified (2-Point) Space Conditioning

2014 EEBA Mini Splits in Northeast23

© buildingscience.com

Simplified Space Conditioning Takes advantage of low heat loss enclosure

(“superinsulated buildings”) Heat “filters through” interior (partitions, floors,

open doorways, interior gains) as fast as is lost through exterior shell

Previous work: best with smaller houses, bedroom doors open often, constant setpoint

Being “completely safe”—with a fully ducted system—you still see temperature variations between spaces (but it is “standard practice”!)

2014 EEBA Mini Splits in Northeast24

© buildingscience.com

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

0

5000

10000

15000

20000

25000

0‐1 1‐2 2‐3 3‐4 4‐5 5‐6 6‐7 7‐8 8‐9 9‐10 10+

Cumulative %

Freq

uency (# Hou

rs)

Maximum ΔT Between Rooms

Frequency Cumulative %

ACCA Manual RS (4ºF Difference) Highest - lowest temperature Omitted bonus room and basements

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

0

5000

10000

15000

20000

25000

0‐1 1‐2 2‐3 3‐4 4‐5 5‐6 6‐7 7‐8 8‐9 9‐10 10+

Cumulative %

Freq

uency (# Hou

rs)

Maximum ΔT Between Rooms

Frequency

Cumulative %

96% of hours below 4ºF requirement

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 6 of 13

Page 7: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast25

© buildingscience.com

Simplified Space ConditioningLocation Lot Square Feet % Under 4°F Sub-Case Devens 3 67%

73% 19% 91% 96%

Full data set; bonus room omitted Winter 2012-2013, MSHP on Winter 2013-2014, MSHP on

Summer 2013 Summer 2012

Easthampton 13 1795 96% Full data setEasthampton 17 1348 86%

95% Full data set

After 2nd MSHP retrofittedEasthampton 23† 1620 75%

82% Full data set

After 2nd MSHP retrofittedEasthampton 30 2151 - Not analyzed (1 head per bedroom) Many houses 70%+ under 4ºF, complaints rare Devens 4, 7, 8 not analyzed—missing data Summer performance better than winter—BUT

low SHGC, glazing ratios

2014 EEBA Mini Splits in Northeast26

© buildingscience.com

Two Stories, One MSHP

2014 EEBA Mini Splits in Northeast27

© buildingscience.com

One Mini Split, Two Floors? Design Heating & Cooling Loads: 11 kBtu/hr heating (left); 10 kBtu/hr heating (right) 12.5 kBtu/hr mini split heating capacity at 5 F

Second floor unit rarely runs (20 F days) Design: single mini-split head on first floor

2014 EEBA Mini Splits in Northeast28

© buildingscience.com

One Mini Split, Two Floors?

Comfort problems even with “redistribution fan” (continuous exhaust fan from MSHP to master bedroom, ~40 CFM)

Redistribution fan—edge cases vs. bad cases

0

500

1000

1500

2000

2500

20

30

40

50

60

70

80

90

100

5/6 5/26 6/15 7/5 7/25 8/14 9/3 9/23

Hou

rly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Stairs T Kids BR (Up) T Master BR (Up) T 1st Floor Wh 2nd Floor Wh

2nd floor MSHP added

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 7 of 13

Page 8: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast29

© buildingscience.com

Retrofitted MSHPs on 2nd Floor

Thermal buoyancy matters for distribution, even in very airtight houses (~1.0 ACH 50)!

1 MSHP & 2 floors = choose heating or cooling Or a really big redistribution system!

2014 EEBA Mini Splits in Northeast30

© buildingscience.com

Bonus Room Geometry

2014 EEBA Mini Splits in Northeast31

© buildingscience.com

Comfort Complaint Many superinsulated/airtight houses running

successfully with two mini split heads Comfort complaint in Central MA house Custom house plan (first floor bump out, bonus rm)

View from Southeast View from Northeast

2014 EEBA Mini Splits in Northeast32

© buildingscience.com

Comfort Complaint Downstairs Ts even Constant setpoint Front BR warmest Rear BR colder Bonus room ~50 F

(homeowner) Worse w. garage open BR doors open/closed ~300 CFM 50 (0.8 ACH 50) Not capacity problem: 2nd floor = 6200 Btu/hour load

View from East (front)

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 8 of 13

Page 9: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast33

© buildingscience.com

Comfort Complaint

Mini split head

2.3:1 exterior: interior

4:1 exterior: interior2:1 exterior: interior

Mini split head

Can calculate room relative heat loss/gain at various outdoor temperatures (SWA work)

2014 EEBA Mini Splits in Northeast34

© buildingscience.com

Temperature & Door Status Monitoring

But open door data—many hours within 4F of hallway—but warmer exterior temperatures

0

20

40

60

80

100

120

140

0

10

20

30

40

50

60

70

80

2/14 2/19 2/24 3/1 3/6 3/11

Tempe

rature (F)

Exterior T First Floor T Front BR T Second Hall T Rear Bedroom (MBR) T

Bonus Room T Front BR Door Rear BR (MBR) Door Bonus Room Door

Bonus RoomRear bedroom

2014 EEBA Mini Splits in Northeast35

© buildingscience.com

Mini split “blowing into open door?”

2014 EEBA Mini Splits in Northeast36

© buildingscience.com

Bonus Room Not Always Problem Comfort complaint → bonus room ≠

Bonus room → comfort complaint!

0

500

1000

1500

2000

2500

3000

3500

‐10

0

10

20

30

40

50

60

70

80

90

12/1/13 12/6/13 12/11/13 12/16/13 12/21/13 12/26/13 12/31/13 1/5/14 1/10/14 1/15/14

Hou

rly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) T

North BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 9 of 13

Page 10: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast37

© buildingscience.com

Bonus Room Not Always Problem Comfort complaint → bonus room ≠

Bonus room → comfort complaint!

0

500

1000

1500

2000

2500

3000

3500

‐10

0

10

20

30

40

50

60

70

80

90

12/1/13 12/6/13 12/11/13 12/16/13 12/21/13 12/26/13 12/31/13 1/5/14 1/10/14 1/15/14

Hou

rly Electric

al Use (W

h/ho

ur)

Tempe

rature (F)

Exterior T First Floor T Second Hall T South Rear BR T Master BR (Front) T

North BR T Bonus Rm T 1st Floor Wh 2nd Floor Wh

2014 EEBA Mini Splits in Northeast38

© buildingscience.com

On-Off Temperature Control/Setbacks

2014 EEBA Mini Splits in Northeast39

© buildingscience.com

Constant-Setpoint Operation

MSHP works at best efficiency—no big “slug of heat” required (max ~1000 W)

Single point works best @ constant—heat “filters out” from the core to exterior rooms

0

200

400

600

800

1000

1200

1400

1600

1800

2000

0

10

20

30

40

50

60

70

80

90

100

2/1 2/3 2/5 2/7 2/9 2/11 2/13 2/15

Hourly Electric

al Use (W

h)

Tempe

rature (F)

Exterior T

First Floor T

Second Hall T

Front BR T

Mid BR T

Master BR T

1st Floor Wh

2nd Floor Wh

2014 EEBA Mini Splits in Northeast40

© buildingscience.com

On-Off Setpoint Operation

Temperature swings between 60 and 70 F System turned off, “coasting” down, then max

capacity Many hours near maximum capacity (2000 W)

0

500

1000

1500

2000

2500

0

10

20

30

40

50

60

70

80

90

100

2/1 2/3 2/5 2/7 2/9 2/11 2/13 2/15

Mini Split Electrical Use (k

Wh)

Tempe

rature (F)

Exterior T

First Floor‐Liv Rm T

First Floor‐Closet T

Master Bedrm T

First Flr BR T

Mini Split 1st

Mini Split 2nd

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 10 of 13

Page 11: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast41

© buildingscience.com

On-Off vs. Constant Setpoint Energy Use

Hourly kWh vs. outdoor temperature Constant setpoint—max ~1500 W for hour On-off—many hours 2000 W+ Little relationship with outdoor T

0.0

0.5

1.0

1.5

2.0

2.5

‐20 0 20 40 60 80 100 120

Hou

rly kWh Sum (A

vg kW)

Outdoor T (F)

1st Floor kWh

0.0

0.5

1.0

1.5

2.0

2.5

‐20 0 20 40 60 80 100 120

Hou

rly kWh Sum (A

vg kW)

Outdoor T (F)

1st Floor kWhConstant Setpoint On-Off Setpoint

2014 EEBA Mini Splits in Northeast42

© buildingscience.com

On-Off vs. Constant Setpoint Energy Use Setbacks and on/off usually “done to save energy” Superinsulation + airtightness → less benefit from

setback (less energy lost during “off” cycle) MSHP → recovery from setback (max capacity) is

lowest efficiency operation, at worst time of day Winter 2012-2013 heating use: 1200 sf constant setpoint = 1385 kWh 1100 sf on-off operation = 2561 kWh On off operation—worst outlier vs. REM/Rate

prediction (157% of prediction)

2014 EEBA Mini Splits in Northeast43

© buildingscience.com

Single Floor Distribution Issues

2014 EEBA Mini Splits in Northeast44

© buildingscience.com

Single Floor Distribution

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 11 of 13

Page 12: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast45

© buildingscience.com

Single Floor Distribution

Think about the path that thermally buoyant or denser/cooled air will take!

In general, open floor plans had few problems—point air leak issue instead

2014 EEBA Mini Splits in Northeast46

© buildingscience.com

Other Items

2014 EEBA Mini Splits in Northeast47

© buildingscience.com

MSHP Heads per Square Foot Square footage sizing methods are suspect But square footage per head—provided for

reference Not intended as “general guidance”

Model AG Square Feet # MSHPs sf/MSHP Victorian 1728 2 864

Farmhouse 1728 2 864 Custom Saltbox 1952 3 651

Ranch 1524 2 762 Farmhouse 1728 2 864

Small Saltbox 1239 1 [2] 1239 [620] Cottage 1132 1 [2] 1132 [566]

Custom Home 2266 2 [4] 1133 [567] Original installed capacity [Retrofitted Equipment Capacity]

2014 EEBA Mini Splits in Northeast48

© buildingscience.com

Snow Blockage Heat pumps: risks of snow blockage of outdoor

unit cutting heating capacity in winter No evidence of issues at two Zone 5A sites Riser blocks or wall brackets recommended

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 12 of 13

Page 13: Heating and Cooling with Mini Splits in the Northeast

2014 EEBA Mini Splits in Northeast49

© buildingscience.com

Summer Dehumidification MSHPs modulate → size matched to house load,

less oversizing causing humidity problems # hours over 60% RH inside measured Summer hours over 60% RH 10-20%; 15-25%; 2-10% for various houses

MSHPs not a panacea for controlling RH BUT: Data not compared with 1 or 2 speed ducted systems No complaints No sign if used MSHP “dry mode” Northeast window opening/night cooling operation

(would increase interior moisture levels)

2014 EEBA Mini Splits in Northeast50

© buildingscience.com

Future Work With Transformations At Easthampton, change to 3:1 indoor: outdoor

MSHPs on 2nd floor More costly equipment (+50%), less efficient Loss of Massachusetts energy incentive ~$5750/house

Small ducted air handler in second floor hallway

2014 EEBA Mini Splits in Northeast51

© buildingscience.com

Conclusions MSHPs as single heating source in Zone 5A Two-point heating works great in many cases, but

problems cases included: Problem geometries (exterior conditions on 5 sides) Single point in two-story houses Extended bedroom door closures Setbacks and on/off cycling (worse energy use too!)

~1100+ sf/head were the problem cases Oversizing MSHPs for heating okay strategy Use of small air handler on second floor—door

closures no longer a concern

2014 EEBA Mini Splits in Northeast52

© buildingscience.com

Questions?Kohta Uenokohta [at] buildingscience [dot] com

EEBA Excellence in Buildings Conference Heating and Cooling with Mini Splits in the Northeast September 24, 2014

Ueno © buildingscience.com 13 of 13